TP09 Final Drawings 05 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Architectural.pdf
PDF 5 MB Posted
- Attached to
- Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES Federal contract opportunity
- Solicitation number
- 36C25521R0103
About this file
This federal contract opportunity notice is for infrastructure upgrades at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The project includes construction of a new fiber backbone and server room to support migration to a new Veterans Health Administration electronic health records system. Renovations to O&IT closets will include room modifications, HVAC upgrades, patch panel and cabling upgrades to CAT6A, and additional power and data drops for end user equipment. The period of performance is estimated at 365 calendar days after notice to proceed. The principal NAICS code is 236220 for commercial and institutional building construction. The solicitation number is 36C25521R0103.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
OI&T
OI&T
ELECTRICAL CLOSET
01D
EXIST. CONC RAM
P DOW
N
E X
IS
T
IN
G
C O
N C
R E
T E
T O
R E
M A
IN
EXIST. CONC RAMP DN TO REMAIN
TYP OF 10
TYP OF 10
E X
IS
T
IN
G
C O
N C
R E
T E
T O
B E
R E
M O
V E
D
61'-6" 9'-3 3/4"
'-0
3' -7
20'-0"
5' -0
'-0
21'-10 1/4" 42'-4" 1'-3 3/4"
21'-3 5/8" 8'-0" 13'-0"
4' -0
50'-4"
'-3
2.09
2.08
2.09
2.10
2.11
2.12
2.132.13
2.142.14
2.132.13
2.08
2.06
2.15
2.05
2.07
2.102.102.10
2.06
2.08
A
2.05
2.08
REFER CIVIL FOR TOTALITY
OF SITE DEMOLITION
2.212.21
1-AE-402 5
2.15
2.15
2.22
2.23
2.24
EXISTING WALL CONSTRUCTION TO
BE DEMOLISHED IN ITS ENTIRETY
EXISTING DOOR AND FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
EXISTING WINDOW AND FRAME TO BE
DEMOLISHED IN THEIR ENTIRETY
EXISTING WALLS TO REMAIN
AREA OF NO WORK
AREA OF DEMOLITION / RENOVATION
DEMOLITION PLAN LEGEND
1. DRAWINGS TO BE TAKEN AS PART OF A COMPLETE DOCUMENT SET.
CONTRACTOR TO CONFIRM ALL ITEMS REQUIRED TO BE DEMOLISHED AND
EXTENT OF DEMOLITION BASED UPON THE OVERALL INTENT OF THE ENTIRE
DOCUMENT SET.
2. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES. COORDINATE
WORK SCHEDULE WITH THE CONTRACTING OFFICERS REPRESENTATIVE.
3. COORDINATE WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS PRIOR TO BEGINNING WORK TO CONFIRM ACCURACY IN THE
DRAWINGS. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER
REPRESENTATIVE.
4. THE DEMOLITION DRAWINGS ARE DEEMED SCHEMATIC. CONTRACTOR
RESPONSIBLE FOR FIELD VERIFYING EXISTING DEMOLITION WORK PRIOR TO
SUBMISSION PROPOSAL.
5. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT
SHALL BE KEPT CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES. ERECT
BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF
THE CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO
SEPARATE WORK AREAS FROM THE EXISTING FACILITIES. VA TO APPROVE
BARRIER LOCATIONS; BARRIERS TO BE CONSTRUCTED PER VA STANDARDS.
6. DURING DEMOLITION, PROVIDE PROTECTION FOR ALL EXISTING SURFACES
AND CONDITIONS TO REMAIN IN PLACE DURING THE RENOVATION WORK.
SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR TO MATCH EXISTING
ADJACENT FINISHES. SUBSTANTIAL DAMAGES TO BE REPORTED TO THE VA
PROJECT MANAGER.
7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE
REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO
ADDITIONAL COST TO THE OWNER.
8. ALL FINISHES INDICATED TO BE DEMOLISHED SHALL BE REMOVED IN THEIR
ENTIRETY INCLUDING RELATED COMPONENTS.
9. PROTECT ADJACENT SURFACES; FOR EXAMPLE BUT NOT LIMITED TO, SILLS,
JAMBS AND HEAD FRAMES AT WINDOWS AND DOORS.
10. REMOVAL OF MECHANICAL, ELECTRICAL, AND PLUMBING SHOULD BE
LIMITED TO WHAT IS NECESSARY FOR SAFE REMOVAL OF THE INDICATED WALL
OR CEILING. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY
SUSPENDED TO PROVIDE ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.
11. CONTRACTOR TO DEMO ALL FIXTURES, CEILINGS, MECHANICAL, PLUMBING,
AND ELECTRICAL AS REQUIRED TO COMPLETE THE SCOPE OF WORK OUTLINED
WITHIN THE CONSTRUCTION DOCUMENTS.
12. REFERENCE TELECOM DOCUMENTS FOR ADDITIONAL DEMOLITION
INFORMATION ON TELECOMMUNICATION EQUIPMENT AND WORK. ON ALL DEMO
SHEETS.
13. REFERENCE ELECTRICAL DOCUMENTS FOR ADDITIONAL DEMOLITION
INFORMATION ON ELECTRICAL EQUIPMENT AND WORK. ON ALL DEMO SHEETS.
14. REFERENCE MECHANICAL DOCUMENTS FOR ADDITIONAL DEMOLITION
INFORMATION ON ELECTRICAL EQUIPMENT AND WORK. ON ALL DEMO SHEETS.
15. REFERENCE FIRE PROTECTION DOCUMENTS FOR ADDITIONAL DEMOLITION
INFORMATION ON FIRE ALARM AND SPRINKLER EQUIPMENT AND WORK. ON ALL
DEMO SHEETS.
16. REFERENCE HAZARDOUS MATERIALS DOCUMENTS FOR ADDITIONAL
DEMOLITION INFORMATION ON WORK ON ALL DEMO SHEETS.
17. GENERAL CONSTRUCTION CONTRACTOR TO COORDINATE ABATEMENT
WORK WITH COR TO ALLOW FOR MAXIMUM OI&T DEMOLITION.
GENERAL DEMOLITION FLOOR PLAN NOTES
BUILDING KEY PLAN
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :0
P
M
1-AD-011
BLDG 1 DEMOLITION PLAN
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
BLDG 1- DEMOLITION PLAN1
N
KEYNOTE LEGEND
2.05 REMOVE EXISTING METAL ROOFING PANELS DOWNSPOUTS, GUTTERS, TRIM, AND ALL
RELATED COMPONENTS. RETURN TO VA FOR STORAGE AND RE-USE
2.06 REMOVE EXISTING STEEL FRAMING SYSTEM, COLUMNS, AND ALL RELATED
COMPONENTS. RETURN TO VA FOR STORAGE AND RE-USE
2.07 DEMOLISH AND COMPLETELY REMOVE EXISTING CONCRETE PIERS
2.08 DEMOLISH PORTION OF CONCRETE PAD
2.09 DEMOLISH EXISTING HVAC EQUIPMENT IN ITS ENTIRETY, REF MECAHNICAL
2.10 REMOVE EXISTING ALUMINUM FRAME WINDOW AND ALL COMPONENTS IN ITS ENTIRETY.
SEAL OPENING TO PREVENT AIR AND MOISTURE INFILTRATION DURING CONSTRUCTION.
2.11 DEMOLISH PORTION OF CONCRETE WALL AND BRICK VENEER. REFER STRUCTURAL
DRAWINGS FOR DEMOLITION REQUIREMENTS. PREPARE ALL SURFACES TO RECEIVE
NEW FINISHES. SEAL OPENING TO PREVENT AIR AND MOISTURE INFILTRATION DURING
CONSTRUCTION.
2.12 DEMOLISH GYPSUM BOARD FURRING AND METAL STUD FRAMING FLOOR TO DECK IN ITS
ENTIRETY
2.13 DEMOLISH RAISED FLOORING, FRAMING, AND ASSOCIATED COMPONENTS
2.14 DEMOLISH ACCOUSTIC TILE CEILING SYSTEM AND ALL RELATED COMPONENTS IN ITS
ENTIRETY
2.15 DEMOLISH METAL CANOPY, FRAMING, AND ASSOICATED COMPONENTS IN ITS ENTIRETY
2.21 RE-INSTALL PREVIOUSLY STORED ACCOUSTICAL CEILING TILE AND METAL GRID. REPAIR
OR REPLACE ANY DAMAGED AREA CAUSED DURING INSTALLATION OF MECHANICAL
DUCTWORK
2.22 REMOVE EXISTING HANDRAILS
2.23 DEMOLISH EXISTING CONCRETE RAMP
2.24 DEMOLISH EXISTING CONCRETE LANDING
1. NOT ALL PARTITION TYPES SHOWN HERE MAY BE USED. REFER TO PLANS FOR
LOCATION AND TYPES OF EACH PARTITION.
2. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES
OF ALL FIRE AND SMOKE WALLS DESIGNATING THE PARTITION RATING INDICATED ON
THE LIFE SAFETY PLAN.
3. REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF ALL
WALL TILE. PROVIDE AND INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GYP. BD.
AT ALL SCHEDULED TILE LOCATIONS. UNLESS NOTED OTHERWISE, TILE SHALL BE
INSTALLED PER TILE COUNCIL OF AMERICA LATEST STANDARDS FOR EACH TYPE OF
BACKING MATERIAL REPRESENTED IN WALL/PARTITION.
4. ALL SUSPENDED WALLS AND PARTITIONS SHALL HAVE GYP. BD. WHICH EXTENDS A
MINIMUM OF 6" ABOVE THE SUSPENDED CEILING UNLESS SHOWN AND/OR NOTED
OTHERWISE BY THE ARCHITECT.
5. REFER TO STRUCTURAL DRAWINGS FOR ALL LOAD BEARING WALL CONDITIONS IN
REGARDS TO STRUCTURAL REQUIREMENTS.
6. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, E.G. WALLS, JAMBS, ETC.
SHALL ALIGN ACROSS VOIDS AND JOINTS.
7. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS
NOTED OTHERWISE) WHERE GYP. BD. CONTINUES ABOVE CEILING AND ABOVE THE
CEILING LEVEL UP TO THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL
HAVE CORNER BEADS MINIMUM FLOOR TO CEILING. ALL PENETRATIONS IN GYP. BD.
CONSTRUCTION ABOVE FINISHED CEILING SHALL BE EFFECTIVELY SEALED TO
PREVENT SOUND LEAKAGE AND FIRE STOPPING TAPE/CAULK AT ALL RATED
PARTITIONS.
8. ALL MECHANICAL CHASES AND OTHER NOTED CHASES ARE TO EXTEND UP TO THE
UNDERSIDE OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS NOTED
OTHERWISE, SHALL EXTEND ABOVE THE HIGHEST ADJOINING CEILING AND BE BRACED
TO STRUCTURE.
9. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL
BE SUPPORTED BY TOP CHORD OF STRUCTURAL JOISTS AND NOT FROM THE METAL
DECK.
10. COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF BLOCKING IN
WALLS/PARTITIONS. ALL WOOD BLOCKING IS TO BE FIRE RETARDANT TREATED.
11. IMPACT RESISTANT GYP. BD., WHERE NOTED, IS OPTIONAL ABOVE 8' AFF AND
BEHIND LOCKERS.
12. SEAL THE TOP AND BOTTOM OF WALL AS WELL AS ALL PENETRATIONS WHERE
SMOKE PARTITIONS ARE DESIGNATED ON THE LIFE SAFETY PLAN TO ELIMINATE THE
PASSAGE OF SMOKE.
13. USE DEFLECTION TRACKS WHERE STUD WALLS ATTACH DIRECTLY TO METAL DECK
GENERAL PARTITION NOTES
BASE
PLAN
HEAD
WALL FINISH (REF: ROOM FINISH SCHEDULE)
FIN FLOOR- (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
CONTINUOUS SEALANT BEAD
WIDTH
STUD
5/8"
WIDTH
ACTUAL
DIM
C 4
FRAMING UNIT SIZE CATEGORY
BASIC PARTITION ASSEMBLY CATEGORY
PARTITION TAG:
METAL STUD PER SCHEDULE
UNDERSIDE OF STRUCTURE
CONTINUOUS SEALANT BEAD
DEFLECTION TRACK AT WALLS TO DECK
5/8 GYPSUM BOARD
U-TRACK- (FASTENED 24" O.C. MAX)
INTERIOR
EXTERIOR
14 GA HOLLOW METAL FRAME
14 GA INSULATED
STEEL DOOR
BACKER ROD & SEALANT, TYP.
EACH SIDE
5/8" HIGH IMPACT GYP. BOARD
TO 4'-0" A.F.F., EXTEND 4'-0"
BEYOND OPENING (MIN), OR TO
INSIDE CORNER. 5/8" TYPE 'X'
GYP BOARD ABOVE TO DECK
ON METAL STUD FRAMING
BRICK VENEER TO
MATCH EXISTING
INSULATION
BOARD
8" NOM. GROUT
FILLED CMU, REF:
STRUCTURAL
BATT INSULATION
2" x 2" x 6'-0" BRUSHED
STAINLESS STEEL HEAVY
DUTY CORNER GUARD,
SCREW-IN TYPE.
BRICK VENEER TO
MATCH EXISTING
BLAST DOOR MFR TO COORD.
POST-INSTALLED ANCHORAGE
TO STRUCTURE AS REQ'D
EXTERIOR INTERIOR
14 GA HOLLOW METAL BLAST
RESISTANT FRAME
FLUSH-BOLT
14 GA INSULATED STEEL
DOOR
FLUSH-BOLT
BACKER ROD & SEALANT,
TYP. EACH SIDE
STEEL LINTEL, PAINT FINISH
SCHEDULED BASE
2" x 2" x 6'-0" BRUSHED
STAINLESS STEEL HEAVY
DUTY CORNER GUARD,
SCREW-IN TYPE.
FINISH FLOOR
PRE-FINISHED METAL
FLASHING
BRICK VENEER TO MATCH
EXISTING
INSULATION BOARD
METAL STUD BOX BEAM
HEADER
CMU BOND BEAM, REF:
STRUCTURAL
A
WIDTH
SCHEDULE
H E
IG
H
T
S C
H E
D U
LE
(PAIR) HOLLOW METAL DOOR
BASIS OF DESIGN FOR HOLLOW
METAL DOORS AND FRAME:
• VA PHYSICAL SECURITY &
RESILIENCY DESIGN MANUAL,
SATCHEL THREAT W1
2"2"
WIDTH
SCHEDULE
2"
H E
IG
H
T
S C
H E
D U
LE
DOOR TYPESFRAME TYPES
F1
HOLLOW METAL DOOR FRAME
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :1
P
M
1-AE-021
PARTITION TYPES, DOOR & ROOM
FINISH SCHEDULE
ECO
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
TYPE MARK WALL TYPE DESCRIPTION ACTUAL WIDTH
A3 NON-INSULATED
5/8" GYPSUM BOARD ON ONE SIDE
OF 3 5/8" METAL STUD
4 1/4"
A4 NON-INSULATED
5/8" GYPSUM BOARD ON ONE SIDE
OF 7/8" HAT CHANNEL
1 1/2"
ROOM FINISH SCHEDULE
ROOM # ROOM NAME
FLOOR FINISHES WALL FINISHES
CEILING
MATERIAL BASE NORTH EAST SOUTH WEST
1A CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
2A CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
3A CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
4A CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
5A CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
52 OI&T
EXISTING RAISED FLOORING &
NEW RAISED FLOORING STAIR /
NEW RAISED FLOORING STAIR &
STATIC DISSIPATIVE FLOORING
RUBBER BASE PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT
OPEN TO DECK
52B OI&T SERVER ROOM STATIC DISSIPATIVE FLOORING RUBBER BASE PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT PAINT TO MATCH ADJACENT OPEN TO DECK
GA CORRIDOR EXISTING TO REMAIN EXISTING TO REMAIN N/A N/A N/A N/A ACT TO MATCH EXISTING
DOOR SCHEDULE
MARK
DOOR PANEL DOOR FRAME
HARDWARE SET COMMENTSTYPE WIDTH HEIGHT MATERIAL FIRE RATING TYPE DEPTH MATERIAL FIRE RATING
38 4'-0" 7'-0"
49 3'-6" 7'-0"
1066 6'-0" 8'-0" F1 HM 14 GA MIN, STEEL DOORS,
BLAST RESISTANT, LOCK,
REFER SPEC
3" = 1'-0"
DOOR DETAIL - JAMB2 3" = 1'-0"
HEAD/SILL DOOR DETAIL1
A HM 5 5/8"
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
106690 MIN90 MIN
D
Y H
D Y
H
H
IG
H W
AY
W
ES
TW
O
O D
BO
U
LE
V
AR
D
EXISTING PARKING TO REMAIN
A.B.R
EFER TO
C IVIL
AND ELE
CTRICAL DRAWING
S FOR A
DDITION AL SITE
IN
FORMATION.
R
EFER TO
SH EET G
I002 FOR APPLICA
BLE ABBREVIATIO
NS, SYM
B OLS A
ND
GENE
RAL NOTES.
S 89°38' E
1339.9'
S
°3
W
.1
N 89°11' W
763.9'
N
°5
W
.5
N
° 3
E
. 6
N
°5
W
.5
LI
M
IT
O
F W O
RK
LI
M
IT
O
F W
O R
K
LIM
IT O
F W O
R K
LIMIT OF WORK
LIM
IT OF W
ORK
SIGN
ELEC. CONTROL
PANEL
FLOOR
433.48
CONC.
WALK
DY
H
STOP
D/W
PA
RK
ING
D/W
D/W
D/W
CO
NC
CO
NC
P
AR
K
IN
G
P
AR
K
IN
G
P
AR
K
IN
G
P
AR
K
IN
G
P
AR
K
IN
G
P
AR
K
IN
G
PARK
ING
P
AR
K
IN
G
D/W ASPHALT
SURFACE
D/W ASPHALT
SURFACE
D/W ASPHALT
SURFACE
D/W ASPHALT
SURFACE
AS
PH
AL
T
SU
RF
AC
E
H
AS
P H
AL
T
AS
P H
AL
T
AS
P H
AL
T
AS
P H
AL
T
AS
PH
AL
T
SU
RF
AC
E
P A R K
IN
G
D W
AS
P H
ALT
SU
R
FAC
E
P A R K
IN
G
P
AR
K
IN
G
PA
RK
ING
AC.
UNIT
AC.
UNITINSIDE
CONC.
WALL
CURB &GUTTER
C U R B
G U
TT
E R
SPEED
BUMP
GUTTER
M O
TO
R C
YC
LE
P
AR
K
IN
G
SPEED
BUMP
LE
AR
NI
NG
R
ES
OU
RC
E
CE
NT
ER FF
E= 6.0
0'
GR
AS
S
EXISTING BUILDING FOOTPRINT
BUILDING NUMBER INDENTIFER1
N . W
E S
T W
O O
D B
L V
D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :2
P
M
AS-001
ARCHITECTURAL SITE PLAN
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/64" = 1'-0"
ARCHITECTURAL SITE PLAN1
N
1-AE-121
OI&T SERVER ROOM
52B
OI&T
DN
DN
82'-11 1/2"
E
D
C
B
A
2 3
DN
1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY
THAT HAS CERTAIN AREAS THAT MUST REMAIN IN SERVICE 24-HOURS A DAY,
7-DAYS A WEEK.
2. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES. COORDINATE
WORK SCHEDULE WITH THE CONTRACTING OFFICERS REPRESENTATIVE.
3. COORDINATE WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS PRIOR TO BEGINNING WORK TO CONFIRM ACCURACY IN THE
DRAWINGS. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER
REPRESENTATIVE.
4. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND
EXISTING STRUCTURAL CONDITIONS.
5. PROVIDE SMOOTH LEVEL TRANSITIONS FROM NEW FINISH TO EXISTING
FINISH TO REMAIN.
6. FINAL FINISH SELECTION TO BE MADE BY THE VA. PROVIDE ALL MATERIAL TO
VA FOR REVIEW AND APPROVAL THROUGH COLOR BOARD SUBMITTAL FOR
BOTH MATERIAL, TYPE AND COLOR.
7. GENERAL CONTRACTOR TO PROVIDE AND INSTALL ALL NEW FINISHES TO
COMPLETE THE WORK AS NECESSARY.
8. REMOVE AND REPLACE ELECTRICAL / DATA PLATES, BOXES, LIGHTS AND
ACCESSORIES AS NECESSARY. ADJUST ELECTRICAL / DATA COMPONENTS AS
NECESSARY.
9. PROTECT ADJACENT SURFACES; FOR EXAMPLE BUT NOT LIMITED TO, SILLS,
JAMBS AND HEAD FRAMES AT WINDOWS AND DOORS TO NAME A FEW.
10. ALL WALLS ARE DIMENSIONED TO FINISH FACE, UNLESS NOTED
OTHERWISE.
11. REFER TO MECHANICAL DRAWINGS FOR NEW MECHANICAL UNITS IN ROOM.
12. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING LOCATIONS.
13. REFER TO TELECOM DRAWINGS FOR UPDATES TO CABLE JACK LOCATIONS.
14. REFER TO ENVIRONMENTAL DRAWINGS FOR ABATEMENT PROCEDURES OF
HAZARDOUS MATERIAL.
15. EXISTING AND NEW CABLE TRAYS NOT SHOWN FOR CLARITY OF
ARCHITECTURAL SCOPE. REFER TO TELECOM DOCUMENTS FOR INFORMATION
RELATED TO THESE ITEMS.
16. REFERENCE TELECOM DOCUMENTS FOR AREAS WHERE NEW DATA JACK
WALL OUTLETS WILL BE PROVIDED IN ROOMS OUTSIDE OF THE TELECOM
ROOMS. PATCH AND PAINT AREAS AROUND DATA JACK WALL OUTLET AS
NEEDED. COORDINATE PAINT COLOR WITH EXISTING WALL COLOR AND VA COR.
GENERAL FLOOR PLAN NOTES
GENERAL FLOOR PLAN NOTES
AREA OF NO WORK
NEW CONCRETE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :1
P
M
1-AE-100
BLDG 1 GROUND FLOOR
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/16" = 1'-0"
BLDG. 1 - FLOOR PLAN - GROUND FLOOR1
N
1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY
THAT HAS CERTAIN AREAS THAT MUST REMAIN IN SERVICE 24-HOURS A DAY,
7-DAYS A WEEK.
2. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES. COORDINATE
WORK SCHEDULE WITH THE CONTRACTING OFFICERS REPRESENTATIVE.
3. COORDINATE WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS PRIOR TO BEGINNING WORK TO CONFIRM ACCURACY IN THE
DRAWINGS. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER
REPRESENTATIVE.
4. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND
EXISTING STRUCTURAL CONDITIONS.
5. PROVIDE SMOOTH LEVEL TRANSITIONS FROM NEW FINISH TO EXISTING
FINISH TO REMAIN.
6. FINAL FINISH SELECTION TO BE MADE BY THE VA. PROVIDE ALL MATERIAL TO
VA FOR REVIEW AND APPROVAL THROUGH COLOR BOARD SUBMITTAL FOR
BOTH MATERIAL, TYPE AND COLOR.
7. GENERAL CONTRACTOR TO PROVIDE AND INSTALL ALL NEW FINISHES TO
COMPLETE THE WORK AS NECESSARY.
8. REMOVE AND REPLACE ELECTRICAL / DATA PLATES, BOXES, LIGHTS AND
ACCESSORIES AS NECESSARY. ADJUST ELECTRICAL / DATA COMPONENTS AS
NECESSARY.
9. PROTECT ADJACENT SURFACES; FOR EXAMPLE BUT NOT LIMITED TO, SILLS,
JAMBS AND HEAD FRAMES AT WINDOWS AND DOORS TO NAME A FEW.
10. ALL WALLS ARE DIMENSIONED TO FINISH FACE, UNLESS NOTED
OTHERWISE.
11. REFER TO MECHANICAL DRAWINGS FOR NEW MECHANICAL UNITS IN ROOM.
12. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING LOCATIONS.
13. REFER TO TELECOM DRAWINGS FOR UPDATES TO CABLE JACK LOCATIONS.
14. REFER TO ENVIRONMENTAL DRAWINGS FOR ABATEMENT PROCEDURES OF
HAZARDOUS MATERIAL.
15. EXISTING AND NEW CABLE TRAYS NOT SHOWN FOR CLARITY OF
ARCHITECTURAL SCOPE. REFER TO TELECOM DOCUMENTS FOR INFORMATION
RELATED TO THESE ITEMS.
16. REFERENCE TELECOM DOCUMENTS FOR AREAS WHERE NEW DATA JACK
WALL OUTLETS WILL BE PROVIDED IN ROOMS OUTSIDE OF THE TELECOM
ROOMS. PATCH AND PAINT AREAS AROUND DATA JACK WALL OUTLET AS
NEEDED. COORDINATE PAINT COLOR WITH EXISTING WALL COLOR AND VA COR.
GENERAL FLOOR PLAN NOTES
GENERAL FLOOR PLAN NOTES
AREA OF NO WORK
NEW CONCRETE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :3
P
M
1-AE-101
BLDG 1 FLOOR PLANS
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/32" = 1'-0"
BLDG. 1 - FLOOR PLAN - FOURTH FLOOR41/32" = 1'-0"
BLDG. 1 - FLOOR PLAN - FIFTH FLOOR5
NN
1/32" = 1'-0"
BLDG. 1 - FLOOR PLAN - THIRD FLOOR3
N
1/32" = 1'-0"
BLDG. 1 - FLOOR PLAN - SECOND FLOOR2 1/32" = 1'-0"
BLDG. 1 - FLOOR PLAN - FIRST FLOOR1
N N
ELDM DM
RE
CR
OI&T
789 SF
ELECTRICAL CLOSET
01D
NEW CONC. RAMP DOWN 0'-7" (4% SLOPE)
STATIC DISSIPATIVE FLOORING
1-AE-201
1-AE-201
1-AE-201
OI&T SERVER ROOM
52B
1319 SF
EXISTING CONC. RAMP
EXISTING CONCRETE PAD TO REMAIN
E X
IS
T
IN
G
L A
N D
S C
A P
IN
G
T O
R E
M A
IN
N
E W
B U
R M
U D
A S
O D
1/
4"
6 1/4" 23'-0" 11'-8"
-1'-2"
-1'-9"
1'-3 3/4"
7'-7 3/4"
'-7
/8
2' -6
AREA FOR
FUTURE VERTICAL
CIRCULATION
1-AE-301
7.87
1-AE-401
8.948.94
7.87
1-AE-401
5.32
5.31
EXISTING
WINDOW WELL
OIT EQUIPMENT, REFER TELECOM
7.15
32.01
1-AE-301
1-AE-311
A3A3A3
A3 A3A3
A3A3
9.86
9.86
9.86
9.86
DN
DN
DN
UP
0' -0
1' -0
0'-0"
N E
W C
O N
C
R A
M P
D O
W N
'-2
(5
S
LO
P
E
0'-0"
NEW CONC. RAMP DOWN 0'-7" (4% SLOPE)
STATIC DISSIPATIVE FLOORING
EXISTING RAISED FLOORING
TO REMAIN
0' -6
0'-6"
1'-0"
5.37
5.36
5.36
9.87
5.31
5.32
DN
DN
E
D
C
B
A
'-4
8"
23'-0"
2" 8'
-0
'-0
8'
-0
1/
4"
1-AE-402
1-AE-402
0'-0"
-0'-7"
-1'-2"
20'-1"
2" 8'
-0
'-0
8'
-0
1' -1
/2
2'-4"
A4
ALIGN
ALIGN
-1'-2"
-1'-2"
5.04
A4
A4
A4
A4
A4
1' -7
4 7/8"
1' -7
4 7/8"
3' -8
/8
4'
-0
7/
8"
46'-6 1/4"
'-6
/4
5.37
-1'-4"
-2'-4"
6'-4" 5'-0"
1-AE-402 5
3'-0"
4.21
4.21
4.21
4.21
4.21
4.21
4.21 4.21
7.87
OIT EQUIPMENT,
REFER TELECOM
7.15
FEC
1'-6"
EXIST.
FEC EXIST.
FEC
5.365.36
1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH AN OPERATING FACILITY
THAT HAS CERTAIN AREAS THAT MUST REMAIN IN SERVICE 24-HOURS A DAY,
7-DAYS A WEEK.
2. SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES. COORDINATE
WORK SCHEDULE WITH THE CONTRACTING OFFICERS REPRESENTATIVE.
3. COORDINATE WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS PRIOR TO BEGINNING WORK TO CONFIRM ACCURACY IN THE
DRAWINGS. REPORT ANY DISCREPANCIES TO THE CONTRACTING OFFICER
REPRESENTATIVE.
4. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND
EXISTING STRUCTURAL CONDITIONS.
5. PROVIDE SMOOTH LEVEL TRANSITIONS FROM NEW FINISH TO EXISTING
FINISH TO REMAIN.
6. FINAL FINISH SELECTION TO BE MADE BY THE VA. PROVIDE ALL MATERIAL TO
VA FOR REVIEW AND APPROVAL THROUGH COLOR BOARD SUBMITTAL FOR
BOTH MATERIAL, TYPE AND COLOR.
7. GENERAL CONTRACTOR TO PROVIDE AND INSTALL ALL NEW FINISHES TO
COMPLETE THE WORK AS NECESSARY.
8. REMOVE AND REPLACE ELECTRICAL / DATA PLATES, BOXES, LIGHTS AND
ACCESSORIES AS NECESSARY. ADJUST ELECTRICAL / DATA COMPONENTS AS
NECESSARY.
9. PROTECT ADJACENT SURFACES; FOR EXAMPLE BUT NOT LIMITED TO, SILLS,
JAMBS AND HEAD FRAMES AT WINDOWS AND DOORS TO NAME A FEW.
10. ALL WALLS ARE DIMENSIONED TO FINISH FACE, UNLESS NOTED
OTHERWISE.
11. REFER TO MECHANICAL DRAWINGS FOR NEW MECHANICAL UNITS IN ROOM.
12. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING LOCATIONS.
13. REFER TO TELECOM DRAWINGS FOR UPDATES TO CABLE JACK LOCATIONS.
14. REFER TO ENVIRONMENTAL DRAWINGS FOR ABATEMENT PROCEDURES OF
HAZARDOUS MATERIAL.
15. EXISTING AND NEW CABLE TRAYS NOT SHOWN FOR CLARITY OF
ARCHITECTURAL SCOPE. REFER TO TELECOM DOCUMENTS FOR INFORMATION
RELATED TO THESE ITEMS.
16. REFERENCE TELECOM DOCUMENTS FOR AREAS WHERE NEW DATA JACK
WALL OUTLETS WILL BE PROVIDED IN ROOMS OUTSIDE OF THE TELECOM
ROOMS. PATCH AND PAINT AREAS AROUND DATA JACK WALL OUTLET AS
NEEDED. COORDINATE PAINT COLOR WITH EXISTING WALL COLOR AND VA COR.
GENERAL FLOOR PLAN NOTES
GENERAL FLOOR PLAN NOTES
AREA OF NO WORK
NEW CONCRETE
EQUIPMENT PROGRAM AREA
OIT IT ACTIVE EQUIPMENT 320 SQ FT
OIT IT PASSIVE EQUIPMENT 200 SQ FT
FMS ACTIVE 160 SQ FT
FMS PASSIVE 200 SQ FT
DIGITAL/VOIP TELE SYSTEM 360 SQ FT
CONDUIT ENTRY AREAS 20 SQ FT
TOTAL SERVER ROOM AREA 260 SQ FT.
20% EXPANSION 252 SQ FT.
FUTURE VERTICAL CIRC. 100 SQ FT
TOTAL PROGRAM AREA 1,872 SQ FT
DESIGNED AREA
ADDITION + EXISTING 2,162 NET SQ FT
ROOM AREA SCHEDULE
BUILDING KEY PLAN
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :4
P
M
1-AE-121
BLDG 1 ENLARGED PLAN - GROUND
FLOOR
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
BLDG. 1 - ENLARGED PLAN - GROUND FLOOR1
N
KEYNOTE LEGEND
4.21 CONTROL JOINT
5.04 WALL MOUNTED ROOF ACCESS LADDER
5.31 NEW STEEL HANDRAIL PAINT FINISH. COLOR TO BE SELECTED BY VA
5.32 NEW STEEL GUARDRAIL PAINT FINISH. COLOR TO BE SELECTED BY VA
5.36 NEW ALUMINUM HANDRAIL, SATIN FINISH
5.37 NEW ALUMINUM GUARDRAIL, SATIN FINISH
7.15 SHEETMETAL DOWNSPOUT
7.87 SEISMIC JOINT
8.94 7-MIL THICK ANTI-SHATTER FILM, REFER SPECIFICATION SECTION 08 80 00 GLAZING
9.86 5/8" GYPSUM BOARD ON 7/8" HAT CHANNEL
9.87 VERTICAL RAISED FLOORING CLOSURE PANEL
32.01 DRAIN BASIN, REF CIVIL
1-AE-133
1-AE-133
1-AE-133
1-AE-133
1-AE-133
1-AE-132
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :5
P
M
1-AE-131
REFLECTED CEILING PLANS
ECO
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/32" = 1'-0"
BLDG 1 - SECOND FLOOR OVERALL REFLECTED CEILING PLAN3
1/32" = 1'-0"
BLDG 1 - THIRD FLOOR OVERALL REFLECTED CEILING PLAN41/32" = 1'-0"
BLDG 1 - FOURTH FLOOR OVERALL REFLECTED CEILING PLAN51/32" = 1'-0"
BLDG 1 - FIFTH FLOOR OVERALL REFLECTED CEILING PLAN6
1/32" = 1'-0"
BLDG 1 - FIRST FLOOR OVERALL REFLECTED CEILING PLAN2 1/32" = 1'-0"
BLDG 1 - GROUND FLOOR OVERALL REFLECTED CEILING PLAN1
1-AE-301
EXPOSED TO STRUCTURE ABOVE
EXPOSED TO STRUCTURE ABOVE EXPOSED TO STRUCTURE ABOVE
EXPOSED TO STRUCTURE ABOVE
1-AE-301
2.212.21
5.40
5.42
5.42
5.41
5.41
EXIT LIGHT
2' x 2' ACT CEILING
GYP. BD. CEILING
2 x 2 LIGHT FIXTURE
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
SD SMOKE DETECTOR (REF FIRE PROTECTION)
CEILING HEIGHT, ABOVE FINISH FLOOR
8" x 8" RECESSED CAN LIGHT
CABLE TRAY, REF: ELECTRICAL
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
2 x 4 LIGHT FIXTURE
ACCESS DOOR
00'-00"
POWER POLE (REF ELECTRICAL)
RCP LEGEND
WALL PACK LIGHTING
BUILDING KEY PLAN
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :5
P
M
1-AE-132
ENLARGED REFLECTED CEILING PLAN
ECO
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
BLDG. 1 - GROUND FLOOR - ENLARGED REFLECTED CEILING PLAN1
N
KEYNOTE LEGEND
2.21 RE-INSTALL PREVIOUSLY STORED ACCOUSTICAL CEILING TILE AND
METAL GRID. REPAIR OR REPLACE ANY DAMAGED AREA CAUSED
DURING INSTALLATION OF MECHANICAL DUCTWORK
5.40 STEEL DECK, REF: STRUCTURAL. PAINT FINISH
5.41 STEEL BEAM, REF: STRUCTURAL. PROVIDE INTUMESCENT PAINT
COATING TO ACHEIVE 3 HOUR FIRE RESISTANCE RATING
5.42 STEEL COLUMN, REF: STRUCTURAL. PROVIDE INTUMESCENT PAINT
COATING TO ACHEIVE 2 HOUR FIRE RESISTANCE RATING. COLUMN TO
RECEIVE BLACK ENAMEL PAINT FINISH OVER INTUMESCENT COATING
FROM FLOOR TO 4" ABOVE FINISH FLOOR TO MATCH ADJACENT
RUBBER BASE HEIGHT
1. ALL CEILINGS TO MATCH EXISTING ADJCENT HEIGHTS
2. ALL ACCOUSTICAL CEILING TILE TO MATCH EXISTING COLOR AND TEXTURE
3. ALL CEILING GRID TO MATCH EXISTING ADJACENT COLOR AND SIZE
GENERAL REFELCTED CEILING PLAN NOTES
2.17
9.22
26.04
OI&T
1003A
ELECTRICAL CLOSET
1068A
CORRIDOR
1A
2.18
9.22
2.17
26.05
OI&T
2000A
CORRIDOR
2A
ELECTRICAL CLOSET
2000B
2.18
2.17
9.22
26.05
OI&T
3000A
CORRIDOR
3A
ELECTRICAL CLOSET
3000B 2.18
2.17
9.22
26.04
OI&T
4054C
ELECTRICAL CLOSET
4054B 2.18
2.17
9.22
26.05
CORRIDOR
5A
OI&T
5A1
ELECTRICAL CLOSET
2.18
EXIT LIGHT
2' x 2' ACT CEILING
GYP. BD. CEILING
2 x 2 LIGHT FIXTURE
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
SD SMOKE DETECTOR (REF FIRE PROTECTION)
CEILING HEIGHT, ABOVE FINISH FLOOR
8" x 8" RECESSED CAN LIGHT
CABLE TRAY, REF: ELECTRICAL
SUSPENDED LIGHT FIXTURE
RE: ELECTRICAL
2 x 4 LIGHT FIXTURE
ACCESS DOOR
00'-00"
POWER POLE (REF ELECTRICAL)
RCP LEGEND
WALL PACK LIGHTING
BUILDING KEY PLAN
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :5
P
M
1-AE-133
ENLARGED REFLECTED CEILING PLANS
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NNN
N N
1/2" = 1'-0"
BLDG 1 - FIRST FLOOR REFLECTED CEILING PLAN11/2" = 1'-0"
BLDG 1 - SECOND FLOOR REFLECTED CEILING PLAN21/2" = 1'-0"
BLDG 1 - THIRD FLOOR REFLECTED CEILING PLAN3
1/2" = 1'-0"
BLDG 1 - FOURTH FLOOR REFLECTED CEILING PLAN41/2" = 1'-0"
BLDG 1 - FIFTH FLOOR REFLECTED CEILING PLAN5
KEYNOTE LEGEND
2.17 ACCOUSTIC TILE CEILING SYSTEM TO REMAIN
2.18 GRILL TO REMAIN
9.22 NEW ACOUSTICAL CEILING TILE AND GRID TO MATCH EXISTING, REF:
ROOM FINISH PLAN
26.04 EXISTING LIGHT FIXTURE TO BE REMOVED AND STORED FOR RE-USE IN
SAME LOCATION
26.05 EXISTING LIGHT FIXTURE TO REMAIN
CEILING LEGEND
1" = 80'-0"
KEY PLAN
1 2
SLOPE 1/4" / FT SLOPE 1/4" / FT
S
LO
P
E 1/4" / FT
SLO
P E 1
/4
F T
SLO
P E 1
/4
F T
S
LO
P
E 1/4" / FT
R
ID
G E
23'-0" 23'-6 1/4"
1-AE-301
7.63
7.16
7.63
7.84
7.83
26.01
TYP.
1-AE-301
5.04
E
D
C
B
A
2 3
2" 8'
-0
'-0
8'
-0
1/
4"
23'-0"
'-6
/4
1-AE-311
1-AE-311
5.39
5.39
23.05 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :0
P
M
1-AE-140
ROOF PLAN
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
B1 - ROOF PLAN1
N
KEYNOTE LEGEND
5.04 WALL MOUNTED ROOF ACCESS LADDER
5.39 ROOF TIE-DOWN, REF: SPECIFICATIONS. COORDINATE
LOCATIONS WITH COR PRIOR TO INSTALLATION
7.16 SHEETMETAL PARAPET CAP
7.63 THROUGH WALL SCUPPER AND CONDUCTOR HEAD
7.83 TPO ROOFING MEMBRANE ON TAPERED INSULATION ON
CONCRETE DECK
7.84 EXPANSION JOINT
7.85 ROOF ANCHOR, REFER SPECIFICATION 07 72 00.
COORDINATE LOCATIONS WITH COR PRIOR TO
INSTALLATION
23.05 ROOF TOP UNIT, REF: MECHANICAL
26.01 LIGHT FIXTURE, REF ELECTRICAL
A DC
TOP OF BRICK
15'-0"
1-AE-301
4.20
4.16
7.63
7.84
7.84
3.14
7.16
2.19
REF: AE-401/402 FOR
RAMP, STAIR, & RAILINGS
5.04
26.01
EDCBA
OI&T FLOOR
-1'-2"
GUARDRAIL
HIDDEN FOR
CLARITY
T.O. STEEL
10'-5 1/2"
1-AE-311
REF: CIVIL / 1-GS 4 FOR
STORM DRAIN CONNECTION
NOTE:
ALIGN TOP OF LIGHTING
FIXTURES WITH BOTTOM
OF CAST STONE BAND.
TYP. ALL EXTERIOR
LIGHTING FIXTURES.
4.214.214.21
4.214.214.21
4.214.214.21
6'-3 1/8"
AD C
TOP OF BRICK
15'-0"
1-AE-301
4.20
4.16
4.20
7.63
7.84
7.16
2.19
REF: AE-401/402 FOR
RAMP & RAILINGS
5.04
26.01
E D C B A
OI&T FLOOR
-1'-2"
T.O. STEEL
10'-5 1/2"
5' -4
'-1 0"
F .V
1-AE-311
REF: CIVIL / 1-GS 4
FOR STORM DRAIN
CONNECTION
4.21
NOTE:
ALIGN TOP OF LIGHTING
FIXTURES WITH BOTTOM
OF CAST STONE BAND.
TYP. ALL EXTERIOR
LIGHTING FIXTURES.
4.214.214.21 4.214.214.21 4.214.214.21
'-1
0"
FIRST FLOOR
11'-0"
TOP OF BRICK
15'-0"
4.20
4.16
7.63
4.20
WINDOW
WELL
23.04
LOW LANDING
-2'-4"
EXISTING
BUILDING
BEYOND
7.16
REF: AE-401/402 FOR
RAMP & RAILINGS
1-AE-301
5.04
26.01
OI&T FLOOR
-1'-2"
5.34
RAILINGS HIDDEN
FOR CLARITY
T.O. STEEL
10'-5 1/2"
7.15
7.16
19'-4"13'-5 1/4"
NOTE:
ALIGN TOP OF LIGHTING
FIXTURES WITH BOTTOM
OF CAST STONE BAND.
TYP. ALL EXTERIOR
LIGHTING FIXTURES.
4.214.214.21 4.214.214.21
'-1
0" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :0
P
M
1-AE-201
ELEVATIONS
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
EAST ELEVATION11/4" = 1'-0"
WEST ELEVATION2
1/4" = 1'-0"
NORTH ELEVATION3
KEYNOTE LEGEND
2.19 EXISTING BUILDING
3.14 CONCRETE RAMP
4.16 CAST STONE TO MATCH EXISTING SIZE, HEIGHT, COLOR,
AND TEXTURE. ATTACH TO STRUCTURE PER
MANUFACTURERS REQUIRMENTS.
4.20 BRICK TO MATCH EXISTING
4.21 CONTROL JOINT
5.04 WALL MOUNTED ROOF ACCESS LADDER
5.34 LOCKABLE PANEL
7.15 SHEETMETAL DOWNSPOUT
7.16 SHEETMETAL PARAPET CAP
7.63 THROUGH WALL SCUPPER AND CONDUCTOR HEAD
7.84 EXPANSION JOINT
23.04 NEW HVAC EQUIPMENT, SEE MECHANICAL DRAWINGS
26.01 LIGHT FIXTURE, REF ELECTRICAL
12 13 2
FIRST FLOOR
11'-0"
TOP OF BRICK
15'-0"
1-AE-311
7.96
3.15
27.01
1-AE-301
OI&T FLOOR
-1'-2"
T.O. STEEL
10'-5 1/2"
'-1
1"
FIRST FLOOR
11'-0"
TOP OF BRICK
15'-0"
1-AE-301
D CE B
4.20
4.16
7.16
1-AE-311
7.84
26.01
E D C B A
OI&T FLOOR
-1'-2"
7.84
1-AE-311
T.O. STEEL
10'-5 1/2" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :1
P
M
1-AE-301
BUILDING SECTIONS
NR
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/4" = 1'-0"
BUILDING SECTION 22
KEYNOTE LEGEND
3.15 CONCRETE DECK
4.16 CAST STONE TO MATCH EXISTING SIZE, HEIGHT, COLOR,
AND TEXTURE. ATTACH TO STRUCTURE PER
MANUFACTURERS REQUIRMENTS.
4.20 BRICK TO MATCH EXISTING
7.16 SHEETMETAL PARAPET CAP
7.84 EXPANSION JOINT
7.96 TAPERED RIGID INSULATION
26.01 LIGHT FIXTURE, REF ELECTRICAL
27.01 OI&T EQUIPMENT, REF TELECOM
1/4" = 1'-0"
BUILDING SECTION1
TOP OF BRICK
15'-0"
4.07
4.20
9.05
9.13
OI&T FLOOR
-1'-2"
T.O. STEEL
10'-5 1/2"
4.16
'-7
/2
4'
-6
/2
NOTE: TURN TPO ROOFING
MEMBRANE UP PARAPET,
OVER TOP OF PARAPET, AND
EXTEND DOWN EXTERIOR
SIDE 4" MIN.
9.88
1-AE-311
7.103
GROUND FLOOR
0"
9.13
1-AE-311
9.88
7.87
3.19
1-AE-311
7.90
B
OI&T FLOOR
-1'-2"
T.O. STEEL
10'-5 1/2"
3' -6
/4
'-5
/2
1' -2
NOTE: TURN TPO
ROOFING MEMBRANE
UP 8" MINIMUM.
7.103
7.87
3.18
4.07
9.02
9.13
7.89
5.33
B
T.O. STEEL
10'-5 1/2"
A
NOTE: TURN TPO
ROOFING MEMBRANE
UP 8" MINIMUM.
EXISTING BUILDING 1
7.83
TOP OF BRICK
15'-0"
T.O. STEEL
10'-5 1/2"
4' -6
/2
NOTE: TURN TPO ROOFING
MEMBRANE UP PARAPET,
OVER TOP OF PARAPET, AND
EXTEND DOWN EXTERIOR
SIDE 4" MIN.
4"
4.18
6"
3" 3"
2" 4"
6"
7.83
7.89
TOP OF BRICK
15'-0"
4.07
9.05
9.134.16
7.16
9.88
4.20
1-AE-311
E
OI&T FLOOR
-1'-2"
T.O. STEEL
10'-5 1/2"
3' -4
F
.V
2' -0
F
.V
2' -8
8'
-2
4' -6
/2
'-7
/2
NOTE: TURN TPO ROOFING
MEMBRANE UP PARAPET,
OVER TOP OF PARAPET, AND
EXTEND DOWN EXTERIOR
SIDE 4" MIN.
5.38
8.77
7.103
9.05
9.13
9.05
2.20
GROUND FLOOR
0"
B A
OI&T FLOOR
-1'-2"
1-AE-311
1-AE-311
1-AE-402
Sim
3.15
9.05
5.36
7.847.84
T.O. STEEL
10'-5 1/2"
'-5
/2
1'
-2
NOTE: TURN TPO
ROOFING MEMBRANE
UP 8" MINIMUM.
'-3
/2
1'
-4
7.87
7.103
B A
T.O. STEEL
10'-5 1/2"
4.07
9.13
A3
EXISTING BUILDING 1
7.84
2"
9.02
9.13
TOP OF BRICK
15'-0"
T.O. STEEL
10'-5 1/2"
4.20
7.16
7.89
2' -0
OI&T FLOOR
-1'-2"
4.20
4.09
7.102
9.16
9.05
9.88
3.02
4.07
3.01
4.08
3.02 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:2 :1
P
M
1-AE-311
WALL SECTIONS
ECO
BKM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/2" = 1'-0" 2/ 1-AE-301
WALL SECTION3 1/2" = 1'-0" 1/ 1-AE-121
WALL SECTION1
KEYNOTE LEGEND
2.20 EXISTING CEILING WHERE APPLICABLE
3.01 CONCRETE FOOTING. SEE STRUCT. DWG'S
3.02 CONCRETE SLAB-ON-GRADE. SEE STRUCT. DWG'S
3.15 CONCRETE DECK
3.18 CONCRETE SLAB ON 2" COMPOSITE DECK, REFER
STRUCTURAL
3.19 FELT JOINT
4.07 REINFORCED CMU BEARING WALL. SEE STRUCT. DWG'S
4.08 CAVITY DRAINAGE MESH
4.09 WEEP HOLE
4.16 CAST STONE TO MATCH EXISTING SIZE, HEIGHT, COLOR,
AND TEXTURE. ATTACH TO STRUCTURE PER
MANUFACTURERS REQUIRMENTS.
4.18 MASONRY WALL TIES
4.20 BRICK TO MATCH EXISTING
5.33 TERMINATION BAR. PROVIDE CONTINUOUS BEAD OF
SEALANT ALONG TOP
5.36 NEW ALUMINUM HANDRAIL, SATIN FINISH
5.38 STEEL LINTEL. REF: STRUCTURAL
7.16 SHEETMETAL PARAPET CAP
7.83 TPO ROOFING MEMBRANE ON TAPERED INSULATION ON
CONCRETE DECK
7.84 EXPANSION JOINT
7.87 SEISMIC JOINT
7.89 RIGID INSULATION BOARD
7.90 TPO ROOFING MEMBRANE
7.102 DRIP EDGE
7.103 TAPERED ROOF INSULATION
8.77 THRESHOLD
9.02 7/8" HAT CHANNEL
9.05 3 5/8" C STUD
9.13 5/8" GYPSUM BOARD
9.16 5/8" TYPE X GYPUSM WALLBOARD
9.88 STATIC DISSIPATIVE FLOORING
1 1/2" = 1'-0" 1/ 1-AE-311
P…
This is the start of the file's text. The full file is on GovTribe.