Structural_Drawing_Set.pdf
PDF 1 MB Posted
- Attached to
- South County Fleet Renovation
- Solicitation number
- 262899MKM
- Issued by
- Sarasota County, Florida
About this file
This is a structural drawing set for the Sarasota County Fleet South Renovation project located at 4571 State Road 776, Venice, Florida, prepared by Hall Darling Design Studio, PA (architect) and Bennett & Pless, Inc. (structural engineer). The project involves renovation of an existing single-story administration building and maintenance garage totaling 10,909 square feet, with construction required to conform to the 2023 Florida Building Code. The scope includes new cast-in-place concrete foundations, footings, slabs-on-grade, masonry walls, reinforced concrete columns and structural elements, structural steel framing with tube steel members and hollow structural sections, new concrete stairs, and connections to existing pre-engineered metal building components. The structural drawings specify design loads including 100 PSF live load on stairs, 250 PSF on loading docks, Risk Category II, ultimate wind speed of 155 MPH, and nominal wind speed of 120 MPH with exposure category C. The contract requires 180 calendar days for substantial completion with liquidated damages of $500 per day for delays beyond substantial completion and $125 per day for delays beyond final acceptance.
The structural design establishes minimum concrete compressive strengths of 3,000 PSI for foundations, retaining walls, slabs-on-grade, and framed floor slabs, and 4,000 PSI for columns and walls. Reinforcing steel must conform to ASTM A615 Grade 60, with structural steel conforming to ASTM A992, A572, and A500 standards as applicable. All structural steel exposed to weather must be hot-dip galvanized per ASTM A123, except surfaces to be field-welded or slip-critical connections. The project involves coordination with architectural, mechanical, electrical, plumbing, and civil consultants, with the contractor responsible for verifying all existing conditions prior to construction and immediately reporting any discrepancies to the architect and structural engineer of record. Shop drawings for concrete reinforcement, masonry, structural steel connections, and other specified elements must be submitted electronically and reviewed by the structural engineer within ten working days before fabrication begins. The contractor is solely responsible for erection bracing, shoring, temporary supports, and all construction means and methods, with field verification of soil bearing capacity and geotechnical conditions required before foundation construction commences.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL:
1. PROVIDE CONSTRUCTION CONFORMING TO THE 2023 FLORIDA BUILDING CODE. REFERENCE TO
LATEST EDITION OR OTHER STANDARDS, SPECIFICATIONS OR CODES SHALL MEET THE LATEST
STANDARD OR CODE PUBLISHED AND ADOPTED BY THE LISTED BUILDING CODE.
2. MATERIAL TESTS AND INSPECTIONS ARE REQUIRED PER CHAPTER 17 OF THE 2023 FLORIDA BUILDING CODE. REFER TO THE PROJECT STATEMENT OF SPECIAL INSPECTIONS FOR REQUIRED
TESTS AND INSPECTIONS.
3. THESE NOTES APPLY EXCEPT WHERE OTHERWISE INDICATED BY DRAWINGS OR SPECIFICATIONS.
4. STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY.
SUBMITTED SHOP DRAWINGS DETAIL ALL CONDITIONS IN ACCORDANCE WITH SPECIFIED
STANDARDS AND THE SPECIFIC REQUIREMENTS OF THIS PROJECT AS INDICATED ON THE
DRAWINGS.
5. COORDINATE THE STRUCTURAL CONTRACT DOCUMENTS WITH ARCHITECTURAL, MECHANICAL,
ELECTRICAL, PLUMBING, CIVIL AND ALL OTHER CONSULTANTS. NOTIFY THE ARCHITECT AND
STRUCTURAL ENGINEER OF RECORD IN WRITING OF ANY CONFLICT AND/OR OMISSION. WHERE A
CONFLICT OCCURS, THE STRICTEST REQUIREMENT SHALL GOVERN UNLESS OTHERWISE DECIDED
BY THE DESIGN TEAM
6. COORDINATE AND VERIFY FLOOR AND ROOF OPENING SIZES AND LOCATIONS SHOWN WITH
ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS. FOR ADDITIONAL
OPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS REFER TO THE ARCHITECTURAL AND
MECHANICAL DRAWINGS. OBTAIN WRITTEN APPROVAL OF ADDITIONAL OPENINGS LARGER THAN
12” x 12” FROM THE STRUCTURAL ENGINEER OF RECORD.
7. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, ADEQUACY AND SAFETY OF
ERECTION BRACING, SHORING, TEMPORARY SUPPORTS AND ALL OTHER MEANS, METHODS,
TECHNIQUES, SEQUENCES AND PROCEDURES OF CONSTRUCTION.
8. COORDINATE THE BUILDING ORIENTATION WITH THE ARCHITECTURAL DRAWINGS.
9. COMPLETE SHOP DRAWINGS FOR CONSTRUCTION OF EACH BUILDING COMPONENT NOT
DESIGNED BY THE DESIGN TEAM OF RECORD AND NOT SPECIFIED ON THE PROJECT
CONSTRUCTION DOCUMENTS SHALL BE SEALED AND SIGNED BY A PROFESSIONAL ENGINEER IN
THE STATE WHERE THE PROJECT IS LOCATED AND SHALL BE MADE AVAILABLE AT THE JOB SITE
10. UNO, FIREPROOFING REQUIREMENTS, METHODS AND MATERIALS FOR STRUCTURAL MEMBERS
ARE NOT SHOWN ON STRUCTURAL DRAWINGS, REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS
11. ALL REACTIONS AND FORCES SHOWN ON THE DRAWINGS ARE SERVICE LOADS (ASD
COMBINATIONS) UNO.
12. DO NOT SCALE OFF OF DRAWINGS, ASK ARCHITECT FOR DIMENSIONS NOT SHOWN.
DESIGN LOADS:
1. LIVE LOADS:
STAIR
LOADING DOCK
2. RISK CATEGORY
3. WIND DESIGN DATA:
ULTIMATE WIND SPEED, V_ULT
NOMINAL WIND SPEED, V_ASD
WIND EXPOSURE
INTERNAL PRESSURE COEFFICIENT
COMPONENTS AND CLADDING PRESSURES
UNIFORM
=100 PSF ON STAIR TREADS
=250 PSF
= II
=155 MPH
=120 MPH
=C =0.18±
=SEE TABLE
EXISTING CONDITIONS:
1. RENOVATION OF EXISTING STRUCTURES REQUIRES THOROUGH COORDINATION OF THE
CONTRACT DOCUMENTS WITH EXISTING CONDITIONS. THE CONTRACTOR MUST VERIFY ALL
RELEVANT EXISTING CONDITIONS, DIMENSIONS AND DETAILS PRIOR TO BEGINNING
CONSTRUCTION. REPORT ANY DEVIATIONS FROM CONDITIONS OR DIMENSIONS SHOWN ON THE
CONTRACT DOCUMENTS TO THE ARCHITECT AND STRUCTURAL ENGINEER OF RECORD FOR
REVIEW OF THE DESIGN AND POSSIBLE REVISION OF THE CONTRACT DOCUMENTS.
2. THE NATURE OF STRUCTURAL DEMOLITION AND STABILIZATION IS INHERENTLY UNCERTAIN. THE
EXACT CONDITION AND CAPACITY OF EACH STRUCTURAL ELEMENT CANNOT BE VERIFIED PRIOR
TO THE COMMENCEMENT OF WORK. AS A RESULT, IT IS IMPERATIVE TO REPORT ANY
DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS, AS WELL
AS ANY ELEMENT OF QUESTIONABLE STRUCTURAL INTEGRITY IMMEDIATELY TO THE ARCHITECT
AND STRUCTURAL ENGINEER OF RECORD FOR REVIEW.
3. NO ATTEMPT HAS BEEN MADE TO DEFINE EACH SPECIFIC STRUCTURAL ELEMENT THAT MUST BE
REMOVED, ENHANCED OR REPLACED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
REVIEW THE CONDITION OF INDIVIDUAL ELEMENTS, TO DETERMINE WHICH ELEMENTS CAN BE
SALVAGED, WHICH ELEMENTS MUST BE REPLACED AND WHICH ELEMENTS ARE QUESTIONABLE.
THE CONTRACTOR SHOULD CONSULT WITH THE ARCHITECT AND STRUCTURAL ENGINEER OF
RECORD TO DETERMINE THE APPROPRIATE PROCEDURE FOR HANDLING ELEMENTS IN
QUESTIONABLE CONDITION.
4. THE DIMENSIONS AND ELEVATIONS SHOWN FOR THE EXISTING CONSTRUCTION ARE NOT AS-BUILT
DIMENSIONS BUT WERE OBTAINED FROM FIELD MEASUREMENTS, OTHER DRAWINGS AND
DOCUMENTS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND MEMBER SIZES AS REQUIRED PRIOR TO BEGINNING CONSTRUCTION, FABRICATION, ETC.
5. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS NOT TO DISTURB OR UNDERMINE ANY
EXISTING BUILDING FOUNDATIONS OR STRUCTURE AND SHALL PROVIDE SHORING AS REQUIRED.
6. IN AREAS WHERE UNDERMINING OF EXISTING BUILDING FOUNDATION OR STRUCTURE IS
REQUIRED BY THE CONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL PROVIDE
UNDERPINNING AND/OR SHORING AS REQUIRED TO SUPPORT THE EXISTING BUILDING
FOUNDATIONS AND STRUCTURES. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND SIGNED
AND SEALED CALCULATIONS FOR APPROVAL PRIOR TO CONSTRUCTION. DESIGN SHALL BE
COORDINATED WITH GEOTECHNICAL ENGINEERS REPORT AND RECOMMENDATIONS.
SHOP DRAWINGS:
1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS THAT ADEQUATELY DEPICT THE STRUCTURAL
ELEMENTS AND CONNECTIONS SHOWN IN THE CONTRACT DOCUMENTS. STRUCTURAL DRAWINGS
INDICATE TYPICAL AND CERTAIN CONDITIONS ONLY. SHOP DRAWINGS SHALL DETAIL ALL
CONDITIONS IN ACCORDANCE WITH SPECIFIED STANDARDS AND SPECIFIC REQUIREMENTS OF
THIS PROJECT.
2. REVIEW OF SUBMITTALS AND SHOP DRAWINGS BY THE ARCHITECT/ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF FULL RESPONSIBILITY FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS.
CONTRACTOR REMAINS SOLELY RESPONSIBLE FOR ERRORS AND OMISSIONS ASSOCIATED WITH
THE PREPARATIONS OF SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS AND
DIMENSIONS SPECIFIED IN THE CONTRACT DOCUMENTS.
3. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF
THE CONTRACT DOCUMENTS ONLY. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF
QUANTITIES, LENGTHS, ELEVATIONS, DIMENSIONS, ETC.
4. SHOP DRAWING SUBMITTALS SHALL BE SUBMITTED ELECTRONICALLY. SHOP DRAWINGS SHALL BE
REVIEWED, STAMPED AND SIGNED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE
ARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED
UNCHECKED.
5. THE USE OR REPRODUCTIONS OF THESE CONTRACT DRAWINGS OR ANY PART OF THEM BY
CONTRACTOR IN LIEU OF PREPARATION OF SHOP DRAWINGS WILL BE REJECTED UNCHECKED.
6. MAXIMUM REQUIRED TURN AROUND TIME FOR SHOP DRAWING APPROVAL BY STRUCTURAL
ENGINEER IS TEN (10) WORKING DAYS.
7. THE FOLLOWING SHOP DRAWINGS SHALL BE SUBMITTED PRIOR TO CONSTRUCTION:
A. CONCRETE MIX DESIGN
B. CONCRETE REINFORCING
C. HEAVY TIMBER
D. TIMBER CONNECTIONS
E. WOOD FLOOR TRUSSES
F. WOOD ROOF TRUSSES
G. MASONRY REINFORCEMENT
H. MASONRY
I. STRUCTURAL STEEL
J. STRUCTURAL STEEL CONNECTIONS REQUIRING ENGINEERING
K. REFABRICATED STEEL STAIRS, RAILINGS AND LADDERS
L. METAL ROOF DECK ASSEMBLIES
M. OPEN WEB STEEL JOISTS AND/OR GIRDERS
N. LIGHT GAUGE STEEL EXTERIOR OR LOADBEARING WALL SYSTEMS
O. GLAZED CURTAIN WALLS
P. PRECAST CONCRETE ELEMENTS
Q. EXCAVATION SHORING AND RETAINING SYSTEMS
R. SHEET PILING
S. SOIL ANCHORS
T. SECANT PILES
U. MECHANICAL ANCHORS
V. CHEMICAL ANCHORS
FOUNDATION:
1. FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf ON
COMPACTED FILL. BEFORE CONSTRUCTION COMMENCES, SOIL BEARING CAPACITY SHALL BE
VERIFIED BY A SUBSURFACE INVESTIGATION, AS WELL AS FIELD AND LABORATORY TESTS
PERFORMED BY A CERTIFIED TESTING LABORATORY, WHOSE REPORT SHALL INCLUDE ANALYSIS
AND RECOMMENDATIONS FOR SITE PREPARATION IN ORDER TO BEAR THE FOUNDATION LOADS.
ABOVE REPORT SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW BEFORE
FOUNDATION CONSTRUCTION BEGINS.
2. AFTER EXCAVATION, IF THE CONDITION OF THE SOILS DO NOT MEET THE RECOMMENDED DESIGN
CRITERIA STATED IN THE GEOTECHNICAL REPORT, NOTIFY THE ARCHITECT AND STRUCTURAL
ENGINEER OF RECORD SO THAT THE FOUNDATIONS MAY BE REDESIGNED IF NECESSARY.
3. THE GEOTECHNICAL ENGINEER MUST VERIFY THE CONDITION AND/OR ADEQUACY OF ALL SUB- GRADES, FILLS AND BACKFILLS PRIOR TO THE PLACEMENT OF FOUNDATIONS, FOOTINGS, SLABS, WALLS, ETC.
4. DESIGN OF SLAB-ON-GRADE IS BASED UPON A MODULUS OF SUBGRADE REACTION OF 150 PCI.
5. CONTACT THE ARCHITECT AND ENGINEER OF RECORD IF, AFTER EXCAVATION, THE CONDITION OF
THE SOIL INDICATES A SAFE BEARING CAPACITY OF LESS THAN ???? PSF. BEAR ALL FOOTINGS ON
ORIGINAL, UNDISTURBED SOIL OR STRUCTURAL FILL.
6. COORDINATE TOP OF FOOTING ELEVATIONS WITH THE REQUIREMENTS OF OTHER TRADES
(PLUMBING, ELECTRICAL, ETC.).
7. LOCATE TOP OF EXTERIOR FOOTING ELEVATIONS ?' - ?” BELOW FINISHED FLOOR, BUT NOT LESS
THAN ?' - ?” BELOW FINISHED GRADE, UNO.
8. LOCATE TOP OF INTERIOR FOOTING ELEVATIONS ?' - ?” BELOW FINISHED FLOOR, UNO.
9. BACK FILLING WALLS:
A. DEPOSIT BACKFILL AGAINST WALLS EVENLY AGAINST BOTH SIDES OF WALL UNTIL THE LOWER
FINAL GRADE IS REACHED.
B. DO NOT PLACE BACKFILL AGAINST WALLS DEPENDENT UPON TOP AND BOTTOM CONCRETE
SLABS FOR SUPPORT UNTIL THE CONCRETE SLABS HAVE ATTAINED 65% OF THEIR DESIGN 28
DAY COMPRESSION STRENGTH.
C. SHORE AND BRACE WALLS SHOWN MONOLITHIC WITH A SLAB-ON-GRADE AT THE TOP OF THE
WALL DURING BACKFILLING OPERATIONS.
10. CONSTRUCT COLUMN FOOTINGS AND WALL FOOTINGS MONOLITHICALLY WITH TOPS OF ADJACENT
FOOTINGS AT THE SAME ELEVATION.
11. FILLS:
A. REMOVE ALL UNSUITABLE SOILS AND REPLACE WITH CLEAN STRUCTURAL FILL AT THE
DIRECTION OF THE GEOTECHNICAL ENGINEER.
B. PLACE FILL SOILS IN 6” MAXIMUM (LOOSE) LIFTS AT MOISTURE CONTENTS AS DESCRIBED IN
THE GEOTECHNICAL REPORT.
C. COMPACT ALL FILL WITHIN 10'-0” OF THE BUILDING LIMIT TO 95% STANDARD PROCTOR.
D. TEST FIELD DENSITY AS DESCRIBED IN THE GEOTECHNICAL REPORT TO VERIFY ADEQUATE
COMPACTION AND DESIGN BEARING PRESSURE.
12. SIDES OF FOUNDATIONS MUST BE FORMED UNLESS CONDITIONS PERMIT EARTH FORMING.
FOUNDATIONS PLACED AGAINST THE EARTH REQUIRE THE FOLLOWING PRECAUTIONS: SLOPE
SIDES OF EXCAVATIONS AS APPROVED BY THE GEOTECHNICAL ENGINEER AND CLEAN UP
SLOUGHING BEFORE AND DURING CONCRETE PLACEMENT.
13. WHERE FOOTING STEPS ARE NECESSARY, SLOPE NO STEEPER THAN ONE VERTICAL TO TWO
HORIZONTAL.
REINFORCED CONCRETE:
1. PROVIDE REINFORCED CONCRETE CONFORMING TO THE FOLLOWING STANDARDS.
A. ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS, LATEST EDITION.
B. ACI 318, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, LATEST EDITION.
C. ACI 302.1R, GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION, LATEST EDITION.
D. ACI 360R, DESIGN OF SLABS-ON-GROUND, LATEST EDITION.
E. PROJECT SPECIFICATION MANUAL DIVISION 3 (WHEN PROVIDED).
2. FULLY DOCUMENT AND SUBMIT FOR REVIEW THE PROPOSED MATERIALS AND MIX DESIGN FOR ALL
CONCRETE. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING THE REQUIRED DESIGN
STRENGTH. ALL CONCRETE TEST DATA MUST BE AVAILABLE AT THE JOB SITE.
3. DETAIL CONCRETE REINFORCEMENT ACCORDING TO ACI MNL-66 DETAILING MANUAL. SUBMIT
SHOP DRAWINGS FOR APPROVAL, SHOWING ALL FABRICATION DIMENSIONS AND LOCATIONS FOR
PLACING CONCRETE REINFORCING AND ACCESSORIES. DO NOT BEGIN FABRICATION UNTIL SHOP
DRAWINGS ARE COMPLETED AND REVIEWED BY THE STRUCTURAL EOR. UNLESS SPECIFICALLY
APPROVED OTHERWISE, DETAIL ALL CONCRETE WALLS AND BEAMS IN ELEVATION.
4. PROVIDE NORMAL WEIGHT CONCRETE WITH THE FOLLOWING 28 DAY COMPRESSIVE STRENGTHS:
• FOUNDATIONS: 3000 PSI
• RETAINING WALLS: 3000 PSI
• SLABS-ON-GRADE: 3000 PSI
• FRAMED FLOOR SLABS: 3000 PSI
• COLUMNS AND WALLS: 4000 PSI
5. PROVIDE CONCRETE WITH:
A. 4% TO 6% ENTRAINED AIR BY VOLUME IN CONCRETE PERMANENTLY EXPOSED TO WEATHER.
B. THE USE OF CALCIUM CHLORIDE, CHLORIDE IONS OR OTHER SALTS IS NOT PERMITTED.
C. PLACE CONCRETE AT A SLUMP OF 5” ± 1” UNO.
6. UNO, PROVIDE REINFORCING STEEL CONFORMING TO ASTM A 615, GRADE 60.
7. PROVIDE WELDED WIRE REINFORCEMENT (MESH) IN FLAT SHEETS (ROLLS NOT PERMITTED)
CONFORMING TO ASTM A1064. LAP WWR A MINIMUM OF 6” AT EACH SPLICE.
8. FIBER REINFORCING MAY BE SUBSTITUTED FOR WWR IN SLABS-ON-GRADE WITH THE APPROVAL
OF THE STRUCTURAL EOR. PROVIDE FIBER REINFORCING CONFORMING TO ASTM A 820, TYPE 1.
9. SEE ARCHITECTURAL DRAWINGS FOR WATERSTOPS.
10. UNO, PROVIDE THE FOLLOWING CONCRETE COVER ON ALL REINFORCING STEEL:
A. CONCRETE AGAINST EARTH (NOT FORMED): 3”
B. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER:
a. #6 THROUGH #18 BARS: 2”
b. #5 BARS AND SMALLER: 1 1/2"
C. FORMED CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
a. SLABS, JOISTS, AND WALLS: 3/4"
b. BEAMS (STIRRUPS) AND COLUMNS (TIES): 1 1/2"
11. REINFORCING, INCLUDING DOWELS, SHALL BE SECURELY TIED AND CAST WITH THE LOWER
MEMBER. PLACING REINFORCING AFTER CONCRETE HAS BEEN PLACED IS NOT PERMITTED.
12. FIELD BENDING OF REINFORCING PARTIAL EMBEDDED IN CONCRETE IS NOT ALLOWED UNLESS
SPECIFICALLY NOTED IN THE STRUCTURAL DOCUMENTS OR APPROVED BY STRUCTURAL
ENGINEER.
13. PROVIDE DOWELS FROM THE FOUNDATION WHICH ARE THE SAME GRADE, SIZE AND NUMBER AS
VERTICAL WALL OR COLUMN REINFORCING UNO.
14. TIE ALL REINFORCING STEEL AND EMBEDDED ITEMS SECURELY IN PLACE PRIOR TO PLACING
CONCRETE. PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF THE
REINFORCEMENT WITHIN SPECIFIED TOLERANCES DURING ALL CONSTRUCTION ACTIVITIES.
15. PROVIDE CORNER BARS AT ALL CORNERS AND INTERSECTIONS OF ALL FOOTINGS, BEAMS AND
WALLS.
16. PROVIDE CONSTRUCTION OR CONTRACTION JOINTS IN SLABS-ON-GRADE SPACED AT A MAXIMUM 12'-0" OC IN EACH DIRECTION AND WITH THE LENGTH BETWEEN CONTROL JOINTS NO GREATER
THAN 1 1/4 TIMES THE WIDTH BETWEEN CONTROL JOINTS.
17. SAWCUT CONTROL JOINTS AS SOON AFTER PLACING AS POSSIBLE, WHEN CONCRETE WILL NOT
RAVEL, TEAR, ABRADE OR OTHERWISE DAMAGE THE SURFACE AND BEFORE THE CONCRETE
DEVELOPS RANDOM SHRINKAGE CRACKING. CURE CONCRETE IN ACCORDANCE WITH ACI 301.
BEGIN CURING IMMEDIATELY AFTER PLACING TO LIMIT CRACKING PRIOR TO SAWCUTTING
CONTROL JOINTS.
18. UNLESS NOTED OTHERWISE, AT BASEMENT WALLS AND RETAINING WALLS:
A. PROVIDE VERTICAL CONTROL JOINTS IN BASEMENT WALLS AND RETAINING WALLS WITH A
MAXIMUM SPACING OF 15'-0” ON CENTER AND 3/4" DEEP V-CHAMFER ON BOTH FACES.
B. INTERRUPT HALF OF THE SPECIFIED HORIZONTAL REINFORCEMENT AT CONTROL JOINTS.
C. CENTER CHAMFER STRIPS BETWEEN VERTICAL REINFORCING BARS.
19. NON-STRUCTURAL EMBEDMENTS (CONDUIT, PIPES, SLEEVES, ETC) WITHIN WALLS, BEAMS OR
SLABS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER AND ARCHITECT FOR REVIEW AND
APPROVAL PRIOR TO CONSTRUCTION. ALL EMBEDMENTS SHALL BE FABRICATED AND INSTALLED
IN ACCORDANCE WITH ACI STANDARDS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
A. ALUMINUM MATERIALS SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE
B. OVERALL OUTSIDE DIMENSION OF EMBEDMENTS SHALL NOT EXCEED 1/3 THE CONCRETE
MEMBER THICKNESS UP TO 2" MAXIMUM.
a. FOR CONCRETE SLABS ON METAL DECK THE MEMBER THICKNESS SHALL BE THE
CONTINUOUS SLAB THICKNESS ABOVE THE DECK.
C. EMBEDMENTS SHALL BE SPACED A MINIMUM OF 6" OC
D. EMBEDMENTS SHALL NOT ALTER OR DISPLACE REINFORCING
E. EMBEDMENTS WITHIN COLUMNS SHALL NOT DISPLACE MORE THAN 4% OF THE AREA OF THE
COLUMN CROSS SECTION.
20. NO HORIZONTAL CONSTRUCTION JOINTS WILL BE ALLOWED IN BEAMS OR JOISTS.
21. --SPECIFICATION BREAK-- THE FOLLOWING NOTES SHALL APPLY WHEN A PROJECT SPECIFICATION
MANUAL HAS NOT BEEN PROVIDED.
22. PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE. SPLICE REINFORCING BARS ONLY
AS SHOWN OR APPROVED. STAGGER SPLICES WHERE POSSIBLE. USE CLASS “B” TENSION
SPLICES UNO, INCLUDING DOWELS.
23. TEST CYLINDERS SHALL BE TAKEN TO THE LESSER OF THE FOLLOWING.
A. 75 CUBIC YARDS
B. 24 HOUR PERIOD
C. CHANGE IN CONCRETE STRENGTH
24. TEST CYLINDERS AT 7 DAYS AND 28 DAYS. SHOULD 28 DAY STRENGTH NOT BE MET, TEST REMAINING CYLINDERS AT 56 DAYS. TEST RESULTS SHALL BE FORWARDED TO THE STRUCTURAL
EOR.
STRUCTURAL MASONRY:
1. PROVIDE STRUCTURAL MASONRY CONFORMING TO THE FOLLOWING STANDARDS:
A. ACI 530 / ASCE 5 / TMS 402, BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY
STRUCTURES, LATEST EDITIONS.
B. ACI 530.1 / ASCE 6 / TMS 602, SPECIFICATIONS FOR CONCRETE MASONRY STRUCTURES,
LATEST EDITIONS.
2. LOAD BEARING MASONRY WALLS ARE DESIGNED IN ACCORDANCE WITH CHAPTERS 1 AND 2 OF ACI
530.
3. PROVIDE HOLLOW, LOAD BEARING CONCRETE MASONRY UNITS (CMU) CONFORMING TO ASTM C 90
WITH A MINIMUM COMPRESSIVE STRENGTH OF MASONRY (F'/M) OF 2,000 PSI AND A NET STRENGTH OF 2,000 PSI ON THE NET CROSS-SECTIONAL AREA OF CMU DETERMINED IN ACCORDANCE WITH
ASTM C 140.
4. PROVIDE BRICK MASONRY UNITS CONSTRUCTED OF CLAY OR SHALE CONFORMING TO ASTM C 652.
5. PROVIDE MORTAR CONFORMING TO ASTM C 270, TYPE S. STANDARD MORTAR BED JOINT
THICKNESS IS 3/8" AND MUST NOT VARY OUTSIDE OF THE RANGE BETWEEN 1/4" AND 1/2". DO NOT
USE AIR ENTRAINED MORTAR.
6. PROVIDE GROUT FOR REINFORCED MASONRY CONFORMING TO ASTM C 476 WITH MINIMUM
COMPRESSIVE STRENGTH OF 2,500 PSI AND A MINIMUM SLUMP OF 10”
7. PROVIDE STEEL REINFORCEMENT IN MASONRY WALLS CONFORMING TO ASTM A615, GRADE 60.
8. PROVIDE MASONRY TIES AND ANCHORS OF THE TYPE AND SPACING AS DETAILED ON THE
STRUCTURAL DRAWINGS AND IN CONFORMANCE WITH ASTM A82.
9. PROVIDE LADDER TYPE HORIZONTAL JOINT REINFORCING CONFORMING TO ASTM A951 IN ALL
MASONRY WALLS. UNO, PLACE 9 GAGE ZINC COATED LADDER TYPE HORIZONTAL JOINT
REINFORCING AT 16” OC. LAP HORIZONTAL JOINT REINFORCING MINIMUM 12”. USE
PREFABRICATED 'L'S AND 'T'S AT CORNERS AND INTERSECTIONS.
10. LAY ALL MASONRY UNITS IN RUNNING BOND.
11. FOR GROUTED WALLS:
A. THE MAXIMUM HEIGHT OF GROUT LIFTS MUST NOT EXCEED 5'-4”.
B. THE MAXIMUM UN-GROUTED HEIGHT OF 8” OR THICKER CMU WALLS PRIOR TO GROUTING
MUST NOT EXCEED 12'-0”.
C. REFER TO TABLE 7 OF ACI 530.1 FOR THE MAXIMUM UN-GROUTED HEIGHT OF CMU WALLS
THINNER THAN 8”.
D. CONSOLIDATE AND RECONSOLIDATE GROUT IN ACCORDANCE WITH PARAGRAPH 3.5.E OF ACI
530.1.
E. ALL GROUT POURS HIGHER THAN 5'-0” MUST HAVE INSPECTION HOLES AT THE BASE OF THE
WALL.
12. REINFORCEMENT:
A. DETAIL REINFORCEMENT IN LOAD BEARING CMU WALLS IN ELEVATION ON SHOP DRAWINGS.
B. LAP VERTICAL MASONRY WALL REINFORCING AS SHOWN IN THE MASONRY LAP LENGTH
SCHEDULE AND PROVIDE MINIMUM BAR SPLICE LENGTH.
13. PROVIDE VERTICAL CONTROL JOINTS IN ALL MASONRY WALLS NOT RETAINING EARTH. UNO ON
THE ARCHITECTURAL DRAWINGS, PLACE VERTICAL CONTROL JOINTS AT THREE TIMES THE WALL STORY HEIGHT, BUT NOT CLOSER THAN 25'-0” ON CENTER OR FARTHER THAN 40'-0” ON CENTER.
14. UNO, PROVIDE MINIMUM (1) #5 VERTICAL BAR, GROUTED FULL STORY HEIGHT, AT EACH SIDE OF OPENINGS AND AT ALL CORNERS AND ENDS OF WALLS, INCLUDING BOTH SIDES AT ENDS OF WALL
PANELS AT VERTICAL CONTROL JOINTS.
15. UNO, ANCHOR SIDES AND TOPS OF MASONRY WALL PANELS TO THE STRUCTURE BY DOVETAIL
ANCHORS, METAL STRAPS OR EQUIVALENT.
16. PLACE CONNECTORS FOR MASONRY VENEERS AT NOT MORE THAN 16” ON CENTER VERTICALLY
OR 24” ON CENTER HORIZONTALLY.
17. PROVIDE A CONTINUOUS BOND BEAM AT THE TOP OF ALL MASONRY WALLS. UNO REINFORCE
BOND BEAMS WITH (2) #4 CONTINUOUS REINFORCING BARS.
18. PROVIDE LEVEL B QUALITY ASSURANCE AS DESCRIBED IN TABLE 4 OF ACI 530.1 / ASCE 6 / TMS 602, LATEST EDITIONS.
19. SAMPLE AND TEST GROUT IN ACCORDANCE WITH ARTICLES 1.4 B AND 1.6 OF ACI 530.1 / ASCE 6 /
TMS 602, LATEST EDITIONS.
REINFORCED CONCRETE CONT:
25. THE LOCATION OF CONSTRUCTION JOINTS REQUIRES THE APPROVAL OF THE STRUCTURAL EOR.
A. UNLESS NOTED OTHERWISE, THOROUGHLY ROUGHEN (BY MECHANICAL MEANS) AND CLEAN
CONSTRUCTION JOINTS.
B. PROVIDE KEYS IN BEAMS AT CONSTRUCTION JOINTS.
C. APPLY SLUSH COAT AS SPECIFIED.
26. PROVIDE THE FOLLOWING NOMINAL SIZE OF KEYS AT WALL CONSTRUCTION JOINTS UNO:
A. 8” THROUGH 10” WALL = 2” x 4” KEY B. 12” THROUGH 16” WALL = 2” x 6” KEY
27. THE PLACEMENT OF ALL REINFORCING STEEL MUST BE REVIEWED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS TO BE CONSTRUCTED OR BY A
REPRESENTATIVE RESPONSIBLE TO HIM (REF: ACI 318).
28. PROVIDE COMPRESSIBLE FILLER AND SEALANT IN SLAB-ON-GRADE AND WALL AND COLUMN
INTERFACES THAT ARE NOT DOWELED TOGETHER.
29. ALL COLUMN POCKETS SHALL BE FILLED WITH CONCRETE AFTER COLUMN IS ERECTED.
30. PROVIDE 4" HIGH CONCRETE HOUSEKEEPING PADS UNDER EQUIPMENT. PADS SHALL EXTEND
BEYOND EQUIPMENT 6" NOMINAL ON ALL SIDES. APPLY BONDING AGENT TO EXISTING CONCRETE
SLAB PRIOR TO PLACING HOUSEKEEPING PAD. SEE DOCUMENTS FROM OTHER DISCIPLINES FOR
EQUIPMENT LOCATIONS.
31. AT FLOOR DRAINS, LOCALLY SLOPE FLOOR TOWARD DRAIN. SEE DOCUMENTS FROM OTHER
DISCIPLINES FOR DRAIN LOCATIONS.
32. UNO, STRUCTURAL SLABS EXPOSED TO WEATHER SHALL BE SLOPED APPROXIMATELY 1/4 INCH
PER FOOT AWAY FROM OCCUPIED SPACE TOWARD FLOOR DRAINS, SCUPPERS, GUTTERS, ETC.
FOR EXTERIOR NON-STRUCTURAL FLATWORK (EX: SIDEWALKS, PAVEMENT) REFERENCE CIVIL
SITE PLAN AND SPECIFICATIONS.
33. SEE ARCHITECTURAL DOCUMENTS FOR MOLDS, GROOVES, ORNAMENTS, CLIPS, ETC REQUIRED TO
BE ENCASED IN CONCRETE AND FOR LOCATION OF FLOOR FINISHES AND SLAB DEPRESSIONS.
1. DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE "STEEL CONSTRUCTION MANUAL" AND THE "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS", BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND THE PROJECT SPECIFICATION MANUAL DIVISION 5
(WHEN PROVIDED).
2. SUBMIT SHOP DRAWINGS FOR FABRICATION AND ERECTION OF ALL STEEL MEMBERS IN ACCORDANCE WITH AISC STANDARDS NOTED ABOVE. DETAILER SHALL ASSUME EQUAL BEAM SPACING BETWEEN COLUMN LINES (OR BETWEEN BEAMS THAT ARE SPECIFICALLY LOCATED ON THE DRAWINGS), UNO ON THE DRAWINGS.
3. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING, UNO:
A. WIDE FLANGE SHAPES AND CHANNELS (W, C, MC) = ASTM A992 (Fy = 50 KSI) B. MISC SHAPES (M, S, L), PLATES, BARS = ASTM A572 (Fy = 50 KSI) C. SQUARE/RECTANGULAR TUBING (HSS) = ASTM A500 GRADE C (Fy = 50 KSI) D. ROUND TUBING (HSS) = ASTM A500 GRADE C (Fy = 50 KSI) E. STRUCTURAL PIPE = ASTM A53 GRADE B (Fy = 35 KSI)
F. STRUCTURAL BOLTS = ASTM A325 OR A490
G. STRUCTURAL NUTS = ASTM A563
H. STRUCTURAL WASHERS = ASTM F436
I. ANCHOR RODS = ASTM F1554 GRADE 55 S1 (WELDABLE)
4. STRUCTURAL STEEL NOT EXPOSED TO WEATHER SHALL BE SHOP PRIMED WITH A RUST-INHIBITIVE PRIMER EXCEPT FOR THE FOLLOWING: SURFACES EMBEDDED IN CONCRETE, SURFACES TO BE FIELD WELDED, SURFACES AT SLIP- CRITICAL CONNECTIONS, SURFACES TO RECEIVE FIRE-RESISTIVE MATERIALS, GALVANIZED STEEL SURFACES, AND WEATHERING STEEL SURFACES. COORDINATE PRIMER SELECTION WITH ARCHITECTURAL FINISH REQUIREMENTS
WHERE APPLICABLE.
5. UNLESS NOTED OTHERWISE, STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A123. GALVANIZE BOLTS AND SIMILAR THREADED FASTENERS IN ACCORDANCE WITH ASTM A153, CLASS C AND D, AS APPLICABLE. ALL WELDS, CUTS, AND ABRASIONS TO GALVANIZED SURFACES SHALL BE REPAIRED IN ACCORDANCE WITH ASTM A780 USING APPROVED ZINC-RICH COATINGS. EXTERIOR STEEL NOTED AS PAINTED SHALL BE PRIMED WITH A RUST-INHIBITIVE PRIMER. COORDINATE PRIMER SELECTION WITH
ARCHITECTURAL FINISH REQUIREMENTS.
6. UNLESS NOTED OTHERWISE, STRUCTURAL STEEL SECTIONS THAT ARE EXPOSED TO WEATHER AND FULLY ENCLOSED, SUCH AS HSS MEMBERS WITH END PLATES, SHALL BE FABRICATED WITH A 1/2" DRAINAGE HOLE LOCATED AT AN INCONSPICUOUS LOCATION NEAR THE LOWEST ELEVATION OF THE MEMBER. FOR VERTICAL HSS SECTIONS, LOCATE DRAINAGE HOLE A MAXIMUM DISTANCE FROM THE BASE EQUAL TO HALF THE CROSS SECTION
DEPTH.
7. STEEL BELOW GRADE SHALL HAVE A MINIMUM OF 3" CONCRETE COVER PROTECTION OR PROTECTED WITH 2 COATS
OF ASPHALTIC PAINT.
8. UNO, ALL STIFFENER PLATES, ANGLES. OR MISCELLANEOUS STEEL SHALL BE WELDED WITH 3/16" FILLET WELD ALL
AROUND WHERE SHOWN IN CONTACT WITH OTHER STEEL MEMBERS.
9. WELDS ARE SCHEMATICALLY INDICATED AS SHOP WELDS OR FIELD WELDS IN DRAWINGS. CONTRACTOR SHALL COORDINATE WELDING SEQUENCE WITH FABRICATOR. SHOP DRAWINGS SHALL DETAIL ALL SHOP AND FIELD
WELDS.
10. GROUT BELOW BASE PLATES SHALL BE HIGH-STRENGTH, NON-SHRINK, NONMETALLIC GROUT, WITH A 28 DAY
MINIMUM COMPRESSIVE STRENGTH OF 7,000 PSI.
11. BEAMS WITHOUT SPECIFIED CAMBER SHALL BE ORIENTED SUCH THAT NATURAL MILL CAMBER IS UPWARD.
12. STRUCTURAL STEEL FRAMING CONNECTIONS SHALL BE BOLTED AND/OR WELDED AND SHALL CONFORM TO THE
FOLLOWING:
A. BOLTED CONNECTIONS SHALL CONFORM TO THE PROVISIONS OF RCSC "SPECIFICATIONS FOR STRUCTURAL
JOINTS USING HIGH-STRENGTH BOLTS."
B. BOLTED CONNECTIONS SHALL USE MINIMUM 3/4" DIAMETER BOLTS AND SHALL HAVE A MINIMUM NUMBER OF
BOLTS PER BEAM DEPTH AS FOLLOWS:
BEAM DEPTH MINIMUM # OF BOLTS
W8 / W10 / W12 2 W14 / W16 / W18 3 W21 / W24 4 W27 / W30 5 W33 / W36 6 W40 / W44 7
C. BOLTS IN BEARING SHALL BE DESIGNED AS TYPE "N".
D. BOLTED CONNECTIONS SHALL BE DESIGNATED AS "SLIP-CRITICAL", "PRETENSIONED", OR "SNUG-TIGHT."
a. SLIP-CRITICAL BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE MINIMUM PRETENSION VALUES IN TABLE J3.1 OF THE AISC SPECIFICATION FOR STRUCTURAL STEEL, SHALL USE TENSION CONTROL BOLTS OR DIRECT TENSION INDICATOR WASHERS, AND SHALL HAVE FAYING SURFACES PROPERLY PREPARED TO MEET CLASS A SURFACE CONDITION, UNO. SLIP-CRITICAL CONNECTIONS SHALL BE REQUIRED AT
LOCATIONS NOTED ON DRAWINGS.
b. PRETENSIONED BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE MINIMUM PRETENSION VALUES IN TABLE J3.1 OF THE AISC SPECIFICATION FOR STRUCTURAL STEEL AND SHALL USE TENSION CONTROL BOLTS OR DIRECT TENSION INDICATOR WASHERS. PRETENSIONED CONNECTIONS INCLUDE ALL MOMENT
CONNECTIONS, BRACED FRAME CONNECTIONS, HANGER CONNECTIONS, GIRT CONNECTIONS,
CONNECTIONS IN TENSION, CONNECTIONS SUBJECT TO VIBRATION, AND ALL CONNECTIONS USING A490
BOLTS.
c. BOLTED CONNECTIONS NOT DESIGNATED AS SLIP-CRITICAL OR PRETENSIONED ARE PERMITTED TO BE
SNUG-TIGHT CONNECTIONS AS DEFINED BY AISC.
E. WELDED CONNECTIONS SHALL CONFORM TO THE PROVISIONS OF THE AWS D1.1 STRUCTURAL WELDING CODE
AND SHALL BE PERFORMED BY CERTIFIED WELDERS.
F. MINIMUM THICKNESS OF ALL CONNECTION MATERIAL SHALL BE 5/16", UNO. MINIMUM THICKNESS OF GUSSET
PLATES AND SHEAR PLATES SHALL BE 3/8".
G. MINIMUM LENGTH OF BEAM CONNECTIONS SHALL BE 1/2 THE BEAM DEPTH.
13. STRUCTURAL STEEL FABRICATOR IS RESPONSIBLE FOR DESIGN AND DETAILING OF STEEL CONNECTIONS
REQUIRED BY THE CONTRACT DOCUMENTS. FABRICATOR SHALL COMPLY WITH THE FOLLOWING:
A. DESIGN ALL CONNECTIONS NOT SPECIFICALLY AND FULLY DETAILED IN THE DRAWINGS.
B. DESIGN CONNECTIONS USING SCHEMATIC DETAILS AND OTHER INFORMATION INDICATED IN THE DRAWINGS.
C. DESIGN CONNECTIONS FOR THE MINIMUM DESIGN LOADS AND MINIMUM CONNECTION REQUIREMENTS NOTED
HEREIN.
D. SUBMIT SIGNED AND SEALED CALCULATIONS FOR THE DESIGN OF MOMENT CONNECTIONS, BRACED FRAME
CONNECTIONS, CONNECTIONS TRANSFERRING AXIAL LOAD, CONNECTIONS THAT ARE PART OF THE BUILDING'S MAIN LATERAL FORCE RESISTING SYSTEM, AND ANY CONNECTIONS OTHER THAN BEAM SIMPLE SHEAR
CONNECTIONS.
E. SELECT AND COMPLETE BEAM SIMPLE SHEAR CONNECTIONS USING SCHEMATIC DETAILS AND THE AISC MANUAL OF STEEL CONSTRUCTION. BEAM SIMPLE SHEAR CONNECTIONS SHALL BE SUBMITTED UPON
REQUEST.
F. REVIEW OF SHOP DRAWINGS SHALL NOT RELIEVE FABRICATOR OF CONNECTION DESIGN RESPONSIBILITY.
14. CONNECTION DESIGN LOADS SHALL BE AS FOLLOWS:
A. ALL DESIGN LOADS INDICATED IN DRAWINGS ARE ASD SERVICE LOADS, UNO.
B. WHERE DRAWINGS INDICATE AXIAL AND/OR MOMENT LOADS IN ADDITION TO BEAM END SHEAR REACTIONS, LOADS SHALL BE CONSIDERED TO ACT SIMULTANEOUSLY, UNO.
C. WHERE MOMENT CONNECTIONS ARE SHOWN WITHOUT A MOMENT LOAD INDICATED, THE MOMENT
CONNECTION SHALL DEVELOP THE FULL MOMENT CAPACITY OF THE BEAM.
D. WHERE BEAM END SHEAR REACTIONS ARE INDICATED IN THE DRAWINGS, CONNECTIONS SHALL DEVELOP THE
REACTIONS INDICATED.
E. WHERE BEAM END SHEAR REACTIONS ARE NOT INDICATED IN THE DRAWINGS, CONNECTION DESIGN LOADS
SHALL BE PROPORTIONED BASED ON THE MAXIMUM TOTAL UNIFORM LOAD TABLES IN PART 3 OF THE AISC MANUAL OF STEEL CONSTRUCTION. NON-COMPOSITE BEAMS SHALL DEVELOP 60% OF THE MAXIMUM TOTAL UNIFORM LOAD FOR THE GIVEN BEAM, SPAN, AND GRADE OF STEEL SPECIFIED. COMPOSITE BEAMS SHALL DEVELOP 90% OF THE MAXIMUM TOTAL UNIFORM LOAD FOR THE GIVEN BEAM, SPAN, AND GRADE OF STEEL
SPECIFIED.
STRUCTURAL STEEL FRAMING:
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2020 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AA 26003955
513 Central Ave.
Sarasota, FL 34236
P:941.917.0883
S-001
GENERAL NOTES
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
100% CONSTRUCTION
DOCUMENTS
24-015
Experience Structural Expertise Atlanta, Boca Raton, Charlotte, Chattanooga, Knoxville, Nashville, Orlando, Raleigh
Copyright • Bennett & Pless, Inc.
All Rights Reserved
B & P Job Number:
1964 - Celebrating Years of Structural Excellence
419 E Oakland Ave, Oakland, Florida 34787 Tel 678 990 8700 x501
2024 60
25.03.025
This item has been electronically signed and sealed by Thomas C. Wilda, P.E., on the date indicated in the digital signature, using a Digital Signature. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
& AND
@ AT
X° DEGREE
∅ DIAMETER
# NUMBER/POUND
ACI AMERICAN CONCRETE INSTITUTE
AESS ARCHITECTURAL EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALT ALTERNATE
ANC ANCHOR
APPROX APPROXIMATE
APC ARCHITECTURAL PRECAST VENEER
AR ANCHOR ROD
ARCH ARCHITECT/ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWPA AMERICAN WOOD PROTECTION ASSOCIATION
AWS AMERICAN WELDING SOCIETY
BB BOND BEAM
B/B BACK TO BACK
BCX BOTTOM CHORD EXTENSION
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BM BEAM
B/ BOTTOM OF
BOT BOTTOM
BP BASE PLATE / BEARING PLATE
BRG BEARING
BRK BRICK
BSMT BASEMENT
BTWN BETWEEN
CANT CANTILEVER
CC CLEAR COVER
CFMF COLD-FORMED METAL FRAMING
CFS COLD-FORMED STEEL
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONNX CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CNR CORNER
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CWI CERTIFIED WELDING INSPECTOR
DBE DECK BEARING ELEVATION
DBL DOUBLE
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DT DOUBLE TEE - PRECAST
DTL DETAIL
DWL DOWEL
DWG DRAWING
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
EMBED EMBEDMENT/EMBEDDED
EPCT EPOXY COATED
EOD EDGE OF DECK
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ESS EXCAVATION SHORING SYSTEM
ESR EVALUATION SERVICES REPORT
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAS FASTENER
FD FLOOR DRAIN
FF FINISH FLOOR
FFE FINISH FLOOR ELEVATION
FIN FINISH
FLR FLOOR
FDN FOUNDATION
FOC FACE OF CONCRETE
FOS FACE OF STEEL
FS FAR SIDE
FT FOOT OR FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GEN GENERAL
GL GRIDLINE
GN GENERAL NOTE
GR GRADE
GS GRIND SMOOTH
HCA HEADED CONCRETE ANCHOR
HC HOLLOW CORE
HDG HOT DIPPED GALVANIZED
HI HIGH
HK HOOK
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL STEEL
HT HEIGHT
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IN INCH
INT INTERIOR
INV INVERT/INVERTED
ISF INSIDE FACE
STRUCTURAL ABBREVIATIONS
JBE JOIST BEARING ELEVATION
JST JOIST
JT JOINT
K KIP (THOUSAND POUNDS)
KSI KIPS PER SQUARE INCH
LAT LATERAL
LBS POUNDS
LF LATERAL FRAME
LFT LINEAR FOOT
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOW
LRFD LOAD RESISTANCE FACTOR DESIGN
LHS LONG HORIZONTAL SLOT
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
LVL LAMINATED VENEER LUMBER
LVS LONG VERTICAL SLOT
MANUF MANUFACTURER
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MID MIDDLE
MILS THOUSANDTH OF AN INCH
MIN MINIMUM
MISC MISCELLANEOUS
ML MASONRY LINTEL
MO MASONRY OPENING
MOM MOMENT
MTL METAL
MW MASONRY WALL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OAE OR APPROVED EQUAL
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND
O/O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OSF OUTSIDE FACE
OSHA OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION
PAF POWDER ACTUATED FASTENERS
PC PRECAST
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PEMB PRE-ENGINEERED METAL BUILDING
PERP PERPENDICULAR
PL PLATE
PLYWD PLYWOOD
PREFAB PREFABRICATED
PROJ PROJECTION
PSF POUND PER SQUARE FOOT
PSI POUND PER SQUARE INCH
PT POINT
RAD RADIUS
RD ROOF DRAIN
REBAR REINFORCING BAR
REF REFERENCE
REINF REINFORCING/REINFORCED
REQD REQUIRED
REQT REQUIREMENT
RTU ROOF TOP UNIT
RXN REACTION
SCHED SCHEDULE
SECT SECTION
SHT SHEET/SHEATING
SIM SIMILAR
SJ SAWN JOINT
SL SLOPE
SOG SLAB ON GRADE
SPA SPACES/SPACING
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SUSP SUSPENDED
SW SHEAR WALL
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE & GROOVE
TCX TOP CHORD EXTENSION
TESS TEMPORARY EXCAVATION
SHORING SYSTEM
THK THICK/THICKNESS
THD THREAD
T/ TOP OF
TMS THE MASONRY SOCIETY
TR TREAD
TS TUBE STEEL
TD TURN DOWN
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UNSCHED UNSCHEDULED
UT UTILITIES
VBF VERTICAL BRACED FRAME
VERT VERTICAL
VIF VERIFY IN FIELD
VX HORIZONTAL SHEAR FORCE
VY VERTICAL SHEAR FORCE
W/ WITH
WD WOOD
WF WIDE FLANGE
W/O WITHOUT
WP WORK POINT
WT WEIGHT
W/T WATER TABLE
WWR WELDED WIRE REINFORCEMENT
WS WATERSTOP
XB X-BRACING
SLOPE
DN
FTG
STEP
T/XXX
X'-X"
ELEVATION MARK
FOOTING STEP
SLAB STEP
TYPICAL FOUNDATION PLAN ELEMENTS
TYPICAL FOUNDATION PLAN ELEMENTS
MASONRY STRUCTURAL WALL
MASONRY STRUCTURAL WALL BELOW
MASONRY PARTITION WALL
MASONRY PARTITION WALL BELOW
CONCRETE WALL
CONCRETE WALL BELOW
STUD WALL
STUD WALL BELOW
STRUCTURAL LEGEND
SLOPE DIRECTION
W12 X65
BP1
P1 F6
WF2
COLUMN SIZE
BASEPLATE SIZE
FOOTING SIZE
PIER SIZE
WALL FOOTING SIZE
PC4
GB1
AUGER
CAST PILE
PILE CAP SIZE
GRADE BEAM SIZE
TYPICAL ROOF BEAM DESIGNATIONS
ADDITIONAL BEAM REACTION DESIGNATIONS
TYPICAL JOIST DESIGNATIONS
TYPICAL FLOOR BEAM DESIGNATIONS
TYPICAL JOIST GIRDER DESIGNATIONS
SR1
1"
FLOOR MARK AND SPAN DIRECTION
ROOF DECK MARK AND SPAN DIRECTION
TENDON DRAPE ELEVATION
STUD RAIL MARK
48G 9N 8.6K/4.0K [-5"]
JOIST GIRDER DEPTH (IN)
TOP OF STEEL RELATIVE TO DBE (-2
1/2" IF NOT SHOWN)
NUMBER OF SPANS BETWEEN
PANEL POINTS
TOTAL LOAD AT EACH PANEL POINT
LIVE LOAD AT EACH PANEL POINT
J3 [-2"]
UNIFORM TOTAL LOAD (LB/FT)
22K4
22K(220/133)
JOIST DEPTH (IN)
UNIFORM LIVE LOAD (LB/FT)
22KSP4
JOIST SIZE
JOIST MARK, SEE SCHEDULE
FOR SIZE
TOP OF STEEL RELATIVE TO DBE (0"
IF NOT SHOWN)
SPECIAL JOIST, SEE NOTES
AND/OR LOAD DIAGRAMS
A=15K
40K-FT
AXIAL LOAD
REACTION
MOMENT
REACTION
MOMENT
CONNECTION
32K-FT
SEISMIC MOMENT
CONNECTION
W16X31 c=1" 27k 27k[-2 1/2"]
BEAM SIZE
CAMBER (0" IF NOT SHOWN)
TOP OF STEEL RELATIVE TO DBE
(0" IF NOT SHOWN)
END SHEAR REACTION
W18X35 (40) c=1 1/4"
34k 34k[-8"]
BEAM SIZE
NUMBER OF SHEAR STUDS
CAMBER (0" IF NOT SHOWN)
TOP OF STEEL RELATIVE TO FFE
(EQUALS SLAB THICKNESS IF NOT SHOWN)
END SHEAR REACTION
6"
#S
#R
GRATING MARK AND SPAN DIRECTION#G
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2020 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AA 26003955
513 Central Ave.
Sarasota, FL 34236
P:941.917.0883
S-002
STRUCTURAL LEGEND AND
ABBREVIATIONS
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
100% CONSTRUCTION
DOCUMENTS
24-015
Experience Structural Expertise Atlanta, Boca Raton, Charlotte, Chattanooga, Knoxville, Nashville, Orlando, Raleigh
Copyright • Bennett & Pless, Inc.
All Rights Reserved
B & P Job Number:
1964 - Celebrating Years of Structural Excellence
419 E Oakland Ave, Oakland, Florida 34787 Tel 678 990 8700 x501
2024 60
25.03.025
This item has been electronically signed and sealed by Thomas C. Wilda, P.E., on the date indicated in the digital signature, using a Digital Signature. Printed copies of this
WF2
WF2
WF2
WF5
WF5
W F
W F
W F
W F2
NOTE 9
NOTE 9
NOTE 9
S-200
S-200
S-200
S-200
S-200
EXISTING TO REMAIN
NOTE 1
NOTE 10
NOTE 10
T.
E.
T.E.8
T.
E.
CJ
CJ
S-200
A
B
C
1 2
C1C1
C1
F3
3'
0"
2' - 0"
F3
S-200
S-200
CJ
CJ
S-200
HSS4X
4X
1/4
HSS4X4X1/4
F2
HSS6X
4X
1/4
HSS6X4X1/4
HSS4X
4X
1/4
HSS4X4X1/4
F2T.
E.
T.E.8
S-300
S-300
SIM
S-300
S-300
SIM
FOUNDATION PLAN NOTES:
1. 6" CONCRETE SLAB WITH #4 BARS @ 18" O.C. MAX. EA. WAY AT MID-DEPTH OF SLAB.
2. SEE ARCHITECTURAL DRAWINGS FOR SLOPES, DROPS AND DRAIN LOCATIONS IN
FLOOR SLABS.
3. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS BEFORE
COMMENCING CONSTRUCTION. DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER. FOR ADDITIONAL
INFORMATION SEE ARCHITECTURAL DRAWINGS.
4. FOR DIMENSIONS NOT SHOWN, SEE OTHER STRUCTURAL DRAWINGS AND VERIFY
WITH ARCHITECTURAL DRAWINGS. DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND THE STRUCTURAL ENGINEER.
5. ELEVATIONS SHOWN REFERENCE SLAB-ON- GRADE, EL 0'-0".
6. KEY ALL INTERSECTING MASONRY WALLS TOGETHER.
7. TOP OF NEW FOOTINGS TO BE AT -1'-4" BELOW GRADE U.N.O.
8. ALL WALLS AND COLUMNS SHALL BE CENTERED ON THEIR FOOTINGS U.N.O., TYP.
9. EXISTING 2'-0" FOOTING, F.V.
10. NEW CONC. STAIRS, SEE SECTIONS.
T.E.8 = 8" WIDE x 16" THICKENED EDGE PER DETAIL ON SHEET S-300 WF2 = 2'-0" x CONT. x 16"THK. W/ (3) #5 BOTT. CONT. W/ #5 @ 10" O.C. BOTT.
WF5 = 5'-0" x CONT. x 16"THK. W/ (6) #5 BOTT. CONT. W/ #5 @ 10" O.C. BOTT.
C1 = 16"x16" CONC. COLUMN W/ (8) #6 VERT. W/ #3 TIES @ 12" O.C. MAX.
F3 = 3'-0" x 3'-0" x 16" THK CONC. FOOTING W/ (4) #5 BOTT. EA. WAY.
11 5/8" CONCRETE WALL W/ #5 EACH FACE VERTICAL &
HORIZONTAL @ 18" O.C MAX.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2020 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AA 26003955
513 Central Ave.
Sarasota, FL 34236
P:941.917.0883
S-101
FOUNDATION PLAN
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
100% CONSTRUCTION
DOCUMENTS
24-015
S-101
FOUNDATION PLAN
SCALE: 1/4" = 1'-0"
Experience Structural Expertise Atlanta, Boca Raton, Charlotte, Chattanooga, Knoxville, Nashville, Orlando, Raleigh
Copyright • Bennett & Pless, Inc.
All Rights Reserved
B & P Job Number:
1964 - Celebrating Years of Structural Excellence
419 E Oakland Ave, Oakland, Florida 34787 Tel 678 990 8700 x501
2024 60
25.03.025
This item has been electronically signed and sealed by Thomas C. Wilda, P.E., on the date indicated in the digital signature, using a Digital Signature. Printed copies of this
NEW HSS 16x4x1/4" (LFV)
(T/STL = 11'-8", VERIFY W/
ARCH/DOOR MANUF)
NEW HSS4X4X1/4"
T/STL = 11'-2"
NEW HSS4x4x1/4"
T/STL = 11'-2"
S-300
NEW HSS 16x4x1/4" (LFV)
(T/STL = 11'-8", VERIFY W/
ARCH/DOOR MANUF)
S-300 SIM.
NOTE 3, TYP. NOTE 3, TYP.NOTE 4, TYP.
NOTE 3, TYP. NOTE 3, TYP.
NOTE 4, TYP.
FRAMING PLAN NOTES:
1. VERIFY DIMENSIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS
BEFORE COMMENCING CONSTRUCTION. DISCREPANCIES SHALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER. FOR
ADDITIONAL INFORMATION SEE ARCHITECTURAL DRAWINGS.
2. FOR DIMENSIONS NOT SHOWN, SEE OTHER STRUCTURAL DRAWINGS AND
VERIFY WITH ARCHITECTURAL DRAWINGS. DISCREPANCIES SHALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND THE STRUCTURAL ENGINEER.
3. WELD NEW COLUMN TO EXISTING PRE-ENGINEERED METAL BUILDING COLUMN
W/ FLARE BEVEL WELD EA. SIDE 2" LG. @ 12" O.C. TYP.
4. WELD ALL TUBE STEEL BEAMS TO TUBE STEEL COLUMNS W/ 1/4" FILLET WELD
ALL AROUND.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2020 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AA 26003955
513 Central Ave.
Sarasota, FL 34236
P:941.917.0883
S-102
FRAMING PLAN
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
100% CONSTRUCTION
DOCUMENTS
24-015
Experience Structural Expertise Atlanta, Boca Raton, Charlotte, Chattanooga, Knoxville, Nashville, Orlando, Raleigh
Copyright • Bennett & Pless, Inc.
All Rights Reserved
B & P Job Number:
1964 - Celebrating Years of Structural Excellence
419 E Oakland Ave, Oakland, Florida 34787 Tel 678 990 8700 x501
2024 60
25.03.025
S-102
FRAMING PLAN
SCALE: 1/4" = 1'-0"
This item has been electronically signed and sealed by Thomas C. Wilda, P.E., on the date indicated in the digital signature, using a Digital Signature. Printed copies of this
FOR REINFORCEMENT
SEE PLAN TYP.
3" CLR.
TY
P.
3" C
LR
11 5/8" MASONRY SITE WALL W/ #5 @ 40"
O.C. MAX. PROVIDE #9 GAGE LADDER
HORIZONTAL REINFORCEMENT EVERY
OTHER COURSE, TYP. f'm=1,900 psi; "S" TYPE MORTAR; 2,000 psi GROUT, MIN.
(M
AX
1'
4" 1'
4"
CONTINUOUS 11 5/8" KNOCK-OUT
BLOCK W/ (2) #6 CONT. GROUT SOLID.
GRADE
DOWELS TO MATCH VERTICAL
REINFORCE MENT. HOOK BOTTOM OF
DOWEL 3" CLEAR FROM BOTTOM OF
FOOTING, TYP. LAP 48 BAR DIA. MIN.
11 5/8" CONCRETE WALL W/ #5 EA.
FACE HORIZ. & VERT. @ 18" O.C. MAX.
LAP 48 BAR DIA. MIN.
3'
4" (M
AX
FOR REINFORCEMENT
SEE PLAN TYP.
3" CLR.
TY
P.
3" C
LR
11 5/8" MASONRY SITE WALL W/ #5 @ 40"
O.C. MAX. PROVIDE #9 GAGE LADDER
HORIZONTAL REINFORCEMENT EVERY
OTHER COURSE, TYP. f'm=1,900 psi; "S" TYPE MORTAR; 2,000 psi GROUT, MIN.
3' -4
" M
AX
1'
4"
1'
4"
CONTINUOUS 11 5/8" KNOCK-OUT
BLOCK W/ (2) #6 CONT. GROUT SOLID.
GRADE
11 5/8" CONCRETE WALL W/ #5 EA. FACE
HORIZ. & VERT. @ 18" O.C. MAX.
CONC. SLAB ON COMPACTED FILL, SEE
PLAN.
DOWELS TO MATCH VERTICAL
REINFORCE MENT. HOOK BOTTOM OF
DOWEL 3" CLEAR FROM BOTTOM OF
FOOTING, TYP. LAP 48 BAR DIA. MIN.
'-4
" M
AX
1' - 0"
1'
4"
6" POURED CONC. STAIR
W/ #4 @ 18" O.C. EA.
WAY.
SEE ARCH. FOR QUANTITY
OF RISERS & RUNS
#4 @ 18" O.C. MAX.
LAP 24" MIN.
(2) #5 BOTT. CONT.
SIDEWALK BY OTHERS.
FOR REINFORCEMENT
SEE PLAN TYP.
3" CLR.
TY
P.
3" C
LR
(M
AX
3'
4" 1'
4"
1'
4"
GRADE
7 5/8" MASONRY SITE WALL W/ #5 @ 48"
O.C. MAX. GROUT FILL WALL SOLID.
PROVIDE #9 GAGE LADDER
HORIZONTAL REINFORCEMENT EVERY
OTHER COURSE, TYP. f'm=1,500 psi; "S" TYPE MORTAR; 2,000 psi GROUT, MIN.
SHORE UP WALL UNTIL SLAB REACHES
28-DAY STRENGTH.
CONC. SLAB ON COMPACTED FILL,
SEE PLAN.
DOWELS TO MATCH VERTICAL
REINFORCEMENT. HOOK BOTTOM OF
DOWEL 3" CLEAR FROM BOTTOM OF
FOOTING, TYP. LAP 48 BAR DIA. MIN.
FOR REINFORCEMENT
SEE PLAN TYP.
3" CLR.
TY
P.
3" C
LR
3' -4
" M
AX
1'
4"
1'
4"
GRADE
CONC. SLAB ON COMPACTED FILL,
SEE PLAN.
NEW 16"x16" CONC. COLUMN W/ (8) #
6 VERTICAL REINF. W/ #3 TIES @ 12"
O.C. MAX.
NEW CANOPY COLUMN & CONNECTION
TO SLAB BY CANOPY MANUF.
CMU WALL (BEYOND)
EXISTING 2'-0" WIDE
FOOTING (F.V.)
CONC. SLAB ON COMPACTED FILL,
SEE PLAN.
NEW CANOPY COLUMN & CONNECTION
TO SLAB BY CANOPY MANUF.
THICKENED EDGE BEYOND.
1/2" ISOLATION JOINT.
EXISTING CMU WALL.
SEE "FOOTING EXTENSION DETAIL"
ON SHEET S-300.
TYP.
3" CLR.
TY
P.
3" C
LR
HSS COLUMN W/ ANCHOR BOLTS
AND BASE PLATE, SEE PLAN.
LEVELING PLATE 3/16xBASE PLATE DIM.
OR USE LEVELING NUTS
1" MIN. NON SHRINK GROUT OR
THICKNESS REQ'D. FOR LEVELING NUTS
SAWCUT EXISTING SLAB AS FIELD
CONDITIONS ALLOW TO MINIMIZE
DAMAGE TO EXPOSED SLAB.
CAREFULLY UNDERMINE EXISTING
SLAB TO PLACE NEW FOOTER, TYP.
TYP. ALL SIDES
1 1/2"
UNDERCUT
1/4"
3" T
YP
3" TYP.
FT
G
D
EP
TH
CONC. FOOTING, SEE PLAN
FOR SIZE AND REINF.
EXIST. S.O.G.
5" DEEP POCKET FOR BASE PLATE.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2020 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AA 26003955
513 Central Ave.
Sarasota, FL 34236
P:941.917.0883
S-200
FOUNDATION SECTIONS
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
100% CONSTRUCTION
DOCUMENTS
24-015
Experience Structural Expertise Atlanta, Boca Raton, Charlotte, Chattanooga, Knoxville, Nashville, Orlando, Raleigh
Copyright • Bennett & Pless, Inc.
All Rights Reserved
B & P Job Number:
1964 - Celebrating Years of Structural Excellence
419 E Oakland Ave, Oakland, Florida 34787 Tel 678 990 8700 x501
2024 60
25.03.025
S-200
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION STAIR SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
S-200
FOUNDATION PLAN
SCALE: 3/4" = 1'-0"
This item has been electronically signed and sealed by Thomas C. Wilda, P.E., on the date indicated in the digital signature, using a Digital Signature. Printed copies of this
3/4"
METAL KEY JOINT
OR FORMED KEY WAY.
SLAB REINF. CONT.
THROUGHT JOINT.
1/ 4" t 3/
8" t t
SAW CUT AS SOON AS POSSIBLE WITHOUT
RAVELING CONCRETE. ( 4 TO 12 HOURS
AFTER POUR)
CUT ALTERNATE CROSS
WIRES AT JOINT.
SAW CUTJOINT FILLER
t
1/ t
1/2" PREMOLDED FILLER W/
PULLOUT TABS FILLED W/
WATERPROOF SEALENT.
t
WALL
OR PIER
(2) #5 CONT. (TOP & BOTTOM) REINF. TO BE
DISCONTINUOUS @ CONSTRUCTION &
CONTROL JOINTS IN SLAB ON GRADE.
2x8 KEY @ CONSTRUCTION JOINT
#4 x 3'-0"
@ 16" O.C.
REINF. (SEE PLAN.)
#4 DISTCONTINUOUS AT
CONSTRUCTION &
CONTROL JOINTS.
(S
EE
P
LA
N
8"
0'
8" M
IN
1'
0" M
AX
CONTINUOUS CMU KNOCK-OUT
BLOCK ONE OR TWO. (SEE
SECTIONS & DETAILS). PROVIDE HOOK ON VERT. INTO TOP
OF CONTINUOUS KNOCK-OUT BLOCK
WITHOUT WALL ABOVE.
VERT. REINFORCING W/ MATCHING
DOWELS IN FOUNDATION. SEE
PLAN FOR SIZE AND LOCATION.
SEE "TYP. MASONRY WALL
CONST. W/ TIE BEAM" FOR TYP.
FDN. INFO.
MORTAR BED
ASTM C-90 C.M.U'S
MORTAR CROSS WEBS ADJACENT
TO FILLED CELLS
LADDER TYPE HORIZ. JOINT REINF. @16"
O.C. STARTING AT FIRST COURSE ABOVE
FOUNDATION. LAP SPLICES 6" USE
PREFAB L'S AND T'S AT WALL
INTERSECTIONS
VERTICAL REINFORCING W/ MATCHING
DOWELS IN FOUNDATION. SEE PLAN
FOR SIZE AND LOCATION.
CAST IN PLACE REINF. CONC. TIE BEAM
SEE PLAND & SECTIONS & DETAILS FOR
SIZE & REINF.
PLACE METAL LATH OR WIRE SCREEN
OVER CORES NOT TO BE FILLED (SHEET
METAL AND FELT PROHIBITED)
GROUT FILLED CELL. PLACE AND
CONSOLIDATE GROUT IN 4 FT. LIFTS
SET FIRST COURSE IN FULL MORTAR
BEDDING
CLEAN OUT OPENINGS AT GROUT FILLED CELL
LOCATIONS. FOR WALLS OVER 4 FT. HIGHFOUNDATION
PROVIDE HOOK ON VERT. INTO TOP
OF CONTINUOUS TIE BEAM
WITHOUT WALL ABOVE.
SIZE & REINF.
SEE PLAN FOR
3" CLR. TYP.
B
AR
D
IA
. L
AP
(T
YP
3"
C
LR
SP
AC
IN
G
(M
AX
1/
TI
E
COLUMN TIES
DOWELS SHALL BE THE SAME
SIZE AND NUMBER AS COLUMN
REINFORCING.
I.J. (TYP.)
TIE ADDED SLAB OR BEAM
SEE PLAN
STD ACI 90 HOOK
VERTICAL REINFORCING (HOOK
AS SHOWN UNDER TOP STEEL)
CONC. COL. SP
AC
IN
G
(M
AX
1/
2" T
IE
COLUMN TIES
EXIST. CONC. FTG., F.V.
SEE PLAN
NEW CONC. FTG, EXT.
TY
P.
3" C
LR
TYP.
3" CLR.
#5 BAR @ 12" O.C. MAX.
INTENTIONALLY ROUGHEN AND APPLY
BONDING AGENT
(2) #5 BOTT. CONT. (MIN.) FOR
EVERY ADDITIONAL 12" EXTENSION
ADD ADDITIONAL #5 BAR.
M
AT
C H
E
XI
ST
DRILL & EPOXY 10" INTO EXIST. CONC.
W/ HILTI RE500 V3 EOPXY.
NEW ROLL-UP DOOR AND
CONNECTION TO TUBE STEEL BEAM
BY ROLL-UP DOOR MANUF. (WT.=
500lbs)
EXISTING STEEL COLUMN, F.V.
NEW HSS 16x4x1/4" STEEL
BEAM.
NEW CONT. STL PLATE (F.V. THICKNESS SO
THAT THE NEW HSS BEAM INSIDE FACE
ALIGNS WITH OUTSIDE FACE OF EXISTING
PEMB COLUMN (BEYOND). CONN.