UFGS_07_22_00-Roof_and_Deck_Insulation.docx

DOCX document 47 KB Posted

Attached to
ROOF INSPECTIONS AND MAINTENANCE @ WATERVLIET ARSENAL
Solicitation number
W911PT26QA051
Issued by

About this file

This file is a Unified Facilities Guide Specification (UFGS) for Section 07 22 00 Roof and Deck Insulation, serving as a technical standard template for roof and deck insulation materials and installation procedures in federal construction projects.

The specification establishes comprehensive requirements for roof insulation products, including expanded perlite board, cellular glass boards, polystyrene board, and mineral fiber insulation board, with minimum recycled content percentages ranging from 9 to 100 percent depending on material type. Installation requirements mandate two-layer applications with staggered joints when total thickness exceeds one-half inch, with specific precautions for foam insulation types requiring protective overlayment boards. Fastener specifications vary by deck type—including barbed nails for wood decks, annular ring shank nails for plywood, hardened penetrating fasteners for steel decks, and screws for concrete decks—all conforming to FM approval standards. Fire performance requirements specify a flame spread rating of 75 or less per ASTM E84, with thermal barrier requirements using glass mat gypsum roof board over steel decks. Cover board options include glass mat gypsum roof board meeting ASTM C1177 standards or high density wood fiber board per ASTM C208. The specification requires indoor air quality certification through UL 2818 Greenguard Gold, SCS Global Services Indoor Advantage Gold, or equivalent third-party programs. Critical execution requirements include surface inspection and preparation prior to installation, environmental condition controls prohibiting installation below 40 degrees Fahrenheit with interior humidity exceeding 45 percent, daily covering of completed insulation work with finished roofing, and comprehensive quality control procedures performed by an experienced roof insulation technician on-site during all operations.

View the file

Other files

File Type Posted
Bid_Items.pdf PDF
RFI RESPONSES.docx DOCX document
Buildings_REV1.pdf PDF
25PW018_SOW.pdf PDF
UFGS_07_32_14-Clay_Tile_Roofing_Replacement_or_Repair.docx DOCX document
07_WVA_01-1-Metal_Roofing.docx DOCX document
07_WVA_01-3-Membrane_Roofing_(EPDM).docx DOCX document
07_WVA_01-2-Membrane_Roofing_(TPO).docx DOCX document
Buildings.pdf PDF
Other_Roof_Warranties.pdf PDF
UFGS_07_51_13-Built-Up_Asphalt_Roofing.docx DOCX document
Solicitation - W911PT26QA051 Professional Appearance.pdf PDF
Flat_Roof_Warranties.pdf PDF
UFGS_07_60_00-Flashing_and_Sheet_Metal.docx DOCX document
WVA_SITEPLAN_Flat_Roofs.pdf PDF
UFGS_07_31_13-Asphalt_Shingles.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION TABLE OF CONTENTS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION SECTION 07 22 00

ROOF AND DECK INSULATION

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 SHOP DRAWINGS

1.4 PRODUCT DATA

1.5 MANUFACTURER'S INSTRUCTIONS

1.6 QUALITY CONTROL

1.7 FIRE PERFORMANCE REQUIREMENTS

1.7.1 Insulation in Roof Systems

1.7.2 Thermal Barrier Requirements

1.7.3 Fire Resistance Ratings for Roofs

1.8 CERTIFICATIONS

1.9 DELIVERY, STORAGE, AND HANDLING

1.9.1 Delivery

1.9.2 Storage and Handling

1.10 ENVIRONMENTAL CONDITIONS

1.11 PROTECTION

1.11.1 Completed Work PART 2 PRODUCTS

2.1 INSULATION

2.1.1 Insulation Types

2.1.2 Mineral Fiber Insulation Board

2.1.3 Recycled Materials

2.1.4 Indoor Air Quality

2.1.5 Insulation Thickness

2.1.6 Tapered Roof Insulation

SECTION 07 22 00

Page

2.2 COVER BOARD

2.2.1 Glass Mat Gypsum Roof Board

2.2.2 High Density Wood Fiber

2.3 FASTENERS

2.3.1 Roofing Nails for Wood Decks

2.3.2 Fasteners for Plywood Decks

2.3.3 Fasteners for Steel Decks

2.3.4 Fasteners for Poured Concrete Decks

2.4 WOOD NAILERS PART 3 EXECUTION

3.1 EXAMINATION AND PREPARATION

3.1.1 Surface Inspection

3.1.2 Surface Preparation

3.2 INSULATION INSTALLATION

3.2.1 Special Precautions for Installation of Foam Insulation

3.2.1.1 Polyisocyanurate Insulation

3.2.1.2 Polystyrene Insulation

3.2.2 Tapered Edge Strips

3.3 PROTECTION

3.3.1 Protection of Applied Insulation

3.3.2 Damaged Work and Materials

3.4 INSPECTION

-- End of Section Table of Contents --

SECTION 07 22 00 ROOF AND DECK INSULATION

03/26

PART 1 GENERAL

1.1. REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C1177/C1177M (2017) Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing

ASTM C1289 (2018a) Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board

ASTM C208 (2012; R 2017; E 2017) Standard Specification for Cellulosic Fiber Insulating Board

ASTM C552 (2017; E 2018) Standard Specification for Cellular Glass Thermal Insulation

ASTM C578 (2018) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation

ASTM C728 (2017a) Standard Specification for Perlite Thermal Insulation Board

ASTM D2178/D2178M (2015a) Asphalt Glass Felt Used in Roofing and Waterproofing

ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing

ASTM D312 (2000; R 2006) Standard Specification for Asphalt Used in Roofing

ASTM D41/D41M (2011; R 2016) Standard Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing

ASTM D4263 (1983; R 2012) Indicating Moisture in Concrete by the Plastic Sheet Method

ASTM D4586/D4586M (2007; E 2012; R 2012) Asphalt Roof

Cement, Asbestos-Free

ASTM D4601/D4601M (2004; R 2012) Asphalt-Coated Glass Fiber Base Sheet Used in Roofing

ASTM D4897/D4897M (2016) Standard Specification for Asphalt-Coated Glass-Fiber Venting Base Sheet Used in Roofing

ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials

FM GLOBAL (FM)

FM 4450 (1989) Approval Standard for Class 1 Insulated Steel Deck Roofs

FM 4470 (2010) Single-Ply, Polymer-Modified Bitumen Sheet, Built-up Roof (BUR), and Liquid Applied Roof Assemblies for Use in Class 1 and Noncombustible Roof Deck Construction

FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/

INTERNATIONAL CODE COUNCIL (ICC)

ICC IBC(2018) International Building Code NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1(2018) Fire Code

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCSSCS Global Services (SCS) Indoor Advantage UNDERWRITERS LABORATORIES (UL)
UL 1256(2002; Reprint Jul 2013) Fire Test of Roof Deck Constructions

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

1.2. SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The “AE” designation identifies the office as that of the Architect or Engineer. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings Insulation Board Layout and Attachment; G, AE Verification of Existing Conditions; G, AE

SD-03 Product Data Insulation; G, AE Cover Board; G, AE Fasteners; G, AE Sheathing Paper; G, AE Moisture Control; G, AE

SD-07 Certificates Installer Qualifications; G, AE Certificates Of Compliance For Felt Materials; G, AE

SD-08 Manufacturer's Instructions Nails and Fasteners; G, AE Roof Insulation; G, AE

1.3. SHOP DRAWINGS

Submit insulation board layout and attachment indicating methods of attachment and spacing, transitions, tapered components, thicknesses of materials, and closure and termination conditions. Show locations of ridges, valleys, crickets, interface with, and slope to, roof drains. Base shop drawings on verified field measurements and include verification of existing conditions.

1.4. PRODUCT DATA

Include data for material descriptions, recommendations for product shelf life, requirements for cover board or coatings, and precautions for flammability and toxicity. Include data to verify compatibility of sealants with insulation.

1.5. MANUFACTURER'S INSTRUCTIONS

Include field of roof and perimeter attachment requirements.

Provide a complete description of installation sequencing for each phase of the roofing system. Include weatherproofing procedures.

1.6. QUALITY CONTROL

Provide certification of installer qualifications from the insulation manufacturer confirming the specific installer has the required qualifications for installing the specific roof insulation system(s) indicated. Provide certificates of compliance for felt materials.

1.7. FIRE PERFORMANCE REQUIREMENTS

1.7.1 Insulation in Roof Systems

Comply with the requirements of ICC IBC. Roof insulation to have a flame spread rating of 75 or less when tested in accordance with ASTM E84. Additional documentation of compliance with flame spread rating is not required when insulation of the type used for this project as part of the specific roof assembly is listed and labeled as FM Class 1 approved.

1.7.2 Thermal Barrier Requirements

Separate insulation from a steel deck with a thermal barrier of glass mat gypsum roof board or other approved barrier material in accordance with the requirements of the ICC IBC.

1.7.3 Fire Resistance Ratings for Roofs

Provide in accordance with ICC IBC Chapter 7 and Table 721.1(3) Min Protection For Floor and Roof Systems.

1.8. CERTIFICATIONS

Provide products certified to meet indoor air quality requirements by UL 2818(Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification by other third-party programs. Provide current product certification documentation from certification body.

1.9. DELIVERY, STORAGE, AND HANDLING

1.9.1. Delivery

Deliver materials to the project site in manufacturer's unopened and undamaged standard commercial containers bearing the following legible information:

1. Name of manufacturer

2. Brand designation

3. Specification number, type, and class, as applicable, where materials are covered by a referenced specification

Deliver materials in sufficient quantity to allow continuity of the work.

1.9.2. Storage and Handling

Store and handle materials in accordance with manufacturer's printed instructions. Protect from damage, exposure to open flame or other ignition sources, wetting, condensation, and moisture absorption. Keep materials wrapped and separated from off-gassing materials (such as drying paints and adhesives). Do not use materials that have visible moisture or biological growth. Store in an enclosed building or trailer that provides a dry, adequately ventilated environment. Store felt rolls on ends. For the 24 hours immediately before application of felts, store felts in an area maintained at a temperature no lower than 10 degrees C 50 degrees F above grade and having ventilation on all sides. Replace damaged material with new material.

1.10. ENVIRONMENTAL CONDITIONS

Do not install roof insulation during inclement weather or when air temperature is below 4 degrees C 40 degrees F and interior humidity is 45 percent or greater, or when there is visible ice, frost, or moisture on the roof deck.

1.11. PROTECTION

1.11.1 Completed Work

Cover completed work with cover board for the duration of construction. Avoid traffic on completed work particularly when ambient temperature is above 27 degrees C 80 degrees F. Replace crushed or damaged insulation prior to roof surface installation.

PART 2 PRODUCTS

2.1 INSULATION

2.1.1 Insulation Types

Provide one, or an assembly of a maximum of three, of the following roof insulation materials. Provide roof insulation that is compatible with attachment methods for the specified insulation and roof membrane.

a. Expanded Perlite Board: Provide in accordance with ASTM C728. Minimum 19 mm 3/4 inch thick when both top and bottom surfaces must be in contact with asphalt.

b. Cellular Glass Boards: ASTM C552, Type IV.

e. Polystyrene Board: In accordance with ASTM C578 REV A, Type II, IV, or X.

2.1.2 Mineral Fiber Insulation Board Provide in accordance with ASTM C726.

2.1.3 Recycled Materials

Provide thermal insulation materials containing recycled content. Unless specified otherwise, the minimum required recycled content for listed materials are:

Perlite Composition Board:
75 percent postconsumer paper
Polyisocyanurate/polyurethane:
9 percent recovered material
Wood Fiberboard:
100 percent recovered material
Cellular Glass Insulation:
75 percent recovered content
Structural Fiberboard:
100 percent recovered content
Fiberglass Insulation:
25 percent recovered content
Fiber (felt) or Fiber composite:
75 percent recovered content
Rubber:
90 percent recovered content
Plastic or Plastic/Rubber composite:
90 percent recovered content
Wood/Plastic Composite:
90 percent total recovered content

Provide data identifying percentage of recycled content for insulation.

2.1.4 Indoor Air Quality

Provide certification of indoor air quality for insulation.

2.1.5 Insulation Thickness

As necessary to provide the thermal resistance (R-value) indicated for average thickness of tapered system. Base calculation on the R-value for aged insulation. For insulation over steel decks, satisfy both specified R-value and minimum thickness for width of rib opening recommended in insulation manufacturer's published literature.

2.1.6 Tapered Roof Insulation

One layer of the tapered roof insulation assembly must be factory tapered to a slope of not less than one in 48 per 1 M, 1/4 inch per foot. Factory fabricate mitered joints from two diagonally cut boards or one board shaped to provide required slopes.

2.2 COVER BOARD

For use as a thermal barrier (underlayment), fire barrier (overlayment), or cover board for hot-mopped, torched-down, or adhesive-applied roofing membrane over roof insulation.

2.2.1 Glass Mat Gypsum Roof Board

ASTM C1177/C1177M, 0 Flame Spread and 0 Smoke Developed when tested in accordance with ASTM E84, 3450 kPa 500 psi, Class A, non-combustible, 6 mm 1/4 inch thick, 1220 by 2440 mm 4 by 8 feet board size.

2.2.2 High Density Wood Fiber

Provide high density fiber board, Grade 2 in accordance with ASTM C208 with a transverse load of 53.4 N 12 lbf.

1.

2.

2.1.

2.2.

2.3 FASTENERS

Provide flush-driven fasteners through flat round or hexagonal steel or plastic plates.Provide zinc-coated steel plates, flat round not less than
35 mm 1 3/8 inch diameter, hexagonal not less than 0.4 mm 28 gage.Provide high-density plastic plates, molded thermoplastic with smooth top surface, reinforcing ribs and not less than 75 mm 3 inches in diameter.Fully recess fastener head into plastic plate after it is driven.Form plates to prevent dishing.Do not use bell or cup shaped plates.Provide fasteners in accordance with insulation manufacturer's recommendations for holding power when driven. Provide fasteners for steel or concrete decks in accordance with FM APP GUIDE (http://www.approvalguide.com/) for Class I roof deck construction, and spaced to withstand the appropriate uplift pressure.

2.3.1 Roofing Nails for Wood Decks

Barbed 3 mm 11 gage, zinc-coated nails with 11 to 16 mm, 7/16 to 5/8 inch, diameter heads or annular ring shank, square head, one piece composite nails. Provide nails long enough to penetrate wood deck at least 16 mm, 5/8 inch without protruding through underside of decking.

2.3.2 Fasteners for Plywood Decks

Annular ring shank, square head, one piece composite nails long enough to penetrate into plywood decks approximately 13 mm 1/2 inch without protruding through underside of decking.

2.3.3 Fasteners for Steel Decks

Approved hardened penetrating fasteners or screws in accordance with FM 4450 and listed in FM APP GUIDE for Class I roof deck construction. Quantity and placement to withstand the appropriate minimum uplift pressure of in accordance with FM APP GUIDE.

2.3.4 Fasteners for Poured Concrete Decks

Approved hardened fasteners or screws to penetrate deck at least 25 mm 1 inch but not more than 38 mm, 1 1/2 inches, in accordance with FM 4470, and listed in FM APP GUIDE for Class I roof deck construction. Quantity and placement to withstand the appropriate uplift pressure in accordance with FM APP GUIDE.

2.4 WOOD NAILERS

Pressure-preservative treated as specified in Section 06 10 00 ROUGH CARPENTRY.

PART 3 EXECUTION

3.1 EXAMINATION AND PREPARATION

3.1.1 Surface Inspection

Ensure surfaces are clean, smooth, and dry prior to application. Check roof deck surfaces, including surfaces sloped to roof drains and outlets, for defects before starting work.

The Contractor must inspect and approve the surfaces immediately before starting installation. Prior to installing insulation, perform the following:

a. Examine wood decks to ascertain that deck boards have been properly nailed and that exposed nail heads have been set.

b. Examine steel decks to ensure that panels are properly secured to structural members and to each other and that surfaces of top flanges are flat or slightly convex.

c. Examine precast concrete decks to ensure that joints between precast units are properly grouted and leveled to provide suitable surfaces for installation of insulation.

e. Prior to installing any roof system on a concrete deck, moisture test the deck in accordance with ASTM D4263. The deck is acceptable for roof system application when there is no visible moisture on underside of plastic sheet after 24 hours.

3.1.2 Surface Preparation

Correct defects and inaccuracies in roof deck surface to eliminate poor drainage from hollow or low spots, perform the following:

a. Provide wood nailers of the same thickness as the insulation at eaves, edges, curbs, walls, and roof openings for securing of cant strips, gravel stops, and flashing flanges.

b. Fill or cover cracks or knot holes larger than 13 mm 1/2 inch in diameter in wood decks as necessary to form an unyielding surface.

3.1

3.2 INSULATION INSTALLATION

Apply insulation in two layers with staggered joints when total required thickness of insulation exceeds 13 mm, 1/2 inch. Lay insulation so that continuous longitudinal joints are perpendicular to direction of roofing and end joints of each course are staggered with those of adjoining courses. When using multiple layers of insulation, provide joints of each succeeding layer that are parallel and offset in both directions with respect to the layer below. Keep insulation 13 mm, 1/2 inch, clear of vertical surfaces penetrating and projecting from roof surface. Verify required slopes to each roof drain.

3.2.1 Special Precautions for Installation of Foam Insulation

3.2.1.1 Polyisocyanurate Insulation

Where polyisocyanurate foam board insulation is provided, install 13 mm, 1/2 inch, thick wood fiberboard, glass mat gypsum roof board, or 19 mm, 3/4 inch, thick expanded perlite board insulation over top surface of foam board insulation. Stagger joints of insulation with respect to foam board insulation below.

3.2.1.2 Polystyrene Insulation

a. Over the top surface of non-composite polystyrene board, install 13 mm, 1/2 inch, thick high density wood fiberboard, 19 mm, 3/4 inch, thick expanded perlite board, glass mat gypsum roof board, or other overlayment approved by roofing sheet manufacturer. Tightly butt and stagger joints of field applied overlayment board at least 150 mm 6 inches with respect to the polystyrene board below. Apply 150 mm 6 inch wide glass fiber roofing tape centered over joints and edges of overlayment board.

b. Where composite boards consisting of polystyrene insulation are provided, apply 150 mm 6 inch wide glass fiber roofing tape centered over joints and edges of composite board. Apply joint strips as recommended by roofing sheet manufacturer.

3.2.2 Tapered Edge Strips

Where indicated, provide edge strips in the right angle formed by the juncture of roof and wood nailing strips that extend above the level of the roof. Install edge strips flush to vertical surfaces of wood nailing strips. Where possible, nail edge strips to adjoining surfaces. Where installed against non-nailable materials, install in an approved adhesive.

3.3 PROTECTION

3.3.1 Protection of Applied Insulation

Completely cover each day's installation of insulation with finished roofing specified on same day. Phased construction is not permitted. Protect open spaces between insulation and parapets or other walls and spaces at curbs, scuttles, and expansion joints, until permanent roofing and flashing are applied. Storing, walking, wheeling, or trucking directly on insulation or on roofed surfaces is not permitted. Provide smooth, clean board or plank walkways, runways, and platforms near supports, as necessary, to distribute weight in accordance with indicated live load limits of roof construction. Protect exposed edges of insulation with cutoffs at the end of each work day or whenever precipitation is imminent. Cutoffs must be two layers of bituminous-saturated felt set in plastic bituminous cement or EPDM membrane set in roof cement. Fill all profile voids in cutoffs to prevent trapping moisture below the membrane. Remove cutoffs when work resumes.

3.3.2 Damaged Work and Materials

Restore work and materials that become damaged during construction to original condition or replace with new materials.

3.4 INSPECTION

Establish and maintain inspection procedures to assure compliance of the installed roof insulation with contract requirements. Remove, replace, correct in an approved manner, any work found not in compliance. Quality control must include, but is not limited to, the following:

a. Observation of environmental conditions; number and skill level of insulation workers; start and end time of work.

b. Verification of certification, listing or label compliance with FM Data Sheets. (https://www.fmglobal.com/fmglobalregistration/Downloads.aspx)

c. Verification of proper storage and handling of insulation and vapor retarder materials before, during, and after installation.

d. Inspection of vapor retarder application, including edge envelopes and mechanical fastening.

e. Inspection of mechanical fasteners; type, number, length, and spacing.

f. Coordination with other materials, cants, sleepers, and nailing strips.

g. Inspection of insulation joint orientation and laps between layers, joint width and bearing of edges of insulation on deck.

h. Installation of cutoffs and proper joining of work on subsequent days.

i. Continuation of complete roofing system installation to cover insulation installed same day.

j. Verification of required slope to each roof drain.

k. A roof insulation technician, responsible directly to the Contractor and experienced in the installation of roof insulation and related work, must perform the inspection functions and be on the site whenever roof insulation operations are in progress.

-- End of Section --