SOQ26_9357_OQ_Attachment_E_Qualifications_Fillin_FormIssue.xls

XLS spreadsheet 118 KB Posted

Attached to
SOQ26 9357 OQ Prequalification for Fern Creek UG 230kV T-Line and Water Main Civil Construction Services
Solicitation number
9357
Issued by
Florida

About this file

This is a Statement of Qualifications (SOQ) attachment form for prequalification for Fern Creek Underground 230kV Transmission-Line and Water Main Civil Construction Services in Florida. The SOQ solicits qualified contractors to demonstrate capabilities in performing civil construction services related to underground utilities for high-voltage power transmission lines, including groundwork, ductbank, manhole, and handhole infrastructures, as well as underground wet utilities for pressure mains. Bidders must submit comprehensive qualifications packages addressing company background, primary contact information, licenses, insurance requirements, financial data, health and safety programs, screening procedures, and project-specific organizational details. The evaluation criteria emphasize past project experience completed within the last seven years, with preference for projects of at least 100kV or greater, minimum half-mile length with splicing in manholes, open cut trenching methodology with trench boxes, and at least one project demonstrating micro-tunneling construction technique experience. Project team members must provide resumes demonstrating a minimum of seven years of industry experience with similar project types.

Minimum insurance requirements include General Liability of $5 Million, Auto Liability of $1 Million with MCS-90 Endorsement Coverage, statutory Worker's Compensation, and Pollution Liability Coverage of $5 Million, with additional insured provisions and waiver of subrogation required for all coverage types except Workers Compensation. Contractors must demonstrate minimum bonding capacity of $30 Million for Payment and Performance Bonds with documentation from a qualified surety. Bidders must provide three reference projects performed in the last seven years, with preference for Florida experience and urban construction environments rather than greenfield construction. The form requests detailed project information including contractor role, contract values, crew composition, equipment used, contract dates, line distance, voltage specifications, and soil conditions. Additionally, contractors must disclose annual dollar volumes for the past four years, Dun and Bradstreet numbers, workers compensation experience modification ratings, OSHA incidence/frequency/severity rates, and details on drug-free workplace policies and emergency response capabilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Background B-1

Fern Creek 230kV Underground Transmission-Line and Water Main Civil Construction Services (Base Bid F) Tab B-1 Qualificatons Company Background
SOQ26 9357 OQBidder’s are to demonstrate its firms qualifications to perform the work associated with civil contruction pertaining to underground utilities for high volatage power transmission lines inclusive of ground work, ductbank, manhole, and handhole infrastructures and underground wet utilites for pressure mains. Bidders interested in performing the associated work shall submit qualifications package as requested in Tabs B-1, B-2, B-3, B-4 & B-5
Qualifications
1Company Background Data
1.1Name of Firm
1.2Name of Parent Company
1.3Complete Business Address
1.4State of Incorporation
2Company Primary Contact Information:
2.1Name
2.2Email Address
2.3Office Phone Number
2.4Mobile Phone Number
2.5Telefax Number
3Licenses
3.1Potential Bidders shall be properly licensed by the State of Florida to perform the type of services requested. Provide a copy of the applicable business license.
4Insurance
4.1Potential Bidders shall be properly insured in accordance with the Minimum specified OUC insurance requirements. Provide a sample copy of your firms insurance certificates.
4.2General Liability $5 Million
4.3Auto Liability $1 Million including MCS-90 Endorsement Coverage
4.4Worker Comp (Statutory)
4.5Pollution Liability Coverage $ 5M
4.5Does Policy allow for additional insured for all coverage types other than Workers Comp and waiver of subrogation for all coverage ttpes in favor of the Owner?
4.6Indicate your firms Bonding Capacity for Payment and Performance Bonds (Provide letter of good standing and Capacity from a qualified Sureity) (Minumum Bonding Capcity is $30M)
4.7Is your firm capable of providing Builders Risk Insurance Coverage values at 100% of the Contract value if selected for award of a Contract resulting form a future RFP in connection with this prequalifictaion process?
5Company Financial
5.1Dunn and Bradstreet Number
5.2Firms annual dollar volume for the last four years specific to the division of the firm to provide the services requested. 2025 through 20222025:
2024:
2023:
2022:
8WMBE InformationThis is for informational Purposes Only and does not represent any specific Minumum WMBE Requirements having to be met for the Firm
8.1Is firm a Women Owned or Minority Owned Business Enterprise? (YES or No) If yes, provide certification documentation.
8.2Does your firm have a Minority/Women business utilization program?
8.3If response was yes to item above, please describe program.
9Company Health and Safety Programs and Record
9.1Provided a copy of your firm’s Health & Safety Manual on CD. (YES OR NO)
9.1aFirms Workman's Comp Exp Mod rating last 3 yrs.2025:
2024:
2023:
9.1bOSHA Incidence Rate for the last 3 years2025:
2024:
2023:
9.1cOSHA Frequency Rate for the last 3 years2025:
2024:
2023:
9.1dOSHA Severity Rate for the last 3 years2025:
2024:
2023:
9.2Has you firm had any incidents resulting in loss of life within the past 5 years related to the production, supply or delivery for any of the chemicals being proposed.
9.2aIf response to 9.2 is yes please provide explanation
9.3Does your firm have a comprehensive employee and vehicle safety program that includes hazardous material response training, ongoing driver safety training, formal incident investigation with root cause analysis, and equipment and vehicle inspection?
9.3aIf Yes to 9.3 please provide a summary of these programs or otherwise specify the specific sections of your firms Health and Safety Manual this is covered by.
9.4Does your company have a program to ensure that all federal, state and local regulations are followed in the handling, storage and disposal of hazardous material?
9.4aIf yes to Item 9.4, please provide brief outline of program
9.5Has your company ever been issued a warning or violation by a regulatory agency for non-compliance with federal or state regulations?
9.5aIf yes to Item 9.5, please describe and include date of violation or warning.
9.6Does your company have a Drug Free Work Place policy?
9.6aIf yes, please provide an outline of your Drug Free Work Place policy Table of Contents.
10Please indicate below if your firm conducts the following screening and testing.
10.1Pre-Employment Criminal Background Checks? (YES or NO)
10.2Workers Compensation History Review? (YES or NO)
10.3Driver License Verification (YES or NO)
10.4Pre-employment Physical Exam (YES or NO)
10.5Provide outline of your firms emergency response programs and capabilities in support of your customers.
10.6Provide any additional information you feel will assist OUC in determining your firm’s qualifications. You may include any related services your company could provide.
11Project Specific Details
11.1Project Specific Org Chart- Should include Home Office Project Manager, Site Project Manager/Superintendents, Forman, Quality, and Safety.

&C&"Arial,Bold"&12DESIGN BUILD SERVICES FOR LANDFILL GAS TO ENERGY PROJECTS

Transmission Quals -Ref B-2

SOQ26 9357 OQFern Creek 230kV Underground Transmission-Line Civil Construction Services (Base Bid F) Tab B-2 Qualifications Past Projects-References
Contractor shall provide 3 references of work that has been completed in the last 7 years of underground construction. These project references are to be of projects that are at least:

o 100kV or greater o Minimum of half mile long with splicing in manholes o Use of open cut trenching methodology with trench box and sloping of earth.

o At least one project should note use of micro-tunnelling construction technique for a portion of the installation. If not, please include experience with micro-tunneling construction methodology.

RESUMES: The proposed team members of the project are to note in their resumes projects that are of similar type to the above referenced request. Ideally, it is recognized the proposed team member does not have longevity with the Contractor to be part of the project references provided. In this event, project team member’s resumes are to demonstrate minimum of 7 years of experience in the industry with similar project’s noted in their resume.

SOQ26 9357 OQQualificationsSuppliers Response
1Is this scope being self performed or Subcontracted.
2Name of Firm
3Complete Business Address
4State of Incorporation
5Provide a narrative describing your firm’s capabilities in regards to the scope of work/services being requested in the SOQ for Roads Restorations Work Scope. Include the overall approach and specific methodology to provide the specified services.
6Number of Years your firm has been in business Supplying Underground Transmission Line Work.
7Number of Years your firm has been in business the peforming the type of work described in this SOQ in Florida
8Provide a narrative describing your firm’s capabilities in regards to the Underground Transmission scope being desribed in the SOQ. Include the overall approach and specific methodology to provide the specified services.
9Provide narrative of your firms past experience where your firm was responsible for obtaining and/or manageing and maintaining MOT permitting with The City of Orlando and/or FDOT in a similar Urban environment.
References/ExperienceReferences: Provide Three (3) projects performed within the last seven (7) years showing experience with preference to inlcude projects performed in Florida. Reference Projects should represent/demonstrare firms experience/qualifications to perform the work associated with civil construction for high voltage underground power transmission lines inclusive of ground work, ductbank, manhole, and handhole infrastructures.. Preference to Include experience references within the past 5 years pertaining to civil installations of ductbanks (via open cut) and manholes for 230kV underground transmission lines and or similar experience with civil installations of ductbanks (via trenchless/jack and bore). Preference is for incusion of Projects performed in an urban construction environment rather than greenfield contruction environment.
Ref # 1
R1-1Name of company or organization the service was provided for.
R1-2Name of facility and its location. Was the work performed in urban area or green field?
R1-3Description of Product/Service provided and Contractors Role
R1-4Cost Method used and Dollar Value
R1-5Final contract Dollar Value including change orders
R1-6Crew Size and Make up
R1-7Types of Equipment Used
R1-8Dates of contract term
R1-9What was the distance covered by the line construction?
R1-10What was voltage of line construction?
R1-11Was project located in sandy, weak (blow counts <10) soils with high (within 6’ of surface) water tables
R1-12Did your firms work for this project include open cut trenching methodology with trench box and sloping of earth?
R1-13Did your firms scope require the use of micro-tunnelling construction technique for a portion of the installation. If not, please include experience with micro-tunneling construction methodology.
R1-14List Name of firm and type of work performed for any major Subcontractors used.
R1-15Contact: Name, phone number, and e-mail address. Contact must be someone currently withing the firm which is familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R1-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
R1-17Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R1-18Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
Ref # 2
R2-1Name of company or organization the service was provided for.
R2-2Name of facility and its location. Was the work performed in urban area or green field?
R2-3Description of Product/Service provided and Contractors Role
R2-4Cost Method used and Dollar Value
R2-5Final contract Dollar Value including change orders
R2-6Crew Size and Make up
R2-7Types of Equipment Used
R2-8Dates of contract term
R2-9What was the distance covered by the line construction?
R2-10What was voltage of line construction?
R2-11Was project located in sandy, weak (blow counts <10) soils with high (within 6’ of surface) water tables
R2-12Did your firms work for this project include open cut trenching methodology with trench box and sloping of earth?
R2-13Did your firms scope require the use of micro-tunnelling construction technique for a portion of the installation. If not, please include experience with micro-tunneling construction methodology.
R2-14List Name of firm and type of work performed for any major Subcontractors used.
R2-15Contact: Name, phone number, and e-mail address. Contact must be someone currently withing the firm which is familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R2-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
R2-17Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R2-18Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
Ref # 3
R3-1Name of company or organization the service was provided for.
R3-2Name of facility and its location. Was the work performed in urban area or green field?
R3-3Description of Product/Service provided and Contractors Role
R3-4Cost Method used and Dollar Value
R3-5Final contract Dollar Value including change orders
R3-6Crew Size and Make up
R3-7Types of Equipment Used
R3-8Dates of contract term
R3-9What was the distance covered by the line construction?
R3-10What was voltage of line construction?
R3-11Was project located in sandy, weak (blow counts <10) soils with high (within 6’ of surface) water tables
R3-12Did your firms work for this project include open cut trenching methodology with trench box and sloping of earth?
R3-13Did your firms scope require the use of micro-tunnelling construction technique for a portion of the installation. If not, please include experience with micro-tunneling construction methodology.
R3-14List Name of firm and type of work performed for any major Subcontractors used.
R3-15Contact: Name, phone number, and e-mail address. Contact must be someone currently withing the firm which is familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R3-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
R3-17Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R3-18Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
Management, Personnel, Facilities and Resources, Other
Location of the local service office to for Underground Transmission Services within OUC's service territory.
Locations of any other facilties that may be utilized in support of a contract resulting from this RFP.
Provide a brief description of current technical and management capabilities and availability to perform the work.
Previous Client experience
Provide a listing of previous experience with Orlando Utilities Commission within the last five (5) years.
For staff who would be assigned to the contract, provide the following:
List names phone and email for the following within your firm responsible for the Underground Transmission Line Services.President:
Vice President
Outside Sales/Account Manager:
Site Superintendants
Site Foreman
Provide outline of your firms emergency response programs and capabilities for the specified services.
Decribe your firms total workforce availability – In the event this project is subject to limits of construction activity in certain road jurisdictions or based on MOT plans, or the project falls behind schedule, the contractor must show the ability to work at multiple sites (multiple crews) simultaneously along the project route.
Provide Resumes for Project Manager, Superintendents, and Foreman that would be assigned to perform work under a resulting contract. The proposed team members of the project are to note in their resumes projects that are of similar type to the above referenced request. Ideally, it is recognized the proposed team member does not have longevity with the Contractor to be part of the project references provided. In this event, project team member’s resumes are to demonstrate minimum of 7 years of experience in the industry with similar project’s noted in their resume.
Describe any training and or other value added support services your firm provides/offers to its customers pertaining to the specified services

Water Main Quals -Ref B-3

SOQ26 9357 OQFern Creek 230kV Water Main Civil Construction Services (Base Bid F) Tab B-3 Qualifications Past Projects-References
Tab B-3
WATER DISTRIBUTION CONSTRUCTION SERVICE QUALIFICATIONSSuppliers Response
1Number of Years your firm has been in business Installing Potable Water Mains.
2Number of Years your firm has been in business Installing Potable Water Mains via jacking and boring (with or without a Subcontractor is acceptable). If a subcontractor was employed for this work, list the subcontractor(s) you have worked with in the past and intend to work with for this project.
3Number of Years your firm has been in business Installing Potable Water Mains via directional drilling (with or without a Subcontractor is acceptable). If a subcontractor was employed for this work, list the subcontractor(s) you have worked with in the past and intend to work with for this project.
4Number of Years your firm has been in business Supplying Underground Water Main Line Work in Florida.
5List of projects or experience directly with OUC within the past 5 years.
6Provide narrative of your firms past experience where your firm was responsible for obtaining and/or manageing and maintaining MOT permitting with the City of Orlando and/or FDOT in a similar Urban environment.
Provide three (3) project references for work completed within the past seven (7) years that demonstrate your firm’s qualifications in civil construction involving installation or modification of pressurized buried pipelines (potable water, reclaimed water, or wastewater force mains) of at least 1,000 linear feet, with at least one project including a minimum of 2,500 linear feet within a residential subdivision. Projects should involve pipe diameters of 6-inch or greater, with experience up to 16-inch ductile iron pipe (DIP), and include associated service connections, maintenance of traffic, and restoration of driveways and sidewalks. Work must have been performed adjacent to existing live watermains, maintaining uninterrupted customer service throughout construction. Projects are preferably located within 100 miles of OUC’s Reliable One Plaza.
Ref # 1
R1-1Name of company or organization the service was provided for.
R1-2Name of project and its location
R1-3Description of Product/Service provided and Contractors Role
R1-4Cost Method used and Dollar Value
R1-5Crew Size and Make up
R1-6Types of Equipment Used
R1-7Did work include open cut, horizontal directional drill or trenchless jack and bore methodology?
R1-8Provide length of pipeline project
R1-9Provide material of pipeline installed
R1-10Provide diameter of pipeline installed
R1-11List Name of firm and type of work performed for any major Subcontractors used.
R1-12Dates of contract term
R1-13Contact: Name, phone number, and e-mail address. Contact must be someone familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R1-14Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
R1-15Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R1-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
Ref # 2
R2-1Name of company or organization the service was provided for.
R2-2Name of project and its location
R2-3Description of Product/Service provided and Contractors Role
R2-4Cost Method used and Dollar Value
R2-5Crew Size and Make up
R2-6Types of Equipment Used
R2-7Did work include open cut, horizontal directional drill or trenchless jack and bore methodology?
R2-8Provide length of pipeline project
R2-9Provide material of pipeline installed
R2-10Provide diameter of pipeline installed
R2-11List Name of firm and type of work performed for any major Subcontractors used.
R2-12Dates of contract term
R2-13Contact: Name, phone number, and e-mail address. Contact must be someone familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R2-14Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
R2-15Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R2-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
Ref # 3
R3-1Name of company or organization the service was provided for.
R3-2Name of project and its location
R3-3Description of Product/Service provided and Contractors Role
R3-4Cost Method used and Dollar Value
R3-5Crew Size and Make up
R3-6Types of Equipment Used
R3-7Did work include open cut, horizontal directional drill or trenchless jack and bore methodology?
R3-8Provide length of pipeline project
R3-9Provide material of pipeline installed
R3-10Provide diameter of pipeline installed
R3-11List Name of firm and type of work performed for any major Subcontractors used.
R3-12Dates of contract term
R3-13Contact: Name, phone number, and e-mail address. Contact must be someone familiar with the details of the actual performance of the contract who can comment on the contractor’s performance from an operations and maintenance perspective.
R3-14Describe any unusual operating conditions, requirements, or circumstances that may serve to distinguish your firm’s qualifications.
R3-15Did your firms scope include any Roadway Restorations? If yes please describe and indicate if the work was self performed or performed by subcontractor.
R3-16Provide photos of the work that was performed. Any work by a subcontractor shall be clearly stated.Provide photos as separate attachments. DO NOT insert photos in the Fill In Form response.
Management, Personnel, Facilities and Resources, Other
6Location of the local service office to for these Services.
7Locations of any other facilities that may be utilized in support of a contract resulting from this RFP.
8Provide a brief description of current technical and management capabilities and availability to perform the work.
9Provide a listing of previous experience with Orlando Utilities Commission within the last five (5) years.
For staff who would be assigned to the contract, provide the following:
10Provide Contact Information to include name, phone, and email for the following within your firm responsible for these Services.
11President
12Vice President
13Outside Sales/ Office Project-Account Manager:
14Site Superintendents
15Site Foreman
16Provide outline of your firms emergency response programs and capabilities for the specified services.
17Describe any other value added support services your firm provides/offers to its customers pertaining to the specified services
18Describe your firms total workforce availability – In the event this project is subject to limits of construction activity in certain road jurisdictions or based on MOT plans, or the project falls behind schedule, the contractor must show the ability to work at multiple sites (multiple crews) simultaneously along the project route.

B-4 Clarifications-Exceptions

EXCEPTIONS AND OR CLARIFICATIONS
No exceptions will be allowed after the response is submitted.
Please indicate yes or none below if clarifications and or exceptions have been taken as part of your firms proposal.
Commercial Clarifications Yes ___ None___ Commercial Exceptions Yes___ None ___
Technical Clarifications Yes___ None ___ Technical Exceptions Yes___ None ___
NOTE: If the Supplier’s has checked the Exceptions block indicating it’s proposal includes clarifications and or exceptions the Supplier shall clearly identify each clarification and or exception below.
All exceptions and or clarifications shall be specific and reference the applicable SOQ article number, and meet with all SOQ requirements.
Respondent shall check the None blocks if the Respondent does not have any commercial or technical exceptions and or clarifications to declare from the requirements of the SOQ documents.
Fern Creek 230kV Underground Transmission-Line and Water Main Civil Construction Services (Base Bid F) Tab B-4 Clarifications and Exceptions
SOQ26 9357 OQ
ExceptionsClarifications
The Respondent's specific Exceptions herein itemized and included with the Resonse represent an exhaustive list of any and all explicit variations or deviations from the requirements of the SOQ documents.All of Respondent’s Clarifications herein itemized and included with the Response do not constitute explicit variation or deviation from the prequalifications in strict accordance with the requirements of SOQ documents.
Commercial ExceptionsCommercial Clarifications
ItemReference ArticleStated Commercial ExceptionsItemReference ArticleStated Commercial Clarifications
CE1CC1
CE2CC2
CE3CC3
CE4CC4
CE5CC5
CE6CC6
CE7CC7
CE8CC8
CE9CC9
CE10CC10
Technical ExceptionsTechnical Clarifications
ItemReferenceStated Technical ExceptionsItemReferenceStated Technical Clarifications
TE1TC1
TE2TC2
TE3TC3
TE4TC4
TE5TC5
TE6TC6
TE7TC7
TE8TC8
TE9TC9
TE10TC10

B-5 Addendum Acknowledments

ADDENDA for Solicitation #: SOQ26 9357 OQ
The undersigned Respondent acknowledges receipt of the following Addenda, which
have been considered in preparing this Response.
Addendum No. 1Dated
Addendum No. 2Dated
Addendum No. 3Dated
Addendum No. 4Dated