TP09 Final Drawings 10 657A4-20-700 Resubmitted SS 100 percent CD Drawings Technology.pdf

PDF 10 MB Posted

Attached to
Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES
Solicitation number
36C25521R0103
Issued by

About this file

This document provides details for a federal contract opportunity for infrastructure upgrades at the John J. Pershing VA Medical Center. The Statement of Work involves construction documents and performance of work associated with upgrading the EHRM infrastructure including construction of a new fiber backbone, new server room, renovations to O&IT closets, HVAC cooling and controls upgrades, patch panel upgrades, cabling upgrades to CAT 6A, additional power and data drops for end user equipment, and power upgrades to O&IT closets and the telephone room. The contractor shall provide all services, materials, labor, supervision, safety certification and expertise for items described in the construction documents and specifications. The period of performance is estimated at 365 calendar days after Notice to Proceed. The principal NAICS code is 236220 for Commercial and Institutional Building Construction and the FSC is Y1DZ for Construction of Other Hospital buildings. The opportunity is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files

File Type Posted
S02 36C25521R0103 0008.pdf PDF
Additional RFI (EHRM).pdf PDF
Wage Determination (9-3-2021).pdf PDF
S02 36C25521R0103 0007.pdf PDF
36C25521R0103 0006.pdf PDF
020-2333 EHRM Geotech Report 111020.pdf PDF
36C25521R0103 0005.pdf PDF
S06 36C25521R0103 0002.pdf PDF
657A4-20-700 EHRM Infrastructure Upgrades 36C25521R0103 0001.pdf PDF
S06 36C25521R0103 0003.pdf PDF
S06 36C25521R0103 0004.pdf PDF
SIGN IN ROSTER (657A4-20-700) EHRM INFRASTRUCTURE UPGRADES.pdf PDF
TP09 Final Specs Vol-01.pdf PDF
00 VA OEHRM Site Infrastructure Requirements - 2 Signed.pdf PDF
EHRM NCO15 Price Estimate Template V1.2.url.xlsx XLSX spreadsheet
S02 36C25521R0103_2.pdf PDF
TP09 Final Drawings 09 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Electrical.pdf PDF
TP09 Final Drawings 08 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Mechanical.pdf PDF
TP09 Final Drawings 01 657A4-20-700 Resubmitted SS 100 percent CD Drawings-General.pdf PDF
TP09 Final Drawings 05 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Architectural.pdf PDF
TP01 Specs Vol-02.pdf PDF
TP01 Specs Vol-01.pdf PDF
TP09 Final Drawings 04 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Structural.pdf PDF
TP09 Final Drawings 02 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Abatement.pdf PDF
36C25521R0103.pdf PDF
TP09 Final Drawings 03 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Civil.pdf PDF
TP09 Final Drawings 06 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Fire Protection.pdf PDF
TP09 Final Drawings 07 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Plumbing.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

STANDARD MOUNTING HEIGHTSANNOTATION

ELECTRICAL:

AUDIBLE APPLIANCES (CENTERLINE) 84"

ALARMS 48"

ANNUNCIATOR PANELS 48"

CLOCK OUTLETS (CENTERLINE) 84"

CONTROLS (TOP) 48"

EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"

FIRE ALARM BELL (EXTERIOR) 120"

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"

INTERCOM (AFEA ONLY) 36"

INTERCOMS (TOP) 48"

PANELS & PANELBOARDS (TOP) 72"

PULL STATIONS (HANDLE) 48"

PHOTOCELLS 144"

RECEPTACLES (BOTTOM) 18"

RECEPTACLES (EXTERIOR) 24"

RECEPTACLES (GARAGES) 26"

RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"

REMOTE INDICATING LIGHT (EQUIPMENT ROOMS) 48"

REMOTE INDICATING LIGHT (FINISHED AREAS) CEILING

SAFETY SWITCHES & STARTERS 48"

SWITCHES (TOP) 48"

TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"

VISIBLE APPLIANCES (CENTERLINE) 84"

(AFF, AFG UNLESS NOTED OTHERWISE)

CU

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE

CALL OUT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

Z

BC

CB

B

DS

E

EP

LS

KS

NA

NM

SS

PS

PS

IC

CATV

FO

T

T/D

D

S

IC

UC

CCTV

S

WAP

#D/#TV

M

S

V

CR

DB

DB

DM

EL

EO

GB

KP

MD

PB

RE

EC

KT

GO

C

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, WALL MOUNTED

SPEAKER, CEILING MOUNTED

SERVER RACK, TWO-POST, FLOOR MOUNTED

3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD

GROUND BAR, TYPE AS NOTED

SERVER RACK, WALL MOUNTED

CABLE TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

TELEPHONE LINE

TELEPHONE/DATA LINE

DATA LINE

SPEAKER LINE

INTERCOM LINE

INTERCOM, "M" DENOTES MASTER STATION

VOLUME CONTROL, WALL MOUNTED

CODE BLUE PUSHBUTTON STATION

DUTY STATION

STAFF EMERGENCY ASSIST STATION

PATIENT EMERGENCY PULL CORD STATION

STAFF LOCATOR SENSOR

NURSE CALL KEY SWITCH

NURSE CALL VISUAL ANNUNCIATOR PANEL

NURSE CALL MASTER STATION

STAFF STATION (NORMAL, EMERGENCY & CODE BLUE)

DOME LIGHT, WALL MOUNTED

DOME LIGHT, CEILING MOUNTED

ZONE DOME LIGHT

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

UNDERGROUND COMMUNICATIONS LINE,

CABLING TYPE AS NOTED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

SERVER RACK, FOUR-POST, FLOOR MOUNTED

SERVER CABINET, FLOOR MOUNTED

CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY

CARD READER, PROXIMITY TYPE

DOOR BELL PUSHBUTTON

DOOR BELL CHIME

DOOR POSITION MONITOR

ELECTRIFIED LOCKING DEVICE, REQUEST TO EXIT SENSOR,

LATCH BOLT MONITOR, AND DOOR POSITION SWITCH

ELECTRIFIED LOCKING DEVICE

GLASS BREAK DETECTOR

INTRUSION DETECTION KEYPAD

INTRUSION DETECTION MOTION DETECTOR

DURESS PUSHBUTTON

REQUEST TO EXIT BUTTON

SINGLE VIEW SECURITY CAMERA

EMERGENCY CALL STATION

RFID KEY TAG READER

GATE OPENER

DUAL VIEW SECURITY CAMERA

180-DEGREE PANORAMIC VIEW SECURITY CAMERA

270-DEGREE PANORAMIC/MULTI-IMAGE VIEW

360-DEGREE PANORAMIC/MULTI-IMAGE VIEW

SECURITY CAMERA

SECURITY CAMERA

PATIENT STATION WITH BED CONNECTOR

PATIENT STATION WITH CODE BLUE

SECURITY SYMBOLS

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

#D = DATA, # = QUANTITY OF CABLES

#E = ELEVATOR, # = QUANTITY OF CABLES

#FMS = FACILITY MONITORING SYSTEM,

# = QUANTITY OF CABLES

NURSE CALL SYMBOLS

COMMUNICATION SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

X

W

V

U

T

S

R

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB JUNCTION BOX

J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

DETAIL REFERENCE

SECTION CUT DESIGNATION

EP-101

EP-101

WP - WEATHERPROOF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:3

A

M

00-T-001

TECHNOLOGY LEGEND

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-501

RACK ELEVATIONS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

J-HOOK, SIZES AS

NEEDED

1/4" OR 3/8" THREADED ROD OR #12 TO #8

HANGER WIRE ATTACHED TO STRUCTURE

ABOVE. (DO NOT USE EXISTING CEILING

HANGER WIRES. MUST HAVE ITS OWN

HANGER WIRE.)

TYPICAL J-HOOK, CABLE LOOP IN

CEILING ABOVE STATION JACK.

J-HOOK SIZE

1"

1-5/16" 2" 3" 4"

CAPACITY

J-HOOK CAPACITY FOR CAT6A CABLE

BASED ON 70% FILL

PARALLEL MOUNTING PERPENDICULAR MOUNTING

HEAVY DUTY (SEISMIC) CABLE

RUNWAY BUTT SPLICE

HEAVY DUTY (SEISMIC) CABLE

RUNWAY JUCTION SPLICE

V1

1A

1B

NOTE:

1. PERMANENTLY LABEL ALL WALL JACKS. COORDINATE LABELING SCHEME WITH FACILITY'S OIT.

2. NUMBER OF JACKS AND FACEPLATE IS DEPENDANT UPON NUMBER OF DROPS SHOWN FOR EACH LOCATION.

REFER TO FLOOR PLANS FOR EXACT NUMBER OF DROPS.

PROVIDE DOUBLE-GANG

BACKBOX WITH SINGLE-GANG

PLASTER RING OR WHERE

NECESSARY USE SINGLE-

GANG LOW VOLTAGE CUT-IN

RING WITH MOUNTING TABS

TO SOLIDLY HOLD RING.

PROVIDE HORIZONTAL

CABLING PER SPECIFICATIONS

WITH RJ45 CONNECTOR FOR

DATA CONNECTIONS.

TERMINATE CABLE IN TR AT

RACK-MOUNTED 48-PORT

MODULAR PATCH PANELS.

(TYPICAL)

J-BOLT, 5/16-18 THD'D

X 2.25" LONG, 2 PLACES

NUT, 5/16-18

HEX, STEEL 2 PLACES

WASHER, SLIT LOCK, FOR

Ø 5/16, SCR STEEL, 2 PLACES

Ø5/16" LAG BOLTS, FOR PLYWOOD

BACKER BOARDS OR Ø5/16" HEX

CAPBOLTS AND APPROPRIATE WALL

ANCHORS FOR CONCRETE WALLS

FLAT WAHWER,

FOR Ø5/16" BOLTS

3/4" FIRE-RETARDANT TREATED

PLYWOOD SPANNING AT LEAST TWO

BUILDING STUDS, OR IF THAT IS NOT

POSSIBLE, ANCHORED INTO AT LEAST

ONE STUD AND TOGGLED INTO THE

DRYWALL WITH 5/16" OR LARGER TOGGLE

BOLT WITH FENDER WASHERS.

A1-A035

WRAPAROUND CABLE

LABEL WITHIN 6" OF

EACH END OF THE CABLE

NOTE:

1. CPI 10562-001 OR EQUIVALENT.

2. SEISMIC INSTALLATION REQUIREMENTS SHALL BE APPROVED BY A LICENSED STRUCTURAL ENGINEER.

DOOR POSITION

SWITCH

ACCESSIBLE CEILING

PROVIDE DOUBLE-GANG

BACKBOX WITH SINGLE-GANG

PLASTER RING FOR DOOR

MOTION DETECTOR.

LOCATION PER PLANS.

3/4" CONDUIT

(TYPICAL, UNO)

ELECTRIFIED

LOCKSET/STRIKE

DOOR

PROVIDE 6"X6"X4" DEEP

JUNCTION BOX WITH

HINGED COVER.

LOCATE ON SECURE

SIDE OF DOOR.

PROVIDE 1" CONDUIT

BACK TO ACCESS

CONTROL PANEL.

PROVIDE DOUBLE-GANG

BACKBOX WITH

SINGLE-GANG PLASTER

RING FOR CARD READER.

LOCATION PER PLANS.

FLOOR

MAX. 48" AFF

OR MATCH

LIGHT SWITCH

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-502

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

J-HOOK DETAILS

SCALE: NTS

CABLE TRAY SUPPORT FROM RACK DETAIL

SCALE: NTS

CABLE TRAY SEISMIC RESTRAINTS DETAIL

SCALE: NTS

DATA OUTLET DETAIL

SCALE: NTS

CABLE TRAY SUPPORT DETAIL

SCALE: NTS

CABLE LABELING DETAIL

SCALE: NTS

SEISMIC BRACING

SCALE: NTS

CARD READER DETAIL

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-503

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

1 TYPICAL ENCLOSURE SPECIFICATION

SCALE: NTS

2 TYPICAL ENCLOSURE FRONT WITH VERTICAL EXHAUST DUCT (VED)

SCALE: NTS

3 TYPICAL ENCLOSURE SIDE VIEW WITH VERTICAL EXHAUST DUCT (VED)

SCALE: NTS

4 TYPICAL ENCLOSURE TOP VIEW WITH VERTICAL EXHAUST DUCT (VED)

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-504

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

1 TYPICAL RACK CONFIGURATION

SCALE: NTS

2 ISOMETRIC VIEW WITH DOORS AND VERTICAL EXHAUST DUCT (VED)

SCALE: NTS

3 FRONT VIEW DIMENSIONS

SCALE: NTS

4 FIBER DISTRIBUTING CABINET

SCALE: NTS

5 UTP PATCH PANEL

SCALE: NTS

6 UTP MEDIA

7 FIBER CASSETTE

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-505

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

1 MAIN DISTRIBUTION AREA (A & B SIDES)

SCALE: NTS

2 CABLE TRAY

3 FIBER PATHWAY AND DETAILS

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-506

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

1 SIDE ELEVATION ENCLOSURE

SCALE: NTS

2 REAR ELEVATION ENCLOSURES

SCALE: NTS

3 PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS

SCALE: NTS

4 EARTHING EXAMPLE (CISCO 6509) REF CISCO PRODUCT INSTALLATION GUIDE

5 TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB)

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-507

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

DIVERSE ROUTING FOR CABLES FROM CABINETS TO HORIZONTAL DISTRIBUTION

AREAS

SCALE: NTS

STANDARD DENSITY EQUIPMENT DISTRIBUTOR ELEVATION FOR CABINETS

SCALE: NTS

DIVERSE ROUTING FOR CABLES FROM HORIZONTAL AREAS TO MAIN DISTRIBUTION

AREAS

SCALE: NTS

DIVERSE ROUTING FOR CABLES FROM MAIN DISTRIBUTION AREAS TO

TELECOMMUNICATIONS ROOMS

SCALE: NTS

TYPICAL END OF ROW HORIZONTAL DISTRIBUTION AREA

CR

DM

EL

RE

MULTI-CONDUCTOR CABLE

PB

LEGEND:

VASS POE GB

SWITCH (ETR)

RACK-MOUNTED

UPS (ETR)

PHYSICAL ACCESS

CONTROL

CABINET(S) (ETR)

PACS BATTERY

CABINET(S) (ETR)

FIRE ALARM

RELAY(S) (ETR)

CARD READERS AND

ASSOCIATED DEVICES PER

PLANS. (TYPICAL)

TR - COMMS ROOM

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

00-T-508

TECHNOLOGY DETAILS

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

SCALE: NTS

2 BACKBONE CABLE ROUTING (REDUNDANT AND DIVERSE) - BUILDING 1

SCALE: NTS

3 BACKBONE CABLE ROUTING (REDUNDANT AND DIVERSE) - CAMPUS

1. PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM COMPATIBLE WITH THE EXISTING CAMPUS PACS SYSTEM. PROVIDE ALL UPGRADES TO THE EXISTING PACS SYSTEM TO INCORPORATE NEW DEVICES.

NOTES:

PHYSICAL ACCESS CONTROL SYSTEM (PACS) CARD READER SCHEDULE

TYPE

SYMBOL

TYPE

FORM FACTOR DESCRIPTION MOUNTING

MOUNTING

HEIGHT

LOCATION MODELS READ RANGE POWER COLOR COMMENTS NOTES

CR-1 OUTDOOR CARD READER

WALL, RE: DETAIL

8/00-T-502

48" TO TOP OF

BOX ABOVE

FINISHED

FLOOR

OUTDOOR

MATCH EXISTING

VA CARD READER

SYSTEM

4" MAXIMUM

85mA AVG/ 116mA PEAK AT

12VDC

BLACK

DUAL AUTHNTICATION CARD READER WITH KEYPAD

COMPATIBLE WITH EXISTING CAMPUS CARD READER SYSTEM,

WITH WEATHER HOOD, BUILT-IN HEATER, AND GASKET FOR

COLD WEATHER.

SCALE: NTS

1 SECURITY RISER DIAGRAM

4 PACS CARD READER SCHEDULE

DN

DN

DN

DN

4 2

2 2

2 2

2 2

ELECTRICAL CLOSET

01D

1-T-401

MATCH LINE

1-T100B

CORRIDOR

GA

2 4

4 4

2 2 2 2

2 2

2 2

93 105106108110

TO URGENT CARE TR.

CAMPUS FIBER OPTIC CABLES

TO GO DOWN THROUGH SLEEVES

AT THIS POINT TO SUB-BASEMENT.

CAMPUS FIBER OPTIC

CABLES TO GO DOWN

THROUGH SLEEVES AT THIS

POINT TO SUB-BASEMENT.

CAMPUS FIBER OPTIC CABLES TO RUN IN SUB-BASEMENT.

ATTACH CABLE RUNS TO SUB-BASEMENT CEILING USING

APPROPRIATE CABLE HANGERS AND RUN WITH OTHER

CABLES AND CONDUITS THROUGH THE EXISTING HANGERS.

BUILDING KEY PLAN

N

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:2

A

M

1-T-100A

BUILDING 1 GROUND LEVEL

TECHNOLOGY FLOOR PLAN - AREA A

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

3/32" = 1'-0"

B1 - GROUND FLOOR - ELECTRICAL TECHNOLOGY PLAN - AREA A

GENERAL NOTES:

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF

CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED

TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN

IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO

OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH

CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH

PANEL IN ITS DESIGNATED TR.

E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED

WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH

PANEL. TEST FIBER WITH OPTICAL POWER METER AND

LIGHT SOURCE.

G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD

FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS

AS REQUIRED FOR A NEAT AND WORKMANLIKE

INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL

WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING

THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

TECHNOLOGY KEYNOTES

93 INSTALL APPROXIMATELY 382 NEW CAT6A DATA CABLES ON

THE GROUND FLOOR TO A MIXTURE OF 128 DUAL AND QUAD

WORK STATION LOCATIONS.

105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST

REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER

TO THE NEW CABLING.

106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM

THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR

ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED

SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD

DATA AND TELEPHONE CABLING ALL THE WAY TO THE

STATION END. ENSURE THAT ANY CABLES IN THE CEILING

AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA

AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY

UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH

PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO

IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING

RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING

FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM.

DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION

EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING

AREA THAT IS FOR OTHER SYSTEMS IS NOT DISTURBED.

SEE PLAN SHEET 1-T-100B

FOR CONTINUATION.

PATHWAY "B"

CAMPUS FIBER OPTIC CABLES TO RUN IN SUB-BASEMENT.

ATTACH CABLE RUNS TO SUB-BASEMENT CEILING USING

APPROPRIATE CABLE HANGERS.

CAMPUS FIBER OPTIC CABLES TO EXIT BUILDING

ONE AT THIS POINT AND TRAVEL THROUGH THE

UTILITY TUNNEL. SEE PLAN SHEET 1-T-508,

DETAIL 3 FOR ADDITIONAL INFORMATION.

J

MATCH LINE

1-T100A

4 4 4

4 4 4

2 2

2 2

93 105106108110

PATHWAY "A"

CAMPUS FIBER OPTIC CABLES TO RUN IN

SUB-BASEMENT. ATTACH CABLE RUNS TO

SUB-BASEMENT CEILING USING APPROPRIATE

CABLE HANGERS.

CAMPUS FIBER OPTIC CABLES TO EXIT BUILDING

ONE AT THIS POINT THROUGH EXISTING 6"

CONDUIT. SEE PLAN SHEET 1-T-508, DETAIL 3

FOR ADDITIONAL INFORMATION.

BUILDING KEY PLAN

N

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:2

A

M

1-T-100B

BUILDING 1 GROUND LEVEL

TECHNOLOGY FLOOR PLAN - AREA B

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

3/32" = 1'-0"

B1 - GROUND FLOOR - ELECTRICAL TECHNOLOGY PLAN - AREA B

TECHNOLOGY KEYNOTES

93 INSTALL APPROXIMATELY 382 NEW CAT6A DATA CABLES ON

THE GROUND FLOOR TO A MIXTURE OF 128 DUAL AND QUAD

WORK STATION LOCATIONS.

105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST

REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER

TO THE NEW CABLING.

106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM

THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR

ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED

SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD

DATA AND TELEPHONE CABLING ALL THE WAY TO THE

STATION END. ENSURE THAT ANY CABLES IN THE CEILING

AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA

AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY

UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH

PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO

IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING

RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING

FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM.

DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION

EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING

AREA THAT IS FOR OTHER SYSTEMS IS NOT DISTURBED.

112 PROVIDE A POWER POLE WITH 6 DATA CABLES TERMINATED

ONTO POWER POLE FACEPLATES.

GENERAL NOTES:

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF

CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED

TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN

IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO

OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH

CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH

PANEL IN ITS DESIGNATED TR.

E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED

WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH

PANEL. TEST FIBER WITH OPTICAL POWER METER AND

LIGHT SOURCE.

G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD

FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS

AS REQUIRED FOR A NEAT AND WORKMANLIKE

INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL

WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING

THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

SEE PLAN SHEET 1-T-100A

FOR CONTINUATION.

2 4 4 2 2 2 4 2 442 42 4

4 2 4 4

2 2

2 2

ELECTRICAL CLOSET

1068A

1-T-101A

MATCH LINE

1-T101A

2 2 2

94 105106108110

OI&T

1003A

5867687071

748287103107105

BUILDING KEY PLAN

N

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:3

A

M

1-T-101A

BUILDING 1 LEVEL 1 TECHNOLOGY

FLOOR PLAN - AREA A

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

3/32" = 1'-0"

B1 - LEVEL 1 - ELECTRICAL TECHNOLOGY PLAN - AREA A

1/2" = 1'-0"

B1 - OI&T / ROOM 1003A - TECHNOLOGY PLAN

TECHNOLOGY KEYNOTES

52 EXISTING 4' CONDUITS TO REMAIN.

54 EXISTING DATA RACK TO REMAIN.

58 PROVIDE AND INSTALL ONE NEW 7' X 19" DATA RACK WITH 2 EACH 3" WIDE DOUBLE-SIDED

VERTICAL WIRE MANAGERS.

59 PROVIDE AND INSTALL 2 EACH 3" WIDE DOUBLE-SIDED VERTICAL WIRE MANAGERS ON THE

EXISTING RACK.

64 INSTALL CABLE RUNWAY FROM FRONT WALL TO BACK WALL AS SHOWN IN TR DETAIL.

INSTALL CABLE RUNWAY FROM THE SIDE WALLS AS SHOWN. ELEVATE THE CABLE RUNWAY

12" ABOVE THE RACKS SO IT INTERSECTS THE WALL ABOVE THE DOORFRAME. CONNECT

RACKS TO THE CABLE RUNWAY USING RACK TO RUNWAY PLATES AND RACK ELEVATION

KITS. USE SEISMICALLY RATED BUTT AND JUNCTION SPLICE KITS.

67 INSTALL SEISMIC BRACING TO RACKS AND CABINETS AS REQUIRED. SEE SHEET 00-T-502

DETAIL 7 AND STRUCTURAL DETAILS.

68 PROVIDE AND INSTALL A FIBER PATCH PANEL ENCLOSURE FOR TERMINATION OF THE NEW

FIBER FROM THE NEW SERVER ROOM. FIBER PATCH PANEL ENCLOSURE SHALL BE SIZED

FOR 50% EXPANSION. SEE SPECIFICATIONS.

70 LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. TEST FIBER WITH OPTICAL

POWER METER AND LIGHT SOURCE.

71 PROVIDE AND INSTALL A RACK-MOUNTED, HORIZONTAL GROUNDING BUSBAR AT THE TOP

ON THE BACK SIDE OF EACH RACK.

74 PROVIDE AND INSTALL 13 EACH HIGH DENSITY, 1 RU ANGLED 48-PORT CAT6A PATCH

PANELS FOR TERMINATION OF THE NEW CAT6A CABLES. SEE SPECIFICATIONS AND RACK

ELEVATION DETAIL, SHEET 00-T-501.

82 PROVIDE AND INSTALL 4 EACH 48-PORT VOICE-GRADE PATCH PANELS FOR CROSS-

CONNECTION BETWEEN THE NEW DATA CABLES AND THE EXISTING TELEPHONE FEED

CABLE FIELD ON THE BACK WALL OF THE TR. MOUNT THESE AT THE TOP OF THE EXISTING

RACK. PROVIDE AND INSTALL 5 EACH 1 RU HORIZONTAL WIRE MANAGERS SO THERE IS A

WIRE MANAGER ABOVE AND BELOW EACH PATCH PANEL. PROVIDE AND INSTALL 4 EACH

50-PAIR CAT3 TELEPHONE FEED CABLES FROM THESE PATCH PANELS TO THE TELEPHONE

FEED CABLE TERMINATION FIELD. TERMINATE ONTO NEW 110-STYLE TERMINATION BLOCKS

FOR CROSS-CONNECTION TO THE TELEPHONE FEED CABLES. MOUNT BLOCKS ADJACENT

TO THE EXISTING TELEPHONE FEED CABLE FIELD. SEE SPECIFICATIONS AND RACK

ELEVATION DETAIL, SHEET 00-T-501.

87 PROVIDE AND INSTALL 6 EACH 1 RU HORIZONTAL WIRE MANAGERS SO THERE IS A WIRE

MANAGER ABOVE AND BELOW EACH DATA SWITCH. SEE RACK ELEVATION DETAIL.

EXISTING SWITCHES TO BE MOVED AND INSTALLED BY VA PERSONNEL.

94 INSTALL APPROXIMATELY 524 NEW CAT6A DATA CABLES ON THE 1ST FLOOR TO A MIXTURE

OF 179 DUAL AND QUAD WORK STATION LOCATIONS.

103 PROVIDE CABLE WATERFALLS FROM THE CABLE RUNWAY ONTO THE DATA RACKS.

105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND

OPERATIONAL UNTIL FINAL CUT-OVER TO THE NEW CABLING.

106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM THE TR ROOM OUT TO THE

CORRIDOR CEILING AREA FOR ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED

SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS.

107 ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS

NEED TO BE INSTALLED TO BOND ALL METAL ELEMENTS OF THE RACK AND RUNWAY

SYSTEM TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD DATA AND TELEPHONE

CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING

AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE ARE NOT

DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH

PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED

EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING

RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING WAS REMOVED.

110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY

BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION

EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER

SYSTEMS IS NOT DISTURBED.

GENERAL NOTES:

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR

ADDS FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO PROVIDE FOR 15% GROWTH

OF ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES, AS

SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH

PANEL IN ITS DESIGNATED TR.

E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. TEST FIBER WITH OPTICAL

POWER METER AND LIGHT SOURCE.

G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT.

PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND WORKMANLIKE INSTALLATION,

UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. SEE

SPECIFICATIONS.

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. REFER TO SHEET 00-T-501 FOR RACK ELEVATIONS.

1-T101A

42 24

4 4

2 2

2 2 2

94 105106108110

BUILDING KEY PLAN

N

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:3

A

M

1-T-101B

BUILDING 1 LEVEL 1 TECHNOLOGY

FLOOR PLAN - AREA B

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

3/32" = 1'-0"

B1 - LEVEL 1 - ELECTRICAL TECHNOLOGY PLAN - AREA B

GENERAL NOTES:

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF

CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED

TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN

IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO

OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH

CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH

PANEL IN ITS DESIGNATED TR.

E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED

WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH

PANEL. TEST FIBER WITH OPTICAL POWER METER AND

LIGHT SOURCE.

G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD

FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS

AS REQUIRED FOR A NEAT AND WORKMANLIKE

INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL

WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING

THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

TECHNOLOGY KEYNOTES

94 INSTALL APPROXIMATELY 524 NEW CAT6A DATA CABLES

ON THE 1ST FLOOR TO A MIXTURE OF 179 DUAL AND QUAD

WORK STATION LOCATIONS.

105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST

REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM

THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR

ALL NEW CABLING. PROVIDE AND INSTALL NEW

FIRE-RATED SLEEVES IN ALL FIRE-RATED WALLS ALONG

THE CABLE PATHWAYS.

108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL

OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE

STATION END. ENSURE THAT ANY CABLES IN THE CEILING

AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA

AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY

UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH

PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO

IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING

RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC

CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE

AND TERMINATION EQUIPMENT. ENSURE THAT ANY

CABLING IN THE CEILING AREA THAT IS FOR OTHER

SYSTEMS IS NOT DISTURBED.

4 2

2 2

2 2

4 2

2 4

4 2

2 2

4 4

1-T-102A

MATCH LINE

1-T102A

2 2

2 2

2 2

2 2

2 2

95 105106108110

OI&T

2000A

5867687071

758291103105107

BUILDING KEY PLAN

N

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

REVISION: DATE:

ARCHITECT:

U.S. Department of Veteran Affairs

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

MO ARCH REG. NO. 2012034754, EXP. 12/31/2022

MO ENGR REG. NO. 2014031351, EXP. 12/31/2022

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

STRUCTURAL ENGINEER

STAND STRUCTURAL ENGINEER

8234 ROBINSON ST.

OVERLAND PARK, KS 66204

(913) 214-9525

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

F U

L L

Y S

P R

IN

K

L E

R E

D

ABATEMENT

RIVERFRONT SAFETY AND HEALTH

11140 S. TOWNE SQ., STE 100

SAINT LOUIS, MO 63123

(314) 917--148

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

/2

/2

:0

:4

A

M

1-T-102A

BUILDING 1 LEVEL 2 TECHNOLOGY

FLOOR PLAN - AREA A

MIJ

ASPEN

RESUBMITTED 100% CONSTRUCTION DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

03/23/2021

657A4-20-700

John J. Pershing VA Medical Center 1500 N. Westwood Blvd.

Poplar Bluff, MO 63901

3/32" = 1'-0"

B1 - LEVEL 2 - ELECTRICAL TECHNOLOGY PLAN - AREA A

1/2" = 1'-0"

B1 - OI&T / ROOM 2000A - TECHNOLOGY PLAN

TECHNOLOGY KEYNOTES

51 REMOVE WALL-MOUNTED MONITOR, PC AND BRACKET FROM BACK WALL. THESE WILL

NEED TO BE RE-LOCATED BY OTHERS.

52 EXISTING 4' CONDUITS TO REMAIN.

53 EXISTING VERTICALLY RUN INSULATED PIPES.

54 EXISTING DATA RACK TO REMAIN.

58 PROVIDE AND INSTALL ONE NEW 7' X 19" DATA RACK WITH 2 EACH 3" WIDE

DOUBLE-SIDED VERTICAL WIRE MANAGERS.

59 PROVIDE AND INSTALL 2 EACH 3" WIDE DOUBLE-SIDED VERTICAL WIRE MANAGERS ON

THE EXISTING RACK.

61 INSTALL A RUN OF 2" UNISTRUT FROM THE FRONT WALL TO THE BACK WALL, AS SHOWN,

TO PROVIDE AN ANCHOR POINT FOR THE CABLE RUNWAY. ENSURE THAT THE CABINET

DOOR TO THE SECURITY SYSTEM POWER SUPPLY CAN OPEN ALL THE WAY.

62 EXISTING SECURITY SYSTEM BOX AND EXISTING POWER SUPPLY BOX MOUNTED ABOVE.

64 INSTALL CABLE RUNWAY FROM FRONT WALL TO BACK WALL AS SHOWN IN TR DETAIL.

INSTALL CABLE RUNWAY FROM THE SIDE WALLS AS SHOWN. ELEVATE THE CABLE

RUNWAY 12" ABOVE THE RACKS SO IT INTERSECTS THE WALL ABOVE THE DOORFRAME.

CONNECT RACKS TO THE CABLE RUNWAY USING RACK TO RUNWAY PLATES AND RACK

ELEVATION KITS. USE SEISMICALLY RATED BUTT AND JUNCTION SPLICE KITS.

67 INSTALL SEISMIC BRACING TO RACKS AND CABINETS AS REQUIRED. SEE SHEET 00-T-502

DETAIL 7 AND…