Genesis Engineering Design Plans
This document comprises engineering design plans prepared for Sarasota County, Florida in connection with the South County Fleet Renovation project, a construction initiative focused on renovating and improving the existing South County Fleet maintenance and support facilities. The design plans establish the technical specifications, site layout, and construction requirements that guide the renovation scope. The plans appear to serve as the foundational engineering documentation that bidders will reference when preparing their construction proposals and cost estimates for the fleet facility improvement project. The documents establish the baseline conditions of the existing facilities and delineate the proposed improvements, configurations, and infrastructure modifications necessary to modernize the maintenance and support operations at the South County Fleet location.
The engineering design plans provide the technical framework upon which construction contractors will base their bids for the renovation contract. These plans function as critical reference materials for all prospective bidders and establish the design standards, material specifications, and construction methodologies that the awarded contractor must follow during project execution. The plans ensure consistency between the County's vision for the facility improvements and the actual construction work performed, serving as the contractual and operational baseline for project delivery and quality assurance throughout the renovation period.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FSD
RD
2023 FBC-EC COMPLIANCE NOTES
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C COMMON
CD CONDENSATE
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CO2 CARBON DIOXIDE
COP COEFFICIENT OF PERFORMANCE
CU CONDENSING UNIT
DAC DEHUMIDIFICATION AHU
DB DRY BULB
DCU DEHUMIDIFICATION CU
DDC DIRECT DIGITAL CONTROL
DEGF DEGREE FAHRENHEIT
DI DIGITAL INPUT
DN DOWN
DO DIGITAL OUTPUT
DWG DRAWING
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
ERV ENERGY RECOVERY VENTILATOR
FC FAIL CLOSED
FC FAN COIL (EXISTING)
FCU FAN COIL UNIT
FD FIRE DAMPER
FF FLOW FEEDBACK/STATUS SIGNAL
FLA FULL LOAD AMPS
FO FAIL OPEN
FPM FEET PER MINUTE
FT FEET
GPM GALLONS PER MINUTE
H HUMIDITY
HS HUMIDISTAT
HP HEAT PUMP
HP HORSEPOWER
HWS HOT WATER SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
IAQ INDOOR AIR QUALITY
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LPS LOW PRESSURE STEAM
LPR LOW PRESSURE RETURN
LWT LEAVING WATER TEMPERATURE
M MOTORIZED
MBH THOUSAND BTUH
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVER CURRENT PROTECTION
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OBD OPPOSED BLADE DAMPER
OA OUTDOOR AIR
P PRESSURE
PF PROPORTIONAL, LINEARIZE FEEDBACK, 4-20mA
SIGNAL
PRV PRESSURE REDUCING VALVE
PRS PRESSURE REDUCING STATION
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RA RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RS/L REFRIGERANT SUCTION/LIQUID
RTU ROOFTOP PACKAGED UNIT
SA SUPPLY AIR
SF SQUARE FEET
SS START/STOP SIGNAL
S.S. STAINLESS STEEL
SP STATIC PRESSURE
T TEMPERATURE
V-PH VOLTAGE-PHASE
TD TIME DELAY
TS TEMPERATURE SENSOR
TSP TOTAL STATIC PRESSURE
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
V/PH VOLTS/PHASE
WB WET BULB
WG WATER GAUGE
WR CHILLED WATER RESET 4-20 mA SIGNAL
W/ WITH
W/O WITHOUT
MECHANICAL ABBREVIATIONS LEGEND
RETURN AIR
SMOKE DETECTOR
SQUARE FEET)
REQUIRED INDICATED IN
DOOR LOUVER (FREE AREA
UNDERCUT DOOR
L
U
S
SINGLE LINE
SUPPLY AIR
RADIUS ELBOW (R=1.5)
CONTROL DAMPER-
AIR REGISTER (R)
SUPPLY AIR GRILLE (G) OR SUPPLY
FLEXIBLE CONNECTION (FXC)
AIR FLOW
RISE OR DROP DIRECTION OF
REC. BRANCH DUCT TAKE-OFF W/ VD
ELBOW W/ TURNING VANES
DIFFUSER
RD
TO BE REMOVED.
EXISTING EQUIPMENT OR DUCTWORK
ACCESS DOOR
MOTOR OPERATED DAMPER (MOD)
MANUAL VOLUME DAMPER (MVD)
NEW DUCTWORK
EXISTING DUCTWORK TO REMAIN
AD
VD
AD
DOUBLE LINE
D R
AD
VD
# KEYED NOTE NUMBER
X
X
X
X
CONNECT NEW TO EXISTING
INDICATES DRAWING ON WHICH
DETAIL APPEARS
INDICATES SECTION NUMBER
INDICATES ON WHICH DRAWING
SECTION APPEARS
INDICATES REVISION & NUMBER
MECHANICAL SYMBOL LEGEND
INDICATES DETAIL, PLAN, SECTION, AND/OR
DIAGRAM(APPLIES ONLY WHERE INDICATED
TYP
X-X
X
X
X
SYSTEM NUMBER
INDICATES TYPICAL DETAIL
(APPLIES TO ALL CONTRACT
ON DRAWINGS)
INDICATES DRAWING ON WHICH
DETAIL APPEARS
(IF APPLICABLE)
DRAWINGS)
EQUIPMENT IDENTITY
(SEE EQUIPMENT ABBREVIATION
LIST AND SCHEDULES)
EQUIPMENT NUMBER
A
CFM
A
CFM
A
CFM
A
CFM
M
DUCT SYMBOLSGENERAL SYMBOLS
ROUND BRANCH DUCT TAKE-OFF W/ VD
T THERMOSTAT
PIPE RISING UP
PIPE DROPPING DOWN
DIRECTION OF FLOW
AUTOMATIC CONTROL VALVE (3-WAY)
PRESSURE REDUCING VALVE (PSI)
AUTOMATIC CONTROL VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
GATE VALVE
PRESSURE GAUGE
PIPE WELL
F.S.
FLOW SWITCH
THERMOMETER
STRAINER
PIPING SYMBOLS
DEMOLISH TO THIS POINT
FIRE DAMPER W/ ACCESS
DOOR
FIRE SMOKE DAMPER W/ ACCESS
DOOR
RADIATION DAMPER W/ ACCESS
THROUGH DEVICE
EXHAUST AIR
AUTO AUTOMATIC
FD
GENERAL NOTES
1. PROVIDE AUTOMATIC CHANGEOVER 7-DAY PROGRAMABLE THERMOSTATS BY
EQUIPMENT MANUFACTURER WITH 2-HOUR OCCUPANT OVERRIDE AND 10-HOUR
MINIMUM BATTERY BACKUP. PROVIDE AT LEAST ONE HUMIDISTAT FOR EACH
DEHUMIDIFICATION (AND/OR HUMIDIFICATION) SYSTEM PROVIDED. PROGRAM
SETBACK TEMPERATURES TO 85°F(COOL) AND 55°F(HEAT). ALL TEMPERATURE
CONTROLS ARE TO BE TESTED, ADJUSTED AND CALIBRATED FOR PROPER
OPERATION. MOUNT ALL THERMOSTATS AND TEMPERATURE SENSORS AS
INDICATED ON THE DRAWINGS. COORDINATE EXACT LOCATION WITH THE
ARCHITECT. PROVIDE LOCKING COVER AS REQUIRED BY THE ARCHITECT OR THE
OWNER. MOUNT BETWEEN 48"-54" AFF. PROVIDE THERMOSTATS WITH 5 DEGREE
DEADBAND AND SETPOINT OVERLAP RESTRICTIONS. (PER FBC-EC C403.2.4)
2. WHERE MECHANICAL VENTILATION IS PROVIDED, THE SYSTEM SHALL PROVIDE THE
CAPABILITY TO REDUCE THE OUTDOOR AIR SUPPLY TO THE MINIMUM REQUIRED BY
CHAPTER 4 OF THE FLORIDA BUILDING CODE - MECHANICAL. (PER FBC-EC C403.2.6)
3. PROVIDE MINIMUM R-4.2 INSULATION FOR ALL SUPPLY AND RETURN DUCTS OR
PLENUMS IN UNCONDITIONED SPACES OR BURIED UNDERGROUND. PROVIDE
MINIMUM R-6 INSULATION FOR ANY DUCTWORK ON EXTERIOR OR IN VENTILATED
ATTIC. INSULATION SHALL BE PROTECTED FROM DAMAGE FROM SUNLIGHT,
MOISTURE, MAINTENANCE, AND WIND. ADDITIONAL INSULATION WITH VAPOR
BARRIER SHALL BE PROVIDED WHERE MINIMUM DUCT INSULATION REQUIREMENTS
ARE INSUFFICIENT TO PREVENT CONDENSATION (PER FBC-EC C403.2.9.1)
4. MECHANICAL SYSTEMS SHALL BE COMMISSIONED AND COMPLETED IN
ACCORDANCE WITH FBC-EC SECTION C408.2, INCLUDED IN THESE SPECIFICATIONS
BY REFERENCE.
SUBMISSION.
1. DO NOT SCALE FROM THESE DRAWINGS. EXACT DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL DRAWINGS.
2. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.
3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND REGULATIONS INCLUDING, BUT NOT
LIMITED TO, NATIONAL, CITY, STATE, AND LOCAL ORDINANCES WHICH MAY BE IN EFFECT. ALL MECHANICAL MATERIALS, INSTALLATION
PROCEDURES, AND SYSTEM LAYOUTS SHALL BE APPROVED BY ALL APPLICABLE CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION, AND IT
SHALL BE THE MECHANICAL CONTRACTOR'S RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS AND APPROVALS FOR THIS INSTALLATION.
4. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW THESE PLANS AND SPECIFICATIONS AS WELL AS THE RELATED
PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS TO BECOME
FAMILIAR WITH THE FULL PROJECT SCOPE. IN ADDITION, THIS CONTRACTOR MUST COORDINATE WITH THE OWNER OR OWNER'S REPRESENTATIVE
TO FULLY UNDERSTAND ALL REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN AND WHICH THE OWNER MAY CONSIDER PART OF THIS
CONTRACT. DURING THE COURSE OF CONSTRUCTION COORDINATION AND ACTUAL CONSTRUCTION, IT IS THE RESPONSIBILITY OF THIS
CONTRACTOR TO WORK CLOSELY WITH ALL ACCOMPANYING CONTRACTORS AND TRADESMEN IN ORDER TO ENSURE A SMOOTH RUNNING AND
CAREFULLY COORDINATED INSTALLATION.
5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE BID DOCUMENTS OR BETWEEN THESE BID DOCUMENTS AND THE RELATED PLUMBING, FIRE
PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS, OR BETWEEN THESE BID
DOCUMENTS AND FIELD CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT, AND ENGINEER PRIOR TO BID
SUBMISSION.
6. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN THESE DRAWINGS, BETWEEN INFORMATION PROVIDED IN THESE DRAWINGS
AND THE PROJECT SPECIFICATIONS, AND/OR WITHIN THE PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST COST
REQUIREMENTS SHALL APPLY. SHOULD THIS CONTRACTOR REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR CLARIFICATION.
WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER OF RECORD SHALL HAVE THE SOLE DISCRETION AND RIGHT TO PROVIDE INTERPRETATION
OF INTENT OF THE CONTRACT DOCUMENTS AS REQUIRED. THIS INTERPRETATION SHALL SERVE TO DIRECT THE CONTRACTOR IN ACCORDANCE
WITH THE IMPLIED INTENT OF THE CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE PROJECT.
7. THE MECHANICAL CONTRACTOR SHALL PROVIDE A COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS, INDICATING THE PRECISE LOCATION OF ALL
SYSTEMS, EQUIPMENT, CONCEALED OR EMBEDDED PIPING, PIPING CONNECTIONS, AND ACCESS DOORS. THESE DRAWINGS SHALL ALSO INCLUDE
ALL CHANGES AND DEVIATIONS FROM THE BID DOCUMENTS.
8. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW MECHANICAL EQUIPMENT WITH NEW LIGHT LOCATIONS AND TILE LOCATIONS.
REFER TO THE ARCHITECT'S REFLECTED CEILING PLAN LAYOUT.
9. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. AIR VELOCITY SHALL NOT EXCEED 700 FEET PER MINUTE IN
DWELLING UNITS.
10. RUN ALL DUCTWORK AND PIPING WITH AS FEW OFFSETS AS POSSIBLE THROUGHOUT THE ENTIRE BUILDING. COORDINATE AND VERIFY WITH
OTHER CONTRACTORS SO AS NOT TO INTERFERE WITH PLUMBING, FIRE PROTECTION PIPING, LIGHTING SYSTEMS, ETC.
11. ALL REQUIRED OFFSETS, RISES, AND DROPS DUE TO POSSIBLE OBSTRUCTIONS OF DUCT AND PIPE RUNS ARE NOT NECESSARILY SHOWN. THIS
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIPING, SUPPORTS, ETC. NECESSARY FOR PROPER
INSTALLATION AND OPERATION OF NEW HVAC SYSTEM. THIS CONTRACTOR SHALL INCLUDE A CONTINGENCY IN HIS/HER BID TO OFFSET ANY COST
REQUIRED FOR ADDITIONAL FITTINGS AND LABOR THAT MAY BE REQUIRED.
12. ALL EXPOSED HORIZONTAL AND VERTICAL DUCTWORK AND PIPING SHALL BE INSTALLED IN A NEAT ARRANGEMENT IN LOCATIONS WHICH ARE THE
MOST INCONSPICUOUS. VERTICAL DROPS SHALL BE KEPT TO AN ABSOLUTE MINIMUM AND THEIR FINAL LOCATIONS SHALL BE COORDINATED AND
RUN WITHIN CHASES, WALLS, AND SOFFITS WITH OTHER MECHANICAL, ELECTRICAL, PLUMBING, ETC. FEEDS. ALL SUCH LOCATIONS ARE TO BE
REVIEWED WITH AN OWNER REPRESENTATIVE AND ARCHITECT PRIOR TO INSTALLATION.
13. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL
ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.
14. ALL DUCT PENETRATIONS THROUGH A RATED FLOOR, WALL ,OR CEILING ASSEMBLY SHALL BE PROVIDED WITH A FIRE DAMPER. FOR AIR DEVICES
INSTALLED IN A RATED FLOOR/CEILING ASSEMBLY, INSTALL A CEILING RADIATION DAMPER. REFER TO DETAIL SHEET.
15. THROUGH PENETRATIONS OF FIRE RESISTANCE RATED HORIZONTAL ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED
THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE
PRESSURE DIFFERENTIAL OF 0.01 INCHES OF WATER (2.49PA). THE SYSTEM SHALL HAVE AN F/T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
THAN THE REQUIRED RATING OF THE FLOOR WALL, OR CEILING PENETRATED. SEE ARCHITECTURAL DRAWINGS FOR RATED ASSEMBLY LOCATIONS, RATINGS, AND DETAILS. EXCEPTIONS: FLOOR PENETRATIONS CONTAINED AND LOCATED WITHIN THE CAVITY OF A WALL ABOVE THE FLOOR
OR BELOW THE FLOOR DO NOT REQUIRE A T RATING.
16. DUCT SMOKE DETECTORS SHOWN ON PLANS ARE DIAGRAMMATIC. REFER TO MANUFACTURER'S INSTRUCTIONS FOR EXACT/OPTIMUM LOCATION IN
DUCTWORK. DUCT SMOKE DETECTORS SHALL BE PURCHASED BY THE ELECTRICAL CONTRACTOR, INSTALLED BY THE MECHANICAL CONTRACTOR
AND WIRED INTO FIRE PROTECTION SYSTEM BY THE FIRE PROTECTION CONTRACTOR.
18. CONDENSATE SHALL BE PIPED FULL SIZE TO THE NEAREST APPROVED FLOOR DRAIN, HUB DRAIN, STORM WATER DRAINAGE SYSTEM, OR
LANDSCAPED/GRASS AREA VIA AN INDIRECT CONNECTION. CONDENSATE SHALL NOT BE ALLOWED TO DRAIN ONTO ANY WALKWAY.
19. DRYER EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF MIN. 0.016" GALVANIZED STEEL WITH A SMOOTH INTERIOR AND NO PROJECTIONS.
JOINTS SHALL RUN IN DIRECTION OF AIRFLOW. PROVIDE FLAPPER STYLE GRAVITY BACKDRAFT DAMPER AT TERMINATION OF EXHAUST OUTLET
INTEGRAL TO WALL OR ROOF CAP. INSTALL PERMANENT LABEL AT DRYER CONNECTION LISTING THE ACTUAL FIELD INSTALLED EQUIVALENT
LENGTH OF THE CONCEALED VENT DUCT.
20. INSULATE EACH REFRIGERANT LINESET WITH 1-INCH FLEXIBLE, CLOSED CELL ELASTOMERIC INSULATION. PROVIDE ALUMINUM JACKETING FOR
EXPOSED PIPING. ALUMINUM JACKETING SHALL BE PAINT GRIPPING TYPE. PROVIDE EXTERIOR PIPING PORTS WITH LOCKING TYPE TAMPER
RESISTANT CAPS.
21. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT. COORDINATE LOCATION WITH ARCHITECTURAL
INTERIOR ELEVATIONS.
22. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. INSTALL CHROME PLATED ESCUTCHEONS FOR PIPING
PENETRATIONS OF WALLS, CEILINGS, AND FLOORS.
23. ALL PLUMBING VENTS AND BUILDING EXHAUST SHALL BE LOCATED A MINIMUM OF 10 FEET FROM MECHANICAL INTAKES AND THREE FEET FROM
OPERABLE OPENINGS, INCLUDING DOORS AND OPERABLE WINDOWS.
24. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES AROUND EQUIPMENT AT A MINIMUM. DO NOT ROUTE PIPING, DUCTWORK, CONTROL WIRE, ETC. THROUGH THE SERVICE CLEARANCE AREAS.
25. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH A FACTORY DISCONNECT SWITCH, STARTER, VFD, OR MOTOR RATED SWITCH AS
REQUIRED FOR CODE COMPLIANT OPERATION OF ALL MOTORIZED EQUIPMENT IN ACCORDANCE WITH CODE AND THE DESIGN INTENT ASSOCIATED
WITH THESE DRAWINGS. COORDINATE ALL DISCONNECTS AND STARTER REQUIREMENTS WITH THE PROJECT ELECTRICAL CONTRACTOR PRIOR TO
BID TO ENSURE A COORDINATED INSTALLATION.
26. CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH VIBRATION ISOLATION IN ACCORDANCE WITH THE 2015 ASHRAE HANDBOOK HVAC
APPLICATION CHAPTER 48 - NOISE AND VIBRATION CONTROL TABLE 47 AND CODES.
17. TEST AND BALANCE BY A THIRD PARTY SHALL BE REQUIRED FOR ALL SUPPLY, RETURN, OA, AND VENTILATION FOR THIS FACILITY.
27. WHERE REQUIRED FOR ACCESS TO EQUIPMENT AND ACCESSORIES ABOVE HARD CEILINGS OR IN WALLS, ACCESS PANELS SHALL BE PROVIDED BY
THIS CONTRACTOR. PANELS IN RATED ASSEMBLIES SHALL HAVE LISTED RATINGS EQUAL TO OR GREATER THAN THE ASSEMBLY IN WHICH THEY
ARE INSTALLED. REFER TO ARCHITECTURAL DRAWINGS FOR ACCESS PANEL SPECIFICATIONS.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
M0.1
LEGENDS AND GENERAL NOTES
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
06/29/2026
MECHANICAL SPECIFICATIONS
1. GENERAL
PROVIDE MATERIALS, EQUIPMENT, ACCESSORIES, INCIDENTALS, ARTICLES,
ITEMS, OPERATIONS, INCLUDING LABOR, NECESSARY FOR COMPLETION OF
WORK INDICATED AND/OR CALLED FOR ON THESE DRAWINGS. SUBMIT
SHOP DRAWINGS AND PRODUCT DATA ON ALL EQUIPMENT, PIPE,
DUCTWORK, AND INSULATION.
PROVIDE A COPY OF BOUND CLOSE-OUT DOCUMENTS TO THE ARCHITECT
FOR APPROVAL. PROVIDE TWO BOUND COPIES OF CLOSE OUT DOCUMENTS
TO THE OWNER'S REPRESENTATIVE AFTER APPROVAL. CLOSE OUT
DOCUMENTS SHALL INCLUDE COMPLETE I.O.M.'S FOR EACH PIECE OF
EQUIPMENT, A FULL-SIZE SET OF AS-BUILT PLANS AND FACTORY
AUTHORIZED SERVICE START-UP FORMS FOR EACH PIECE OF EQUIPMENT
INDICATING PROPER OPERATION ACROSS THE SEQUENCE.
2. REGULATORY REQUIREMENTS
ALL WORK SHALL BE PER FBC MECHANICAL, NEC, NFPA, UL, STATE, LOCAL
INSPECTORS AND OTHER APPLICABLE CODES.
3. COORDINATION
INSTALLATION OF ALL WORK SHALL BE COORDINATED WITH OTHER TRADES
AND WITH EXISTING CONDITIONS. CONTRACTOR SHALL VISIT THE SITE AND
VERIFY SIZES, CAPACITY, PERFORMANCE, AND LOCATION OF ALL EXISTING
WORK.
4. GUARANTEES
THE CONTRACTOR SHALL PROVIDE A ONE YEAR WRITTEN GUARANTEE FOR
ALL MATERIALS AND LABOR FROM THE DATE OF SUBSTANTIAL
COMPLETION. GUARANTEE SHALL COVER ALL LABOR AND MATERIALS TO
REPLACE DEFECTIVE MATERIALS AND TO ENSURE PROPER OPERATION OF
ALL SYSTEMS.
5. INSTALLATION
A. ALL EQUIPMENT AND MATERIAL SHALL BE INSTALLED PER THEIR
RESPECTIVE MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE
ADEQUATE CLEARANCE FOR ALL EQUIPMENT AND MATERIAL FOR
REGULAR MAINTENANCE, REMOVAL AND AIR FLOW. CONTRACTOR
SHALL PROVIDE CONTROLS, INCLUDING THERMOSTATS, CONTROL
POWER TRANSFORMERS, WIRING, PROGRAMMING, ETC., TO OPERATE
ALL EQUIPMENT UTILIZED FOR THIS PROJECT. ADJUST AIR HANDLING
UNITS, EXHAUST FANS, AND AIR DEVICES TO PROVIDE CFM'S AS SHOWN.
B. DUCTS SHALL BE SUPPORTED ON TRAPEZE WITH HANGER RODS.
6. DUCTWORK
A. GENERAL: EXCEPT FOR SYSTEMS SPECIFIED OTHERWISE, CONSTRUCT
DUCTS,CASINGS, AND ACCESSORIES OF GALVANIZED SHEET STEEL,
ASTM A653, G90 GALVANIZING. DUCT SHEET METAL THICKNESS SHALL BE
IN ACCORDANCE WITH THE SMACNA DUCT CONSTRUCTION MANUAL.
DUCT INSTALLATION METHODS, SUPPORTS AND OTHER PERTINENT
INSTALLATION CRITERIA SHALL BE AS INDICATED IN THE SMACNA DUCT
CONSTRUCTION STANDARDS AND SMACNA DUCT INSTALLATION
MANUALS.
B. JOINT SEALING: REFER TO SMACNA HVAC DUCT CONSTRUCTION
STANDARDS AND APPLICABLE MECHANICAL AND ENERGY CODES FOR
RECOMMENDED SEAL CLASS. SYSTEMS SHALL BE SEALED TO SEAL
CLASS A.
1. SEALANT: ELASTOMERIC COMPOUND, GUN OR BRUSH GRADE,
MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPED (DRY STATE)
COMPOUNDED SPECIFICALLY FOR SEALING DUCTWORK AS
RECOMMENDED BY THE MANUFACTURER.
2. GASKETS IN FLANGED JOINTS: SOFT NEOPRENE. APPROVED FACTORY
MADE JOINTS MAY BE USED.
C. DUCT MATERIALS:
1. SINGLE WALL GALVANIZED STEEL RECTANGULAR AND ROUND DUCTS:
ASTM A525 OR ASTM A527 GALVANIZED STEEL SHEET, LOCK-FORMING
QUALITY, HAVING ZINC COATING OF .90 OZ. PER SQ.FT. FOR EACH SIDE
IN CONFORMANCE WITH ASTM A90.
2. DOUBLE WALL GALVANIZED STEEL ROUND DUCTS: GALVANIZED STEEL
MEETING ASTM A653 STANDARDS WITH FINISH SELECTED BY
ARCHITECT, ONE INCH (1”) THICK FIBERGLASS INSULATION, SPIRAL
OUTER SHELL AND PERFORATED INNER LINER. A UL APPROVED MYLAR
FILM AND TAPED JOINTS SHALL SEPARATE THE INTERNAL FIBERGLASS
LINING AND AIRSTREAM. DUCT SYSTEMS SHALL BE FACTORY
PRE-FABRICATED. DUCTS SHALL HAVE SPIRAL LOCKSEAM
CONSTRUCTION. FITTINGS SHALL BE CONSTRUCTED OF A
PERFORATED SHEET METAL INTERNAL LINER, 1 INCH LAYER OF
FIBERGLASS INSULATION, MYLAR FILM AND AN OUTER GALVANIZED
PRESSURE SHELL WITH FINISH SELECTED BY ARCHITECT. STANDING
SEAM JOINTS SHALL BE USED WHEREVER POSSIBLE ON FITTINGS. ALL
STANDING SEAM JOINTS SHALL BE SEALED WITH A UL CLASSIFIED ZERO
FLAME SPREAD AND ZERO SMOKE DEVELOPED CEMENT SPECIALLY
FORMULATED FOR BONDING METAL-TO-METAL JOINTS. ALL WELDED
JOINTS SHALL BE COATED WITH A PROTECTIVE PAINT, INSIDE AND OUT,
TO PREVENT DAMAGE TO THE GALVANIZED SURFACE. ALL DOUBLE
WALL DUCT AND FITTINGS SHALL BE PROVIDED WITH BOTH AN INNER
LINER COUPLING AND AN OUTER PRESSURE SHELL COUPLING. OUTER
SHELL CONNECTIONS CAN BE BY SLIP JOINT (UP TO 24” DIAMETER) OR
BOLTED FLANGED JOINT WITH AIR SEAL GASKET.
SUBMIT DUCT FINISH TO ARCHITECT FOR APPROVAL.
D. FLEXIBLE FIBERGLASS DUCT: FLEXIBLE FIBERGLASS DUCT WITH A
MAXIMUM THERMAL CONDUCTIVITY OF 0.23 BTU/HR - DEGREES F -
SQ.FT. AT 75 DEGREES F MEAN TEMPERATURE WITH A MAXIMUM FLAME
SPREAD RATING OF 25 AND SMOKE DEVELOPED RATING OF 50.
FLEXIBLE FIBERGLASS DUCT SHALL BE OWENS-CORNING VALUFLEX OR
APPROVED EQUAL.
1. FLEXIBLE FIBERGLASS DUCT SHALL BE PROVIDED WITH SPIN-IN
BELLMOUTH FITTING, VOLUME DAMPER AND STAINLESS STEEL
CLAMP.
2. FLEXIBLE FIBERGLASS DUCT SIZE SHALL BE SAME AS AIR DEVICE
NECK SIZE UNLESS OTHERWISE NOTED.
3. FLEXIBLE FIBERGLASS DUCT LENGTH SHALL BE BETWEEN 6 AND 10
FEET.
4. FLEXIBLE DUCT SHALL BE USED FOR CONNECTION OF SUPPLY AIR
DEVICES ONLY. ALL EXHAUST AND RETURN DUCTWORK SHALL BE
RIGID DUCTWORK.
5. PROVIDE MANUAL VOLUME DAMPERS IN BRANCH DUCTS TO ALL AIR
DEVICES.
E. DUCT SCHEDULE (SEE SCHEDULE SHEET)
7. DUCT ACCESSORIES
A. VOLUME DAMPERS: SINGLE BLADE OR OPPOSED BLADE, MULTI-LOUVER
TYPE AS DETAILED IN SMACNA STANDARDS. ANY DAMPERS REQUIRED
TO HAVE A MOTORIZED DAMPER SHALL BE PROVIDED BY THE
MECHANICAL CONTRACTOR AS A COMPLETE SYSTEM INCLUDING THE
DAMPER, ACTUATOR AND LINKAGE ATTACHMENTS. ACTUATORS SHALL
BE AS PROVIDED BY BELIMO. IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO PROVIDE ALL DAMPERS AND ACTUATORS AS
REQUIRED AND THESE SYSTEMS SHALL BE COORDINATED WITH THE
CONTROLS CONTRACTOR AND ELECTRICAL CONTRACTOR
ACCORDINGLY FOR POWER OR CONTROL REQUIREMENTS.
8. DUCT INSULATION (CONCEALED LOCATIONS ONLY, SEE DOUBLE-WALL DUCT
SECTION FOR EXPOSED LOCATIONS)
A. INDOOR DUCTWORK: ASTM C553 (BLANKET, FLEXIBLE) TYPE I; 6.0
INSTALLED 'R' VALUE (MINIMUM) AT 75 DEGREES F, FOR USE FOR
SYSTEM TEMPERATURES BETWEEN 40 AND 250 DEGREES F . PROVIDE
FOIL SCRIM (FSK) FACING. SEAMS SEALED WITH PRESSURE SENSITIVE
TAPE AND MASTIC.
B. OUTDOOR DUCTWORK: RIGID GLASS FIBER BOARD; ANSI/ASTM C612;
COMMERCIAL GRADE; 8.0 INSTALLED 'R' VALUE (MINIMUM) AT 75
DEGREES F, FOIL SCRIM KRAFT FACING FOR AIR CONDITIONING DUCTS
(NOMINALLY 2" THICK) EXPOSED TO THE WEATHER. SEAMS SEALED
WITH PRESSURE SENSITIVE TAPE AND MASTIC. PROVIDE WITH
ALUMINUM WEATHER PROOF JACKETING AND ENSURE THAT TOPS OF
DUCTS ARE 'TENTED' TO PROHIBIT THE PONDING OF WATER. ALL
SEAMS IN INSULATION AND JACKET SHALL BE SEALED WATER TIGHT.
INSULATION SHALL BE EQUAL TO CERTAINTEED, CERTAPRO
COMMERCIAL BOARD WITH FSK FACING, TYPE CB 300 (3.0 LB/CU.FT.)
MINIMUM DENSITY.
9. AIR HANDLING UNITS
A. GENERAL: UNIT SHALL BE VERTICAL OR HORIZONTAL AIRFLOW (SEE
SCHEDULE). UNIT BE FACTORY RUN TESTED TO CHECK COOLING AND
HEATING OPERATION, FAN ROTATION, AND CONTROL. THE
HEATING/COOLING PERFORMANCE OF THE INDOOR UNIT AND OUTDOOR
UNIT SHALL BE CERTIFIED TO ANSI STANDARDS. SUBMIT AHRI
PERFORMANCE INFORMATION. WIRING INTERNAL TO THE UNIT SHALL BE
COLORED AND NUMBERED FOR IDENTIFICATION. UNITS SHALL BE UL
LISTED AND LABELED. PROVIDE WITH FACTORY MOUNTED CIRCUIT
BREAKER. ELECTRICAL CONTRACTOR TO PROVIDE UNIT DISCONNECT
SWITCH.
B. UNIT CASING: ALL COMPONENTS SHALL BE MOUNTED IN A HEAVY GAUGE,
GALVANIZED STEEL, INSULATED, AND GASKETED CABINET WITH
CORROSION RESISTANT SCREWS. ACCESS PANELS SHALL BE PROVIDED
FOR UNIT CONTROLS, COIL, FILTER, HEATER AND FAN. INDOOR AIR SECTION
COMPARTMENT SHALL BE COMPLETELY INSULATED WITH FIREPROOF,
PERMANENT, ODORLESS GLASS FIBER MATERIAL. KNOCKOUTS SHALL BE
PROVIDED FOR UTILITY AND CONTROL CONNECTIONS.
C. EVAPORATOR COIL: COIL SHALL BE INTERNALLY FINNED OR SMOOTH BORE
3/8" COPPER TUBES MECHANICALLY BONDED TO ALUMINUM FINS.
EVAPORATOR COIL LEAK AND PRESSURE TESTED TO 200 PSIG.
D. SUPPLY AIR FAN: DIRECT-DRIVE, FORWARD-CURVED, CENTRIFUGAL WHEEL.
MOTOR SHALL HAVE THERMAL OVERLOAD PROTECTION AND PERMANENTLY
LUBRICATED MOTOR BEARINGS. MOTOR/BLOWER ASSEMBLY ISOLATED
FROM UNIT WITH RUBBER MOUNTS.
E. ELECTRIC HEATER ELEMENTS SHALL BE CONSTRUCTED OF HEAVY-DUTY
NICKEL CHROMIUM ELEMENTS INTERNALLY DELTA CONNECTED FOR 240
VOLT, WYE CONNECTED FOR 480 VOLT. CAPACITY MODULATION SHALL BE
ACHIEVED THROUGH THE USE OF PULSE WIDTH MODULATION CONTROL.
EACH HEATER PACKAGE SHALL HAVE AUTOMATICALLY RESET HIGH LIMIT
CONTROL OPERATING THROUGH HEATING ELEMENT CONTACTORS. ALL
HEATERS SHALL BE INDIVIDUALLY FUSED FROM FACTORY AND SHALL MEET
ALL NEC AND LOCAL CODE REQUIREMENTS. POWER ASSEMBLIES SHALL
PROVIDE SINGLE-POINT CONNECTION. ELECTRIC HEAT MODULES SHALL BE
UL LISTED.
F. UNIT FILTER FRAME TO HOUSE A MINIMUM MERV 6 FILTER PER ASHRAE 62.2
REQUIREMENTS.
G. MODULATING ECONOMIZER (WHERE SPECIFIED ON SCHEDULE) :
ACCESSORY SHALL BE FIELD INSTALLED AND BE COMPOSED OF THE
FOLLOWING ITEMS: 0-100% FRESH AIR DAMPER, DAMPER DRIVE MOTOR,
FIXED DRY BULB ENTHALPY CONTROL, AND LOW VOLTAGE WIRING PLUG
FOR ELECTRICAL CONNECTIONS. DIFFERENTIAL ENTHALPY CONTROL IS
REQUIRED. ECONOMIZER OPERATIONS SHALL BE CONTROLLED BY THE
PRESET POSITION OF THE ENTHALPY CONTROL. A BAROMETRIC RELIEF
DAMPER SHALL BE STANDARD WITH THE ECONOMIZER AND PROVIDE A
PRESSURE OPERATED DAMPER THAT SHALL BE GRAVITY CLOSING AND
PROHIBIT ENTRANCE OF OUTSIDE AIR ON EQUIPMENT “OFF” CYCLE.
H. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ALL
APPLICABLE CODES AND STANDARDS AS REQUIRED AT THE PROJECT
LOCATION.
I. MANUFACTURER SHALL FURNISH A FACTORY-TRAINED SERVICE ENGINEER
WITHOUT ADDITIONAL CHARGE TO PREPARE THE MACHINE FOR
OPERATION, START THE UNIT AND CERTIFY INITIAL FIELD STARTUP. THE
MANUFACTURER SHALL PROVIDE A WRITTEN CERTIFICATION TO THE
ARCHITECT/ENGINEER THAT THE UNIT HAS BEEN PREPARED AND IS READY
FOR OPERATION.
J. INSTALL UNIT WITH PROGRAMMABLE 7-DAY THERMOSTAT CAPABLE OF
AUTOMATIC HEAT / COOL CHANGEOVER, ADJUSTABLE DEAD-BAND,
ADAPTIVE HEAT RECOVERY, INSULATED MOUNTING BASE, 24V POWER WITH
BATTERY BACKUP TO PRESERVE PROGRAM. MOUNT THERMOSTAT LEVEL
AND PER THE ARCHITECT'S INTERIOR FINISH ELEVATIONS.
10. HEAT PUMP AND CONDENSING UNITS
A. GENERAL: INDOOR AND OUTDOOR UNIT BE FACTORY RUN TESTED TO
CHECK COOLING AND HEATING OPERATION, FAN ROTATION, AND CONTROL.
UNITS SHALL BE DESIGNED TO OPERATE AT REFRIGERANT SYSTEM AT
AMBIENT TEMPERATURES BETWEEN 55°F AND 115°F AS MANUFACTURED.
THE HEATING/COOLING PERFORMANCE SHALL BE CERTIFIED TO ANSI
STANDARDS.
B. UNIT CASING: ALL COMPONENTS SHALL BE MOUNTED IN A HEAVY GAUGE,
GALVANIZED STEEL, INSULATED, AND GASKETED CABINET WITH A WEATHER
RESISTANT FINISH AND CORROSION RESISTANT SCREWS. ACCESS PANELS
SHALL BE PROVIDED FOR UNIT CONTROLS, COIL AND FAN (S).
C. COMPRESSOR: THE COMPRESSOR SHALL BE HERMETICALLY SEALED, HIGH
EFFICIENCY. PROVIDE INTERNAL OVERCURRENT AND OVER TEMPERATURE
PROTECTION AND INTERNAL PRESSURE RELIEF.
D. REFRIGERATION SYSTEM: SYSTEM SHALL UTILIZE R-401A. SERVICE
PRESSURE TAP PORTS, THERMAL EXPANSION VALVE AND A REFRIGERANT
LINE FILTER DRYER SHALL BE PROVIDED. PROVIDE TAMPER RESISTANT
LOCKING PORT CAPS. EACH REFRIGERANT CIRCUIT SHALL HAVE THERMAL
EXPANSION VALVE, SERVICE PRESSURE PORTS AND REFRIGERANT LINE
FILTER DRYERS FACTORY-INSTALLED AS STANDARD. PROVIDE WITH
FACTORY MOUNTED CIRCUIT BREAKER. ELECTRICAL CONTRACTOR TO
PROVIDE UNIT DISCONNECT SWITCH. PROVIDE ALL MANUFACTURER'S
RECOMMENDED COMPONENTS FOR EXTENDED LINE LENGTH AND LIFT
APPLICATIONS.
E. CONDENSER COIL: COIL SHALL BE CONTINUOUSLY WRAPPED, CORROSION
RESISTANT ALL ALUMINUM WITH MINIMUM BRAZED JOINTS. 3/8 INCH O.D.
SEAMLESS ALUMINUM TUBING GLUED TO A CONTINUOUS ALUMINUM FIN.
COIL TO BE LAB TESTED TO WITHSTAND 2,000 POUNDS OF PRESSURE PER
SQUARE INCH. CONDENSER COIL SHALL BE LEAK AND PRESSURE TESTED
TO 450 PSIG.
F. CONDENSER FAN: DIRECT-DRIVE, DRAW THRU PROPELLER TYPE.
WEATHER-PROOFED PERMANENT SPLIT CAPACITOR FAN MOTOR SHALL
HAVE BUILT-IN THERMAL OVERLOAD AND PERMANENTLY LUBRICATED
MOTOR BEARINGS.
G. ROOF CURB: REFER TO STRUCTURAL ENGINEER'S DETAIL FOR EQUIPMENT
CURB. COORDINATE AND VERIFY THAT ROOF IS READY TO RECEIVE WORK.
H. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ALL
APPLICABLE CODES AND STANDARDS AS REQUIRED AT THE PROJECT
LOCATION.
I. MANUFACTURER SHALL FURNISH A FACTORY-TRAINED SERVICE ENGINEER
WITHOUT ADDITIONAL CHARGE TO PREPARE THE MACHINE FOR
OPERATION, START THE UNIT AND CERTIFY INITIAL FIELD STARTUP. THE
MANUFACTURER SHALL PROVIDE A WRITTEN CERTIFICATION TO THE
ARCHITECT/ENGINEER THAT THE UNIT HAS BEEN PREPARED AND IS READY
FOR OPERATION.
11. AIR DEVICES
FURNISH AS SCHEDULED OR OBTAIN PRIOR APPROVAL TO SUBMIT AN
ALTERNATE MANUFACTURER / MODEL.
DEVICE SHALL BE OF ALUMINUM CONSTRUCTION, WITH BAKED WHITE
ENAMEL FINISH UNLESS OTHERWISE STATED. FURNISH DEVICE WITH
ACCESSORIES SCHEDULED, INCLUDING PLASTER TRIM RING FOR HARD
CEILING INSTALLATION, UL-LISTED FIRE RADIATION DAMPER FOR RATED
PARTITION INSTALLATIONS. OPPOSED-BLADE OR BUTTERFLY (ROUND ONLY)
DAMPERS MAY BE INSTALLED ONLY WHEN BRANCH TAKE-OFF VOLUME
DAMPERS CANNOT BE INSTALLED AND ONLY WITH PRIOR APPROVAL BY THE
ENGINEER. INSTALL INSULATION ON BACK PANELS FOR ALL CEILING
SUPPLY GRILLES. PLENUMS SHALL BE CONSTRUCTED TO SMACNA
STANDARDS FOR DUCT RIGIDITY AND SEAL, LINED WITH 1" CERTAINTEED
TOUGHGUARD LINER BOARD INSTALLED PER MANUFACTURES DIRECTIONS
AND FINISHED BLACK.
12. REFRIGERANT PIPING
A. LINE TEST PRESSURE FOR REFRIGERANT R-32:
SUCTION LINES FOR AIR-CONDITIONING APPLICATIONS: 450 PSIG
SUCTION LINES FOR HEAT-PUMP APPLICATIONS: 600 PSIG
HOT-GAS AND LIQUID LINES: 600 PSIG
B. REFRIGERANT PIPING INDICATED ON DRAWINGS IS SCHEMATIC ONLY.
SIZE PIPING AND DESIGN ACTUAL PIPING LAYOUT, INCLUDING OIL TRAPS,
DOUBLE RISERS, SPECIALTIES, AND PIPE AND TUBE SIZES TO
ACCOMMODATE, AS A MINIMUM, EQUIPMENT PROVIDED, ELEVATION
DIFFERENCE BETWEEN COMPRESSOR AND EVAPORATOR, AND LENGTH OF
PIPING TO ENSURE PROPER OPERATION AND COMPLIANCE WITH
WARRANTIES OF CONNECTED EQUIPMENT.
C. SUBMIT WELDING CERTIFICATES, PIPING, VALVES, HANGERS AND
INSULATION FOR APPROVAL.
D. PIPING TO BE COPPER TUBE: ASTM B 280, TYPE ACR, WITH
WROUGHT-COPPER FITTINGS PER ASME B16.22. BRAZING FILLER METALS:
AWS A5.8. INSULATE WITH 1-INCH ELASTOMERIC. PROVIDE ALUMINUM
JACKETING FOR PIPING EXPOSED TO WEATHER.
E. SLOPE REFRIGERANT PIPING AS FOLLOWS:
1.1 INSTALL HORIZONTAL HOT-GAS DISCHARGE PIPING WITH A UNIFORM
SLOPE DOWNWARD AWAY FROM COMPRESSOR.
1.2 INSTALL HORIZONTAL SUCTION LINES WITH A UNIFORM SLOPE
DOWNWARD TO COMPRESSOR.
1.3 INSTALL TRAPS AND DOUBLE RISERS TO ENTRAIN OIL IN VERTICAL
RUNS. LIQUID LINES MAY BE INSTALLED LEVEL.
1.4 WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS
AND SIGHT GLASSES; ALSO REMOVE VALVE STEMS, SEATS, AND PACKING,
AND ACCESSIBLE INTERNAL PARTS OF REFRIGERANT SPECIALTIES. DO NOT
APPLY HEAT NEAR EXPANSION-VALVE BULB.
F. HANGERS TO BE MALLEABLE IRON CARBON STEEL, ADJUSTABLE SWIVEL,
SPLIT RING. PROVIDE TRAPEZE HANGERS (STEEL CHANNEL WITH WELDED
SPACERS) FOR MULTIPLE PIPE SUPPORT. PROVIDE SADDLE TO PROTECT
INSULATION. PROVIDE STEEL RISER CLAMP FOR VERTICAL SUPPORT.
SUPPORT VERTICALLY AT EVERY FLOOR.
G. PROVIDE TAMPER RESISTANT, LOCKING-TYPE, ACCESS PORT CAPS ON
ALL PIPING PORTS LOCATED OUTSIDE.
13. TEST AND BALANCE
TEST AND BALANCE CONTRACTOR SHALL BE CERTIFIED BY AABC OR NEBB.
SUBMIT TAB QUALIFICATIONS AND SAMPLE REPORT FORMS FOR APPROVAL
BY THE ENGINEER. SUBMIT TAB REPORT TO ENGINEER FOR REVIEW. UPON
REQUEST, TAB CONTRACTOR SHALL DEMONSTRATE ON-SITE
CONFIRMATION OF THE TAB REPORT MEASUREMENTS WITNESSED BY THE
ENGINEER. DISCREPANCIES WILL REQUIRE ADDITIONAL TAB SAMPLING AND
RE-BALANCE OF THE SYSTEMS.
ADJUST ALL SYSTEM COMPONENTS, EQUIPMENT, FLOW DEVICES AND
SENSORS PER "AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE,
V 2002".
PROVIDE BELT AND SHEAVE CHANGES AS REQUIRED FOR BALANCING OF
ALL FANS INDICATED ON THESE DRAWINGS. BELT AND SHEAVE CHANGES
SHALL BE PROVIDED AT THE CONTRACTOR'S EXPENSE.
FLOW TOLERANCES:
AIR HANDLING UNITS, (CUBIC FEET PER MINUTE): MINUS 0 PERCENT TO
PLUS 10 PERCENT.
EXHAUST FANS: 0 PERCENT TO PLUS 10 PERCENT.
MINIMUM OUTSIDE AIR: 0 PERCENT TO PLUS 10 PERCENT.
INDIVIDUAL ROOM AIR OUTLETS AND INLETS, AND AIR FLOW RATES NOT
MENTIONED ABOVE: MINUS 5 PERCENT TO PLUS 10 PERCENT EXCEPT IF
THE AIR TO A SPACE IS 100 CFM OR LESS THE TOLERANCE WOULD BE
MINUS 5 TO PLUS 5 PERCENT.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
M0.2
SPECIFICATIONS
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
M2.0
M3.1
M2.1
M3.0
M4.0
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
M1.0
OVERALL FLOOR PLAN - PHASE
SCOPE
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
1/4" = 1'-0"M1.0
1 OVERALL FLOOR PLAN
N
AHU-EX-1
AHU-EX-2
T
T
7 7 7
CU-EX-1 CU-EX-2
8 8
GENERAL NOTES
A. COORDINATE HVAC DEMOLITION WITH OTHER TRADES AND GENERAL CONTRACTOR.
DO NOT DEMOLISH EQUIPMENT OR COMPONENTS WITHOUT APPROVAL.
B. �PRIOR TO START OF ANY DEMOLITION WORK, CONTRACTOR SHALL PRE TEST ALL AIR
DEVICES SCHEDULED TO BE REUSED, EXHAUST FANS, AND AIR HANDLING UNITS
WITHIN THE PROJECT LIMITS. PROVIDE A REPORT SHOWING AIR FLOWS OF EACH
DEVICE TO ARCHITECT AND ENGINEER.
C. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE DAMAGE OR REMOVAL IN
WHOLE OR IN PART OF ANY STRUCTURAL MEMBER WITHOUT EXPRESS APPROVAL OF
THE GENERAL CONTRACTOR.
D. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT, PIPE, OR ELECTRICAL CABLE /
CONDUIT THAT RESULTS FROM DEMOLITION. UNDER NO CIRCUMSTANCE WILL
DEMOLITION RESULT IN THE PERMANENT EXPOSURE OF ANY CHARGED OR LIVE
COMPONENT OF ANY EQUIPMENT TO BE RE-USED.
E. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT THEREOF THAT SHALL BE RE-
USED.
F. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH THE GENERAL CONTRACTOR.
TURN OVER ANY COMPONENTS TO THE OWNER AS DESIGNATED IN CLEAN CONDITION,
WITHOUT DAMAGE, AND WITH OPENING SEALED. FURNISH RECEIPTS OF PROPER
DISPOSAL OF ALL ITEMS REMOVED TO THE GENERAL CONTRACTOR UPON REQUEST.
RECEIPTS SHALL INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL, STATE, AND
FEDERAL REGULATIONS.
G. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL PERFORM MAINTENANCE
SERVICE TO EXISTING EQUIPMENT TO BE REUSED IN THE NEW LAYOUT (TO REMAIN OR
TO BE RELOCATED). NOTIFY ARCHITECT, OWNER, AND ENGINEER OF ANY DEFICIENCY
FOUND DURING PRE-CONSTRUCTION MAINTENANCE SERVICE.
KEYNOTES
1. EXISTING AIR HANDLING UNIT AND ASSOCIATED DUCTWORK MAINS EXISTING TO
REMAIN UP TO POINT INDICATED ON PLAN.. CONTRACTOR SHALL CLEAN, TEST, AND
INSPECT UNIT AND ASSOCIATED MECHANICAL EQUIPMENT FOR PROPER OPERATION.
REPLACE UNIT IN KIND IF FOUND TO BE DEFECTIVE. REPLACE DUCTWORK,
INSULATION, ETC. IN KIND IF FOUND TO BE DEFECTIVE.
2. CONTRACTOR SHALL REMOVE EXISTING SUPPLY DIFFUSER AND ALL ASSOCIATED
DUCTWORK, FITTINGS, AND ACCESSORIES.
3. CONTRACTOR SHALL REMOVE EXISTING RETURN GRILLE AND ALL ASSOCIATED
DUCTWORK, FITTINGS, AND ACCESSORIES.
4. EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL COORDINATE THE REMOVAL
AND RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR.
CONTRACTOR SHALL CLEAN, INSPECT, AND TEST THERMOSTAT FOR PROPER
OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.
5. EXISTING OUTSIDE AIR INTAKE GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN,
INSPECT, AND TEST EQUIPMENT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND
TO BE DEFECTIVE. ASSUMED 8" CLEAR INSIDE DIAMETER. CONTRACTOR SHALL NOTIFY
ARCHITECT AND ENGINEER IF EXISTING DUCT DOES NOT MAINTAIN REQUIRED FREE
AREA.
6. CONTRACTOR SHALL PERFORM A PRE-TEST OF SUPPLY, RETURN, AND OUTSIDE AIR
CAPABILITIES OF EXISTING AHU-EX-1 AND AHU-EX-2 PRIOR TO START OF ANY
DEMOLITION WORK. PRE-TEST SHALL AT A MINIMUM INCLUDE AIRFLOW VALUES,
ENTERING AIR TEMPS, AND LEAVING AIR TEMPS. PROVIDE REPORT TO ARCHITECT
AND ENGINEER.
7. CONTRACTOR SHALL REMOVE EXISTING EXHAUST FAN, AND ALL ASSOCIATED
DUCTWORK, MOUNTING EQUIPMENT, CONTROLLERS, ETC. COORDINATE THE
REMOVAL OF EXTERIOR WALL CAP TERMINATIONS. CONTRACTOR SHALL PATCH AND
SEAL BUILDING EXTERIOR TO MATCH WHERE EXISTING PENETRATIONS ARE NOT
REUSED.
8. EXISTING CONDENSING UNIT TO REMAIN. CONTRACTOR SHALL TEST AND INSPECT
UNIT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.
CONTRACTOR SHALL INSPECT UNIT MOUNTING EQUIPMENT FOR PROPER OPERATION.
REPLACE HURRICANE CLIPS, MOUNTING PADS, ETC. AS REQUIRED.
NOT ALL KEYNOTES NECESSARILY APPLY
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
M2.0
FIRST FLOOR DEMOLITION PLAN
- OFFICE
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
1/4" = 1'-0"M2.0
1 DEMOLITION FLOOR PLAN - WEST
GUH-EX-2
GUH-EX-1
GEF-EX-1
GENERAL NOTES
A. COORDINATE HVAC DEMOLITION WITH OTHER TRADES
AND GENERAL CONTRACTOR. DO NOT DEMOLISH
EQUIPMENT OR COMPONENTS WITHOUT APPROVAL.
B. PRIOR TO START OF ANY DEMOLITION WORK,
�CONTRACTOR SHALL PRE TEST ALL AIR DEVICES
SCHEDULED TO BE REUSED, EXHAUST FANS, AND AIR
HANDLING UNITS WITHIN THE PROJECT LIMITS. PROVIDE
A REPORT SHOWING AIR FLOWS OF EACH DEVICE TO
ARCHITECT AND ENGINEER.
C. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE
DAMAGE OR REMOVAL IN WHOLE OR IN PART OF ANY
STRUCTURAL MEMBER WITHOUT EXPRESS APPROVAL
OF THE GENERAL CONTRACTOR.
D. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT,
PIPE, OR ELECTRICAL CABLE / CONDUIT THAT RESULTS
FROM DEMOLITION. UNDER NO CIRCUMSTANCE WILL
DEMOLITION RESULT IN THE PERMANENT EXPOSURE OF
ANY CHARGED OR LIVE COMPONENT OF ANY
EQUIPMENT TO BE RE-USED.
E. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT
THEREOF THAT SHALL BE RE-USED.
F. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH
THE GENERAL CONTRACTOR. TURN OVER ANY
COMPONENTS TO THE OWNER AS DESIGNATED IN
CLEAN CONDITION, WITHOUT DAMAGE, AND WITH
OPENING SEALED. FURNISH RECEIPTS OF PROPER
DISPOSAL OF ALL ITEMS REMOVED TO THE GENERAL
CONTRACTOR UPON REQUEST. RECEIPTS SHALL
INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL,
STATE, AND FEDERAL REGULATIONS.
G. PRIOR TO START OF CONSTRUCTION, CONTRACTOR
SHALL PERFORM MAINTENANCE SERVICE TO EXISTING
EQUIPMENT TO BE REUSED IN THE NEW LAYOUT (TO
REMAIN OR TO BE RELOCATED). NOTIFY ARCHITECT,
OWNER, AND ENGINEER OF ANY DEFICIENCY FOUND
DURING PRE CONSTRUCTION MAINTENANCE SERVICE.
KEYNOTES
1. EXISTING GARAGE UNIT HEATER TO REMAIN.
CONTRACTOR SHALL CLEAN, INSPECT, AND TEST UNIT
HEATER FOR PROPER OPERATION. REPAIR OR REPLACE
IN KIND IF FOUND TO BE DEFECTIVE. CONTRACTOR
SHALL CLEAN, INSPECT, AND TEST UNIT HEATER VENT
PIPING FOR DEFECTS, LEAKS, ROOF PENETRATIONS,
ROOF CAPS, ETC. FOR PROPER OPERATION. REPAIR OR
REPLACE VENT PIPING IF FOUND TO BE DEFECTIVE.
2. CONTRACTOR SHALL REMOVE EXISTING LOUVER.
PATCH AND SEAL BUILDING PENETRATIONS AS
REQUIRED FOR NEW WALL MOUNTED EXHAUST FAN
SLEEVE. COORDINATE FINAL CONSTRUCTION AND
FINISH WITH ARCHITECT AND GENERAL CONTRACTOR.
3. CONTRACTOR SHALL REMOVE EXISTING GARAGE
EXHAUST FAN. REMOVE ALL ASSOCIATED MECHANICAL
EQUIPMENT, SUPPORTS, CONTROLS, ETC. COORDINATE
THE REMOVAL OF ELECTRICAL DISCONNECTS, AND ANY
ADDITIONAL ELECTRICAL EQUIPMENT WITH ELECTRICAL
CONTRACTOR.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
M2.1
FIRST FLOOR DEMOLITION PLAN
- APPARATUS BAY
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
1/4" = 1'-0"M2.1
1 DEMOLITION FLOOR PLAN - EAST
NAPA ROOM
OPEN OFFICE
OFFICE
BREAK ROOM
LOCKER ROOM
RESTROOM
RESTROOM
A
A
A
A
A
A
A 150A
EF-2
EF-1
B
B
A
AHU-EX-1
AHU-EX-2
T
T
A
A
A
B
B
B
16"x12" SA
20"x12" RA
20"x12" SA
20"x12" RA
"x
S A
"x
R
A
"x
S A
"x
S A
"x
R
A
10"ø OA
"ø
O A
20"x12" SA 12"x12" SA
M
M
M 400M
EF-3
X
M
CU-EX-1 CU-EX-2 CU-C1
9 9 8
T
T
6"ø EA
T
U
U
"x
6"ø
EF-6
"ø
E A
U
6"ø EA
JAN.
GENERAL NOTES
A. REFER TO M0.1 GENERAL NOTES AND M0.2 PROJECT SPECIFICATIONS FOR ALL REQUIREMENTS.
B. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS
OTHERWISE NOTED. SEE M0.1 GENERAL NOTES.
C. MECHANICAL DRAWINGS ARE DIAGRAMMATIC. SEE M0.1 GENERAL NOTES.
D. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF INSTALLATION WORK WITH OTHER TRADES TO AVOID CONFLICTS. SEE M0.1 GENERAL NOTES FOR COORDINATION DRAWING REQUIREMENTS.
E. MAINTAIN A 10 FOOT MINIMUM SEPARATION BETWEEN MECHANICAL INTAKE AND BUILDING
EXHAUST AND PLUMBING VENTS.
F. MAINTAIN A 3 FOOT MINIMUM SEPARATION BETWEEN BUILDING EXHAUST AND ANY BUILDING
OPENINGS.
G. ALL EXHAUST WALL CAPS TO BE PROVIDED WITH A FLAPPER-TYPE BACKDRAFT DAMPER AND INLET
SCREEN. REMOVE INLET SCREEN ON DRYER VENT WALL CAPS.
H. ALL DUCT PENETRATIONS THROUGH A ONE-HOUR FIRE-RATED PARTITION SHALL BE PROVIDED
WITH A FIRE DAMPER.
I. ANY DUCTS (EXCEPT DRYER AND RANGE HOOD DUCTS) THAT PENETRATE THE MEMBRANE OF THE RATED FLOOR/CEILING ASSEMBLY SHALL BE PROTECTED WITH A UL LISTED, DYNAMICALLY RATED
CEILING RADIATION DAMPER LISTED FOR THIS SPECIFIC APPLICATION AND INSTALLED IN
ACCORDANCE WITH ITS UL DETAIL.
J. PROVIDE CONDENSATE DRAIN PIPING FROM EACH COIL CONNECTION TO A PLUMBING RECEPTACLE.
CONDENSATE SHALL BE PIPED FULL SIZE AND CONNECTED VIA AN INDIRECT CONNECTION.
CONDENSATE PIPING SHALL BE BY THE MECHANICAL CONTRACTOR.
K. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT.
COORDINATE LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS AND LIGHTING CONTROL
LOCATIONS.
KEYNOTES
1. EXISTING THERMOSTAT TO BE RELOCATED. CONTRACTOR SHALL COORDINATE THE REMOVAL AND
RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR. CONTRACTOR SHALL
CLEAN, INSPECT, AND TEST THERMOSTAT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND
TO BE DEFECTIVE.
2. EXISTING OUTSIDE AIR INTAKE GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN, INSPECT, AND
TEST EQUIPMENT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.
ASSUMED 8" CLEAR INSIDE DIAMETER. CONTRACTOR SHALL NOTIFY ARCHITECT AND ENGINEER IF
EXISTING DUCT DOES NOT PROVIDE REQUIRED FREE AREA.
3. CONTRACTOR SHALL PERFORM A PRE-TEST OF SUPPLY, RETURN, AND OUTSIDE AIR CAPABILITIES OF EXISTING AHU-EX-1 AND AHU-EX-2 PRIOR TO START OF ANY DEMOLITION WORK. PRE-TEST SHALL AT A MINIMUM INCLUDE AIRFLOW VALUES, ENTERING AIR TEMPS, AND LEAVING AIR TEMPS.
PROVIDE REPORT TO ARCHITECT AND ENGINEER.
4. PROVIDE MOTORIZED DAMPER WITHIN OUTSIDE AIR DUCT. DAMPER SHALL BE FULLY OPEN
WHENEVER COMPRESSOR IS OPERATING IN OCCUPIED MODE. PROVIDE MANUAL DAMPER FOR
BALANCING PURPOSES. PROVIDE ACCESS PANEL FOR DAMPER SERVICE. COORDINATE FINAL
LOCATION OF ACCESS PANEL WITH ARCHITECTS AND GENERAL CONTRACTOR. ALL OUTSIDE AIR
DUCT ROUTED WITHIN THE BUILDING SHALL BE EXTERNALLY INSULATED.
5. PROVIDE WALL LOUVER TERMINATION FOR EXHAUST DUCT, X-VENT-BOX,
SERIES S (OR EQUAL COMPATIBLE WITH EXTERIOR BUILDING CONSTRUCTION)
FOR SINGLE 6" DIAMETER EXHAUST DUCT TERMINATION. COORDINATE FINAL
TERMINATION LOCATION AND BUILDING EXTERIOR CONSTRUCTION WITH
ARCHITECT AND GENERAL CONTRACTOR. FINAL COLOR/FINISH SHALL BE AS SELECTED BY
ARCHITECT. EXHAUST TERMINATION MUST MAINTAIN A MINIMUM DISTANCE OF 10'-0" FROM ALL OA
INTAKES AND 3'-0" FROM ALL BUILDING OPENINGS.
6. PROVIDE WALL LOUVER TERMINATION FOR EXHAUST DUCT, X-VENT-BOX, SERIES S (OR EQUAL
COMPATIBLE WITH EXTERIOR BUILDING CONSTRUCTION) FOR DOUBLE DUCT TERMINATION,
CONSISTING OF (1) 6" DIA EXHAUST DUCT AND (1) 8" DIA EXHAUST DUCT. COORDINATE FINAL
TERMINATION LOCATION, HORIZONTAL/VERTICAL CONFIGURATION, AND BUILDING EXTERIOR
CONSTRUCTION WITH ARCHITECT AND GENERAL CONTRACTOR. FINAL COLOR/FINISH SHALL BE AS SELECTED BY ARCHITECT. EXHAUST TERMINATION MUST MAINTAIN A MINIMUM DISTANCE OF 10'-0"
FROM ALL OA INTAKES AND 3'-0" FROM ALL BUILDING OPENINGS.
7. CONTRACTOR SHALL PROVIDE AHU WITH AIR-PLUS BIPOLAR IONIZATION UNIT MODEL FM-6000 (OR
EQUAL). INSTALL UNIT PER MANUFACTURER INSTALLATION GUIDELINES.
8. CONTRACTOR SHALL MOUNT CONDENSING UNIT ON PREFABRICATED 4" THICK CONCRETE
HOUSEKEEPING PAD. INSTALL UNIT PER 2023 FBC-M WIND LOAD REQUIREMENTS. COORDINATE
FINAL LOCATION WITH ARCHITECT AND GENERAL CONTRACTOR.
9. EXISTING CONDENSING UNIT TO REMAIN. CONTRACTOR SHALL TEST AND INSPECT UNIT FOR
PROPER OPERATION. REPAIR OR REPLACE IN KIND IF FOUND TO BE DEFECTIVE. CONTRACTOR
SHALL INSPECT UNIT MOUNTING EQUIPMENT FOR PROPER OPERATION. REPLACE HURRICANE
CLIPS, MOUNTING PADS, ETC. AS REQUIRED.
10. EXISTING THERMOSTAT TO BE RELOCATED. CONTRACTOR SHALL COORDINATE THE REMOVAL AND
RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR. CONTRACTOR SHALL
PROVIDE ADDITIONAL ACCESSORIES REQUIRED FOR AVERAGING STAT CAPABILITIES.
CONTRACTOR SHALL REPLACE THERMOSTAT IF NOT COMPATIBLE WITH AVERAGING SENSOR
COMPONENTS WITH 7-DAY PROGRAMMABLE THERMOSTAT WITH WIFI COMMUNICATION,
INTERFACE FOR REMOTE CONNECTION, AND ADMINISTRATION VIA WEB OR PHONE APP, AND THE
ABILITY TO COMMUNICATE WITH AVERAGING SENSORS.
11. APPROXIMATE LOCATION OF REMOTE AVERAGING TEMPERATURE SENSOR. COORDINATE FINAL
LOCATION WITH ARCHITECT AND GENERAL CONTRACTOR.
12. ROUTE 6" ROUND EXHAUST DUCT UP THROUGH ROOF. SEAL ROOF PENETRATION WEATHER-
TIGHT. TERMINATE MINIMUM 12" ABOVE ROOF WITH RAINCAP PER 2023 FBC-M WIND LOAD
REQUIREMENTS. FINAL DISCHARGE LOCATION SHALL BE MINIMUM 10'-0" FROM ALL OA INTAKES.
NOT ALL KEYNOTES NECESSARILY APPLY
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING…