This solicitation is for infrastructure upgrade services at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The contractor will provide construction documents, project management, and construction services to upgrade the facility's fiber backbone, server room, O&IT closets, HVAC systems, electrical and data cabling, and additional power and drops for the new EHRM system. Key aspects of the work include renovating spaces for additional cooling and controls, upgrading patch panels and cabling to CAT6A, and providing supplemental power and user equipment locations. The period of performance is approximately 365 calendar days after notice to proceed. The primary NAICS code is 236220 and FSC Y1DZ. The contracting agency is the Department of Veterans Affairs Veterans Health Administration.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FACU
SPD
FIRST FLOOR
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL
CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND
TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.
THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION
AFTER SUCCESSFUL COMPLETION OF THE PROJECT.
2 3
SECOND FLOOR
s
THIRD FLOOR
s
FOURTH FLOOR
s
FIFTH FLOOR
s
GROUND FLOOR
S
WF VS
AIM AIMAIM
ASD
s
S AOM
AHU
AOM
FACU
EXISTING FIRE ALARM/MASS NOTIFICATION
CONTROL UNIT
FIRE ALARM LEGEND
SPD EXISTING SURGE PROTECTIVE DEVICE
s EXISTING SMOKE DETECTOR - SPOT TYPE
WF NEW WATERFLOW DEVICE
OUT OF SCOPE AREA
VS NEW VALVE SUPERVISORY SWITCH
AIM NEW ADDRESSABLE INPUT MODULE
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL
BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,
NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM
CONTRACTOR IS RESPONSIBLE FOR DEVELOPING
CALCULATIONS AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH
RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING
MANUFACTURER AND MODEL OR BE COMPATIBLE WITH
THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL
BE WHITE FINISH TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH OWNER
PRIOR TO COMMENCING WORK TO PREVENT
INTERRUPTION OF SERVICE.
5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL
AREAS OF RENOVATION SHALL BE PROVED WITH NEW
SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE
INSTALLED IN ACCORDANCE WITH NFPA 72 AND
COORDINATED WITH OTHER TRADES TO ENSURE
COMPLIANT INSTALLATION.
6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR
DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER
INPUTS SHALL MATCH EXISTING PANEL.
FIRE ALARM GENERAL NOTES
S
ASD
NEW AIR SAMPLING SMOKE DETECTOR
ASPIRATING SMOKE DETECTION SYSTEM PANELASD
S
NEW SMOKE DETECTOR - DUCT TYPE
AOM NEW ADDRESSABLE OUTPUT MODULE
AIR HANDLING UNIT CONTROLLERAHU
SYMBOL MODIFIERS
ncd nW
CANDELA RATING
WATT TAP
5 WATERFLOW/PRESSURE SWITCH X X X X X X X X 5
9 ASPIRATING SMOKE DETECTOR (0.07% OBS./FT.) - ACTION X X X 9
17 ANY OTHER SYSTEM TROUBLE X X X 17
7 CONTROL VALVE SUPERVISORY SWITCH X X X 7
8 ASPIRATING SMOKE DETECTOR (0.05% OBS./FT.) - ALERT X X X 8
SUPERVISORY CONDITIONS A B C D E F G H I J K L M
6 SMOKE DETECTOR - DUCT TYPE X X X X 6
A B C D E F G H I J K L M
X PERFORM OPERATION/REPORT DEVICE STATUS
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E P
R E
-R E
C O
R D
E D
S T
A F
F A
L E
R T
M E
S S
A G
E T
H R
O U
G H
O U
T T
H
B
U
IL
D
IN
G
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
A C
T
IV
A T
E E
L E
C T
R
IC
A L D
IS
C
O N
N E
C T
O F
E Q
U
IP
M E
N T
I N
I T
E S
P A
C E
S
C L O
S E
S M
O K
E B
A R
R
IE
R D
O O
R S
O N
A S
S O
C
IA
T E
D F
L O
O R
ALARM CONDITIONS A B C D E F G H I J K L M
1 MANUAL ALARM PULL STATION X X X X X X X X 1
2 SMOKE DETECTOR - SPOT TYPE X X X X X X X 2
3 ASPIRATING SMOKE DETECTOR (0.12% OBS./FT.) - FIRE1 X X X X X X X 3
4 ASPIRATING SMOKE DETECTOR (1% OBS./FT.) - FIRE2 X X X X X X X 4
TROUBLE CONDITIONS A B C D E F G H I J K L M
10 AC POWER FAILURE X X X 10
11 LOW BATTERY X X X 11
12 OPEN CIRCUIT X X X 12
13 GROUND FAULT X X X 13
14 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 14
15 REMOTE POWER SUPPLY COMMON TROUBLE X X X 15
16 ASPIRATING SMOKE DETECTION SYSTEM COMMON TROUBLE X X X 16
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:5
A
M
1-FA-001
BLDG 1 FIRE ALARM / MASS
NOTIFICATION GENERAL NOTES
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NO SCALE
BLDG 1 - FIRE ALARM RISER DIAGRAM1NO SCALE
BLDG 1 - FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 1. NOT ALL EXISTING INPUTS AND OUTPUTS ARE
REPRESENTED ON THIS MATRIX. PLEASE REFER TO THE EXISTING FIRE ALARM PANEL LOCATED IN BUILDING 1 FOR ALL OF THE INPUTS AND OUTPUTS.
2. ELECTRICAL DISCONNECT SHALL ONLY BE INITIATED FOR ALARM CONDITIONS DETECTED IN THE ITE SPACES.
1-FA-102
1-FA-102
1-FA-102
1-FA-102
1-FA-102
1-FA-102
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:5
A
M
1-FA-101
BLDG 1 OVERALL FIRE ALARM PLANS
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - FIRST FLOOR2
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - SECOND FLOOR3
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - THIRD FLOOR4
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - FOURTH FLOOR5
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - FIFTH FLOOR6
N
1/32" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - GROUND FLOOR1
1003A
OI&T
1003A s
2000A
OI&T
2000A s
3000A
OI&T
3000A s 4054C
OI&T
4054C s
5A1
OI&T
5A1 s
52B
OI&T
SERVER
ROOM
52B s
F A
C U
OI&T
S
A S
D1
S
S
S
CRU-1
S
CRU-2
F
WF VS
0.25W
30cd
0.25W
30cd
S
CRU-3
.2
W c d
AOM ITE SPACE ELECTRICAL
DISCONNECT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:5
A
M
1-FA-102
BLDG 1 ENLARGED FIRE ALARM PLANS
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
3/4" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - ROOM 1003A2
N
3/4" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - ROOM 2000A3
N
3/4" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - ROOM 3000A4
N
3/4" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - ROOM 4054C5
N
3/4" = 1'-0"
BLDG 1 - FIRE ALARM PLAN - ROOM 5A16
N
1/8" = 1'-0"
BLDG 1 - GROUND FLOOR - ROOMS OI&T 52 AND OI&T 52B1
SHEET KEYNOTES
MARK KEYNOTE
1 AN ASPIRATING SMOKE DETECTION SYSTEM SHALL
BE INSTALLED IN THE SERVER ROOM TO PRVOIDE
EARLY WARNING OF A POTENTIAL FIRE EVENT.
SAMPLING PORTS FOR THE ASPIRATING SMOKE
DETECTION SHALL BE INSTALLED AND LOCATED IN
ACCORDANCE WITH NFPA 72. ASPIRATING SMOKE
DETECTION CONTROL UNIT SHALL BE UL LISTED
AND FM APPROVED. THE SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 75. REFER TO
INPUT/OUTPUT MATRIX ON SHEET 1-FA-001 FOR
SENSITIVITY SETTINGS. SAMPLING PORTS ARE
ONLY TO BE INSTALLED AT THE CEILING. THIS
SPACE DOES NOT HAVE A RAISED FLOOR.
2 ASPIRATING SMOKE DETECTION CONTROL PANEL
SHALL BE POWERED FROM THE EXISTING FIRE
ALARM CONTROL UNIT OR BY A REMOTE POWER
SUPPLY.
3 INSTALLED UNDER RAISED FLOOR.
DN
DN
1-FX-102
1-FX-102
1-FX-102
1-FX-102
1-FX-102
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
1-FX-102
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
1-FX-101
BLDG 1 OVERALL FIRE SUPPRESSION
HAZARD CLASSIFICATION PLANS
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - FIRST FLOOR2
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - SECOND FLOOR3
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - THIRD FLOOR4
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - FOURTH FLOOR5
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - FIFTH FLOOR6
N
1/32" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - GROUND FLOOR1
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL AND NFPA 13-2019.
2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA
REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC
EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND
SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE
FUSIBLE-LINK TYPE.
3. WHERE FEASABLE, ALL TELECOMMUNICATIONS AND
SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE
EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH
APPLICABLE CODES AND STANDARDS. WHERE EXISTING
CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”
CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,
BUILT-IN TROUGHS AND/OR LEAK DETECTION IN
ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO
PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY
WET-PIPE SPRINKLER LEAKAGE.
FIRE SUPPRESSION GENERAL NOTES:
1003A
1003A
2000A
OI&T
2000A
3000A
OI&T
3000A
4054C
OI&T
4054C
5A1
OI&T
5A1
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
52B
OI&T
SERVER
ROOM
52B
OI&T
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
1-FX-102
BLDG 1 ENLARGED FIRE SUPPRESSION
HAZARD CLASSIFICATION PLANS
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
3/4" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 1003A2
N
3/4" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 2000A3
N
3/4" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 3000A4
N
3/4" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 4054C5
N
3/4" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOM 5A16
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL AND NFPA 13-2019.
2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA
REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC
EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND
SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE
FUSIBLE-LINK TYPE.
3. WHERE FEASABLE, ALL TELECOMMUNICATIONS AND
SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE
EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH
APPLICABLE CODES AND STANDARDS. WHERE EXISTING
CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”
CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,
BUILT-IN TROUGHS AND/OR LEAK DETECTION IN
ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO
PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY
WET-PIPE SPRINKLER LEAKAGE.
FIRE SUPPRESSION GENERAL NOTES:
N
1/8" = 1'-0"
BLDG 1 - HAZARD CLASSIFICATION PLAN - ROOMS OI&T 52 AND OI&T 52B1
SHEET KEYNOTES
MARK KEYNOTE
1 CONTRACTOR TO TIE INTO EXISTING FIRE
SPRINKLER SYSTEM PIPING IN OI&T 52 AND LOCATE
ZONE CONTROL VALVE ABOVE LAY-IN CEILING.
COORDINATE LOCATION WITH OTHER DISCIPLINES.
2 THIS SPACE HAS EXISTING FIRE SPRINKLER
PROTECTION, CONTRACTOR TO REPLACE
NON-COMPLIANT SPRINKLERS WITH STANDARD
RESPONSE, FUSIBLE-LINK SPRINKLERS.
BASEMENT
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM
DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT
ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF
DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT
INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE
GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION
OF THE PROJECT.
s
WF VS
AIM AIM
8 ANY OTHER SYSTEM TROUBLE X X X 8
A B C D E F G H I
X PERFORM OPERATION/REPORT DEVICE STATUS
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E A
U D
IB
L E
N O
T
IF
IC
A
T
IO
N D
E V
IC
E
S T
H R
O U
G H
O U
T B
U
IL
D
IN
G
A C
T
IV
A T
E V
IS
U
A L N
O T
IF
IC
A T
IO
N
D E
V
IC
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
ALARM CONDITIONS A B C D E F G H I
1 SMOKE DETECTOR - SPOT TYPE X X X X X 1
TROUBLE CONDITIONS A B C D E F G H I
2 AC POWER FAILURE X X X 2
3 LOW BATTERY X X X 3
4 OPEN CIRCUIT X X X 4
5 GROUND FAULT X X X 5
6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6
7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7
FACU
EXISTING FIRE ALARM/MASS NOTIFICATION
CONTROL UNIT
FIRE ALARM LEGEND
SPD EXISTING SURGE PROTECTIVE DEVICE
s EXISTING SMOKE DETECTOR - SPOT TYPE
WF EXISTING WATERFLOW DEVICE
OUT OF SCOPE AREA
VS EXISTING VALVE SUPERVISORY SWITCH
AIM EXISTING ADDRESSABLE INPUT MODULE
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL
BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,
NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM
CONTRACTOR IS RESPONSIBLE FOR DEVELOPING
CALCULATIONS AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH
RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING
MANUFACTURER AND MODEL OR BE COMPATIBLE WITH
THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL
BE WHITE FINISH TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH OWNER
PRIOR TO COMMENCING WORK TO PREVENT
INTERRUPTION OF SERVICE.
5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL
AREAS OF RENOVATION SHALL BE PROVED WITH NEW
SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE
INSTALLED IN ACCORDANCE WITH NFPA 72 AND
COORDINATED WITH OTHER TRADES TO ENSURE
COMPLIANT INSTALLATION.
6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR
DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER
INPUTS SHALL MATCH EXISTING PANEL.
FIRE ALARM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
5-FA-001
BLDG 5 FIRE ALARM GENERAL NOTES,
DIAGRAMS, AND LEGEND
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NO SCALE
BLDG 5 - FIRE ALARM RISER DIAGRAM1NO SCALE
FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 5. NOT
ALL EXISTING INPUTS AND OUTPUTS ARE REPRESENTED ON THIS MATRIX.
5-FA-101
WF VS
OI&T
s
FACU
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
5-FA-101
BLDG 5 FIRE ALARM FLOOR PLAN -
BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 5 - FIRE ALARM PLAN - BASEMENT1
N
3/4" = 1'-0"
BLDG 5 - FIRE ALARM PLAN - ROOM 042
5-FX-101
OI&T
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
EXISTING FIRE SUPPRESSION RISER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
5-FX-101
BLDG 5 FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 5 - HAZARD CLASSIFICATION PLAN - BASEMENT1
N
3/4" = 1'-0"
BLDG 5 - HAZARD CLASSIFICATION PLAN - ROOM 042
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL AND NFPA 13-2019.
2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA
REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC
EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND
SWITCH ROOMS) SHALL BE NEW STANDARD RESPONSE
FUSIBLE-LINK TYPE.
3. WHERE FEASIBLE, ALL TELECOMMUNICATIONS AND
SERVER ROOMS SHALL HAVE 18” CLEARANCE ABOVE
EQUIPMENT TO SPRINKLER PIPING IN ACCORDANCE WITH
APPLICABLE CODES AND STANDARDS. WHERE EXISTING
CONSTRUCTION ROOM HEIGHT LIMITATIONS OCCUR, 18”
CLEARANCE MAY NOT BE ACHIEVABLE. IN ADDITION,
BUILT-IN TROUGHS AND/OR LEAK DETECTION IN
ACCORDANCE WITH NFPA 70 SHALL BE PROVIDED TO
PROTECT TELECOMMUNICATION EQUIPMENT FROM ANY
WET-PIPE SPRINKLER LEAKAGE.
FIRE SUPPRESSION GENERAL NOTES:
SHEET KEYNOTES
MARK KEYNOTE
1 THIS SPACE HAS EXISTING FIRE SPRINKLER
PROTECTION, CONTRACTOR TO REPLACE
NON-COMPLIANT SPRINKLERS WITH STANDARD
RESPONSE, FUSIBLE-LINK SPRINKLERS.
EXISTING FIRE ALARM/MASS NOTIFICATION
CONTROL UNIT
FIRE ALARM LEGEND
SPD EXISTING SURGE PROTECTIVE DEVICE
s EXISTING SMOKE DETECTOR - SPOT TYPE
OUT OF SCOPE AREA
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL
BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,
NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM
CONTRACTOR IS RESPONSIBLE FOR DEVELOPING
CALCULATIONS AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH
RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING
MANUFACTURER AND MODEL OR BE COMPATIBLE WITH
THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL
BE WHITE FINISH TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH OWNER
PRIOR TO COMMENCING WORK TO PREVENT
INTERRUPTION OF SERVICE.
5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL
AREAS OF RENOVATION SHALL BE PROVED WITH NEW
SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE
INSTALLED IN ACCORDANCE WITH NFPA 72 AND
COORDINATED WITH OTHER TRADES TO ENSURE
COMPLIANT INSTALLATION.
6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR
DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER
INPUTS SHALL MATCH EXISTING PANEL.
FIRE ALARM GENERAL NOTES
FACU
SPD
BASEMENT
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM
DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT
ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF
DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT
INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE
GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION
OF THE PROJECT.
s
8 ANY OTHER SYSTEM TROUBLE X X X 8
A B C D E F G H I
X PERFORM OPERATION/REPORT DEVICE STATUS
SYSTEM OUTPUTS
SYSTEM INPUTS
F
A C
U A
N N
U N
C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E A
U D
IB
L E
N O
T
IF
IC
A
T
IO
N D
E V
IC
E
S T
H R
O U
G H
O U
T B
U
IL
D
IN
G
A C
T
IV
A T
E V
IS
U
A L N
O T
IF
IC
A T
IO
N
D E
V
IC
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
ALARM CONDITIONS A B C D E F G H I
1 SMOKE DETECTOR - SPOT TYPE X X X X X 1
TROUBLE CONDITIONS A B C D E F G H I
2 AC POWER FAILURE X X X 2
3 LOW BATTERY X X X 3
4 OPEN CIRCUIT X X X 4
5 GROUND FAULT X X X 5
6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6
7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
6-FA-001
BLDG 6 FIRE ALARM GENERAL NOTES,
DIAGRAMS, AND LEGEND
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NO SCALE
BLDG 6 - FIRE ALARM RISER DIAGRAM1NO SCALE
FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 6. NOT
6-FA-101
MECHANICAL
ROOM
s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
6-FA-101
BLDG 6 FIRE ALARM FLOOR PLAN -
BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 6 - FIRE ALARM PLAN - BASEMENT1
N
BLDG 6 - FIRE ALARM PLAN - ROOM 032
MECHANICAL
ROOM
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
6-FX-101
BLDG 6 FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 6 - HAZARD CLASSIFICATION PLAN - BASEMENT1
SHEET KEYNOTES
MARK KEYNOTE
1 NO EXISTING FIRE SPRINKLER SYSTEM. NO
MODIFICATION WILL BE MADE TO INCLUDE SPRINKLER
PROTECTION FOR THIS SCOPE OF WORK AREA.
EXISTING FIRE ALARM/MASS NOTIFICATION
CONTROL UNIT
FIRE ALARM LEGEND
SPD EXISTING SURGE PROTECTIVE DEVICE
s EXISTING SMOKE DETECTOR - SPOT TYPE
OUT OF SCOPE AREA
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL
BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,
NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM
CONTRACTOR IS RESPONSIBLE FOR DEVELOPING
CALCULATIONS AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH
RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING
MANUFACTURER AND MODEL OR BE COMPATIBLE WITH
THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL
BE WHITE FINISH TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH OWNER
PRIOR TO COMMENCING WORK TO PREVENT
INTERRUPTION OF SERVICE.
5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL
AREAS OF RENOVATION SHALL BE PROVED WITH NEW
SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE
INSTALLED IN ACCORDANCE WITH NFPA 72 AND
COORDINATED WITH OTHER TRADES TO ENSURE
COMPLIANT INSTALLATION.
6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR
DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER
INPUTS SHALL MATCH EXISTING PANEL.
FIRE ALARM GENERAL NOTES
FACU
SPD
BASEMENT
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM
DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT
ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF
DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT
INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE
GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION
OF THE PROJECT.
s
8 ANY OTHER SYSTEM TROUBLE X X X 8
A B C D E F G H I
X PERFORM OPERATION/REPORT DEVICE STATUS
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E A
U D
IB
L E
N O
T
IF
IC
A
T
IO
N D
E V
IC
E
S T
H R
O U
G H
O U
T B
U
IL
D
IN
G
A C
T
IV
A T
E V
IS
U
A L N
O T
IF
IC
A T
IO
N
D E
V
IC
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
ALARM CONDITIONS A B C D E F G H I
1 SMOKE DETECTOR - SPOT TYPE X X X X X 1
TROUBLE CONDITIONS A B C D E F G H I
2 AC POWER FAILURE X X X 2
3 LOW BATTERY X X X 3
4 OPEN CIRCUIT X X X 4
5 GROUND FAULT X X X 5
6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6
7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
7-FA-001
BLDG 7 FIRE ALARM GENERAL NOTES,
DIAGRAMS, AND LEGEND
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NO SCALE
BLDG 7 - FIRE ALARM RISER DIAGRAM1NO SCALE
FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 7. NOT
OI&T TR
7-FA-101
OI&T TR
212 s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
7-FA-101
BLDG 7 FIRE ALARM FLOOR PLAN -
BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 7 - FIRE ALARM PLAN - BASEMENT1
N
BLDG 7 - FIRE ALARM PLAN - ROOM 2122
OI&T TR
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
7-FX-101
BLDG 7 FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - BASEMENT
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 7 - HAZARD CLASSIFICATION PLAN - BASEMENT1
SHEET KEYNOTES
MARK KEYNOTE
1 NO EXISTING FIRE SPRINKLER SYSTEM. NO
MODIFICATION WILL BE MADE TO INCLUDE SPRINKLER
PROTECTION FOR THIS SCOPE OF WORK AREA.
LEVEL 1
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM
DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT
ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF
DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT
INDICATED. THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE
GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL COMPLETION
OF THE PROJECT.
s
WF VS
AIM AIM
8 ANY OTHER SYSTEM TROUBLE X X X 8
A B C D E F G H I
X PERFORM OPERATION/REPORT DEVICE STATUS
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E A
U D
IB
L E
N O
T
IF
IC
A
T
IO
N D
E V
IC
E
S T
H R
O U
G H
O U
T B
U
IL
D
IN
G
A C
T
IV
A T
E V
IS
U
A L N
O T
IF
IC
A T
IO
N
D E
V
IC
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
ALARM CONDITIONS A B C D E F G H I
1 SMOKE DETECTOR - SPOT TYPE X X X X X 1
TROUBLE CONDITIONS A B C D E F G H I
2 AC POWER FAILURE X X X 2
3 LOW BATTERY X X X 3
4 OPEN CIRCUIT X X X 4
5 GROUND FAULT X X X 5
6 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 6
7 REMOTE POWER SUPPLY COMMON TROUBLE X X X 7
FACU
EXISTING FIRE ALARM/MASS NOTIFICATION
CONTROL UNIT
FIRE ALARM LEGEND
SPD EXISTING SURGE PROTECTIVE DEVICE
s EXISTING SMOKE DETECTOR - SPOT TYPE
WF EXISTING WATERFLOW DEVICE
OUT OF SCOPE AREA
VS EXISTING VALVE SUPERVISORY SWITCH
AIM EXISTING ADDRESSABLE INPUT MODULE
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM SHALL
BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
VA FIRE PROTECTION DESIGN MANUAL-SEVENTH EDITION,
NFPA 70-2020, AND NFPA 72-2019. FIRE ALARM
CONTRACTOR IS RESPONSIBLE FOR DEVELOPING
CALCULATIONS AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED WITH
RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH EXISTING
MANUFACTURER AND MODEL OR BE COMPATIBLE WITH
THE EXISTING SYSTEM. SPEAKERS AND STROBES SHALL
BE WHITE FINISH TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH OWNER
PRIOR TO COMMENCING WORK TO PREVENT
INTERRUPTION OF SERVICE.
5. EXISTING SMOKE DETECTION SHALL BE REMOVED. ALL
AREAS OF RENOVATION SHALL BE PROVED WITH NEW
SMOKE DETECTION. NEW SMOKE DETECTION SHALL BE
INSTALLED IN ACCORDANCE WITH NFPA 72 AND
COORDINATED WITH OTHER TRADES TO ENSURE
COMPLIANT INSTALLATION.
6. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED FOR
DEVICES LOCATED IN THE PROJECT AREA. ALL OTHER
INPUTS SHALL MATCH EXISTING PANEL.
FIRE ALARM GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
8-FA-001
BLDG 8 FIRE ALARM GENERAL NOTES,
DIAGRAMS, AND LEGEND
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NO SCALE
BLDG 8 - FIRE ALARM RISER DIAGRAM1NO SCALE
FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 8. NOT
8-FA-101
WF
VS
1006A
OI&T TR
1006A s th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
8-FA-101
BLDG 8 FIRE ALARM FLOOR PLAN -
FIRST FLOOR
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 8 - FIRE ALARM PLAN - FIRST FLOOR1
N
BLDG 8 - FIRE ALARM PLAN - ROOM 1006A2
8-FX-101
1006A
OI&T TR
1006A
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
EXISTING FIRE SUPPRESSION RISER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
F U
L L
Y S
P R
IN
K
L E
R E
D
/2
/2
:5
:0
A
M
8-FX-101
BLDG 8 FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - FIRST FLOOR
SAB
DBN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/4" = 1'-0"
BLDG 8 - HAZARD CLASSIFICATION PLAN - FIRST FLOOR1
N
3/4" = 1'-0"
BLDG 8 - HAZARD CLASSIFICATION PLAN - ROOM 1006A2
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL AND NFPA 13-2019.
2. PER VA FIRE PROTECTION DESIGN MANUAL AND VA
REQUEST, ALL SPRINKLERS IN PROTECTING ELECTRONIC
EQUIPMENT AREAS (DATA, TELECOM, SERVER, AND
SWITCH ROOMS) SHALL BE NEW…