TP09 Final Drawings 08 657A4-20-700 Resubmitted SS 100 percent CD Drawings-Mechanical.pdf
PDF 3 MB Posted
- Attached to
- Y1DZ--657A4-20-700, EHRM INFRASTRUCTURE UPGRADES
- Solicitation number
- 36C25521R0103
About this file
This federal contract opportunity solicitation is for construction services to upgrade infrastructure at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The scope of work includes constructing a new fiber backbone and server room, renovating O&IT closets, upgrading cabling and power, and adding additional data and power drops. Work will be phased to avoid disrupting medical center operations. The performance period is estimated at 365 days from notice to proceed. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 15. The primary NAICS code is 236220 for commercial and institutional building construction. The estimated value is $39.5 million.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CWR
CWS
PD
CD
LPC
LPS
MPC
MPS
HPC
HPS H
T
H
T
AV
26-P-3
MH-100
MH-100
ETR
GENERAL DUCT SYMBOLSVALVE SYMBOLSHVAC PIPING SYMBOLS
PUMP NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (PUMP)
ANCHOR
ECCENTRIC REDUCER
DROP IN PIPE
STRAINER
FLOAT & THERMOSTATIC TRAP SET W/
PIPING ACCESSORIES
PIPING ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING
THERMOSTATIC MIXING VALVE
ELBOW DOWN WITH SHUT-OFF VALVE
TEE DOWN WITH SHUT-OFF VALVE (SOV)
TEE UP WITH SHUT-OFF VALVE (SOV)
FLANGE CONNECTION
ELBOW DOWN
ELBOW UP
TEE DOWN
ELBOW UP WITH SHUT-OFF VALVE (SOV)
TEE UP
UNION
PRESSURE REDUCING VALVE
REDUCER
BALL VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
GATE VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
GLOBE VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
AUTOMATIC AIR VENT
MECHANICAL PLAN KEY NOTE
NEW WORK TO EXISTING WORK
CONNECTION POINT
DETAIL NUMBER
SHEET NUMBER
PIPE FITTINGS AND ACCESSORIES
SHEET NUMBER
SECTION NUMBER
CONDENSATE DRAIN (CD)
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
T
T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
S
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIONALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
M
M METER, SI UNIT
M/s METERS PER SECOND (OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
H
H HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
C
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING
TOWER
CWS CONDENSER WATER SUPPLY (FROM COOLING
TOWER)
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
EXISTING TO REMAIN
LIMIT OF DEMOLITION
A
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACDTP AUTOMATIC CONTROL DMPR, TWO POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
10"x8"AUTOMATIC BALANCING CONTROL VALVE
WYE STRAINER (WITH BALL VALVE
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
QUICK-COUPLE HOSE CONNECTOR
WYE STRAINER WITH VALVED DRAIN AND
EXISTING TO BE REMOVED
EXISTING TO REMAIN
BRANCH DUCT WITH 45° RECTANGLE-ROUND
BRANCH FITTING AND MANUAL VOLUME DAMPER
BRANCH DUCT WITH BELL-MOUTH FITTING &
MANUAL VOLUME CONTROL DAMPER
RETURN, EXHAUST, OR OUTSIDE AIR
DUCT DOWN
SUPPLY AIR DUCT UP
RETURN, EXHAUST, OR OUTSIDE AIR
DUCT UP
ELBOW WITH TURNING VANES
TYPE
CFM OF AIR DEVICE
MOTORIZED DAMPER
VOLUME DAMPER
THERMOSTAT
FIRE DAMPER
FIRE SMOKE DAMPER
SMOKE DAMPER
MANUAL VOLUME DAMPER
SQUARE TO ROUND TRANSITION
RISER DESIGNATION
HUMIDISTAT
CD-1
BACKDRAFT DAMPER
SUPPLY AIR DUCT DOWN
DUCT MOUNTED SMOKE DETECTOR
(SD=SUPPLY/RD=RETURN)
NEW DUCT (INSIDE DIMENSIONS: W x D)
LOUVER
DUCT WITH SOUND LINING
DAMPERS: (BD, FD, FSD, MD, SD, VD)
GAS COCK
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER SUPPLY (CWS)
CONDENSER WATER RETURN (CWR)
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
CHILLED WATER SUPPLY
HIGH PRESSURE STEAM CONDENSATE (HPC)
HIGH PRESSURE STEAM SUPPLY (HPS)
MEDIUM PRESSURE STEAM CONDENSATE (MPC)
MEDIUM PRESSURE STEAM SUPPLY (MPS)
LOW PRESSURE STEAM CONDENSATE (LPC)
LOW PRESSURE STEAM SUPPLY (LPS)
CONDENSATE PUMP DISCHARGE (PD)
EXPANSION JOINT
TRIPLE DUTY VALVE WITH PRESSURE PORTS
BALANCING VALVE WITH PRESSURE PORTS
SOLENOID VALVE
STRAINER WITH BLOWOFF
EJ
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM RELIEF VALVE
PRESSURE / VACUUM SWITCH
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTING
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
BACK DRAFT DAMPER
BDD
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
MAKE-UP WATER
CHILLED GLYCOL-WATER RETURN
CHILLED GLYCOL-WATER SUPPLY
GHS
GHR
GCR
GCS
MW
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURNGRR
GRS
VACUUM CONDENSATE RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
FEEDWATER SAMPLE (DEAERATOR)
BOILER WATER SAMPLE
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF
TUBE CLEANER WATER SUPPLY
OVERFLOW
TEMPERATURE SENSOR
HUMIDITY SENSOR
DUCT W/DAMPERS
DIFFUSERS,GRILLES, FLEX CONNECTIONS
FITTINGS & TRANSITIONS
SOFTENED WATERSW
BRINE & SOFT WATER
PLANT PIPING
STEAM
Y
YR YEAR
W
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
U
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
& HOSE CONNECTION)
ABBREVIATIONS
SD
VD
FD
BD
MD
BD
ANNOTATION
GENERAL NOTES:
1. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY
ILLUSTRATE THE SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN
NATURE.
2. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE
INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT
ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT WITH
APPLICABLE CODES.
3. REFER TO FLOW DIAGRAMS, DETAILS AND SPECIFICATIONS FOR
REQUIRED PIPING, VALVES AND GAUGES.
4. MECHANICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH
BUILDING DISCIPLINES, HOWEVER DO NOT SHOW EVERY OFFSET IN
DUCT OR PIPING REQUIRED FOR INSTALLATION. COORDINATION WITH
OTHER TRADES IS REQUIRED.
5. DUCT SIZES SHOWN REPRESENT INSIDE CLEAR DIMENSIONS.
CONTRACTOR SHALL ADJUST SHEET METAL SIZE TO ACCOUNT FOR
LINER THICKNESS WHEN LINER IS ALLOWED PER THE CONTRACT
DOCUMENTS.
6. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE
SPECIFICATION SECTION "PAINTING".
7. PIPING CONNECTIONS TO MECHANCIAL EQUIPMENT SHOWN ON
DRAWINGS IS APPROXIMATE. CONTRACTOR SHALL ADJUST ROUTING
TO MATCH APPROVED EQUIPMENT CONNECTIONS AND
MANUFACTURERS RECOMMENDATIONS.
8. COORDINATE FAN COIL (FCU) AND VARIABLE AIR VOLUME (VAV) UNIT
RIGHT OR LEFT HAND COIL CONNECTIONS WITH PIPING PLANS.
9. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT
SHALL BE SIZED BY THE GAS-FIRED EQUIPMENT MANUFACTURER
BASED ON THE SPECIFIC PIPE ROUTING AND ELEVATIONS FOR THIS
PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND
LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND
COMBUSTION AIR PIPING MATERIALS.
10. ALL FLOOR MOUNTED HVAC EQUIPMENT SHALL HAVE A 6" TALL
HOUSEKEEPING PAD. REFER TO STRUCTURAL PLANS AND DETAILS
FOR CONCRETE PAD CONSTRUCTION.
11. THE MECHANICAL CONTRACTOR SHALL NOT USE SADDLE TAPS FOR
ANY NEW HVAC DUCTING AND PIPING CONSTRUCTION. COORDINATE
WITH THE VA COR FOR PREFERRED CONNECTION METHODS.
12. THE MECHANICAL CONTRACTOR SHALL NOT USE WOOD SUPPORTS
FOR INSTALLATION OF ANY NEW HVAC EQUIPMENT.
13. THE CONTROLS CONTRACTOR SHALL TIE ALL NEW HVAC CONTROLS
INTO THE EXISTING JOHNSON CONTROLS SYSTEM.
14. THE MECHANICAL CONTRACTOR SHALL OPTIMIZE THE PHASING OF
ALL HVAC DEMOLITION AND NEW HVAC CONSTRUCTION TO AVOID
IMPACTING THE DAILY VA FACILITY OPERATIONS. COORDINATE WITH
THE VA COR FOR PHASING AND OPERATION SCHEDULES.
FSD COMBINATION FIRE / SMOKE DAMPER
BUILDING NUMBER WHERE EQUIPMENT
IS LOCATED
26-TU-1-1
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT)
BUILDING NUMBER WHERE EQUIPMENT
IS LOCATED
SERVED BY AIR HANDLER UNIT NO. 1
TERMINAL UNIT TAG
MECHANICAL EQUIPMENT TAG
FD FLOOR DRAIN
I
1 OWNER FURNISHED, CONTRACTOR
INSTALLED EQUIPMENT DESIGNATION
RD
BO
BWS
CF
CHR
CHS
CBD
FWPD
FWPS
FWS
HHR
HHS
HPWR
HPWS
TC
OFL
F&T TRAP
CAP
CONNECTION - BOTTOM, 45° OR 90°
RS
RL
RD
RDB
RV
REFRIGERANT DISCHARGE BYPASS (RDB)
REFRIGERANT SUCTION (RS)
REFRIGERANT DISCHARGE (HOT GAS) (RD)
REFRIGERANT LIQUID (RL)
REFRIGERANT VENT (RV)
REFRIGERANT SIGHT GLASS
REFRIGERANT
CONNECTION - SIDE
CONNECTION - TOP, 45° OR 90°
DIRECTION OF FLOW
QUICK-COUPLE HOSE CONNECTOR
P-TRAP
TRAP PRIMER
M
LC
TRAP PRIMER WITH DISTRIBUTION UNIT
WATER LEVEL CONTROLLER
FLOW METER
EQUIPMENT WITH FLEXIBLE DUCT CONNECTION
INSULATED FLEXIBLE DUCT (MAX. 5'-0" LONG)
LINEAR SLOT DIFFUSER
TYPE
CFM OF AIR DEVICE
EG-1
FSD
THIS LEGEND DEFINING TYPICAL ABBREVIATIONS AND SYMBOLS IS INTENDED TO BE AN OVERALL LEGEND FOR ALL PROJECTS. PLEASE UNDERSTAND THAT NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR EVERY PROJECT. MANY OF THE SYMBOLS WILL BE UTILIZED IN DETAILS AND DIAGRAMS VICE PLAN SHEETS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:3
A
M
M-000
MECHANICAL LEGEND AND
ABBREVIATIONS
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
DN
DN
1-M-401
1-M-401
OI&T SERVER ROOM
52B
OI&T
1-M-401
1-M-401
OI&T
ELECTRICAL CLOSET
01D
CORRIDOR
GA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:5
A
M
1-M-100
BLDG 1 - MECHANICAL GROUND FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL GROUND FLOOR PLAN1
HD-1
1-M-101
1-M-101
OI&T
1003A
CORRIDOR
1A
ELECTRICAL CLOSET
1068A
ACU-1
OI&T
1003A
1 5 9
3/4" CD
3/4" CD
OI&T
1003A
D4
T
D8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:0
A
M
1-M-101
BLDG 1 - MECHANICAL FIRST FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
MECHANICAL DEMO PLAN NOTES
D4 REMOVE DUCTWORK AND ALL ASSOCIATED ACCESSORIES BACK TO NEAREST
BRANCH AND CAP.
D8 REMOVE THERMOSTAT AND ALL ASSOCIATED ACCESSORIES.
MECHANICAL PLAN NOTES
1 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM FAN COIL UNIT TO THE
ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE ROOF.
5 ROUTE CONDENSATE LINE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR
DRAIN BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. TERMINATE WITH
MINIMUM 2" AIR GAP. COMBINE CONDENSATE FROM ALL FAN COIL UNITS INTO A
SINGLE CONDENSATE RISER.
9 INSTALL SPLIT SYSTEM FAN COIL UNIT ABOVE TELECOM ROOM DOOR. COORDINATE
EXACT LOCATION WITH EXISTING CABLES.
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL FIRST FLOOR PLAN1
N
1/2" = 1'-0"
OI&T 1003A ENLARGED PLAN2
N
1/2" = 1'-0"
OI&T 1003A ENLARGED DEMOLITION PLAN3
1-M-102
1-M-102
OI&T
2000A
ELECTRICAL CLOSET
2000B
CORRIDOR
2A
ACU-2
OI&T
2000A
1 5 9
3/4" CD
3/4" CD5
OI&T
2000A
D4
T
D8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:0
A
M
1-M-102
BLDG 1 - MECHANICAL SECOND FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
MECHANICAL DEMO PLAN NOTES
D4 REMOVE DUCTWORK AND ALL ASSOCIATED ACCESSORIES BACK TO NEAREST
BRANCH AND CAP.
D8 REMOVE THERMOSTAT AND ALL ASSOCIATED ACCESSORIES.
MECHANICAL PLAN NOTES
1 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM FAN COIL UNIT TO THE
ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE ROOF.
5 ROUTE CONDENSATE LINE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR
DRAIN BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. TERMINATE WITH
MINIMUM 2" AIR GAP. COMBINE CONDENSATE FROM ALL FAN COIL UNITS INTO A
SINGLE CONDENSATE RISER.
9 INSTALL SPLIT SYSTEM FAN COIL UNIT ABOVE TELECOM ROOM DOOR. COORDINATE
EXACT LOCATION WITH EXISTING CABLES.
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL SECOND FLOOR PLAN1
N
1/2" = 1'-0"
OI&T 2000A ENLARGED PLAN2
N
OI&T 2000A ENLARGED DEMOLITION PLAN3
1-M-103
1-M-103
OI&T
3000A
ELECTRICAL CLOSET
3000B
CORRIDOR
3A
ACU-3
OI&T
3000A
1 5 9
3/4" CD
3/4" CD
REFRIGERANT LINE
FROM ABOVE
OI&T
3000A
D4
T
D8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:1
A
M
1-M-103
BLDG 1 - MECHANICAL THIRD FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
MECHANICAL DEMO PLAN NOTES
D4 REMOVE DUCTWORK AND ALL ASSOCIATED ACCESSORIES BACK TO NEAREST
BRANCH AND CAP.
D8 REMOVE THERMOSTAT AND ALL ASSOCIATED ACCESSORIES.
MECHANICAL PLAN NOTES
1 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM FAN COIL UNIT TO THE
ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE ROOF.
5 ROUTE CONDENSATE LINE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR
DRAIN BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. TERMINATE WITH
MINIMUM 2" AIR GAP. COMBINE CONDENSATE FROM ALL FAN COIL UNITS INTO A
SINGLE CONDENSATE RISER.
9 INSTALL SPLIT SYSTEM FAN COIL UNIT ABOVE TELECOM ROOM DOOR. COORDINATE
EXACT LOCATION WITH EXISTING CABLES.
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL THIRD FLOOR PLAN1
N
1/2" = 1'-0"
OI&T 3000A ENLARGED PLAN2
N
OI&T 3000A ENLARGED DEMOLITION PLAN3
1-M-104
1-M-104
OI&T
4054C
ELECTRICAL CLOSET
4054B
CORRIDOR
4A
ACU-4
OI&T
4054C
1 5 9
3/4" CD
3/4" CD5
REFRIGERANT LINE
FROM ABOVE
OI&T
4054C
D4
T
D8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:1
A
M
1-M-104
BLDG 1 - MECHANICAL FOURTH FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
MECHANICAL DEMO PLAN NOTES
D4 REMOVE DUCTWORK AND ALL ASSOCIATED ACCESSORIES BACK TO NEAREST
BRANCH AND CAP.
D8 REMOVE THERMOSTAT AND ALL ASSOCIATED ACCESSORIES.
MECHANICAL PLAN NOTES
1 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM FAN COIL UNIT TO THE
ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE ROOF.
5 ROUTE CONDENSATE LINE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR
DRAIN BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. TERMINATE WITH
MINIMUM 2" AIR GAP. COMBINE CONDENSATE FROM ALL FAN COIL UNITS INTO A
SINGLE CONDENSATE RISER.
9 INSTALL SPLIT SYSTEM FAN COIL UNIT ABOVE TELECOM ROOM DOOR. COORDINATE
EXACT LOCATION WITH EXISTING CABLES.
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL FOURTH FLOOR PLAN1
N
1/2" = 1'-0"
OI&T 4054C ENLARGED PLAN2
N
OI&T 4054C ENLARGED DEMOLITION PLAN3
1-M-105
1-M-105
OI&T
5A1
ELECTRICAL CLOSET
CORRIDOR
5A
ACU-5
OI&T
5A1
1 5 9
3/4" CD
3/4" CD5
REFRIGERANT LINES
FROM ABOVE
OI&T
5A1
D4
T
D8 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:2
A
M
1-M-105
BLDG 1 - MECHANICAL FIFTH FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
MECHANICAL DEMO PLAN NOTES
D4 REMOVE DUCTWORK AND ALL ASSOCIATED ACCESSORIES BACK TO NEAREST
BRANCH AND CAP.
D8 REMOVE THERMOSTAT AND ALL ASSOCIATED ACCESSORIES.
MECHANICAL PLAN NOTES
1 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM FAN COIL UNIT TO THE
ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE ROOF.
5 ROUTE CONDENSATE LINE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR
DRAIN BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. TERMINATE WITH
MINIMUM 2" AIR GAP. COMBINE CONDENSATE FROM ALL FAN COIL UNITS INTO A
SINGLE CONDENSATE RISER.
9 INSTALL SPLIT SYSTEM FAN COIL UNIT ABOVE TELECOM ROOM DOOR. COORDINATE
EXACT LOCATION WITH EXISTING CABLES.
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL FIFTH FLOOR PLAN1
N
1/2" = 1'-0"
OI&T 5A1 ENLARGED PLAN2
N
OI&T 5A1 ENLARGED DEMOLITION PLAN3
OI&T
6000A 1-M-106
CU-1
CU-2
CU-3
OI&T
6000A
NOTE:
1. THE MECHANICAL CONTRACTOR
SHALL NOT USE WOOD SUPPORTS FOR
THE INSTALLATION OF SPLIT SYSTEM
CONDENSING UNITS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:2
A
M
1-M-106
BLDG 1 - MECHANICAL SIXTH FLOOR
PLAN
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/16" = 1'-0"
BLDG 1 - MECHANICAL SIXTH FLOOR PLAN1
MECHANICAL PLAN NOTES
3 PROVIDE REFRIGERANT LINES FROM SPLIT SYSTEM CONDENSING UNIT ON THE ROOF
TO THE ASSOCIATED SPLIT SYSTEM INDOOR FAN COIL UNIT.
N
1/8" = 1'-0"
BLDG 1 - MECHANICAL SIXTH FLOOR ENLARGED PLAN2
CRU-1
ACCU-3
ACCU-1
CRU-3
OI&T SERVER ROOM
52B
OI&T
CRU-2
66"x30" RA 36"x30" RA
36"x30" RA
66"x30" RA
ACCU-2
8"x8" EA
EG-1
12"x8" OA
8"x6" OA
8"x6" OA
13 13
1 32
A
E
B
D
C
RG-1
CD-1
315RG-1
RG-1
RG-1
CD-1
CD-1
CD-1
CD-1
CD-1
315 CD-1
CD-1
28"x16" RA
8"x6" OA
CORRIDOR
GA
EXHAUST
FAN (ETR)
T H
TH
ROOF HOOD
ABOVE
D2 D2
D1
D1
D3 D5
OI&T
D7
EXHAUST
FAN (ETR)
D2 D2
D1
D1
8" CHR
8" CHS
8" CHR
8" CHS
D6
D6D6
CRU-1
ACCU-3
ACCU-1
CRU-3
OI&T SERVER ROOM
52B
OI&T
2 6 8
3/4" CD
3/4" CD
1" CD
3/4" CD
1" CD
8" CHR
8" CHS
3" CHS3" CHR
CRU-2268
3" CHS
3" CHR
3" CHR
3" CHS
1" CD
ACCU-2
EG-1
1 32
A
E
B
D
C
EXISTING CHILLED WATER MAINS
IN BASEMENT CRAWL SPACE
1" CD
3" CHR
3" C
H S
2" C
H S
2" CHR
20202020
CORRIDOR
GA
ELECTRICAL CLOSET
01D
OI&T
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:2
A
M
1-M-401
MECHANICAL ENLARGED PLANS
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
N
1/8" = 1'-0"
SERVER ROOM ENLARGED HVAC PLAN2
N
1/8" = 1'-0"
SERVER ROOM ENLARGED HVAC DEMOLITION PLAN1
MECHANICAL DEMO PLAN NOTES
D1 REMOVE COMPUTER ROOM UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES, AND
CONTROLS.
D2 REMOVE AIR COOLED CONDENSING UNIT AND ALL ASSOCIATED PIPING,
ACCESSORIES, AND CONTROLS.
D3 REMOVE ALL CEILING MOUNTED DIFFUSERS.
D5 REMOVE ALL PERFORATED FLOOR TILES. REFER ARCHITECTURAL DRAWINGS FOR
PARTIAL DEMOLITION OF RAISED FLOOR.
D6 REMOVE ALL CHILLED WATER PIPING BELOW RAISED FLOOR BACK TO CHILLED
WATER MAIN IN BASEMENT CRAWL SPACE. REMOVE EXISTING TEE AND PREPARE
FOR NEW 3" CHILLED WATER PIPING CONNECTIONS.
D7 REMOVE EXHAUST LOUVER AND ASSOCIATED DUCTWORK BACK TO THE EXHAUST
FAN.
MECHANICAL PLAN NOTES
2 PROVIDE REFRIGERANT LINES FROM COMPUTER ROOM UNIT TO THE ASSOCIATED
AIR COOLED CONDENSING UNIT OUTSIDE. COORDINATE EXACT PIPE ELEVATION WITH
PLUMBING, ELECTRICAL, TELECOMMUNICATION, AND STRUCTURAL TRADES.
4 PROVIDE REFRIGERANT LINES FROM AIR COOLED CONDENSING UNIT OUTSIDE TO
THE ASSOCIATED COMPUTER ROOM UNIT.
6 ROUTE CONDENSATE FROM COMPUTER ROOM UNIT TO EXISTING FLOOR DRAIN
BENEATH RAISED FLOOR IN EXISTING SERVER ROOM. SLOPE CONDENSATE PIPING A
MINIMUM OF 1/8" PER FOOT TOWARD THE FLOOR DRAIN. TERMINATE WITH MINIMUM
2" AIR GAP.
7 ROUTE OUTSIDE AIR DUCT FROM ROOF INTAKE HOOD TO EACH COMPUTER ROOM
UNIT. BALANCE AIR FLOW TO EACH UNIT AS SCHEDULED.
8 ROUTE CHILLED WATER SUPPLY AND RETURN LINES FROM EXISTING MAINS IN
BASEMENT CRAWL SPACE TO COMPUTER ROOM UNIT.
10 TAP NEW CHILLED WATER SUPPLY AND RETURN BRANCH LINES FROM EXISTING
MAINS IN THE BASEMENT CRAWL SPACE. TAP NEW LINES FROM THE SAME LOCATION
AS DEMOLISHED LINES. REPLACE EXISTING TEE WITH A NEW 3" TEE. ROUTE NEW
BRANCH LINES UNDER FLOOR SLAB.
11 ROUTE CONDENSATE DRAIN TO EXISTING FLOOR DRAIN IN EXISTING SERVER ROOM.
ROUTE BELOW RAISED FLOOR. TERMINATE WITH MINIMUM 2" AIR GAP.
12 CONTRACTOR SHALL INSTALL REFRIGERANT LINES USING MANUFACTURER'S
RECOMMENDED SIZES, ROUTING, REQUIREMENTS, ETC.
13 INSTALL COMPUTER ROOM UNIT SUCH THAT THE FRONT DISCHARGE SUPPLY
GRILLES ARE CENTERED BETWEEN THE 2 ROWS OF SERVER RACKS. REFER TO
TELECOMMUNICATION DRAWINGS FOR EXACT LOCATION OF SERVER RACKS.
14 INSTALL EXHAUST LOUVER ON THE EXTERNAL WALL ABOVE THE WINDOW. ROUTE
EXHAUST DUCT FROM EXISTING EXHAUST FAN TO NEW LOUVER. CONTRACTOR
SHALL VERIFY EXACT EXHAUST FAN LOCATION AND COORDINATE DUCT ROUTING
WITH EXISTING CONDITIONS ABOVE THE CEILING.
15 TAP 3" CHILLED WATER SUPPLY AND RETURN LINES FROM BRANCH LINES UP
THROUGH THE FLOOR SLAB. ROUTE BETWEEN FLOOR SLAB AND RAISED FLOOR TO
THE PIPE CHASE.
16 TURN 2" CHILLED WATER SUPPLY AND RETURN UP AND ROUTE BETWEEN FLOOR
SLAB AND RAISED FLOOR TO CONNECT INTO COMPUTER ROOM UNIT.
17 TURN 3" CHILLED WATER SUPPLY AND RETURN UP IN THE PIPE CHASE. ROUTE PIPING
BELOW STRUCTURE. COORDINATE EXACT PIPE ELEVATION WITH PLUMBING,
ELECTRICAL, TELECOMMUNICATION, AND STRUCTURAL TRADES.
18 ROUTE 3/4" CONDENSATE RISER FROM ABOVE, BETWEEN FLOOR SLAB AND RAISED
FLOOR TO THE EXISTING FLOOR DRAIN BENEATH THE RAISED FLOOR.
19 TURN 1" CONDENSATE LINE DOWN IN THE PIPE CHASE AND TURN AGAIN TO ROUTE
BELOW THE EXISTING RAISED FLOOR INTO THE FLOOR DRAIN BENEATH THE RAISED
FLOOR. SLOPE CONDENSATE PIPING A MINIMUM OF 1/8" PER FOOT TOWARD THE
FLOOR DRAIN. TERMINATE WITH MINIMUM 2" AIR GAP.
20 ALL THE PIPING IN THIS AREA WILL BE ROUTED HIGH BELOW STRUCTURE. SLOPE
CONDENSATE PIPING A MINIMUM OF 1/8" PER FOOT TOWARD THE PIPE CHASE IN
OI&T-52. COORDINATE EXACT PIPE ELEVATION WITH PLUMBING, ELECTRICAL,
TELECOMMUNICATION, AND STRUCTURAL TRADES.
21 PROVIDE MANUAL BALANCING DAMPER TO ENSURE MINIMUM OA AIRFLOWS ARE
PROVIDED TO EACH CRU AS INDICATED IN SCHEDULES ON SHEET 1-M-601.
22 PROVIDE HUMIDITY SENSOR AND ADJUSTABLE THERMOSTAT FOR COMPUTER ROOM
UNITS. COORDINATE EXACT LOCATION WITH OWNER AND CONTROLS CONTRACTOR.
REFER SHEET 1-M-702 FOR CONTROLS.
23 CONNECT FULL SIZE RETURN DUCT FROM THE SERVER CABINET DUCT OPENING TO
THE RETURN DUCT ABOVE (TYPICAL FOR ALL SERVER CABINETS).N
1/8" = 1'-0"
SERVER ROOM ENLARGED PIPING DEMOLITION PLAN3
N
1/8" = 1'-0"
SERVER ROOM ENLARGED PIPING PLAN4
AIR FLOW
MV
MV
MV
MV
NOTES:
1. INSTALL CONTROL VALVE BETWEEN UNIONS OR FLANGES.
2. PROVIDE CONCENTRIC REDUCERS BOTH SIDES OF CONTROL VALVE AS REQUIRED.
3. REPLACE UNION/FLANGE SET WITH A FLEXIBLE PIPE CONNECTOR WHERE EQUIPMENT IS
SUPPORTED OR SUSPENDED BY SPRING ISOLATORS.
4. ARRANGEMENT SHOWN FOR FULL FLOW THROUGH COIL ON FAILURE.
COMBINATION UNION
AND PT PORT (TYP)
COIL
COIL DRAIN WITH
CAP AT LOWEST
POINT OF COIL (TYP)
PRESSURE
GAUGE (TYP)
THERMOMETER
(TYP)
MANUAL AIR VENT
(TYP)
WYE STRAINER WITH
BLOW DOWN AND
HOSE CONNECTION
DANFOSS AB-QM 2-WAY
PRESSURE INDEPENDENT
CONTROL VALVE
SEE NOTE 2
UNION (TYP)
ISOLATION VALVE (TYP)
INSTALL MANUAL AIR VENT AT HIGH
POINT WHEN TAPPED INTO TO OF
MAINS. USE A PIPE STUB WITH MIN
HEIGHT OF 4 PIPE DIAMETERS (TYP)
CONNECT TO SUPPLY AND RETURN
MAINS AS SHOWN ON PLAN
RETURN PIPING MAIN
SUPPLY PIPING MAIN
SEE PLAN FOR PIPE SIZES
P
VANE
VANE
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/6W.
SHORT RADIUS ELBOW
WITH TWO VANES
SHORT RADIUS ELBOW
WITH ONE VANE
STANDARD RADIUS OR
LONG RADIUS ELBOW
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED
AND FASTENED AS RECOMMENDED BY SMACNA.
NOTE:
1.
2.
W
R
1/6W
/3
W
1/2W
W
/3
W
2/3W
R
R
W
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE
TYPE.
NOTE:
1.
2.
3.
4.
W1
W
DRAW THRU
BLOW THRU
1" [50mm]
PLUS X
1" [25mm]
MINIMUM
MIN. 4"
OR
X+1/2"
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT
LEAST THE SAME SIZE AS THE
NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID
COPPER TYPE L OR TYPE M.
MECHANICAL
EQUIPMENT DRAIN PAN
NOTE:
1. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
2. REFERENCE FLOOR PLANS FOR EXACT SIZE AND ROUTING OF
CONDENSATE DRAIN PIPING.
A B
DIELECTRIC
FITTING
MIN. 4"
OR
X+1/2"
FLEXIBLE ADAPTER
COUPLING FOR
ATTACHEMENT TO A
MOTORIZED UNIT.
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON FAN
SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON
12" [300mm] CENTERS
RIVET ON 4"
[100mm] CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION
OF BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
1 1/2"1/2"1/2"
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. [453KG] UNIFORM LOAD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
NOM. SIZE
IN.
[mm]
FT.
[mm]
FT.
[mm]
TUBING
PIPE
[2 m m
M A
X
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD
AT HANGER
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
1-5/8" [43mm] 12 GAUGE
CHANNEL OR 2"x2"x1/4"
[50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
BAND
SADDLE
WELD
PIPEPIPE SLEEVE
WHERE SPECIFIED
FIRE-STOPPING
MATERIAL
BOLT
RISER
CLAMP
PIPE SLEEVE
WHERE
SPECIFIED
RISER
CLAMP
INSULATION
ELEVATION
RISER
PLAN
RISER CLAMP.
BOTTOM CLAMP
REQUIRED AT
ANCHOR POINTS
ONLY.
PROVIDE ANCHORS ONLY
WHERE SHOWN ON
DRAWINGS.
EXTEND SLEEVE ABOVE
FLOOR WHERE SPECIFIED.
BOLT
(TYPICAL)
FLOOR
SLAB
NOTES:
1.
2.
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITONS. REFER TO
SPECIFICATIONS FOR MORE INFORMATION. PIPE AND CONDUIT OF ALL TRADES MAY BE COMBINED ON
THE SAME SUPPORT CHANNEL. COORDINATE SUPPORT CHANNEL LENGTH WITH PIPING AND CONDUIT TO BE SUPPORTED. SUPPORT CHANNEL SPACING SHALL BE DETERMINED BY SMALLEST PIPE TO BE
SUPPORTED. CHANNEL SUPPORT MAY BE USED AS A WALL BRACKET, ATTACH TO WALL WITH ANCHOR
BOLTS PER SPECIFICATIONS. FOR HORIZONTAL INSULATED PIPING, ATTACH CLAMPS AS INDICATED
ABOVE, FOR VERTICAL INSULATED PIPING, ATTACH CLAMPS TO THE PIPE AND SEAL INSULATION AT BOTH
CLAMP ENDS.
SUPPORT WASHERS AND
LOCKNUTS (TYP.).
UNINSULATED STEEL OR
PLASTIC PIPE.
PROVIDE PLASTIC GALVANIC
ISOLATOR FOR COPPER PIPE
(TYP.)
UNINSULATED COPPER PIPE.
COLD INSULATED PIPE.
PIPE INSULATION (TYP.)
HOT INSULATED PIPE.
PROVIDE 1-5/8"x1-5/8" 14 GA.
CHANNEL SUPPORT.
CUT INSULATION TO FIT AROUND
TRAPEZE HANGER. SEAL BOTH
ENDS OF EXPOSED INSULATION
WITH JOINT SEALANT.
PROVIDE METAL 360° INSULATION SHIELD
AND HIGH DENSITY INSULATION OR
PRE-ENGINEERED THERMAL
HANGER-SHIELD INSERT OF CALCIUM
SILICATE INSULATION. FOR PIPES 4" AND
SMALLER, PRE-ENGINEERED THERMAL
HANGER-SHIELD INSERT OF FLEXIBLE
UNICELLULAR INSULATION MAY BE
PROVIDED.
SIZE AND QUANTITY OF HANGER
RODS PER MANUFACTURER'S
RECOMMENDATIONS.
PROVIDE TWO-PIECE PIPE
CLAMP (TYP.).
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:2
A
M
1-M-501
MECHANICAL DETAILS
SCP
JRM
RESUBMITTED 100% CONSTRUCTION DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
03/23/2021
657A4-20-700
John J. Pershing VA Medical Center 1500 N. Westwood Blvd.
Poplar Bluff, MO 63901
NTS
CRU COIL PIPING CONNECTION - 2 WAY
PRESSURE INDEPENDENT CONTROL VALVE7
NTS
DUCTWORK RADIUS ELBOWS1NTS
DUCTWORK SQUARE VANE ELBOWS2
NTS
CONDENSATE TRAP DETAIL8
NTS
FLEXIBLE DUCT CONNECTIONS4NTS
PIPE HANGERS5NTS
SUPPORT ANCHOR FOR PIPE RISER6
NTS
VOLUME DAMPER3
NTS
TRAPEZE PIPE HANGER9
"4"
GAS IN
LIQUID
OUT
COORDINATE MOUNTING
RAILS WITH ROOF ASSEMBLY NOTE:
1. INSTALLING CONTRACTOR SHALL VERIFY WITH EQUIPMENT MANUFACTURER PIPE
SIZES AND MAXIMUM RUN LENGTHS TO ENSURE PROPER OPERATION.
2. CONTRACTOR TO INSTALL OIL TRAPS IN REFRIGERANT LINE BEFORE EVAPORATOR
COIL AND NEAR CONDENSING UNIT TO HELP PREVENT OIL BUILD-UP IN COILS.
ACU - INDOOR UNIT
CU - OUTDOOR UNIT
3/8" RL / 5/8" RG
A P
P R
O X
CLAMP
CROSS BRACING RODS
ALL FOUR SIDES
HANGER
ROD (TYP)
RESILIENT PAD
BONDED STEEL
PLATE
NEOPRENE WASHER
& SLEEVE
ANCHOR BOLTEQUIPMENT
BASE
FLOOR
FLOOR MOUNT EQUIPMENT
RESTRAINED BY RESILIENT PADS
(TYPE DS)
SEISMIC BRACING FOR LIGHT
SUSPENDED EQUIPMENT
EQUIPMENT WEIGHT 250
LBS. [114KG] OR LESS
NOTE:
NOT REQUIRED FOR
AIR TERMINAL UNITS.
LOCK
NUTS (TYP)
OPTION "A"
OPTION "B"
ROOF DECK
ABS CURB CAB
EPDM RUBBER CAP
INSULATION
1" CLEAR OPENING AROUND PIPE TO
ALLOW FOR PIPE MOVEMENT
INSULATED ROOF CURB
WITH 26 GA. GALVANIZED
COUNTER FLASHING
ACRYLIC COATED ABS
RIB REINFORCED
PLASTIC CURB COVER
EPDM PROTECTIVE
RUBBER CAP
STAINLESS
STEEL CLAMP
SINGLE OR MULTIPLE
PIPE PENETRATIONS
PIPE PENETRATION(S) PER
PLAN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
REVISION: DATE:
ARCHITECT:
U.S. Department of Veteran Affairs
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
MO ARCH REG. NO. 2012034754, EXP. 12/31/2022
MO ENGR REG. NO. 2014031351, EXP. 12/31/2022
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
STRUCTURAL ENGINEER
STAND STRUCTURAL ENGINEER
8234 ROBINSON ST.
OVERLAND PARK, KS 66204
(913) 214-9525
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
F U
L L
Y S
P R
IN
K
L E
R E
D
ABATEMENT
RIVERFRONT SAFETY AND HEALTH
11140 S. TOWNE SQ., STE 100
SAINT LOUIS, MO 63123
(314) 917-0148
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
/2
/2
:2
:3
A
M
1-M-502
MECHANICAL DETAILS
SCP
JRM