This is a Pre-Renovation Asbestos and Limited Lead-Containing Paint Survey Report prepared by Atlas Technical Consultants LLC for the Michigan Department of Military and Veteran Affairs, specifically for Building 536Q at Camp Grayling in Grayling, Michigan. The survey was conducted on February 25, 2026, by State of Michigan certified asbestos inspector Andrew DeLodder (Certification No. A48677) to identify asbestos-containing materials (ACMs) and lead-containing paint (LCP) prior to renovation activities. The inspection identified 29 homogeneous areas and collected 87 asbestos bulk samples totaling 104 analyzed layers, as well as 4 paint chip samples from interior and exterior surfaces of the barracks building. The survey was completed and reported on March 20, 2026.
Laboratory analysis using Polarized Light Microscopy (PLM) and Flame Atomic Absorption Spectroscopy (AAS) revealed that one material contained greater than 1 percent asbestos (the vibration dampener with 40% Chrysotile), three materials contained less than 1 percent asbestos (exterior caulk at 0.25% Chrysotile, window glaze at 0.25% Chrysotile, and window glaze at 0.25% Chrysotile), and all four paint samples tested exceeded laboratory reporting limits for lead content, with the mechanical room floor paint registering 0.901 percent lead by weight. The report recommends that any additional suspect materials discovered during renovation activities be treated as presumed asbestos-containing material and either sampled or handled as ACM in accordance with OSHA standards 29 CFR 1926.1101 and 1910.1001. Contractors performing renovation activities must evaluate potential worker exposures to airborne lead and ensure compliance with EPA waste disposal regulations for lead-containing materials.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRE-RENOVATION ASBESTOS AND LIMITED LEAD-CONTAINING PAINT SURVEY
CAMP GRAYLING: BUILDING 536Q
Camp Grayling Grayling, Michigan Project #188BS26106
PREPARED FOR:
Michigan Department of Military and Veteran Affairs
PREPARED BY:
Atlas Technical Consultants LLC 46555 Humboldt Drive, Suite 100 Novi, Michigan 48377 March 20, 2026
Page | 1
46555 Humboldt Drive, Suite 100 Novi, Michigan 48377
(248) 669-5147 | oneatlas.com
March 20, 2026
Jon Jorgensen NCARB Design Manager Michigan Department of Military and Veterans Affairs Construction & Facilities Management Office (CFMO) Reserve Forces Support Center 3423 N. Martin Luther King Jr. Blvd. #321K Lansing, MI 48906
Subject: Pre-Renovation Asbestos and Limited Lead-Containing Paint Survey Camp Grayling: Building 536Q 12950 E. Grand River Ave Brighton, MI 48116
Dear Mr. Jorgensen:
Atlas is pleased to present this report detailing the findings of the pre-renovation asbestos and limited lead-containing paint survey performed at the above referenced site. The purpose of this sampling was to identify and collect samples of suspect asbestos containing materials (ACMs) and lead-containing paint (LCP) prior to renovation activities.
The pre-demolition asbestos and limited lead-containing paint sampling was conducted on February 25, 2026, by Industrial Hygienist, Mr. Andrew DeLodder, State of Michigan certified asbestos inspector. The sampling was conducted in accordance with sampling criteria specified in the Occupational Safety and Health Administration’s (OSHA) Asbestos Construction Industry Standard (29 CFR 1926.1101), and the Asbestos Hazard and Emergency Response Act of 1987
(AHERA).
If you have any questions, please call us at 248.669.5140.
Respectfully submitted, Kandy Rauser Project Manager Atlas Technical Consultants LLC
Page | i
CONTENTS
EXECUTIVE SUMMARY
1. INTRODUCTION
1.1 Purpose
1.2 Pre-Renovation Asbestos Survey
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
2.2 Exterior Finish Descriptions
2.3 Interior Building Descriptions
3. PRE-RENOVATION ASBESTOS SURVEY
3.1 Homogeneous Areas
3.2 Hazard Assessment Factors
3.3 Laboratory Analytical Methodology
3.4 Sampling Results
4. LEAD-CONTAINING PAINT SAMPLING
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos Containing Materials
5.2 Lead-Containing Paint
6. ASSUMPTIONS AND LIMITATIONS
TABLES
Table 3-1 ACM Sampling Results
Table 4-1 Lead-Containing Paint Sampling Results
APPENDICES
Appendix A Sample Location Drawing and Photolog Appendix B Asbestos Laboratory Report Appendix C Lead-Containing Paint Laboratory Report
Page | 2
EXECUTIVE SUMMARY
Atlas representative Mr. Andrew DeLodder, completed the pre-renovation asbestos and limited lead-containing paint survey of building 536Q, located at Camp Grayling, in Grayling, Michigan, on February 25, 2026.
Eighty-seven (87) asbestos bulk samples, taken from twenty-nine (29) homogenous areas, were collected and submitted for analysis by Polarized Light Microscopy (PLM). Of the eighty-seven samples submitted, one hundred-four (104) sample layers were analysed. The results of laboratory testing indicated that one
(1) of the suspect materials contained greater than 1 percent asbestos. The results of laboratory testing indicated that three (3) of the suspect materials contained less than 1 percent asbestos.
Four (4) representative sample of paint, taken from interior of the building, was collected and submitted for analysis by Flame AAS. The results of laboratory testing of the paint chip sample indicated that four (4) samples contained levels of lead greater than the laboratory reporting limits.
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
Page | 3
1. INTRODUCTION
1.1 Purpose
The purpose of this project was to conduct a pre-renovation asbestos and limited lead-containing paint survey of building 536 Q, located at Camp Grayling in Grayling, Michigan.
1.2 Pre-Renovation Asbestos Survey
The scope of the pre-renovation asbestos survey included the following:
• Review of existing asbestos reports for the building(s), if available;
• Survey of the property building(s);
• Identification of accessible suspect asbestos-containing materials (ACMs);
• Collection and analysis of bulk samples of suspect friable and non-friable materials.
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
General property and building information is presented in the following table:
General Property and Building Information
Date of Inspection: February 25,2026
Inspectors Andrew DeLodder Inspector # A48677
Property Address: Camp Grayling, Grayling Michigan
Property Owner Michigan Department of Military and Veteran Affairs
Building Description: Barracks
2.2 Exterior Finish Descriptions
The exterior of the building includes CMU block walls, concrete slab foundation, and a pitched asphalt shingled roof.
2.3 Interior Building Descriptions
The interior finishes of the building included CMU block walls, wall board system ceilings and concrete floors.
3. PRE-RENOVATION ASBESTOS SURVEY
Atlas representative Mr. Andrew DeLodder conducted the pre-renovation asbestos inspection of the building
Camp Grayling on February 25,2026. Mr. DeLodder is a State of Michigan Certified Asbestos Inspector’s
(Certification No. A48677). The areas identified for renovation were visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation Program
(NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e. fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
> Conducting a visual inspection of the structures;
> Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and miscellaneous materials; and
Page | 4
> Sampling accessible, friable and non-friable suspect materials.
3.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance and function. Actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and professional opinion of the inspector.
3.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list. A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
• Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
• Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
• Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor covering, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
All materials were assessed related to their condition in one of the three categories: good (intact), fair
(damaged) or poor (significantly damaged) per Title 40 Code of Federal Regulations Part 763. Material with localized, significant damage was also assessed as poor.
3.3 Laboratory Analytical Methodology
Bulk samples were analyzed by Environmental Testing Laboratories, Inc. (ETL) using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No. 103, May
27, 1982 pg. 23376). This laboratory participates in the National Voluntary Laboratory Accreditation Program
(NVLAP #201028-0), a quality assurance program for PLM analysis, and is accredited by the National Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in
Appendix A. Positive sample results are reported in percent asbestos by volume of the sample and the type of asbestos material within the sample. Other common non-asbestos components may also be noted on the analytical reports. Inspector and laboratory accreditations are provided in Appendix C.
3.4 Sampling Results
Bulk samples were collected from the cabin and analyzed by polarized light microscopy (PLM), EPA Method
600/R-93/116.
The following table provides a summary of accessible suspect and confirmed ACMs from the site structure:
Table 3-1 ACM Sampling Results
Sample ID/Material
Location of Materials
Material Estimated Quantity
Asbestos Content
1-CC-ABC EA 1,2,3,4 Exterior concrete - walkways 1,965 SF ND
Page | 5
Sample ID/Material
Location of Materials
Material Estimated Quantity
Asbestos Content
2-BM-ABC
EA 1,2,3,4
FS 1-9
Brick mortar - CMU block walls
13,845
SF
ND
3-EJ-ABC EA 2,4
Expansion joint - grey, in CMU block walls
80 LF ND
4-EC-ABC EA 1,2,3,4
Exterior caulk - grey, soft, around aluminum window frames(3'x4' window) and door frames
530 LF ND
5-WG-ABC EA 1,2,3,4
Window glaze - white, crumbly, aluminum windows (3'x4' window)
704 LF ND
6-EC-ABC EA 2 & FS 9
Exterior caulk - black, hard, perimeter of mechanical room door frame
20 LF ND
7-EC-ABC EA 2
Exterior caulk - grey, crumbly, natural gas penetration into wall
1 LF ND
8-EC-ABC EA 2
Exterior caulk - white, crumbly, perimeter of steel window frame
10 LF
.25% Chrysotile
(PC)
9-WG-ABC EA 2
Window glaze - light grey, on steel window
12 LF
.25% Chrysotile
(PC)
10-WG-ABC EA 1
Window glaze - white, on entry door window
12 LF ND
11-RM-ABC EA 5
Roofing materials, brownish red asphalt roof
8,625 SF ND
12-EC-ABC EA 5
Exterior caulk - grey, on exhaust fan
1 LF ND
13-CC-ABC FS 1-9
Concrete chip - poured concrete slab foundation
7,730 SF ND
14-EJ-ABC FS 1,3,4,6,8
Expansion joint - black, fibrous, perimeter of concrete slab foundation
580 LF ND
15-EJ-ABC FS 1,3,4,6,8
Expansion joint - grey, soft, seams of concrete slab foundation
290 LF ND
16-IC-ABC FS 1,2,3,4,6,8
Interior caulk - grey, soft, perimeter of door and window frames
1,115 LF ND
17-EC-ABC EA 3
Exterior caulk - grey, perimeter of electrical penetration
1 LF ND
18-VD-ABC FS 2,7
Vibration dampener - white, canvas, on air handling unit
40 SF (4
Each)
40% Chrysotile
19-EJ-ABC FS 4
Expansion joint - grey, hard, in
CMU block wall
20 LF ND
20-IC-ABC FS 4
Interior caulk - grey, hard, perimeter of door frame
60 LF ND
21-IC-ABC FS 5
Interior caulk - white, hard, between shower "step-up" and concrete floor
10 LF ND
Page | 6
Sample ID/Material
Location of Materials
Material Estimated Quantity
Asbestos Content
22-WG-ABC FS 4
Window glaze - grey, on 3 pane door window
50 LF (2
Doors)
0.25% Chrysotile (PC)
23-WBS-
ABC
FS 5
Wallboard system - bathroom ceiling
1,040 SF ND
24-BM-ABC FS 5
Pipe fitting - fiberglass fitting with plastic cover and brown adhesive
525 SF ND
25-IC-ABC FS 5
Interior caulk - white, on ceiling/wall wood trim in shower area
155 LF ND
26-IC-ABC FS 1,3,4,6,8
Interior caulk - white, aligator cracking texture, on ground over expansion joint (FS-14) in front of doorways
30 LF ND
27-BM-ABC FS 9 Brick mortar - chimney stack 60 SF ND
28-TC-ABC FS 9 Terracotta - chimney liner 20 SF ND
29-SC-ABC FS 9
Stack cement - steel penetration
5 SF ND
EA=Exterior Area FS Functional Space NA=Not Applicable UNQ=Unquantified ND= None Detected
In the event additional suspect material is discovered during demolition activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR
1926.1101 and 1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
4. LEAD-CONTAINING PAINT SAMPLING
Atlas representative Mr. Andrew DeLodder conducted the lead-containing paint (LCP) sampling of the property building on February 25, 2026. The sampling included physical sampling of paint coatings that were deemed representative of the predominant paint coatings observed.
Five (5) paint chip sample was collected and submitted to Accurate Analytical Testing Laboratory, 30105
Beverly Road, Romulus, Michigan for lead analysis. Bulk samples were analyzed using the Environmental
Protection Agency's Test Method SW 846-7420 and 3050B using Flame AAS to determine lead concentration in percent (%) by weight. Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in Appendix B. Laboratory accreditations are provided in Appendix C.
The following table provides a summary of the LCP sampling:
Table 4-1 Lead-Containing Paint Sampling Results
Sample ID Sample Location Color Lead
Content
Reporting Limit
1-LBP-Beige Exterior Paint on CMU block wall Beige 0.00159 0.000548
2-LBP-White Exterior paint on steel doors White 0.00483 0.000588
3-LBP-Grey Interior paint on mechanical room floor Grey 0.901 0.000508
Page | 7
Sample ID Sample Location Color Lead
Content
Reporting Limit
4-LBP-White Interior paint from shower ceiling White 0.00297 0.000611
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos Containing Materials
The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that one (1) of the materials sampled were found to contain greater than 1% asbestos. The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that three
(3) of the materials sampled were found to contain less than 1% asbestos.
If any additional materials are discovered during demolition/renovation activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
5.2 Lead-Containing Paint
Four (4) representative sample of paint, taken from the exterior and interior of the building, were collected and submitted for analysis by Flame AAS. The results of laboratory testing during the limited lead-containing paint sampling conducted at the property indicate that four samples contained levels of lead greater than the laboratory reporting limits.
The presence of lead-containing paint requires, under OSHA 1926.62 requirements, that the contractor performing renovation, surface preparation, and other activities that impact or potentially impact the lead-coated components, evaluate potential worker exposures to airborne lead. This evaluation can be based, for the specific activities denoted in 1926.62, on objective data obtained by the contractor on other, similar, worksites within the prior calendar year. In addition, lead-containing paint and lead-coated waste and construction debris must be evaluated and, on a case-by-case basis depending on this evaluation, quantitative analysis be performed on these waste steams to ensure compliance with EPA waste disposal regulations.
The presence of Lead-Containing Paint (LCP) and/or Lead-Based Paint (LBP) does not, in itself, trigger regulatory compliance actions. However, when these materials are disturbed, the requirements of OSHA
(1926.1101) and EPA may become operative. Appropriate actions in terms of removal methods, emissions control, worker protection, and waste disposal should be considered by the general contractor and applicable subcontractors while completing renovation activities.
6. ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted during the NESHAP inspections conducted on February 25, 2026, performed by
Atlas. Selection of sample locations and frequency of sampling were based on EPA Guidance documents, Atlas’s observations, and the assumption that building vintage and renovation history information presented to Atlas allowed the proper designation of homogenous materials for each building.
This document does not contain the elements necessary for an Abatement Work plan, and this document does not contain, nor should it take the place of technical specifications for ACM removal.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against changes to material from future operations or conditions, nor does it warrant against operations or conditions against present ACM material in locations not investigated.
Page | 8
The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
APPENDIX A
SAMPLE LOCATION DRAWING AND PHOTOLOG
Camp Grayling
Photograph Log Building 536Q Grayling, Michigan 49738
188BS26106
Photograph #1
Homogenous Material Description
HA-1: Concrete walkways
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1965 SF
Additional Notes
Photograph #2
HA-2: Brick mortar – CMU block walls
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
13845 SF
Photograph #3
HA-3: Expansion joint – grey, in CMU block walls
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
80 LF
Grayling, Michigan 49738
Photograph #4
HA-4: Grey caulk – perimeter of aluminum window frames, and steel door frames
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
530 LF
Photograph #5
HA-5: Window glaze
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
704 LF
Photograph #6
HA-6: Black door frame caulk
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
20 LF
Grayling, Michigan 49738
Photograph #7
HA-7: Grey caulk, on natural gas penetration
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1 LF
Additional Notes
Very little left after sampling
Photograph #8
HA-8: White caulk, steel window frame
Asbestos Present (Yes/No/Assumed)
Yes: .25% Chrysotile
Total Quantity Present
10 LF
Photograph #9
HA-9: Window glaze – steel window
Asbestos Present (Yes/No/Assumed)
Yes: .25% Chrysotile
Total Quantity Present
12 LF
Grayling, Michigan 49738
Photograph #10
HA-10: Window glaze – white, on entry door
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
12 LF
Photograph #11
HA-11: Asphalt roofing materials
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
8625 SF
Photograph #12
HA-12: Grey caulk on exhaust penetration
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1 SF
Grayling, Michigan 49738
Photograph #13
HA-13: Concrete slab foundation
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
7730 SF
Photograph #14
HA-14: Black fibrous expansion joint
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
580 LF
Photograph #15
HA-15: Grey, soft expansion joint
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
290 LF
Grayling, Michigan 49738
Photograph #16
HA-16: Grey caulk, on door/window frames
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1115 LF
Photograph #17
HA-17: Grey caulk on power penetration
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1 LF
Photograph #18
HA-18: White canvas vibration dampener
Asbestos Present (Yes/No/Assumed)
Yes: 40% Chrysotile
Total Quantity Present
40 SF
4 dampeners
Grayling, Michigan 49738
Photograph #19
HA-19: Expansion joint, grey, hard, in wall
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
Photograph #20
HA-20: Grey caulk, hard, door frame
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
Photograph #21
HA-21: White caulk in shower
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
10 LF
Grayling, Michigan 49738
Photograph #22
HA-22: Window glaze on shower room doors
Asbestos Present (Yes/No/Assumed)
Yes: .25% Chrysotile
Total Quantity Present
50 LF (2 doors)
Photograph #23
HA-23: Wallboard system
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
1040 SF
Photograph #24
HA-24: Glaze block mortar
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
525 SF
Grayling, Michigan 49738
Photograph #25
HA-25: White caulk on ceiling trim
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
155 LF
Photograph #26
HA-26: White caulk, seams of doorways
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
30 LF
Photograph #27
HA-27: Chimney brick mortar
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
60 SF
Grayling, Michigan 49738
Photograph #28
HA-28: Terracotta chimney liner
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
20 SF
Photograph #29
HA-29: Stack cement
Asbestos Present (Yes/No/Assumed)
No
Total Quantity Present
5 SF
Asbestos / Lead-Based Paint
Sampling Location Map
Building Exterior
PROJECT NUMBER: 188BS26106
DRAWN BY: AHD REVIEWED BY Atlas
FIGURE:
DATE: 2/25/2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
N o v i , M i c h i g a n 4 8 3 7 7
P h : ( 2 4 8 ) 6 6 9 - 5 1 4 0 ~ F a x : ( 2 4 8 ) 6 6 9 - 5 1 4 7
= Asbestos Sample Number
= Lead-Based Paint Sample Location
Camp Grayling
Building # 536Q
Grayling, Michigan 49738
Map Key
EA-1
EA-2
EA-3
EA-4
EA-5
1-LBP-Beige
2-LBP-White
11-RM-A
11-RM-B
11-RM-C
12-EC-A,B,C
1-CC-A
1-CC-B
1-CC-C
2-BM-A 2-BM-B
2-BM-C
3-EJ-A
3-EJ-B
3-EJ-C
4-EC-A
4-EC-B
4-EC-C
5-WG-A
5-WG-B
5-WG-C
6-EC-A,B,C
9-WG-A,B,C
10-WG-A,B,C
17-EC-A,B,C
Asbestos / Lead-Based Paint
Sampling Location Map
Building Interior
PROJECT NUMBER: 188BS26106
DRAWN BY: AHD REVIEWED BY Atlas
FIGURE:
DATE: 2/25/2026
4 6 5 5 5 H u m b o l d t D r i v e , S u i t e 1 0 0
N o v i , M i c h i g a n 4 8 3 7 7
P h : ( 2 4 8 ) 6 6 9 - 5 1 4 0 ~ F a x : ( 2 4 8 ) 6 6 9 - 5 1 4 7
= Asbestos Sample Number
= Lead-Based Paint Sample Location
Camp Grayling
Building # 536Q
Grayling, Michigan 49738
Map Key
13-CC-A
13-CC-B
13-CC-C
14-EJ-A
14-EJ-B
14-EJ-C
15-EJ-A
15-EJ-B
15-EJ-C
16-IC-A
16-IC-B
16-IC-C
18-VD-C
19-EJ-A
19-EJ-B,C
20-IC-A 20-IC-B,C
21-IC-A,B,C
22-WG-A,B 22-WG-C
-W
B S
-A
23-WBS-B
23-WBS-C
24-BM-A,B,C
25-IC-A,B,C
26-IC-A
26-IC-B
26-IC-C
27-BM-A,B,C
28-TC-A,B,C
29-SC-A,B,C
3-LBP-Grey
FS-1
F S
-2
FS-3
FS-4
FS-5
FS-6
F S
-7
FS-8
FS-9
18-VD-A,B
4-LBP-White
APPENDIX B
ASBESTOS LABORATORY REPORT
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location:
Camp Grayling
536Q
Client Project: 188BS26106
288778ETL Job:
Jennifer Fashbaugh
Report Issued: 03/10/2026
Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst
1867545 Asbestos1-CC-A 03/10/2026 OJ Ivey02/25/2026
1867546 Asbestos1-CC-B 03/10/2026 OJ Ivey02/25/2026
1867547 Asbestos1-CC-C 03/10/2026 OJ Ivey02/25/2026
1867548 Asbestos2-BM-A 03/10/2026 OJ Ivey02/25/2026
1867549 Asbestos2-BM-B 03/10/2026 OJ Ivey02/25/2026
1867550 Asbestos2-BM-C 03/10/2026 OJ Ivey02/25/2026
1867551 Asbestos3-EJ-A 03/10/2026 OJ Ivey02/25/2026
1867552 Asbestos3-EJ-B 03/10/2026 OJ Ivey02/25/2026
1867553 Asbestos3-EJ-C 03/10/2026 OJ Ivey02/25/2026
1867554 Asbestos4-EC-A 03/10/2026 OJ Ivey02/25/2026
1867555 Asbestos4-EC-B 03/10/2026 OJ Ivey02/25/2026
1867556 Asbestos4-EC-C 03/10/2026 OJ Ivey02/25/2026
1867557 Asbestos5-WG-A 03/10/2026 OJ Ivey02/25/2026
1867558 Asbestos5-WG-B 03/10/2026 OJ Ivey02/25/2026
1867559 Asbestos5-WG-C 03/10/2026 OJ Ivey02/25/2026
1867560 Asbestos6-EC-A 03/10/2026 OJ Ivey02/25/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.
Lab Sample Number Client Sample Number Sample Type CompletedSampled Analyst
1867561 Asbestos6-EC-B 03/10/2026 OJ Ivey02/25/2026
1867562 Asbestos6-EC-C 03/10/2026 OJ Ivey02/25/2026
1867563 Asbestos7-EC-A 03/10/2026 OJ Ivey02/25/2026
1867564 Asbestos7-EC-B 03/10/2026 OJ Ivey02/25/2026
1867565 Asbestos7-EC-C 03/10/2026 OJ Ivey02/25/2026
1867566 Asbestos8-EC-A 03/10/2026 OJ Ivey02/25/2026
1867567 Asbestos8-EC-B 03/10/2026 OJ Ivey02/25/2026
1867568 Asbestos8-EC-C 03/10/2026 OJ Ivey02/25/2026
1867569 Asbestos9-WG-A 03/10/2026 OJ Ivey02/25/2026
1867570 Asbestos9-WG-B 03/10/2026 OJ Ivey02/25/2026
1867571 Asbestos9-WG-C 03/10/2026 OJ Ivey02/25/2026
1867572 Asbestos10-WG-A 03/10/2026 OJ Ivey02/25/2026
1867573 Asbestos10-WG-B 03/10/2026 OJ Ivey02/25/2026
1867574 Asbestos10-WG-C 03/10/2026 OJ Ivey02/25/2026
1867575 Asbestos11-RM-A 03/10/2026 Erica Marcos02/25/2026
1867576 Asbestos11-RM-B 03/10/2026 Erica Marcos02/25/2026
1867577 Asbestos11-RM-C 03/10/2026 Erica Marcos02/25/2026
1867578 Asbestos12-EC-A 03/10/2026 Erica Marcos02/25/2026
1867579 Asbestos12-EC-B 03/10/2026 Erica Marcos02/25/2026
1867580 Asbestos12-EC-C 03/10/2026 Erica Marcos02/25/2026
1867581 Asbestos13-CC-A 03/10/2026 Erica Marcos02/25/2026
1867582 Asbestos13-CC-B 03/10/2026 Erica Marcos02/25/2026
1867583 Asbestos13-CC-C 03/10/2026 Erica Marcos02/25/2026
1867584 Asbestos14-EJ-A 03/10/2026 Erica Marcos02/25/2026
1867585 Asbestos14-EJ-B 03/10/2026 Erica Marcos02/25/2026
1867586 Asbestos14-EJ-C 03/10/2026 Erica Marcos02/25/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
1867587 Asbestos15-EJ-A 03/10/2026 Erica Marcos02/25/2026
1867588 Asbestos15-EJ-B 03/10/2026 Erica Marcos02/25/2026
1867589 Asbestos15-EJ-C 03/10/2026 Erica Marcos02/25/2026
1867590 Asbestos16-IC-A 03/10/2026 Erica Marcos02/25/2026
1867591 Asbestos16-IC-B 03/10/2026 Erica Marcos02/25/2026
1867592 Asbestos16-IC-C 03/10/2026 Erica Marcos02/25/2026
1867593 Asbestos17-EC-A 03/10/2026 Asha Davidson02/25/2026
1867594 Asbestos17-EC-B 03/10/2026 Asha Davidson02/25/2026
1867595 Asbestos17-EC-C 03/10/2026 Asha Davidson02/25/2026
1867596 Asbestos18-VD-A 03/10/2026 Asha Davidson02/25/2026
1867597 Asbestos18-VD-B 03/10/2026 Asha Davidson02/25/2026
1867598 Asbestos18-VD-C 03/10/2026 Asha Davidson02/25/2026
1867599 Asbestos19-EJ-A 03/10/2026 Asha Davidson02/25/2026
1867600 Asbestos19-EJ-B 03/10/2026 Asha Davidson02/25/2026
1867601 Asbestos19-EJ-C 03/10/2026 Asha Davidson02/25/2026
1867602 Asbestos20-IC-A 03/10/2026 Asha Davidson02/25/2026
1867603 Asbestos20-IC-B 03/10/2026 Asha Davidson02/25/2026
1867604 Asbestos20-IC-C 03/10/2026 Asha Davidson02/25/2026
1867605 Asbestos21-IC-A 03/10/2026 Asha Davidson02/25/2026
1867606 Asbestos21-IC-B 03/10/2026 Asha Davidson02/25/2026
1867607 Asbestos21-IC-C 03/10/2026 Asha Davidson02/25/2026
1867608 Asbestos22-WG-A 03/10/2026 Asha Davidson02/25/2026
1867609 Asbestos22-WG-B 03/10/2026 Asha Davidson02/25/2026
1867610 Asbestos22-WG-C 03/10/2026 Asha Davidson02/25/2026
1867611 Asbestos23-WBS-A 03/10/2026 Teagan Murphy02/25/2026
1867612 Asbestos23-WBS-B 03/10/2026 Teagan Murphy02/25/2026
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
1867613 Asbestos23-WBS-C 03/10/2026 Teagan Murphy02/25/2026
1867614 Asbestos24-BM-A 03/10/2026 Teagan Murphy02/25/2026
1867615 Asbestos24-BM-B 03/10/2026 Teagan Murphy02/25/2026
1867616 Asbestos24-BM-C 03/10/2026 Teagan Murphy02/25/2026
1867617 Asbestos25-IC-A 03/10/2026 Teagan Murphy02/25/2026
1867618 Asbestos25-IC-B 03/10/2026 Teagan Murphy02/25/2026
1867619 Asbestos25-IC-C 03/10/2026 Teagan Murphy02/25/2026
1867620 Asbestos26-IC-A 03/10/2026 Ben Jones02/25/2026
1867621 Asbestos26-IC-B 03/10/2026 Ben Jones02/25/2026
1867622 Asbestos26-IC-C 03/10/2026 Ben Jones02/25/2026
1867623 Asbestos27-BM-A 03/10/2026 Ben Jones02/25/2026
1867624 Asbestos27-BM-B 03/10/2026 Ben Jones02/25/2026
1867625 Asbestos27-BM-C 03/10/2026 Ben Jones02/25/2026
1867626 Asbestos28-TC-A 03/10/2026 Ben Jones02/25/2026
1867627 Asbestos28-TC-B 03/10/2026 Ben Jones02/25/2026
1867628 Asbestos28-TC-C 03/10/2026 Ben Jones02/25/2026
1867629 Asbestos29-SC-A 03/10/2026 Ben Jones02/25/2026
1867630 Asbestos29-SC-B 03/10/2026 Ben Jones02/25/2026
1867631 Asbestos29-SC-C 03/10/2026 Ben Jones02/25/2026
Reviewed by:
Summary
Sample Layer MasticMethod
PLM 95
Point Count 9
Dawson Bradley
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Certificate of Analysis
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867545
1-CC-A
PLM 95% OtherPLM 5% CelluloseGreyExterior Concrete
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867545
1-CC-A
PLM 98% OtherPLM 2% CelluloseWhiteGrout
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867546
1-CC-B
PLM 97% OtherPLM 3% CelluloseGreyExterior Concrete
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867546
1-CC-B
PLM 99% OtherPLM 1% CelluloseWhiteGrout
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867547
1-CC-C
PLM 99% OtherPLM 1% CelluloseGreyExterior Concrete
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867547
1-CC-C
PLM 99% OtherPLM 1% CelluloseWhiteGrout
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867548
2-BM-A
PLM 96% OtherPLM 4% CelluloseGreyBrick
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867548
2-BM-A
PLM 98% OtherPLM 2% CelluloseLight GreyMortar
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867549
2-BM-B
PLM 97% OtherPLM 3% CelluloseGreyBrick
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867549
2-BM-B
PLM 97% OtherPLM 3% CelluloseLight GreyMortar
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867550
2-BM-C
PLM 99% OtherPLM 1% CelluloseGreyBrick
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867550
2-BM-C
PLM 97% OtherPLM 3% CelluloseLight GreyMortar
Non-Fibrous
Homogenous Layer-2 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867551
3-EJ-A
PLM 97% OtherPLM 3% CelluloseGreyExpansion Joint
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867552
3-EJ-B
PLM 98% OtherPLM 2% CelluloseGreyExpansion Joint
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867553
3-EJ-C
PLM 96% OtherPLM 4% CelluloseGreyExpansion Joint
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867554
4-EC-A
PLM 96% OtherPLM 4% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867555
4-EC-B
PLM 96% OtherPLM 4% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867556
4-EC-C
PLM 98% OtherPLM 2% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867557
5-WG-A
PLM 97% OtherPLM 3% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867558
5-WG-B
PLM 95% OtherPLM 5% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867559
5-WG-C
PLM 97% OtherPLM 3% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867560
6-EC-A
PLM 94% OtherPLM 6% CelluloseBlackExterior Caulk
Non-Fibrous
Non-Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
With Adhesive
PLM None Detected 1867561
6-EC-B
PLM 95% OtherPLM 5% CelluloseBlackExterior Caulk
Non-Fibrous
Non-Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
With Adhesive
PLM None Detected 1867562
6-EC-C
PLM 94% OtherPLM 6% CelluloseBlackExterior Caulk
Non-Fibrous
Non-Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
With Adhesive
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867563
7-EC-A
PLM 95% OtherPLM 5% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867564
7-EC-B
PLM 97% OtherPLM 3% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867565
7-EC-C
PLM 98% OtherPLM 2% CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PC 0.25% Chrysotile1867566
8-EC-A
PC 97% OtherPC 2.75% CelluloseWhiteExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PC Trace Chrysotile1867567
8-EC-B
PC 98.75% OtherPC 1.25% CelluloseWhiteExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PC Trace Chrysotile1867568
8-EC-C
PC 99% OtherPC 1% CelluloseWhiteExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PC Trace Chrysotile1867569
9-WG-A
PC 99.5% OtherPC 0.5% CelluloseLight GreyWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PC 0.25% Chrysotile1867570
9-WG-B
PC 99.5% OtherPC 0.25% CelluloseLight GreyWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PC 0.25% Chrysotile1867571
9-WG-C
PC 98.75% OtherPC 1% CelluloseLight GreyWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867572
10-WG-A
PLM 97% OtherPLM 3% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867573
10-WG-B
PLM 98% OtherPLM 2% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
PLM None Detected 1867574
10-WG-C
PLM 98% OtherPLM 2% CelluloseWhiteWindow Glaze
Non-Fibrous
Homogenous Layer-1 Analyst: OJ Ivey
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867575
11-RM-A
PLM 100% OtherPLM Trace Cellulose
PLM Trace Fiberglass
Brownish RedRoofing Materials
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867576
11-RM-B
PLM 100% OtherPLM Trace Cellulose
PLM Trace Fiberglass
Brownish RedRoofing Materials
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867577
11-RM-C
PLM 100% OtherPLM Trace Cellulose
PLM Trace Fiberglass
Brownish RedRoofing Materials
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867578
12-EC-A
PLM 100% OtherPLM Trace CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867579
12-EC-B
PLM 100% OtherPLM Trace CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867580
12-EC-C
PLM 100% OtherPLM Trace CelluloseGreyExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Camp Grayling
536Q
ETL Job :
Client Project :
288778
188BS26106
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
02/25/2026
03/05/2026
Date Collected :
Date Received :
PLM None Detected 1867581
13-CC-A
PLM 100% OtherPLM Trace CelluloseGreyConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867582
13-CC-B
PLM 100% OtherPLM Trace CelluloseGreyConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867583
13-CC-C
PLM 100% OtherPLM Trace CelluloseGreyConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867583
13-CC-C
PLM 100% OtherPLM Trace CelluloseWhiteCementitious Material
Non-Fibrous
Homogenous Layer-2 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867584
14-EJ-A
PLM 3% OtherPLM 97% CelluloseBlackExpansion Joint
Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
PLM None Detected 1867585
14-EJ-B
PLM 3% OtherPLM 97% CelluloseBlackExpansion Joint
Fibrous
Homogenous Layer-1 Analyst: Erica Marcos
Date Analyzed : 03/10/2026
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e.