Genesis_Engineering_Electrical_Plans.pdf

PDF 2 MB Posted

Attached to
South County Fleet Renovation
Solicitation number
262899MKM
Issued by
Sarasota County, Florida

About this file

This is an electrical plans document prepared by Genesis Engineering for Sarasota County's South County Fleet Renovation project in Florida. The document provides detailed electrical system designs and specifications for the renovation and improvement of the existing South County Fleet maintenance and support facilities. The plans outline the electrical infrastructure requirements necessary to support the modernized fleet maintenance operations, including power distribution systems, lighting design, control systems, and equipment connections throughout the facility. The electrical plans serve as technical guidance for contractors bidding on the construction project and establish the baseline requirements for electrical installation and compliance with applicable building codes and safety standards.

The electrical plans document functions as a supporting exhibit to the invitation for bids solicitation, providing contractors with the detailed technical specifications required to develop accurate cost estimates and construction schedules. These plans are essential for contractors to understand the scope of electrical work involved in the renovation project and to ensure compliance with all electrical code requirements and the County's specifications during the bidding and construction phases.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

S

S

S

S

TV

DR

AD

SP

IC

S

D

H

F

F

F

DH

FS

TS

FR

MM

FACP

FAAP

SD

PS

C

NAC

KNO

B

S

ML

KP

CR

MD

CAM

P

P

TELEPHONE/DATA/COMMUNICATION

TELEPHONE OUTLET. #V SUBSCRIPT INDICATE NUMBER OF

DATA AND TELEPHONE JACKS. IF NO SUBSCRIPTS ARE

GIVEN, PROVIDE BLANK COVERPLATE.

MOUNT AT 18" AFF, UNO

DATA RACK (REFER TO RISER, AND/OR SPECIFICATIONS FOR

TYPE)

CABLE TELEVISION OUTLET MOUNT AT 18" AFF, UNO

PUSHBUTTON (SUBSCRIPT INDICATES TYPE)

EPO - EMERGENCY POWER OFF

DB - DOOR BELL

HC - DOOR OPENER

AUDIBLE/VISUAL DOORBELL CHIME

MOUNT AT 46" AFF, UNO

MOUNTING HEIGHT PER ADA

SPEAKER

SYMBOL DESCRIPTION REMARKS

#V

WIRELESS ACCESS POINTW

DATA OUTLET. #D SUBSCRIPT INDICATE NUMBER OF DATA

AND TELEPHONE JACKS. IF NO SUBSCRIPTS ARE GIVEN,

PROVIDE BLANK COVERPLATE.

MOUNT AT 18" AFF, UNO

#D

TELEPHONE/DATA OUTLET. #D #V SUBSCRIPT INDICATE

NUMBER OF DATA AND TELEPHONE JACKS. IF NO

SUBSCRIPTS ARE GIVEN, PROVIDE BLANK COVERPLATE.

MOUNT AT 18" AFF, UNO

#D#V

INTERCOM STATION

J

POWER - BRANCH DEVICES

SYMBOL DESCRIPTION REMARKS

DUPLEX RECEPTACLE

DUPLEX RECEPTACLE

MOUNT AT 18" AFF, UNO

MOUNT ABOVE COUNTER, UNO

MOUNT HORIZONTAL FOR ADA

TWO DUPLEX RECEPTACLES MOUNTED IN COMMON BOX MOUNT AT 18" AFF, UNO

MOUNT AT 18" AFF, UNOSPECIAL PURPOSE RECEPTACLE, SUBSCRIPT INDICATES TYPE

JUNCTION BOX OR OUTLET BOX

MOUNT AT 18" AFF, UNOSIMPLEX RECEPTACLE

RECEPTACLE(S) IN RECESSED FLOOR BOX

CEILING MOUNTED RECEPTACLE(S)

POWER - DISTRIBUTION

PANELBOARD (FLUSH-MOUNTED)

PANELBOARD (SURFACE-MOUNTED)

TRANSFORMER

AUTOMATIC TRANSFER SWITCH

MANUAL TRANSFER SWITCH

DISCONNECT SWITCH (NON-FUSED)

DISCONNECT SWITCH (FUSED)

MANUAL MOTOR STARTER

MAGNETIC MOTOR STARTER

COMBINATION MAGNETIC MOTOR STARTER/DISCONNECT

VARIABLE FREQUENCY DRIVE (VFD)

MOTOR

GENERATOR

SYMBOL

G

T

ATS

MTS

MS

VFD

DESCRIPTION REMARKS

SYMBOL

CIRCUIT BREAKER

FUSE

DISCONNECT SWITCH (NON-FUSED)

DISCONNECT SWITCH (FUSED)

ONE-LINE/RISER

TRANSFER SWITCH

TRANSFORMER

PANELBOARD

METER (SELF CONTAINED)

GENERATOR

GROUND CONNECTION

MOTOR (NUMBER INDICATES HORSEPOWER)#

G

METER (WITH CURRENT TRANSFORMERS)M

M

CONTINUATION

DESCRIPTION REMARKS

SYMBOL

KEYED DRAWING NOTE

REMOVALS

CIRCUIT

BASIC DRAWING

DESCRIPTION REMARKS

SYMBOL

LINE WEIGHT & LINE TYPE DESIGNATIONS

EXISTING (UNLESS OTHERWISE INDICATED)

PROVIDE AS NEW (UNLESS OTHERWISE INDICATED)

DESCRIPTION REMARKS

FIRE ALARM

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

SMOKE DETECTOR

HEAT DETECTOR

DUCT SMOKE DETECTOR

STROBE NOTIFICATION DEVICE

COMBINATION HORN/STROBE NOTIFICATION DEVICE

MANUAL PULL STATION

DOOR HOLD-OPEN DEVICE

WATER FLOW DETECTION SWITCH

TAMPER SWITCH

FIRE ALARM RELAY

MONITOR MODULE

SMOKE DAMPER

PRESSURE SWITCH

CARBON MONOXIDE DETECTOR

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL

KNOX BOX

SYMBOL

LIGHT FIXTURE

LIGHT FIXTURE

LIGHT FIXTURE

WALL MOUNTED

CEILING MOUNTED

CEILING MOUNTED

WALL MOUNTEDLIGHT FIXTURE

EXIT LIGHT (HATCHING/ARROW INDICATES FACE/DIRECTION)

EMERGENCY BATTERY PACK LIGHT FIXTURE

CEILING MOUNTED

WALL MOUNTED

EXIT LIGHT (HATCHING/ARROW INDICATES FACE/DIRECTION) WALL MOUNTED

SINGLE POLE SWITCH

SINGLE POLE SWITCH (3-WAY)

SINGLE POLE SWITCH (DIMMER)

MOUNT AT 48" AFF, UNO

MOUNT AT 48" AFF, UNO

MOUNT AT 48" AFF, UNO

MOUNT AT 48" AFF, UNO

OCCUPANCY SENSOR (SUBSCRIPT INDICATES TYPE)

POWER PACK

OS

SITE LIGHT FIXTURE POLE MOUNTED

PP

PC

D

DESCRIPTION REMARKS

OS

CEILING MOUNTED

OCCUPANCY SENSOR/WALL SWITCH (SUBSCRIPT

INDICATES TYPE)

EMERGENCY LIGHT FIXTURE

EMERGENCY LIGHT FIXTURE

EMERGENCY LIGHT FIXTURE

EMERGENCY LIGHT FIXTURE

WALL MOUNTED

CEILING MOUNTED

CEILING MOUNTED

WALL MOUNTED

FIRE PROTECTION ALARM BELL

PHOTOCELL

LIGHT FIXTURE CEILING MOUNTED

EMERGENCY LIGHT FIXTURE CEILING MOUNTED

LIGHT FIXTURE CEILING MOUNTED

EMERGENCY LIGHT FIXTURE CEILING MOUNTED

TELEPHONE BACKBOARD (TBB) SEE PLANS

SEE DETAIL ON PLANSGROUNDING BUSBAR

SINGLE POLE SWITCH (LOW VOLTAGE) MOUNT AT 48" AFF, UNOLV

PS PARTITION SENSORPS

MANUAL PULL STATION (POLICE ALERT SYSTEM)

COMBINATION HORN/STROBE NOTIFICATION DEVICE

(POLICE ALERT SYSTEM)

FBO

FBO

PL PLUG LOAD CONTROLLER

AMPERE(S)A

ALTERNATING CURRENTAC

ARC-FAULT CIRCUIT INTERRUPTERAFCI

ABOVE FINISHED FLOORAFF

AMERICAN WIRE GAUGEAWG

ABOVE FINISHED GRADEAFG

AUTHORITY HAVING JURISDICTIONAHJ

AMERICAN NATIONAL STANDARDS

INSTITUTE

ANSI

AUTOMATIC TRANSFER SWITCHATS

BUILDINGBLDG

CONDUITC

CIRCUIT BREAKERCB/CKT BKR

CLOSETCL

CEILINGCLG

CONCRETECONC

CONDUCTORCOND

CIRCUITCKT

CONDUIT ONLYCO

CONSTRUCTIONCONST

CONTROL PANELCP

CURRENT TRANSFORMERCT

COPPERCU

DEDICATEDDED

DISCONNECTDISC

DIVISIONDIV

DRAWINGDWG

EACHEA

ELECTRICAL CONTRACTOREC

ELECTRICELEC

EMERGENCYEM/EMER

EXISTINGEX/EXIST

FUSEF

FIRE ALARMFA

FURNISHED BY OTHERSFBO

FEEDERFDR

FULL LOAD AMPSFLA

FEETFT

GROUNDG/GND

GROUND FAULT INTERRUPTERGFI

HUNG CEILINGHC

HAND-OFF-AUTO SELECTOR SWITCHHOA

HORSEPOWERHP

KAIC 1000 AMPERE INTERRUPTING

CAPACITY

KCMIL 1000 CIRCULAR MIL(S)

KVA KILOVOLT AMPERE(S)

KW KILOWATT(S)

LIGHTINGLTG

MAIN CIRCUIT BREAKER

MCA MINIMUM CIRCUIT AMPACITY

MCB

MISCELLANEOUSMISC

MINIMUMMIN

MANUFACTURERMFR

MOUNTING HEIGHTMH

MOUNTEDMTD

NEUTRALN

NORMALLY CLOSEDNC

NATIONAL ELECTRIC CODENEC

NATIONAL FIRE PROTECTION

ASSOCIATION

NFPA

NIGHT LIGHTNL

NORMALLY OPENNO

NOT TO SCALENTS

POLEP

PULL BOXPB

PHASEPH/Ø

PANELPNL

PRIMARYPRI

POWERPWR

QUANTITYQTY

RECEPTACLEREC/RECEPT

SECONDARYSEC

SPECIFICATIONSPEC

SWITCHSW

TELEPHONETEL

TYPICALTYP

UNDERGROUNDUG

UNDERWRITER'S LABORATORIESUL

UNLESS NOTED OTHERWISEUNO

UNLESS OTHERWISE NOTEDUON

UNINTERRUPTIBLE POWER SUPPLYUPS

ULTRAVIOLETUV

VOLT(S)V

VOLTAMPERE(S)VA

VARIABLE FREQUENCY DRIVEVFD

WATT(S)W

WEATHERPROOFWP

DISHWASHERDISH

DISPOSALDISP

REFRIGERATORREF

AMERICANS WITH DISABILITIES ACTADA

MECHANICAL CONTRACTORMC

GENERAL CONTRACTORGC

INFRAREDIR

DUAL TECHNOLOGY (IR/US)DT

ULTRASONICUS

LIGHT EMITTING DIODELED

EQUIPMENT GROUNDINGEGC

EQUIPMENTEQUIPT

CONDUCTOR

SURGE PROTECTION DEVICESPD

WEATHER RESISTANCEWR

BELOW FINISHED GRADEBFG

LOW VOLTAGELV

FLORIDA BUILDING CODEFBC

REMOTE GEN ANNUNCIATORRGA

GENERATORGEN

AUTOMATIC DOOR OPENERADO

PROPOSEDPROP.

PLUG LOADPL

JUNCTION BOXJB

BI-DIRECTIONAL AMPLIFIERBDA

USB RECEPTACLE COMBOUSB/C

EXISTING TO BE RELOCATEDERL

RELOCATEDREL

LIGHTING (LETTER INDICATES TYPE, REFER TO LUMINAIRE SCHEDULE FOR ADDITIONAL INFORMATION)

SYMBOL DESCRIPTION REMARKS

MULTI-ROOM CIRCUIT

INVERTER CIRCUIT

1. THE GENERAL NOTES APPLY TO ALL DRAWINGS UNDER THIS CONTRACT. REFER TO INDIVIDUAL DRAWINGS FOR

ADDITIONAL NOTES.

2. ALL ELECTRICAL WORK SHOWN SHALL BE PROVIDED AS NEW UNLESS OTHERWISE NOTED.

3. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW

DRAWING IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS.

MAINTAIN HEADROOM AND SPACE CONDITIONS. BRANCH CIRCUIT NUMBERS ARE FOR REFERENCE ONLY.

CONTRACTOR SHALL DETERMINE THE CIRCUIT NUMBERS AND PROVIDE A SCHEDULE IN PANEL IDENTIFYING

BRANCH CIRCUITS.

4. JUNCTION AND PULL BOXES SHALL GENERALLY BE LOCATED FOR FLUSH MOUNTING IN FINISHED SPACES.

WHERE NECESSARY, CONDUITS SHALL BE REROUTED OR OTHER ARRANGEMENTS MADE FOR CONCEALMENT.

PULL BOXES SHALL BE PROVIDED AS INDICATED AND WHEREVER NECESSARY TO FACILITATE PULLING OF WIRE

AND COORDINATE LOCATIONS WITH OTHER TRADES. COVERS OF JUNCTION AND PULL BOXES SHALL BE

ACCESSIBLE. FOR EMPTY RACEWAY RUNS, PULL BOXES SHALL BE PROVIDED EVERY 100 FEET AND AS

INDICATED OR NECESSARY.

5. BOXES SHALL BE SET SQUARE AND TRUE WITH BUILDING FINISH. WALL AND SWITCH OUTLETS SHALL BE

ERECTED IN ADVANCE OF FURRING AND FIREPROOFING. BOXES SHALL BE SECURED TO BUILDING STRUCTURE

BY ADJUSTABLE STRAP IRONS.

6. IN EXISTING BUILDINGS, ALL REQUIRED ACCESS DOORS SHALL BE FURNISHED AND INSTALLED UNDER THE

ELECTRICAL SECTION. ALL ACCESS DOOR LOCATIONS SHALL BE FIELD COORDINATED WITH THE OWNER.

7. NO ELECTRICAL RACEWAYS OR CONDUCTORS SHALL BE INSTALLED WITHIN 3 INCHES OF STEAM OR HOT

WATER PIPES, OR APPLIANCES, EXCEPT FOR CROSSING WHERE RACEWAYS SHALL BE AT LEAST 1 INCH FROM

PIPE COVER.

8. SUFFICIENTLY LONG WIRE SLACK SHALL BE LEFT IN RUNS TO ALLOW FOR MAKING PROPER FINAL

CONNECTIONS. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH #12 AWG STEEL DRAG WIRES.

9. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL HVAC EQUIPMENT. (AC UNITS, FANS, VAV

BOXES, ETC).

10. REFER TO PLUMBING DRAWINGS FOR EXACT LOCATION OF ALL PLUMBING EQUIPMENT.

11. ALL WIRING SHALL BE ROUTED IN AN ORGANIZED AND NEAT MANNER.

12. SUBMIT DIMENSIONED LAYOUTS OF ALL ELECTRIC EQUIPMENT WITH EQUIPMENT SUBMITTALS.

13. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL RACEWAYS RUNS WITH EXISTING

CONDITIONS AND INCLUDE ALL PULLBOXES, OFFSETS, CUTTING, PATCHING, PAINTING TO MATCH EXISTING, SUPPORTS, ETC. AS REQUIRED.

14. THE ROUTING AND LOCATION OF CONDUIT RUNS ARE GENERALLY NOT DIMENSIONAL ON THE DRAWINGS BUT

SHALL BE DETERMINED IN THE FIELD TO SUIT THE LOCATIONS OF EQUIPMENT, TO CONFORM TO STRUCTURAL

AND ARCHITECTURAL FEATURES AND TO AVOID INTERFERENCES.

15. ALL CUTTING AND RESTORATION OF SLAB AND FLOOR SHALL BE IN ACCORDANCE WITH STRUCTURAL

ENGINEER'S REQUIREMENTS AND AS APPROVED BY ENGINEER.

16. ELECTRICAL CONTRACTOR SHALL VERIFY ALL PENETRATIONS, POKE THRUS, AND EXISTING CONDUIT

LOCATIONS PRIOR TO MODIFICATION.

17. ALL SIGHT EXPOSED ELECTRICAL DEVICES SHALL BE LOCATED AS PER ARCHITECT'S DRAWINGS AND/OR

DIRECTION.

18. WHERE CONDUIT OR JUNCTION BOXES ARE RUN IN SLAB, THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR

ALL CUTTING, PATCHING, AND RESTORATION OF SLAB AND FLOOR.

19. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL LIGHT FIXTURES, REMOTE BALLASTS AND

ASSOCIATED WIRING, SUPPORTS, HARDWARE, AND ACCESSORIES AS REQUIRED.

20. SYMBOLS AND LEGENDS SHOWN ON THIS DRAWING ARE FOR ELECTRICAL DRAWINGS ONLY. SEE

ARCHITECTURAL DRAWINGS AND TRADE DRAWINGS FOR RESPECTIVE SYMBOLS AND LEGENDS.

21. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL SLAB CUTS, FOUNDATION WALL

PENETRATIONS, WALL OPENINGS, CORE DRILLING, ROOF PENETRATIONS, ETC. AND PATCHING AS REQUIRED

TO PROVIDE ALL ELECTRICAL WORK. FOR FOUNDATION WALL PENETRATIONS PROVIDE 4"X4"X3/8" WELDED

STEEL ANGLE BY THE CONTRACTOR AND APPROVED BY THE STRUCTURAL ENGINEER AND PROVIDE WATER

PROOFING . ALL ROOF, TUNNEL AND FOUNDATION PENETRATIONS SHALL BE WATER PROOFED. COORDINATE

WORK SO AS TO MAINTAIN ANY AND ALL WARRANTIES FOR ROOF SYSTEMS, FOUNDATIONS, ETC.

22. ALL TELEPHONE/DATA RACEWAYS SHALL BE PROVIDED WITH INSULATED END BUSHINGS.

23. SEPARATE RACEWAYS SHALL BE PROVIDED FOR CONDUCTORS OF NORMAL AND EMERGENCY CIRCUITS.

24. HORIZONTAL OR CROSS RUNS IN PARTITIONS OR WALLS ARE NOT PERMITTED.

25. THE ELECTRICAL CONTRACTOR SHALL NOT INSTALL MORE THAN THE NUMBER OF CIRCUITS SHOWN IN ANY

HOMERUN CIRCUIT.

26. CONTRACTOR TO PROVIDE FIRE PROOFING AT ALL PENETRATIONS OF RATED PARTITIONS, FLOORS, AND

WHERE THE EXISTING FIRE PROOFING WAS REMOVED TO EXPOSE EXISTING STEEL FOR NEW HANGER

INSTALLATION. REFER TO SPECIFICATION SECTION FIRE PROOFING.

27. LOCATIONS INDICATED FOR LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS, INSTALL SWITCH ON SIDE OPPOSITE HINGE (VERIFY FINAL DOOR HINGE LOCATION IN FIELD PRIOR TO SWITCH

OUTLET INSTALLATION).

28. EXACT LOCATION OF LIGHTING FIXTURES SHALL BE IN ACCORDANCE WITH ARCHITECTURAL REFLECTED

CEILING PLAN OR AS DIRECTED BY THE ARCHITECT.

29. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL CEILING WORK WITH CEILING CONTRACTOR AND

DETERMINE CEILING TYPE PRIOR TO THE PURCHASING AND INSTALLATION OF LIGHTING FIXTURES, SPEAKERS, SMOKE DETECTORS, EXIT LIGHTS, OR ANY OTHER CEILING MOUNTED ELECTRICAL ELEMENTS. THE ELECTRICAL

CONTRACTOR SHALL ALSO COORDINATE ALL ELECTRICAL WORK WITH LOCATION OF DIFFUSERS AND

SPRINKLERS AND OTHER MECHANICAL WORK.

30. EXACT LOCATION AND MOUNTING OF LIGHTING FIXTURES IN MECHANICAL AREAS SHALL BE COORDINATED

WITH THE MECHANICAL TRADES TO AVOID CONFLICT WITH PIPING, DUCTS AND EQUIPMENT. IN GENERAL, THE

FINAL LOCATION OF LIGHTING FIXTURES SHALL BE GOVERNED BY THE NEED OF TASK LIGHTING IN THE VICINITY

OF PANEL BOARDS, MOTOR CONTROLS, CONTROL AND INSTRUMENT PANELS AND GAUGES.

31. LOCATIONS OF OUTLETS AND SWITCHES IN FINISHED ROOMS SHALL BE VERIFIED WITH ARCHITECTURAL

DRAWINGS OF INTERIOR DETAILS AND FINISHES. IN CENTERING OUTLETS AND LOCATING BOXES AND OUTLETS, ALLOW FOR OVERHEAD PIPES, DUCTS AND MECHANICAL EQUIPMENT, VARIATIONS IN FIREPROOFING AND

PLASTERING, WINDOW AND DOOR TRIMS, PANELING, SUSPENDED CEILINGS AND THE LIKE. CORRECT ANY

INACCURACY RESULTING FROM FAILURE TO DO SO WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER.

32. ALL RACEWAYS, WIRING, AND ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE ROUTED CONCEALED EXCEPT IN

UNFINISHED AREAS.

33. ALL EQUIPMENT, MATERIALS, ETC. SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL. REFER TO

SPECIFICATIONS FOR ADDITIONAL ACTION SUBMITTAL AND SHOP DRAWING REQUIREMENTS.

34. PRIOR TO CONSTRUCTION, COORDINATE WITH LOCAL AHJ THE UL CONDITIONAL LISTING REQUIREMENTS FOR

ALL JUNCTIONS BOXES UTILIZED IN RATED WALLS AND CEILINGS.

35. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN THESE DRAWINGS OR BETWEEN

INFORMATION PROVIDED IN THESE DRAWINGS AND THE PROJECT SPECIFICATIONS OR WITHIN THE PROJECT

SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST COST REQUIREMENTS SHALL APPLY. SHOULD THE

CONTRACTOR REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR CLARIFICATION. WHERE

CONFLICTS DO EXIST, THE PROJECT ENGINEER OF RECORD SHALL HAVE THE SOLE DISCRETION AND RIGHT TO

PROVIDE INTERPRETATION OF INTENT OF THE CONTRACT DOCUMENTS AS REQUIRED AND THIS

INTERPRETATION SHALL SERVE TO DIRECT THE CONTRACTOR IN ACCORDANCE WITH THE IMPLIED INTENT OF

THE CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE PROJECT.

36. ALL VALUE ENGINEERING OR DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE SUBMITTED IN

WRITING TO THE DESIGN TEAM FOR APPROVAL. ANY COST INCURRED AS A RESULT OF ANY DEVIATIONS FROM

THE BASIS OF DESIGN INDICATED IN THE CONTRACT DOCUMENTS (E.G. ELECTRICAL MODIFICATIONS TO

ACCOMMODATE ALTERNATE EQUIPMENT SELECTIONS, DESIGN RELATED EXPENSES FOR REQUIRED DRAWING

MODIFICATIONS, ETC)SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. NO INCREASE IN CONTRACT

COST WILL BE GRANTED UNLESS BORNE BY AND APPROVED IN WRITING BY THE OWNER. CONTRACT

DOCUMENTS ARE DEFINED TO INCLUDE ALL DISCIPLINES AND DIVISIONS OF THE CONTRACT.

SYMBOL

SECURITY/ACCESS CONTROL

DOOR CONTACT

MOTION DETECTOR

CARD READER

KEY PAD

DOOR STRIKE

MAGNETIC LOCK

COMBINATION HORN/STROBE NOTIFICATION DEVICE

DS

DC

DESCRIPTION

CCTV CAMERA (SUBSCRIPT INDICATES TYPE)

SCOPE OF WORK SHALL BE RACEWAY ONLY. FOR EACH WALL DEVICE LOCATION, PROVIDE

RECESSED WALL-BOX AND 3/4" CONDUIT STUB WITH PULL STRING TO ACCESSIBLE ABOVE CEILING

SPACE. FOR EACH CEILING DEVICE LOCATION, PROVIDE RECESSED CEILING BOX AND 3/4" CONDUIT

TO NEAREST ACCESSIBLE ABOVE-CEILING SPACE. DEVICES, CABLING, EQUIPMENT, ETC. PROVIDED

BY OTHERS.

BEFORE FINAL INSPECTION A FACTORY CONTROL CONSULTANT SHALL PROVIDE EVIDENCE THAT

LIGHTING CONTROLS HAVE BEEN TESTED, CALIBRATED, ADJUSTED, PROGRAMMED AND ARE IN

WORKING CONDITION.

• TEST OCCUPANCY SENSORS.

• TEST AUTO TIME SWITCH.

• TEST DAYLIGHT RESPONSIVENESS.

PROVIDE OWNER DOCUMENTS CERTIFYING LIGHTING CONTROLS MEET PERFORMANCE CRITERIA

WITHIN 90 DAYS AFTER CERTIFICATE OF OCCUPANCY.

SCOPE OF WORK SHALL BE RACEWAY ONLY. FOR EACH WALL DEVICE LOCATION, PROVIDE RECESSED WALL-BOX AND 1" CONDUIT STUB WITH PULL STRING TO ACCESSIBLE ABOVE CEILING SPACE. FOR EACH CEILING DEVICE LOCATION, PROVIDE RECESSED CEILING BOX AND 1" CONDUIT TO NEAREST ACCESSIBLE ABOVE-CEILING SPACE. DEVICES, CABLING, EQUIPMENT, ETC. PROVIDED BY OTHERS.

ELECTRICAL SYMBOL LEGEND GENERAL NOTES KEY CODES AND STANDARDS

LIGHTING SYSTEM FUNCTIONAL TESTING

ABBREVIATIONS

IEEE-C2, 2017 EDITION, NATIONAL ELECTRICAL SAFETY CODE (NESC)

NFPA 70, 2020 EDITION, NATIONAL ELECTRICAL CODE (NEC)

NFPA 70E, 2021 EDITION, STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE

NFPA 101A, 2022 EDITION, GUIDE ON ALTERNATIVE APPROACHES TO LIFE SAFETY

NFPA 70B, 2019 EDITION, RECOMMENDED PRACTICE FOR ELECTRICAL EQUIPMENT

MAINTENANCE

UL 467, 10TH EDITION, 2017, GROUNDING AND BONDING EQUIPMENT

OTHER PUBLICATIONS AND CODE COMPLIANCE:

IN ADDITION TO THE CODES AND STANDARDS LISTED ABOVE, ALL ELECTRICAL WORK SHALL

COMPLY WITH THE APPLICABLE REQUIREMENTS OF THE LATEST EDITION OF THE STANDARDS

OF THE NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA); INSULATED POWER

CABLE ENGINEER'S ASSOCIATION (IPCEA); AND ALL APPLICABLE FEDERAL, STATE, CITY, AND

LOCAL CODES, REGULATIONS, ORDINANCES, PUBLICATIONS AND MANUALS. ALL NEW

MANUFACTURED EQUIPMENT, DEVICES, ETC. SHALL BE LISTED BY THE UNDERWRITER'S

LABORATORY (UL).

NFPA 110, 2022 EDITION, STANDARD FOR EMERGENCY & STANDBY POWER SYSTEMS

NFPA 72, 2019 EDITION, NATIONAL FIRE ALARM AND SIGNALING CODE

RULE CHAPTER 69A-60, THE FLORIDA FIRE PREVENTION CODE

FBC 2023, 8TH EDITION, CHAPTER 35, FLORIDA BUILDING CODE-BUILDING

NFPA 75, 2020 EDITION, STANDARD FOR THE FIRE PROTECTION OF

NFPA 90A, 2021 EDITION, STANDARD FOR THE INSTALLATION OF AIR-

INFORMATION TECHNOLOGY EQUIPMENT`

CONDITIONING AND VENTILATING SYSTEMS

2020 RULE 69A-3.012, STANDARDS OF THE NATIONAL FIRE PROTECTION

ASSOCIATION AND OTHER STANDARDS ADOPTED

FLORIDA STATE FIRE MARSHAL RULE (EFFECTIVE DATE - DECEMBER 31, 2023):

2023 8TH EDITION - FLORIDA FIRE PREVENTION CODE

NFPA 101, 2021 EDITION, LIFE SAFETY CODE

NFPA 1, 2018 EDITION, THE FIRE CODE

SECTIONS 633.206(1)(a) AND (b), F.S.:

(a) NFPA 2, 2020 EDITION, HYDROGEN TECHNOLOGIES CODE

(b) NFPA 3, 2021 EDITION, RECOMMENDED PRACTICE FOR COMMISSIONING OF

FIRE PROTECTION AND LIFE SAFETY SYSTEMS

FBC 2023, 8TH EDITION, FLORIDA BUILDING CODE ENERGY CONSERVATION

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY DANIEL MARK SCHAFRAN, PE.

ON THE DATE ADJACENT TO THE SEAL USING A

SHA AUTHENTICATION CODE. PRINTED COPIES

OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA

AUTHENTICATION CODE MUST BE VERIFIED ON

ANY ELECTRONIC COPIES.

G

STATE OF

No. 84419

ROL

F A

DI

EL

I C E N S

NAL EN

I N

P R O F E

S I O

S

E E R

DA

NI

EL

MA SCHAFRAN

RK

E0.1

LEGENDS AND GENERAL NOTES

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

PERMIT

24-015

BASIC REQUIREMENTS

1. GENERAL

1.A. GENERAL CONTRACT PROVISIONS APPLY TO THE WORK OF THIS SECTION.

1.B. CODE: COMPLY WITH THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE (NEC), ALL GOVERNING

BUILDING CODES AND ENERGY CODES, NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),

UNDERWRITER'S LABORATORIES (UL), AUTHORITIES HAVING JURISDICTION (AHJ), AND ALL APPLICABLE

RULES AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES .

1.C. PROVIDE ALL NECESSARY PERMITS, LICENSES, INSPECTIONS AND APPROVALS AS REQUIRED BY THE

UTILITY COMPANY AND LOCAL AHJ. CONTRACTOR IS RESPONSIBLE FOR PAYING ALL ASSOCIATED AND

REQUIRED FEES IN CONNECTION WITH THE WORK OF THIS CONTRACT.

1.D. ALL ELECTRICAL MATERIALS, EQUIPMENT, APPLIANCES, ETC. SHALL HAVE THE LISTING OF THE

UNDERWRITER'S LABORATORIES, INC., AND SHALL BE TYPES APPROVED BY LOCAL AUTHORITIES HAVING

JURISDICTION.

2. UTILITY COORDINATION

2.A. COMPLY WITH THE REQUIREMENTS OF THE LOCAL UTILITY COMPANY AND PERFORM ALL REQUIRED

COORDINATION WITH UTILITY PRIOR TO PERFORMING WORK.

2.B. PROVIDE ALL EQUIPMENT AS REQUIRED BY UTILITY COMPANY AND IN COMPLIANCE WITH ALL UTILITY

COMPANY REQUIREMENTS AND REGULATIONS.

2.C. COORDINATE WITH ALL OTHER TRADES AND CONTRACTORS IN RELATION TO UTILITY COMPANY

REQUIREMENTS AND INSTALLATIONS.

2.D. CONTRACTOR SHALL COORDINATE NEW SERVICE WITH THE UTILITY CO., AS FOLLOWS:

2.D.A. SERVICE WIRING

2.D.B. SUPPLY AND INSTALL WATT HOUR METERS.

2.D.C. FINAL CONNECTIONS TO METERING EQUIPMENT.

2.D.D. ARRANGE WITH THE UTILITY CO FOR SERVICE FACILITIES AND PAY ALL CHARGES.

2.D.E. EXTEND SERVICE FROM UTILITY CO TERMINATIONS.

2.D.F. INSTALLATION OF UTILITY CO. CURRENT TRANSFORMERS.

2.D.G. PROVIDE METERING ENCLOSURES AND METER PANS.

2.D.H. METER WIRING EXCEPT FINAL CONNECTIONS.

2.D.I. OBTAIN UTILITY CO APPROVAL FOR ALL ELECTRIC SERVICE WORK AND SERVICE

EQUIPMENT SHOP DRAWINGS.

2.D.J. PROVIDE ALL ASSOCIATED INSTALLATION COMPONENTS AND ACCESSORIES.

2.E. CONTRACTOR SHALL EXAMINE THE LOCATION WHERE SERVICE EQUIPMENT AND RACEWAYS ARE TO BE

INSTALLED, DETERMINE SPACE REQUIREMENTS AND NOTIFY THE ARCHITECT/ENGINEER IN WRITING OF

THE CONDITIONS DETRIMENTAL TO PROPER AND TIMELY COMPLETION OF THE WORK

3. WORK INCLUDED

3.A. UNLESS NOTED AS EXISTING OR PROVIDED BY OTHERS, CONTRACTOR SHALL PROVIDE ALL WORK AND

MATERIALS SHOWN ON DRAWINGS AND INDICATED WITHIN THESE SPECIFICATIONS.

3.B. ALL MATERIALS PROVIDED SHALL BE NEW AND UNUSED.

3.C. THESE SPECIFICATIONS AND ACCOMPANYING DRAWINGS ARE INTENDED TO SECURE THE PROVISIONS

OF ALL MATERIAL AND LABOR NECESSARY FOR THE COMPLETE INSTALLATIONS, TESTED AND READY

FOR SERVICE, TOGETHER WITH COMPLETE ELECTRICAL WORK AS CALLED FOR HEREIN AND AS

INDICATED ON THE DRAWINGS. WHEN CONFLICTS OCCUR IN THE SPECIFICATIONS OR ON THE

DRAWINGS, OR BETWEEN EITHER, THE ITEMS OF GREATER QUANTITY OR HIGHER COST SHALL BE

PROVIDED.

3.D. PROVIDE A COMPLETE WIRING SYSTEMS FOR LIGHTING AND POWER INSTALLATION, HVAC, PLUMBING

AND SPRINKLER SYSTEMS AND MISCELLANEOUS DEVICES.

3.E. A GENERAL DESCRIPTION OF THE ELECTRICAL WORK I NCLUDES, BUT IS NOT LIMITED TO THE

FOLLOWING:

3.E.A. RELOCATION AND/OR REMOVAL OF EXISTING ELECTRICAL WORK IN ACCORDANCE WITH

DEMOLITION SCHEME, OR AS DIRECTED AND REQUIRED. RESTORATION OF ELECTRICAL

SERVICE IN AFFECTED ADJOINING AREAS WHICH ARE TO CONTINUE TO FUNCTION.

3.E.B. REMOVAL AND/OR REINSTALLATION OF EXISTING CONSTRUCTION (CEILINGS, LIGHTING, ELECTRICAL EQUIPMENT, FIRE ALARM DEVICES, FURNISHINGS, ETC.) AS NECESSARY TO

COMPLETE THE REMOVALS AND RENOVATION WORK REQUIRED BY THE DRAWINGS AND

SPECIFICATIONS. REPLACE ANY ITEMS DAMAGED BY OR DUE TO THIS REMOVAL AND

REINSTALLATION WITH NEW ITEMS TO MATCH EXISTING.

3.E.C. TEMPORARY LIGHT AND POWER FOR CONSTRUCTION PURPOSES.

3.E.D. ELECTRICAL SERVICE INSTALLATION.

3.E.E. BRANCH CIRCUIT WIRING, SWITCHES, RECEPTACLES, TELEPHONE AND SIGNAL OUTLETS , AND ALL ASSOCIATED RACEWAYS. UNLESS NOTED OTHERWISE, WIRING, CONDUIT

ROUTING, RACEWAYS, ETC. SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS, IN WALLS,

OR BENEATH FINISHED FLOORS IN ALL FINISHED SPACES. UNLESS NOTED OTHERWISE,

DEVICES SHALL BE FLUSH MOUNTED IN ALL FINISHED SPACES.

3.E.F. LIGHTING FIXTURES AND LAMPS.

3.E.G. POWER WIRING TO MECHANICAL EQUIPMENT.

3.E.H. CUTTING AND ROUGH PATCHING REQUIRED TO PERFORM ELECTRICAL WORK, UNLESS

NOTED OTHERWISE ON THE DRAWINGS. IN ADDITION, PATCH ALL OPENINGS CREATED BY

ELECTRICAL DEMOLITION ACTIVITIES WHICH ARE NOT BEING UTILIZED FOR CONSTRUCTION.

PATCH TO MATCH EXISTING ADJACENT SURFACES IN MATERIAL FINISH, TEXTURE, AND

COLOR.

3.E.I. FURNISHING AND SETTING OF ALL SLEEVES THROUGH FLOORS, WALLS, WHERE REQUIRED, INCLUDING WATERPROOF AND FIREPROOF SEALING.

3.E.J. FIRE SEALING AROUND ALL BOXES, RACEWAYS, SLEEVES, ETC. WHERE PASSING THROUGH

OR PENETRATING CONCRETE SLABS/WALLS AND ALL OTHER FIRE PARTITIONS. FIRE SEAL

SHALL BE APPROVED AND INSTALLED IN ACCORDANCE WITH ASTM E814 AND AHJ

REQUIREMENTS.

3.E.K. CORE DRILLING ASSOCIATED WITH THE ELECTRICAL WORK.

3.E.L. POWER AND LIGHT DISTRIBUTION SYSTEM

3.E.M. PANELBOARDS.

3.E.N. SAFETY DISCONNECT SWITCHES WHERE REQUIRED, UNLESS FURNISHED WITH STARTERS

OR ON EQUIPMENT.

3.E.O. GROUNDING AS REQUIRED BY CODE.

3.E.P. IDENTIFICATION OF EQUIPMENT.

3.E.Q. PRIME PAINTING ELECTRICAL EQUIPMENT AND INSTALLATION COMPONENTS.

3.E.R. FIRE ALARM, SMOKE DETECTION AND SPRINKLER ALARM SYSTEMS.

3.E.S. CABLE SUPPORT AND PULLBOXES.

3.E.T. TELEPHONE AND LOW-VOLTAGE SYSTEM EMPTY CONDUIT SYSTEMS.

3.E.U. WHERE INDICATED, INSTALLATION OF EQUIPMENT FURNISHED BY OTHERS.

3.E.V. HANGERS, ANCHORS, INSERTS, SUPPORTS, SLEEVES, CHASES , ETC. AS REQUIRED TO

SECURELY FASTEN ELECTRICAL WORK TO BUILDING STRUCTURE .

3.E.W. STORAGE, RIGGING, SCAFFOLDING AND HANDLING OF ALL MATERIALS AND EQUIPMENT.

3.E.X. TESTS AND INSPECTIONS OF ALL SYSTEMS UNDER THIS SECTION.

3.E.Y. PAYING ALL FEES AND PERFORMING ALL TESTING AND ADJUSTING, AND FURNISHING ALL

CERTIFICATES OF APPROVAL.

4. RELATED WORK SPECIFIED IN OTHER SECTIONS

4.A. UNLESS NOTED OTHERWISE IN CONTRACT DOCUMENTS, THE FOLLOWING WORK, RELATED TO THIS

SECTION, WILL BE FURNISHED AND/OR PERFORMED UNDER OTHER SECTIONS OF THE SPECIFICATIONS, OR BY OTHERS, AND SHALL NOT BE CONSIDERED AS PART OF THE WORK OF THIS SECTION:

4.A.L. [FURNISHING MOTOR STARTERS AND ALL CONTROL DEVICES FOR MOTORS AND

EQUIPMENT SPECIFIED UNDER OTHER CONTRACTS. ]

4.A.M. [OPENINGS FOR SLEEVES IN WALLS AND FLOOR SLABS. ]

4.A.N. [FINISH PAINTING.]

4.A.O. [FINISH PAINTING OF EXPOSED CONDUITS, BOXES, HANGERS, APPARATUS, ETC.

4.A.P. TEMPERATURE AND MOTOR CONTROL WIRING, UNLESS OTHERWISE INDICATED ON THE

DRAWINGS.]

4.A.Q. [DATA/TELEPHONE SYSTEM CABLES, WIRES, CONNECTIONS, AND INSTRUMENTS. ]

5. SUBMITTALS/SHIPPING & HANDLING

5.A. SUBMITTAL SHALL INCLUDE MANUFACTURER'S STANDARD DATA, INSTALLATION INSTRUCTIONS AND

SPECIFICATIONS.

5.B. SUBMIT SAMPLES FOR EACH ITEM AS REQUIRED.

5.C. SUBMIT SHOP DRAWINGS FOR ALL ITEMS DESCRIBED IN THE CONTRACT DOCUMENTS OR AS MAY BE

REQUIRED BY THE ARCHITECT AND/OR ENGINEER INCLUDING (BUT NOT LIMITED TO):

5.C.A. LIGHT FIXTURES

5.C.B. POWER DISTRIBUTION EQUIPMENT (PANELBOARDS, TRANSFORMERS, SWITCHES, ETC.)

5.C.C. WIRING DEVICES

5.C.D. RACEWAY AND BOXES

5.C.E. WIRING

5.C.F. FIRE ALARM SYSTEM

5.D. CONTRACTOR IS RESPONSIBLE FOR SHIPPING AND STORING OF ALL MATERIALS. HANDLE PRODUCTS

CAREFULLY DURING SHIPPING, STORING, AND INSTALLING. DO NOT INSTALL DAMAGED EQUIPMENT OR

COMPONENTS. IN SUCH INSTANCES REPLACE WITH NEW.

6. EXAMINATION OF EXISTING CONDITIONS OF PREMISES

6.A. BEFORE SUBMITTING THE BID, THIS CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND SHALL

THOROUGHLY FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS AFFECTING THE WORK. NO

EXTRA PAYMENTS WILL BE ALLOWED ON ACCOUNT OF EXTRA WORK MADE NECESSARY BY FAILURE TO

DO SO.

6.B. EXAMINE ALL WORK PREPARED BY OTHERS TO RECEIVE THE WORK OF THIS SECTION AND REPORT ANY

DEFECTS AFFECTING INSTALLATION TO THE GENERAL CONTRACTOR FOR CORRECTION.

COMMENCEMENT OF WORK WILL BE CONSTRUED AS COMPLETE ACCEPTANCE OF PREPARATORY WORK

BY OTHERS.

6.C. CONTRACTOR SHALL TEST ALL EXISTING BRANCH CIRCUITS IN EXISTING PANELBOARDS PRIOR TO

RE-USING SAID BRANCH CIRCUITS FOR THIS PROJECT. TESTING SHALL BE DONE DURING PREMIUM TIME, UNLESS APPROVED BY BUILDING OWNER AND EXISTING TENANTS.

7. REMOVAL OF EXISTING WORK

7.A. REMOVE AND/OR RELOCATE ALL ELECTRICAL EQUIPMENT, WIRING AND OTHER ELECTRICAL WORK SO

INDICATED OR REQUIRED BY REMOVAL OF OR CHANGES IN EXISTING CONSTRUCTION. DISCONNECT

LOAD AND LINE ENDS OF CONDUCTORS FEEDING PANELBOARDS, CONTROLLERS, MOTORS, APPLIANCES, AND DEVICES WHICH ARE TO BE REMOVED OR ABANDONED. REMOVE CONDUCTORS FROM EXISTING

CONDUITS THROUGH WHICH NEW CONDUCTORS ARE TO BE PULLED. CUT AND CAP FLUSH WITH FLOOR

ALL ABANDONED CONDUITS. REMOVE ABANDONED SURFACE MOUNTED CONDUITS. REMOVE MATERIAL

AND EQUIPMENT AND DISPOSE OF SAME AS DIRECTED. WHERE ANY FIXTURE OR WIRING DEVICE IS

REMOVED, PROVIDE ADEQUATE SIZE AND TYPE OF BLANK COVER PLATE OVER EACH OUTLET.

8. COORDINATION OF WORK WITH OTHER S

8.A. THE WORK OF THIS SECTION SHALL BE COORDINATED WITH THE WORK OF ALL OTHER CONTRACTS, THE

UTILITY COMPANY, AND OF THE TELECOMMUNICATIONS COMPANY, AND SHALL BE SO ARRANGED THAT

THERE WILL BE NO DELAY IN THE PROPER INSTALLATION AND COMPLETION OF ANY PART OR PARTS OF

EACH RESPECTIVE WORK WHEREIN IT MAY BE INTERRELATED WITH THAT OF THIS CONTRACT SO THAT

GENERALLY ALL CONSTRUCTION WORK CAN PROCEED IN ITS NATURAL SEQUENCE WITHOUT

UNNECESSARY DELAY.

8.B. COORDINATE WORK WITH OTHER TRADES AND ADJUST EQUIPMENT LOCATIONS ACCORDINGLY TO FIT

SPACES ALLOTTED.

8.C. ELECTRICAL EQUIPMENT AND DEVICE LOCATIONS SHOWN ARE APPROXIMATE. COORDINATE EXACT

MOUNTING LOCATIONS AND HEIGHTS WITH OTHER TRADES AND ARCHITECTURAL ELEVATIONS, PLANS, AND FURNITURE LAYOUTS. VERIFY EXACT EQUIPMENT LOCATIONS PRIOR TO FEEDER ROUGH IN.

8.D. PRIOR TO ROUGH-IN FOR ANY CEILING MOUNTED ELECTRICAL DEVICE OR LIGHT FIXTURE, COORDINATE

THE LOCATIONS OF SPRINKLER HEADS WITH PLUMBING CONTRACTOR. ALL CEILING-MOUNTED

EQUIPMENT SHALL BE MOUNTED AT A DISTANCE FROM SPRINKLER HEADS THAT MEET NFPA MINIMUM

REQUIREMENTS.

8. SHUTDOWNS/UTILITY INTERRUPTIONS

8.A. PLAN INSTALLATION OF NEW WORK AND CONNECTIONS TO EXISTING WORK TO INSURE MINIMUM

INTERFERENCE WITH REGULAR OPERATION OF EXISTING FACILITIES. TO INSURE CONTINUOUS

OPERATION, MAKE NECESSARY TEMPORARY CONNECTIONS BETWEEN NEW AND EXISTING WORK WHEN

SO REQUIRED.

8.B. WHEN INSTALLATION OF A NEW SYSTEM REQUIRES THE TEMPORARY SHUTDOWN OF AN EXISTING

OPERATING SYSTEM, THE CONNECTION OF THE NEW SYSTEM SHALL BE PERFORMED AT SUCH TIME AS

DESIGNATED BY THE OWNER.

8.C. NOTIFY AND OBTAIN PERMISSION FROM OWNER A MINIMUM OF 48 HOURS IN ADVANCE OF ANY UTILITY

INTERRUPTION. COORDINATE ANY UTILITY INTERRUPTIONS WITH ALL OTHER CONTRACTORS.

8.D. WORK SHALL BE ARRANGED FOR CONTINUOUS PERFORMANCE, INCLUDING OVERTIME, AT NO EXTRA

COST TO THE OWNER TO ASSURE THAT EXISTING OPERATION SERVICES WILL BE SHUT DOWN ONLY

DURING THE TIME ACTUALLY REQUIRED TO MAKE NECESSARY CONNECTIONS.

9. MATERIAL AND WORKMANSHIP

9.C. ALL MATERIAL AND EQUIPMENT SHALL COMPLY WITH ALL ASSOCIATED CODES AND STANDARDS FOR THE

INTENDED MATERIAL AND EQUIPMENT. CODES AND STANDARDS INCLUDE, BUT ARE NOT LIMITED TO, NATIONAL ELECTRIC CODE (NEC), UL, NMEA/ICEA, IEEE, AND NFPA.

9.D. ALL MATERIAL SHALL BE NEW AND OF THE BEST QUALITY AND SHALL HAVE THE APPROVED

UNDERWRITER'S LABEL ATTACHED. THE LABEL OF APPROVAL SHALL BE OF THE TYPE FOR THE INTENDED

APPLICATION. THE WORK THROUGHOUT SHALL BE EXECUTED IN THE BEST AND MOST THOROUGH

MANNER UNDER THE DIRECTION OF, AND TO THE SATISFACTION OF, THE OWNER WHO WILL INTERPRET

THE MEANINGS OF THE DRAWINGS AND SPECIFICATIONS, AND THE OWNER SHALL HAVE THE POWER TO

REJECT ANY WORK AND MATERIALS WHICH, IN THEIR OPINION, IS NOT IN FULL CONFORMANCE

THEREWITH.

9.E. IF, AFTER INSTALLATION, OPERATION OF THE EQUIPMENT PROVES TO BE UNSATISFACTORY TO THE

OWNER BY REASONS OF DEFECTS, ERRORS OR OMISSIONS, THE OWNER RESERVES THE RIGHT TO

OPERATE THE EQUIPMENT UNTIL IT CAN BE REMOVED FROM SERVICE FOR CORRECTION BY THE

CONTRACTOR. THE CONTRACTOR SHALL PAY FOR ALL DAMAGES TO WORK OF OTHER TRADES CAUSED

BY THIS DEFECTIVE EQUIPMENT AND ITS REPLACEMENT.

9.F. FURNISH WRITTEN GUARANTEE COVERING MATERIAL, OPERATION, AND WORKMANSHIP FOR A PERIOD OF

ONE YEAR.

9.G. INSTALL ALL CIRCUITRY PARALLEL OR PERPENDICULAR TO WALLS, FLOOR, AND CEILING.

9.H. REMOVE MATERIALS AS WORK PROGRESSES, UPON COMPLETION OF WORK. LEAVE AREAS IN A CLEAN

CONDITION.

9.I. PROVIDE A COMPETENT SUPERINTENDENT WHO SHALL BE IN CHARGE OF THE WORK TO BE INSTALLED

UNDER THIS SECTION OF THE SPECIFICATIONS.

10. LABELING

10.A. ALL DEVICE AND EQUIPMENT LABELING SHALL BE TYPEWRITTEN. HANDWRITTEN LABELS WILL NOT BE

ACCEPTED.

10.B. ALL DEVICE LABELING SHALL BE TYPEWRITTEN USING A LABEL MAKER AND SHALL BE PERMANENTLY

AFFIXED TO EACH FACEPLATE.

10.C. FOR ALL EQUIPMENT PROVIDED UNDER PROJECT, PROVIDE STANDARD PHENOLIC NAMEPLATE WITH 1"

MINIMUM SIZE ENGRAVED LETTERING INDICATING LOAD SERVED, POWER SOURCE, VOLTAGE, PHASE, AND CIRCUIT NUMBER. NAMEPLATES SHALL BE WHITE LETTERING ON BLACK BACKGROUND OR AS

DIRECTED BY OWNER TO MATCH EXISTING LABELING.

10.D. UPON COMPLETION OF PROJECT, THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN, UP-TO-DATE

CIRCUIT BREAKER DIRECTORIES FOR ALL EXISTING PANELBOARDS IMPACTED BY PROJECT TO DESCRIBE

NEW EQUIPMENT AND DEFINE THEIR CORRESPONDING CIRCUIT BREAKER.

10.E. UPON COMPLETION OF PROJECT, THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN, UP-TO-DATE CIRCUIT

BREAKER DIRECTORIES FOR ALL NEW PANELBOARDS PROVIDED UNDER PROJECT.

10.F. EACH RECEPTACLE AND SWITCH PROVIDED OR ALTERED UNDER THIS CONTRACT SHALL BE LABELED

WITH THE CORRESPONDING POWER PANEL NAME AND CIRCUIT BREAKER NUMBER.

10.G. ALL JUNCTION BOXES, OUTLET BOXES, PULL BOXES, ETC. SHALL BE CLEARLY LABELED WITH BLACK

PERMANENT MAKER IDENTIFYING THE ASSOCIATED PANELBOARD AND CIRCUIT NUMBER.

11. FINAL INSPECTIONS, TESTS, AND CLOSE-OUTS

11.A. UPON COMPLETION OF THE ELECTRICAL INSTALLATION, CONDUCT A LOAD TEST BY TURNING ON ALL

ELECTRICAL EQUIPMENT THROUGHOUT THE ENTIRE PROJECT FOR A CONTINUOUS PERIOD. ALTER

FUSES, CIRCUIT BREAKERS, CIRCUIT CONNECTION ARRANGEMENTS, ETC. AS REQUIRED TO PERMIT

SATISFACTORY PERFORMANCE. LOAD SHALL BE BALANCED WITHIN 5%.

11.B. AT THE TIME OF THE FINAL INSPECTION AND TESTS, ALL CONNECTIONS AT PANELS AND ALL SPLICES, ETC., MUST BE MADE. ALL FUSES MUST BE IN PLACE AND THE CIRCUITS CONTINUOUS

FROM SERVICE SWITCHES TO ALL PANELS, RECEPTACLES, OUTLETS, MOTORS, ETC. EACH ENTIRE

WIRING SYSTEM MUST TEST FREE FROM ALL SHORT CIRCUITS AND FROM GROUNDS AS REQUIRED

BY THE N.E.C..

11.C. AFTER SUBSTANTIAL COMPLETION, PROVIDE OWNER DESIGNATED PERSONNEL WITH INSTRUCTIONS

ON INSTALLED SYSTEMS.

11.D. PROVIDE OWNER WITH AN OPERATION AND MAINTENANCE MANUAL FOR EACH INSTALLED SYSTEM.

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

1. UNLESS NOTED OTHERWISE AND AS APPROVED BY THE AHJ, CONDUIT TYPES SHALL BE USED AS FOLLOWS:

1.A. ROMEX: PROVIDE FOR ALL INTERIOR BRANCH CIRCUITS, UNLESS

OTHERWISE INDICATED.

1.B. FLEXIBLE METAL CONDUIT (FMC): PROVIDE FOR FINAL BRANCH CIRCUIT CONDUIT CONNECTION TO

RECESSED CEILING LIGHT FIXTURES, 6' MAXIMUM LENGTH.

1.C. LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC): PROVIDE FOR FINAL CIRCUIT CONNECTIONS TO

MOTORS AND EQUIPMENT, 6' MAXIMUM LENGTH.

1.D. INTERMEDIATE METAL CONDUIT (IMC): PROVIDE FOR ALL FEEDERS.

1.E. RIGID METAL CONDUIT (RMC): PROVIDE FOR ALL EXTERIOR EXPOSED, RISERS FROM GRADE, INTERIOR/EXTERIOR WET LOCATIONS, AND IN ALL INTERIOR/EXTERIOR AREAS WHERE PHYSICAL

DAMAGE MAY OCCUR.

1.F. RIGID POLYVINYL CHLORIDE CONDUIT (PVC): PROVIDE FOR ALL UNDERGROUND EXTERIOR, UNDER-SLAB, AND CONCRETE ENCASED CIRCUITS/FEEDERS. SCHEDULE 80 PVC SHALL BE USED

FOR ALL DIRECT-BURY APPLICATIONS. SCHEDULE 40 PVC SHALL BE USED UNDER-SLAB AND

CONCRETE ENCASEMENT APPLICATIONS.

2. FITTINGS, SUPPORTS, ACCESSORIES, ETC. SHALL BE SPECIFICALLY DESIGNED FOR ASSOCIATED CONDUIT

TYPES AND SHALL BE OF SAME MANUFACTURER OF CONDUIT PROVIDED.

3. MINIMUM RACEWAY SIZE SHALL BE 3/4".

4. PROVIDE PULL CORDS IN ALL CONDUITS/RACEWAYS FOR PULLING OF CABLING/WIRING.

5. RACEWAYS SHALL NOT CROSS PIPE SHAFTS OR VENTILATION DUCT OPENINGS AND SHALL NOT BE ROUTED

THROUGH ELEVATOR SHAFTS OR ELEVATOR MACHINE ROOMS UNLESS SPECIFICALLY SERVING ELEVATOR

OR ELEVATOR RELATED SYSTEMS.

6. PROVIDE BOXES AND FITTINGS OF TYPES AND SIZES WHICH ARE SUITABLE FOR INSTALLATION. COMPLY

WITH PROVISIONS OF NEC FOR BOXES AND FITTINGS.

7. IN ADDITION TO BOXES SHOWN, PROVIDE ADDITIONAL BOXES WHERE REQUIRED TO PREVENT DAMAGE TO

CABLES AND WIRES DURING PULLING OPERATIONS.

8. PROVIDE PULL BOXES AFTER EVERY TWO 90 DEGREE BENDS FOR ALL 4" CONDUITS. FOR ALL OTHER

CONDUIT SIZES/RUNS PROVIDE PULL BOXES ARE REQUIRED BY NEC. SIZE ALL PULL BOXES PER NEC

REQUIREMENTS.

9. PROVIDE ACCESSORIES AS REQUIRED FOR EACH INSTALLATION.

10. COUPLINGS AND CONNECTORS SHALL BE SET-SCREW TYPE.

11. SUPPORT ALL RACEWAYS AND BOXES SECURELY TO BUILDING STRUCTURE.

11.A. FASTEN ELECTRICAL BOXES SECURELY AND RIGIDLY TO STRUCTURAL SURFACES TO WHICH THEY

ARE ATTACHED.

11.B. RACEWAYS SHALL BE SUPPORTED WITHIN 3' OF CONNECTION TO EQUIPMENT, BOXES, CABINETS, ETC.

11.C. PROVIDE RACEWAY SUPPORTS PER NEC SUPPORT SPACING REQUIREMENTS.

12. MECHANICALLY JOIN ALL METAL RACEWAYS, ENCLOSURES , AND RACEWAYS FOR CONDUCTORS TO FORM A

CONTINUOUS ELECTRICAL CONDUCTOR. CONNECT ALL ELECTRICAL BOXES, FITTINGS AND CABINETS SO

AS TO PROVIDE AN EFFECTIVE ELECTRICAL CONTINUITY AND A FIRM MECHANICAL ASSEMBLY.

13. INSTALL RACEWAYS SO THAT REQUIRED CONDUCTORS MAY BE DRAWN IN WITHOUT INJURY OR EXCESSIVE

STRAIN TO THE RACEWAY OR CABLE.

14. INSTALL RACEWAYS TO AVOID PROXIMITY TO STEAM AND HOT WATER PIPES. KEEP RACEWAYS A MINIMUM

OF 3" FROM SUCH PIPES.

15. KEEP ENDS OF RACEWAYS PLUGGED OR CAPPED DURING CONSTRUCTION. PROVIDE INSULATED BUSHINGS

FOR ALL EMPTY CONDUITS AND CONDUIT ENDS.

16. PROVIDE EXPANSION - DEFLECTION FITTINGS IN ALL RACEWAYS PASSING THROUGH STRUCTURAL

EXPANSION JOINTS.

17. FEEDERS TO PANELS SHALL BE IN SER CABLE.

18. COMBINING OF CIRCUITS IN SAME RACEWAY, OTHER THAN THOSE INDICATED ON DRAWING SHALL NOT BE

PERMITTED.

19. ALL CONDUITS RUN UNDERGROUND OR BENEATH CONCRETE SLAB SHALL COMPLY WITH SET LOCATION

REQUIREMENTS OF THE NEC.

20. RACEWAY PENETRATIONS OF FIRE-RATED WALLS, CEILINGS, AND/OR FLOORS SHALL BE SEALED TO

MAINTAIN THE INTEGRITY OF CONSTRUCTION/RATING. ALL PRODUCTS, MATERIALS, AND METHODS OF

INSTALLATION SHALL BE UL APPROVED AND MEET NFPA REQUIREMENTS. WHERE BOXES ARE PROVIDED IN

FIRE RATED ASSEMBLIES, COORDINATE INSTALLATION WITH ALL REQUIREMENTS OF THE ASSOCIATED

ASSEMBLY SO AS TO MAINTAIN ASSEMBLY RATING. INSTALLATION SHALL COMPLY WITH ALL UL

REQUIREMENTS AND SPECIFIC BOX MANUFACTURER INSTALLATION REQUIREMENTS FOR MAINTAINING FIRE

RATING (INCLUDING, BUT NOT LIMITED TO, BOX DIMENSIONS, BOX DEPTH, SPACING WITH IN THE ASSEMBLY, DISTANCE FROM OTHER BOXES, ETC.

CONDUCTORS AND CABLES

1. ALL CONDUCTORS SHALL BE COPPER, UNLESS OTHERWISE INDICATED.

2. ALL BRANCH CIRCUIT WIRING SHALL BE INSULATED COPPER CONDUCTORS (MINIMUM #12 AWG). #12 AWG

AND #10 AWG SHALL BE SOLID, #8 AWG AND LARGER SHALL BE STRANDED. BRANCH CIRCUITS LONGER THAN

100' FROM PANEL TO LOAD SHALL BE #10 AWG MINIMUM FOR THE ENTIRE CIRCUIT.

3. UNLESS NOTED OTHERWISE AND AS APPROVED BY AHJ, CONDUCTOR (WIRE) TYPES SHALL BE AS FOLLOWS:

3.A. DRY, DAMP, AND WET LOCATIONS: TYPE THHN-THWN OR XHHW-2 WITH INSULATION RATING OF 75°

PROVIDED AS CONDUCTORS IN CONDUIT. 90° INSULATION RATING MAY BE USED FOR DRY

LOCATIONS ONLY.

3.B. DIRECT BURIAL: TYPE UF OR USE

3.C. THE USE OF AC CABLE, MC CABLE, OR FLEXIBLE METAL CONDUIT IS PERMITTED IN LIEU OF WIRE IN

CONDUIT FOR BRANCH CIRCUITS 20A OR LESS IN INTERIOR SPACES. FOR ALL OTHER AREAS AND

APPLICATIONS, THE USE OF TYPE AC CABLE, MC CABLE OR FLEXIBLE METAL CONDUIT WITH

CONDUCTORS IS NOT PERMITTED, EXCEPT FOR FINAL CONNECTIONS TO LIGHT FIXTURES, HVAC

EQUIPMENT, AND OTHER EQUIPMENT/TRANSFORMERS (FINAL FLEXIBLE CONNECTION LENGTH IS

LIMITED TO MAXIMUM OF 6'). AC CABLE AND MC CABLE SHALL BE PROVIDED WITH AN INSULATED

GREEN EQUIPMENT GROUND CONDUCTOR.

4. ALL CONDUCTORS SHALL BE COLOR CODED AS REQUIRED BY NEC. COLOR CODING SHALL BE BY MEANS OF

COLORED INSULATING MATERIAL, COLORED BRAID OR JACKET OVER THE INSULATION, OR BY MEANS OF

SUITABLE COLORED, PERMANENT, NON-AGING, INSULATING TAPE APPLIED TO CONDUCTORS AT EACH

CABINET OR JUNCTION POINT. THE COLOR CODING SHALL BE ACCOMPLISHED AS THE CONDUCTORS ARE

BEING INSTALLED.

5. DRAWING FEEDER CONDUCTOR SIZES INDICATED ARE COPPER. WHERE APPROVED BY OWNER AND AHJ, ALUMINUM EQUIVALENT FEEDERS MAY BE USED FOR FEEDER SIZES OVER #8 AWG. CONTRACTOR IS

RESPONSIBLE FOR PROVIDING EQUIVALENT CONDUCTOR SIZES/TYPES AND ANY ASSOCIATED INCREASE IN

CONDUIT SIZE AS REQUIRED BY NEC.

6. CONNECTORS SHALL BE UL LISTED AND PROVIDED WITH APPROPRIATE TEMPERATURE RATINGS.

7. PROVIDE CONNECTORS AND FILLER WHICH ARE COMPATIBLE WITH THE CONDUCTOR MATERIAL.

CONNECTORS AND FILLER INCLUDES, BUT ARE NOT LIMITED TO, INDENT-TYPE CONNECTORS, INDENT-TYPE

PRESSURE CONNECTORS, SPRING-TYPE CONNECTORS, BOLT-ON PRESSURE CONNECTORS, TWO AND

THREE-WAY CONNECTORS, AND FILLER FOR INDENTIONS IN CONNECTOR BODIES.

8. PROVIDE SPLICE KITS AND INSULATION TAPES WITH MECHANICAL STRENGTH AND INSULATION RATING

EQUIVALENT OR BETTER THAN CONDUCTORS BEING SPLICED.

9. PRIOR TO ENERGIZING CIRCUITRY, CHECK INSTALLED WIRES AND CABLES WITH MEGOHM METER TO

DETERMINE INSULATION RESISTANCE LEVELS AND ENSURE REQUIREMENTS ARE FULFILLED.

10. PRIOR TO ENERGIZING, TEST WIRES AND CABLES FOR ELECTRICAL CONTINUITY AND FOR SHORT CIRCUITS.

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

1. THE ENTIRE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED BY

UL 467 AND NATIONAL ELECTRICAL CODE (NEC).

2. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS AND AT

ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. METALLIC RACEWAYS SHALL NOT BE CONSIDERED

SOLE MEANS OF GROUNDING.

3. A SEPARATE COPPER CONDUCTOR SHALL BE INSTALLED IN ALL RACEWAYS AS THE EQUIPMENT

GROUNDING MEANS. UNLESS NOTED OTHERWISE, GROUNDING CONDUCTOR SHALL BE SIZED PER NEC

BASED ON THE SIZE OF THE RESPECTIVE FEEDER OVERCURRENT PROTECTIVE DEVICE. TERMINATE

GROUNDING CONDUCTORS ON THE DEVICE/EQUIPMENT GROUND TERMINAL AND ON THE GROUND BUS

INSTALLED IN PANELBOARDS, MOTOR CENTERS, ETC.

4. PROVIDE A DEDICATED NEUTRAL CONDUCTOR THE ENTIRE LENGTH OF ALL CIRCUITS. TERMINATE

NEUTRAL CONDUCTORS ON THE DEVICE/EQUIPMENT NEUTRAL TERMINAL AND ON THE NEUTRAL BUS

INSTALLED IN PANELBOARDS, MOTOR CENTERS, ETC. SHARED NEUTRAL CONDUCTORS ARE NOT

PERMITTED.

5. GROUNDING CONNECTIONS:

5.A. EXOTHERMIC WELDING PROCESS: CADWELD OR APPROVED EQUAL

5.B. MECHANICAL COMPRESSION:

5.B.A. TIN-PLATED, HIGH-CONDUCTIVITY PURE ELECTROLYTIC COPPER EXTRUSION

FITTINGS.

5.B.B. HYDRAULIC COMPRESSION EQUIPMENT AND DIES AS RECOMMENDED BY

MANUFACTURER.

5.B.C. BOLTED CONNECTIONS: HIGH CONDUCTIVITY COPPER FITTINGS WITH CORROSION

RESISTANT NUTS AND BOLTS.

6. PROVIDE BONDING FITTINGS AND BONDING JUMPERS TO ASSURE ELECTRICAL CONTINUITY OF THE

GROUNDING CIRCUIT OF SERVICE EQUIPMENT AND ENCLOSURES THAT CONTAIN SERVICE CONDUCTORS.

SIZE THE BONDING JUMPERS PER NEC BASED UPON THE SIZE OF THE SYSTEM PHASE CONDUCTORS.

7. PROVIDE GROUNDING BUSHINGS ON ALL CONDUIT TERMINATIONS AT PANELBOARDS AND JUNCTIONS

BOXES. GROUND BUSHINGS TO EQUIPMENT GROUNDING BUSSES USING AN INSULATED, CONTINUOUS, STRANDED, COPPER CONDUCTOR (#12 AWG MINIMUM).

8. PROVIDE GROUNDING FOR TVSS SERIES FILTER PER MANUFACTURER'S WRITTEN INSTALLATION

INSTRUCTIONS AND NEC.

9. TIGHTEN GROUNDING AND BONDING CONNECTORS AND TERMINALS, INCLUDING SCREWS AND BOLTS, IN

ACCORDANCE WITH MANUFACTURER'S PUBLISHED TORQUE TIGHTENING VALUES FOR CONNECTORS AND

BOLTS.

10. CONTRACTOR SHALL TEST GROUNDING SYSTEM. THE RESISTANCE TO GROUND SHALL NOT BE MORE

THAN TWENTY FIVE (25) OHMS. SUBMIT TEST RESULTS TO ENGINEER. CONTRACTOR SHALL MAKE ALL

UPGRADES AND ADDITIONS AS REQUIRED TO ACHIEVE THE FIVE (25) OHM REQUIREMENT.

PANELBOARDS

1. ELECTRICAL PANELS SHALL BE DEAD - FRONT TYPE CONSTRUCTION AND EQUIPPED WITH OVERCURRENT

PROTECTIVE DEVICES, AS SCHEDULED ON THE DRAWINGS. THEY SHALL BE COMPLETE WITH CABINET, TRIM, HINGED DOOR, LOCKS (WITH TWO KEYS), AND TYPEWRITTEN DIRECTORY AND SUCH ADDITIONAL

FEATURES AND COMPONENTS AS HEREIN SPECIFIED OR SHOWN ON THE DRAWINGS. CONSTRUCTION OF

PANELBOARDS SHALL BE IN ALL WAYS SATISFACTORY TO THE ARCHITECT AND/OR ENGINEER AND

SUBJECT TO THEIR APPROVAL.

2. PROVIDE PANELBOARDS, ENCLOSURES, AND ANCILLARY COMPONENTS OF TYPES, SIZES, RATINGS

INDICATED WHICH COMPLY WITH MANUFACTURER'S STANDARD MATERIALS. DESIGN AND CONSTRUCTION

SHALL BE IN ACCORDANCE WITH PUBLISHED PRODUCT INFORMATION. WHERE TYPES, SIZES, OR RATINGS

ARE NOT OTHERWISE INDICATED, COMPLY WITH NEC, UL, AND ESTABLISHED INDUSTRY STANDARDS FOR

APPLICATIONS INDICATED.

3. PROVIDE KAIC RATING AS INDICATED ON SCHEDULES. PROVIDE FULLY RATED PANELBOARD ASSEMBLY.

4. PROVIDE ASSEMBLIES THAT ARE NATURALLY VENTED AND THAT ARE CONSTRUCTED IN SUCH A MANNER

THAT THE TEMPERATURE RISE WITH CIRCUIT BREAKERS INSTALLED DOES NOT CAUSE NUISANCE

TRIPPING.

5. BUS BARS:

5.A. PROVIDE PANELBOARDS WITH FACTORY INSTALLED BARE ALUMINUM BUS BARS, ALUMINUM

EQUIPMENT GROUND BUS, AND SUPPORTS INSULATED TO SUIT SYSTEM VOLTAGE.

5.B. PROVIDE AMPERE RATING OF BUS BARS NOT LESS THAN EITHER THE FRAME SIZE OF MAIN

CIRCUIT BREAKER IN THE PANELBOARD, OR, IN THE CASE OF MAIN LUG ONLY PANELBOARDS, THE

NEC AMPERE RATING OF THE FEEDER CONDUCTORS.

5.C. PROVIDE BUS BARS BRACED TO WITHSTAND THE SAME FAULT CURRENTS AS THE BRANCH

CIRCUIT BREAKER SPECIFIED.

5.D. BUSSES SHALL EXTEND ENTIRE PANEL LENGTH.

5.E. PROVIDE FULL CAPACITY NEUTRAL BUS.

5.F. PROVIDE AN ADEQUATE NUMBER OF LUGS TO ACCEPT QUANTITIES OF CABLES INDICATED FOR

INCOMING AND OUTGOING CONDUCTORS PLUS SPARE FOR FUTURE CONNECTION.

6. ENCLOSURES:

6.A. PROVIDE BACKBOXES FABRICATED OF CODE GAUGE HOT GALVANIZED STEEL WITH CORNERS

LAPPED AND RIVETED OR WELDED, CONFORMING TO UNDERWRITER'S LABORATORIES

REQUIREMENTS.

6.B. BACKBOXES SHALL BE OF MANUFACTURER'S STANDARD WIDTH.

6.C. PROVIDE TRIMS OF CODE GAUGE STEEL WITH RUST-INHIBITING PRIMER AND BAKED ENAMEL

FINISH.

6.D. PROVIDE ONE-PIECE, DOOR-IN-DOOR TRIM.

6.E. CABINETS SHALL BE AS SHOWN ON THE DRAWINGS. BACK BOX SHALL BE OF SUFFICIENT SIZE TO

PROVIDE MINIMUM GUTTER SPACE ON ALL FOUR SIDES, BASED ON THE PANELS MAXIMUM CIRCUIT

OVERCURRENT PROTECTIVE DEVICE AND AS REQUIRED BY UL AND NEC.

6.F. KEY ALL PANELBOARDS ALIKE. IN ADDITION TO THE LOCK, EQUIP ALL DOORS OVER 48" IN HEIGHT

WITH A NICKEL-PLATED VAULT HANDLE AND 3-POINT CATCH ARRANGED TO FASTEN DOOR AT TOP, BOTTOM, AND CENTER.

7. MOLDED CASE CIRCUIT BREAKERS:

7.A. SHALL BE BOLT-ON

7.B. CURRENT RATINGS SHALL BE PERMANENTLY ENGRAVED ON OPERATING HANDLES.

7.C. SHALL BE FULLY RATED TO MEET AVAILABLE FAULT CURRENTS.

7.D. PROVIDE STANDARD FRAME SIZES, TRIP RATINGS, AND NUMBER OF POLES AS INDICATED ON

DRAWINGS AND SCHEDULES

7.E. PROVIDE ACCESSORIES (I.E. HANDLE LOCK) AS CALLED FOR ON DRAWINGS.

7.F. THERMAL MAGNETIC: SHALL BE QUICK MAKE/QUICK BREAK TOGGLE ACTION WITH POSITIVE

INDICATION OF TRIP AND TRIP-FREE MECHANISM.

8. WHERE NEW CIRCUIT BREAKERS ARE REQUIRED FOR INSTALLATION IN EXISTING PANELBOARDS, CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WHICH ARE COMPATIBLE WITH EXISTING PANELBOARD.

MATCH EXISTING PANELBOARD CONSTRUCTION, FRAME SIZE, KAIC RATINGS, ETC.

9. EQUIP SECTIONS DESIGNATED AS "SPACE" WITH ALL ACCESSORIES REQUIRED TO ACCEPT A FUTURE

CIRCUIT BREAKER.

10. INSTALL PANELBOARDS AND ENCLOSURES AS INDICATED, IN ACCORDANCE WITH MANUFACTURER'S

WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC AND NECA'S "STANDARD OF INSTALLATION,"

AND IN COMPLIANCE WITH RECOGNIZED INDUSTRY PRACTICES.

11. PROVIDE ALL PANELBOARDS BY THE SAME MANUFACTURER.

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

STRUCTURAL ENGINEER

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

coa #31580

SEAL

Hall Darling Design Studio, PA

AR 97844

2168 Main Street

Sarasota, FL 34237

P:941.917.0883 genesis engineering

6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.

project #: 25-011

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY DANIEL MARK SCHAFRAN, PE.

ON THE DATE ADJACENT TO THE SEAL USING A

SHA AUTHENTICATION CODE. PRINTED COPIES

OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA

AUTHENTICATION CODE MUST BE VERIFIED ON

ANY ELECTRONIC COPIES.

G

STATE OF

No. 84419

ROL

F A

DI

EL

I C E N S

NAL EN

I N

P R O F E

S I O

S

E E R

DA

NI

EL

MA SCHAFRAN

RK

E0.2

SPECIFICATIONS

SARASOTA COUNTY FLEET SOUTH

RENOVATION

06.26.2026

4571 STATE ROAD 776, VENICE,

FL 34293

12. TIGHTEN ALL ACCESSIBLE CONNECTIONS TO MANUFACTURER'S TIGHTENING TORQUE SPECIFICATIONS.

13. PRIOR TO ENERGIZATION OF PANELBOARDS, CHECK WITH GROUND RESISTANCE TESTER PHASE-TO-PHASE AND

PHASE-TO-GROUND INSULATION RESISTANCE LEVELS TO ENSURE REQUIREMENTS ARE FULFILLED.

14. PRIOR TO ENERGIZATION OF PANELBOARDS, CHECK FOR ELECTRICAL CONTINUITY OF CIRCUITS AND FOR SHORT

CIRCUITS.

15. ACCEPTABLE MANUFACTURERS: SQUARE D, CUTLER HAMMER, GENERAL ELECTRIC, APPROVED EQUAL

ENCLOSED SAFETY SWITCHES (DISCONNECT SWITCHES) AND CIRCUIT BREAKERS

1. SAFETY SWITCHES

1.A. UNLESS OTHERWISE NOTED, PROVIDE SAFETY SWITCHES OF TYPES, SIZES, CHARACTERISTICS, AND RATINGS

INDICATED WHICH COMPLY WITH MANUFACTURER'S STANDARD DESIGN, MATERIALS, COMPONENTS, AND

CONSTRUCTION IN ACCORDANCE WITH PUBLISHED PRODUCT INFORMATION; AND AS REQUIRED FOR A

COMPLETE INSTALLATION.

1.B. SWITCHES SHALL BE RATED 240 VOLTS FOR 208 VOLT AND 240 VOLT SYSTEMS, AND 600 VOLTS FOR 480 VOLT

SYSTEMS.

1.C. PROVIDE AMPERE RATING AND NUMBER OF POLES AS INDICATED ON THE CONTRACT DRAWINGS, OR IF NOT

INDICATED, SAME AS BRANCH CIRCUIT OR FEEDER SERVING THE SWITCH.

1.D. PROVIDE WITH NEUTRAL BUS WHEN NEUTRAL AND/OR GROUNDING CONDUCTOR IS INCLUDED IN THE CIRCUIT.

1.E. PROVIDE FUSED OR UNFUSED AS INDICATED.

1.F. PROVIDE IN AN APPROVED NEMA ENCLOSURE , OR AS INDICATED .

1.G. SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK-MAKE, QUICK-BREAK WITH DUAL COVER

INTERLOCK.

2. ENCLOSED CIRCUIT BREAKERS

2.A. SHALL MEET ALL REQUIREMENTS OF "MOLDED CASE CIRCUIT BREAKERS" AS SPECIFIED HEREIN.

2.B. PROVIDE IN APPROVED NEMA ENCLOSURE, OR AS INDICATED.

3. INSTALL SAFETY SWITCHES AND ENCLOSED CIRCUIT BREAKERS AS INDICATED, COMPLYING WITH MANUFACTURER'S

WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC, NEMA, AND NECA'S "STANDARD OF INSTALLATION," AND

IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES.

FUSES

1. UNLESS OTHERWISE NOTED, PROVIDE FUSES OF MANUFACTURER'S STANDARD MATERIALS, AS INDICATED BY

PUBLISHED PRODUCT INFORMATION, AND AS DESIGNED AND CONSTRUCTED AS RECOMMENDED BY THE

MANUFACTURER AND AS REQUIRED FOR A COMPLETE INSTALLATION.

2. PROVIDE FUSES IN ALL FUSIBLE EQUIPMENT.

3. PROVIDE FUSES FROM ONE MANUFACTURER.

4. FUSES FOR ALL SAFETY SWITCHES AND SERVICE DISCONNECTS THAT ARE RATED 600 VOLTS AND LESS SHALL BE AS

FOLLOWS:

4.A. TYPE: CARTRIDGE, TIME DELAY

4.B. INTERRUPTING…