Genesis Engineering Design Plans

This document comprises engineering design plans prepared for Sarasota County, Florida in connection with the South County Fleet Renovation project, a construction initiative focused on renovating and improving the existing South County Fleet maintenance and support facilities. The design plans establish the technical specifications, site layout, and construction requirements that guide the renovation scope. The plans appear to serve as the foundational engineering documentation that bidders will reference when preparing their construction proposals and cost estimates for the fleet facility improvement project. The documents establish the baseline conditions of the existing facilities and delineate the proposed improvements, configurations, and infrastructure modifications necessary to modernize the maintenance and support operations at the South County Fleet location.

The engineering design plans provide the technical framework upon which construction contractors will base their bids for the renovation contract. These plans function as critical reference materials for all prospective bidders and establish the design standards, material specifications, and construction methodologies that the awarded contractor must follow during project execution. The plans ensure consistency between the County's vision for the facility improvements and the actual construction work performed, serving as the contractual and operational baseline for project delivery and quality assurance throughout the renovation period.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FSD

RD

2023 FBC-EC COMPLIANCE NOTES

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFR ABOVE FINISHED ROOF

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AO ANALOG OUTPUT

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BHP BRAKE HORSE POWER

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C COMMON

CD CONDENSATE

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN

CO2 CARBON DIOXIDE

COP COEFFICIENT OF PERFORMANCE

CU CONDENSING UNIT

DAC DEHUMIDIFICATION AHU

DB DRY BULB

DCU DEHUMIDIFICATION CU

DDC DIRECT DIGITAL CONTROL

DEGF DEGREE FAHRENHEIT

DI DIGITAL INPUT

DN DOWN

DO DIGITAL OUTPUT

DWG DRAWING

DP DIFFERENTIAL PRESSURE

EA EXHAUST AIR

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EAT ENTERING AIR TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

ERV ENERGY RECOVERY VENTILATOR

FC FAIL CLOSED

FC FAN COIL (EXISTING)

FCU FAN COIL UNIT

FD FIRE DAMPER

FF FLOW FEEDBACK/STATUS SIGNAL

FLA FULL LOAD AMPS

FO FAIL OPEN

FPM FEET PER MINUTE

FT FEET

GPM GALLONS PER MINUTE

H HUMIDITY

HS HUMIDISTAT

HP HEAT PUMP

HP HORSEPOWER

HWS HOT WATER SUPPLY

HPS HIGH PRESSURE STEAM

HWR HOT WATER RETURN

IAQ INDOOR AIR QUALITY

IN INCH

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LPS LOW PRESSURE STEAM

LPR LOW PRESSURE RETURN

LWT LEAVING WATER TEMPERATURE

M MOTORIZED

MBH THOUSAND BTUH

MCA MINIMUM CIRCUIT AMPACITY

MOCP MAXIMUM OVER CURRENT PROTECTION

NC NORMALLY CLOSED

NO NORMALLY OPEN

NTS NOT TO SCALE

OBD OPPOSED BLADE DAMPER

OA OUTDOOR AIR

P PRESSURE

PF PROPORTIONAL, LINEARIZE FEEDBACK, 4-20mA

SIGNAL

PRV PRESSURE REDUCING VALVE

PRS PRESSURE REDUCING STATION

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

RA RETURN AIR

RH RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

RS/L REFRIGERANT SUCTION/LIQUID

RTU ROOFTOP PACKAGED UNIT

SA SUPPLY AIR

SF SQUARE FEET

SS START/STOP SIGNAL

S.S. STAINLESS STEEL

SP STATIC PRESSURE

T TEMPERATURE

V-PH VOLTAGE-PHASE

TD TIME DELAY

TS TEMPERATURE SENSOR

TSP TOTAL STATIC PRESSURE

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

V/PH VOLTS/PHASE

WB WET BULB

WG WATER GAUGE

WR CHILLED WATER RESET 4-20 mA SIGNAL

W/ WITH

W/O WITHOUT

MECHANICAL ABBREVIATIONS LEGEND

RETURN AIR

SMOKE DETECTOR

SQUARE FEET)

REQUIRED INDICATED IN

DOOR LOUVER (FREE AREA

UNDERCUT DOOR

L

U

S

SINGLE LINE

SUPPLY AIR

RADIUS ELBOW (R=1.5)

CONTROL DAMPER-

AIR REGISTER (R)

SUPPLY AIR GRILLE (G) OR SUPPLY

FLEXIBLE CONNECTION (FXC)

AIR FLOW

RISE OR DROP DIRECTION OF

REC. BRANCH DUCT TAKE-OFF W/ VD

ELBOW W/ TURNING VANES

DIFFUSER

RD

TO BE REMOVED.

EXISTING EQUIPMENT OR DUCTWORK

ACCESS DOOR

MOTOR OPERATED DAMPER (MOD)

MANUAL VOLUME DAMPER (MVD)

NEW DUCTWORK

EXISTING DUCTWORK TO REMAIN

AD

VD

AD

DOUBLE LINE

D R

AD

VD

# KEYED NOTE NUMBER

X

X

X

X

CONNECT NEW TO EXISTING

INDICATES DRAWING ON WHICH

DETAIL APPEARS

INDICATES SECTION NUMBER

INDICATES ON WHICH DRAWING

SECTION APPEARS

INDICATES REVISION & NUMBER

MECHANICAL SYMBOL LEGEND

INDICATES DETAIL, PLAN, SECTION, AND/OR

DIAGRAM(APPLIES ONLY WHERE INDICATED

TYP

X-X

X

X

X

SYSTEM NUMBER

INDICATES TYPICAL DETAIL

(APPLIES TO ALL CONTRACT

ON DRAWINGS)

INDICATES DRAWING ON WHICH

DETAIL APPEARS

(IF APPLICABLE)

DRAWINGS)

EQUIPMENT IDENTITY

(SEE EQUIPMENT ABBREVIATION

LIST AND SCHEDULES)

EQUIPMENT NUMBER

A

CFM

A

CFM

A

CFM

A

CFM

M

DUCT SYMBOLSGENERAL SYMBOLS

ROUND BRANCH DUCT TAKE-OFF W/ VD

T THERMOSTAT

PIPE RISING UP

PIPE DROPPING DOWN

DIRECTION OF FLOW

AUTOMATIC CONTROL VALVE (3-WAY)

PRESSURE REDUCING VALVE (PSI)

AUTOMATIC CONTROL VALVE

BUTTERFLY VALVE

BALL VALVE

CHECK VALVE

GATE VALVE

PRESSURE GAUGE

PIPE WELL

F.S.

FLOW SWITCH

THERMOMETER

STRAINER

PIPING SYMBOLS

DEMOLISH TO THIS POINT

FIRE DAMPER W/ ACCESS

DOOR

FIRE SMOKE DAMPER W/ ACCESS

DOOR

RADIATION DAMPER W/ ACCESS

THROUGH DEVICE

EXHAUST AIR

AUTO AUTOMATIC

FD

GENERAL NOTES

1. PROVIDE AUTOMATIC CHANGEOVER 7-DAY PROGRAMABLE THERMOSTATS BY

EQUIPMENT MANUFACTURER WITH 2-HOUR OCCUPANT OVERRIDE AND 10-HOUR

MINIMUM BATTERY BACKUP. PROVIDE AT LEAST ONE HUMIDISTAT FOR EACH

DEHUMIDIFICATION (AND/OR HUMIDIFICATION) SYSTEM PROVIDED. PROGRAM

SETBACK TEMPERATURES TO 85°F(COOL) AND 55°F(HEAT). ALL TEMPERATURE

CONTROLS ARE TO BE TESTED, ADJUSTED AND CALIBRATED FOR PROPER

OPERATION. MOUNT ALL THERMOSTATS AND TEMPERATURE SENSORS AS

INDICATED ON THE DRAWINGS. COORDINATE EXACT LOCATION WITH THE

ARCHITECT. PROVIDE LOCKING COVER AS REQUIRED BY THE ARCHITECT OR THE

OWNER. MOUNT BETWEEN 48"-54" AFF. PROVIDE THERMOSTATS WITH 5 DEGREE

DEADBAND AND SETPOINT OVERLAP RESTRICTIONS. (PER FBC-EC C403.2.4)

2. WHERE MECHANICAL VENTILATION IS PROVIDED, THE SYSTEM SHALL PROVIDE THE

CAPABILITY TO REDUCE THE OUTDOOR AIR SUPPLY TO THE MINIMUM REQUIRED BY

CHAPTER 4 OF THE FLORIDA BUILDING CODE - MECHANICAL. (PER FBC-EC C403.2.6)

3. PROVIDE MINIMUM R-4.2 INSULATION FOR ALL SUPPLY AND RETURN DUCTS OR

PLENUMS IN UNCONDITIONED SPACES OR BURIED UNDERGROUND. PROVIDE

MINIMUM R-6 INSULATION FOR ANY DUCTWORK ON EXTERIOR OR IN VENTILATED

ATTIC. INSULATION SHALL BE PROTECTED FROM DAMAGE FROM SUNLIGHT,

MOISTURE, MAINTENANCE, AND WIND. ADDITIONAL INSULATION WITH VAPOR

BARRIER SHALL BE PROVIDED WHERE MINIMUM DUCT INSULATION REQUIREMENTS

ARE INSUFFICIENT TO PREVENT CONDENSATION (PER FBC-EC C403.2.9.1)

4. MECHANICAL SYSTEMS SHALL BE COMMISSIONED AND COMPLETED IN

ACCORDANCE WITH FBC-EC SECTION C408.2, INCLUDED IN THESE SPECIFICATIONS

BY REFERENCE.

SUBMISSION.

1. DO NOT SCALE FROM THESE DRAWINGS. EXACT DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL DRAWINGS.

2. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.

3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND REGULATIONS INCLUDING, BUT NOT

LIMITED TO, NATIONAL, CITY, STATE, AND LOCAL ORDINANCES WHICH MAY BE IN EFFECT. ALL MECHANICAL MATERIALS, INSTALLATION

PROCEDURES, AND SYSTEM LAYOUTS SHALL BE APPROVED BY ALL APPLICABLE CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION, AND IT

SHALL BE THE MECHANICAL CONTRACTOR'S RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS AND APPROVALS FOR THIS INSTALLATION.

4. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW THESE PLANS AND SPECIFICATIONS AS WELL AS THE RELATED

PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS TO BECOME

FAMILIAR WITH THE FULL PROJECT SCOPE. IN ADDITION, THIS CONTRACTOR MUST COORDINATE WITH THE OWNER OR OWNER'S REPRESENTATIVE

TO FULLY UNDERSTAND ALL REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN AND WHICH THE OWNER MAY CONSIDER PART OF THIS

CONTRACT. DURING THE COURSE OF CONSTRUCTION COORDINATION AND ACTUAL CONSTRUCTION, IT IS THE RESPONSIBILITY OF THIS

CONTRACTOR TO WORK CLOSELY WITH ALL ACCOMPANYING CONTRACTORS AND TRADESMEN IN ORDER TO ENSURE A SMOOTH RUNNING AND

CAREFULLY COORDINATED INSTALLATION.

5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE BID DOCUMENTS OR BETWEEN THESE BID DOCUMENTS AND THE RELATED PLUMBING, FIRE

PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS, OR BETWEEN THESE BID

DOCUMENTS AND FIELD CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT, AND ENGINEER PRIOR TO BID

SUBMISSION.

6. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN THESE DRAWINGS, BETWEEN INFORMATION PROVIDED IN THESE DRAWINGS

AND THE PROJECT SPECIFICATIONS, AND/OR WITHIN THE PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST COST

REQUIREMENTS SHALL APPLY. SHOULD THIS CONTRACTOR REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR CLARIFICATION.

WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER OF RECORD SHALL HAVE THE SOLE DISCRETION AND RIGHT TO PROVIDE INTERPRETATION

OF INTENT OF THE CONTRACT DOCUMENTS AS REQUIRED. THIS INTERPRETATION SHALL SERVE TO DIRECT THE CONTRACTOR IN ACCORDANCE

WITH THE IMPLIED INTENT OF THE CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE PROJECT.

7. THE MECHANICAL CONTRACTOR SHALL PROVIDE A COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS, INDICATING THE PRECISE LOCATION OF ALL

SYSTEMS, EQUIPMENT, CONCEALED OR EMBEDDED PIPING, PIPING CONNECTIONS, AND ACCESS DOORS. THESE DRAWINGS SHALL ALSO INCLUDE

ALL CHANGES AND DEVIATIONS FROM THE BID DOCUMENTS.

8. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW MECHANICAL EQUIPMENT WITH NEW LIGHT LOCATIONS AND TILE LOCATIONS.

REFER TO THE ARCHITECT'S REFLECTED CEILING PLAN LAYOUT.

9. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. AIR VELOCITY SHALL NOT EXCEED 700 FEET PER MINUTE IN

DWELLING UNITS.

10. RUN ALL DUCTWORK AND PIPING WITH AS FEW OFFSETS AS POSSIBLE THROUGHOUT THE ENTIRE BUILDING. COORDINATE AND VERIFY WITH

OTHER CONTRACTORS SO AS NOT TO INTERFERE WITH PLUMBING, FIRE PROTECTION PIPING, LIGHTING SYSTEMS, ETC.

11. ALL REQUIRED OFFSETS, RISES, AND DROPS DUE TO POSSIBLE OBSTRUCTIONS OF DUCT AND PIPE RUNS ARE NOT NECESSARILY SHOWN. THIS

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIPING, SUPPORTS, ETC. NECESSARY FOR PROPER

INSTALLATION AND OPERATION OF NEW HVAC SYSTEM. THIS CONTRACTOR SHALL INCLUDE A CONTINGENCY IN HIS/HER BID TO OFFSET ANY COST

REQUIRED FOR ADDITIONAL FITTINGS AND LABOR THAT MAY BE REQUIRED.

12. ALL EXPOSED HORIZONTAL AND VERTICAL DUCTWORK AND PIPING SHALL BE INSTALLED IN A NEAT ARRANGEMENT IN LOCATIONS WHICH ARE THE

MOST INCONSPICUOUS. VERTICAL DROPS SHALL BE KEPT TO AN ABSOLUTE MINIMUM AND THEIR FINAL LOCATIONS SHALL BE COORDINATED AND

RUN WITHIN CHASES, WALLS, AND SOFFITS WITH OTHER MECHANICAL, ELECTRICAL, PLUMBING, ETC. FEEDS. ALL SUCH LOCATIONS ARE TO BE

REVIEWED WITH AN OWNER REPRESENTATIVE AND ARCHITECT PRIOR TO INSTALLATION.

13. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL

ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.

14. ALL DUCT PENETRATIONS THROUGH A RATED FLOOR, WALL ,OR CEILING ASSEMBLY SHALL BE PROVIDED WITH A FIRE DAMPER. FOR AIR DEVICES

INSTALLED IN A RATED FLOOR/CEILING ASSEMBLY, INSTALL A CEILING RADIATION DAMPER. REFER TO DETAIL SHEET.

15. THROUGH PENETRATIONS OF FIRE RESISTANCE RATED HORIZONTAL ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED

THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE

PRESSURE DIFFERENTIAL OF 0.01 INCHES OF WATER (2.49PA). THE SYSTEM SHALL HAVE AN F/T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS

THAN THE REQUIRED RATING OF THE FLOOR WALL, OR CEILING PENETRATED. SEE ARCHITECTURAL DRAWINGS FOR RATED ASSEMBLY LOCATIONS, RATINGS, AND DETAILS. EXCEPTIONS: FLOOR PENETRATIONS CONTAINED AND LOCATED WITHIN THE CAVITY OF A WALL ABOVE THE FLOOR

OR BELOW THE FLOOR DO NOT REQUIRE A T RATING.

16. DUCT SMOKE DETECTORS SHOWN ON PLANS ARE DIAGRAMMATIC. REFER TO MANUFACTURER'S INSTRUCTIONS FOR EXACT/OPTIMUM LOCATION IN

DUCTWORK. DUCT SMOKE DETECTORS SHALL BE PURCHASED BY THE ELECTRICAL CONTRACTOR, INSTALLED BY THE MECHANICAL CONTRACTOR

AND WIRED INTO FIRE PROTECTION SYSTEM BY THE FIRE PROTECTION CONTRACTOR.

18. CONDENSATE SHALL BE PIPED FULL SIZE TO THE NEAREST APPROVED FLOOR DRAIN, HUB DRAIN, STORM WATER DRAINAGE SYSTEM, OR

LANDSCAPED/GRASS AREA VIA AN INDIRECT CONNECTION. CONDENSATE SHALL NOT BE ALLOWED TO DRAIN ONTO ANY WALKWAY.

19. DRYER EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF MIN. 0.016" GALVANIZED STEEL WITH A SMOOTH INTERIOR AND NO PROJECTIONS.

JOINTS SHALL RUN IN DIRECTION OF AIRFLOW. PROVIDE FLAPPER STYLE GRAVITY BACKDRAFT DAMPER AT TERMINATION OF EXHAUST OUTLET

INTEGRAL TO WALL OR ROOF CAP. INSTALL PERMANENT LABEL AT DRYER CONNECTION LISTING THE ACTUAL FIELD INSTALLED EQUIVALENT

LENGTH OF THE CONCEALED VENT DUCT.

20. INSULATE EACH REFRIGERANT LINESET WITH 1-INCH FLEXIBLE, CLOSED CELL ELASTOMERIC INSULATION. PROVIDE ALUMINUM JACKETING FOR

EXPOSED PIPING. ALUMINUM JACKETING SHALL BE PAINT GRIPPING TYPE. PROVIDE EXTERIOR PIPING PORTS WITH LOCKING TYPE TAMPER

RESISTANT CAPS.

21. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT. COORDINATE LOCATION WITH ARCHITECTURAL

INTERIOR ELEVATIONS.

22. INSTALL SLEEVES FOR PIPING PENETRATIONS OF WALLS, CEILINGS, AND FLOORS. INSTALL CHROME PLATED ESCUTCHEONS FOR PIPING

PENETRATIONS OF WALLS, CEILINGS, AND FLOORS.

23. ALL PLUMBING VENTS AND BUILDING EXHAUST SHALL BE LOCATED A MINIMUM OF 10 FEET FROM MECHANICAL INTAKES AND THREE FEET FROM

OPERABLE OPENINGS, INCLUDING DOORS AND OPERABLE WINDOWS.

24. MAINTAIN MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES AROUND EQUIPMENT AT A MINIMUM. DO NOT ROUTE PIPING, DUCTWORK, CONTROL WIRE, ETC. THROUGH THE SERVICE CLEARANCE AREAS.

25. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH A FACTORY DISCONNECT SWITCH, STARTER, VFD, OR MOTOR RATED SWITCH AS

REQUIRED FOR CODE COMPLIANT OPERATION OF ALL MOTORIZED EQUIPMENT IN ACCORDANCE WITH CODE AND THE DESIGN INTENT ASSOCIATED

WITH THESE DRAWINGS. COORDINATE ALL DISCONNECTS AND STARTER REQUIREMENTS WITH THE PROJECT ELECTRICAL CONTRACTOR PRIOR TO

BID TO ENSURE A COORDINATED INSTALLATION.

26. CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH VIBRATION ISOLATION IN ACCORDANCE WITH THE 2015 ASHRAE HANDBOOK HVAC

APPLICATION CHAPTER 48 - NOISE AND VIBRATION CONTROL TABLE 47 AND CODES.

17. TEST AND BALANCE BY A THIRD PARTY SHALL BE REQUIRED FOR ALL SUPPLY, RETURN, OA, AND VENTILATION FOR THIS FACILITY.

27. WHERE REQUIRED FOR ACCESS TO EQUIPMENT AND ACCESSORIES ABOVE HARD CEILINGS OR IN WALLS, ACCESS PANELS SHALL BE PROVIDED BY

THIS CONTRACTOR. PANELS IN RATED ASSEMBLIES SHALL HAVE LISTED RATINGS EQUAL TO OR GREATER THAN THE ASSEMBLY IN WHICH THEY

ARE INSTALLED. REFER TO ARCHITECTURAL DRAWINGS FOR ACCESS PANEL SPECIFICATIONS.

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING A SHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

M0.1

LEGENDS AND GENERAL NOTES

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

24-015

06/29/2026

MECHANICAL SPECIFICATIONS

1. GENERAL

PROVIDE MATERIALS, EQUIPMENT, ACCESSORIES, INCIDENTALS, ARTICLES,

ITEMS, OPERATIONS, INCLUDING LABOR, NECESSARY FOR COMPLETION OF

WORK INDICATED AND/OR CALLED FOR ON THESE DRAWINGS. SUBMIT

SHOP DRAWINGS AND PRODUCT DATA ON ALL EQUIPMENT, PIPE,

DUCTWORK, AND INSULATION.

PROVIDE A COPY OF BOUND CLOSE-OUT DOCUMENTS TO THE ARCHITECT

FOR APPROVAL. PROVIDE TWO BOUND COPIES OF CLOSE OUT DOCUMENTS

TO THE OWNER'S REPRESENTATIVE AFTER APPROVAL. CLOSE OUT

DOCUMENTS SHALL INCLUDE COMPLETE I.O.M.'S FOR EACH PIECE OF

EQUIPMENT, A FULL-SIZE SET OF AS-BUILT PLANS AND FACTORY

AUTHORIZED SERVICE START-UP FORMS FOR EACH PIECE OF EQUIPMENT

INDICATING PROPER OPERATION ACROSS THE SEQUENCE.

2. REGULATORY REQUIREMENTS

ALL WORK SHALL BE PER FBC MECHANICAL, NEC, NFPA, UL, STATE, LOCAL

INSPECTORS AND OTHER APPLICABLE CODES.

3. COORDINATION

INSTALLATION OF ALL WORK SHALL BE COORDINATED WITH OTHER TRADES

AND WITH EXISTING CONDITIONS. CONTRACTOR SHALL VISIT THE SITE AND

VERIFY SIZES, CAPACITY, PERFORMANCE, AND LOCATION OF ALL EXISTING

WORK.

4. GUARANTEES

THE CONTRACTOR SHALL PROVIDE A ONE YEAR WRITTEN GUARANTEE FOR

ALL MATERIALS AND LABOR FROM THE DATE OF SUBSTANTIAL

COMPLETION. GUARANTEE SHALL COVER ALL LABOR AND MATERIALS TO

REPLACE DEFECTIVE MATERIALS AND TO ENSURE PROPER OPERATION OF

ALL SYSTEMS.

5. INSTALLATION

A. ALL EQUIPMENT AND MATERIAL SHALL BE INSTALLED PER THEIR

RESPECTIVE MANUFACTURER'S WRITTEN INSTRUCTIONS. PROVIDE

ADEQUATE CLEARANCE FOR ALL EQUIPMENT AND MATERIAL FOR

REGULAR MAINTENANCE, REMOVAL AND AIR FLOW. CONTRACTOR

SHALL PROVIDE CONTROLS, INCLUDING THERMOSTATS, CONTROL

POWER TRANSFORMERS, WIRING, PROGRAMMING, ETC., TO OPERATE

ALL EQUIPMENT UTILIZED FOR THIS PROJECT. ADJUST AIR HANDLING

UNITS, EXHAUST FANS, AND AIR DEVICES TO PROVIDE CFM'S AS SHOWN.

B. DUCTS SHALL BE SUPPORTED ON TRAPEZE WITH HANGER RODS.

6. DUCTWORK

A. GENERAL: EXCEPT FOR SYSTEMS SPECIFIED OTHERWISE, CONSTRUCT

DUCTS,CASINGS, AND ACCESSORIES OF GALVANIZED SHEET STEEL,

ASTM A653, G90 GALVANIZING. DUCT SHEET METAL THICKNESS SHALL BE

IN ACCORDANCE WITH THE SMACNA DUCT CONSTRUCTION MANUAL.

DUCT INSTALLATION METHODS, SUPPORTS AND OTHER PERTINENT

INSTALLATION CRITERIA SHALL BE AS INDICATED IN THE SMACNA DUCT

CONSTRUCTION STANDARDS AND SMACNA DUCT INSTALLATION

MANUALS.

B. JOINT SEALING: REFER TO SMACNA HVAC DUCT CONSTRUCTION

STANDARDS AND APPLICABLE MECHANICAL AND ENERGY CODES FOR

RECOMMENDED SEAL CLASS. SYSTEMS SHALL BE SEALED TO SEAL

CLASS A.

1. SEALANT: ELASTOMERIC COMPOUND, GUN OR BRUSH GRADE,

MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPED (DRY STATE)

COMPOUNDED SPECIFICALLY FOR SEALING DUCTWORK AS

RECOMMENDED BY THE MANUFACTURER.

2. GASKETS IN FLANGED JOINTS: SOFT NEOPRENE. APPROVED FACTORY

MADE JOINTS MAY BE USED.

C. DUCT MATERIALS:

1. SINGLE WALL GALVANIZED STEEL RECTANGULAR AND ROUND DUCTS:

ASTM A525 OR ASTM A527 GALVANIZED STEEL SHEET, LOCK-FORMING

QUALITY, HAVING ZINC COATING OF .90 OZ. PER SQ.FT. FOR EACH SIDE

IN CONFORMANCE WITH ASTM A90.

2. DOUBLE WALL GALVANIZED STEEL ROUND DUCTS: GALVANIZED STEEL

MEETING ASTM A653 STANDARDS WITH FINISH SELECTED BY

ARCHITECT, ONE INCH (1”) THICK FIBERGLASS INSULATION, SPIRAL

OUTER SHELL AND PERFORATED INNER LINER. A UL APPROVED MYLAR

FILM AND TAPED JOINTS SHALL SEPARATE THE INTERNAL FIBERGLASS

LINING AND AIRSTREAM. DUCT SYSTEMS SHALL BE FACTORY

PRE-FABRICATED. DUCTS SHALL HAVE SPIRAL LOCKSEAM

CONSTRUCTION. FITTINGS SHALL BE CONSTRUCTED OF A

PERFORATED SHEET METAL INTERNAL LINER, 1 INCH LAYER OF

FIBERGLASS INSULATION, MYLAR FILM AND AN OUTER GALVANIZED

PRESSURE SHELL WITH FINISH SELECTED BY ARCHITECT. STANDING

SEAM JOINTS SHALL BE USED WHEREVER POSSIBLE ON FITTINGS. ALL

STANDING SEAM JOINTS SHALL BE SEALED WITH A UL CLASSIFIED ZERO

FLAME SPREAD AND ZERO SMOKE DEVELOPED CEMENT SPECIALLY

FORMULATED FOR BONDING METAL-TO-METAL JOINTS. ALL WELDED

JOINTS SHALL BE COATED WITH A PROTECTIVE PAINT, INSIDE AND OUT,

TO PREVENT DAMAGE TO THE GALVANIZED SURFACE. ALL DOUBLE

WALL DUCT AND FITTINGS SHALL BE PROVIDED WITH BOTH AN INNER

LINER COUPLING AND AN OUTER PRESSURE SHELL COUPLING. OUTER

SHELL CONNECTIONS CAN BE BY SLIP JOINT (UP TO 24” DIAMETER) OR

BOLTED FLANGED JOINT WITH AIR SEAL GASKET.

SUBMIT DUCT FINISH TO ARCHITECT FOR APPROVAL.

D. FLEXIBLE FIBERGLASS DUCT: FLEXIBLE FIBERGLASS DUCT WITH A

MAXIMUM THERMAL CONDUCTIVITY OF 0.23 BTU/HR - DEGREES F -

SQ.FT. AT 75 DEGREES F MEAN TEMPERATURE WITH A MAXIMUM FLAME

SPREAD RATING OF 25 AND SMOKE DEVELOPED RATING OF 50.

FLEXIBLE FIBERGLASS DUCT SHALL BE OWENS-CORNING VALUFLEX OR

APPROVED EQUAL.

1. FLEXIBLE FIBERGLASS DUCT SHALL BE PROVIDED WITH SPIN-IN

BELLMOUTH FITTING, VOLUME DAMPER AND STAINLESS STEEL

CLAMP.

2. FLEXIBLE FIBERGLASS DUCT SIZE SHALL BE SAME AS AIR DEVICE

NECK SIZE UNLESS OTHERWISE NOTED.

3. FLEXIBLE FIBERGLASS DUCT LENGTH SHALL BE BETWEEN 6 AND 10

FEET.

4. FLEXIBLE DUCT SHALL BE USED FOR CONNECTION OF SUPPLY AIR

DEVICES ONLY. ALL EXHAUST AND RETURN DUCTWORK SHALL BE

RIGID DUCTWORK.

5. PROVIDE MANUAL VOLUME DAMPERS IN BRANCH DUCTS TO ALL AIR

DEVICES.

E. DUCT SCHEDULE (SEE SCHEDULE SHEET)

7. DUCT ACCESSORIES

A. VOLUME DAMPERS: SINGLE BLADE OR OPPOSED BLADE, MULTI-LOUVER

TYPE AS DETAILED IN SMACNA STANDARDS. ANY DAMPERS REQUIRED

TO HAVE A MOTORIZED DAMPER SHALL BE PROVIDED BY THE

MECHANICAL CONTRACTOR AS A COMPLETE SYSTEM INCLUDING THE

DAMPER, ACTUATOR AND LINKAGE ATTACHMENTS. ACTUATORS SHALL

BE AS PROVIDED BY BELIMO. IT SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR TO PROVIDE ALL DAMPERS AND ACTUATORS AS

REQUIRED AND THESE SYSTEMS SHALL BE COORDINATED WITH THE

CONTROLS CONTRACTOR AND ELECTRICAL CONTRACTOR

ACCORDINGLY FOR POWER OR CONTROL REQUIREMENTS.

8. DUCT INSULATION (CONCEALED LOCATIONS ONLY, SEE DOUBLE-WALL DUCT

SECTION FOR EXPOSED LOCATIONS)

A. INDOOR DUCTWORK: ASTM C553 (BLANKET, FLEXIBLE) TYPE I; 6.0

INSTALLED 'R' VALUE (MINIMUM) AT 75 DEGREES F, FOR USE FOR

SYSTEM TEMPERATURES BETWEEN 40 AND 250 DEGREES F . PROVIDE

FOIL SCRIM (FSK) FACING. SEAMS SEALED WITH PRESSURE SENSITIVE

TAPE AND MASTIC.

B. OUTDOOR DUCTWORK: RIGID GLASS FIBER BOARD; ANSI/ASTM C612;

COMMERCIAL GRADE; 8.0 INSTALLED 'R' VALUE (MINIMUM) AT 75

DEGREES F, FOIL SCRIM KRAFT FACING FOR AIR CONDITIONING DUCTS

(NOMINALLY 2" THICK) EXPOSED TO THE WEATHER. SEAMS SEALED

WITH PRESSURE SENSITIVE TAPE AND MASTIC. PROVIDE WITH

ALUMINUM WEATHER PROOF JACKETING AND ENSURE THAT TOPS OF

DUCTS ARE 'TENTED' TO PROHIBIT THE PONDING OF WATER. ALL

SEAMS IN INSULATION AND JACKET SHALL BE SEALED WATER TIGHT.

INSULATION SHALL BE EQUAL TO CERTAINTEED, CERTAPRO

COMMERCIAL BOARD WITH FSK FACING, TYPE CB 300 (3.0 LB/CU.FT.)

MINIMUM DENSITY.

9. AIR HANDLING UNITS

A. GENERAL: UNIT SHALL BE VERTICAL OR HORIZONTAL AIRFLOW (SEE

SCHEDULE). UNIT BE FACTORY RUN TESTED TO CHECK COOLING AND

HEATING OPERATION, FAN ROTATION, AND CONTROL. THE

HEATING/COOLING PERFORMANCE OF THE INDOOR UNIT AND OUTDOOR

UNIT SHALL BE CERTIFIED TO ANSI STANDARDS. SUBMIT AHRI

PERFORMANCE INFORMATION. WIRING INTERNAL TO THE UNIT SHALL BE

COLORED AND NUMBERED FOR IDENTIFICATION. UNITS SHALL BE UL

LISTED AND LABELED. PROVIDE WITH FACTORY MOUNTED CIRCUIT

BREAKER. ELECTRICAL CONTRACTOR TO PROVIDE UNIT DISCONNECT

SWITCH.

B. UNIT CASING: ALL COMPONENTS SHALL BE MOUNTED IN A HEAVY GAUGE,

GALVANIZED STEEL, INSULATED, AND GASKETED CABINET WITH

CORROSION RESISTANT SCREWS. ACCESS PANELS SHALL BE PROVIDED

FOR UNIT CONTROLS, COIL, FILTER, HEATER AND FAN. INDOOR AIR SECTION

COMPARTMENT SHALL BE COMPLETELY INSULATED WITH FIREPROOF,

PERMANENT, ODORLESS GLASS FIBER MATERIAL. KNOCKOUTS SHALL BE

PROVIDED FOR UTILITY AND CONTROL CONNECTIONS.

C. EVAPORATOR COIL: COIL SHALL BE INTERNALLY FINNED OR SMOOTH BORE

3/8" COPPER TUBES MECHANICALLY BONDED TO ALUMINUM FINS.

EVAPORATOR COIL LEAK AND PRESSURE TESTED TO 200 PSIG.

D. SUPPLY AIR FAN: DIRECT-DRIVE, FORWARD-CURVED, CENTRIFUGAL WHEEL.

MOTOR SHALL HAVE THERMAL OVERLOAD PROTECTION AND PERMANENTLY

LUBRICATED MOTOR BEARINGS. MOTOR/BLOWER ASSEMBLY ISOLATED

FROM UNIT WITH RUBBER MOUNTS.

E. ELECTRIC HEATER ELEMENTS SHALL BE CONSTRUCTED OF HEAVY-DUTY

NICKEL CHROMIUM ELEMENTS INTERNALLY DELTA CONNECTED FOR 240

VOLT, WYE CONNECTED FOR 480 VOLT. CAPACITY MODULATION SHALL BE

ACHIEVED THROUGH THE USE OF PULSE WIDTH MODULATION CONTROL.

EACH HEATER PACKAGE SHALL HAVE AUTOMATICALLY RESET HIGH LIMIT

CONTROL OPERATING THROUGH HEATING ELEMENT CONTACTORS. ALL

HEATERS SHALL BE INDIVIDUALLY FUSED FROM FACTORY AND SHALL MEET

ALL NEC AND LOCAL CODE REQUIREMENTS. POWER ASSEMBLIES SHALL

PROVIDE SINGLE-POINT CONNECTION. ELECTRIC HEAT MODULES SHALL BE

UL LISTED.

F. UNIT FILTER FRAME TO HOUSE A MINIMUM MERV 6 FILTER PER ASHRAE 62.2

REQUIREMENTS.

G. MODULATING ECONOMIZER (WHERE SPECIFIED ON SCHEDULE) :

ACCESSORY SHALL BE FIELD INSTALLED AND BE COMPOSED OF THE

FOLLOWING ITEMS: 0-100% FRESH AIR DAMPER, DAMPER DRIVE MOTOR,

FIXED DRY BULB ENTHALPY CONTROL, AND LOW VOLTAGE WIRING PLUG

FOR ELECTRICAL CONNECTIONS. DIFFERENTIAL ENTHALPY CONTROL IS

REQUIRED. ECONOMIZER OPERATIONS SHALL BE CONTROLLED BY THE

PRESET POSITION OF THE ENTHALPY CONTROL. A BAROMETRIC RELIEF

DAMPER SHALL BE STANDARD WITH THE ECONOMIZER AND PROVIDE A

PRESSURE OPERATED DAMPER THAT SHALL BE GRAVITY CLOSING AND

PROHIBIT ENTRANCE OF OUTSIDE AIR ON EQUIPMENT “OFF” CYCLE.

H. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ALL

APPLICABLE CODES AND STANDARDS AS REQUIRED AT THE PROJECT

LOCATION.

I. MANUFACTURER SHALL FURNISH A FACTORY-TRAINED SERVICE ENGINEER

WITHOUT ADDITIONAL CHARGE TO PREPARE THE MACHINE FOR

OPERATION, START THE UNIT AND CERTIFY INITIAL FIELD STARTUP. THE

MANUFACTURER SHALL PROVIDE A WRITTEN CERTIFICATION TO THE

ARCHITECT/ENGINEER THAT THE UNIT HAS BEEN PREPARED AND IS READY

FOR OPERATION.

J. INSTALL UNIT WITH PROGRAMMABLE 7-DAY THERMOSTAT CAPABLE OF

AUTOMATIC HEAT / COOL CHANGEOVER, ADJUSTABLE DEAD-BAND,

ADAPTIVE HEAT RECOVERY, INSULATED MOUNTING BASE, 24V POWER WITH

BATTERY BACKUP TO PRESERVE PROGRAM. MOUNT THERMOSTAT LEVEL

AND PER THE ARCHITECT'S INTERIOR FINISH ELEVATIONS.

10. HEAT PUMP AND CONDENSING UNITS

A. GENERAL: INDOOR AND OUTDOOR UNIT BE FACTORY RUN TESTED TO

CHECK COOLING AND HEATING OPERATION, FAN ROTATION, AND CONTROL.

UNITS SHALL BE DESIGNED TO OPERATE AT REFRIGERANT SYSTEM AT

AMBIENT TEMPERATURES BETWEEN 55°F AND 115°F AS MANUFACTURED.

THE HEATING/COOLING PERFORMANCE SHALL BE CERTIFIED TO ANSI

STANDARDS.

B. UNIT CASING: ALL COMPONENTS SHALL BE MOUNTED IN A HEAVY GAUGE,

GALVANIZED STEEL, INSULATED, AND GASKETED CABINET WITH A WEATHER

RESISTANT FINISH AND CORROSION RESISTANT SCREWS. ACCESS PANELS

SHALL BE PROVIDED FOR UNIT CONTROLS, COIL AND FAN (S).

C. COMPRESSOR: THE COMPRESSOR SHALL BE HERMETICALLY SEALED, HIGH

EFFICIENCY. PROVIDE INTERNAL OVERCURRENT AND OVER TEMPERATURE

PROTECTION AND INTERNAL PRESSURE RELIEF.

D. REFRIGERATION SYSTEM: SYSTEM SHALL UTILIZE R-401A. SERVICE

PRESSURE TAP PORTS, THERMAL EXPANSION VALVE AND A REFRIGERANT

LINE FILTER DRYER SHALL BE PROVIDED. PROVIDE TAMPER RESISTANT

LOCKING PORT CAPS. EACH REFRIGERANT CIRCUIT SHALL HAVE THERMAL

EXPANSION VALVE, SERVICE PRESSURE PORTS AND REFRIGERANT LINE

FILTER DRYERS FACTORY-INSTALLED AS STANDARD. PROVIDE WITH

FACTORY MOUNTED CIRCUIT BREAKER. ELECTRICAL CONTRACTOR TO

PROVIDE UNIT DISCONNECT SWITCH. PROVIDE ALL MANUFACTURER'S

RECOMMENDED COMPONENTS FOR EXTENDED LINE LENGTH AND LIFT

APPLICATIONS.

E. CONDENSER COIL: COIL SHALL BE CONTINUOUSLY WRAPPED, CORROSION

RESISTANT ALL ALUMINUM WITH MINIMUM BRAZED JOINTS. 3/8 INCH O.D.

SEAMLESS ALUMINUM TUBING GLUED TO A CONTINUOUS ALUMINUM FIN.

COIL TO BE LAB TESTED TO WITHSTAND 2,000 POUNDS OF PRESSURE PER

SQUARE INCH. CONDENSER COIL SHALL BE LEAK AND PRESSURE TESTED

TO 450 PSIG.

F. CONDENSER FAN: DIRECT-DRIVE, DRAW THRU PROPELLER TYPE.

WEATHER-PROOFED PERMANENT SPLIT CAPACITOR FAN MOTOR SHALL

HAVE BUILT-IN THERMAL OVERLOAD AND PERMANENTLY LUBRICATED

MOTOR BEARINGS.

G. ROOF CURB: REFER TO STRUCTURAL ENGINEER'S DETAIL FOR EQUIPMENT

CURB. COORDINATE AND VERIFY THAT ROOF IS READY TO RECEIVE WORK.

H. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ALL

APPLICABLE CODES AND STANDARDS AS REQUIRED AT THE PROJECT

LOCATION.

I. MANUFACTURER SHALL FURNISH A FACTORY-TRAINED SERVICE ENGINEER

WITHOUT ADDITIONAL CHARGE TO PREPARE THE MACHINE FOR

OPERATION, START THE UNIT AND CERTIFY INITIAL FIELD STARTUP. THE

MANUFACTURER SHALL PROVIDE A WRITTEN CERTIFICATION TO THE

ARCHITECT/ENGINEER THAT THE UNIT HAS BEEN PREPARED AND IS READY

FOR OPERATION.

11. AIR DEVICES

FURNISH AS SCHEDULED OR OBTAIN PRIOR APPROVAL TO SUBMIT AN

ALTERNATE MANUFACTURER / MODEL.

DEVICE SHALL BE OF ALUMINUM CONSTRUCTION, WITH BAKED WHITE

ENAMEL FINISH UNLESS OTHERWISE STATED. FURNISH DEVICE WITH

ACCESSORIES SCHEDULED, INCLUDING PLASTER TRIM RING FOR HARD

CEILING INSTALLATION, UL-LISTED FIRE RADIATION DAMPER FOR RATED

PARTITION INSTALLATIONS. OPPOSED-BLADE OR BUTTERFLY (ROUND ONLY)

DAMPERS MAY BE INSTALLED ONLY WHEN BRANCH TAKE-OFF VOLUME

DAMPERS CANNOT BE INSTALLED AND ONLY WITH PRIOR APPROVAL BY THE

ENGINEER. INSTALL INSULATION ON BACK PANELS FOR ALL CEILING

SUPPLY GRILLES. PLENUMS SHALL BE CONSTRUCTED TO SMACNA

STANDARDS FOR DUCT RIGIDITY AND SEAL, LINED WITH 1" CERTAINTEED

TOUGHGUARD LINER BOARD INSTALLED PER MANUFACTURES DIRECTIONS

AND FINISHED BLACK.

12. REFRIGERANT PIPING

A. LINE TEST PRESSURE FOR REFRIGERANT R-32:

SUCTION LINES FOR AIR-CONDITIONING APPLICATIONS: 450 PSIG

SUCTION LINES FOR HEAT-PUMP APPLICATIONS: 600 PSIG

HOT-GAS AND LIQUID LINES: 600 PSIG

B. REFRIGERANT PIPING INDICATED ON DRAWINGS IS SCHEMATIC ONLY.

SIZE PIPING AND DESIGN ACTUAL PIPING LAYOUT, INCLUDING OIL TRAPS,

DOUBLE RISERS, SPECIALTIES, AND PIPE AND TUBE SIZES TO

ACCOMMODATE, AS A MINIMUM, EQUIPMENT PROVIDED, ELEVATION

DIFFERENCE BETWEEN COMPRESSOR AND EVAPORATOR, AND LENGTH OF

PIPING TO ENSURE PROPER OPERATION AND COMPLIANCE WITH

WARRANTIES OF CONNECTED EQUIPMENT.

C. SUBMIT WELDING CERTIFICATES, PIPING, VALVES, HANGERS AND

INSULATION FOR APPROVAL.

D. PIPING TO BE COPPER TUBE: ASTM B 280, TYPE ACR, WITH

WROUGHT-COPPER FITTINGS PER ASME B16.22. BRAZING FILLER METALS:

AWS A5.8. INSULATE WITH 1-INCH ELASTOMERIC. PROVIDE ALUMINUM

JACKETING FOR PIPING EXPOSED TO WEATHER.

E. SLOPE REFRIGERANT PIPING AS FOLLOWS:

1.1 INSTALL HORIZONTAL HOT-GAS DISCHARGE PIPING WITH A UNIFORM

SLOPE DOWNWARD AWAY FROM COMPRESSOR.

1.2 INSTALL HORIZONTAL SUCTION LINES WITH A UNIFORM SLOPE

DOWNWARD TO COMPRESSOR.

1.3 INSTALL TRAPS AND DOUBLE RISERS TO ENTRAIN OIL IN VERTICAL

RUNS. LIQUID LINES MAY BE INSTALLED LEVEL.

1.4 WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS

AND SIGHT GLASSES; ALSO REMOVE VALVE STEMS, SEATS, AND PACKING,

AND ACCESSIBLE INTERNAL PARTS OF REFRIGERANT SPECIALTIES. DO NOT

APPLY HEAT NEAR EXPANSION-VALVE BULB.

F. HANGERS TO BE MALLEABLE IRON CARBON STEEL, ADJUSTABLE SWIVEL,

SPLIT RING. PROVIDE TRAPEZE HANGERS (STEEL CHANNEL WITH WELDED

SPACERS) FOR MULTIPLE PIPE SUPPORT. PROVIDE SADDLE TO PROTECT

INSULATION. PROVIDE STEEL RISER CLAMP FOR VERTICAL SUPPORT.

SUPPORT VERTICALLY AT EVERY FLOOR.

G. PROVIDE TAMPER RESISTANT, LOCKING-TYPE, ACCESS PORT CAPS ON

ALL PIPING PORTS LOCATED OUTSIDE.

13. TEST AND BALANCE

TEST AND BALANCE CONTRACTOR SHALL BE CERTIFIED BY AABC OR NEBB.

SUBMIT TAB QUALIFICATIONS AND SAMPLE REPORT FORMS FOR APPROVAL

BY THE ENGINEER. SUBMIT TAB REPORT TO ENGINEER FOR REVIEW. UPON

REQUEST, TAB CONTRACTOR SHALL DEMONSTRATE ON-SITE

CONFIRMATION OF THE TAB REPORT MEASUREMENTS WITNESSED BY THE

ENGINEER. DISCREPANCIES WILL REQUIRE ADDITIONAL TAB SAMPLING AND

RE-BALANCE OF THE SYSTEMS.

ADJUST ALL SYSTEM COMPONENTS, EQUIPMENT, FLOW DEVICES AND

SENSORS PER "AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE,

V 2002".

PROVIDE BELT AND SHEAVE CHANGES AS REQUIRED FOR BALANCING OF

ALL FANS INDICATED ON THESE DRAWINGS. BELT AND SHEAVE CHANGES

SHALL BE PROVIDED AT THE CONTRACTOR'S EXPENSE.

FLOW TOLERANCES:

AIR HANDLING UNITS, (CUBIC FEET PER MINUTE): MINUS 0 PERCENT TO

PLUS 10 PERCENT.

EXHAUST FANS: 0 PERCENT TO PLUS 10 PERCENT.

MINIMUM OUTSIDE AIR: 0 PERCENT TO PLUS 10 PERCENT.

INDIVIDUAL ROOM AIR OUTLETS AND INLETS, AND AIR FLOW RATES NOT

MENTIONED ABOVE: MINUS 5 PERCENT TO PLUS 10 PERCENT EXCEPT IF

THE AIR TO A SPACE IS 100 CFM OR LESS THE TOLERANCE WOULD BE

MINUS 5 TO PLUS 5 PERCENT.

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING A SHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

M0.2

SPECIFICATIONS

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

M2.0

M3.1

M2.1

M3.0

M4.0

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING A SHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

M1.0

OVERALL FLOOR PLAN - PHASE

SCOPE

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

24-015

1/4" = 1'-0"M1.0

1 OVERALL FLOOR PLAN

N

AHU-EX-1

AHU-EX-2

T

T

7 7 7

CU-EX-1 CU-EX-2

8 8

GENERAL NOTES

A. COORDINATE HVAC DEMOLITION WITH OTHER TRADES AND GENERAL CONTRACTOR.

DO NOT DEMOLISH EQUIPMENT OR COMPONENTS WITHOUT APPROVAL.

B. �PRIOR TO START OF ANY DEMOLITION WORK, CONTRACTOR SHALL PRE TEST ALL AIR

DEVICES SCHEDULED TO BE REUSED, EXHAUST FANS, AND AIR HANDLING UNITS

WITHIN THE PROJECT LIMITS. PROVIDE A REPORT SHOWING AIR FLOWS OF EACH

DEVICE TO ARCHITECT AND ENGINEER.

C. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE DAMAGE OR REMOVAL IN

WHOLE OR IN PART OF ANY STRUCTURAL MEMBER WITHOUT EXPRESS APPROVAL OF

THE GENERAL CONTRACTOR.

D. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT, PIPE, OR ELECTRICAL CABLE /

CONDUIT THAT RESULTS FROM DEMOLITION. UNDER NO CIRCUMSTANCE WILL

DEMOLITION RESULT IN THE PERMANENT EXPOSURE OF ANY CHARGED OR LIVE

COMPONENT OF ANY EQUIPMENT TO BE RE-USED.

E. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT THEREOF THAT SHALL BE RE-

USED.

F. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH THE GENERAL CONTRACTOR.

TURN OVER ANY COMPONENTS TO THE OWNER AS DESIGNATED IN CLEAN CONDITION,

WITHOUT DAMAGE, AND WITH OPENING SEALED. FURNISH RECEIPTS OF PROPER

DISPOSAL OF ALL ITEMS REMOVED TO THE GENERAL CONTRACTOR UPON REQUEST.

RECEIPTS SHALL INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL, STATE, AND

FEDERAL REGULATIONS.

G. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL PERFORM MAINTENANCE

SERVICE TO EXISTING EQUIPMENT TO BE REUSED IN THE NEW LAYOUT (TO REMAIN OR

TO BE RELOCATED). NOTIFY ARCHITECT, OWNER, AND ENGINEER OF ANY DEFICIENCY

FOUND DURING PRE-CONSTRUCTION MAINTENANCE SERVICE.

KEYNOTES

1. EXISTING AIR HANDLING UNIT AND ASSOCIATED DUCTWORK MAINS EXISTING TO

REMAIN UP TO POINT INDICATED ON PLAN.. CONTRACTOR SHALL CLEAN, TEST, AND

INSPECT UNIT AND ASSOCIATED MECHANICAL EQUIPMENT FOR PROPER OPERATION.

REPLACE UNIT IN KIND IF FOUND TO BE DEFECTIVE. REPLACE DUCTWORK,

INSULATION, ETC. IN KIND IF FOUND TO BE DEFECTIVE.

2. CONTRACTOR SHALL REMOVE EXISTING SUPPLY DIFFUSER AND ALL ASSOCIATED

DUCTWORK, FITTINGS, AND ACCESSORIES.

3. CONTRACTOR SHALL REMOVE EXISTING RETURN GRILLE AND ALL ASSOCIATED

DUCTWORK, FITTINGS, AND ACCESSORIES.

4. EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL COORDINATE THE REMOVAL

AND RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR.

CONTRACTOR SHALL CLEAN, INSPECT, AND TEST THERMOSTAT FOR PROPER

OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.

5. EXISTING OUTSIDE AIR INTAKE GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN,

INSPECT, AND TEST EQUIPMENT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND

TO BE DEFECTIVE. ASSUMED 8" CLEAR INSIDE DIAMETER. CONTRACTOR SHALL NOTIFY

ARCHITECT AND ENGINEER IF EXISTING DUCT DOES NOT MAINTAIN REQUIRED FREE

AREA.

6. CONTRACTOR SHALL PERFORM A PRE-TEST OF SUPPLY, RETURN, AND OUTSIDE AIR

CAPABILITIES OF EXISTING AHU-EX-1 AND AHU-EX-2 PRIOR TO START OF ANY

DEMOLITION WORK. PRE-TEST SHALL AT A MINIMUM INCLUDE AIRFLOW VALUES,

ENTERING AIR TEMPS, AND LEAVING AIR TEMPS. PROVIDE REPORT TO ARCHITECT

AND ENGINEER.

7. CONTRACTOR SHALL REMOVE EXISTING EXHAUST FAN, AND ALL ASSOCIATED

DUCTWORK, MOUNTING EQUIPMENT, CONTROLLERS, ETC. COORDINATE THE

REMOVAL OF EXTERIOR WALL CAP TERMINATIONS. CONTRACTOR SHALL PATCH AND

SEAL BUILDING EXTERIOR TO MATCH WHERE EXISTING PENETRATIONS ARE NOT

REUSED.

8. EXISTING CONDENSING UNIT TO REMAIN. CONTRACTOR SHALL TEST AND INSPECT

UNIT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.

CONTRACTOR SHALL INSPECT UNIT MOUNTING EQUIPMENT FOR PROPER OPERATION.

REPLACE HURRICANE CLIPS, MOUNTING PADS, ETC. AS REQUIRED.

NOT ALL KEYNOTES NECESSARILY APPLY

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING A SHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

M2.0

FIRST FLOOR DEMOLITION PLAN

- OFFICE

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

24-015

1/4" = 1'-0"M2.0

1 DEMOLITION FLOOR PLAN - WEST

GUH-EX-2

GUH-EX-1

GEF-EX-1

GENERAL NOTES

A. COORDINATE HVAC DEMOLITION WITH OTHER TRADES

AND GENERAL CONTRACTOR. DO NOT DEMOLISH

EQUIPMENT OR COMPONENTS WITHOUT APPROVAL.

B. PRIOR TO START OF ANY DEMOLITION WORK,

�CONTRACTOR SHALL PRE TEST ALL AIR DEVICES

SCHEDULED TO BE REUSED, EXHAUST FANS, AND AIR

HANDLING UNITS WITHIN THE PROJECT LIMITS. PROVIDE

A REPORT SHOWING AIR FLOWS OF EACH DEVICE TO

ARCHITECT AND ENGINEER.

C. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE

DAMAGE OR REMOVAL IN WHOLE OR IN PART OF ANY

STRUCTURAL MEMBER WITHOUT EXPRESS APPROVAL

OF THE GENERAL CONTRACTOR.

D. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT,

PIPE, OR ELECTRICAL CABLE / CONDUIT THAT RESULTS

FROM DEMOLITION. UNDER NO CIRCUMSTANCE WILL

DEMOLITION RESULT IN THE PERMANENT EXPOSURE OF

ANY CHARGED OR LIVE COMPONENT OF ANY

EQUIPMENT TO BE RE-USED.

E. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT

THEREOF THAT SHALL BE RE-USED.

F. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH

THE GENERAL CONTRACTOR. TURN OVER ANY

COMPONENTS TO THE OWNER AS DESIGNATED IN

CLEAN CONDITION, WITHOUT DAMAGE, AND WITH

OPENING SEALED. FURNISH RECEIPTS OF PROPER

DISPOSAL OF ALL ITEMS REMOVED TO THE GENERAL

CONTRACTOR UPON REQUEST. RECEIPTS SHALL

INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL,

STATE, AND FEDERAL REGULATIONS.

G. PRIOR TO START OF CONSTRUCTION, CONTRACTOR

SHALL PERFORM MAINTENANCE SERVICE TO EXISTING

EQUIPMENT TO BE REUSED IN THE NEW LAYOUT (TO

REMAIN OR TO BE RELOCATED). NOTIFY ARCHITECT,

OWNER, AND ENGINEER OF ANY DEFICIENCY FOUND

DURING PRE CONSTRUCTION MAINTENANCE SERVICE.

KEYNOTES

1. EXISTING GARAGE UNIT HEATER TO REMAIN.

CONTRACTOR SHALL CLEAN, INSPECT, AND TEST UNIT

HEATER FOR PROPER OPERATION. REPAIR OR REPLACE

IN KIND IF FOUND TO BE DEFECTIVE. CONTRACTOR

SHALL CLEAN, INSPECT, AND TEST UNIT HEATER VENT

PIPING FOR DEFECTS, LEAKS, ROOF PENETRATIONS,

ROOF CAPS, ETC. FOR PROPER OPERATION. REPAIR OR

REPLACE VENT PIPING IF FOUND TO BE DEFECTIVE.

2. CONTRACTOR SHALL REMOVE EXISTING LOUVER.

PATCH AND SEAL BUILDING PENETRATIONS AS

REQUIRED FOR NEW WALL MOUNTED EXHAUST FAN

SLEEVE. COORDINATE FINAL CONSTRUCTION AND

FINISH WITH ARCHITECT AND GENERAL CONTRACTOR.

3. CONTRACTOR SHALL REMOVE EXISTING GARAGE

EXHAUST FAN. REMOVE ALL ASSOCIATED MECHANICAL

EQUIPMENT, SUPPORTS, CONTROLS, ETC. COORDINATE

THE REMOVAL OF ELECTRICAL DISCONNECTS, AND ANY

ADDITIONAL ELECTRICAL EQUIPMENT WITH ELECTRICAL

CONTRACTOR.

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING A SHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

M2.1

FIRST FLOOR DEMOLITION PLAN

- APPARATUS BAY

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

24-015

1/4" = 1'-0"M2.1

1 DEMOLITION FLOOR PLAN - EAST

NAPA ROOM

OPEN OFFICE

OFFICE

BREAK ROOM

LOCKER ROOM

RESTROOM

RESTROOM

A

A

A

A

A

A

A 150A

EF-2

EF-1

B

B

A

AHU-EX-1

AHU-EX-2

T

T

A

A

A

B

B

B

16"x12" SA

20"x12" RA

20"x12" SA

20"x12" RA

"x

S A

"x

R

A

"x

S A

"x

S A

"x

R

A

10"ø OA

"ø

O A

20"x12" SA 12"x12" SA

M

M

M 400M

EF-3

X

M

CU-EX-1 CU-EX-2 CU-C1

9 9 8

T

T

6"ø EA

T

U

U

"x

6"ø

EF-6

"ø

E A

U

6"ø EA

JAN.

GENERAL NOTES

A. REFER TO M0.1 GENERAL NOTES AND M0.2 PROJECT SPECIFICATIONS FOR ALL REQUIREMENTS.

B. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS

OTHERWISE NOTED. SEE M0.1 GENERAL NOTES.

C. MECHANICAL DRAWINGS ARE DIAGRAMMATIC. SEE M0.1 GENERAL NOTES.

D. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF INSTALLATION WORK WITH OTHER TRADES TO AVOID CONFLICTS. SEE M0.1 GENERAL NOTES FOR COORDINATION DRAWING REQUIREMENTS.

E. MAINTAIN A 10 FOOT MINIMUM SEPARATION BETWEEN MECHANICAL INTAKE AND BUILDING

EXHAUST AND PLUMBING VENTS.

F. MAINTAIN A 3 FOOT MINIMUM SEPARATION BETWEEN BUILDING EXHAUST AND ANY BUILDING

OPENINGS.

G. ALL EXHAUST WALL CAPS TO BE PROVIDED WITH A FLAPPER-TYPE BACKDRAFT DAMPER AND INLET

SCREEN. REMOVE INLET SCREEN ON DRYER VENT WALL CAPS.

H. ALL DUCT PENETRATIONS THROUGH A ONE-HOUR FIRE-RATED PARTITION SHALL BE PROVIDED

WITH A FIRE DAMPER.

I. ANY DUCTS (EXCEPT DRYER AND RANGE HOOD DUCTS) THAT PENETRATE THE MEMBRANE OF THE RATED FLOOR/CEILING ASSEMBLY SHALL BE PROTECTED WITH A UL LISTED, DYNAMICALLY RATED

CEILING RADIATION DAMPER LISTED FOR THIS SPECIFIC APPLICATION AND INSTALLED IN

ACCORDANCE WITH ITS UL DETAIL.

J. PROVIDE CONDENSATE DRAIN PIPING FROM EACH COIL CONNECTION TO A PLUMBING RECEPTACLE.

CONDENSATE SHALL BE PIPED FULL SIZE AND CONNECTED VIA AN INDIRECT CONNECTION.

CONDENSATE PIPING SHALL BE BY THE MECHANICAL CONTRACTOR.

K. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT.

COORDINATE LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS AND LIGHTING CONTROL

LOCATIONS.

KEYNOTES

1. EXISTING THERMOSTAT TO BE RELOCATED. CONTRACTOR SHALL COORDINATE THE REMOVAL AND

RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR. CONTRACTOR SHALL

CLEAN, INSPECT, AND TEST THERMOSTAT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND

TO BE DEFECTIVE.

2. EXISTING OUTSIDE AIR INTAKE GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN, INSPECT, AND

TEST EQUIPMENT FOR PROPER OPERATION. REPLACE IN KIND IF FOUND TO BE DEFECTIVE.

ASSUMED 8" CLEAR INSIDE DIAMETER. CONTRACTOR SHALL NOTIFY ARCHITECT AND ENGINEER IF

EXISTING DUCT DOES NOT PROVIDE REQUIRED FREE AREA.

3. CONTRACTOR SHALL PERFORM A PRE-TEST OF SUPPLY, RETURN, AND OUTSIDE AIR CAPABILITIES OF EXISTING AHU-EX-1 AND AHU-EX-2 PRIOR TO START OF ANY DEMOLITION WORK. PRE-TEST SHALL AT A MINIMUM INCLUDE AIRFLOW VALUES, ENTERING AIR TEMPS, AND LEAVING AIR TEMPS.

PROVIDE REPORT TO ARCHITECT AND ENGINEER.

4. PROVIDE MOTORIZED DAMPER WITHIN OUTSIDE AIR DUCT. DAMPER SHALL BE FULLY OPEN

WHENEVER COMPRESSOR IS OPERATING IN OCCUPIED MODE. PROVIDE MANUAL DAMPER FOR

BALANCING PURPOSES. PROVIDE ACCESS PANEL FOR DAMPER SERVICE. COORDINATE FINAL

LOCATION OF ACCESS PANEL WITH ARCHITECTS AND GENERAL CONTRACTOR. ALL OUTSIDE AIR

DUCT ROUTED WITHIN THE BUILDING SHALL BE EXTERNALLY INSULATED.

5. PROVIDE WALL LOUVER TERMINATION FOR EXHAUST DUCT, X-VENT-BOX,

SERIES S (OR EQUAL COMPATIBLE WITH EXTERIOR BUILDING CONSTRUCTION)

FOR SINGLE 6" DIAMETER EXHAUST DUCT TERMINATION. COORDINATE FINAL

TERMINATION LOCATION AND BUILDING EXTERIOR CONSTRUCTION WITH

ARCHITECT AND GENERAL CONTRACTOR. FINAL COLOR/FINISH SHALL BE AS SELECTED BY

ARCHITECT. EXHAUST TERMINATION MUST MAINTAIN A MINIMUM DISTANCE OF 10'-0" FROM ALL OA

INTAKES AND 3'-0" FROM ALL BUILDING OPENINGS.

6. PROVIDE WALL LOUVER TERMINATION FOR EXHAUST DUCT, X-VENT-BOX, SERIES S (OR EQUAL

COMPATIBLE WITH EXTERIOR BUILDING CONSTRUCTION) FOR DOUBLE DUCT TERMINATION,

CONSISTING OF (1) 6" DIA EXHAUST DUCT AND (1) 8" DIA EXHAUST DUCT. COORDINATE FINAL

TERMINATION LOCATION, HORIZONTAL/VERTICAL CONFIGURATION, AND BUILDING EXTERIOR

CONSTRUCTION WITH ARCHITECT AND GENERAL CONTRACTOR. FINAL COLOR/FINISH SHALL BE AS SELECTED BY ARCHITECT. EXHAUST TERMINATION MUST MAINTAIN A MINIMUM DISTANCE OF 10'-0"

FROM ALL OA INTAKES AND 3'-0" FROM ALL BUILDING OPENINGS.

7. CONTRACTOR SHALL PROVIDE AHU WITH AIR-PLUS BIPOLAR IONIZATION UNIT MODEL FM-6000 (OR

EQUAL). INSTALL UNIT PER MANUFACTURER INSTALLATION GUIDELINES.

8. CONTRACTOR SHALL MOUNT CONDENSING UNIT ON PREFABRICATED 4" THICK CONCRETE

HOUSEKEEPING PAD. INSTALL UNIT PER 2023 FBC-M WIND LOAD REQUIREMENTS. COORDINATE

FINAL LOCATION WITH ARCHITECT AND GENERAL CONTRACTOR.

9. EXISTING CONDENSING UNIT TO REMAIN. CONTRACTOR SHALL TEST AND INSPECT UNIT FOR

PROPER OPERATION. REPAIR OR REPLACE IN KIND IF FOUND TO BE DEFECTIVE. CONTRACTOR

SHALL INSPECT UNIT MOUNTING EQUIPMENT FOR PROPER OPERATION. REPLACE HURRICANE

CLIPS, MOUNTING PADS, ETC. AS REQUIRED.

10. EXISTING THERMOSTAT TO BE RELOCATED. CONTRACTOR SHALL COORDINATE THE REMOVAL AND

RELOCATION AS REQUIRED WITH ARCHITECT AND GENERAL CONTRACTOR. CONTRACTOR SHALL

PROVIDE ADDITIONAL ACCESSORIES REQUIRED FOR AVERAGING STAT CAPABILITIES.

CONTRACTOR SHALL REPLACE THERMOSTAT IF NOT COMPATIBLE WITH AVERAGING SENSOR

COMPONENTS WITH 7-DAY PROGRAMMABLE THERMOSTAT WITH WIFI COMMUNICATION,

INTERFACE FOR REMOTE CONNECTION, AND ADMINISTRATION VIA WEB OR PHONE APP, AND THE

ABILITY TO COMMUNICATE WITH AVERAGING SENSORS.

11. APPROXIMATE LOCATION OF REMOTE AVERAGING TEMPERATURE SENSOR. COORDINATE FINAL

LOCATION WITH ARCHITECT AND GENERAL CONTRACTOR.

12. ROUTE 6" ROUND EXHAUST DUCT UP THROUGH ROOF. SEAL ROOF PENETRATION WEATHER-

TIGHT. TERMINATE MINIMUM 12" ABOVE ROOF WITH RAINCAP PER 2023 FBC-M WIND LOAD

REQUIREMENTS. FINAL DISCHARGE LOCATION SHALL BE MINIMUM 10'-0" FROM ALL OA INTAKES.

NOT ALL KEYNOTES NECESSARILY APPLY

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING…