TP09 Final Drawings 06 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Fire Protection.pdf

PDF 2 MB Posted

Attached to
Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES Federal contract opportunity
Solicitation number
36C25521R0103
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This solicitation is for infrastructure upgrade services at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The contractor will provide construction documents, project management, and construction services to upgrade the facility's fiber backbone, server room, O&IT closets, HVAC systems, electrical and data cabling, and additional power and drops for the new EHRM system. Key aspects of the work include renovating spaces for additional cooling and controls, upgrading patch panels and cabling to CAT6A, and providing supplemental power and user equipment locations. The period of performance is approximately 365 calendar days after notice to proceed. The primary NAICS code is 236220 and FSC Y1DZ. The contracting agency is the Department of Veterans Affairs Veterans Health Administration.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES, newest first.
File Type Posted
S02 36C25521R0103 0008.pdf PDF
Additional RFI (EHRM).pdf PDF
Wage Determination (9-3-2021).pdf PDF
S02 36C25521R0103 0007.pdf PDF
36C25521R0103 0006.pdf PDF
020-2333 EHRM Geotech Report 111020.pdf PDF
36C25521R0103 0005.pdf PDF
S06 36C25521R0103 0003.pdf PDF
S06 36C25521R0103 0002.pdf PDF
S06 36C25521R0103 0004.pdf PDF
657A4-20-700 EHRM Infrastructure Upgrades 36C25521R0103 0001.pdf PDF
SIGN IN ROSTER (657A4-20-700) EHRM INFRASTRUCTURE UPGRADES.pdf PDF
TP09 Final Specs Vol-01.pdf PDF
00 VA OEHRM Site Infrastructure Requirements - 2 Signed.pdf PDF
S02 36C25521R0103_2.pdf PDF
EHRM NCO15 Price Estimate Template V1.2.url.xlsx XLSX spreadsheet
TP09 Final Drawings 08 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Mechanical.pdf PDF
TP09 Final Drawings 10 657A4-20-700 Resubmitted SS 100 percent CD Drawings Technology.pdf PDF
TP09 Final Drawings 09 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Electrical.pdf PDF
TP09 Final Drawings 01 657A4-20-700 Resubmitted SS 100 percent CD Drawings-General.pdf PDF
TP09 Final Drawings 04 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Structural.pdf PDF
TP01 Specs Vol-01.pdf PDF
TP01 Specs Vol-02.pdf PDF
TP09 Final Drawings 03 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Civil.pdf PDF
TP09 Final Drawings 07 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Plumbing.pdf PDF
TP09 Final Drawings 05 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Architectural.pdf PDF
TP09 Final Drawings 02 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Abatement.pdf PDF
36C25521R0103.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FACU

SPD

FIRST FLOOR

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL

CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND

TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.

THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION

AFTER SUCCESSFUL COMPLETION OF THE PROJECT.

2 3

SECOND FLOOR

s

THIRD FLOOR

s

FOURTH FLOOR

s

FIFTH FLOOR

s

GROUND FLOOR

S

WF VS

AIM AIMAIM

ASD

s

S AOM

AHU

AOM

FACU

EXISTING FIRE ALARM/MASS NOTIFICATION

CONTROL UNIT

FIRE ALARM LEGEND

SPD EXISTING SURGE PROTECTIVE DEVICE

s EXISTING SMOKE DETECTOR - SPOT TYPE

WF NEW WATERFLOW DEVICE

OUT OF SCOPE AREA

VS NEW VALVE SUPERVISORY SWITCH

AIM NEW ADDRESSABLE INPUT MODULE

1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL

BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE

VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,

NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

CALCULATIONS AND SHOP DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH

RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING

MANUFACTURER AND MODEL OR BE COMPATIBLE WITH

THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL

BE WHITE FINISH TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH OWNER

PRIOR TO COMMENCING WORK TO PREVENT

INTERRUPTION OF SERVICE.

5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL

AREAS OF RENOVATION SHALL BE PROVED WITH NEW

SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE

INSTALLED IN ACCORDANCE WITH NFPA 72 AND

COORDINATED WITH OTHER TRADES TO ENSURE

COMPLIANT INSTALLATION.

6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR

DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER

INPUTS SHALL MATCH EXISTING PANEL.

FIRE ALARM GENERAL NOTES

S

ASD

NEW AIR SAMPLING SMOKE DETECTOR

ASPIRATING SMOKE DETECTION SYSTEM PANELASD

S

NEW SMOKE DETECTOR - DUCT TYPE

AOM NEW ADDRESSABLE OUTPUT MODULE

AIR HANDLING UNIT CONTROLLERAHU

SYMBOL MODIFIERS

ncd nW

CANDELA RATING

WATT TAP

5 WATERFLOW/PRESSURE SWITCH X X X X X X X X 5

9 ASPIRATING SMOKE DETECTOR (0.07% OBS./FT.) - ACTION X X X 9

17 ANY OTHER SYSTEM TROUBLE X X X 17

7 CONTROL VALVE SUPERVISORY SWITCH X X X 7

8 ASPIRATING SMOKE DETECTOR (0.05% OBS./FT.) - ALERT X X X 8

SUPERVISORY CONDITIONS A B C D E F G H I J K L M

6 SMOKE DETECTOR - DUCT TYPE X X X X 6

A B C D E F G H I J K L M

X PERFORM OPERATION/REPORT DEVICE STATUS

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E T

E M

P O

R A

L

A L E

R T

T O

N E

A N

D P

R E

-R E

C O

R D

E D

F

IR

E

V

A C

U A

T

IO

N M

E S

S A

G E

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E S

T R

O B

E S

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E P

R E

-R E

C O

R D

E D

S T

A F

F A

L E

R T

M E

S S

A G

E T

H R

O U

G H

O U

T T

H

B

U

IL

D

IN

G

A U

X

IL

IA

R

Y F

U N

C T

IO

N

S

S H

U T

D O

W N

A S

S O

C

IA

T E

D A

IR

H

A N

D L

IN

G U

N

IT

A C

T

IV

A T

E E

L E

C T

R

IC

A L D

IS

C

O N

N E

C T

O F

E Q

U

IP

M E

N T

I N

I T

E S

P A

C E

S

C L O

S E

S M

O K

E B

A R

R

IE

R D

O O

R S

O N

A S

S O

C

IA

T E

D F

L O

O R

ALARM CONDITIONS A B C D E F G H I J K L M

1 MANUAL ALARM PULL STATION X X X X X X X X 1

2 SMOKE DETECTOR - SPOT TYPE X X X X X X X 2

3 ASPIRATING SMOKE DETECTOR (0.12% OBS./FT.) - FIRE1 X X X X X X X 3

4 ASPIRATING SMOKE DETECTOR (1% OBS./FT.) - FIRE2 X X X X X X X 4

TROUBLE CONDITIONS A B C D E F G H I J K L M

10 AC POWER FAILURE X X X 10

11 LOW BATTERY X X X 11

12 OPEN CIRCUIT X X X 12

13 GROUND FAULT X X X 13

14 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 14

15 REMOTE POWER SUPPLY COMMON TROUBLE X X X 15

16 ASPIRATING SMOKE DETECTION SYSTEM COMMON TROUBLE X X X 16

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:5

A

M

1-FA-001

BLDG 1 FIRE ALARM / MASS

NOTIFICATION GENERAL NOTES

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

NO SCALE

BLDG 1 - FIRE ALARM RISER DIAGRAM1NO SCALE

BLDG 1 - FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 1. NOT ALL EXISTING INPUTS AND OUTPUTS ARE

REPRESENTED ON THIS MATRIX. PLEASE REFER TO THE EXISTING FIRE ALARM PANEL LOCATED IN BUILDING 1 FOR ALL OF THE INPUTS AND OUTPUTS.

2. ELECTRICAL DISCONNECT SHALL ONLY BE INITIATED FOR ALARM CONDITIONS DETECTED IN THE ITE SPACES.

1-FA-102

1-FA-102

1-FA-102

1-FA-102

1-FA-102

1-FA-102

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:5

A

M

1-FA-101

BLDG 1 OVERALL FIRE ALARM PLANS

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - FIRST FLOOR2

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - SECOND FLOOR3

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - THIRD FLOOR4

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - FOURTH FLOOR5

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - FIFTH FLOOR6

N

1/32" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - GROUND FLOOR1

1003A

OI&T

1003A s

2000A

OI&T

2000A s

3000A

OI&T

3000A s 4054C

OI&T

4054C s

5A1

OI&T

5A1 s

52B

OI&T

SERVER

ROOM

52B s

F A

C U

OI&T

S

A S

D1

S

S

S

CRU-1

S

CRU-2

F

WF VS

0.25W

30cd

0.25W

30cd

S

CRU-3

.2

W c d

AOM ITE SPACE ELECTRICAL

DISCONNECT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:5

A

M

1-FA-102

BLDG 1 ENLARGED FIRE ALARM PLANS

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

3/4" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - ROOM 1003A2

N

3/4" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - ROOM 2000A3

N

3/4" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - ROOM 3000A4

N

3/4" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - ROOM 4054C5

N

3/4" = 1'-0"

BLDG 1 - FIRE ALARM PLAN - ROOM 5A16

N

1/8" = 1'-0"

BLDG 1 - GROUND FLOOR - ROOMS OI&T 52 AND OI&T 52B1

SHEET KEYNOTES

MARK KEYNOTE

1 AN ASPIRATING SMOKE DETECTION SYSTEM SHALL

BE INSTALLED IN THE SERVER ROOM TO PRVOIDE

EARLY WARNING OF A POTENTIAL FIRE EVENT.

SAMPLING PORTS FOR THE ASPIRATING SMOKE

DETECTION SHALL BE INSTALLED AND LOCATED IN

ACCORDANCE WITH NFPA 72. ASPIRATING SMOKE

DETECTION CONTROL UNIT SHALL BE UL LISTED

AND FM APPROVED. THE SYSTEM SHALL MEET THE

REQUIREMENTS OF NFPA 75. REFER TO

INPUT/OUTPUT MATRIX ON SHEET 1-FA-001 FOR

SENSITIVITY SETTINGS. SAMPLING PORTS ARE

ONLY TO BE INSTALLED AT THE CEILING. THIS

SPACE DOES NOT HAVE A RAISED FLOOR.

2 ASPIRATING SMOKE DETECTION CONTROL PANEL

SHALL BE POWERED FROM THE EXISTING FIRE

ALARM CONTROL UNIT OR BY A REMOTE POWER

SUPPLY.

3 INSTALLED UNDER RAISED FLOOR.

DN

DN

1-FX-102

1-FX-102

1-FX-102

1-FX-102

1-FX-102

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

1-FX-102

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

1-FX-101

BLDG 1 OVERALL FIRE SUPPRESSION

HAZARD CLASSIFICATION PLANS

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - FIRST FLOOR2

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - SECOND FLOOR3

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - THIRD FLOOR4

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - FOURTH FLOOR5

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - FIFTH FLOOR6

N

1/32" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - GROUND FLOOR1

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL AND NFPA 13-2019.

2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA

REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC

EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND

SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE

FUSIBLE-LINK TYPE.

3. WHERE FEASABLE, ALL TELECOMMUNICATIONS AND

SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE

EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH

APPLICABLE CODES AND STANDARDS. WHERE EXISTING

CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”

CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,

BUILT-IN TROUGHS AND/OR LEAK DETECTION IN

ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO

PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY

WET-PIPE SPRINKLER LEAKAGE.

FIRE SUPPRESSION GENERAL NOTES:

1003A

1003A

2000A

OI&T

2000A

3000A

OI&T

3000A

4054C

OI&T

4054C

5A1

OI&T

5A1

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

52B

OI&T

SERVER

ROOM

52B

OI&T

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

1-FX-102

BLDG 1 ENLARGED FIRE SUPPRESSION

HAZARD CLASSIFICATION PLANS

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

3/4" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 1003A2

N

3/4" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 2000A3

N

3/4" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 3000A4

N

3/4" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 4054C5

N

3/4" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 5A16

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL AND NFPA 13-2019.

2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA

REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC

EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND

SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE

FUSIBLE-LINK TYPE.

3. WHERE FEASABLE, ALL TELECOMMUNICATIONS AND

SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE

EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH

APPLICABLE CODES AND STANDARDS. WHERE EXISTING

CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”

CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,

BUILT-IN TROUGHS AND/OR LEAK DETECTION IN

ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO

PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY

WET-PIPE SPRINKLER LEAKAGE.

FIRE SUPPRESSION GENERAL NOTES:

N

1/8" = 1'-0"

BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOMS OI&T 52 AND OI&T 52B1

SHEET KEYNOTES

MARK KEYNOTE

1 CONTRACTOR TO TIE INTO EXISTING FIRE

SPRINKLER SYSTEM PIPING IN OI&T 52 AND LOCATE

ZONE CONTROL VALVE ABOVE LAY-IN CEILING.

COORDINATE LOCATION WITH OTHER DISCIPLINES.

2 THIS SPACE HAS EXISTING FIRE SPRINKLER

PROTECTION, CONTRACTOR TO REPLACE

NON-COMPLIANT SPRINKLERS WITH STANDARD

RESPONSE, FUSIBLE-LINK SPRINKLERS.

BASEMENT

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM

DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT

ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF

DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT

INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE

GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION

OF THE PROJECT.

s

WF VS

AIM AIM

8 ANY OTHER SYSTEM TROUBLE X X X 8

A B C D E F G H I

X PERFORM OPERATION/REPORT DEVICE STATUS

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E A

U D

IB

L E

N O

T

IF

IC

A

T

IO

N D

E V

IC

E

S T

H R

O U

G H

O U

T B

U

IL

D

IN

G

A C

T

IV

A T

E V

IS

U

A L N

O T

IF

IC

A T

IO

N

D E

V

IC

E S

T H

R O

U G

H O

U T

B U

IL

D

IN

G

ALARM CONDITIONS A B C D E F G H I

1 SMOKE DETECTOR - SPOT TYPE X X X X X 1

TROUBLE CONDITIONS A B C D E F G H I

2 AC POWER FAILURE X X X 2

3 LOW BATTERY X X X 3

4 OPEN CIRCUIT X X X 4

5 GROUND FAULT X X X 5

6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6

7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7

FACU

EXISTING FIRE ALARM/MASS NOTIFICATION

CONTROL UNIT

FIRE ALARM LEGEND

SPD EXISTING SURGE PROTECTIVE DEVICE

s EXISTING SMOKE DETECTOR - SPOT TYPE

WF EXISTING WATERFLOW DEVICE

OUT OF SCOPE AREA

VS EXISTING VALVE SUPERVISORY SWITCH

AIM EXISTING ADDRESSABLE INPUT MODULE

1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL

BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE

VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,

NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

CALCULATIONS AND SHOP DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH

RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING

MANUFACTURER AND MODEL OR BE COMPATIBLE WITH

THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL

BE WHITE FINISH TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH OWNER

PRIOR TO COMMENCING WORK TO PREVENT

INTERRUPTION OF SERVICE.

5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL

AREAS OF RENOVATION SHALL BE PROVED WITH NEW

SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE

INSTALLED IN ACCORDANCE WITH NFPA 72 AND

COORDINATED WITH OTHER TRADES TO ENSURE

COMPLIANT INSTALLATION.

6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR

DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER

INPUTS SHALL MATCH EXISTING PANEL.

FIRE ALARM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

5-FA-001

BLDG 5 FIRE ALARM GENERAL NOTES,

DIAGRAMS, AND LEGEND

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

NO SCALE

BLDG 5 - FIRE ALARM RISER DIAGRAM1NO SCALE

FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 5. NOT

ALL EXISTING INPUTS AND OUTPUTS ARE REPRESENTED ON THIS MATRIX.

5-FA-101

WF VS

OI&T

s

FACU

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

5-FA-101

BLDG 5 FIRE ALARM FLOOR PLAN -

BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 5 - FIRE ALARM PLAN - BASEMENT1

N

3/4" = 1'-0"

BLDG 5 - FIRE ALARM PLAN - ROOM 042

5-FX-101

OI&T

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

EXISTING FIRE SUPPRESSION RISER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

5-FX-101

BLDG 5 FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN - BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 5 - HAZARD CLASSIFICATION PLAN - BASEMENT1

N

3/4" = 1'-0"

BLDG 5 - HAZARD CLASSIFICATION PLAN - ROOM 042

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL AND NFPA 13-2019.

2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA

REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC

EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND

SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE

FUSIBLE-LINK TYPE.

3. WHERE FEASIBLE, ALL TELECOMMUNICATIONS AND

SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE

EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH

APPLICABLE CODES AND STANDARDS. WHERE EXISTING

CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”

CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,

BUILT-IN TROUGHS AND/OR LEAK DETECTION IN

ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO

PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY

WET-PIPE SPRINKLER LEAKAGE.

FIRE SUPPRESSION GENERAL NOTES:

SHEET KEYNOTES

MARK KEYNOTE

1 THIS SPACE HAS EXISTING FIRE SPRINKLER

PROTECTION, CONTRACTOR TO REPLACE

NON-COMPLIANT SPRINKLERS WITH STANDARD

RESPONSE, FUSIBLE-LINK SPRINKLERS.

EXISTING FIRE ALARM/MASS NOTIFICATION

CONTROL UNIT

FIRE ALARM LEGEND

SPD EXISTING SURGE PROTECTIVE DEVICE

s EXISTING SMOKE DETECTOR - SPOT TYPE

OUT OF SCOPE AREA

1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL

BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE

VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,

NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

CALCULATIONS AND SHOP DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH

RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING

MANUFACTURER AND MODEL OR BE COMPATIBLE WITH

THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL

BE WHITE FINISH TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH OWNER

PRIOR TO COMMENCING WORK TO PREVENT

INTERRUPTION OF SERVICE.

5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL

AREAS OF RENOVATION SHALL BE PROVED WITH NEW

SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE

INSTALLED IN ACCORDANCE WITH NFPA 72 AND

COORDINATED WITH OTHER TRADES TO ENSURE

COMPLIANT INSTALLATION.

6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR

DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER

INPUTS SHALL MATCH EXISTING PANEL.

FIRE ALARM GENERAL NOTES

FACU

SPD

BASEMENT

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM

DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT

ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF

DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT

INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE

GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION

OF THE PROJECT.

s

8 ANY OTHER SYSTEM TROUBLE X X X 8

A B C D E F G H I

X PERFORM OPERATION/REPORT DEVICE STATUS

SYSTEM OUTPUTS

SYSTEM INPUTS

F

A C

U A

N N

U N

C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E A

U D

IB

L E

N O

T

IF

IC

A

T

IO

N D

E V

IC

E

S T

H R

O U

G H

O U

T B

U

IL

D

IN

G

A C

T

IV

A T

E V

IS

U

A L N

O T

IF

IC

A T

IO

N

D E

V

IC

E S

T H

R O

U G

H O

U T

B U

IL

D

IN

G

ALARM CONDITIONS A B C D E F G H I

1 SMOKE DETECTOR - SPOT TYPE X X X X X 1

TROUBLE CONDITIONS A B C D E F G H I

2 AC POWER FAILURE X X X 2

3 LOW BATTERY X X X 3

4 OPEN CIRCUIT X X X 4

5 GROUND FAULT X X X 5

6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6

7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

6-FA-001

BLDG 6 FIRE ALARM GENERAL NOTES,

DIAGRAMS, AND LEGEND

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

NO SCALE

BLDG 6 - FIRE ALARM RISER DIAGRAM1NO SCALE

FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 6. NOT

6-FA-101

MECHANICAL

ROOM

s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

6-FA-101

BLDG 6 FIRE ALARM FLOOR PLAN -

BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 6 - FIRE ALARM PLAN - BASEMENT1

N

BLDG 6 - FIRE ALARM PLAN - ROOM 032

MECHANICAL

ROOM

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

6-FX-101

BLDG 6 FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN - BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 6 - HAZARD CLASSIFICATION PLAN - BASEMENT1

SHEET KEYNOTES

MARK KEYNOTE

1 NO EXISTING FIRE SPRINKLER SYSTEM. NO

MODIFICATION WILL BE MADE TO INCLUDE SPRINKLER

PROTECTION FOR THIS SCOPE OF WORK AREA.

EXISTING FIRE ALARM/MASS NOTIFICATION

CONTROL UNIT

FIRE ALARM LEGEND

SPD EXISTING SURGE PROTECTIVE DEVICE

s EXISTING SMOKE DETECTOR - SPOT TYPE

OUT OF SCOPE AREA

1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL

BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE

VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,

NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

CALCULATIONS AND SHOP DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH

RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING

MANUFACTURER AND MODEL OR BE COMPATIBLE WITH

THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL

BE WHITE FINISH TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH OWNER

PRIOR TO COMMENCING WORK TO PREVENT

INTERRUPTION OF SERVICE.

5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL

AREAS OF RENOVATION SHALL BE PROVED WITH NEW

SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE

INSTALLED IN ACCORDANCE WITH NFPA 72 AND

COORDINATED WITH OTHER TRADES TO ENSURE

COMPLIANT INSTALLATION.

6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR

DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER

INPUTS SHALL MATCH EXISTING PANEL.

FIRE ALARM GENERAL NOTES

FACU

SPD

BASEMENT

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM

DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT

ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF

DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT

INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE

GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION

OF THE PROJECT.

s

8 ANY OTHER SYSTEM TROUBLE X X X 8

A B C D E F G H I

X PERFORM OPERATION/REPORT DEVICE STATUS

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E A

U D

IB

L E

N O

T

IF

IC

A

T

IO

N D

E V

IC

E

S T

H R

O U

G H

O U

T B

U

IL

D

IN

G

A C

T

IV

A T

E V

IS

U

A L N

O T

IF

IC

A T

IO

N

D E

V

IC

E S

T H

R O

U G

H O

U T

B U

IL

D

IN

G

ALARM CONDITIONS A B C D E F G H I

1 SMOKE DETECTOR - SPOT TYPE X X X X X 1

TROUBLE CONDITIONS A B C D E F G H I

2 AC POWER FAILURE X X X 2

3 LOW BATTERY X X X 3

4 OPEN CIRCUIT X X X 4

5 GROUND FAULT X X X 5

6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6

7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

7-FA-001

BLDG 7 FIRE ALARM GENERAL NOTES,

DIAGRAMS, AND LEGEND

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

NO SCALE

BLDG 7 - FIRE ALARM RISER DIAGRAM1NO SCALE

FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 7. NOT

OI&T TR

7-FA-101

OI&T TR

212 s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

7-FA-101

BLDG 7 FIRE ALARM FLOOR PLAN -

BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 7 - FIRE ALARM PLAN - BASEMENT1

N

BLDG 7 - FIRE ALARM PLAN - ROOM 2122

OI&T TR

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

7-FX-101

BLDG 7 FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN - BASEMENT

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 7 - HAZARD CLASSIFICATION PLAN - BASEMENT1

SHEET KEYNOTES

MARK KEYNOTE

1 NO EXISTING FIRE SPRINKLER SYSTEM. NO

MODIFICATION WILL BE MADE TO INCLUDE SPRINKLER

PROTECTION FOR THIS SCOPE OF WORK AREA.

LEVEL 1

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM

DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT

ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF

DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT

INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE

GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION

OF THE PROJECT.

s

WF VS

AIM AIM

8 ANY OTHER SYSTEM TROUBLE X X X 8

A B C D E F G H I

X PERFORM OPERATION/REPORT DEVICE STATUS

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E A

U D

IB

L E

N O

T

IF

IC

A

T

IO

N D

E V

IC

E

S T

H R

O U

G H

O U

T B

U

IL

D

IN

G

A C

T

IV

A T

E V

IS

U

A L N

O T

IF

IC

A T

IO

N

D E

V

IC

E S

T H

R O

U G

H O

U T

B U

IL

D

IN

G

ALARM CONDITIONS A B C D E F G H I

1 SMOKE DETECTOR - SPOT TYPE X X X X X 1

TROUBLE CONDITIONS A B C D E F G H I

2 AC POWER FAILURE X X X 2

3 LOW BATTERY X X X 3

4 OPEN CIRCUIT X X X 4

5 GROUND FAULT X X X 5

6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6

7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7

FACU

EXISTING FIRE ALARM/MASS NOTIFICATION

CONTROL UNIT

FIRE ALARM LEGEND

SPD EXISTING SURGE PROTECTIVE DEVICE

s EXISTING SMOKE DETECTOR - SPOT TYPE

WF EXISTING WATERFLOW DEVICE

OUT OF SCOPE AREA

VS EXISTING VALVE SUPERVISORY SWITCH

AIM EXISTING ADDRESSABLE INPUT MODULE

1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL

BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE

VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,

NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

CALCULATIONS AND SHOP DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH

RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING

MANUFACTURER AND MODEL OR BE COMPATIBLE WITH

THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL

BE WHITE FINISH TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH OWNER

PRIOR TO COMMENCING WORK TO PREVENT

INTERRUPTION OF SERVICE.

5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL

AREAS OF RENOVATION SHALL BE PROVED WITH NEW

SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE

INSTALLED IN ACCORDANCE WITH NFPA 72 AND

COORDINATED WITH OTHER TRADES TO ENSURE

COMPLIANT INSTALLATION.

6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR

DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER

INPUTS SHALL MATCH EXISTING PANEL.

FIRE ALARM GENERAL NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

8-FA-001

BLDG 8 FIRE ALARM GENERAL NOTES,

DIAGRAMS, AND LEGEND

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

NO SCALE

BLDG 8 - FIRE ALARM RISER DIAGRAM1NO SCALE

FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 8. NOT

8-FA-101

WF

VS

1006A

OI&T TR

1006A s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

8-FA-101

BLDG 8 FIRE ALARM FLOOR PLAN -

FIRST FLOOR

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 8 - FIRE ALARM PLAN - FIRST FLOOR1

N

BLDG 8 - FIRE ALARM PLAN - ROOM 1006A2

8-FX-101

1006A

OI&T TR

1006A

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

EXISTING FIRE SUPPRESSION RISER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

F U

L L

Y S

P R

IN

K

L E

R E

D

/2

/2

:5

:0

A

M

8-FX-101

BLDG 8 FIRE SUPPRESSION HAZARD

CLASSIFICATION PLAN - FIRST FLOOR

SAB

DBN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

N

1/4" = 1'-0"

BLDG 8 - HAZARD CLASSIFICATION PLAN - FIRST FLOOR1

N

3/4" = 1'-0"

BLDG 8 - HAZARD CLASSIFICATION PLAN - ROOM 1006A2

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL AND NFPA 13-2019.

2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA

REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC

EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND

SWITCH ROOMS) SHALL BE NEW…