This document is a Questions and Answers (Q&A) file for Solicitation FA282325Q3006, which involves purchasing and installing an air compressor and supporting equipment in Building 1343 at Eglin Air Force Base. The Q&A addresses technical specifications for the air compressor system, including flow requirements (200 CFM at 150 PSI or alternatively 200+ CFM at 125 PSI), dryer configuration (internal refrigerated air dryer preferred), filtration requirements (meeting ISO 8573-1:2010 class purity), and EPA-mandated oil water separator. Key technical details revealed include flexibility in compressor specifications, confirmation of an existing (likely abandoned) compressor setup in the building, and environmental compliance requirements for condensate discharge and filtration.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA282325Q3006 PURCHASE/INSTALL AIR COMPRESSOR AND SUPPORTING

EQUIPMENT IN BLDG 1343 AND CONNECT ELECTRICIAL

Questions and answers

Q: Can you tell me if there is an existing compressor setup in the building?

A: There is. Likely abandon in place

Q: Flow requirements:

Are the flow requirements for the system hard set to be 200CFM at 150PSI? A: It is optimal.

If 150PSI is not needed for your end use, a 40HP compressor could produce 200+ CFM at 125PSI. A: This would work

Q: Dryer:

Are you requiring a standalone air dryer? A: No We offer our rotary screw compressors with an internal refrigerated air dryer, saving on space and maintenance. A: Ok

Q: Filtration:

Is there a specific ISO 8573-1:2010 class purity your trying to reach?

I know that the Mikropor dryer has internal filtration, as well as the standalone carbon filter for oil removal to .003ppm. Should we try to meet their specifications? A: Yes

Q: Will there need to be an oil water separator? A: Yes Oil water separators are required by the EPA for all the condensate discharge leaving the compressor, filters, tanks, and dryers. This ensures that there is no oil carryover in the waste water drains.