This document provides details for a federal contract opportunity for infrastructure upgrades at the John J. Pershing VA Medical Center. The Statement of Work involves construction documents and performance of work associated with upgrading the EHRM infrastructure including construction of a new fiber backbone, new server room, renovations to O&IT closets, HVAC cooling and controls upgrades, patch panel upgrades, cabling upgrades to CAT 6A, additional power and data drops for end user equipment, and power upgrades to O&IT closets and the telephone room. The contractor shall provide all services, materials, labor, supervision, safety certification and expertise for items described in the construction documents and specifications. The period of performance is estimated at 365 calendar days after Notice to Proceed. The principal NAICS code is 236220 for Commercial and Institutional Building Construction and the FSC is Y1DZ for Construction of Other Hospital buildings. The opportunity is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
STANDARD MOUNTING HEIGHTSANNOTATION
ELECTRICAL:
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS 48"
ANNUNCIATOR PANELS 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (HANDLE) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES (EXTERIOR) 24"
RECEPTACLES (GARAGES) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS) 48"
REMOTE INDICATING LIGHT (FINISHED AREAS) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
(AFF, AFG UNLESS NOTED OTHERWISE)
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE
CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
Z
BC
CB
B
DS
E
EP
LS
KS
NA
NM
SS
PS
PS
IC
CATV
FO
T
T/D
D
S
IC
UC
CCTV
S
WAP
#D/#TV
M
S
V
CR
DB
DB
DM
EL
EO
GB
KP
MD
PB
RE
EC
KT
GO
C
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
SERVER RACK, TWO-POST, FLOOR MOUNTED
3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD
GROUND BAR, TYPE AS NOTED
SERVER RACK, WALL MOUNTED
CABLE TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
TELEPHONE/DATA LINE
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
CODE BLUE PUSHBUTTON STATION
DUTY STATION
STAFF EMERGENCY ASSIST STATION
PATIENT EMERGENCY PULL CORD STATION
STAFF LOCATOR SENSOR
NURSE CALL KEY SWITCH
NURSE CALL VISUAL ANNUNCIATOR PANEL
NURSE CALL MASTER STATION
STAFF STATION (NORMAL, EMERGENCY & CODE BLUE)
DOME LIGHT, WALL MOUNTED
DOME LIGHT, CEILING MOUNTED
ZONE DOME LIGHT
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
UNDERGROUND COMMUNICATIONS LINE,
CABLING TYPE AS NOTED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
SERVER RACK, FOUR-POST, FLOOR MOUNTED
SERVER CABINET, FLOOR MOUNTED
CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY
CARD READER, PROXIMITY TYPE
DOOR BELL PUSHBUTTON
DOOR BELL CHIME
DOOR POSITION MONITOR
ELECTRIFIED LOCKING DEVICE, REQUEST TO EXIT SENSOR,
LATCH BOLT MONITOR, AND DOOR POSITION SWITCH
ELECTRIFIED LOCKING DEVICE
GLASS BREAK DETECTOR
INTRUSION DETECTION KEYPAD
INTRUSION DETECTION MOTION DETECTOR
DURESS PUSHBUTTON
REQUEST TO EXIT BUTTON
SINGLE VIEW SECURITY CAMERA
EMERGENCY CALL STATION
RFID KEY TAG READER
GATE OPENER
DUAL VIEW SECURITY CAMERA
180-DEGREE PANORAMIC VIEW SECURITY CAMERA
270-DEGREE PANORAMIC/MULTI-IMAGE VIEW
360-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
SECURITY CAMERA
PATIENT STATION WITH BED CONNECTOR
PATIENT STATION WITH CODE BLUE
SECURITY SYMBOLS
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#E = ELEVATOR, # = QUANTITY OF CABLES
#FMS = FACILITY MONITORING SYSTEM,
# = QUANTITY OF CABLES
NURSE CALL SYMBOLS
COMMUNICATION SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
X
W
V
U
T
S
R
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
WP - WEATHERPROOF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
00-T-001
TECHNOLOGY LEGEND
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-501
RACK ELEVATIONS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
J-HOOK, SIZES AS
NEEDED
1/4" OR 3/8" THREADED ROD OR #12 TO #8
HANGER WIRE ATTACHED TO STRUCTURE
ABOVE. (DO NOT USE EXISTING CEILING
HANGER WIRES. MUST HAVE ITS OWN
HANGER WIRE.)
TYPICAL J-HOOK, CABLE LOOP IN
CEILING ABOVE STATION JACK.
J-HOOK SIZE
1"
1-5/16" 2" 3" 4"
CAPACITY
J-HOOK CAPACITY FOR CAT6A CABLE
BASED ON 70% FILL
PARALLEL MOUNTING PERPENDICULAR MOUNTING
HEAVY DUTY (SEISMIC) CABLE
RUNWAY BUTT SPLICE
HEAVY DUTY (SEISMIC) CABLE
RUNWAY JUCTION SPLICE
V1
1A
1B
NOTE:
1. PERMANENTLY LABEL ALL WALL JACKS. COORDINATE LABELING SCHEME WITH FACILITY'S OIT.
2. NUMBER OF JACKS AND FACEPLATE IS DEPENDANT UPON NUMBER OF DROPS SHOWN FOR EACH LOCATION.
REFER TO FLOOR PLANS FOR EXACT NUMBER OF DROPS.
PROVIDE DOUBLE-GANG
BACKBOX WITH SINGLE-GANG
PLASTER RING OR WHERE
NECESSARY USE SINGLE-
GANG LOW VOLTAGE CUT-IN
RING WITH MOUNTING TABS
TO SOLIDLY HOLD RING.
PROVIDE HORIZONTAL
CABLING PER SPECIFICATIONS
WITH RJ45 CONNECTOR FOR
DATA CONNECTIONS.
TERMINATE CABLE IN TR AT
RACK-MOUNTED 48-PORT
MODULAR PATCH PANELS.
(TYPICAL)
J-BOLT, 5/16-18 THD'D
X 2.25" LONG, 2 PLACES
NUT, 5/16-18
HEX, STEEL 2 PLACES
WASHER, SLIT LOCK, FOR
Ø 5/16, SCR STEEL, 2 PLACES
Ø5/16" LAG BOLTS, FOR PLYWOOD
BACKER BOARDS OR Ø5/16" HEX
CAPBOLTS AND APPROPRIATE WALL
ANCHORS FOR CONCRETE WALLS
FLAT WAHWER,
FOR Ø5/16" BOLTS
3/4" FIRE-RETARDANT TREATED
PLYWOOD SPANNING AT LEAST TWO
BUILDING STUDS, OR IF THAT IS NOT
POSSIBLE, ANCHORED INTO AT LEAST
ONE STUD AND TOGGLED INTO THE
DRYWALL WITH 5/16" OR LARGER TOGGLE
BOLT WITH FENDER WASHERS.
A1-A035
WRAPAROUND CABLE
LABEL WITHIN 6" OF
EACH END OF THE CABLE
NOTE:
1. CPI 10562-001 OR EQUIVALENT.
2. SEISMIC INSTALLATION REQUIREMENTS SHALL BE APPROVED BY A LICENSED STRUCTURAL ENGINEER.
DOOR POSITION
SWITCH
ACCESSIBLE CEILING
PROVIDE DOUBLE-GANG
BACKBOX WITH SINGLE-GANG
PLASTER RING FOR DOOR
MOTION DETECTOR.
LOCATION PER PLANS.
3/4" CONDUIT
(TYPICAL, UNO)
ELECTRIFIED
LOCKSET/STRIKE
DOOR
PROVIDE 6"X6"X4" DEEP
JUNCTION BOX WITH
HINGED COVER.
LOCATE ON SECURE
SIDE OF DOOR.
PROVIDE 1" CONDUIT
BACK TO ACCESS
CONTROL PANEL.
PROVIDE DOUBLE-GANG
BACKBOX WITH
SINGLE-GANG PLASTER
RING FOR CARD READER.
LOCATION PER PLANS.
FLOOR
MAX. 48" AFF
OR MATCH
LIGHT SWITCH
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-502
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
J-HOOK DETAILS
SCALE: NTS
CABLE TRAY SUPPORT FROM RACK DETAIL
SCALE: NTS
CABLE TRAY SEISMIC RESTRAINTS DETAIL
SCALE: NTS
DATA OUTLET DETAIL
SCALE: NTS
CABLE TRAY SUPPORT DETAIL
SCALE: NTS
CABLE LABELING DETAIL
SCALE: NTS
SEISMIC BRACING
SCALE: NTS
CARD READER DETAIL
e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-503
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
1 TYPICAL ENCLOSURE SPECIFICATION
SCALE: NTS
2 TYPICAL ENCLOSURE FRONT WITH VERTICAL EXHAUST DUCT (VED)
SCALE: NTS
3 TYPICAL ENCLOSURE SIDE VIEW WITH VERTICAL EXHAUST DUCT (VED)
SCALE: NTS
4 TYPICAL ENCLOSURE TOP VIEW WITH VERTICAL EXHAUST DUCT (VED)
e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-504
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
1 TYPICAL RACK CONFIGURATION
SCALE: NTS
2 ISOMETRIC VIEW WITH DOORS AND VERTICAL EXHAUST DUCT (VED)
SCALE: NTS
3 FRONT VIEW DIMENSIONS
SCALE: NTS
4 FIBER DISTRIBUTING CABINET
SCALE: NTS
5 UTP PATCH PANEL
SCALE: NTS
6 UTP MEDIA
7 FIBER CASSETTE
e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-505
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
1 MAIN DISTRIBUTION AREA (A & B SIDES)
SCALE: NTS
2 CABLE TRAY
3 FIBER PATHWAY AND DETAILS
e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-506
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
1 SIDE ELEVATION ENCLOSURE
SCALE: NTS
2 REAR ELEVATION ENCLOSURES
SCALE: NTS
3 PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS
SCALE: NTS
4 EARTHING EXAMPLE (CISCO 6509) REF CISCO PRODUCT INSTALLATION GUIDE
5 TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB)
e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-507
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
DIVERSE ROUTING FOR CABLES FROM CABINETS TO HORIZONTAL DISTRIBUTION
AREAS
SCALE: NTS
STANDARD DENSITY EQUIPMENT DISTRIBUTOR ELEVATION FOR CABINETS
SCALE: NTS
DIVERSE ROUTING FOR CABLES FROM HORIZONTAL AREAS TO MAIN DISTRIBUTION
AREAS
SCALE: NTS
DIVERSE ROUTING FOR CABLES FROM MAIN DISTRIBUTION AREAS TO
TELECOMMUNICATIONS ROOMS
SCALE: NTS
TYPICAL END OF ROW HORIZONTAL DISTRIBUTION AREA
CR
DM
EL
RE
MULTI-CONDUCTOR CABLE
PB
LEGEND:
VASS POE GB
SWITCH (ETR)
RACK-MOUNTED
UPS (ETR)
PHYSICAL ACCESS
CONTROL
CABINET(S) (ETR)
PACS BATTERY
CABINET(S) (ETR)
FIRE ALARM
RELAY(S) (ETR)
CARD READERS AND
ASSOCIATED DEVICES PER
PLANS. (TYPICAL)
TR - COMMS ROOM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
00-T-508
TECHNOLOGY DETAILS
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
SCALE: NTS
2 BACKBONE CABLE ROUTING (REDUNDANT AND DIVERSE) - BUILDING 1
SCALE: NTS
3 BACKBONE CABLE ROUTING (REDUNDANT AND DIVERSE) - CAMPUS
1. PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM COMPATIBLE WITH THE EXISTING CAMPUS PACS SYSTEM. PROVIDE ALL UPGRADES TO THE EXISTING PACS SYSTEM TO INCORPORATE NEW DEVICES.
NOTES:
PHYSICAL ACCESS CONTROL SYSTEM (PACS) CARD READER SCHEDULE
TYPE
SYMBOL
TYPE
FORM FACTOR DESCRIPTION MOUNTING
MOUNTING
HEIGHT
LOCATION MODELS READ RANGE POWER COLOR COMMENTS NOTES
CR-1 OUTDOOR CARD READER
WALL, RE: DETAIL
8/00-T-502
48" TO TOP OF
BOX ABOVE
FINISHED
FLOOR
OUTDOOR
MATCH EXISTING
VA CARD READER
SYSTEM
4" MAXIMUM
85mA AVG/ 116mA PEAK AT
12VDC
BLACK
DUAL AUTHNTICATION CARD READER WITH KEYPAD
COMPATIBLE WITH EXISTING CAMPUS CARD READER SYSTEM,
WITH WEATHER HOOD, BUILT-IN HEATER, AND GASKET FOR
COLD WEATHER.
SCALE: NTS
1 SECURITY RISER DIAGRAM
4 PACS CARD READER SCHEDULE
DN
DN
DN
DN
4 2
2 2
2 2
2 2
ELECTRICAL CLOSET
01D
1-T-401
MATCH LINE
1-T100B
CORRIDOR
GA
2 4
4 4
2 2 2 2
2 2
2 2
93 105106108110
TO URGENT CARE TR.
CAMPUS FIBER OPTIC CABLES
TO GO DOWN THROUGH SLEEVES
AT THIS POINT TO SUB-BASEMENT.
CAMPUS FIBER OPTIC
CABLES TO GO DOWN
THROUGH SLEEVES AT THIS
POINT TO SUB-BASEMENT.
CAMPUS FIBER OPTIC CABLES TO RUN IN SUB-BASEMENT.
ATTACH CABLE RUNS TO SUB-BASEMENT CEILING USING
APPROPRIATE CABLE HANGERS AND RUN WITH OTHER
CABLES AND CONDUITS THROUGH THE EXISTING HANGERS.
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:2
A
M
1-T-100A
BUILDING 1 GROUND LEVEL
TECHNOLOGY FLOOR PLAN - AREA A
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/32" = 1'-0"
B1 - GROUND FLOOR - ELECTRICAL TECHNOLOGY PLAN - AREA A
GENERAL NOTES:
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF
CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED
TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN
IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO
OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH
CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH
PANEL IN ITS DESIGNATED TR.
E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED
WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH
PANEL. TEST FIBER WITH OPTICAL POWER METER AND
LIGHT SOURCE.
G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD
FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS
AS REQUIRED FOR A NEAT AND WORKMANLIKE
INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL
WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING
THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
TECHNOLOGY KEYNOTES
93 INSTALL APPROXIMATELY 382 NEW CAT6A DATA CABLES ON
THE GROUND FLOOR TO A MIXTURE OF 128 DUAL AND QUAD
WORK STATION LOCATIONS.
105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST
REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER
TO THE NEW CABLING.
106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM
THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR
ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED
SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD
DATA AND TELEPHONE CABLING ALL THE WAY TO THE
STATION END. ENSURE THAT ANY CABLES IN THE CEILING
AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA
AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY
UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH
PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO
IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING
RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING
FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM.
DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION
EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING
AREA THAT IS FOR OTHER SYSTEMS IS NOT DISTURBED.
SEE PLAN SHEET 1-T-100B
FOR CONTINUATION.
PATHWAY "B"
CAMPUS FIBER OPTIC CABLES TO RUN IN SUB-BASEMENT.
ATTACH CABLE RUNS TO SUB-BASEMENT CEILING USING
APPROPRIATE CABLE HANGERS.
CAMPUS FIBER OPTIC CABLES TO EXIT BUILDING
ONE AT THIS POINT AND TRAVEL THROUGH THE
UTILITY TUNNEL. SEE PLAN SHEET 1-T-508,
DETAIL 3 FOR ADDITIONAL INFORMATION.
J
MATCH LINE
1-T100A
4 4 4
4 4 4
2 2
2 2
93 105106108110
PATHWAY "A"
CAMPUS FIBER OPTIC CABLES TO RUN IN
SUB-BASEMENT. ATTACH CABLE RUNS TO
SUB-BASEMENT CEILING USING APPROPRIATE
CABLE HANGERS.
CAMPUS FIBER OPTIC CABLES TO EXIT BUILDING
ONE AT THIS POINT THROUGH EXISTING 6"
CONDUIT. SEE PLAN SHEET 1-T-508, DETAIL 3
FOR ADDITIONAL INFORMATION.
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:2
A
M
1-T-100B
BUILDING 1 GROUND LEVEL
TECHNOLOGY FLOOR PLAN - AREA B
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/32" = 1'-0"
B1 - GROUND FLOOR - ELECTRICAL TECHNOLOGY PLAN - AREA B
TECHNOLOGY KEYNOTES
93 INSTALL APPROXIMATELY 382 NEW CAT6A DATA CABLES ON
THE GROUND FLOOR TO A MIXTURE OF 128 DUAL AND QUAD
WORK STATION LOCATIONS.
105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST
REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER
TO THE NEW CABLING.
106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM
THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR
ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED
SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD
DATA AND TELEPHONE CABLING ALL THE WAY TO THE
STATION END. ENSURE THAT ANY CABLES IN THE CEILING
AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA
AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY
UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH
PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO
IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING
RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING
FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM.
DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION
EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING
AREA THAT IS FOR OTHER SYSTEMS IS NOT DISTURBED.
112 PROVIDE A POWER POLE WITH 6 DATA CABLES TERMINATED
ONTO POWER POLE FACEPLATES.
GENERAL NOTES:
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF
CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED
TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN
IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO
OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH
CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH
PANEL IN ITS DESIGNATED TR.
E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED
WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH
PANEL. TEST FIBER WITH OPTICAL POWER METER AND
LIGHT SOURCE.
G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD
FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS
AS REQUIRED FOR A NEAT AND WORKMANLIKE
INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL
WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING
THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
SEE PLAN SHEET 1-T-100A
FOR CONTINUATION.
2 4 4 2 2 2 4 2 442 42 4
4 2 4 4
2 2
2 2
ELECTRICAL CLOSET
1068A
1-T-101A
MATCH LINE
1-T101A
2 2 2
94 105106108110
OI&T
1003A
5867687071
748287103107105
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
1-T-101A
BUILDING 1 LEVEL 1 TECHNOLOGY
FLOOR PLAN - AREA A
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/32" = 1'-0"
B1 - LEVEL 1 - ELECTRICAL TECHNOLOGY PLAN - AREA A
1/2" = 1'-0"
B1 - OI&T / ROOM 1003A - TECHNOLOGY PLAN
TECHNOLOGY KEYNOTES
52 EXISTING 4' CONDUITS TO REMAIN.
54 EXISTING DATA RACK TO REMAIN.
58 PROVIDE AND INSTALL ONE NEW 7' X 19" DATA RACK WITH 2 EACH 3" WIDE DOUBLE-SIDED
VERTICAL WIRE MANAGERS.
59 PROVIDE AND INSTALL 2 EACH 3" WIDE DOUBLE-SIDED VERTICAL WIRE MANAGERS ON THE
EXISTING RACK.
64 INSTALL CABLE RUNWAY FROM FRONT WALL TO BACK WALL AS SHOWN IN TR DETAIL.
INSTALL CABLE RUNWAY FROM THE SIDE WALLS AS SHOWN. ELEVATE THE CABLE RUNWAY
12" ABOVE THE RACKS SO IT INTERSECTS THE WALL ABOVE THE DOORFRAME. CONNECT
RACKS TO THE CABLE RUNWAY USING RACK TO RUNWAY PLATES AND RACK ELEVATION
KITS. USE SEISMICALLY RATED BUTT AND JUNCTION SPLICE KITS.
67 INSTALL SEISMIC BRACING TO RACKS AND CABINETS AS REQUIRED. SEE SHEET 00-T-502
DETAIL 7 AND STRUCTURAL DETAILS.
68 PROVIDE AND INSTALL A FIBER PATCH PANEL ENCLOSURE FOR TERMINATION OF THE NEW
FIBER FROM THE NEW SERVER ROOM. FIBER PATCH PANEL ENCLOSURE SHALL BE SIZED
FOR 50% EXPANSION. SEE SPECIFICATIONS.
70 LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. TEST FIBER WITH OPTICAL
POWER METER AND LIGHT SOURCE.
71 PROVIDE AND INSTALL A RACK-MOUNTED, HORIZONTAL GROUNDING BUSBAR AT THE TOP
ON THE BACK SIDE OF EACH RACK.
74 PROVIDE AND INSTALL 13 EACH HIGH DENSITY, 1 RU ANGLED 48-PORT CAT6A PATCH
PANELS FOR TERMINATION OF THE NEW CAT6A CABLES. SEE SPECIFICATIONS AND RACK
ELEVATION DETAIL, SHEET 00-T-501.
82 PROVIDE AND INSTALL 4 EACH 48-PORT VOICE-GRADE PATCH PANELS FOR CROSS-
CONNECTION BETWEEN THE NEW DATA CABLES AND THE EXISTING TELEPHONE FEED
CABLE FIELD ON THE BACK WALL OF THE TR. MOUNT THESE AT THE TOP OF THE EXISTING
RACK. PROVIDE AND INSTALL 5 EACH 1 RU HORIZONTAL WIRE MANAGERS SO THERE IS A
WIRE MANAGER ABOVE AND BELOW EACH PATCH PANEL. PROVIDE AND INSTALL 4 EACH
50-PAIR CAT3 TELEPHONE FEED CABLES FROM THESE PATCH PANELS TO THE TELEPHONE
FEED CABLE TERMINATION FIELD. TERMINATE ONTO NEW 110-STYLE TERMINATION BLOCKS
FOR CROSS-CONNECTION TO THE TELEPHONE FEED CABLES. MOUNT BLOCKS ADJACENT
TO THE EXISTING TELEPHONE FEED CABLE FIELD. SEE SPECIFICATIONS AND RACK
ELEVATION DETAIL, SHEET 00-T-501.
87 PROVIDE AND INSTALL 6 EACH 1 RU HORIZONTAL WIRE MANAGERS SO THERE IS A WIRE
MANAGER ABOVE AND BELOW EACH DATA SWITCH. SEE RACK ELEVATION DETAIL.
EXISTING SWITCHES TO BE MOVED AND INSTALLED BY VA PERSONNEL.
94 INSTALL APPROXIMATELY 524 NEW CAT6A DATA CABLES ON THE 1ST FLOOR TO A MIXTURE
OF 179 DUAL AND QUAD WORK STATION LOCATIONS.
103 PROVIDE CABLE WATERFALLS FROM THE CABLE RUNWAY ONTO THE DATA RACKS.
105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND
OPERATIONAL UNTIL FINAL CUT-OVER TO THE NEW CABLING.
106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM THE TR ROOM OUT TO THE
CORRIDOR CEILING AREA FOR ALL NEW CABLING. PROVIDE AND INSTALL NEW FIRE-RATED
SLEEVES IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS.
107 ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS
NEED TO BE INSTALLED TO BOND ALL METAL ELEMENTS OF THE RACK AND RUNWAY
SYSTEM TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL OLD DATA AND TELEPHONE
CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING
AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE ARE NOT
DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH
PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED
EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING
RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING WAS REMOVED.
110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY
BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION
EQUIPMENT. ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER
SYSTEMS IS NOT DISTURBED.
GENERAL NOTES:
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR
ADDS FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO PROVIDE FOR 15% GROWTH
OF ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES, AS
SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH
PANEL IN ITS DESIGNATED TR.
E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. TEST FIBER WITH OPTICAL
POWER METER AND LIGHT SOURCE.
G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT.
PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND WORKMANLIKE INSTALLATION,
UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. SEE
SPECIFICATIONS.
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. REFER TO SHEET 00-T-501 FOR RACK ELEVATIONS.
1-T101A
42 24
4 4
2 2
2 2 2
94 105106108110
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:3
A
M
1-T-101B
BUILDING 1 LEVEL 1 TECHNOLOGY
FLOOR PLAN - AREA B
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/32" = 1'-0"
B1 - LEVEL 1 - ELECTRICAL TECHNOLOGY PLAN - AREA B
GENERAL NOTES:
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF
CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED
TO PROVIDE FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN
IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
D. EACH NEW DATA DROP LOCATION WILL CONSIST OF TWO
OR FOUR CAT6A CABLES, AS SHOWN ON THE PLANS. EACH
CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH
PANEL IN ITS DESIGNATED TR.
E. EXISTING DATA DROP LOCATIONS SHALL BE RE-USED
WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH
PANEL. TEST FIBER WITH OPTICAL POWER METER AND
LIGHT SOURCE.
G. PROVIDE 1 EACH SMALL DIAMETER CAT6A PATCH CORD
FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS
AS REQUIRED FOR A NEAT AND WORKMANLIKE
INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL
WIRE MANAGERS AS APPLICABLE. SEE SPECIFICATIONS.
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING
THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
TECHNOLOGY KEYNOTES
94 INSTALL APPROXIMATELY 524 NEW CAT6A DATA CABLES
ON THE 1ST FLOOR TO A MIXTURE OF 179 DUAL AND QUAD
WORK STATION LOCATIONS.
105 NOTE: ALL EXISTING DATA CABLES AND CIRCUITS MUST
REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
106 PROVIDE AND INSTALL NEW FIRE-RATED SLEEVES FROM
THE TR ROOM OUT TO THE CORRIDOR CEILING AREA FOR
ALL NEW CABLING. PROVIDE AND INSTALL NEW
FIRE-RATED SLEEVES IN ALL FIRE-RATED WALLS ALONG
THE CABLE PATHWAYS.
108 AFTER CUT-OVER TO THE NEW CABLING DEMOLISH ALL
OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE
STATION END. ENSURE THAT ANY CABLES IN THE CEILING
AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA
AND TELEPHONE ARE NOT DISTURBED. BLANK OFF ANY
UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH
PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO
IT DATA AND TELEPHONE, TO REMAIN IN THE EXISTING
RACK. FIRESTOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
110 AFTER CUT-OVER REMOVE ALL OLD IT FIBER OPTIC
CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE
AND TERMINATION EQUIPMENT. ENSURE THAT ANY
CABLING IN THE CEILING AREA THAT IS FOR OTHER
SYSTEMS IS NOT DISTURBED.
4 2
2 2
2 2
4 2
2 4
4 2
2 2
4 4
1-T-102A
MATCH LINE
1-T102A
2 2
2 2
2 2
2 2
2 2
95 105106108110
OI&T
2000A
5867687071
758291103105107
BUILDING KEY PLAN
N
AREA OF WORK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917--148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:0
:4
A
M
1-T-102A
BUILDING 1 LEVEL 2 TECHNOLOGY
FLOOR PLAN - AREA A
MIJ
ASPEN
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
3/32" = 1'-0"
B1 - LEVEL 2 - ELECTRICAL TECHNOLOGY PLAN - AREA A
1/2" = 1'-0"
B1 - OI&T / ROOM 2000A - TECHNOLOGY PLAN
TECHNOLOGY KEYNOTES
51 REMOVE WALL-MOUNTED MONITOR, PC AND BRACKET FROM BACK WALL. THESE WILL
NEED TO BE RE-LOCATED BY OTHERS.
52 EXISTING 4' CONDUITS TO REMAIN.
53 EXISTING VERTICALLY RUN INSULATED PIPES.
54 EXISTING DATA RACK TO REMAIN.
58 PROVIDE AND INSTALL ONE NEW 7' X 19" DATA RACK WITH 2 EACH 3" WIDE
DOUBLE-SIDED VERTICAL WIRE MANAGERS.
59 PROVIDE AND INSTALL 2 EACH 3" WIDE DOUBLE-SIDED VERTICAL WIRE MANAGERS ON
THE EXISTING RACK.
61 INSTALL A RUN OF 2" UNISTRUT FROM THE FRONT WALL TO THE BACK WALL, AS SHOWN,
TO PROVIDE AN ANCHOR POINT FOR THE CABLE RUNWAY. ENSURE THAT THE CABINET
DOOR TO THE SECURITY SYSTEM POWER SUPPLY CAN OPEN ALL THE WAY.
62 EXISTING SECURITY SYSTEM BOX AND EXISTING POWER SUPPLY BOX MOUNTED ABOVE.
64 INSTALL CABLE RUNWAY FROM FRONT WALL TO BACK WALL AS SHOWN IN TR DETAIL.
INSTALL CABLE RUNWAY FROM THE SIDE WALLS AS SHOWN. ELEVATE THE CABLE
RUNWAY 12" ABOVE THE RACKS SO IT INTERSECTS THE WALL ABOVE THE DOORFRAME.
CONNECT RACKS TO THE CABLE RUNWAY USING RACK TO RUNWAY PLATES AND RACK
ELEVATION KITS. USE SEISMICALLY RATED BUTT AND JUNCTION SPLICE KITS.
67 INSTALL SEISMIC BRACING TO RACKS AND CABINETS AS REQUIRED. SEE SHEET 00-T-502
DETAIL 7 AND…