Statement of Work_Redacted.pdf
PDF 384 KB Posted
- Attached to
- PURCHASE/INSTALL AIR COMPRESSOR AND SUPPORTING EQUIPMENT IN BLDG 1343 AND CONNECT ELECTRICIAL
- Solicitation number
- FA282325Q3006
About this file
This Statement of Work (SOW) details a project to procure and install a new air compressor with supporting equipment in Building 1343 at Eglin Air Force Base, Florida. The project requires a 50 hp variable speed compressor and dryer providing 200+ CFM at 150 PSI, including plumbing for air and power, with a minimum 1-year warranty. The contractor must handle equipment installation, electrical work (including potential disconnect switch and breaker upgrades), and comply with fire protection, life safety, and OSHA standards.
Key requirements include turn-key installation of the compressor system, adherence to UFC 3-600-01 and NFPA standards, and strict safety protocols. The contractor must notify the 96 TW Safety Office within one hour of any mishaps involving property damage or personnel injuries. Subcontractors must also comply with safety provisions, and the contractor cannot use hallways for storage. Required documentation includes various site and floor plans, with the project expected to be completed according to all applicable construction codes and safety standards.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The new disconnect switch needs to be fused IF the contractor doesn’t swap out the breaker in the panel to the correct amperage of the compressor.
If the disconnect switch is not fusible, then the breaker will need to be swapped out to the correct amperage as well.”
c. FIRE PROTECTION and LIFE SAFETY:
i. The Contractor is expected to maintain, at all times, good and accepted construction practices and comply with OSHA safety standards.
ii. All work shall be in accordance with the latest NFPA and NEC requirements to ensure maximum protection against loss of life and property by fire.
iii. Design and installation must meet all UFC 3-600-01 and applicable NFPA Standards.
1. Any sprinkler system modification must be IAW UFC 3-600-01 Chapters 9-6 & 9-7, and all testing must be IAW NFPA 13 (Current Edition).
2. Any fire alarm system modification must be IAW UFC 3-600-01 Chapter 9-18, and all testing must be IAW NFPA 72 (current edition).
d. SPECIAL INSTRUCTIONS:
3. MISHAP NOTIFICATION REQUIREMENTS for CONTRACTORS PER DAFI 91-
204, para 2.4.4.: The contractor shall notify the 96 TW Safety Office telephonically within one (1) hour after initial notification of all mishaps or incidents involving damage to DoD property (material plus labor) or injuries to government personnel because of contractor operations and work-related injury to contractor personnel that results in fatality, in-patient hospitalization, amputation, or eye loss. The Safety Office can be reached at (850) 882-2540 extension 3 during duty hours and (850) 883-4020 after hours. Initial written confirmation of the mishap must be forwarded within five (5) calendar days to the Contracting Officer (CO) who will forward the report to 96 TW/SEG (Safety Office) 96TW.SEG.OccupationalSafety@us.af.mil. A complete report shall be provided within 5 calendar days after the mishap.
a. Mishap notification shall contain, as a minimum, the following information:
i. Contract, Contract Number, Name and Title of Person(s) Reporting
ii. Date, Time, and exact location of accident/incident
iii. Brief Narrative of accident/incident (Events leading to accident/incident)
iv. Cause of accident/incident, if known
v. Estimated cost of accident/incident (material and labor to repair/replace)
vi. Nomenclature of equipment and personnel involved in accident/incident
vii. Corrective actions (taken or proposed)
b. The contractor shall immediately secure the mishap scene/damaged property and impound pertinent maintenance and training records until released by the 96 TW
File details come from the government source that posted it. Updated .