This solicitation is for construction services to support infrastructure upgrades at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The scope of work includes construction of a new fiber backbone, server room, renovations to O&IT closets, HVAC cooling and controls upgrades, patch panel upgrades, cabling upgrades to CAT 6A, additional power and data drops for end user equipment, and power upgrades to O&IT closets and the telephone room. The period of performance is estimated at 365 calendar days after notice to proceed. The principal NAICS code is 236220 for commercial and institutional building construction. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL GENERAL NOTES:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE "INTERNATIONAL BUILDING
CODE, 2018 EDITION" AND ALL APPLICABLE VA DOCUMENTS, INCLUDING HANDBOOK 18-8.
REFER TO THE SPECIAL STRUCTURAL INSPECTION NOTES FOR ADDITIONAL
REQUIREMENTS.
2. CONTRACTOR TO VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING CONDITIONS
AND REPORT ANY DISCREPANCIES TO THE ARCHITECT IMMEDIATELY.
3. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS, ARCHITECTURAL PLANS,
OTHER PLANS, OR SPECIFICATIONS, THE CONTRACTOR OR SUBCONTRACTOR SHALL
PROVIDE A WRITTEN REQUEST FOR CLARIFICATION FROM THE ARCHITECT AND/OR
ENGINEER PRIOR TO PROCEEDING WITH THE WORK
4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE
BUILDING IS FULLY COMPLETED. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO
EXECUTE AND DETERMINE FINAL ERECTION PROCEDURES, SEQUENCING AND TO
INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION.
THIS INCLUDES WHATEVER SHORING, SHEETING, TEMPORARY BRACING, GUYING OR TIE
DOWNS WHICH MIGHT BE NECESSARY.
5. THE STRUCTURE AND FOUNDATIONS ARE DESIGNED FOR A ONE-STORY ADDITION.
6. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT CHANGES
MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH THE CONTRACT DOCUMENTS.
7. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR TRIMMED FOR
ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
8. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE REVIEWED
BY THE ARCHITECT BEFORE PLACEMENT THROUGH STRUCTURAL MEMBERS.
9. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS DO
NOT COINCIDE WITH EQUIPMENT SHOWN ON THE PLANS, COORDINATE ADJUSTMENTS
WITH THE ARCHITECT.
10. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION MATERIALS
OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE CENTERED UNDER
SUPPORTING MEMBERS (TYPICAL UNLESS NOTED).
12. FOR DEFERRED SUBMITTALS (E.G. HELICAL PILES AND SEISMIC BRACING), SHOP
DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL ENGINEER LICENSED TO
PRACTICE IN THE JURISDICTION OF THE PROJECT SHALL BE FURNISHED TO THE
ENGINEER OF RECORD FOR REIVEW.
13. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED "S0XX". THE INCLUDED
TYPICAL DETAILS MAY OR MAY NOT BE CUT / REFERENCED ON PLANS OR SECTIONS, BUT
ARE TO BE USED AS APPLICABLE.
STRUCTURAL DESIGN CRITERIA (2018 IBC AND ASCE 7-16):
1. BUILDING OCCUPANCY RISK CATEGORY IV.
2. LIVE LOADS [UNIFORM (PSF) / POINT LOADS (KIPS)]:
-- ROOF:………………………………………...............20 PSF / 300#
-- OFFICES:………………….…..…............................50 PSF + 15 PSF PARTITIONS / 2.0 K
-- UPPER LEVEL CORRIDORS................................80 PSF / 2.0 K
-- GROUND LEVEL SLAB ........................................100 PSF / 2.0 K
-- STAIRS ................................................................100 PSF / 300# -- LOBBIES ..............................................................100 PSF / 2.0 K
-- ACCESS FLOOR / SERVER ROOM.....................100 PSF / 2.0 K
3. ROOF SNOW LOAD:
-- GROUND SNOW LOAD (Pg):……………………....15 PSF -- FLAT ROOF SNOW LOAD (Pf): ...........................13 PSF W/ DRIFT -- MIN UNIFORM ROOF SNOW LOAD (Pm):…...….15 PSF (NO DRIFT OR RAIN) -- RAIN ON SNOW SURCHARGE (Prs) ...................5.0 PSF -- SNOW EXPOSURE FACTOR (Ce):………………..1.0, EXPOSURE B & C -- SNOW LOAD IMPORTANCE FACTOR (Is):….......1.0 -- THERMAL FACTOR (Ct):……………………….......1.1 (just above freezing)
4. WIND DESIGN DATA:
-- BASIC WIND SPEED (3 SEC GUST):……………..116 MPH
-- WIND EXPOSURE:…………………………………..B
-- DIRECTIONALITY FACTOR (Kd) .........................0.85
-- INTERNAL PRESSURE COEFF:………….……….0.18
-- COMPONENTS AND CLADDING WIND (ULTIMATE 1.0*W) PRESSURES
(BASED ON TRIB 10 S.F., EXP. B. MAY BE REDUCED FOR COMPONENTS
WITH LARGER TRIB PER BLDG CODE):
WALLS AT CORNERS & EDGES:…………………+30 / -40 PSF
ALL OTHER MAIN WALL CONDITIONS:…………+30 / -33 PSF
ROOF CORNERS:…...................……………….....+15 / -57 PSF
ROOF EDGES: .....................................................+15 / -39 PSF
ALL OTHER MAIN ROOF CONDITIONS:…………+15 / -23 PSF
5. EARTHQUAKE DESIGN DATA:
-- SEISMIC IMPORTANCE FACTOR (Ie):………......1.5
-- NONSTRUCTURAL COMPONENT IMPORTANCE
FACTOR (Ip):…….....................................…...1.5 -- MAPPED SPECTRAL RESP ACCEL (Ss / S1):…..1.04/ 0.344
-- SITE CLASS:………………………………………….D
-- SPECTRAL RESPONSE COEFF (Sds / Sd1):……0.752 / 0.393
-- SEISMIC DESIGN CATEGORY:……………………D
-- SEISMIC FORCE RESISTING SYSTEM:…………
SPECIAL REINFORCED MASONRY SHEAR WALLS (ASCE 7-16 TYPE A7)
-- DESIGN BASE SHEAR:……………………………..117 KIPS
-- SEISMIC RESPONSE COEFF (Cs):……………….0.225
-- ANALYSIS PROCEDURE:…………………………..RSA/ELF
-- MAX PERMITTED INTERSTORY DRIFT:..………..5/8 INCH
6. GUARD RAILS:.........................................................50 PLF, AND/OR 200# CONCENTRATED
LOAD APPLIED IN ANY DIRECTION.
CONCRETE AND MASONRY REINFORCING STEEL:
1. SUBMIT SHOP DRAWINGS FOR REBAR. ALL REINFORCING BARS SHALL MEET ASTM
A615 GRADE 60.
2. ALL MESH SHALL MEET ASTM A-185: LAP A MINIMUM OF 8” OR ONE FULL MESH,
WHICHEVER IS GREATER.
3. REINFORCING BARS QUANTITIES SHOWN ARE FOR ESTIMATING PURPOSES ONLY.
4. PROVIDE AN ADDITIONAL ALLOWANCE OF 1% OF THE TOTAL REINFORCING SHOWN ON
THE FINAL DRAWINGS TO BE FABRICATED AND ERECTED DURING THE PROGRESS OF THE
WORK AT THE DIRECTION OF THE STRUCTURAL ENGINEER. FOR THE ADDITIONAL
REINFORCING ALLOWANCE, INCLUDE BOTH THE COST OF THE REINFORCING AND THE
LABOR TO PLACE IT.
5. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE ¾” CLEAR FOR SLABS, 2”
CLEAR FOR FORMED SURFACES AND 3” CLEAR FOR FOOTINGS (TYPICAL UNLESS NOTED).
6. CONTRACTOR SHALL VERIFY THAT ALL REINFORCEMENT, SLAB DOWELS, INSERTS,
SLEEVES AND EMBEDDED ITEMS ARE PROPERLY LOCATED AND RIGIDLY SECURED PRIOR
TO CONCRETE PLACEMENT, “WET STICKING” DOWELS WILL NOT BE ALLOWED.
7. REINFORCEMENT SHALL BE DETAILED IN ACCORDANCE WITH THE LATEST A.C.I.
DETAILING MANUAL BY A QUALIFIED AND EXPERIENCED FIRM AND PERSON. PLACE AND
SUPPORT REINFORCEMENT WITH ACCESSORIES: MAXIMUM SPACING - 48” CENTERS
(PLASTIC-TIPPED LEGS FOR EXPOSED SURFACES). USE 3” SBP SUPPORTS AT ALL
FOOTINGS.
CAST IN PLACE CONCRETE:
1. SUBMIT PROPOSED MIXED DEIGNS OF EACH TYPE FOR REVIEW.
REQUIRED MINIMUM CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS:
a. FOOTING AND GRADEBEAM CONCRETE………………..4000 PSI
b. BASEMENT / FOUNDATION WALL CONCRETE………….4000 PSI
c. SLAB ON GRADE AND STRUC SLAB ABOVE GRADE…..4000 PSI
2. ALL CONCRETE MIX DESIGNS SHALL HAVE WATER TO CEMENT RATIOS LESS THAN
0.52, WITH A MAXIMUM 60/40 FINE TO COARSE AGGREGATE RATIO. CONCRETE MIX
DESIGNS THAT DO NOT CONFORM TO THE ABOVE STANDARD AND/OR CONTAIN WATER
REDUCING ADMIXTURES SHALL BE SUBMITTED WITH APPROPRIATE TEST DATA PER
A.C.I.. ALL CONCRETE SHALL BE IN CONFORMANCE WITH THE LATEST A.C.I. 301
STANDARDS PUBLICATION.
2A. LIGHTWEIGHT CONCRETE SHALL HAVE A MAXIMUM DRY UNITY WEIGHT OF 118 PCF.
3. EXTERIOR CONCRETE (FLOOR SLABS, WALLS, ETC) SHALL HAVE 6% (PLUS/MINUS 1%)
ENTRAINED AIR.
4. CHAMFER ALL EXPOSED CONCRETE EDGES 3/4” (VERIFY WITH ARCHITECT).
5. NO ALUMINUM SHALL BE EMBEDDED IN ANY CONCRETE.
6. NO CALCIUM CHLORIDE SHALL BE USED IN CONCRETE
7. THE DESIGN, CONSTRUCTION, AND SAFETY OF ALL FORMWORK IS THE
RESPONSIBILITY OF THE CONTRACTOR
8. ALL CONCRETE IS REINFORCED UNLESS SPECIFICALLY NOTED AS UNREINFORCED.
REINFORCE ALL CONCRETE NOT OTHERWISE SHOWN WITH THE SAME REINFORCING AS
SIMILAR SECTIONS OR AREAS.
9. CONSTRUCTION JOINTS IN GRADE BEAMS, CONTINUOUS FOOTINGS, AND WALLS THAT
DO NOT CHANGE DIRECTION SHALL BE SPACED NO GREATER THAN 60’-0”.
INTERMEDIATE CONTROL JOINTS SHALL BE SPACED AT 25’-0” MAX FOR WALLS. CONTROL
JOINTS IN WALLS SHALL ALSO BE LOCATED 15’-0” FROM CORNERS AND AT CHANGES IN
WALL THICKNESS
10. WHERE FRESH CONCRETE IS DEPOSITED AGAINST HARDENED CONCRETE (GREATER
THAN 8 HRS OLD), CLEAN EXISTING SURFACE OF LAITANCE AND FOREIGN MATERIAL AND
DAMPEN THE EXISTING SURFACE. IF REQUIRED, ROUGHEN EXISTING CONCRETE TO ¼”
AMPLITUDE.
11. SLABS ON GRADE SHALL BE 6” THICK MINIMUM ON 4” OF GRANULAR FILL. REINF SLAB
WITH #4 BARS @ 12" OC EA WAY. PLACE REINF IN UPPER 1/3 OF SLAB THICKNESS. AT
INTERIOR SLABS, A 10 MIL VAPOR BARRIER SHALL BE PLACED BETWEEN THE CONCRETE
AND GRANULAR BASE AND CARE SHOULD BE TAKEN DURING CURING TO PREVENT SLAB
CURLING. THIS NOTE SHALL BE TYPICAL UNLESS NOTED OTHERWISE
12. SAW CUT JOINTS OR KEYED CONSTRUCTION JOINTS IN SLABS ON GRADE SHALL BE
SPACED TO DIVIDE THE SLAB INTO PANELS NOT TO EXCEED 225 SQUARE FEET. THE
LONGER DIMENSION OF EACH PANEL SHALL NOT EXCEED THE SHORTER DIMENSIONS BY
MORE THAN 40%. JOINTS SHALL BE LOCATED AT COLUMN CENTERLINES WHERE
POSSIBLE. SPACING BETWEEN JOINTS SHALL NOT EXCEED 15 FEET. CONTRACTOR SHALL
SUBMIT JOINT LAYOUT TO ARCHITECT FOR APPROVAL. REFER TO TYP DETAIL RC-001A.
13. REINFORCEMENT SHALL BE CONTINUOUS AND LAPPED 53 BAR DIAMETERS (2’ -6”
MIN.) EXCEPT AS NOTED AND PROVIDE CORNER BARS OF SAME SIZE AND SPACING.
14. MINIMUM CONCRETE WALL REINFORCING (WALL 10” OR GREATER) SHALL BE #5 AT
10” CENTERS EACH WAY, EACH FACE
15. MINIMUM REINFORCING AROUND CONCRETE WALL OPENINGS 2’-0” OR GREATER
(TYPICAL UNLESS NOTED): 2 - #5, EXTEND REINF 2’-0” PAST OPENINGS. PROVIDE 2-#5 x
4’-0” DIAGONAL BARS AT CORNERS
16. CONTRACTOR SHALL COORDINATE ALL CURING COMPOUNDS WITH FLOOR FINISH
REQUIREMENTS TO ENSURE COMPATIBILITY.
17. FOUNDATION CONTRACTOR TO ENSURE PROPER ANCHOR ROD PROJECTION AND
THAT ANCHOR RODS ARE HELD SECURELY IN POSITION PRIOR TO CONCRETE
PLACEMENT. INSTALL ANCHOR RODS TO THE STRICT DIMENSIONAL TOLERANCES PER
AISC REQUIREMENTS. STRUCTURAL STEEL COLUMN ANCHOR RODS SHALL BE SET WITH
A RIGID TEMPLATE.
18. AGGREGATES AND/OR CONCRETE MIXES SHALL BE CERTIFIED TO BE FREE OF AND
ELIMINATE DAMAGE OF CONCRETE DUE TO ALKALI-SILICA REACTION OR ALKALI-
AGGREGATE REACTIONS WHEN EXPOSED TO SOILS AND/OR AN EXTERIOR
ENVIRONMENT.
19. PROVIDE ARCHITECTURALLY RUBBED FINISH FOR ALL EXPOSED VERTICAL
CONCRETE SURFACES (RE: ARCH).
STRUCTURAL STEEL:
1. SUBMIT SHOP DRAWINGS FOR STEEL.
STRUCTURAL STEEL SHAPES AND PLATE MATERIAL REQUIREMENTS (TYPICAL UNLESS
NOTED OTHERWISE):
a. WIDE FLANGE SHAPES - ASTM A992 (FY = 50 KSI MIN.)
b. CHANNELS, ANGLES, AND PLATES: - ASTM A36 (FY = 36 KSI MIN)
c. ROUND HSS - ASTM A500, GR B (FY = 42 KSI)
d. RECTANGULAR HSS - ASTM A500, GR B (FY = 46 KSI)
e. PIPE - ASTM A53, GR B (FY = 35 KSI)
f. ANCHOR RODS - ASTM F1554 (FY = 36 KSI MIN.),
2. STRUCTURAL STEEL SHALL BE NEW AND MEET THE 13TH EDITION A.I.S.C.
“SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS AND BRIDGES”, AND THE “CODE
OF STANDARD PRACTICES FOR STEEL BUILDINGS AND BRIDGES”, EXCLUDING SECTION
4.4.1.B.
3. THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC QUALITY CERTIFIED
COMPANY FOR THE CATEGORY OF WORK IN THIS PROJECT OR PROVIDE A QUALITY
ASSURANCE PLAN AND SPECIAL INSPECTIONS AS DEFINED IN THE CODE.
4. USE STANDARD AISC FRAMING CONNECTIONS WITH A325-N BOLTS, F436 WASHERS,
AND A563 HEAVY-HEX NUTS AS REQUIRED, UNLESS NOTED OTHERWISE.
5. BOLTS IN MOMENT AND BRACED FRAME CONNECTIONS SHALL BE PRE-TENSIONED.
ALL A490 BOLTS SHALL BE PRE-TENSIONED. OTHER BOLTED CONNECTIONS USING A325
BOLTS MAY BE SNUG-TIGHTENED, UNLESS NOTED OTHERWISE.
6. STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP.
7. WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE AWS STANDARDS AND
BE COMPLETED BY AN AWS CERTIFIED WELDER. ALL WELDS SHALL UTILIZE E70xx
ELECTRODES. SHOP DRAWINGS SHALL SHOW FIELD WELDS, AS APPROPRIATE.
a. AWS D1.1 - STRUCTURAL WELDING CODE - STEEL
b. AWS D1.3 - STRUCTURAL WELDING CODE - SHEET STEEL
c. AWS D1.6 - STRUCTURAL WELDING CODE - STAINLESS STEEL
8. WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED EFFECTIVE THROAT
WIDTH IF GAPS EXIST AT THE FAYING SURFACE
9. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON THE STRUCTURAL
DRAWINGS, WILL BE ALLOWED WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL
ENGINEER.
10. SEE ARCHITECTURAL PLANS FOR FIREPROOFING & FINISHING REQUIREMENTS, AND
COORDINATE STEEL PRIMING & COATINGS ACCORDINGLY.
11. GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE NON-METALLIC
NON-SHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF 6000 PSI AT 28 DAYS
CONFORMING TO ASTM C1107
12. ALL POST-INSTALLED ANCHORS WHERE NOTED SHALL BE MANUFACTURED BY
SIMPSON STRONG-TIE OR HILTI, INC. AND INSTALLED PER MANUFACTURER'S
SPECIFICATIONS. SUBSTITUTIONS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
WITH APPROPRIATE IC-ES EVALUATION REPORTS.
13. ALL STEEL NOT PROTECTED FROM WEATHER AND WHOLLY WITHIN A CONDITIONED
SPACE (INCLUDING ALL MASONRY LINTELS) SHALL BE HOT DIPPED GALVANIZED PER
ASTM A123.
METAL DECK:
1. SUBMIT SHOP DRAWINGS FOR ALL METAL DECKING.
A. COMPOSITE FLOOR DECK: 3 1/2” 18 GA (FY = 33 KSI MIN), G60 GALVANIZED, MIN
FASTENING PATTERN: 36/4 WITH 3 SIDELAPS PER SPAN (UNO),
2. STEEL DECK MANUFACTURER SHALL BE A MEMBER OF THE STEEL DECK INSTITUTE
(S.D.I.). ALL METAL DECK TO BE ERECTED PER MANUFACTURER REQUIREMENTS AND
SPECIFICATIONS
3. DECK SHALL BE WELDED AT SUPPORTS WITH 5/8” DIA PUDDLE WELDS MIN. AND
SIDELAP CONNECTIONS SHALL BE #10 TEK SCREWS MIN (UNO).
4. ALL METAL DECK HAS BEEN DESIGNED TO BE CONTINUOUS OVER 2 SPANS MINIMUM
AND SHALL BEAR 2” MINIMUM ON STEEL SUPPORTS. FOR ONE OR TWO SPAN
CONDITIONS CONTRACTOR SHALL PROVIDE SHORING AS REQUIRED OR FURNISH
THICKER GAGE DECK TO SUPPORT ALL APPLICABLE LOADS. CONTRACTOR TO SUBMIT
ALTERNATES FOR APPROVAL.
5. PROVIDE REINFORCING CHANNELS, STANDARD CLOSURES, CANT STRIPS, SUMP
PANS, AND OTHER ACCESSORIES AS REQUIRED FOR A PROPERLY FINISHED JOB, EVEN
IF NOT SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS. PROVIDE BEARING
ANGLES WELDED TO COLUMNS AS REQUIRED TO SUPPORT METAL DECK.
6. ONE OPENING PER DECK SHEET, 6” OR LESS IN DIAMETER, IS PERMISSIBLE. HOLES
LARGER THAN 6” IN DIAMETER OR MORE THAN ONE HOLE PER DECK SHEET REQUIRES
REINFORCING PER SDI. HOLES LARGER THAN 12” (ROUND OR SQUARE) REQUIRE A
STEEL FRAME
7. OPENINGS IN ROOF DECK TO BE FRAMED WITH L4x4x1/4 ANGLE. EXTEND ANGLES TO
STRUCTURAL SUPPORTS, BLOCK VERTICAL LEGS AND FIELD WELD. TYPICAL UNLESS
NOTED OTHERWISE.
STRUC ABREVIATIONS
Abrev Text
A.R. ANCHOR ROD
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED STRUC STL
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECT OR ARCHITECTURAL
atat PLUS OR MINUS
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
CF COLD FORMED METAL FRAMING
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DIA DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EE EXTENDED END
EJ EXPANSION JOINT
EL ELEVATION
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQP EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
F.V. FIELD VERIFY
FLG FLANGE
FLR FLOOR
FND FOUNDATION
FS FAR SIDE
FTG FOOTING
G.C. GENERAL CONTRACTOR
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
k KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SPLICE LENGTH
LW LIGHTWEIGHT
MAS MASONRY
MATL MATERIAL
MFCR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NS NON-SHRINK
NTS NOT TO SCALE
O.F. OUTSIDE FACE
OC ON CENTER
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PEN PENETRATION
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAL FOOT
PMB PRE-ENGINEERED METAL BUILDING
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R.F. RIGID FRAME
RC REINFORCED CONCRETE
RE: OR REF REFER TO
REINF REINFORCING
REQD REQUIRED
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TOS TOP OF STEEL
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWF WELDED WIRE FABRIC
SPECIAL INSPECTIONS
1. PROVIDE SPECIAL STRUCTURAL INSPECTIONS AND VERIFICATIONS BY A THIRD PARTY
MEETING THE REQUIRMENTS OF CHAPTER 17 OF THE BUILDING CODE AND THE BUILDING
OFFICAL.
2. SPECIAL INSPECTORS SHALL BE QUALIFIED AND FURNISH THEIR REPORTS IN A
TIMELY MANNER TO THE CONTRACTOR, BUILDING OFFICALS, ARCHITECT, AND/R
ENGINEER
3. SHOULD INSPECTOR IDENTIFY ANY DISCREPANCY, THEY SHAL NOTIFY CONTRACTOR
FIRST, AND THEN ARCHT/ ENGINEER IMMEDIATELY THEREAFTER IF CORRECTIVE ACTION
IS NEEDED.
4. SPECIAL INSPECTIONS AS REQUIRED BY CODE:
A. STEEL: SECTION 1705.2, AISC 360, AND TABLE 1705.2.2. PERIODIC OBSERVATIONS
OF CONNECTION, ALL BRACED-FRAME CONNECTIONS, WELDERS & FIELD WELDING.
B. CONCRETE: SECTION 1705.3 AND TABLE 1705.3 CONCRETE MATERIAL SAMPLING
AND TESTING, REBAR OBSERVATIONS. TAKE SET OF (3) CYLINDERS FOR EVERY 50 C.Y.,
BUT NOT LESS THAN ONE SET OF SAMPLES PER DAY'S WORK AND PER MIX.
C. EARTHWORK: FOUNDATION BEARING, EXCAVATION, FILL PLACEMENT.
EARTHWORK AND FOUNDATIONS:
1. REFERENCE THE GEOTECHNICAL INVESTIGATION PREPARED BY OLSSON, INC DATED
10 NOVEMBER 2020 (JOB NO. 020-2333). THE CONTRATOR SHALL OBTAIN A COPY OF THIS
REPORT AND FOLLOW ALL RECOMMENDATIONS WITHIN.
2. ALL FOOTINGS SHALL BEAR A MINIMUM DEPTH BELOW GRADE OF 3'-0" ON FIRM
NATIVE MATERIALS, COMPACTED OR ENGINEERED FILL CAPABLE OF SUPPORTING AN
ALLOWABLE BEARING PRESSURE OF 2,500 PSF PER THE GEOTECHNICAL REPORT.
DEEPEN FOOTINGS, AND REMOVE AND REPLACE SOFT SOILS WITH ENGINEERED FILL AS
REQUIRED TO PROVIDE THIS MINIMUM DEPTH AND SUITABLE BEARING.
3. UNDERCUT THE PAD TO A DEPTH OF 18-INCHES BELOW BOTTOM OF FLOOR SLAB
ELEVATION AND REPLACE WITH LOW-VOLUME-CHANGE MATERIALS PER THE
GEOTECHNICAL REPORT.
4. FILL PLACEMENT, COMPACTION, AND SOIL BEARING TESTS SHALL BE PERFORMED BY
A GEOTECHNICAL ENGINEER PRIOR TO INSTALLING FOOTINGS TO ENSURE DESIGN
ALLOWABLE BEARING VALUES AND SLAB SUBGRADE REQUIREMENTS ARE SATISFIED. IF
ACTUAL SITE CONDITIONS DO NOT SATISFY THESE REQUIREMENTS, COORDINATE
ADJUSTMENTS WITH ARCHITECT/ENGINEER/ GEOTECHNICAL ENGINEER
5. SURFACE WATER SHALL NOT BE ALLOWED TO STAND ADJACENT TO OR DRAIN
TOWARDS THE FOUNDATION AND SLAB SUBGRADES UNDER ANY CIRCUMSTANCES.
REFER TO CIVIL FOR ELEVATIONS OF PAVEMENTS AND GRADED SOILS.
6. FOOTINGS MAY BE POURED TO NEAT LINES OF EXCAVATIONS PROVIDING VERTICAL
LINES OF EXCAVATIONS CAN BE MAINTAINED DURING CONCRETE PLACEMENT.
7. FOUNDATION WALL BACKFILL SHALL NOT BE UNBALANCED BY MORE THAN TWO FEET
ON EITHER SIDE AT ANY TIME. BASEMENT WALL AND RESTRAINED RETAINING WALL
BACKFILL SHALL NOT BE PLACED, UNLESS THE WALL IS ADEQUATELY BRACED.
RETAINING WALL AND BASEMENT WALL BACKFILL SHALL BE FREE DRAINING GRANULAR
BACKFILL ACCEPTABLE TO THE GEOTECHNICAL ENGINEER.
8. NOTE THAT PREVIOUS BORINGS INDICATE THE POSSIBLE PRESENCE OF BOULDERS
AT THE SITE. THE GEOTECHNICAL REPORT RECOMMENDS INSTALLING A TEST HELICAL
PILE TO EVALUATE THE FEASIBILITY OF USING THAT FOUNDATION SYSTEM.
9. BEDROCK WAS NOT ENCOUNTERED WITHIN A DEPTH OF 20 FEET
CONCRETE MASONRY UNITS:
1. ALL MASONRY SHALL BE IN ACCORDANCE WITH ACI 530 / TMS 402. REFER TO
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR NON-STRUCTURAL BRICK
REQUIREMENTS. INDIVIDUAL CMU'S SHALL BE PER ASTM C90, GROUT SHALL BE PER ASTM
C476, MORTAR SHALL BE PER ASTM C270.
A. USE OF MASONRY CEMENT IS PROHIBITED.
B. USE OF AIR-ENTRAINING ADMIXTURES IS PROHIBITED.
2. MASONRY MATERIALS SHALL BE AS FOLLOWS:
A. f'm = 1,500 PSI MINIMUM. ALL UNITS SHALL BE LIGHT-WEIGHT BLOCK.
B. GROUT STRENGTH NOT LESS THAN 2,000 PSI. GROUT SHEAR WALLS SOLID.
C. MORTAR TYPE S. (USE TYPE M OR S, OR BETTER FOR PORTIONS BELOW-GRADE).
4. WHERE NOT OTHERWISE SHOWN, MINIMUM WALL REINFORCEMENT SHALL BE (1) #4 VERT
AT 8" O.C. MAX. PROVIDE NOT LESS THAN 9-GAGE HORIZONTAL LADDER-TYPE
REINFORCEMENT AT NOT MORE THAN 16" O.C. VERTICALLY, LAPPED 8" MINIMUM.
DISCONTINUE HORIZ REINF AT CONTROL JOINT LOCATIONS. REBAR POSITIONERS SHALL
BE USED FOR ALL VERTICAL BARS SUCH THAT A MINIMUM 3" OF SPACE IS MAINTAINED
CLEAR FOR PLACEMENT OF GROUT.
5. ALL BLOCKS SHALL BE LAID IN RUNNING BOND.
6. GROUT SOLID ALL UNITS LOCATED BELOW FINISH FLOOR.
A. ALL GROUND-LEVEL SHEAR WALLS SHALL BE GROUTED SOLID.
B. GROUND POUR HEIGHTS SHALL NOT EXCEED 5'-0" UNLESS CLEAN-OUTS ARE
PROVIDED AND INSPECTED. THE MAXIMUM GROUT POUR HEIGHT WITH CLEANOUTS SHALL
NOT EXCEED 12'-0". STOP GROUT POURS AT 1-1/2" BELOW THE TOP OF THE CMU COURSE.
CONSOLIDATE GROUT WITH VIBRATOR.
7. ALL OPENINGS IN NEW CONCRETE MASONRY WORK REQUIRE A BOND-BEAM LINTEL PER
TYPICAL DETAILS AND PLANS.
A. GALVANIZED LOOSE-ANGLE STEEL LINTELS SHALL BE UTILIZED TO SUPPORT BRICK
VENEER, AND WHERE CUTTING IN NEW OPENINGS IN EXISTING BRICK AND TILE WALLS.
8. PROVIDE CONTROL JOINTS AS SHOWN ON ARCHITECTURAL AND/OR STRUCTURAL
DRAWINGS. WHERE NOT SHOWN OR OTHERWISE DENOTED, PROVIDE CONTROL JOINTS AT
NOT MORE THAN 25'-0" O.C., LOCATED AT OPENINGS, AND NEAR CORNERS, AS SHOWN ON
TYPICAL DETAILS.
9. PLACEMENT OF REINFORCEMENT SHALL OCCUR PRIOR TO PLACEMENT OF GROUT. ALL
REINFORCEMENT IN STRUCTURAL AND SHEAR WALLS SHALL BE INSPECTED PRIOR TO
GROUTING, AND ALL MATERIALS AND MATERIAL PLACEMENT INSPECTED AND TESTED.
10. EXTEND HORIZONTAL REINFORCEMENT IN BOND BEAMS, LINTELS AND SILL NOT LESS
THAN 2'-0" PAST ENDS OF ALL OPENINGS.
11. PROVIDE LOOSE ANGLE STEEL LINTELS PER THE TYPICAL DETAILS.
12. REINFORCE BOND BEAMS W/ (1) #5 BAR MIN, UNLESS NOTED OTHERWISE.
13. PROVIDE BOND BEAMS SPACED AT 4'-0" O.C. MAX AND WITHIN 1'-4" OF TOP AND BOTTOM
OF WALLS (AND AS NOTED ON DRAWINGS).
14. PROVIDE STANDARD HOOK AROUND VERTICAL BAR WHEN BOND BEAM TERMINATES AT
AN OPENING.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2 :2
P
M
1-S-001
STRUCTURAL GENERAL NOTES
NH/EJSPWS
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
HELICAL PILE FOUNDATIONS:
1. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE
CURRENT INTERNATIONAL BUILDING CODE (IBC) ADOPTED BY THE LOCAL JURISDICTION.
2. HELICAL PILE SHALL BE RECONGNIZED BY ICC AND THE MANUFACTURER SHALL HOLD A
CURRENT ICC-ES ESR REPORT SHOWING COMPLIANCE WITH AC358 AND CURRENT
INTERNATIONAL BUILDING CODE (IBC) ADOPTED BY THE LOCAL JURISDICTION.
3. MINIMUM AND MAXIMUM INSTALLATION TORQUES SHALL BE SPECIFIED BY THE HELICAL
PILE MANUFACTURER. THE MINIMUM INSTALLATION TORQUE SHALL BE HIGH ENOUGH TO
ACHIEVE THE REQUIRED BEARING CAPACITY, INCLUDING A SAFETY FACTOR OF 2. THE
MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLE TORSIONAL
CAPACITY OF THE PILE SHAFTS.
4. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED TO RESIST ALL STRESSES
INDUCED BY INSTALLATION.
5. EXISTING CONDITIONS AND UNDERGROUND OBSTRUCTIONS SHALL BE CONFIRMED BY
THE PILE INSTALLER. PROBING OR SCANNING MAY BE NECESSARY TO LOCATE
UNDERGROUND OBSTRUCTIONS. REPORT ANY UNFORSEEN OBSTRUCTIONS TO THE
STRUCTURAL ENGINEER.
6. LOCATIONS OF PILES SHALL NOT BE CHANGED WITHOUT WRITTEN APPROVAL FROM THE
STRUCTURAL ENGINEER.
7. SPECIAL INSPECTION OF THE HELICAL PILE INSTALLATION SHALL BE PERFORMED IN
ACCORDANCE WITH SECTION 1705.9 OF THE 2018 IBC UNLESS EXCEPTIONS NOTED IN
SECTION 1704.2 OF IBC ARE MET. THE INSPECTOR SHALL RECORD THE FOLLOWING:
A. INSTALLATION DATE.
B. PILE MANUFACTURER.
C. INSTALLATION CONTRACTOR.
D. IDENTIFICATION OF INSTALLATION EQUIPMENT.
E. MINIMUM ALLOWABLE INSTALLATION TORQUE.
F. MAXIMUM ALLOWABLE INSTALLATION TORQUE.
G. CENTRAL SHAFT DIAMETER OF EACH PILE.
H. HELIX PLATE CONFIGURATION OF EACH PILE.
I. ACTUAL TIP EMBEDMENT OF EACH PILE.
J. ACTUAL INSTALLATION TORQUE OF EACH PILE.
K. ULTIMATE CAPACITY OF EACH PILE AS SPECIFED BY MANUFACTURER.
L. ALLOWABLE CAPACITY OF EACH PILE AS SPECIFIED BY MANUFACTURER.
03/23/2021
DEVELOPMENT AND LAP SPLICE SCHEDULE
#3
#4
#5
#6
#7
#8
#9
BAR
F'c = 3000 psi
EMBEDMENT
8 21
COMPR TENSION (LTE)
OTHER
LAP SPLICE
(LCS) TOP
COMPR TENSION (LTS)
OTHER
HOOK
(LDH)
16 12 28 21 6
22 15 37 28 8
27 19 46 36 10
33 23 56 43 12
48 26 81 62 13
55 30 93 71 15
80 62 34 105 80 17
F'c = 4000 psi
EMBEDMENT
(LCE) TOP
COMPR TENSION (LTE)
OTHER
LAP SPLICE
(LCS) TOP
COMPR TENSION (LTS)
OTHER
HOOK
(LDH)
18 14 12 24 18 6
25 19 15 32 25 7
31 24 19 40 31 8
37 28 23 48 37 10
54 42 26 70 54 12
62 47 30 80 62 13
70 54 34 91 70 15
(LCE)
#10 90 70 38 118 90 19 24 78 60 38 102 78 17
#11 100 77 42 131 100 22 27 87 67 42 113 87 1931
TOP
NOTES (GENERAL):
1. STAGGER ALL SPLICES 12 db MIN, BUT NOT LESS THAN 12"
2. ALL DIMENSIONS INDICATED IN TABLE ARE IN INCHES
3. BARS GREATER THAN #11 SHALL BE MECHANICALLY SPLICED
4. ALL SPLICES SHALL BE WIRED IN CONTACT STACKED VERTICAL.
MULTIPLIERS:
ALL EMBEDMENT AND LAP SPLICE LENGTHS SHALL BE INCREASED
AS REQD BY THE MULIPLIERS BELOW. APPLY MULTIPLE
MULTIPLIERS IF APPLICABLE.
1.3 -- IF CONC CONTAINS LIGHT WEIGHT AGGREGATES
1.3 -- IF EPOXY COATED REBAR USED
NOTES (PERTAINING TO TABLE):
1. TOP BARS ARE HORIZONTAL BARS THAT HAVE MORE THAN 12" OF FRESH
CONCRETE CAST BELOW THEM.
2. ALL BARS THAT ARE NOT "TOP BARS" ARE "OTHER" BARS
3. ABBREVIATIONS:
- LCE - COMPRESSION EMBEDMENT LENGTH
- LTE - TENSION EMBEDMENT LENGTH
- LCS - COMPRESSION LAP SPLICE LENGTH
- LTS - TENSION LAP SPLICE LENGTH
- LDH - HOOKED BAR TENSION EMBEDMENT LENGTH
90.00°
90.00°
CONTROL OR
CONSTRUCTION
JOINT
4" M
IN (TYP)
1/4" PREFORMED
JOINT FILLER AROUND
COLUMN AND AT EDGE
OF BLOCKOUT. FILL
JOINT WITH SEALANT
(TYP)
EDGE OF SLAB
OR FACE OF
WALL
NOTE:
PROVIDE SONOTUBE BLOCKOUT
WHEN CONTROL / CONSTRUCTION
JOINTS DO NOT EXTEND FROM ALL
CORNERS OF BLOCKOUT
EDGE OF SLAB OR
FACE OF WALL
EDGE OF
BLOCK OUT
EDGE OF
BLOCKOUT
INTERIOR COL
EXTERIOR COL
CORNER COL
1/
2"
5/16" CONT
BENT PL
1/4" CONT
BENT PL
5/16"
5/16"
L1
L2
L3
L4
MARK
L5
L6
OPENING SIZE
UP TO 1'-8"
1'-9" TO 3'-0"
3'-1" TO 4'-5"
4'-6" TO 6'-3"
6'-4" TO 8'-0"
8'-1" TO 12'-0"
1/4" PL x WALL WIDTH - 1/2"
LINTEL SIZE
L 3-1/2" x 3-1/2" x 1/4"
L 4" x 3-1/2" x 5/16"
L 5" x 3-1/2" x 3/8"
L 6" x 3-1/2" x 3/8"
5/16" & 1/4" BENT PL (SEE DTL A)
DETAIL A
LOOSE LINTEL SCHEDULE
DETAIL NOTES:
1. HEIGHT OF MASONRY ABOVE LINTEL MUST
BE MINIMUM OF 1/2 THE OPENING WIDTH
2. PROVIDE ONE STEEL LINTEL FOR EACH 4"
THICKNESS OF MASONRY. (FOR EXAMPLE: 3
ANGLES FOR 12" OF WALL)
3. LINTELS SPECIFICALLY CALLED OUT ON
DRAWINGS SHALL GOVERN OVER THIS
SCHEDULE
4. ALL STEEL ANGLES SHALL BE GALVANIZED
AND SHALL HAVE SHORT LEG HORIZONTAL
(SLH)
5. L6 REQUIRES A 2" MIN AIR GAP TO FIT IN
WALL CAVITY.
BRG LEN
4"
4"
4"
4"
8"
8"
4 3/4"
5"
9"
SEE GEN NOTES FOR MAX SPACING
CONTROL JOINTS
NOTES:
A. CONTRACTOR SHALL COORD W/ ENGINEER
ANY CONDITION & LOCATIONS WERE OPENING
DIMENSIONS EXCEED THOSE SHOWN ON PLANS
B. LINTELS AND BOND BEAMS ARE REQD
ABOVE AND BELOW ANY OPENING EXCEEDING
8" IN EITHER THE HORIZONTAL OR VERITICAL
DIMENSION. THIS INCLUDES, BUT IS NOT
LIMITED TO MECHANICAL, ELECTRICAL,
PLUMBING, DOOR OR WINDOW OPENINGS.
LINTEL PER
SCHEDULE OVER
ALL OPENINGS 8"
OR WIDER
PROVIDE BOND BEAM PER
GENERAL NOTES UNDER ALL
WINDOWS (AND SIMILAR
OPENINGS)
BOND BEAM PER GENERAL
NOTES AT THE TOPS OF ALL
WALLS
CONTROL JOINTS SHALL
OFFSET HORIZONTALLY
THE LINTEL BEARING
WIDTH AT ALL WALL
OPENINGS.
#9 LADDER TYPE HORIZ
JOINT REINF @ 16"oc (TYP
UNO)
PROVIDE BOND BEAMS
WHERE FLOORS AND
ROOFS ATTACH TO THE
WALL. ALSO, PROVIDE
BOND BEAMS AT JOIST AND
BEAM BEARING
ELEVATIONS.
LADDER TYPE HORIZONTAL REINF SHALL
BE DISCONTINUOUS AT ALL CONTROL
JOINTS.
PROVIDE DWLS
INTO FTG THAT
MATCH VERT
BAR SIZE AND
SPACING
WALL VERT
REINF PER
PLAN OR
GENERAL
NOTES
HORIZONTAL REINF ACROSS CONTROL
JOINTS SHALL BE CONT AT EACH DECK
LEVEL AND AT THE TOPS OF WALLS
2' - 0" MIN. TYP.
CMU WALL
BOND BEAM
(3) VERT BARS AT
INTERSECTION. MATCH TYP
WALL REINF
BOND BEAM BARS, TYP
VERT BARS. SEE WALL
SECTION TYP
CMU WALL
BOND BEAM
(4) VERT BARS AT
INTERSECTION. MATCH TYP
WALL REINF
BOND BEAM BARS, TYP.
VERT. BARS. SEE WALL
SECTION, TYP.
2'-0" MIN
40 BAR DIA
#3 TIES, TYP.
#5 VERTICALS TYP.
PIER SECTION
PIER ELEVATION
(NTS)
NOTE:
THIS DETAIL
APPLIES FOR CMU
PIERS 24" TO 40"
ONLY.
OPENING
OPENING
24" TO 40"
A
LO
N G
H E
IG
H
T O
F O
P E
N
IN
G
#3 T
IE
S oc
0' -9
T
Y P
U N
O
3/4" DIA. ANCHOR
ROD. RODS TO
EXTEND 1/2" MIN
THRU NUTS TOP AND
BOTTOM
COLUMN, RE: PLAN
1-1/2" MIN NON-SHRINK, NON-
METALLIC GROUT
NOTES:
1. ACCOUNT FOR GROUT THICKNESS WHEN
DETERMINING BOTTOM OF BASE PLATE ELEVATION
3. ANCHOR RODS SHALL BE F1554 GR. 36 UNO
3" SQ X 1/4" PL WASHER
WITH HEAVY HEX NUT.
TACK WELD WASHER TO
ANCHOR ROD
PROVIDE OVERSIZED HOLES IN BASE PLATE AND
1/4" PL WASHER WITH HEAVY HEX NUTS ON
ANCHOR RODS. WELD WASHERS TO BASE PLATE
1" MIN ALL 4 SIDES.
BASE PLATE, RE: TYP
DETAILS
1'
1/4
BASE PLATE HOLE DIA PER AISC 360
TABLE 14-2 (1 5/16" FOR 3/4" DIA ANCHOR)
HSS COLUMN, RE: PLAN
1' - 0"
1/
2"
1/ 2"
1/
2"
1/ 2"
1 1/2"
4 1/2" 4 1/2"
1 1/2"
ANCHOR ROD (TYP)
RE: TYP DETAIL ST-001
3/4" THICK BASE PLATE
NOTES:
1. SEE DETAIL ST-001 FOR ANCHOR ROD SETTING INFORMATION.
2. SEE STRUCTURAL NOTES FOR BASE PLATE MATERIAL REQUIREMENTS.
3. WET-SETTING/FLOATING OF ANCHOR RODS IS NOT ALLOWED. ACCURATELY SET AND
SECURELY SUPPORT ANCHOR RODS DURING PLACEMENT OF CONCRETE.
NOTES:
ROOF STRUCTURE, RE: PLAN.
POST-INSTALLED ANCHOR TO ROOF STRUCTURE.
STRUT CHANNEL BRACE
ATTACHMENT TO EQUIPMENT / CABINET.
POST-INSTALLED ANCHOR INTO FLOOR SLAB, TYP
CONCRETE FLOOR SLAB, RE: PLAN. AVOID
DAMAGING REINFORCEMENT.
ANCHORAGE BRACKET PER EQUIPMENT
MANUFACTURER
EQUIPMENT / CABINET
1 2
5 6
CONTRACTOR SHALL PROVIDE
FINAL DESIGN IN COMPLIANCE
WITH SEISMIC REQUIREMENTS
OUTLINED IN THE SPECIFICATIONS
NOTES:
CONCRETE ANCHOR (TYP)
CONCRETE TOPPED METAL
DECK, RE: PLAN
STEEL ANGLE
THREADED ROD HANGER
NOTE: SUSPENDED LOADS AT EACH HANGER
SHALL NOT EXCEED 350 LBS.
1 2
(S
LA
B T
H
IC
K N
E S
S R
E F
T
O P
LA
N
SAW JOINT (SJ) CUT JUST AS
SOON AS EQUIPMENT CAN BE
PLACED ON SLAB WITHOUT DAMAGE
MESH OR REBAR CONT
SAW CUT JOINT
KEYED CONSTRUCTION JOINT (CJ)
USE BOND BREAKER
DETAIL NOTE:
THIS DETAIL MAY BE USED IN LIEU OF SAW CUT JOINT
FORMED KEY
(NO METAL KEY)
(S
LA
B T
H
IC
K N
E S
S R
E F
T
O P
LA
N
CUT MESH OR
REBAR AT JOINT
T /3 T
/4
T T
T
2 x T 2 x T
3/4" MIN
3/4" x 16" SMOOTH
DWLS @ 12" OC
CONTROL AND CONSTRUCTION JOINTS
DO OPP FIELD CUT ALTERNATE
HORIZ BARS EA FACE
1/2" DIA x 1'-0" DWLS @ 12" OC
VERTICALLY WITH GREASED SLEEVE
SEALANT
BOTH SIDES
EXPANSION JOINT
CONTROL AND CONSTRUCTION JOINTS
FORM KEYWAY AT
CONSTRUCTION
JOINTS. NOT REQ'D AT
CONTROL JOINTS
W
.1- 1/
2"
. .3/8" 3/8"
1-1/2"
. 1- 1/
2"
. .3/8" 3/8"
1-1/2"
W
FORM KEYWAY AT
CONSTRUCTION
JOINTS. NOT REQ'D AT
CONTROL JOINTS
DO OPP FIELD CUT ALTERNATE
HORIZ BARS EA FACE
W /2
W /2
.5-1/2".1"
2"
2"
1" EXPANSION
JOINT IN WALL
1-1/2"1-1/2"
1/2" DIA x 1'-0" DWLS @ 12" OC
VERTICALLY WITH GREASED SLEEVE
SEALANT
BOTH SIDES
EXPANSION JOINT
W /2
W /2
.5-1/2".1"
2"
2"
1" EXPANSION
JOINT IN WALL
1-1/2"1-1/2"
CORNERSINTERSECTIONS ENDS
DWLS TO
MATCH
HORIZ REINF
SIZE AND
SPACING (TYP)
HORIZONTAL BARS
STD HOOK
WALLS WITH 2 LAYERS OF REINF (10" OR GREATER)
WALLS WITH 1 LAYER OF REINF (< 10")
LTS
STD HOOK
LTS
LT
S
CORNER BARS.
MATCH HORIZ
REINF SIZE AND
SPACING
DWLS TO MATCH
HORIZ REINF SIZE AND
SPACING. ALT HOOK
DIRECTIONS (TYP)
LT
S
U-BARS TO MATCH SIZE AND
SPACING OF HORIZ BARS (TYP)
8" CMU LINTEL SCEHULE
CMU LINTEL
8" HIGH LINTEL UNIT W/ 2-#5 HORZ BOTTOM
16" HIGH LINTEL UNIT W/ 2-#5 HORZ BOTTOM
W8X15 BEAM W/ 1/4" X 7" BOTTOM PLATE
W8X21 BEAM W/ 1/4" X 7" BOTTOM PLATE
W16X31 BEAM W/ 1/4" X 7" BOTTOM PLATE
6'-0"
MAX OPNG
"W"
8'-0"
10'-0"
12'-0"
16'-0"
LINTEL UNIT
DETAIL NOTES:
REINF PER SCHEDULE. EXTEND
24" BEYOND EA EDGE OF
OPENING
LINTEL UNIT W/ 8" MIN BEARING
EA END
3/8" STEEL
PLATE (CONT)
1/4" 3 - 12
TYP
W8X24 (TYP)
EXISTING WALL
PROVIDE 4" MIN BEARING
AT EACH END (TYP)
NEW LINTEL,
RE: TYP DETAIL
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2 :2
P
M
1-S-010
TYPICAL DETAILS
NH/EJSPWS
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/4" = 1'-0"
RC-004 SPLICE & DEVELOPMENT SCHEDULE
3/4" = 1'-0"
RC-001B - SOG JOINTS AT COLS
1 1/2" = 1'-0"
MS-311 BRICK LINTEL SCHEDULE12
1/4" = 1'-0"
MS-001 TYP WALL REINF4
3/4" = 1'-0"
MS-002A BOND BEAM CORNERS
3/4" = 1'-0"
MS-002B BOND BEAM INTERSECTION
3/4" = 1'-0"
MS-009 PIER REINFORCING7
3/4" = 1'-0"
ST-001 - TYP ANCHOR ROD9
1 1/2" = 1'-0"
HSS COLUMN BASE PLATE
3/4" = 1'-0"
CONCEPTUAL EQUIPMENT BRACING AND ANCHORAGE DETAILS
1 1/2" = 1'-0"
CONCEPTUAL HANGER ATTACHMENT DETAIL10 3/4" = 1'-0"
RC-001A - TYP SOG CONTROL JOINTS3
1/2" = 1'-0"
RC-002 CONC WALL JOINTS13
1/2" = 1'-0"
RC-003 CONC WALL CORNERS14
3/4" = 1'-0"
MS-003 TYP LINTEL SCHEDULE
151 1/2" = 1'-0"
LINTEL AT EXISTING WALL
T ectonic Cop yright 2007
DN
1 3
E
A
[EXISTING BUILDING]
PLAN NOTES:
8" CMU WALL, FULLY GROUTED; REINF W/ #4 @ 8" O.C. RE: TYP DETAILS. CMU
WALLS ARE LATERAL LOAD RESISTING SYSTEM ELEMENTS.
24" WIDE X 36" DEEP GRADE BEAM W/ (3) #8 BARS CONTINUOUS TOP & BOTTOM
AND #4 TIES @ 12" O.C. MAX
8" CONC SLAB W/ #4 @ 12" O.C. EA WAY BOT AND #4 @ 12" O.C. X 8'-0" LONG TOP
BARS IN N-S DIRECTION OVER INTERIOR GRADE BEAMS
CONCRETE STAIRS, RE: CIVIL
6" THICK CONCRETE RAMP AND LANDING, RE: ARCH DRAWINGS. PROVIDE
JOINTS AT 8'-0" MAX
HSS 6X6X1/4 COL. RE: TYP DETAILS
LINTEL OVER DOORWAY, RE: TYP DETAILS
CURB W/ RAILING, RE: ARCH
HELICAL PIER BELOW. SIZE, LENGTH AND LOCATION TBD. CONCRETE
MICROPILES MAY BE CONSIDERED AS ALTERNATE IF SUBSURFACE BOULDERS
PREVENT INSTALLATION OF HELICAL PILES.
PROVIDE (2) #5 VERT BARS IN EACH OF THE TWO END CELLS AT DOOR OPENING
4 TYP
1-S-500
C
LR
M
IN
6'
23' - 0" 23' - 0"
2"
1-S-500
1-S-500
B
C
D
8'
8'
1-S-500
1'
2'
7' - 6" 7' - 6" 4' - 0" 4' - 0" 7' - 6" 7' - 6"
HP-B HP-B
HP-B HP-B
HP-AHP-A
HP-AHP-AHP-D
HP-D
HP-D HP-DHP-D HP-D
HP-A
HP-C HP-C
HP-D
HP-C
HP-B
HP-D
HP-C
HP-B
HP-A
HP-C
HP-C
HP-D
HP-A 10
1 3
E
A
PLAN NOTES:
6 1/2" NW COMPOSITE SLAB (3" TOPPING OVER 3 1/2" 18 GA
COMPOSITE DECK). REINF W/ #4 BARS @ 8" O.C. EA. WAY.
PROVIDE SHORING AT LONG MIDDLE SPAN. RE: GEN NOTES
COLUMN BELOW, RE: FDN PLAN
SEISMIC JOINT, RE: DETAIL 7/1-S-500
CMU WALL W/ PARAPET, RE: FOUNDATION PLAN
1-S-500
[EXISTING BUILDING]
23' - 0" 23' - 0"
W14X61 (64)
W14X61 (64)
B
C
D
2"
8'
8'
35K 35K 35K 35K
35K 35K 35K 35K
TOS = 110'-5 1/2"
TOS = 110'-5 1/2"
1-S-500
1-S-500
TYP
46' - 0"
13' - 4"
3'
13' - 4"
3'
CJ
CJ
CJ
CJ
CJ CJ
CJ
CJ
CJ
CJ
3'
13' - 4" 13' - 4"
3'
19' - 4"
19' - 4"
4 TYP
1-S-500
TYP
TYP
W18X40 (28) C=1/2"
LEFT END
VERTICAL
SHEAR
REACTION
(KIPS)
NUMBER OF SHEAR
STUDS
FOR UNIFORM
SPACING
CAMBER
RIGHT END
VERTICAL SHEAR
REACTION (KIPS)
(8) (5) (10) (5)
NUMBER OF
SHEAR
CONNECTORS FOR
POINT LOADING (IF
APPLICABLE)
DENOTES MOMENT
CONNECTION
BEAM LEGEND
DENOTES AXIAL
CONNECTION
*IF NO AXIAL LOAD CALLED OUT ASSUMED 10K
*ALL REACTIONS (M,A,V) ARE SERVICE LOADS(ASD)
15K 15K th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2 :2
P
M
1-S-100
STRUCTURAL PLANS
NH/EJSPWS
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NORTH
1/4" = 1'-0"
FOUNDATION PLAN
NORTH
1/4" = 1'-0"
ROOF PLAN
SHEET NOTES
A. REFERENCE SHEET 1-S-001 FOR STRUCTURAL GENERAL NOTES AND
1-S-010 FOR TYPICAL STRUCTURAL DETAILS. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT
SHOWN.
C. FINISH FLOOR ELEVATION = 98'-10" UNO (THIS CORRESPONDS TO EL
421 PER CIVIL DRAWINGS. VERIFY IN FIELD).
D. THE BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE 3'-0" MIN.
BELOW GRADE (UNLESS NOTED OTHERWISE), DEEPEN FOOTINGS AS
REQUIRED.
E. HELICAL PIERS ARE DENOTED AS "HP-XX". SEE GENERAL NOTES FOR
DESIGN REQUIREMENTS. DESIGN LOADS ARE AS FOLLOWS:
HP-A: 22 KIPS (C), 5 KIPS (T)
HP-B: 40 KIPS (C), 26 KIPS (T)
HP-C: 65 KIPS (C), 0 KIPS (T)
HP-D: 85 KIPS (C), 0 KIPS (T)
NOTES:
CMU WALL, RE: PLAN
BOND BEAM
CMU PILASTER
STEEL BEAM, RE: PLAN
COMPSITE DECK & SLAB, RE: PLAN
INSULATION AND WATERPROOFING
MEMBRANE, RE: ARCH
HEADED STUD
EMBEDED PLATE
#4 BENT DOWELS @ 8" O.C.
WALL REINF (CONT), RE: PLAN
SLAB REINF, RE: PLAN
3/8" x3" LONG (MIN) SCREW ANCHOR @
12" O.C. MAX
T.O. STEEL
RE: PLAN
2" GAP
NOTES:
EXISTING BUILDING
CMU WALL, RE: PLAN
FLOOR SLAB, RE: PLAN
GRADE BEAM, RE: PLAN
BOND BREAKER
PILE FOUNDATION, RE: PLAN
VOID FORM BELOW GRADE BEAMS OVER
EXISTING FOOTINGS
6' - 6" CLR (MIN)
T.O. CONC
RE: PLAN
NOTES:
CMU WALL, RE: PLAN
#5 DOWELS @ 8" O.C.
GRADE BEAM, RE: PLAN
FLOOR SLAB (REINF. NOT SHOWN),
RE: PLAN
PILE FDN, RE: PLAN
BRICK FACADE, RE: ARCH
3'
T.O. CONC
RE: PLAN
NOTES:
CMU WALL, RE: PLAN
#5 DOWELS @ 8" O.C.
GRADE BEAM, RE: PLAN & DETAIL 9/1-S-500
CONC RAMP, RE: PLAN
PILE FDN, RE: PLAN
COMPACTED GRAVEL
#4 BARS @ 12" O.C. MAX EACH WAY
CONC CURB AND RAILING, RE: ARCH
EXTEND EVERY OTHER VERT BAR INTO CURB
8"
3'
M
IN
TYP
T.O. CONC
RE: PLAN
T.O. CONC
RE: PLAN
NOTES:
EXISTING BLDG
FLASHING, RE: ARCH
FLEXIBLE SEALANT FOR SEISMIC JOINT, RE: ARCH
FORMSAVER REBAR COUPLER
BOND BEAM
WALL REINF. (CONT), RE: PLAN
#4 BENT DOWELS @ 8" O.C. MAX
ROOFING MEMBRANE AND INSULATION, RE: ARCH
3/8" x3" LONG (MIN) SCREW ANCHOR @ 12" O.C. MAX
CONC SLAB ON METAL DECK, RE: PLAN
WATERPROOFING MEMBRANE, RE: ARCH
9 10
1 1/2" 1 1/2"
1/4"
NOTES:
RIGID INSULATION, RE: ARCH
WATERPROOFING MEMBRANE, RE: ARCH
SLAB REINF, RE: PLAN
COMPOSITE SLAB ON METAL DECK, RE: PLAN
(4) 3/4" DIA A325 BOLTS
PL 1/2x12x9
HSS COL, RE: PLAN
STEEL BEAM, RE: PLAN
1 2 3 4
TYP
T.O. STEEL
RE: PLAN
NOTES:
FACADE, RE: ARCH
FLASHING, RE: ARCH
WATERPROOFING MEMBRANE, RE: ARCH
FORMSAVER REBAR COUPLER
BOND BEAM
WALL REINF. (CONT), RE: PLAN
#4 BENT DOWELS @ 8" O.C. MAX
RIGID INSULATION, RE: ARCH
3/8" x3" LONG (MIN) SCREW ANCHOR @
12" O.C. MAX
CONC SLAB ON METAL DECK, RE: PLAN
9 10
T.O. WALL
RE: ARCH
NOTES:
EXISTING BUILDING WALL
#4 BARS @ 12" O.C. MAX EA WAY
CONCRETE RAMP/LANDING, RE: PLAN
CONCRETE CURB W/ RAILING, RE: ARCH
COMPACTED GRAVEL
EXTEND EVERY OTHER VERTICAL BAR INTO
CURB AS SHOWN
8"
3'
M
IN
2'
8"
6"
T.O. CONC
RE: PLAN
8" 1' - 4"
3'
M
IN
NOTES:
CONC RAMP, RE: PLAN
COMPACTED GRAVEL
#4 BARS @ 12" O.C. MAX EACH WAY
CONCRETE CURB W/ RAILING, RE: ARCH
EXTEND EVERY OTHER VERTICAL BAR
INTO CURB AS SHOWN
RE: NOTES ON 3/S500
1' - 4"
TYP
4 TYP
RE: CIVIL
RE: CIVIL RE: CIVIL
TYP
T.O.C. VARIES
RE: CIVIL
T.O. CONC
RE: PLAN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2 :2
P
M
1-S-500
SECTIONS
NH/EJSPWS
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1 1/2" = 1'-0"
SECTION @ ROOF
3/4" = 1'-0"
INTERFACE W/ EXIST. BLDG2
3/4" = 1'-0"
SECTION AT PERIMETER GRADE BEAM9 3/4" = 1'-0"
SECTION @ EAST RAMP3
1 1/2" = 1'-0"
INTERFACE AT ROOF LEVEL
1 1/2" = 1'-0"
SECTION AT BEAM-COLUMN CONNECTION6
1 1/2" = 1'-0"
SECTION AT PARAPET8 3/4" = 1'-0"
RAMP @ EXISTING BLDG5
NTS
SECTION @ NORTH RAMP & LANDING
SHEET NOTES
A. REFERENCE SHEET S001 FOR STRUCTURAL GENERAL NOTES AND S010
FOR TYPICAL STRUCTURAL DETAILS. REVIEW NOTES & DETAILS FOR
APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
| Sheets |
| 1-S-001 - STRUCTURAL GENERAL NOTES |
| 1-S-010 - TYPICAL DETAILS |
| 1-S-100 - STRUCTURAL PLANS |
| 1-S-500 - SECTIONS |