Genesis_Engineering_Fire_and_Floor_Plans.pdf
PDF 3 MB Posted
- Attached to
- South County Fleet Renovation
- Solicitation number
- 262899MKM
- Issued by
- Sarasota County, Florida
About this file
This document comprises fire protection system design and specification plans for the Sarasota County Fleet South Renovation project located at 4571 State Road 776, Venice, Florida (Permit 24-015). The project involves modifying an existing fire sprinkler system to accommodate a new architectural layout for renovated office space within an automotive maintenance repair shop. The scope includes providing automatic fire suppression systems for complete facility protection with multiple hazard classifications: light hazard areas designed for 0.10 GPM/SF over 1,500 SF with 30-minute water supply duration and 225 SF maximum sprinkler spacing; ordinary hazard group I areas designed for 0.15 GPM/SF with 60-90 minute duration and 130 SF maximum spacing; and ordinary hazard group II areas (canopies and covered parking) designed for 0.20 GPM/SF with 60-90 minute duration and 130 SF maximum spacing. The project requires wet pipe sprinkler systems with quick response standard spray sprinklers manufactured by Victaulic, comprehensive testing in accordance with NFPA 13 (2019) and NFPA 24 standards, and installation by a Florida-licensed fire protection contractor. Drawings are dated June 26, 2026, with certifications dated June 29, 2026.
All fire protection equipment, piping, fittings, valves, couplings, hangers, and devices must be UL-listed and/or FM-approved. The system design must comply with the 2023 Florida Building Code and Fire Prevention Code, along with applicable NFPA standards including NFPA 13, 13R, 14, 20, 24, and NFPA 101 Life Safety Code (Florida-specific, 2021 edition). Hydrostatic testing requirements include 200 PSI pressure testing for 2 hours minimum for aboveground piping and 200 PSI or 50 PSI in excess of system working pressure (whichever is greater) for underground piping. The existing fire main connects to a municipal water supply via a 4" fire main and existing 6" domestic water supply, with an existing backflow preventer to remain. Acceptable product manufacturers include Victaulic for sprinklers; Stockham, NIBCO, Victaulic, Grinnell, Mueller, Kennedy, Crane, and Central for valves; and various approved suppliers for hangers, supports, and fire stopping materials. Contractor submittals must include manufacturer literature, 1/8" scale piping shop drawings with sprinkler head counts by type and elevation sections, and hydraulic calculations demonstrating compliance with NFPA 13 requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
61G15-32 FAC COMPLIANCE NOTES
NOTE: THESE DOCUMENTS ARE PERFORMANCE CRITERIA DOCUMENTS INTENDED TO
CONVEY DESIGN INTENT OF THE ENGINEER OF RECORD IN ACCORDANCE WITH
FLORIDA ADMINISTRATIVE CODE 61G15-32. THE DESIGN OF THE FIRE SUPPRESSION
SYSTEM SHALL BE BY THE SPRINKLER CONTRACTOR AS OUTLINED BY STATE
ORDINANCES. SYSTEM DESIGN SHALL BE COORDINATED WITH OTHER TRADES,
BUILDING STRUCTURE, ETC. AND SHALL BE SUBMITTED FOR PERMIT AND FIRE
MARSHAL APPROVAL. PREPARE AND SUBMIT FIRE SPRINKLER LAYOUT DRAWINGS AND
CALCULATIONS IN ACCORDANCE WITH NFPA 13, PREVAILING CODES AND FAC 61G15-32.
61G15-32.003
A. SCOPE OF WORK:
PROVIDE AUTOMATIC FIRE SUPPRESSION SYSTEMS FOR COMPLETE PROTECTION
OF AN AUTOMOTIVE MAINTENANCE REPAIR SHOP.
SPACE IS CURRENTLY SPRINKLERED. MODIFY EXISTING SPRINKLER SYSTEM TO
ACCOMMODATE NEW ARCHITECTURAL LAYOUT TO PROVIDE AUTOMATIC FIRE
SUPPRESSION SYSTEMS FOR COMPLETE PROTECTION OF A RENOVATED OFFICE
SPACE.
B. ACCEPTANCE TEST CRITERIA:
SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 13 (2019), CHAPTER 25 AND AS
REQUIRED BY THE AHJ. CONTRACTOR SHALL:
1. ABOVEGROUND:
a. NOTIFY AHJ AND OWNER OF THE TIME AND DATE TESTING WILL BE
PERFORMED.
b. PERFORM HYDROSTATIC TEST AT 200 PSI FOR 2 HOURS MINIMUM WITHOUT
PRESSURE LOSS. ANY TEST BLANKS REQUIRED FOR HYDROSTATIC TESTING
OF PORTIONS OF THE SYSTEM SHALL BE REMOVED AFTER COMPLETION OF
TESTING. BLANKS SHALL BE NUMBERED AND THE CONTRACTOR SHALL
HAVE A RECORD KEEPING METHOD ENSURING THEIR REMOVAL AFTER
WORK IS COMPLETED.
c. PERFORM WATER FLOW TEST OF WATER FLOW DETECTING DEVICES, INCLUDING THE ASSOCIATED ALARM CIRCUIT, THROUGH THE INSPECTOR'S
TEST CONNECTION.
d. PERFORM OPERATIONAL TEST OF CONTROL VALVES, INCLUDING THE
ASSOCIATED TAMPER SWITCH ALARM CIRCUIT.
e. PERFORM MAIN DRAIN VALVE TEST. RECORD STATIC AND RESIDUAL
PRESSURE ON CONTRACTOR'S MATERIAL AND TEST CERTIFICATE.
f. PERFORM BACKFLOW PREVENTER FORWARD FLOW TEST. THE MINIMUM
FLOW RATE SHALL BE THE SYSTEM DEMAND.
g. COMPLETE AND SIGN CONTRACTOR'S MATERIAL AND TEST CERTIFICATE
AND PROVIDE AHJ AND OWNER WITH COPIES.
h. REMOVE ALL CAPS AND STRAPS PRIOR TO PLACING THE SPRINKLER
SYSTEM IN SERVICE.
2. UNDERGROUND:
a. NOTIFY AHJ AND OWNER OF TIME AND DATE TESTING WILL BE PERFORMED.
b. FLUSH WATER PIPING FROM THE WATER SUPPLY TO THE SYSTEM RISER IN
ACCORDANCE WITH NFPA 24, 10.10.2.1. LEAD-IN CONNECTIONS TO THE
SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE THE CONNECTION
IS MADE TO DOWNSTREAM FIRE PROTECTION PIPING.
c. ALL PIPING AND ATTACHED APPURTENANCES SUBJECT TO SYSTEM
WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED AT 200 PSI OR
50 PSI IN EXCESS OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS
GREATER, AND SHALL MAINTAIN THAT PRESSURE AT 5PSI FOR 2 HOURS.
PRESSURE DROP SHALL BE DETERMINED BY A DROP IN GAUGE PRESSURE
OR VISUAL LEAKAGE. THE TEST PRESSURE SHALL BE READ FROM ONE OF
THE FOLLOWING, LOCATED AT THE LOWEST ELEVATION OF THE SYSTEM OR
THE PORTION OF THE SYSTEM BEING TESTED:
1. A GAUGE LOCATED AT ONE OF THE HYDRANT OUTLETS.
2. A GAUGE LOCATED AT THE LOWEST POINT WHERE NO HYDRANTS ARE
PROVIDED.
d. THE TRENCH SHALL BE BACKFILLED BETWEEN JOINTS BEFORE TESTING TO
PREVENT MOVEMENT OF PIPE.
e. WHERE ADDITIONAL WATER IS ADDED TO MAINTAIN THE REQUIRED TEST
PRESSURE, THE AMOUNT OF WATER SHALL BE MEASURED AND SHALL NOT
EXCEED THE LIMITS INDICATED IN NFPA 24, TABLE 10.10.2.2.6. IF QUANTITY
OF WATER EXCEEDS INDICATED LIMITS, REPAIR LEAKING JOINTS AND
RETEST AS NECESSARY UNTIL ALL SYSTEMS HAVE BEEN TESTED AND PASS
ACCEPTANCE REQUIREMENTS.
f. OPERATING TESTS SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 24,
10.10.2.4. HYDRANTS SHALL BE FULLY OPENED AND CLOSED UNDER SYSTEM
WORKING PRESSURE. ALL CONTROL VALVES SHALL BE FULLY CLOSED AND
OPENED UNDER SYSTEM WORKING PRESSURE TO ENSURE PROPER
OPERATION.
g. COMPLETE AND SIGN CONTRACTOR'S MATERIAL AND TEST CERTIFICATE
FOR UNDERGROUND PIPING AND PROVIDE AHJ AND OWNER WITH COPIES.
C. HAZARD CLASSIFICATION:
1. LIGHT HAZARD AT INDICATED LOCATIONS.
2. ORDINARY HAZARD AT INDICATED LOCATIONS.
D. STANDARDS SHALL BE APPLIED:
1. 2023 FLORIDA BUILDING CODE, BUILDING, 8TH EDITION.
2. 2023 FLORIDA FIRE PREVENTION CODE, 8TH EDITION, AND ALL ERRATA.
3. NFPA 13, 2019 EDITION; NFPA 13R, 2019 EDITION; NFPA 14, 2019 EDITION; NFPA 20, 2019 EDITION; NFPA 24, 2019 EDITION.
4. NFPA 101, FLORIDA SPECIFIC, 2021 EDITION.
5. OWNER'S INSURANCE UNDERWRITER REQUIREMENTS.
E. STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS:
1. THE FACILITY STRUCTURE IS DESIGNED TO ACCOMMODATE THE SUPPORT OF
THE FIRE SUPPRESSION SYSTEM. THE WORST CASE ANTICIPATED LOAD IS FOR
SUSPENDED 4" WATER FILLED SCHEDULE 10 STEEL PIPE (11.79 LBS PER FOOT
OF PIPE), PLUS 250 LBS. WITH A MAXIMUM HANGER DISTANCE OF 15 FEET.
CALCULATED WORST CASE LOAD AT HANGER CONNECTION IS 338.4 LBS.
F. FIRE ALARM SYSTEM:
1. REFER TO ELECTRICAL DOCUMENTS FOR ALARMING REQUIREMENTS.
61G15-32.004 (2)
A. POINT OF SERVICE:
1. THE FIRE PROTECTION SYSTEM IS SERVED BY AN EXISTING FIRE MAIN
CONNECTED TO THE MUNICIPAL WATER SUPPLY WITH AN EXISTING AUTOMATIC
SPRINKLER RISER.
B. APPLICABLE NFPA STANDARDS SHALL BE FOLLOWED:
1. NFPA 13, 2019 EDITION; NFPA 13R, 2019 EDITION; NFPA 14, 2019 EDITION; NFPA 20, 2019 EDITION; NFPA 24, 2019 EDITION; NFPA 101 LIFE SAFETY CODE - FLORIDA
SPECIFIC, 2021 EDITION.
C. CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA:
1. LIGHT HAZARD: SEE PLANS FOR LOCATIONS.
2. ORDINARY HAZARD: SEE PLANS FOR LOCATIONS.
D. DESIGN APPROACH:
1. LIGHT HAZARD:
a. PROVIDE COMPLETE SPRINKLER COVERAGE IN INDICATED AREAS WITH
QUICK RESPONSE STANDARD SPRAY SPRINKLERS. SPRINKLERS IN LIGHT
HAZARD AREAS SHALL NOT EXCEED 225 SF SPACING. SYSTEM DESIGN
SHALL UTILIZE DENSITY/AREA METHOD WITH MINIMUM 0.10 GPM/SF OVER
THE MOST HYDRAULICALLY REMOTE 1,500 SF.
2. ORDINARY HAZARD GROUP I:
a. PROVIDE COMPLETE SPRINKLER COVERAGE IN INDICATED AREAS WITH
QUICK RESPONSE STANDARD SPRAY SPRINKLERS. SPRINKLERS IN
ORDINARY HAZARD AREAS SHALL NOT EXCEED 130 SF SPACING. SYSTEM
DESIGN SHALL UTILIZE DENSITY/AREA METHOD WITH MINIMUM 0.15 GPM/SF
OVER THE MOST HYDRAULICALLY REMOTE 1,500 SF.
3. ORDINARY HAZARD GROUP II:
a. PROVIDE COMPLETE SPRINKLER COVERAGE IN INDICATED AREAS WITH
QUICK RESPONSE STANDARD SPRAY SPRINKLERS. SPRINKLERS IN
ORDINARY HAZARD AREAS SHALL NOT EXCEED 130 SF SPACING. SYSTEM
DESIGN SHALL UTILIZE DENSITY/AREA METHOD WITH MINIMUM 0.20 GPM/SF
OVER THE MOST HYDRAULICALLY REMOTE 1,500 SF.
E. CHARACTERISTICS OF THE WATER SUPPLY AVAILABLE:
1. THE 4" FIRE MAIN SERVING THE FACILITY CONNECTS TO A 6" DOMESTIC WATER
LOCATED ON SITE.
2. THE MUNICIPAL WATER SUPPLY IS DEEMED RELIABLE TO MEET THE MINIMUM 60
MINUTE DURATION FOR THE MOST HYDRAULICALLY DEMANDING AREA.
F. FLOW TEST DATA:
1. SEE TEST DATA ON THIS SHEET.
G. VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS
AND UNRECOGNIZED FLOW OF WATER:
1. THE (EXISTING) FIRE SPRINKLER RISER AND BACKFLOW PREVENTER FOR THIS
BUILDING SHALL BE (ARE) EQUIPPED WITH EQUIPMENT THAT WILL MINIMIZE THE
POTENTIAL FOR SYSTEM IMPAIRMENT OR WATER FLOW BY MONITORED
ELECTRONIC SIGNALING DEVICES.
H. MICROBIOLOGICAL INDUCED CORROSION (M.I.C):
1. WATER SOURCE IS FROM EXISTING PUBLIC UTILITY WATER MAIN. THERE ARE
NO KNOWN CONDITIONS PRESENT THAT CONTRIBUTE TO MICROBIOLOGICAL
CORROSION (M.I.C.).
I. BACKFLOW PREVENTION AND METERING SPECIFICATIONS:
1. A BACKFLOW PREVENTION DEVICE ASSEMBLY, MEETING THE REQUIREMENTS
OF THE LOCAL WATER PURVEYOR, SHALL BE PROVIDED ON SITE TO PROTECT
THE MUNICIPAL WATER SUPPLY FROM CROSS CONTAMINATION, AND IS
EXISTING TO REMAIN. SEE FP1.1 AND CIVIL DRAWINGS FOR BACKFLOW
PREVENTER LOCATION. SEE CIVIL DRAWINGS FOR BACKFLOW PREVENTER
SPECIFICATIONS.
J. QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL EXTERIOR AND INTERIOR
FIRE PROTECTION COMPONENTS:
1. ALL FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED.
DESCRIPTIONSYMBOL
- REVISION REFERENCE
- ROOF MANIFOLD
- POST INDICATOR VALVE W/TAMPER SWITCH
- SPRINKLER AND DRAIN RISER
- FLUSHING CONNECTION
- FLOW SWITCH
- SPRINKLER SYSTEM PIPING
- CONTROL VALVE W/TAMPER SWITCH
- CHECK VALVE
- FIRE DEPARTMENT CONNECTION
- STANDPIPE WITH FIRE DEPARTMENT VALVE
- BACKFLOW PREVENTER W/TAMPER SWITCHES
- FIRE MAIN PIPING
FP-1
BOTTOM-DRAWING# SHOWN ON
- ENLARGED PLAN REFERENCE: TOP-PLAN#,
- POINT OF CONNECTION TO EXISTING
- POINT OF DEMOLITION EXTENTS
OR
PIV
FDV
FDC
FIRE PROTECTION SYMBOLS
F.C.
SP
F
AC - AIR COMPRESSOR
ADSP - AUTOMATIC DRY STAND PIPE
AFF - ABOVE FINISH FLOOR
A/S - AUTOMATIC SPRINKLER, WET
A/S (DRY) - AUTOMATIC SPRINKLER SYSTEM, DRY
BFF - BELOW FINISH FLOOR
BFP - BACK FLOW PREVENTER
DN - DOWN
DR - DRAIN RISER
(E) - EXISTING
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FM - FIRE MAIN
FP - FIRE PUMP
FPTH - FIRE PUMP TEST HEADER
FWS - FIRE WATER CITY SUPPLY
JP - JOCKEY PUMP
I.E. - INVERT ELEVATION
MDSP - MANUAL DRY STAND PIPE
NTS - NOT TO SCALE
PIV - POST INDICATOR VALVE
SF - SQUARE FEET
SFM - STATE FIRE MARSHAL
SOV - SHUT OFF VALVE
U/G - UNDER GROUND
UMC - UNIVERSAL MANIFOLD CHECK VALVE
UNO - UNLESS NOTED OTHERWISE
WPIV - WALL POST INDICATOR VALVE
FIRE PROTECTION ABBREVIATIONS
FIRE PROTECTION DESIGN CRITERIA
THE FOLLOWING PUBLICATIONS SHALL BE USED AS A REFERENCE FOR DESIGN OF THE FIRE SUPPRESSION
SYSTEM(S) ON THIS PROJECT.
1. FLORIDA ADMINISTRATIVE CODE 61G15-32
2. 2023 FLORIDA BUILDING CODE, BUILDING, 8TH EDITION
3. 2023 FLORIDA FIRE PREVENTION CODE, 8TH EDITION AND ALL ERRATA
4. NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
5. NFPA 13R - INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, 2019 EDITION
6. NFPA 14 - INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2019 EDITION
7. NFPA 20 - INSTALLATION OF STATIONARY FIRE PUMPS FOR FIRE PROTECTION SYSTEMS, 2019 EDITION
8. NFPA 24 - PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2019 EDITION
9. NFPA 101 - LIFE SAFETY CODE - FLORIDA SPECIFIC, 2021 EDITION
10. OWNER'S INSURANCE UNDERWRITER REQUIREMENTS
11. ALL ADDITIONAL REQUIREMENTS OF FIRE MARSHAL HAVING JURISDICTION
OFFICES, AND SIMILAR AREAS:
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
SYSTEM TYPE: WET PIPE
DESIGN DENSITY: 0.10 GPM/SF
HYDRAULIC REMOTE AREA: 1,500 SF
SPRINKLER ORIFICE SIZE: 1/2"
DURATION OF SUPPLY: 30 MIN.
MAXIMUM COVERAGE/SPRINKLER HEAD: 225 SF
HOSE STREAM ALLOWANCE: 100 GPM
STORAGE, MECHANICAL, ELECTRICAL ROOMS, AND SIMILAR AREAS:
OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP I
SYSTEM TYPE: WET PIPE
DESIGN DENSITY: 0.15 GPM/SF
HYDRAULIC REMOTE AREA: 1,500 SF
SPRINKLER ORIFICE SIZE: 1/2"
DURATION OF SUPPLY: 60-90 MIN.
MAXIMUM COVERAGE/SPRINKLER HEAD: 130 SF
HOSE STREAM ALLOWANCE: 250 GPM
CANOPIES AND COVERED PARKING:
OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP II
SYSTEM TYPE: WET PIPE
DESIGN DENSITY: 0.20 GPM/SF
HYDRAULIC REMOTE AREA: 1,500 SF
SPRINKLER ORIFICE SIZE: 1/2"
DURATION OF SUPPLY: 60 - 90 MIN.
MAXIMUM COVERAGE/SPRINKLER HEAD: 130 SF
HOSE STREAM ALLOWANCE: 250 GPM
EXISTING STANDPIPE:
SYSTEM DESCRIPTION: AUTOMATIC WET (CLASS I - COMBINED)
HYDRAULIC DESIGN CRITERIA: HYDRAULIC CALCULATIONS AND PIPE SIZES FOR EACH
STANDPIPE SHALL BE BASED ON PROVIDING 250 GPM AT
THE HYDRAULICALLY MOST REMOTE TWO HOSE
CONNECTIONS ON THE MOST REMOTE STANDPIPE AND
250 GPM FROM THE MOST REMOTE HOSE CONNECTION
ON EACH ADDITIONAL STANDPIPE AT A MINIMUM
RESIDUAL PRESSURE OF 199 PSI AT THE HOSE VALVE
OUTLET. ASSUME A FIXED PRESSURE LOSS OF 5 PSI
ACROSS THE HOSE VALVE, WHICH EQUATES TO AN INLET
RESIDUAL PRESSURE TO THE HOSE VALVE OF 105 PSI.
STANDPIPE:
SYSTEM DESCRIPTION: MANUAL WET (CLASS I - COMBINED)
HYDRAULIC DESIGN CRITERIA: HYDRAULIC CALCULATIONS AND PIPE SIZES FOR EACH
STANDPIPE SHALL BE BASED ON PROVIDING 500 GPM AT
THE HYDRAULICALLY MOST REMOTE TWO HOSE
CONNECTIONS ON THE MOST REMOTE STANDPIPE AND
250 GPM FROM THE MOST REMOTE HOSE CONNECTION
ON EACH ADDITIONAL STANDPIPE. PRESSURE SUPPLIED
HALL MEET HYDRAULIC DEMAND FOR THE MOST REMOTE
SPRINKLER ZONE. PRESSURE INCREASE FOR HOSE
STREAM TO BE PROVIDED VIA FDC AND FIRE
DEPARTMENT PUMP TRUCK. ASSUME A FIXED PRESSURE
LOSS OF 5 PSI ACROSS THE HOSE VALVE, WHICH
EQUATES TO AN INLET RESIDUAL PRESSURE TO THE
HOSE VALVE OF 105 PSI.
FLOW TEST DATA
WATER SUPPLY NOTES:
1. THERE HAVE BEEN NO REPORTED CASES OF M.I.C.
THE PROJECT SCOPE DOES NOT INCLUDE THE HYDRAULIC REMOTE AREA IN THE BUILDING. THE
MODIFICATIONS REQUIRED TO PROVIDE PROTECTION FOR THE PROPOSED TENANT IMPROVEMENT
ARCHITECTURAL LAYOUT IS NOT ANTICIPATED TO RESULT IN HYDRAULICALLY DETRIMENTAL
EFFECTS. HOWEVER, IF REQUIRED BY THE AHJ, THE CONTRACTOR SHALL PROVIDE COMPLETE
SYSTEM DESIGN DOCUMENTS WITH SUPPORTING HYDRAULIC CALCULATIONS.
FIRE SPRINKLER SCHEDULE
QUICK155° 6.9 WHITE V3426 RESIDENTIAL - PENDENT - SEMI-RECESSED WHITE VICTAULIC1/2"
RESPONSETEMP MFG.TRIMSTYLEMODELFINISHK-FACORFSYMBOL
5.6 V2710 HORIZONTAL SIDEWALL - SEMI-RECESSED
BRASS V2704 UPRIGHT N/A
WHITE V3606 DRY PENDENT - SEMI-RECESSED WHITE
V2708 PENDENT - SEMI-RECESSED
BRASS V3802 PENDENT - CONCEALED
R
WHITE V3610 HORIZ. DRY SIDEWALL - SEMI-RECESSED
VICTAULIC
QUICK155° WHITE WHITE VICTAULIC1/2"
5.6QUICK155°1/2"
VICTAULIC5.6QUICK155°1/2"
WHITE WHITE VICTAULIC5.6QUICK155°1/2"
WHITE VICTAULIC5.6QUICK155°1/2"
WHITE VICTAULIC5.6QUICK155°1/2"
PIPE
PACK CERAMIC FIBER OR
MINERAL WOOL TO RETAIN
MATERIAL SEALANT
PIPE SLEEVE
CAULK ANNULAR SPACE
W/NON-HARDENING SEALANT
TO A WET DEPTH OF 1" MIN
NON-FIRE RATED WALL
CHROME PLATED STEEL
ESCUTCHEON PLATE
WHEN PIPE SLEEVE IS
EXPOSED TO VIEW (TYP)
PIPE INSULATION
CONTINUOUS
THROUGH WALL
CAULK ANNULAR SPACE WITH
NON-HARDENING SEALANT
PIPE HANGER SCHEDULE
TYPE OF PIPE SIZE OF PIPE HANGER SPACING
STEEL THREADED PIPE
3/4" SIZE & SMALLER
1" SIZE & LARGER
10 FT. INTERVALS
12 FT. INTERVALS
6 FT. INTERVALS
10 FT. INTERVALS
1-1/4" SIZE & SMALLER
1-1/2" SIZE & LARGER
COPPER TUBE
4' INTERVALS
PROVIDE SUPPORTS AT END OF
ALL BRANCHES AND AT ALL
CHANGES OF DIRECTION & ELEVATION
ALL SIZESPLASTIC PIPE
CAST IRON PIPE ALL SIZES
MINIMUM OF 1 HANGER PER PIPE
LENGTH LOCATED WITHIN 18" OF EACH
JOINT (UP TO 10' MAXIMUM), AT
BRANCH CONNECTIONS
1" DROP
SPRINKLER HEAD
1" 90° ELL
1" 90° ELL
REDUCER BRANCH LINE
CEILING
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
FP0.1
LEGENDS AND GENERAL NOTES
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
1/8" = 1'-0"
PIPE SLEEVE THRU CMU WALL
1/8" = 1'-0"
PIPE HANGER SCHEDULE
1/8" = 1'-0"
TYPICAL RETURN BEND
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
06/29/2026
PART 1 - GENERAL
1.01 SUMMARY
A. GENERAL: PROVIDE THE FIRE PROTECTION SYSTEMS INDICATED ON THE DRAWINGS AND WITHIN THIS
SPECIFICATION SECTION.
1.02 SUBMITTAL
A. MANUFACTURER'S LITERATURE: PROVIDE DIMENSIONAL OUTLINE DRAWING, PRODUCT DATA, AND
VERIFICATION OF UL/FM APPROVAL FOR ALL FIRE PROTECTION EQUIPMENT AND PRODUCTS.
B. PIPING SHOP DRAWINGS: SUBMIT 1/8" SCALE PIPING SHOP DRAWINGS. SHOP DRAWINGS SHALL INCLUDE AT A MINIMUM; A SITE PLAN, SPRINKLER PIPING CUT SPRINKLER HEAD COUNT BY TYPE, ELEVATION SECTIONS, AND
OTHER INSTALLATION INFORMATION.
C. SUBMIT HYDRAULIC CALCULATIONS PROVING THE VIABILITY OF THE MOST HYDRAULICALLY REMOTE AREA OF THE PROJECT. INDICATE HYDRAULIC REFERENCE POINTS AND SUBMIT COMPUTER ANALYZED NODAL CALCULATIONS IN BOTH TABULAR AND GRAPHICAL FORMATS. HYDRAULIC IMBALANCE SHALL NOT EXCEED
0.01 GPM AT ANY NODE, AND WATER VELOCITY SHALL NOT EXCEED 20 FEET PER SECOND. DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF NFPA 13 REGARDING DENSITY, AREA OF APPLICATION, SELECTION OF HYDRAULICALLY REMOTE AREAS, AND MAXIMUM COVERAGE PER SPRINKLER.
1.03 APPLICABLE STANDARDS
A. EDITIONS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) CODES, OR THE LATEST REVISIONS OF
THESE CODES AS ADOPTED BY THE AUTHORITY HAVING LAWFUL JURISDICTION, AS FOLLOWS:
1. NFPA - FIRE SPRINKLER SYSTEM: THE FIRE SPRINKLER PROTECTION SYSTEMS INSTALLATION, FLUSHING
AND TESTING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13 AND NFPA 24.
B. UL/FM APPROVAL: ALL EQUIPMENT, PIPING, FITTINGS, VALVES, COUPLINGS, HANGERS, AND DEVICES SHALL
BE APPROVED BY UNDERWRITERS' LABORATORY (UL) AND FACTORY MUTUAL (FM) FOR USE IN FIRE
PROTECTION SERVICE.
C. LICENSURE: THE FIRE PROTECTION SYSTEMS SHALL BE INSTALLED BY A STATE OF FLORIDA LICENSED FIRE
PROTECTION CONTRACTOR.
PART 2 - PRODUCTS
2.01 MANUFACTURER
A. SINGLE MANUFACTURER: ALL ITEMS OF A SIMILAR TYPE SHALL BE BY THE SAME MANUFACTURER.
2.02 SPRINKLERS
A. PROVIDE SPRINKLERS OF PROPER TYPES, RATINGS, AND SPACING FOR THE AREAS INVOLVED. PROVIDE APPROPRIATE FINISHES COMPATIBLE WITH SPACE FINISHES BEING SERVED. MANUFACTURER: VICTAULIC OR
APPROVED EQUAL. SEE SPRINKLER SCHEDULE.
B. SPARE FIRE SPRINKLER HEAD CABINETS: PROVIDE SUFFICIENT SPARE SPRINKLER HEAD CABINETS TO STORE THE REQUIRED QUANTITIES OF SPRINKLER HEADS. STORAGE CABINETS SHALL BE RED GLASS, POLYESTER- COATED STEEL CONSTRUCTION. PROVIDE A MINIMUM OF SIX SPARE HEADS OF EACH TYPE AND EACH DIFFERENT TEMPERATURE RATING INSTALLED; PROVIDE 2 INSTALLATION TOOLS OR WRENCHES WITH EACH DIFFERENT TYPE OF SPRINKLER HEAD. CABINET SHALL HAVE CATCH-LOCK AND CONTINUOUS PIANO HINGE.
LOCATE THE SPARE SPRINKLER HEAD CABINET(S) AS DIRECTED BY THE OWNER'S REPRESENTATIVE.
C. SPRINKLER CAGE GUARDS: PROVIDE SPRINKLER HEAD OPEN-WIRE CAGE GUARDS TO PROTECT SPRINKLER HEADS WHERE REQUIRED. CAGE WIRE SHALL BE CADMIUM-PLATED STEEL. INSTALL CAGE GUARDS IN MECHANICAL ROOMS AND ELECTRICAL ROOMS OR ELSEWHERE WHERE SPRINKLER HEADS ARE EXPOSED TO
POTENTIAL DAMAGE.
2.03 PIPE AND FITTINGS
A. ABOVE GROUND PIPE AND FITTINGS: STEEL
1. ABOVE SLAB PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE CONFORMING TO ASTM A135 OR ASTM
A53 (2" AND SMALLER), AND SCHEDULE 10, ASTM A135 (2-1/2" AND LARGER).
2. BELOW SLAB AND BELOW GRADE PIPING AT THE SERVICE ENTRY SHALL BE CEMENT LINED DUCTILE IRON
PIPE WITH RESTRAINED JOINTS OR UL/FM APPROVED TYPE 304 STAINLESS STEEL SINGLE EXTENDED 90
DEGREE FITTING FIRE RISER (AMES FIRE & WATERWORKS OR EQUAL).
3. DRY PIPE SPRINKLER SYSTEM PIPING SHALL BE HOT DIPPED GALVANIZED STEEL.
4. FITTINGS:
a. CAST IRON THREADED FITTINGS, ANSI B16.4 CLASS 125.
b. CAST IRON FLANGED FITTINGS, ANSI B16.1 CLASS 125.
c. MECHANICAL JOINT, GROOVED COUPLINGS, AS MANUFACTURED BY VICTAULIC, ANVIL, S.P. FITTINGS
(STAR), OR CENTRAL. ALL GROOVE COUPLINGS AND FITTINGS SHALL BE FURNISHED BY A SINGLE
MANUFACTURER.
d. SYSTEM PRESSURES EXCEEDING 175 PSI SHALL HAVE CAST IRON THREADED FITTINGS, GROOVE
COUPLINGS AND FLANGED FITTINGS, CLASS 250 RATED FOR A MINIMUM 400 PSI.
5. PIPING FOR DRAINAGE SYSTEMS SHALL BE SCHEDULE 40 OR 10 GALVANIZED STEEL PIPE, ASTM A795 OR A135 WITH GALVANIZED THREADED FITTINGS, ANSI B16.4, GALVANIZED COATED, BOTH INTERIOR AND
EXTERIOR OF PIPE AND FITTINGS.
B. PIPE AND FITTING ALTERNATE:
1. CPVC FIRE SPRINKLER PIPE AND FITTINGS. THE PIPE AND FITTING COMPOUNDS SHALL MEET CELL CLASS
23547 AND 24447, RESPECTIVELY, AS DEFINED BY ASTM D1784, AND SHALL BE CERTIFIED BY NSF INTERNATIONAL FOR USE WITH POTABLE WATER. BOTH PIPE AND FITTING COMPOUNDS SHALL BE
PRESSURE RATED BY PLASTICS PIPE INSTITUTE (PPI).
2. ACCEPTABLE MANUFACTURERS:
a. BLAZEMASTER® BY LUBRIZOL ADVANCED MATERIALS.
b. FLAMEGUARD® BY SPEARS MANUFACTURING COMPANY.
3. PIPE SHALL MEET OR EXCEED THE REQUIREMENTS OF ASTM F442 IN STANDARD DIMENSION RATIO (SDR) 13.5.
4. FITTINGS SHALL MEET OR EXCEED THE REQUIREMENTS OF ASTM F437 (SCHEDULE 80 THREADED), ASTM
F438 (SCHEDULE 40 SOCKET) AND ASTM F439 (SCHEDULE 80 SOCKET).
5. BOTH PIPE AND FITTINGS SHALL BE LISTED BY UL FOR USE IN WET AUTOMATIC FIRE SPRINKLER SYSTEMS AND SHALL BEAR THE LOGO OF THE LISTING AGENCY. SEE UL FIRE PROTECTION EQUIPMENT DIRECTORY, CATEGORIES VIWT AND HFYH.
6. ANCILLARY PRODUCTS COMING INTO CONTACT WITH PIPE AND FITTINGS MUST BE CHEMICALLY
COMPATIBLE AS DETERMINED BY CPVC PIPE AND FITTINGS MANUFACTURER OR COMPOUND
MANUFACTURER, AND THUS LISTED ON PIPE, FITTINGS, OR COMPOUND MANUFACTURER’S CHEMICAL
COMPATIBILITY PROGRAM (I.E. FGG/BM/CZ™ SYSTEM COMPATIBLE PROGRAM).
C. SOLVENT CEMENT
1. ALL SOCKET TYPE JOINTS SHALL BE MADE UP EMPLOYING SOLVENT CEMENTS THAT MEET OR EXCEED
THE REQUIREMENTS OF ASTM F493. THE STANDARD PRACTICE FOR SAFE HANDLING OF SOLVENT CEMENTS SHALL BE IN ACCORDANCE WITH ASTM F402. SOLVENT CEMENT SHALL BE LISTED BY NSF
INTERNATIONAL FOR USE WITH POTABLE WATER, AND APPROVED BY THE MANUFACTURER. THE
SOLVENT CEMENTS SHALL BE COMPATIBLE WITH THEIR CPVC PIPE AND FITTINGS.
2. FOLLOW MANUFACTURER’S INSTRUCTIONS FOR SET AND CURE TIMES FOR SOLVENT CEMENT JOINTS.
AVOID SIGNIFICANT STRESSES DURING SET AND CURE TIMES. DO NOT APPLY ANY STRESS THAT WILL DISTURB AN UN-DRIED JOINT. SPRINKLER FITTINGS SHALL BE ALLOWED TO CURE IN ACCORDANCE WITH THE MANUFACTURER’S GUIDELINES AND THE CONTRACTOR SHALL ASSURE THE OUTLETS ARE CLEAR OF
ANY EXCESS CEMENT PRIOR TO INSTALLING SPRINKLERS.
2.04 HANGERS, SUPPORTS, AND SLEEVES:
A. SUPPORT PIPING WITH UL AND FM APPROVED HANGERS. HANGERS AND RODS SHALL BE GALVANIZED.
B. ACCEPTABLE MANUFACTURERS: GRINNELL, B-LINE, HILTI, FEE & MASON, MICHIGAN, AND PHD.
C. ADJUSTABLE CLEVIS HANGER: GRINNELL FIG. 260.
D. ADJUSTABLE SWIVEL LOOP HANGER: GRINNELL FIG. 69.
E. BEAM CLAMP: GRINNELL FIG. 92 AND GRINNELL FIG. 218.
F. CONCRETE FASTENERS: GRINNELL STEEL SHELL AND EXPANDER PLUG.
G. CONCRETE INSERT: GRINNELL FIG. 152.
H. RISER CLAMP: GRINNELL FIG. 261.
I. POWDER-DRIVEN INSERTS SHALL NOT BE ACCEPTED.
J. THREADED RODS SHALL BE GALVANIZED COATED. ALL HANGERS SHALL BE GALVANIZED COATED.
FIRE PROTECTION SPECIFICATIONS
2.05 FIRE STOPPING:
A. ALL PIPES PASSING THROUGH RATED FLOORS OR WALLS SHALL BE SLEEVED AND FIRESTOPPED TO AN EQUIVALENT RATING OF THE FLOOR OR WALL ASSEMBLY. FIRESTOP MATERIALS SHALL MEET ASTM E814
REQUIREMENTS.
B. ACCEPTABLE MANUFACTURERS: HILTI AND 3M.
2.06 VALVES
A. ACCEPTABLE VALVE MANUFACTURERS: STOCKHAM, NIBCO, VICTAULIC, GRINNELL, MUELLER, KENNEDY, CRANE, AND CENTRAL.
B. INTERIOR VALVES:
1. CHECK VALVES:
a. IRON BODY, STOCKHAM G-939 SWING CHECK VALVE, FLANGED BODY.
b. BRONZE BODY, NIBCO KT-403-W THREADED CHECK VALVE WITH DIELECTRIC UNIONS.
c. GROOVED IRON BODY, CENTRAL CV-1F CHECK VALVE.
d. WAFER CHECK, CENTRAL MODEL "B", WAFER CHECK VALVE.
e. RISER CHECK, CENTRAL AV-1-175 ALARM CHECK VALVE.
2. GATE VALVES:
a. IRON BODY, O.S.&Y. GATE VALVES, STOCKHAM G-634, FLANGED AND G-633 THREADED.
b. BRONZE BODY, O.S.&Y. GATE VALVE, NIBCO T 104-0, THREADED WITH DIELECTRIC UNIONS.
3. BUTTERFLY VALVES (WITH INTEGRAL TAMPER SWITCH):
a. GROOVED, 2-1/2" THROUGH 12", NIBCO GD-4765-8N.
b. GROOVED, 1" THROUGH 2-1/2", MILWAUKEE BUTTERBALL.
4. FIRE DEPARTMENT CONNECTION:
a. WALL MOUNTED SIAMESE APPLICATIONS: CAST BRASS TWO-WAY INLET BODY, SWING CLAPPER AND
PIN LUG SWIVEL, PIN LUG PLUGS WITH CHAINS, BACK OUTLET WITH WALL ESCUTCHEON PLATE
LETTERED "AUTO SPKR", SIZE 4" X 2-1/2" X 2-1/2", POTTER ROEMER MODEL 5710.
b. REMOTE FREESTANDING APPLICATIONS: CAST BRASS ANGLE BODY, SIZE OF OUTLET AND NUMBER OF INLETS AS INDICATED ON PLANS; CAST BRASS IDENTIFICATION BASE PLATE; CAST BRASS PLUGS AND CHAINS ON EACH PIN LUG SWIVEL, ROUGH CHROME PLATED BODY WITH POLISHED CHROME PLATED
TRIM.
2.07 SUPERVISORY SWITCHES AND WATERFLOW DEVICES
A. ACCEPTABLE MANUFACTURERS: POTTER ELECTRIC SIGNAL CO., POTTER-ROEMER, SYSTEM SENSOR, SIMPLEX, AND GEM.
B. GATE VALVE TAMPER SWITCH: PROVIDE AN ELECTRONIC SUPERVISORY TAMPER SWITCH ON EACH ISOLATION VALVE IN THE SPRINKLER SYSTEM. UNIT SHALL HAVE A RED TAMPER-PROOF COVER, WHICH WILL ACTIVATE AN ALARM OR TROUBLE SIGNAL WHEN ADJUSTED. PROVIDE UNIT WITH SINGLE-POLE, DOUBLE THROW
SWITCHES, AND MOUNTING BRACKET, POTTER ELECTRIC SIGNAL CO. OSYSU-1.
C. FLOW SWITCH: PROVIDE AN ELECTRIC FLOW SWITCH WHERE INDICATED OR REQUIRED. FLOW SHALL BE SENSED BY AN IMMERSION PADDLE, WITH AN ADJUSTABLE RETARD SETTING FROM 0 TO 70 SECONDS TO MINIMIZE FALSE ALARMS. FLOW SWITCH SHALL HAVE SINGLE-POLE, DOUBLE THROW SWITCHES TO ACTIVATE A FLOW ALARM, OR TO INDICATE A TROUBLE SIGNAL IF THE FLOW SWITCH HOUSING IS TAMPERED. FLOW ALARM SHALL BE AUTOMATICALLY RESETTING. PROVIDE CLAMP-ON HOUSING TO SECURE UNIT TO PIPE, OR
THREADED CONNECTION FOR TEE FITTING, POTTER ELECTRIC SIGNAL CO. VSR-F.
2.08 INSPECTOR'S TEST AND DRAIN
A. ACCEPTABLE MANUFACTURERS: G/J INNOVATIONS, AGF MANUFACTURING, AND TESTDRAIN.
B. SIGHT DRAIN: SIGHT DRAIN SHALL HAVE 2 VIEW WINDOWS TO PROVIDE VISUAL OBSERVATION OF WATER FLOW, AND SHALL HAVE FEMALE THREADED CONNECTIONS, POTTER-ROEMER 6171/6172/6173/6174.
C. INSPECTOR'S TEST AND DRAIN: TEST AND DRAIN SHALL BE PROVIDED WITH INTEGRAL SIGHT GLASS, INTEGRAL 1/2 INCH TEST ORIFICE AND POSITIVE POSITIONING OF HANDLE FOR OFF, TEST, AND DRAIN
OPERATIONS, G/J INNOVATIONS, INC "SURE-TEST".
PART 3 - EXECUTION
3.01 INSTALLATION
A. HANGERS: ALL HANGER SPACING SHALL COMPLY WITH REQUIREMENTS OF NFPA 13.
B. SPRINKLER HEAD LOCATION: INSTALL SPRINKLER HEADS IN THE CENTER OF THE CEILING TILES FOR
SUSPENDED CEILING APPLICATIONS.
C. SPRINKLER HEAD LOCATION: SPRINKLER HEADS SHALL BE INSTALLED NO CLOSER THAN 4 INCHES TO ANY
CEILING GRID OR WALL.
D. GAUGES: PROVIDE GAUGE ON EACH SPRINKLER SYSTEM CONTROL ASSEMBLY. GAUGE SCALE SHALL BE 0-300
PSI UNLESS OTHERWISE INDICATED.
E. FLUSHING: THE ENTIRE SYSTEM SHALL BE FLUSHED WITH CLEAN WATER TO REMOVE DEBRIS RESULTING
FROM INSTALLATION. FLUSH THROUGH A BURLAP BAG TO RETAIN DEBRIS FOR EXAMINATION.
F. PROHIBITED: DO NOT PAINT THE COVERS OF CONCEALED SPRINKLERS.
G. PROVIDE DRAIN VALVES, PIPES AND TEST CONNECTIONS AS REQUIRED BY NFPA 13. PIPE DRAIN LINES AND
TEST CONNECTIONS TO EXTERIOR OF THE BUILDING, DRAIN RISER, OR APPROVED LOCATION.
H. DRAIN PLUGS SHALL BE INSTALLED ON TRAPPED SECTIONS OF PIPING 5 GALLONS OR LESS. AUXILIARY DRAIN VALVES 3/4 INCH OR LARGER AND PLUGS SHALL BE INSTALLED ON TRAPPED SECTIONS OF PIPE GREATER
THAN 5 GALLONS.
I. HEAT TRACE SYSTEM: COORDINATE INSTALLATION WITH FIRE ALARM CONTRACTOR AND GENERAL
CONTRACTOR PRIOR TO START OF WORK.
3.02 HYDROSTATIC TESTS
A. GENERAL: ABOVE GROUND PIPING SYSTEMS SHALL BE HYDROSTATICALLY TESTED AT NOT LESS THAN 200 PSI PRESSURE, OR AT 50 PSI IN EXCESS OF THE MAXIMUM PRESSURE, WHICHEVER IS GREATER, FOR A PERIOD OF 2 HOURS. TEST PRESSURE SHALL BE READ FROM A GAUGE LOCATED AT THE LOW ELEVATION POINT OF THE INDIVIDUAL SYSTEM OR PORTION OF THE SYSTEM BEING TESTED. THE UNDERGROUND PIPING SHALL NOT HAVE LEAKAGE EXCEEDING THE AMOUNTS SPECIFIED IN NFPA 24. LEAKAGE QUANTITIES SHALL BE DETERMINED BY PUMPING AT THE SPECIFIED TEST PRESSURE FROM A CALIBRATED CONTAINER. REPAIR LEAKING JOINTS AND RETEST AS NECESSARY UNTIL ALL SYSTEMS HAVE BEEN TESTED. TEST THE PIPING BETWEEN THE CHECK VALVE IN THE FIRE DEPARTMENT INLET PIPE AND THE OUTSIDE CONNECTION THE
SAME AS THE BALANCE OF THE SYSTEM.
3.03 SYSTEM INSPECTION AND CHECKOUT GENERAL
A. AFTER INSTALLATION IS COMPLETE, THE SYSTEM SHALL BE INSPECTED BY FACTORY TRAINED PERSONNEL IN
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDED PROCEDURES.
B. SYSTEM OPERATION: OPERATE SYSTEMS AS REQUIRED TO DEMONSTRATE THE SYSTEMS ARE OPERATING IN ACCORDANCE WITH THE DESIGN, INCLUDING LINE PRESSURE TESTING. SUPPLY INSTRUMENTS REQUIRED TO READ DATA. ADJUST SYSTEMS TO OPERATE AT THE REQUIRED PERFORMANCE LEVELS. ADVISE ARCHITECT 7 DAYS PRIOR TO TESTING. TABULATE DATA AND SUBMIT ON 8-1/2 X 11-INCH SHEETS WITH TIME, NAME OF TESTER, AND THE LOCAL AUTHORITY HAVING JURISDICTION WITNESSING THE TEST, WITH ONE COPY FOR
EACH TECHNICAL INFORMATION BROCHURE.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
FP0.2
SPECIFICATIONS
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
PREPARE EXISTING FIRE SPRINKLER PIPING AND
HEADS TO ACCOMMODATE NEW FLOOR PLAN.
THIS AREA CURRENTLY NOT SPRINKLERED.
PREPARE EXISTING
FIRE SPRINKLER
PIPING AND HEADS
TO ACCOMMODATE
NEW FLOOR PLAN.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
FP1.0
FIRST FLOOR DEMOLITION PLAN
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-0153/16" = 1'-0"FP1.0
1 DEMOLITION FLOOR PLAN
N
OFFICE
OPEN OFFICE
OPEN OFFICE
LOCKER ROOM
BREAK ROOM
RESTROOM
RESTROOM
NAPA ROOM
LIGHT HAZARD
U.N.O.
0.10 GPM / SF
ORDINARY
HAZARD
GROUP I
0.15 GPM / SF
ORDINARY
HAZARD
GROUP I
0.15 GPM / SF
JAN.
MECH
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2025 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
STRUCTURAL ENGINEER
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
coa #31580
SEAL
Hall Darling Design Studio, PA
AR 97844
2168 Main Street
Sarasota, FL 34237
P:941.917.0883 genesis engineering
6700 professional pkwy w sarasota, fl 34275 www.geneng.net group, llc.
project #: 25-011
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING A SHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
FP2.0
PROPOSED FIRST FLOOR PLAN
SARASOTA COUNTY FLEET SOUTH
RENOVATION
06.26.2026
4571 STATE ROAD 776, VENICE,
FL 34293
PERMIT
24-015
3/16" = 1'-0"FP2.0
1 PROPOSED FLOOR PLAN - WEST
N
| Sheets |
| FP0.1 - LEGENDS AND GENERAL NOTES |
| FP0.2 - SPECIFICATIONS |
| FP1.0 - FIRST FLOOR DEMOLITION PLAN |
| FP2.0 - PROPOSED FIRST FLOOR PLAN |