TP09 Final Drawings 09 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Electrical.pdf
PDF 4 MB Posted
- Attached to
- Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES
- Solicitation number
- 36C25521R0103
About this file
This solicitation is for construction services to support infrastructure upgrades at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The scope of work includes constructing a new fiber backbone and server room, renovating O&IT closets, upgrading cabling and power, and providing additional data and power drops. The period of performance is estimated at 365 days from notice to proceed. Relevant agencies include the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. The principal NAICS code is 236220 for commercial and institutional building construction.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UE
OE
M/G 400A/3P
M/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
LP1
A1
LIGHT FIXTURE, CEILING MOUNTED
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
LIGHT FIXTURE, POLE MOUNTED
LIGHT FIXTURE, WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD, ARROWS INDICATE
NUMBER OF CIRCUITS, TICK MARKS INDICATE
NUMBER OF CONDUCTORS. DESIGNATIONS ARE
PANELBOARD AND CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARDA1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
OCCUPANCY SENSOR, CEILING MOUNTED
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
OVERHEAD ELECTRIC LINE
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
PLAN NOTE CALL OUT
TRANSFER SWITCH, RATINGS AS INDICATED
ATS = AUTOMATIC TRANSFER SWITCH
TX#
600AF
3P
500AT
400AS
3P
225AF
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
3P
500AT
CIRCUIT BREAKER,
RATINGS AS
INDICATED
LPS-R
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
NEMA 1
AMMETER
VOLTMETER
COMBINATION DIGITAL
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
AMMETER/VOLTMETER
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
SURGE ARRESTER
HEATER
225A 3P
NEMA 1
INDICATED
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED AS INDICATED
225A 3P
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
MTS = MANUAL TRANSFER SWITCH
EP-101
EP-101
LIGHTNING PROTECTION SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESISTANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
LIGHTING SYMBOLS
POWER EQUIPMENT SYMBOLS
WIRING DEVICE SYMBOLS
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS (TOP) 48"
ANNUNCIATOR PANELS (TOP) 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (TOP) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES, EXTERIOR (BOTTOM) 24"
RECEPTACLES, GARAGES (BOTTOM) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
X
W
V
U
T
S
R
CIRCUITING SYMBOLS
ANNOTATION STANDARD MOUNTING HEIGHTS
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
ABBREVIATIONS
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION
PANEL
BRKR BREAKER
BYP BY PASS
IC INSULATION CONTACT
ES EMERGENCY SHUNT RELAY
GENERAL NOTES
1. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE
STILL DIAGRAMMATIC IN NATURE.
2. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO
BE INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR
ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND
COMPLIANT WITH APPLICABLE CODES.
3. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION
WITH OTHER TRADES IS REQUIRED.
4. ALL UPS(S) PROVIDED IN INDIVIDUAL TELECOMMUNICATIONS
ROOMS SHALL BE BACNET COMPATIBLE AND PROVIDE THE
FOLLOWING INFORMATION:
A. UPS STATUS
B. ROOM TEMPERATURE
C. ROOM HUMIDITY
5. UPS BASIS OF DESIGN FOR EACH TELECOMMUNICATIONS
ROOM IS APC MODEL NUMBER SMT1500RM2UNC. UPS SHALL
BE PROVIDED WITH RACK MOUNTED BATTERIES SUPPLYING A
MINIMUM OF 20 MINUTES WORTH OF RUN TIME.
6. UPS BASIS OF DESIGN FOR THE SERVER ROOM IS A 100KW
APC SYMMETRA PX.
7. PROVIDE MGE REMOTE ALARM STATUS PANEL IN THE NEW
URGENT CARE WING TO MONITOR APC SYMMETRA PX.
COORDINATE EXACT MOUNTING LOCATION WITH VA PRIOR
TO BID.
8. PROVIDE AP9613 RELAY CARD FOR USE WITH APC SYMMETRA
PX AND MGE REMOTE ALARM STATUS PANEL.
9. SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION
REGARDING SCHEDULE AND PHASING REQUIREMENTS.
SCHEDULE WORK TO MINIMIZE DISRUPTION OF SERVICES.
10. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
11. PANELBOARD'S AND OTHER ELECTRICAL EQUIPMENT
REQUIRE SHUTDOWN. COORDINATE SERVICE SHUT-DOWN
FOR ALL EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
12. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH WIRING
DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
13. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE
COMPLETION OF THE PROJECT.
14. CONTRACTOR SHALL METER PANELBOARDS INDICATED IN
THE DRAWING SET FOR A MINIMUM OF 30 DAYS IN
ACCORDANCE WITH ARTICLE 220.87 OF THE 2020 NATIONAL
ELECTRICAL CODE. THE MAXIMUM METERED DEMAND PLUS
125 PERCENT SHALL NOT EXCEED THE PANELBOARD RATING.
IF CALCULATED LOAD EXCEEDS THE PANELBOARD RATING,
CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD.
POWER BUSWAY TAP WITH SINGLE BREAKER 3' DROP
CORD WITH L21-20R FOR STANDARD-DENSITY CABINETS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
00-E-001
ELECTRICAL LEGEND
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
JGW
M
IN
IM
U
M
24"MINIMUM
W
ALL
GRADE
GROUND ROD
CABLE TO GROUND
ROD CLAMP
1" SCHEDULE 40 PVC
RACEWAY
GROUNDING CONDUCTOR
GENERAL NOTE:
1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.
2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
1"
STEEL EXPANSION
ANCHOR
SECTION
1/4" DIA. HOLE
TYP OF (8)
2'-0" MIN
1/4" THICK
CU BUSS
1/2" FENDER WASHERS (EACH SIDE)
1/2" STANDARD WASHER
1/2" LOCK WASHER
1/2" NUT
1/2"DIA. x2"L. BOLT
TYP. OF (2)
3/8" DIA. HOLE
TYP. OF (6)
3" DEEP FIBERGLASS
CHANNEL SAME
LENGTH AS CU BUSS
1/4" DIA.
MOUNTING HOLES
TYP. OF (4)
[51mm]
MIN
2"
[1 m m
/8
1 1/2" TYP
2" 1" 1" m m
(1
M
A X m m
(1
M
A X
SECTION "A-A"
ELEVATION
RIGID STEEL CONDUIT
FOR SUPPORT PER N.E.C.
ART. 314
ROOF PENETRATION AND
CONDUIT SUPPORT PER
SD260533-05
RIGID STEEL CONDUIT
FOR WIRING
A
A
CAST METAL
"WHILE-IN-USE"
WP COVER(S) &
RECEPTACLE(S).
CAST METAL, 2-GANG, NEMA
3R JUNCTION BOX WITH
THREADED HUBS.
CONDUIT, TYP. MINERAL WOOL
(FIRMLY PACKED)
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, TYP.
STEEL EXPANSION
ANCHOR, TYP.
FIRESTOP SEALANT
PER SECTION 07 84 00,
FIRESTOPPING
FLOOR SLAB,
TYP.
9.52mm
(3/8") MAX
SPRING
NUT, TYP.
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
1 2
3 4
SECONDARY
BONDING BUSBAR
(BY DIV. 26)
WHERE ACCESSIBLE, BOND TGB
TO BUILDING STEEL WITHIN
COMMUNICATIONS ROOM. (BY DIV. 27)
PROVIDE SEPARATE, MINIMUM #6 AWG
STRANDED BONDING CONDUCTOR FROM
EACH RACK AND EQUIPMENT ENCLOSURE
TO TGB. (TYPICAL) (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR FROM CABLE TRAY
TO TGB. (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR OR BONDING STRAP
BETWEEN SECTIONS AND JUNCTIONS OF
CABLE TRAYS. (TYPICAL) (BY DIV. 27)
PROVIDE BONDING BUSHING AT
CONDUIT END AND MINIMUM #6 AWG
STRANDED BONDING CONDUCTOR
TO CABLE TRAY. (BY DIV. 27)
PROVIDE MINIMUM #6 AWG STRANDED
BONDING CONDUCTOR FROM CABLE
TRAY TO FIRE STOP CABLE PENETRATION
ON EACH SIDE OF WALL. (BY DIV. 27)
FLOORTR - COMMS ROOM CORRIDOR
TO ADDITIONAL TELECOM
GROUND BAR TGB
(BY DIV. 26)
MAIN BUILDING
GROUND BAR (MBG)
(BY DIV. 26)
M
IN
10'-0" MIN.
GROUNDING ELECTRODE
(SIZE PER NEC 2020 ARTICLE
250, TABLE 250.66) (BY DIV. 26)
GROUNDING ELECTRODE
(SIZE PER NEC 2020 ARTICLE
250, TABLE 250.66) (BY DIV. 26)
GROUND WELL
SERVICE ENTRANCE
EQUIPMENT
MAIN BONDING JUMPER
PHASE CONDUCTORS
GROUNDING
CONDUCTOR
NEUTRAL
CONDUCTOR
M
IN
ONE OR MORE
SUPPLEMENTAL GROUND ROD(S)
(AS REQUIRED) (BY DIV. 26)
BREAKERS
WHERE POSSIBLE, PENETRATE
BUILDING ENVELOPE JUST
ABOVE LEVEL 1 FLOOR.
MAIN ELECTRICAL ROOM
TELECOMMUNICATIONS BONDING
BACKBONE (TBB) SHALL BE 1/0
AWG MIN. EXACT SIZE TO BE
BASED OFF OF LENGTH PER
TIA-607-C. (BY DIV. 26)
LISTED EXOTHERMIC WELD,
LISTED IRREVERSIBLE
COMPRESSION-TYPE CONNECTOR
OR EQUIVALENT (BY DIV. 26)
LISTED EXOTHERMIC WELD
(BY DIV. 26)
MAXIMUM RESISTANCE TO GROUND
SHALL BE 1 OHM FOR 125VAC OR 0.8
OHM FOR 277VAC (IF NOT OTHERWISE
NOTED ELSEWHERE)
TOP OF HANDLE
6'-6" AFF MAXIMUM
4'-0" +/- AFF
FRONT VIEWSIDE VIEW
DISCONNECT SWITCH, CIRCUIT
BREAKER ENCLOSURE, OR
MOTOR CONTROLLER
CHANNEL STRUT POST BASE W
(4) 1/4" EXPANSION ANCHORS.
(TYPICAL)
PROVIDE RIGID CONDUIT TO
MECHANICAL/PLUMBING
EQUIPMENT. CONVERT TO
FLEXIBLE CONDUIT WITH BOND
WIRE FOR FINAL CONNECTION TO
EQUIPMENT.
ROOF
CHANNEL STRUT SUPPORT
FRAME.
1'-7" (MIN.)
CHANNEL STRUT
ANGLE BRACKET SUPPORT
FOR EACH SUPPORT LEG WITH
1/2" FLOOR EXPANSION
ANCHOR.
PROVIDE RIGID CONDUIT BACK
TO ELECTRICAL SOURCE.
NOTE:
1. DISCONNECT SWITCHES, CIRCUIT BREAKER ENCLOSURES, MOTOR CONTROLLERS & VARIABLE FREQUENCY DRIVES, AND CONTROL CABINETS MAY BE DIRECTLY MOUNTED TO STRUCTURAL WALLS, OR TO MECHANICAL EQUIPMENT
WHEN PERMITTED BY THE MECHANICAL EQUIPMENT MANUFACTURER AND WHERE IT DOES NOT BLOCK ACCESS OR
OPERATION OF THE EQUIPMENT. WHERE A SUITABLE STRUCTURAL WALL IS NOT AVAILABLE, PROVIDE SUPPORT FRAME AND
CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A
RIGID ASSEMBLY.
COORDINATE ALL ROOF FASTENING
AND PENETRATIONS WITH VA ROOFING
CONTRACTOR. PERFORM WORK IN A
MANNER THAT DOES NOT VOID ROOF
WARRANTEES AND IS COMPLETELY
SEALED PER ROOF TYPE AND
CONTRACTOR SPECIFICATIONS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
00-E-501
ELECTRICAL DETAILS
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
DOWNLEAD TO GROUND ROD
SCALE: NTS
GROUNDING BAR DETAIL
SCALE: NTS
RECEPTACLE ROOF MOUNTING DETAIL
SCALE: NTS
FLOOR SLAB PENETRATION DETAIL
LIGHT FIXTURE SCHEDULE
TYPE
BASIS OF DESIGN:
MANUFACTURER AND MODEL
MOUNTING
LAMP BALLAST/DRIVER
DESCRIPTION
TYPE LUMENS
COLOR
TEMP
TYPE VOLTAGE
INPUT
WATTS
INPUT
VA
F1
LITHONIA ZL1N SERIES:
ZL1N-L48-5000LM-FST-MVOLT-35K-80CRI-LBOZU-WH
CHAIN MOUNT
INTEGRAL
WHITE LED
5000 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 34 W 34 VA 4' LONG LED STRIP LIGHT.
F1B
LITHONIA ZL1N SERIES:
ZL1N-L48-5000LM-FST-E7W-MVOLT-35K-80CRI-LBOZU-WH
CHAIN MOUNT
INTEGRAL
WHITE LED
5000 lm 3500 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 34 W 34 VA
4' LONG LED STRIP LIGHT WITH 90-MINUTE BATTERY
BACKUP.
W1 LITHONIA ARC2 LED - P5 - 40K - MVOLT
WALL MOUNT AT
8'-0", UNO
INTEGRAL
WHITE LED
6500 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 51 W 57 VA LED WALLPACK
W1E LITHONIA ARC2 LED - P5 - 40K - MVOLT
WALL MOUNT AT
8'-0", UNO
INTEGRAL
WHITE LED
6500 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 51 W 57 VA
SAME AS TYPE "W1" EXCEPT WITH 90-MINUTE
BATTERY BACKUP.
W2 LITHONIA ARC2 LED - P3 - 40K - MVOLT
WALL MOUNT AT
8'-0", UNO
INTEGRAL
WHITE LED
3000 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 24 W 24 VA LED WALLPACK
W3 LITHONIA ARC2 LED - P1 - 40K - MVOLT
WALL MOUNT AT
8'-0", UNO
INTEGRAL
WHITE LED
3000 lm 4000 K
STANDARD
ELECTRONIC LED
DRIVER
120 V 11 W 11 VA LED WALLPACK
X1E
WILLIAMS EXIT/CA SERIES:
EXIT/CA-R-AF-BA-EM-SDT
UNIVERSAL
TOP/END MOUNT
LED 0 lm 0 K
STANDARD EXIT
SIGN LED DRIVER
120 V 4 W 4 VA
UNIVERSAL MOUNT, SINGLE/DOUBLE FACE EXIT SIGN
WITH RED LETTERING BRUSHED ALUMINUM
HOUSING, SELF DIAGNOSTICS AND CONNECTED TO
LIFE SAFETY BRANCH CIRCUIT.
SCALE: NTS
BUILDING GROUNDING SCHEMATIC RISER DIAGRAM
SCALE: NTS
ELECTRICAL EQUIPMENT MOUNTING DETAIL
BUS CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
LOCATIONS & SIZE OF
BUSWAYS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
B1 - LEVEL 1
0' - 0 3/4"
/6
/6
D C
HVAC DUCT
LIGHTING
CABLE TRAY
USPS-A - BUS-1
UPS-B-BUS-2
DATA CENTER FINISH FLOOR
BOTTOM OF
ROOF DECK
OI&T FLOOR
-12' - 1 1/4"
CABLE TRAY
UPS-A-BUS-2
USPS-A - BUS-1
RACK DISCONNECTS
WITH TWISTLOCK
PLUGS
RACK DISCONNECTS
WITH TWISTLOCK
PLUGS
COLUMN
COLUMN
SERVER CABINETS
ROOF
SERVER CABINETS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
00-E-502
ELECTRICAL DETAILS
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
BUS TRAPEZE MOUNTING DETAIL
3/4" = 1'-0"
SERVER ROOM ELEVATION
00-E-502
DNDN
PAVILION
PANEL (ETD)
(ETD)
EXISTING
LIGHTING (ETD)
TYPICAL
EXISTING FAN (ETD)
(TYP. OF 3)
7 (TYP. OF 4)
(ETD)
(ETD)
(ETD)
(ETD)
(ETD)
(ETD)
(ETD)
(ETD)
(ETD)
8 8
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:2
A
M
1-ESD101
BUILDING 1 PAVILION COURTYARD SITE
PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - PAVILION - ELECTRICAL SITE PLAN - DEMOLITION
ELECTRICAL KEYNOTES
6 DEMOLISH THE PANELBOARD AND FEEDER BACK TO THE
SOURCE.
7 REMOVE POLE MOUNTED RECEPTACLES AND DEMOLISH
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO
SOURCES PANEL.
8 COORDINATE WITH MECHANICAL TO DISCONNECT POWER
FOR CONDENSING UNITS AND DEMOLISH ASSOCIATED
CIRCUITS BACK TO THEIR SOURCE.
DN
ETR
Panel CRM
(ETD)
SPD (ETR)PANELBOARD
(ETR)
3 4 5
ETD
ETD
ETD
ETD
UPS (ETR)
1-EP100
OI&T
ETR ETR
ETR
ETR
ETR
ETD ETD ETD
ETD ETD ETD
ETD
ETD
ETD
ETD
ETD ETD ETD
ETD
ETDETD
ETD
ETD
ETR
72"ETR
OI&T
ELECTRICAL CLOSET
01D
CORRIDOR
GA
LOAD CENTER
(ETR)
BUILDING KEY PLAN
N
AREAS OF WORK
OI&T
OI&T
ELECTRICAL CLOSET
01D
1-E-401
PANELBOARD
(ETR)
1-E-401
1-EP100
1-EP100
F1 F1 F1
F1F1F1F1
F1
F1
100/3/90
1-SDP
14,16,18
GA3 (NEW)
GA3
D
C
F1F1
F1F1
1 2 3
E
B
UPS (ETR)
CRU-3
LOAD CENTER
(ETR)
ETD
HORIZONTAL POWER
STRIP (ETD)
VERTICAL POWER
STRIP (ETD)
ETD
OI&T
ETRETR
OI&T
GROUND BAR (NEW)
GA3
GA3
F1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:5
A
M
1-EP100
BUILDING 1 GROUND LEVEL
ELECTRICAL FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - GROUND FLOOR - ELECTRICAL POWER PLAN - DEMOLITION
ELECTRICAL KEYNOTES
3 ALL ELECTRICAL DEVICES TO REMAIN UNLESS NOTED OTHERWISE, TYPICAL.
4 ALL UN-USED UNDERFLOOR POWER DISTRIBUTION, BRANCH CIRCUITS, FEEDERS, RECEPTACLES, JUNCTION BOXES, AND CONDUIT TO BE DEMOLISHED BACK TO SOURCE, TYPICAL.
5 DEMOLISH EXISTING LIGHTS AND ASSOCIATED SWITCHES. DEMOLISHED LIGHT CIRCUITING CONDUCTORS BACK TO THE
NEAREST JUNCTION BOX, AND MAINTAIN CIRCUIT FOR FUTURE USE, TYPICAL.
25 REUSE EXISTING CIRCUIT AVAILABLE FROM DEMOLITION. REFER TO 1/1-EP100 ON THIS SHEET FOR ADDITIONAL NOTES.
27 DEMOLISH ALL CIRCUITS BACK TO NEAREST JUNCTION BOX. REMAINING CIRCUITING SHALL BE REUSED FOR NEW
LOADS.
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE (2) #12'S, (1)#12G IN 3/4"
CONDUIT AS REQUIRED TO EXTEND CONDUIT.
45 NORMAL AND EMERGENCY POWER FEEDERS UP FROM CRAWLSPACE BELOW. ROUTE UP WALL AND TIGHT TO
STRUCTURE ABOVE, CONTINUE ROUTING TO THE NEW SERVER ROOM AS SHOWN.
1/8" = 1'-0"
B1 - GROUND FLOOR - ELECTRICAL POWER PLAN - NEW
1/2" = 1'-0"
B1 - OI&T ROOM 00 - DEMOLITION
31/2" = 1'-0"
B1 - OI&T ROOM 00 - ELECTRICAL POWER PLAN
4 1/2" = 1'-0"
B1 - OI&T ROOM 00 - LIGHTING PLAN
CONTINUED
ON 2/1-E-401
1-EP101A
1-EP101A
1-EP101A
BUILDING KEY PLAN
N
AREA OF WORK
OI&T
1003A
ETD
VERTICAL POWER
STRIP (ETD)
ETD
66"
ETR
OI&T
1003A
F1
OI&T
1003A
GROUND BAR (NEW)
M
GA3
GA3
43,45,47
GA3
GA3
GA3
GA3
49,51,53
31 32
ACU-1
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:5
A
M
1-EP101A
BUILDING 1 LEVEL 1 ELECTRICAL
FLOOR PLAN - CORE
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - LEVEL 1 - ELECTRICAL FLOOR PLAN - CORE
N
1/2" = 1'-0"
B1 - OI&T ROOM 1003A - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T ROOM 1003A - LIGHTING PLAN
N
1/2" = 1'-0"
B1 - OI&T ROOM 1003A - ELECTRICAL POWER PLAN
ELECTRICAL KEYNOTES
27 DEMOLISH ALL CIRCUITS BACK TO NEAREST JUNCTION BOX. REMAINING CIRCUITING
SHALL BE REUSED FOR NEW LOADS.
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE
(2) #12'S, (1)#12G IN 3/4" CONDUIT AS REQUIRED TO EXTEND CONDUIT.
30 PROVIDE NEW NEMA L21-20R RECEPTACLE TO BE USED WITH NEW 20A RACK-MOUNTED
UPS.
31 PROVIDE NEW 20A, 208V, 3-PHASE RACK-MOUNTED UPS IN ACCORDANCE WITH
SPECIFICATIONS. TIE NEW UPS INTO EXISTING BUILDING MANAGEMENT SYSTEM WITH
CATEGORY 6A CABLING. REFER TO SHEET 00-E-001 FOR NEW UPS BASIS OF DESIGN.
32 PROVIDE TWO (2) NEW VERTICAL RACK-MOUNTED POWER STRIPS WITH A MINIMUM OF
FOURTEEN (14) 5-20R RECEPTACLES. THE POWER STRIPS SHALL BE PLUGGED INTO THE
NEW RACK-MOUNTED UPS.
33 ROUTE TO ASSOCIATED OUTDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
D H W P
101 SF
PHYS NRS
LL24
102 SF
NURSE MGR
LL23
148 SF
TRIAGE
LL12
127 SF
EXAM 2
LL14
127 SF
EXAM 3
LL15
137 SF
ISOLATION
LL17
74 SF
DECON
LL18
70 SF
BEDBUG
LL19
82 SF
VESTIBULE
LL20
73 SF
I.T.
LL39
57 SF
TOILET
LL40
169 SF
WMN EXAM
LL38
208 SF
EQUIP
LL37
181 SF
PROCEDURE
LL25
92 SF
SOILED
LL26
121 SF
CLEAN
LL27
156 SF
MEDICATION
LL30
57 SF
TOILET
LL11
57 SF
TOILET
LL10
164 SF
PSYCH
LL35
54 SF
TOILET
LL33
52 SF
TOILET
LL34
321 SF
MULTIPURPOSE
LL32
77 SF
HOLDING
LL05
63 SF
JANITOR
LL06
202 SF
SECURITY
LL04
96 SF
WHEELCHAIR
LL02
184 SF
ENTRY
LL01
636 SF
LOWER LOBBY
LL03
542 SF
WAITING
LL08
186 SF
RECEPTION
LL09
STAIR 1
ST1
CORRIDOR
LL21
CORRIDOR
LL22
CORRIDOR
LL31
CORRIDOR
LL28
148 SF
NURSE ST
LL29
768 SF
LOBBY
G01
223 SF
EXAM 4
LL16
128 SF
EXAM 1
LL13
88 SF
ELEV. EQUIP.
G02
95 SF
ELECTRIC
LL07
20 SF
SYSTEMS
LL36
PANELBOARD
CP1
139139139139140141
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:5
A
M
1-EP101B
BUILDING 1 LEVEL 1 ELECTRICAL
FLOOR PLAN - URGENT CARE
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - LEVEL 1 - ELECTRICAL FLOOR PLAN - URGENT CARE
ELECTRICAL KEYNOTES
139 PROVIDE AND INSTALL NEW MGE REMOTE ALARM STATUS PANEL, OR EQUIVALENT,
FOR USE WITH NEW UPS' LOCATED IN OI&T SERVER ROOM 52B. COORDINATE EXACT
MOUNTING LOCATION WITH VA PRIOR TO INSTALLATION.
140 PROVIDE CATEGORY CABLING FROM NEW UPS' TO REMOTE ALARM STATUS PANEL
AS REQUIRED FOR A FULLY FUNCTIONING SYSTEM.
141 PROVIDE (2)#12'S, (1)#12G IN 3/4" CONDUIT TO SPARE 20A CIRCUIT BREAKER IN
PANELBOARD CP1. COORDINATE EXACT LOCATION OF SPARE CIRCUIT BREAKERS
PRIOR TO INSTALLATION.
1-EP102
1-EP102
1-EP102
OI&T
2000A
PANEL 2A2
(ETR)
BUILDING KEY PLAN
N
AREA OF WORK
ETD
ETD
VERTICAL POWER
STRIP (ETD)
F1B
GROUND BAR (NEW)
GA3
GA3
GA3
GA3
M
OI&T
2000A
GA3
55,57,59
31 32
GA3
61,63,65
PIPES (ETR)
PIPES
(ETR)
ACU-2
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:0
A
M
1-EP102
BUILDING 1 LEVEL 2 ELECTRICAL
FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - LEVEL 2 - ELECTRICAL POWER PLAN - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T ROOM - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T ROOM - LIGHTING PLAN
N
1/2" = 1'-0"
B1 - OI&T ROOM - ELECTRICAL POWER PLAN
ELECTRICAL KEYNOTES
27 DEMOLISH ALL CIRCUITS BACK TO NEAREST JUNCTION BOX. REMAINING CIRCUITING
SHALL BE REUSED FOR NEW LOADS.
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE
(2) #12'S, (1)#12G IN 3/4" CONDUIT AS REQUIRED TO EXTEND CONDUIT.
30 PROVIDE NEW NEMA L21-20R RECEPTACLE TO BE USED WITH NEW 20A RACK-MOUNTED
UPS.
31 PROVIDE NEW 20A, 208V, 3-PHASE RACK-MOUNTED UPS IN ACCORDANCE WITH
SPECIFICATIONS. TIE NEW UPS INTO EXISTING BUILDING MANAGEMENT SYSTEM WITH
CATEGORY 6A CABLING. REFER TO SHEET 00-E-001 FOR NEW UPS BASIS OF DESIGN.
32 PROVIDE TWO (2) NEW VERTICAL RACK-MOUNTED POWER STRIPS WITH A MINIMUM OF
FOURTEEN (14) 5-20R RECEPTACLES. THE POWER STRIPS SHALL BE PLUGGED INTO THE
NEW RACK-MOUNTED UPS.
33 ROUTE TO ASSOCIATED OUTDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
137 REROUTE CONDUIT TO BE AS CLOSE AS POSSIBLE TO THE BOTTOM OF THE ELECTRICAL
BOXES ABOVE THE DOORWAY. SPLICE AS NEEDED.
1-EP103
1-EP103
1-EP103
PANEL 3A2
(ETR)
BUILDING KEY PLAN
N
AREA OF WORK
OI&T
3000A
ETD
ETD
VERTICAL POWER
STRIP (ETD)
ETR
OI&T
3000A
F1B
OI&T
3000A
GROUND BAR (NEW)
GA3
GA3
GA3
M
GA3
GA3
44,46,48
GA3
50,52,54
ETR
PIPES (ETR)
PIPES
(ETR)
ACU-3
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:0
A
M
1-EP103
BUILDING 1 LEVEL 3 ELECTRICAL
FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - LEVEL 3 - ELECTRICAL POWER PLAN - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T ROOM 3000A - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T ROOM 3000A - LIGHTING PLAN
N
1/2" = 1'-0"
B1 - OI&T ROOM 3000A - ELECTRICAL POWER PLAN
ELECTRICAL KEYNOTES
27 DEMOLISH ALL CIRCUITS BACK TO NEAREST JUNCTION BOX. REMAINING CIRCUITING
SHALL BE REUSED FOR NEW LOADS.
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE
(2) #12'S, (1)#12G IN 3/4" CONDUIT AS REQUIRED TO EXTEND CONDUIT.
30 PROVIDE NEW NEMA L21-20R RECEPTACLE TO BE USED WITH NEW 20A RACK-MOUNTED
UPS.
31 PROVIDE NEW 20A, 208V, 3-PHASE RACK-MOUNTED UPS IN ACCORDANCE WITH
SPECIFICATIONS. TIE NEW UPS INTO EXISTING BUILDING MANAGEMENT SYSTEM WITH
CATEGORY 6A CABLING. REFER TO SHEET 00-E-001 FOR NEW UPS BASIS OF DESIGN.
32 PROVIDE TWO (2) NEW VERTICAL RACK-MOUNTED POWER STRIPS WITH A MINIMUM OF
FOURTEEN (14) 5-20R RECEPTACLES. THE POWER STRIPS SHALL BE PLUGGED INTO THE
NEW RACK-MOUNTED UPS.
33 ROUTE TO ASSOCIATED OUTDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
1-EP104
1-EP104
1-EP104
OI&T
4054C
BUILDING KEY PLAN
N
AREA OF WORK
VERITICAL POWER
STRIP (ETD)
VERITICAL POWER
STRIP (ETD)
ETD
ETD
FLOOR MOUNTED
RACK (ETR)
F1B
GROUND BAR (NEW)
GA3
GA3
GA3
GA3
M
OI&T
4054C
GA3
56,58,60
GA3
62,64,66
ACU-4
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:1
A
M
1-EP104
BUILDING 1 LEVEL 4 ELECTRICAL
FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/8" = 1'-0"
B1 - LEVEL 4 - ELECTRICAL FLOOR PLAN
N
1/2" = 1'-0"
B1 - OI&T RM 4054C - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T RM 4054C - LIGHTING PLAN
N
1/2" = 1'-0"
B1 - OI&T RM 4054C - ELECTRICAL POWER PLAN
ELECTRICAL KEYNOTES
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE
(2) #12'S, (1)#12G IN 3/4" CONDUIT AS REQUIRED TO EXTEND CONDUIT.
30 PROVIDE NEW NEMA L21-20R RECEPTACLE TO BE USED WITH NEW 20A RACK-MOUNTED
UPS.
31 PROVIDE NEW 20A, 208V, 3-PHASE RACK-MOUNTED UPS IN ACCORDANCE WITH
SPECIFICATIONS. TIE NEW UPS INTO EXISTING BUILDING MANAGEMENT SYSTEM WITH
CATEGORY 6A CABLING. REFER TO SHEET 00-E-001 FOR NEW UPS BASIS OF DESIGN.
32 PROVIDE TWO (2) NEW VERTICAL RACK-MOUNTED POWER STRIPS WITH A MINIMUM OF
FOURTEEN (14) 5-20R RECEPTACLES. THE POWER STRIPS SHALL BE PLUGGED INTO THE
NEW RACK-MOUNTED UPS.
33 ROUTE TO ASSOCIATED OUTDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
1-EP105
1-EP105
1-EP105
OI&T
5A1
PANEL 5A2
(ETR)
BUILDING KEY PLAN
N
AREA OF WORK
18" (ETR)
ETD
ETD
FLOOR MOUNTED
RACK (ETR)
VERTICAL POWER
STRIP (ETD)
VERTICAL POWER
STRIP (ETD)
F1B
18" (ETR)
GROUND BAR (NEW)
M
GA3
GA3
GA3
GA3
OI&T
5A1
GA3
68,70,72
GA3
74,76,78
ACU-5
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:1
A
M
1-EP105
BUILDING 1 LEVEL 5 ELECTRICAL
FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/8" = 1'-0"
B1 - LEVEL 5 - ELECTRICAL FLOOR PLAN
N
1/2" = 1'-0"
B1 - OI&T RM 5A1 - DEMOLITION
N
1/2" = 1'-0"
B1 - OI&T RM 5A1 - LIGHTING PLAN
N
1/2" = 1'-0"
B1 - OI&T RM 5A1 - ELECTRICAL POWER PLAN
ELECTRICAL KEYNOTES
27 DEMOLISH ALL CIRCUITS BACK TO NEAREST JUNCTION BOX. REMAINING CIRCUITING
SHALL BE REUSED FOR NEW LOADS.
28 TIE NEW LIGHT FIXTURE INTO NEAREST CRITICAL BRANCH LIGHTING CIRCUIT. PROVIDE
(2) #12'S, (1)#12G IN 3/4" CONDUIT AS REQUIRED TO EXTEND CONDUIT.
33 ROUTE TO ASSOCIATED OUTDOOR UNIT PER MANUFACTURER'S RECOMMENDATIONS.
CU-3 CU-2 CU-1
30/2/NF/3R
30/2/NF/3R
30/2/NF/3R
GA3
9,11
GA3
13,15
GA3
17,19
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:1
A
M
1-EP106
BUILDING 1 LEVEL 6 ELECTRICAL
FLOOR PLAN
MIJ
BEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
1/8" = 1'-0"
B1 - LEVEL 6/ ROOF - ELECTRICAL POWER PLAN - NEW
ELECTRICAL KEYNOTES
142 PROVIDE UNISTRUT RACK(S) FOR MOUNTING OF DISCONNECT
SWITCHES. DO NOT MOUNT DISCONNECTS TO THE EQUIPMENT.
CONTACT VA ROOFING CONTRACTOR TO OBTAIN ROOF WARRANTY
REQUIREMENTS RELATED TO RACK INSTALLATION.
OI&T SERVER ROOM
52B
SERVER CABINETSCRU-1
ACCU-1
ACCU-3
UPS-A (NEW)
1-SDP (NEW)
GS1 (NEW)
GROUND BAR (NEW)
ATS-5
(NEW)
UPS-B (NEW)
CRU-2
GS1
1,3,5
1-SDP
ACCU-2
GS2 (NEW)
GS2
7,9,11
400/3/NF/3R
400/3/NF/3R
1-SDP
2,4,6
1-SDP
8,10,12
400/3/225
400/3/225
UPS-B-BUS-2
UPS-B-BUS-1
UPS-A-BUS-2
UPS-A-BUS-1
GS1
7,9,11
GS2
1,3,5
1-SDP
20,22,24
1-SDP
19,21,23
1-SDP
13,15,17
1-SDP
1-SDP
1-SDP
1-SDP
1-SDP
00-E-501
(TYPICAL)
(TYPICAL)
(TYPICAL)
00-E-502
SERVER CABINETS
D
C
CONTINUED ON
2/1-EP-100
400/3/NF/3R
1 2 3
E
B
OI&T SERVER ROOM
52B
SERVER CABINETS
CRU-1
F1F1
1-SDP (NEW)
GS1 (NEW)
GROUND
BAR (NEW)
ATS-5
(NEW)
UPS-A (NEW)
UPS-B (NEW)
F1 F1F1
F1 F1 F1 F1
F1
F1 F1 F1 F1
F1
F1
CRU-2
W2
W1 W1 W1E W1E
1-SDP
1-SDP
GS2 (NEW)
ACCU-2
ACCU-1
ACCU-3
SERVER CABINETS
W3
W3
W3
00-E-502
F1
D
C
1 2 3
E
B
W2
W2
X1E
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th…