This document is a technical survey report on floor vibration noise conducted at the Advanced Photon Source (APS) experiment hall at Argonne National Laboratory. The study measured vibration displacement across 35 different beamlines in three directional axes (X, Y, Z) using high-sensitivity accelerometers. Key findings include that beamlines 10-20 demonstrated particularly low vibration levels, and throughout most of the 5-100 Hz vibration spectrum, the beamlines fell below the most stringent NEST vibration criteria.

The researchers discovered two primary trends: first, the vibration magnitude of a column floor strongly correlates with the nearby beamline floor's vibration magnitude, particularly in lower frequency bands. Second, a specific region of the experiment hall (beamlines 10-20) exhibited notably low vibration magnitudes. During a special measurement where mechanical equipment was powered off, the study found that columns represent a significant vibration source, contributing approximately a half-order of magnitude increase in vibrations at various frequencies. The researchers concluded that the entire APS experiment hall is an extremely quiet facility, which provides an excellent foundation for sensitive experimental equipment.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A Survey of Floor Vibration Noise at all Sectors in the APS Experiment Hall

Steven Kearney1 and Deming Shu1

1X-ray Science Division, APS, Argonne National Laboratory, Argonne, IL. 60439

ANL/APS/LS-344

A vibration survey of the APS experiment hall floor was conducted. It was found that beamlines 10-20 have particularly low levels of vibration when compared to the rest of the facility.

The vibration spectrum for each beamline floor can be found in the appendix. Throughout the majority of the 5-100 Hz vibration spectrum beamlines at the APS fall below the most stringent

NEST vibration criteria. Lastly, it was concluded that the magnitude of vibrations at a particular beamline is largely dependent upon the magnitude of vibrations present at the nearby mezzanine support column.

1 Introduction

Vibration noise in the experiment hall of the Advanced Photon Source (APS) is a potential primary source of mechanical noise induced into experiments being conducted at the APS. Therefore, understanding the current levels of vibration and locations of particularly low and high vibrations is of upmost importance. In addition, with the planned APS upgrade new beamline construction and/or redesigns of existing beamlines is expected, so it is beneficial to know the current levels of vibration at these locations for planning purposes. This survey was conducted at each beamline of the APS and presents the findings with a brief analysis of potential vibration sources as well as identifying locations of low vibration noise.

2 Procedure

A vibration noise survey was conducted at the Argonne National Laboratory Advanced Photon

Source experiment floor. Data was recorded at all beamlines over multiple sessions. For consistency, measurements were only taken the day before the scheduled weekly machine intervention when most users were not running experiments, but with the beam still on. Also, to limit the influence of transient vibrations, data was recorded only after 5 pm or on the weekends.

The specific dates of measurement sessions were: 3/28/2016, 4/4/2016, 4/11/2016, 4/18/2016, 4/25/2016, and 6/12/2016. In addition, a separate special case data set was recorded in sector

21 during electrical maintenance (4/30/2016) in which the mechanical air handling unit, DI pumps, 3/4/20 and vacuum pumps, were shut down in sectors 20-23. This data was then used to assess the contribution of these systems to the vibration noise in sector 21. This is just a single sector comparison, but due to the modular similarity of mechanical equipment around the storage ring this can be assumed to represent typical mechanical noise contributions for all beamlines.

To measure the vibration noise, 3 high sensitivity accelerometers were used (VibraMetrics

1030, Mistras Group Inc., Princeton Junction, NJ) for each Cartesian direction, see Table 1. In line with the accelerometers were 3 power supplies for each channel (VibraMetrics P5000, Mistras

Group Inc., Princeton Junction, NJ). For data acquisition a Photon+ 4 channel (Brüel & Kjær) signal analyzer was used with RT Pro Version 7.20 dynamic signal analysis software (Brüel &

Kjær). The data acquisition settings can be seen in Table 2.

Data was acquired separately at all 35 beamlines of the APS. Two measurement points for each beamline were chosen based on similar construction geometry and for the best representation of vibrations for the entire beamline. These two points can be seen in Figure 1.

The column floor point is assumed to represent the majority of the noise source to the floor for the nearest beamline. This assumption comes from the fact that the column is a support structure for the mechanical equipment mezzanine floor. There are many more columns than there are beamlines so the column closet to the floor measurement point was chosen, see Table 3 for the specific column measured and which beamline it represents. Similarly, the beamline floor point is assumed to represent the noise present for that entire beamline. Notice that the red dashed line shows many potential measurement points. This is required due to the varying construction designs and surrounding equipment layout of each column and end station.

Table 1. Specifications and settings of accelerometers used for each channel recorded. See Figure 1 for specific channel location and coordinate frame.

Channel Direction Model No. Serial No. Gain Sensitivity [V/g]

1 X VibraMetrics 1030 1349 x1 7.088

2 Y VibraMetrics 1030 1625 x1 7.000

3 Z VibraMetrics 1030 1493 x1 7.010

Table 2. Parameter settings used in the RT Pro 7.2 dynamic signal analysis software for data acquisition.

Parameter Value Unit

Sampling Frequency 375 Hz

Number of Samples 4096

Bandwidth 150 Hz

Frequency Resolution 0.091 Hz

Window Hanning

Averages 20

For analysis, the data is presented in spectral RMS displacement and in one third octave bands. RMS displacement is derived from the raw accelerometer voltage data using

𝑈𝑟𝑚𝑠 = 𝑔𝑉𝑟𝑚𝑠

(gain)(sensitivity) , with 𝑔 = 9.81 𝑚 𝑠⁄ . (1)

The one third octave bands are defined as

𝑉𝑂𝑐𝑡𝑘 = √ ∑ 𝑉𝑟𝑚𝑠(𝑖)2,

𝑓ℎ𝑖𝑔ℎ(𝑘) 𝑖=𝑓𝑙𝑜𝑤(𝑘)

(2) with 𝑘 defined as the band number, 𝑖 representing each frequency bin, and 𝑁𝑘 the number of bins in band 𝑘. Additionally, the cumulative RMS displacement (Rogers et al. 1997) is defined as

𝑈𝑐𝑢𝑚𝑟𝑚𝑠 = ∑ 𝑈𝑟𝑚𝑠(𝑖), 𝑓ℎ𝑖𝑔ℎ(𝑘) 𝑓𝑙𝑜𝑤(𝑖)

(3)

In Equation (2) the units are still in RMS displacement with the RMS subscript removed for clarity.

Presenting the data in bands rather than full spectral plots allows for a quick and concise comparison of a single value for each beamline. For this study standard 1/3 octave bands were used and are listed in Table 4 as well as the number of frequency bins used in each band to calculate the mean.

Figure 1. A bird’s eye view of the two measurement points used for each beamline (not to scale).

On the left is the setup for the column floor measurement point and on the right the beamline floor measurement point. For both, the coordinate frame is shown in the lower left with X away from the storage ring center, Y in the vertical direction, and Z in the beam direction. The hutch end station is located in the -X direction on the opposite side of the expansion joint of the column.

The red dashed line represents potential placement locations of the sensor block, with the transparent blocks showing other potential locations, based on accessibility to the floor.

Table 3. Beamlines and the associated nearby column that was measured.

Beamline Column Beamline Column Beamline Column

1 C069C 13 C104C 25 C140C

2 C072C 14 C106C 26 C143C

3 C074C 15 C110C 27 C145C

4 C078C 16 C113C 28 C149C

5 C081C 17 C116C 29 C152C

6 C083C 18 C119C 30 C154C

7 C086C 19 C121C 31 C159C

8 C090C 20 C125C 32 C162C

9 C093C 21 C129C 33 C165C

10 C095C 22 C131C 34 C167C

11 C098C 23 C135C 35 C169C

12 C101C 24 C137C

Table 4. One third octave bands used in the comparison of beamlines with upper and lower frequency bounds listed and the number of frequency bins averaged, 𝑁𝑘.

Band flow [Hz] fhigh [Hz] Band flow [Hz] fhigh [Hz]

1 2.8 3.5 9 17.5 22.0

2 3.5 4.4 10 22.0 27.8

3 4.4 5.5 11 27.8 35.1

4 5.5 7.0 12 35.1 44.2

5 7.0 8.8 13 44.2 55.7

6 8.8 11.0 14 55.7 70.2

7 11.0 13.9 15 70.2 88.4

8 13.9 17.5 16 88.4 111.4

3 Results and Discussion

3.1 Experiment Hall Floor Vibration Levels

Each beamline was individually measured at two points, the floor next to the nearest column and the beamline floor just outside the end station hutch. Full X, Y, Z spectrums of vibration displacement for each beamline floor can be seen in the Appendix. Every individual beamline floor vibration spectrum (designated by the ID # in the title over each plot) displays the beamline in a bold black line, and, for comparison, the maximum/minimum, and mean of all APS beamline floor vibrations are plotted in solid gray and red dash dot lines, respectively. From these spectrums a trend starts to appear; a trend that beamlines close to each other tend to have similar levels of noise. This trend will be much more clear when we look at band data in the next section.

We can also use the entire set of beamline floor data to see the magnitude of vibrations in the APS experiment hall as a whole. Figure 2, displays the X, Y, Z spectral vibration magnitude range of all the beamlines. Figure 3 displays the vibration velocity RMS in 1/3 octave bands.

Included in this plot are a few of the most stringent standard vibration criteria (VC) created by the

Institute of Environmental Sciences and Technology (IEST) (Amick et al. 2005). Each curve is subsequently more sensitive and thus harder to achieve, with VC-E at 3.2 µm/s, VC-F at 1.56 µm/s, and VC-G at 0.78 µm/s. VC-E, is described as “Challenging to achieve … Assumed to be adequate for the most demanding of sensitive systems.”, with an achievable detail size in microelectronics fabrication of less than 100 nm. As can be seen in Figure 3 almost all of the floor vibrations are below the VC-E curve with the exception being the maximum line at 30 Hz. Even more encouraging is that the majority of vibration magnitudes are below the most stringent VC-G curve with only 5 peaks in the maximum line breaking the VC-G curve at 15 Hz, 18 Hz, 23 Hz, 30

Hz, and 60 Hz. Overall the entire APS experiment hall floor is an extremely quiet facility and a very good starting point to build the most sensitive equipment on. However, there is still room for improvement, particularly in the 10 – 60 Hz band, which will be made clearer in Section 3.3.

Figure 2. Vibration displacement spectrum of the entire experiment hall for all beamline floors in all 3 directions. The dashed line is the mean of all beamline floors, the solid black line represents the maximum and minimum vibrations of all beamlines.

Figure 3. One third octave bands of the entire experiment hall for all beamline floors in all 3 directions.

The dashed line is the mean of all beamline floors, the filled in area represents the minimum to maximum range.

Figure 4. Cumulative vibration displacement spectrum of the entire experiment hall for all beamline floors in all 3 directions. The dashed line is the mean of all beamline floors, the solid black line represents the maximum and minimum vibrations of all beamlines.

3.2 Comparison of Beamline Vibration Bands

One of the goals of this survey was to elucidate locations in the APS experiment hall that are particularly quiet. Using velocity RMS data for a particular octave band assigns a single scalar magnitude to a beamline for that band, which makes direct comparison of beamline to beamline much more straight forward. Figures 4-9, display the 1/3 octave bands for each beamline in the

X, Y, and Z directions, respectively. Also included are the velocity RMS vibrations for the columns as well.

From the band plots two trends can be seen. The first trend is that the higher the vibration magnitude in the column floor the higher the vibration magnitude of the beamline floor. This can be seen by following the trend of the column curve which then mirrors the beamline curves, particularly in the lower octave bands 1-11. In octave bands 12-16 we start to see a separation in magnitude, which makes sense as higher frequency vibrations dampen at a much greater rate than low frequency vibrations. However, even with the separation in magnitude the trends of column and beamline seem to still have the same general profile.

The second trend is that there is a clear region of the experiment hall that has particularly low magnitude vibrations. This region is located approximately in beamlines 10-20. However, in the bands 12-16 there seems to be a greater variation from beamline to beamline. Even beamlines right next to each other can have much higher vibration magnitudes, which is also reflected in the columns. This might be in direct response to a particularly noisy localized area in the mechanical mezzanine floor. There are also two major outliers. In the maximum extreme is beamline 29, and it is clear that column 152 nearby 29-ID is also particularly noisy. So, it is likely that the high vibrations at 29 are from some noisy source on the mezzanine nearby. On the other hand, is the minimum extreme, and this is located at beamline 16, especially in the Y direction. Beamline 16-

ID is unique in that the floor is actually a bridge over a road access tunnel. It is possible that being constructed on a bridge structure the floor is more isolated from the lower frequency noise associated with ground motion and traffic, and that noise from the mechanical equipment on the mezzanine floor has a longer direct path to the beamline floor allowing for greater damping of vibrations by the time they reach the measurement point.

Figure 5. Comparison of column and floor vibrations in 1/3 octave bands 1-8 for each beamline in the X-direction.

Figure 6. Comparison of column and floor vibrations in 1/3 octave bands 9-16 for each beamline in the

X-direction.

Figure 7. Comparison of column and floor vibrations in 1/3 octave bands 1-8 for each beamline in the Y-

Figure 8. Comparison of column and floor vibrations in 1/3 octave bands 9-16 for each beamline in the

Y-direction.

Figure 9. Comparison of column and floor vibrations in 1/3 octave bands 1-8 for each beamline in the Z-

Figure 10. Comparison of column and floor vibrations in 1/3 octave bands 9-16 for each beamline in the

Z-direction.

3.3 Contribution of Mechanical Equipment to Noise

In addition to the survey of floor vibrations a unique opportunity presented itself to measure the floor vibrations while the power to mechanical equipment was off. Vacuum pumps, DI pumps, and air handling equipment, all located on the mezzanine floor, were shut off for electrical maintenance in sectors 20-23. The same measurement points as when power was on during the initial survey was then measured again during the shutdown for beamline 21.

First, looking at the difference in column floor vibrations with power on and off, see Figure

11, we can see that there is a noticeable reduction in vibration magnitude throughout much of the spectrum. This is particularly evident in the X direction, and in the Y direction the reduction seems to be localized to the 10-60 Hz range. The 10-60 Hz range makes sense as this is the range in which the equipment normally produces vibration noise. There is almost no visible reduction in the Z direction, which suggests that the column is stiffer in that direction.

Now looking at 21-ID beamline floor vibrations, Figure 12, we can similar reductions across the spectrum as was seen in the column. The reduction in the Y direction is, in this case throughout the entire spectrum, however the largest reduction is still in the 10-60 Hz range. In this case the 10-60 Hz reduction is seen in all three directions, which is likely from a combination of vibrations of multiple columns from varying angles to the measurement point contributing to the vibration noise. From this data it can be concluded that the columns represent a significant source, approximately a half order of magnitude increase of vibrations at various frequencies, and any reduction in vibration noise to mechanical equipment on the mezzanine floor should have a measured reduction in vibrations on the beamline floor.

Figure 11. Comparison of column C129C floor vibration displacement spectrum with the power on and power off to the mechanical equipment on the mezzanine.

Figure 12. Comparison of the beamline floor vibration displacement spectrum with the power on and power off to the mechanical equipment on the mezzanine.

4 Conclusions

A survey of the experiment hall at the APS was conducted and several conclusions can be gained from this survey. It was found that the entire APS experiment hall is an extremely vibration quiet research facility when compared to the VC curves from NEST. Even though, it was found that some regions of the floor have even lower magnitude vibrations than others, particularly beamlines 10-20. In the lower frequency bands, up to 22 Hz, local similarity of vibration magnitudes could be seen, however above 22 Hz variation was seen from one beamline to the next. It was found that the column vibrations mirrored those of the nearby beamlines, and when the power was turned off to the mechanical equipment on the mezzanine the affected column and beamline floor had visible reductions in vibration magnitudes. This all points to the columns being a primary conveyor and source of vibration noise to the experiment hall floor. It is hoped that the results and conclusions of this survey will be used in support of the selection of future beamline construction areas, as a planning tool for future beamline designs, and to help identify sources of vibration noise. Cumulative

Acknowledgements

The authors would like to acknowledge Dean Haeffner and Patricia Fernandez for their management and support of this project, and also Curt Preissner for his advice and professional insight into the project. Work supported by the U.S. Department of Energy, Office of Science, under Contract No. DE-AC02-06CH11357.

References

Amick, Hal, Michael Gendreau, Todd Busch, and Colin Gordon. 2005. "Evolving criteria for research facilities: vibration." Optics & Photonics 2005.

Rogers, Melissa JB, Kenneth Hrovat, Kevin McPherson, Milton E Moskowitz, and Timothy Reckart. 1997. "Accelerometer data analysis and presentation techniques."

Revision Note 2/28/2020

This new revised version removed VC curves from the Figure 2 spectral plot because VC curves are not normally displayed in spectral plots as they are defined in proportional octave bands. The original metric (the mean of summed frequency bands) used to compare floor vibrations to column vibrations was non-standard and has been replaced by 1/3 octave band comparison. Figures 3, 4, and at the start of appendix were added to aid analysis of vibrations around the experiment hall floor. The conclusions of the original paper have not changed.

Appendix – Complete Beamline Floor Data Set