26B1516001 RENOVATE BUILDINGS 536Q+534Q DRAWINGS PART 4.pdf
PDF 1 MB Posted
- Solicitation number
- RFQ 171 260000000277 1
- Issued by
- Crawford County, Michigan
About this file
Project Summary
This file contains electrical construction drawings (Part 4) for the renovation of Buildings 536Q and 534Q at Camp Grayling Joint Maneuver Training Center in Grayling, Michigan, prepared by the Michigan Department of Military and Veterans Affairs, Design and Construction Division. The project involves comprehensive electrical system upgrades including demolition of existing electrical infrastructure, installation of new electrical distribution panels (MDP), lighting systems with occupancy sensors, fire alarm systems, data/communications networks, and HVAC equipment controls. The scope encompasses interior electrical work across multiple rooms, exterior site power distribution, and communications infrastructure. The base bid incorporates both buildings 536Q and 534Q; however, if pricing exceeds budget constraints, Building 534Q may be dropped as a deductive alternate, requiring bidders to account for this possibility in their quantity takeoffs. The contract documents indicate an April 2026 project completion date, and all work must comply with the National Electrical Code and applicable Michigan state and local electrical codes.
The project requires coordination across multiple trades including mechanical systems, fire protection, and structural work, with the general contractor responsible for site verification prior to bidding, ensuring all subcontractors receive complete contract documents, and maintaining an on-site representative during construction with approved shop drawings. Key requirements include installation of new underground electrical feeders from switchboard P-538, new data cabling terminating in a communications server rack, fire alarm system integration with remote monitoring capability, and disconnection and removal of existing underground electrical feeders. The contractor must contact utilities at least 72 hours before excavation work (reference Mr. C.G. Michael Halcomb at 989-344-6184). All electrical conduit must transition from PVC to galvanized rigid metal conduit when crossing concrete slabs or transitioning from below-grade to above-grade locations, and all exposed conduit must be painted to match adjacent wall and ceiling finishes.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R ss ss s s s s ss ss s s s ss s s sss ss ss s s
3 3 ss s ss s s
7 7
3 3
DATA/TELEPHONE SYSTEM OUTLET, WALL MOUNTED
TELEPHONE TERMINAL CABINET
ELECTRICAL DISTRIBUTION PANEL
ELECTRICAL LIGHTING PANEL
IN A SINGLE GANG DEVICE BOX
ELECTRICAL LEGEND
LIGHTING CONTACTOR
FOUR WAY SWITCH
THREE WAY SWITCH
ELECTRIC MOTOR
DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER
MAGNETIC MOTOR STARTER
TWO POLE SWITCH
A
C
S SINGLE POLE SWITCH
EXIT LIGHT, WALL MOUNTED
EXIT LIGHT, CEILING MOUNTED
LETTER INDICATES TYPE
HOMERUN TO LIGHTING, RECEPTACLE OR POWER PANEL
CONDUIT AND WIRE CONCEALED IN CEILING OR WALL
SPECIAL RECEPTACLE 250V. 2P-3WIRE GROUNDING TYPE
DUPLEX CONVENIENCE RECEPTACLE WITH GROUND
DUPLEX RECEPTACLE 20A. 125V. 2 POLE 3 WIRE
LED LIGHT FIXTURE, LETTER INDICATES TYPE
WALL MOUNTED LIGHTING FIXTURE
DUPLEX CONVENIENCE RECEPTACLE WITH GFI
ACT
MANUAL MOTOR STARTER WITH THERMAL OVERLOADS
T
BUSSMAN "FUSESTAT" BOXCOVER WITH SWITCH
EMERGENCY OFF PUSHBUTTON STATION,
MOUNT ABOVE COUNTER TOPACT
ABOVE FINISH FLOORAFF
S
S
S
S & SCREW-IN FUSE SIZED FOR LOAD
FAULT PROTECTION
GROUNDING TYPE
PROTECTION; ABOVE COUNTER TOP
REFER TO SPECIFICATION
C
LETTER INDICATES TYPE
CEILING MOUNTED LIGHTING FIXTURE
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
E-
JU
L
AP
R
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
TE
G
AY
LI
N G
, M
IC
H
IG
AN
E-1
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND
BUILDING 534Q UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, SCHEDULES SHOWN ARE FOR 1
EACH BUILDING; CONTRACTOR SHALL BE RESPONSIBLE FOR
THE QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS
536Q AND 534Q ARE REMODELED.
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND BUILDING 534Q
UNLESS OTHERWISE NOTED. BASE BID INCORPORATES BOTH BUILDINGS
536Q & 534Q. CONTRACTOR SHALL BE RESPONSIBLE FOR THE
QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS 536Q AND 534Q
ARE REMODELED. IF PRICING IS TOO HIGH, BUILDING 534Q WILL BE
DROPPED FROM THE CONTRACT (DEDUCTIVE ALTERNATE) SO BIDDING
CONTRACTORs NEED TO DO THEIR TAKE-OFFs WITH THIS IN MIND.
ELECTRICAL FIRST FLOOR DEMOLITION PLAN
SCALE 1/8" = 1'-0"
ELECTRICAL DEMOLITION KEY NOTES X :
1. APPROXIMATE UNDERGROUND ROUTE OF BUILDING PANEL FEEDER. CONTRACTOR
SHALL DISCONNECT FEEDER, REMOVE FROM BUILDING AND OUTSIDE WALL, CUT
CONDUIT AND WIRE BELOW GRADE AND ABANDON IN PLACE. PATCH HOLES IN
MASONRY WALLS AND FLOOR WITH EPOXY GROUT.
2. EXISTING UNDERGROUND FEEDER BETWEEN BUILDING 536Q AND EXISTING
SWITCHBOARD P-538 IS ROUTED ON THE NORTH SIDE OF THE SAND DRIVE AND
PARALLEL WITH THE BUILDINGS UNTIL IT IS DIRECTLY NORTH OF P-538. IT THEN CUTS
DIRECTLY SOUTH, UNDERGROUND TO P-538.
3. REMOVE EXISTING EXTERIOR LIGHTING FIXTURES. PATCH HOLES IN MASONRY WALLS
AND FLOOR WITH EPOXY GROUT.
4. REMOVE EXISTING CONDUIT, WIRE, RECEPTACLES, DEVICES AND BOXES IN THIS ROOM.
REMOVE LIGHTING FIXTURES, SWITCHES AND SWITCH BOXES. ALL CIRCUITS AND
RACEWAYS SHALL BE REMOVED BACK TO THEIR SOURCE.
5. REMOVE EXISTING PANELBOARD, CONDUIT AND WIRING ONCE NEW ELECTRICAL
SYSTEM IS OPERATIONAL. PATCH ALL MASONRY HOLES WITH EPOXY GROUT IN BILLET
LOCATION.
6. DISCONNECT EXISTING EXHAUST FANS AND AIR HANDLING EQUIPMENT. REMOVE
ELECTRICAL CONDUIT AND WIRE BACK TO IT'S SOURCE. REMOVE CONTROLS
EQUIPEMENT, DEVICES, WIRING, AND CONDUIT BACK TO SOURCE.
7. EXISTING UNDERGROUND TELECOMM CABLE ROUTE. CABLE RUNS UP ALONG SIDE OF
BUILDING WALL, ENTERS THE BUILDING, AND ROUTES ALONG TO THE "COMMSCOPE
BMP" ENCLOSURE. CONTRACTOR SHALL DISCONNECT AND REMOVE THIS CABLE, COIL
IT UP OUTSIDE THE BUILDING, PROTECT IT DURING CONSTRUCTION, AND REROUTE IT
INTO THE TO THE NEW COMMUNICATIONS RACK IN FAN ROOM 103S. THE CONTRACTOR
SHALL ALSO REMOVE, SAVE, STORE, PROTECT, AND REMOUNT THE EXISTING
TELEPHONE CABLE TERMINATION "COMMSCOPE BMP" ENCLOSURE NEXT TO THE NEW
COMM RACK
**534Q EXISTING LATRINE
**THE EXISTING LATRINE FLOOR PLANS FOR 536Q
AND 534Q ARE DIFFERENT - THESE TWO PLANS
SHOW THE DIFFERENCES; THE REMAINING FLOOR
PLAN AREAS ARE THE SAME IN EACH BUILDING.**536Q EXISTING LATRINE
E-1
2 ELECTRICAL FIRST FLOOR DEMOLITION PLAN
SCALE 1/8" = 1'-0"
GENERAL ELECTRICAL CONSTRUCTION NOTES (APPLIES TO ALL
ELECTRICAL DRAWINGS & DETAILS):
1. SEAL ALL FIRE RATED WALL & CEILING PENETRATIONS WITH FIRE RATED CAULK.
2. CONNECT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO LOCAL LIGHTING CIRCUITS AHEAD OF THE ROOM LIGHTING
CONTROL.
3. COORDINATE LOCATIONS OF LIGHT FIXTURES WITH ALL PIPING, DUCTWORK, AND EQUIPMENT. MOUNT LIGHT FIXTURES TO
ALLOW THE GREATEST POSSIBLE HEADROOM.
4. UNLESS OTHERWISE NOTED OR DETAILED, INSTALL ALL CONDUCTORS IN CONDUIT. THIS INCLUDES FIRE ALARM, DDC, LOW
VOLTAGE LIGHTING CONTROL WIRING, AND DATA CABLES.
5. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ACCEPTED EDITION OF THE NATIONAL ELECTRICAL
CODE AND ALL STATE AND LOCAL CODES.
6. COORDINATE THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT AND CONNECTIONS WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
7. "BACK TO BACK" OR THROUGH THE WALL BOXES SHALL NOT BE USED.
8. RECEPTACLES INDICATED AS GROUND FAULT CIRCUIT INTERRUPTER TYPE MAY BE EITHER GFI RECEPTACLES OR
SPECIFICATION GRADE DUPLEX RECEPTACLES CONNECTED TO A CIRCUIT PROTECTED BY A GFI CIRCUIT BREAKER.
9. PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN EVERY POWER AND LIGHTING CONDUIT, ONE GROUNDING CONDUCTOR
FOR EACH CIRCUIT INCLUDING LIGHTING FIXTURE WHIPS (IF INSTALLED). ALL 120V CIRCUITS SHALL CONSIST OF AN UNGROUNDED CONDUCTOR, AN INSULATED NEUTRAL AND A GROUNDING CONDUCTOR. THERE SHALL BE NO SHARING OF
NEUTRALS.
10. ALL LIGHTING AND POWER CONDUCTORS SHALL BE 12 AWG MINIMUM.
11. MINIMUM CONDUIT SIZE SHALL BE 3/4" INTERNAL DIAMETER.
12. ARMORED CABLE TYPE AC or "BX" AND METAL CLAD TYPE MC CABLE SHALL NOT BE USED ON THIS PROJECT.
13. CONTRACTOR SHALL TRANSITION FROM PVC CONDUIT TO GALVANIZED RIGID METALLIC CONDUIT (GRC) WHEN TURNING UP
FROM BELOW A CONCRETE SLAB OR FROM BELOW GRADE TO ABOVE GRADE, WEATHER INDOORS OR OUTDOORS, BY INSTALLING A GRC NINETY DEGREE ELBOW AND THEN CONTINUING ABOVE SLAB OR GRADE UTILIZING GALVANIZED RIGID METAL CONDUIT. THIS APPLIES TO ALL RACEWAYS FOR ALL SYSTEMS INCLUDING DATA, UTILITY POWER AND/OR
EMERGENCY POWER, LIGHTING, & COMMUNICATIONS SYSTEMS.
14. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE PRIOR TO BIDDING TO VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS.
15. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING HIS SUBCONTRACTORS AND SUPPLIERS ALL THE NECESSARY CONTRACT DOCUMENTS TO ENSURE THEY INCLUDE ALL ITEMS IN THEIR BID THAT ARE WITHIN THEIR
DISCIPLINE.
16. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK REQUIRED AND PERFORMED TO CARRY OUT THE INTENT OF
THIS PROJECT; INCLUDING THAT WORK REQUIRED AND PERFORMED BY THE SUBCONTRACTORS.
17. THE GENERAL CONTRACTOR SHALL HAVE A RESPONSIBLE REPRESENTATIVE FROM THEIR COMPANY ON SITE AT ALL TIMES DURING HIS COMPANY'S WORK, OR THE WORK OF ONE OF THE SUBCONTRACTORS. THIS REPRESENTATIVE SHALL HAVE ON SITE, HIS OWN COPY OF THE CONTRACT SPECIFICATIONS, DRAWINGS AND DMVA APPROVED SHOP DRAWINGS.
18. DISCREPANCIES FOUND BETWEEN THE SPECIFICATIONS AND THE DRAWINGS SHALL BE SUBMITTED TO DMVA IN THE FORM OF AN RFI FOR CLARIFICATION PRIOR TO ANY WORK INVOLVING THIS DISCREPANCY. ELECTRICAL DEMOLITION PLANS
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text 102N
AutoCAD SHX Text 100S
AutoCAD SHX Text 104N
AutoCAD SHX Text 102S
AutoCAD SHX Text 104S
AutoCAD SHX Text 100S
AutoCAD SHX Text
AutoCAD SHX Text 103S
AutoCAD SHX Text 100N
AutoCAD SHX Text 100N
AutoCAD SHX Text 103N
AutoCAD SHX Text 4" D.
AutoCAD SHX Text 10" D.
AutoCAD SHX Text 8" D.
AutoCAD SHX Text 8" D.
AutoCAD SHX Text 10" D.
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text 100S
AutoCAD SHX Text 100S
AutoCAD SHX Text
AutoCAD SHX Text 103S
AutoCAD SHX Text 100N
AutoCAD SHX Text 100N
AutoCAD SHX Text 103N
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
EWC
GFI, A18
ENC-2 ENC-3
J
FIRE SUPPRESSION
SYSTEM HORN &
STROBE, NOTE 11
EWC
GFI, B18
R
R
NOTES
1 & 11NOTES
1 & 11
NOTE 20 NOTE 20
MDP-19
(B-1, P-1)
MDP-21
(B-2, P-2)
JNOTES
9 & 10
NOTES
16, 21
R
R
FIRE
SUPPRESSION
EQUIPMENT
(MDP-23)
NOTES
9 & 10
EXTEND TELECOMM.
CABLING TO 103S,
REMOUNT EXISTING
TERMINATION
EQUIPMENT, INSTALL
NEW SERVER RACK AND
IT EQUIPMENT, SEE
NOTES 16, & 21
NEW HANDHOLE FOR
NEW FIBER CABLE -
REFER TO CIVIL
DRAWINGS FOR
UNDERGROUND CABLE
PATH TO HANDHOLE,
ROUTE IN ORANGE
INNERDUCT TO SERVER
RACK IN FAN ROOM 103S
NEW SERVER RACK,
SEE NOTES AND
DETAIL ON E-6
SEE
HANDHOLE
SCHEDULE
ON SHEET
E-4
DATA REQURIED FOR
FIRE ALARM PANEL
DATA REQUIRED
FOR BMS
ENCLOSURE
UNIT HEATER
FAN RUN OFF
LINE VOLTAGE
THERMOSTAT,
SEE MECH.
Future Refrig
PANEL B PANEL A
A19
A7
42" AFF 42" AFF
GFI
B11
MDP-8,10,12
AHU-2
MDP 9,11
AHU-1
ACT
GFI
Future Refrig
A19 A19
A19
A11 A11 A11 A11
A11
A7 A7
A7
A9A9 A9 A9
A9
A4
A4
A4A4A4
A2
A2A2A2A2
A8 A8
A8
A8 A6A8 A6A6
A7
A15/17 A8
A16
ACT
B15,17 B8
B13
A12
A12
GFI
42" AFF
B12
B12B12
B16
GFI
GFI
ACT
GFI
A16
ACT
GFI
A16
ACT
GFI
A16
ACT
GFI
B16
ACT
GFI
B16
ACT
GFI
B16
B7
B11 B11 B11 B19
B11
B9
B9 B9B9 B9
B7
B7 B7 B7
B6
B4
B4
B4 B4 B4
B6 B6 B8B8
B8
B2
B2
B2 B2 B2
B8 B8
A12
GFI
42" AFF
HH-A
NOTES 1 & 11
NOTES 1 & 11
NOTES 1 & 11
NOTES 1 & 11
10'-0"
NEW UNDERGROUND MDP FEEDER FROM P-538
MDP CU-1
B14 A14
B19 B19
B19
B-1
P-1
B-2
P-5
P-3
MDP-16
ENC-1
MDP 31,33
MDP-17
NOTE 17
GFI
UH-1
MDP-22
MDP-25
WP, GFI
MDP-20
MDP-26,28,30
CU-2
WP, GFI
MDP-20
P-2
NOTE 22
NOTE 22 NOTE 22
NOTE 22
P-4
FACP
P-6 MDP-15
GM-1
GFI
GFI
MDP-20
MDP-24
MDP-18
MDP-27
B5
GFI
A5
GFI
B5
MDP-16
HH-B
MDP 1,3,5MDP 2,4,6
A13
EF-1
MDP-14
EF-2
MDP-14
A5
CU
NOTE 1
CONDENSING UNIT DISCONNECT DETAIL NOTES:
1. THE BUILDING'S EXTERIOR'S SPLIT-FACE BLOCK PRESENTS AN
UNEVEN MOUNTING SURFACE, THEREFORE PROVIDE & INSTALL A
GALVANIZED U-CHANNEL RACK TO HOLD THE TWO ELECTRICAL
DISCONNECTS FOR THE CONDENSING UNITS. SIZE AS NEEDED TO
HOLD THE SWITCHES AND JUNCTION BOX.
2. CONFIGURE U-CHANNEL RACK SUCH THAT THE DISCONNECT
SWITCHES ARE 2'-0" TO BOTTOM OF SWITCH ENCLOSURE.
3. THE RACKS LOCATION SHALL BE IN FRONT OF THE TWO CONDENSING
UNITS PROVIDING THE PROPER NEC CLEARANCE SPACE.
4. ROUTE THE CONDUCTORS FROM EACH DISCONNECT TO THE
RESPECTIVE CONDENSING UNIT UTILIZING LIQUID-TITE FLEXIBLE
METAL CONDUIT.
5. BRANCH CIRCUITS FROM MDP. ROUTE UNDERSLAB THEN
UNDERGROUND FROM MDP TO THIS DISCONNECT RACK. RACEWAY
SHALL BE RIGID METAL CONDUIT WHERE EXPOSED.
6. UTILIZE STAINLESS STEEL HARDWARE TO SECURE U-CHANNEL STEEL
TO THE CONCRETE. PROVIDE AND INSTALL EXPANSION ANCHORS
INTO CONCRETE. BRACE THE RACK FROM BEHIND WITH TWO
U-CHANNEL LENGTHS AT A 45° ANGLE TO THE CONCRETE SLAB.
VERTICAL U-CHANNEL BASE PLATE SHALL BE MANUFACTURED BY THE
SAME COMPANY THAT MANUFACTURERS THE U-CHANNEL.
7. MOUNT A NEW GFI RECEPTACLE IN A WEATHERPROOF DEVICE BOX
WITH A WEATHERPROOF RECEPTACLE COVER ON THE BACKSIDE OF
THE U-CHANNEL RACK.
NOTE 5
NOTE 6
CONCRETE
SLAB -
SEE CIVIL
NOTE 7
24" BETWEEN TOP OF
CONDUITS AND UNDERSIDE
OF SLAB
Grade
NEW HANDHOLE HH-A
SIZED AS INDICATED IN
HANDHOLE SCHEDULE
ON SHEET E-4
TWO (2) 2" PVC CONDUITS
FROM THE HAND HOLE TO
THE MECHANICAL ROOM.
30° BEND UP INTO
OPEN BOTTOM
OF HANDHOLE
FIN FLOOR
TRANSITION FROM PVC TO
RIGID METAL CONDUIT
BELOW CONCRETE SLAB
MAIN
DISTRIBUTION
PANEL MDP
BOX OUT OPENING DURING
FOUNDATION POUR. COORDINATE
WITH GENERAL TRADES
R
R
MDP-19
(B-1, P-1)
MDP-21
(B-2, P-2)
R
R
FIRE
SUPPRESSION
EQUIPMENT
(MDP-23)
EXTEND TELECOMM.
CABLING TO 103S,
REMOUNT EXISTING
TERMINATION
EQUIPMENT, INSTALL
NEW SERVER RACK AND
IT EQUIPMENT, SEE
NOTES 16, & 21
NEW HANDHOLE FOR
NEW FIBER CABLE -
REFER TO CIVIL
DRAWINGS FOR
UNDERGROUND CABLE
PATH TO HANDHOLE,
ROUTE IN ORANGE
INNERDUCT TO SERVER
RACK IN FAN ROOM 103S
SEE
HANDHOLE
SCHEDULE
ON SHEET
E-4
DATA REQURIED FOR
FIRE ALARM PANEL
DATA REQUIRED
FOR BMS
ENCLOSURE
UNIT HEATER
FAN RUN OFF
LINE VOLTAGE
THERMOSTAT,
SEE MECH.
B13
HH-A
10'-0"
MDP
B-1
P-1
B-2
P-5
P-3
MDP-16
ENC-1
NOTE 17
GFI
UH-1
MDP-22
MDP-25
P-2
P-4
FACP
P-6 MDP-15
GM-1
GFI
GFI
MDP-20
MDP-24
MDP-18
MDP-27
MDP-16
HH-B
A13
DATA/TELEPHONE SYSTEM OUTLET, WALL MOUNTED
TELEPHONE TERMINAL CABINET
ELECTRICAL DISTRIBUTION PANEL
ELECTRICAL LIGHTING PANEL
IN A SINGLE GANG DEVICE BOX
ELECTRICAL LEGEND
LIGHTING CONTACTOR
FOUR WAY SWITCH
THREE WAY SWITCH
ELECTRIC MOTOR
DISCONNECT SWITCH
COMBINATION MAGNETIC MOTOR STARTER
MAGNETIC MOTOR STARTER
TWO POLE SWITCH
A
C
S SINGLE POLE SWITCH
EXIT LIGHT, WALL MOUNTED
EXIT LIGHT, CEILING MOUNTED
LETTER INDICATES TYPE
HOMERUN TO LIGHTING, RECEPTACLE OR POWER PANEL
CONDUIT AND WIRE CONCEALED IN CEILING OR WALL
SPECIAL RECEPTACLE 250V. 2P-3WIRE GROUNDING TYPE
DUPLEX CONVENIENCE RECEPTACLE WITH GROUND
DUPLEX RECEPTACLE 20A. 125V. 2 POLE 3 WIRE
LED LIGHT FIXTURE, LETTER INDICATES TYPE
WALL MOUNTED LIGHTING FIXTURE
DUPLEX CONVENIENCE RECEPTACLE WITH GFI
ACT
MANUAL MOTOR STARTER WITH THERMAL OVERLOADS
T
BUSSMAN "FUSESTAT" BOXCOVER WITH SWITCH
EMERGENCY OFF PUSHBUTTON STATION,
MOUNT ABOVE COUNTER TOPACT
ABOVE FINISH FLOORAFF
S
S
S
S & SCREW-IN FUSE SIZED FOR LOAD
FAULT PROTECTION
GROUNDING TYPE
PROTECTION; ABOVE COUNTER TOP
REFER TO SPECIFICATION
C
LETTER INDICATES TYPE
CEILING MOUNTED LIGHTING FIXTURE
RELAYR
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
E-
JU
L
AP
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
E-2
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
COORDINATION NOTES:
· SEE SHEET C-1 FOR SITE UTILITIES.
· 536Q & 534Q FOLLOW THE SAME FLOOR PLAN UNLESS
OTHERWISE NOTED; SITE UTILITIES,
SITE GRADING, LANDSCAPING AND SIDEWALKS MAY BE
SLIGHTLY DIFFERENT FROM BUILDING TO BUILDING; SEE
DRAWING SHEETS C-1 THRU C-3.
ELECTRICAL POWER PLAN NOTES:
1. NEW RECEPTACLE CIRCUITS SHALL BE RUN HORIZONTALLY IN SURFACE MOUNTED
RACEWAY, SECURED TO THE EXISTING BLOCK WALL WITH HALF STRAPS AND LEAD
ANCHORS, WHERE NEW INTERIOR WALL SURFACES ARE NOT CONSTRUCTED.
DEVICE BOXES SHALL BE FD TYPE CAST BOXES WITH MATCHING DEVICE COVERS.
UTILIZE COMPRESSION TYPE FITTINGS (COUPLINGS & CONNECTORS) ON THESE
RACEWAYS.
2. ALL JUNCTION BOXES IN THE ATTIC SHALL BE MOUNTED TO THE TRUSSES ABOVE
THE INSULATION LINE.
3. ATTIC ACCESS PANEL.
4. MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" ABOVE FLOOR, UNLESS NOTED
OTHERWISE.
5. NOT USED
6. PROVIDE AND INSTALL 4"x4" JUNCTION BOX AND BLANK COVER FOR CONNECTING
THE EXTERIOR LIGHTING FIXTURE CONTROL TO THE LIGHTING CONTROL RELAY.
MOUNT ON WALL ABOVE THE MAIN DISTRIBUTION PANEL MDP. PLACE AN
IDENTIFICATION PLATE INDICATING THE BOX AND RELAY ARE "EXTERIOR LIGHTING
FIXTURE CONTROL".
7. PROVIDE A CONDUIT FROM BOTTOM OF PANEL MDP DOWN THROUGH THE FLOOR
AND THROUGH THE NEW MECHANICAL ROOM FOUNDATION WALL IN THE SPECIFIED
SLEEVES (COORDINATED). EXTERIOR CONDUIT AND LB FITTINGS WILL NOT BE
ALLOWED. THE SLEEVES SHALL BE COORDINATED WITH OTHER DISCIPLINES AT
THE TIME THE FOUNDATION IS BEING BUILT.
8. ALL EXPOSED ELECTRICAL CONDUIT SHALL BE PAINTED TO MATCH THE ADJACENT
WALLS/CEILINGS FINISH COLOR.
9. ROUTE 4#14 AWG THHN, 3/4" C BETWEEN EACH CONDENSING UNIT AND IT'S
ASSOCIATED AIR HANDLING UNIT (i.e. CU-1 & AHU-1).
10.REFER TO THE CONDENSING UNIT DISCONNECT DETAIL, SHEET E-2 FOR
ELECTRICAL RACEWAY AND SWITCH PLACEMENT REQUIREMENTS.
11.COORDINATE THE HEIGHT ABOVE FINISH GRADE OF THE DEVICE BOX FOR THE FIRE
SUPPRESSION SYSTEM HORN & STROBE UNIT.
12.CONNECT THE INCOMING POWER CONDUCTOR FOR THE EXHAUST FAN TO THE
ROOM'S LIGHTING SYSTEM OCCUPANCY SENSOR'S INTERNAL RELAY SO THAT THE
FAN INDICATED COMES ON WHEN THE OCCUPANCY SENSOR SENSES MOVEMENT.
SET THE SENSOR'S TIME-OFF TO 20 MINUTES. (EF-2, EF-3)
13.CONNECT THE INCOMING POWER CONDUCTOR FOR EXHAUST FAN EF-1 TO THE
LIGHTING SYSTEM OCCUPANCY SENSORS RELAY CONTROLLING THE TYPE D & D2
LIGHTING FIXTURES IN ROOM 105S SO THAT THE FAN COMES ON WHEN THE
OCCUPANCY SENSOR SENSES MOVEMENT. SET THE SENSOR'S TIME-OFF TO 20
MINUTES. EF-1 IS INSTALLED ABOVE THE FIRE PROTECTION SYSTEM'S PIPING NEAR
THE CEILING IN MECHANICAL ROOM 107.
14.CONNECT THE INCOMING POWER CONDUCTOR FOR EXHAUST FAN EF-6 TO THE
LIGHTING SYSTEM OCCUPANCY SENSORS RELAY CONTROLLING THE TYPE D & D2
LIGHTING FIXTURES IN ROOM 105N SO THAT THE FAN COMES ON WHEN THE
OCCUPANCY SENSOR SENSES MOVEMENT. SET THE SENSOR'S TIME-OFF TO 20
MINUTES. EF-6 IS INSTALLED ABOVE BOILER B-1 NEAR THE CEILING IN MECHANICAL
ROOM 107.
15.FOR HVAC PUMPS P-3, P-4, P-5, AND P-6 PROVIDE AND INSTALL A MANUAL MOTOR
STARTER AND RIB UNIT AS DETAILED ON THIS SHEET "HVAC MOTOR STARTER
DETAIL. COORDINATE EXACT MOUNTING LOCATIONS OF THESE MOTOR STARTER
COMPONENTS WITH THE MECHANICAL TRADES.
16.REMOUNT THE EXISTING TELECOMMUNICATIONS TERMINATION/TELEPHONE CABLE
TERMINATION/FUSE ENCLOSURE NEXT TO THE NEW COMMUNICATIONS RACK ON
THE PLYWOOD BACKBOARD.
17.PROVIDE A 2-POLE BOILER EMERGENCY PUSHBUTTON TO TURN OFF BOTH BOILER
CIRCUITS WITH ONE BUTTON, 20AMP CONTACT RATING.
18.CONNECT THE INCOMING POWER CONDUCTOR FOR EXHAUST FAN EF-4 TO THE
LIGHTING SYSTEM OCCUPANCY SENSORS RELAY CONTROLLING THE TYPE D & D2
LIGHTING FIXTURES IN ROOM 205N SO THAT THE FAN COMES ON WHEN THE
OCCUPANCY SENSOR SENSES MOVEMENT. SET THE SENSOR'S TIME-OFF TO 20
MINUTES.
19.CONNECT THE INCOMING POWER CONDUCTOR FOR EXHAUST FAN EF-5 TO THE
LIGHTING SYSTEM OCCUPANCY SENSORS RELAY CONTROLLING THE TYPE D & D2
LIGHTING FIXTURES IN ROOM 205S SO THAT THE FAN COMES ON WHEN THE
OCCUPANCY SENSOR SENSES MOVEMENT. SET THE SENSOR'S TIME-OFF TO 20
MINUTES.
20. INSTALL NEW DATA RECEPTACLE. RUN CAT 6A CABLING IN CONDUIT BACK TO
PATCH PANEL IN SERVER RACK. TERMINATE, LABEL, AND TEST. PROVIDE
ADDITIONAL PATCH CABLES 1 PER DATA DROP FOR DMVA IT TO PERFORM FINAL
CONNECTIONS.
21. MOUNT THE NEW DATA RACK AND EXISTING/SAVED "COMMSCOPE BEP" TELEPHONE
ENCLOSURE ON THE NEW PLYWOOD BACKBOARD. 4' T x 3' W X 3/4" FIRE PROOF
PLYWOOD BACKBOARD. 36" AFF TO BOTTOM OF PLYWOOD.
22. NEW CEILING MOUNTED DATA RECEPTACLE FOR FUTURE WIRELESS ACCESS
POINT. RUN CAT 6A CABLING IN CONDUIT BACK TO PATCH PANEL IN SERVER RACK.
TERMINATE, LABEL, AND TEST. PROVIDE PATCH CABLES 1 PER TERMINATION FOR
DMVA IT TO PERFORM FINAL CONNECTIONS FROM PATCH PANEL TO SWITCH.
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND
BUILDING 534Q UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, SCHEDULES SHOWN ARE FOR 1
EACH BUILDING; CONTRACTOR SHALL BE RESPONSIBLE FOR
THE QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS
536Q AND 534Q ARE REMODELED.
HVAC MOTOR STARTER DETAIL NOTES:
1. PROVIDE AND INSTALL A MOTOR STARTER & MANUAL DISCONNECT FOR THE MECHANICAL ITEM
INDICATED ON THE DRAWINGS. STARTER SHALL BE RIB MODEL #RIBX24SBA CONNECTED TO A
MANUAL MOTOR STARTER. RIB UNIT SHALL HAVE AN ENCLOSURE AND A HAND-OFF-AUTO SELECTOR
SWITCH MOUNTED ON THE SIDE. MANUAL MOTOR STARTER SHALL BE THE OPEN TYPE AND
MOUNTED IN A 4-SQUARE BOX WITH A MUD RING.
2. RIB UNIT BY FUNCTIONAL DEVICES, INC. (PHONE 800.888.5538, WWW.FUNCTIONALDEVICES.COM).
3. MANUAL MOTOR STARTER: SQUARE D/SCHNEIDER ELECTRIC CLASS 2510 SINGLE UNIT TYPE, 16A
RATED, WITH MELTING ALLOY TYPE THERMAL OVERLOADS. THE TOGGLE SWITCH MUST HAVE A
PILOT LIGHT AND THE ABILITY TO BE LOCKED WHEN THE UNIT IS SWITCHED TO THE "OFF" POSITION.
HVAC MANUAL MOTOR STARTER DETAIL
NO SCALE
4-SQUARE BOX
RIB RELAY UNIT
MANUAL MOTOR
STARTER
PILOT LIGHT
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND BUILDING 534Q
UNLESS OTHERWISE NOTED. BASE BID INCORPORATES BOTH BUILDINGS
536Q & 534Q. CONTRACTOR SHALL BE RESPONSIBLE FOR THE
QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS 536Q AND 534Q
ARE REMODELED. IF PRICING IS TOO HIGH, BUILDING 534Q WILL BE
DROPPED FROM THE CONTRACT (DEDUCTIVE ALTERNATE) SO BIDDING
CONTRACTORs NEED TO DO THEIR TAKE-OFFs WITH THIS IN MIND.
ELECTRICAL FIRST FLOOR
POWER/DATA PLAN
SCALE 1/8" = 1'-0"
GENERAL ELECTRICAL CONSTRUCTION NOTES (APPLIES TO ALL
ELECTRICAL DRAWINGS & DETAILS):
1. SEAL ALL FIRE RATED WALL & CEILING PENETRATIONS WITH FIRE RATED CAULK.
2. CONNECT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO LOCAL LIGHTING CIRCUITS AHEAD OF THE ROOM LIGHTING
CONTROL.
3. COORDINATE LOCATIONS OF LIGHT FIXTURES WITH ALL PIPING, DUCTWORK, AND EQUIPMENT. MOUNT LIGHT FIXTURES TO
ALLOW THE GREATEST POSSIBLE HEADROOM.
4. UNLESS OTHERWISE NOTED OR DETAILED, INSTALL ALL CONDUCTORS IN CONDUIT. THIS INCLUDES FIRE ALARM, SOUND
AND PAGING, AND DATA CABLES.
5. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ACCEPTED EDITION OF THE NATIONAL ELECTRICAL
CODE AND ALL STATE AND LOCAL CODES.
6. COORDINATE THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT AND CONNECTIONS WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
7. "BACK TO BACK" OR THROUGH THE WALL BOXES SHALL NOT BE USED.
8. RECEPTACLES INDICATED AS GROUND FAULT CIRCUIT INTERRUPTER TYPE MAY BE EITHER GFI RECEPTACLES OR
SPECIFICATION GRADE DUPLEX RECEPTACLES CONNECTED TO A CIRCUIT PROTECTED BY A GFI CIRCUIT BREAKER.
9. PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN EVERY POWER AND LIGHTING CONDUIT, ONE GROUNDING CONDUCTOR
FOR EACH CIRCUIT INCLUDING LIGHTING FIXTURE WHIPS (IF INSTALLED). ALL 120V CIRCUITS SHALL CONSIST OF AN UNGROUNDED CONDUCTOR, AN INSULATED NEUTRAL AND A GROUNDING CONDUCTOR. THERE SHALL BE NO SHARING OF
NEUTRALS.
10. ALL LIGHTING AND POWER CONDUCTORS SHALL BE 12 AWG MINIMUM.
11. MINIMUM CONDUIT SIZE SHALL BE 3/4" INTERNAL DIAMETER.
12. ARMORED CABLE TYPE AC or "BX" AND METAL CLAD TYPE MC CABLE SHALL NOT BE USED ON THIS PROJECT.
13. CONTRACTOR SHALL TRANSITION FROM PVC CONDUIT TO GALVANIZED RIGID METALLIC CONDUIT (GRC) WHEN TURNING UP
FROM BELOW A CONCRETE SLAB OR FROM BELOW GRADE TO ABOVE GRADE, WEATHER INDOORS OR OUTDOORS, BY INSTALLING A GRC NINETY DEGREE ELBOW AND THEN CONTINUING ABOVE SLAB OR GRADE UTILIZING GALVANIZED RIGID METAL CONDUIT. THIS APPLIES TO ALL RACEWAYS FOR ALL SYSTEMS INCLUDING DATA, UTILITY POWER AND/OR
EMERGENCY POWER, LIGHTING, & COMMUNICATIONS SYSTEMS.
14. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE PRIOR TO BIDDING TO VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS.
15. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING HIS SUBCONTRACTORS AND SUPPLIERS ALL THE NECESSARY CONTRACT DOCUMENTS TO ENSURE THEY INCLUDE ALL ITEMS IN THEIR BID THAT ARE WITHIN THEIR
DISCIPLINE.
16. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK REQUIRED AND PERFORMED TO CARRY OUT THE INTENT OF
THIS PROJECT; INCLUDING THAT WORK REQUIRED AND PERFORMED BY THE SUBCONTRACTORS.
17. THE GENERAL CONTRACTOR SHALL HAVE A RESPONSIBLE REPRESENTATIVE FROM THEIR COMPANY ON SITE AT ALL TIMES DURING HIS COMPANY'S WORK, OR THE WORK OF ONE OF THE SUBCONTRACTORS. THIS REPRESENTATIVE SHALL HAVE ON SITE, HIS OWN COPY OF THE CONTRACT SPECIFICATIONS, DRAWINGS AND DMVA APPROVED SHOP DRAWINGS.
18. DISCREPANCIES FOUND BETWEEN THE SPECIFICATIONS AND THE DRAWINGS SHALL BE SUBMITTED TO DMVA IN THE FORM
OF AN RFI FOR CLARIFICATION PRIOR TO ANY WORK INVOLVING THIS DISCREPANCY.
CONDENSING UNIT
DISCONNECT DETAIL
NOT TO SCALE
MECHANICAL ROOM WALL SECTION
SCALE 1/2 " = 1'-0"
E-2
2 ENLARGED MECHANICAL POWER PLAN
SCALE 1/4" = 1'-0"
E-2
ELECTRICAL POWER PLANS AND DETAILS
E-2
E-2
E-2
AutoCAD SHX Text 102N
AutoCAD SHX Text 100S
AutoCAD SHX Text 104N
AutoCAD SHX Text 105N
AutoCAD SHX Text
105NA
AutoCAD SHX Text 102S
AutoCAD SHX Text 104S
AutoCAD SHX Text 103S
AutoCAD SHX Text 101S
AutoCAD SHX Text 100N
AutoCAD SHX Text 105S
AutoCAD SHX Text
105SA
AutoCAD SHX Text 101N
AutoCAD SHX Text 106S
AutoCAD SHX Text 106N
AutoCAD SHX Text 103N
AutoCAD SHX Text
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
Panel A
X
S 3A1 3S
X A1
S
X
A1
S3
X
X
X
3S
X
AE A
X
A
X
B1
X
X X
D
DE
JE
J
F
E S 3
E
Note 5
Note 5
A1
S
B3
B3
B3
S
B1
B1
3SPanel B
E
B BE B B BE
B
C
J
F
S
HH
HH
B1
D
DE J
JE
S
B3
B3
A3
A3
J
A3
MDP-7
A3
X A3
A X X
B3
A3
OC1
OC1
OC1
OC1
3S
B3
AE
OC1
B
BE B B BE B
B BE B B BE
B B
BE B B BE B
OC2
AEA
A
A3
A
AE
OC1
OC2
E
B3
A3
S 3
CKT MDP-13 VIA RELAY
IN MECH ROOM
MOUNT AT HEIGHT AS
INDICATED ON SHEET A2.1
CKT MDP-13 VIA
RELAY IN MECH ROOM
OC1 OC1
X
X
E
MOUNT AT HEIGHT AS
INDICATED ON SHEET A2.1
MOUNT AT HEIGHT
AS INDICATED ON
SHEET A2.1
E CKT MDP-13 VIA
RELAY IN MECH ROOM
MOUNT AT HEIGHT
AS INDICATED ON
SHEET A2.1
E
CKT MDP-13 VIA
RELAY IN MECH ROOM
MOUNT AT HEIGHT
AS INDICATED ON
SHEET A2.1
E
CKT MDP-13 VIA
RELAY IN MECH ROOM
JR
Note 8
LOW
TEMPERATURE
LIGHT
TEMPERATURE
SENSOR CONNECTED
TO THE LOW
TEMPERATURE LIGHT
MDP
CE
F
F
Note 5
Note 5 F
F
C
Note 10
ALL 'X' FIXTURES -
MDP 29
Note 5
ALL 'X' FIXTURES -
MDP 29
ALL 'X' FIXTURES -
MDP 29
FREEZE ALARM NOTES:
DESCRIPTION OF OPERATION:
PROVIDE & INSTALL ALL MATERIALS TO CONNECT THE FREEZE ALARM TO OPERATE AS FOLLOWS:
· WHEN THE TEMPERATURE REACHES THE LOW TEMP SET-POINT THE FREEZE ALARM WILL
CLOSE IT'S INTEGRAL CONTACT AND ENABLE THE LED LIGHT.
COMPONENTS:
1. FREEZE ALARM THERMOSTAT: EMERSON WHITE-ROGERS MODEL #1687-9.
2. 2 #12AWG & #12 GND ROUTED IN CONDUIT TO RED ALARM LAMP AT PEAK OF SOUTH
EXTERIOR WALL.
3. FLUSH MOUNTED DEVICE BOX WITH AN AIMABLE LAMPHOLDER : HUBBELL-BELL #5606-2.
4. LED LAMP, RED, 120VAC: PHILLIPS ORDER # BC8A19/LED/RED/ND 120V.
FREEZE ALARM & OPERATION DETAIL
NO SCALE
N
1 3
CKT. AS INDICATED
IN PANEL SCHEDULE
FREEZE ALARM
THERMOSTAT "T"
RED LED LIGHT "G" ON
EXTERIOR OF BUILDING
G
G
B22
T
T
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
E-
JU
L
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
E-3
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND
BUILDING 534Q UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, SCHEDULES SHOWN ARE FOR 1
EACH BUILDING; CONTRACTOR SHALL BE RESPONSIBLE FOR
THE QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS
536Q AND 534Q ARE REMODELED.
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND BUILDING 534Q
UNLESS OTHERWISE NOTED. BASE BID INCORPORATES BOTH BUILDINGS
540Q & 538Q. CONTRACTOR SHALL BE RESPONSIBLE FOR THE
QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS 536Q AND 534Q
ARE REMODELED. IF PRICING IS TOO HIGH, BUILDING 534Q WILL BE
DROPPED FROM THE CONTRACT (DEDUCTIVE ALTERNATE) SO BIDDING
CONTRACTORs NEED TO DO THEIR TAKE-OFFs WITH THIS IN MIND.
ELECTRICAL FIRST FLOOR LIGHTING PLAN
SCALE 1/8" = 1'-0"
LIGHTING FIXTURE SCHEDULE
MARK
A
DESCRIPTION MANUFACTURER & CAT. NO. REMARKS NOTES
LIGHTING FIXTURE SCHEDULE NOTES:
1. CONTRACTOR MAY SUBSTITUTE LIGHTING FIXTURES BY OTHER MANUFACTURERS IF EQUAL IN ALL
RESPECTS; IF NOT, PROVIDE THE FIXTURE SPECIFIED. SUBMIT SHOP DRAWINGS FOR ALL SUBSTITUTIONS.
2. PROVIDE INTERNAL FAST BLOW FUSING IN EACH FIXTURE.
3. PROVIDE WITH INTEGRAL EMERGENCY LIGHT OPTION.
1,2
D
1,2,3
LED INDUSTRIAL STRIP FIXTURE
1,2,3
C
120V OPERATION, 4000K COLOR TEMP.
WILLIAMS INDOOR
75R-4-L85-840-DIM-UNV
MOUNTING
WILLIAMS INDOOR
PTS-24-L49-835-RA-DIM-UNV
F
LED SURFACE MOUNT WET LOCATION
120V OPERATIONCHAIN-HANG 8'-0" AFF
120V OPERATION AND
BATTERY BACK-UPDE
EXTERIOR BUILDING MOUNT
HEIGHT AS NOTED
120V OPERATION, 4000K COLOR TEMP.AE LED 2'x4' SURFACE MOUNT WITH BATTERY BACKUP
WILLIAMS
SLF-4-L52-HIA-(L37)-SILVER-DIM-UNV
WALL MOUNT OVER BATHROOM MIRROR 3000K
SURFACE MOUNT TO CEILING
SURFACE MOUNT TO CEILING
WILLIAMS INDOOR
96-4-L62-840-HIAFR-(L55)-DIM-UNV SURFACE MOUNT TO CEILING
SURFACE MOUNT TO CEILING
LED 2'x4' SURFACE MOUNT
FE
LED SURFACE MOUNT WET LOCATION WITH
BATTERY BACKUP
H SURFACE MOUNT TO WALL 120V OPERATION, 3000K COLOR TEMP.
E 120V OPERATION, 5000K COLOR TEMP.
X
OCCUPANCY SENSOR SCHEDULE NOTES:
1. OCCUPANCY SENSORS MANUFACTURED BY COOPER INDUSTRIES, HUBBELL, LEVITON, SENSOR SWITCH &
LUTRON ELECTRONICS ARE ACCEPTABLE IF EQUAL IN ALL RESPECTS.
2. PROVIDE WITH LIGHTING FIXTURE CIRCUIT CONTROL RELAY (POWER PACK) AND LOW-VOLTAGE POWER SUPPLY
FOR A COMPLETE AND WORKING CONTROL SYSTEM.
3. OCCUPANCY SENSOR SHALL HAVE AN ADDITIONAL/OPTIONAL RELAY TO TURN ON/OFF EXHAUST FANS (120VAC)
OR SIGNAL THE DDC SYSTEM.
FIRST FLOOR LIGHTING PLAN NOTES:
1. ROUTE CONDUIT IN CONCEALED SPACES WHERE AVAILABLE. ALL EXPOSED
ELECTRICAL CONDUIT SHALL BE PAINTED TO MATCH THE WALLS/CEILINGS FINISH
COLOR. UTILIZE COMPRESSION FITTINGS (COUPLINGS & CONNECTORS) FOR EMT
(SET SCREW FITTINGS WILL NOT BE APPROVED.)
2. ALL JUNCTION BOXES IN THE ATTIC SHALL BE MOUNTED TO THE TRUSSES ABOVE
THE INSULATION LINE.
3. ROUTE EXTERIOR LIGHTING FIXTURE CONDUITS THRU EXISTING SPLIT FACE
BLOCK AND CONCEAL BETWEEN NEW AND EXISTING BLOCK. SURFACE MOUNTED
CONDUIT ON EXTERIOR WALLS IS NOT ALLOWED.
4. CONNECT EMERGENCY LIGHTING UNITS AND EXIT FIXTURES TO THE LIGHTING
CIRCUIT IN THAT ROOM AHEAD OF THE SWITCH. TYPICAL OF ALL ROOMS.
5. COORDINATE THE LOCATION OF EACH TYPE "F" AND "C" LIGHTING FIXTURES IN
ROOMS 103N, 103S, AND 107 WITH THE MECHANICAL TRADES.
6. CONNECT THE LIGHTING CIRCUIT TO THE ROOM EXHAUST FAN.
7. SET THE OCCUPANCY SENSORS IN THE JANITOR CLOSETS, ROOM NUMBERS 101N
& 101S TO DELAY-OFF AT 20 MINUTES.
8. EXTERIOR BUILDING MOUNTED LIGHTING CONTROL WORK: CONNECT THE
EXTERIOR LIGHTING FIXTURES TO THE J-BOX INDICATED THEN CONTINUE TO MDP.
PROVIDE AND INSTALL AN ENCLOSED RELAY AND A 4-SQUARE JUNCTION BOX
ALONG WITH A BLANK COVER ON THE WALL AT 60" AFF. PROVIDE IDENTIFICATION
ON THE BLANK COVER INDICATING WHICH LIGHTING FIXTURES ARE CONTROLLED.
PROVIDE ENCLOSED RELAY BY FUNCTIONAL DEVICES, INC. MODEL #RIB2421SB.
MOUNT RELAY AND THE J-BOX ABOVE AND TO THE LEFT OF MSB.
9. CONNECT TYPE X - EXIT SIGNS TO MDP CIRCUIT 29.
10.COORDINATION MAY BE REQUIRED BETWEEN PIPING AND LIGHT FIXTURE
LOCATIONS IN THE MECHANICAL ROOM. FINAL LOCATION OF FIXTURES TO BE
DETERMINED IN THE FIELD WITH DMVA REPRESENTATIVE AND APPROVED BY
ENGINEER.
1,2
1,2,3
1,2
1,2
LED EMERGENCY EXIT SIGN WITH BATTERY BACKUP
MOUNT HIGH ON WALL INTERIOR
SIDE (THERMOSTAT)
TEMPERATURE SENSOR
MOUNT HIGH ON WALL
EXTERIOR SIDE, 6" BELOW
EAVE (RED LIGHT)
1,2G&T FREEZE ALARM REFER TO COMMENTS AND DETAIL SEE THE "FREEZE ALARM & OPERATION DETAIL" , THIS SHEET
G T
GENERAL ELECTRICAL CONSTRUCTION NOTES (APPLIES TO ALL
ELECTRICAL DRAWINGS & DETAILS):
1. SEAL ALL FIRE RATED WALL & CEILING PENETRATIONS WITH FIRE RATED CAULK.
2. CONNECT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO LOCAL LIGHTING CIRCUITS AHEAD OF THE ROOM LIGHTING
CONTROL.
3. COORDINATE LOCATIONS OF LIGHT FIXTURES WITH ALL PIPING, DUCTWORK, AND EQUIPMENT. MOUNT LIGHT FIXTURES TO
ALLOW THE GREATEST POSSIBLE HEADROOM.
4. UNLESS OTHERWISE NOTED OR DETAILED, INSTALL ALL CONDUCTORS IN CONDUIT. THIS INCLUDES FIRE ALARM, SOUND
AND PAGING, AND DATA CABLES.
5. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ACCEPTED EDITION OF THE NATIONAL ELECTRICAL
CODE AND ALL STATE AND LOCAL CODES.
6. COORDINATE THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT AND CONNECTIONS WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
7. "BACK TO BACK" OR THROUGH THE WALL BOXES SHALL NOT BE USED.
8. RECEPTACLES INDICATED AS GROUND FAULT CIRCUIT INTERRUPTER TYPE MAY BE EITHER GFI RECEPTACLES OR
SPECIFICATION GRADE DUPLEX RECEPTACLES CONNECTED TO A CIRCUIT PROTECTED BY A GFI CIRCUIT BREAKER.
9. PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN EVERY POWER AND LIGHTING CONDUIT, ONE GROUNDING CONDUCTOR
FOR EACH CIRCUIT INCLUDING LIGHTING FIXTURE WHIPS (IF INSTALLED). ALL 120V CIRCUITS SHALL CONSIST OF AN UNGROUNDED CONDUCTOR, AN INSULATED NEUTRAL AND A GROUNDING CONDUCTOR. THERE SHALL BE NO SHARING OF
NEUTRALS.
10. ALL LIGHTING AND POWER CONDUCTORS SHALL BE 12 AWG MINIMUM.
11. MINIMUM CONDUIT SIZE SHALL BE 3/4" INTERNAL DIAMETER.
12. ARMORED CABLE TYPE AC or "BX" AND METAL CLAD TYPE MC CABLE SHALL NOT BE USED ON THIS PROJECT.
13. CONTRACTOR SHALL TRANSITION FROM PVC CONDUIT TO GALVANIZED RIGID METALLIC CONDUIT (GRC) WHEN TURNING UP
FROM BELOW A CONCRETE SLAB OR FROM BELOW GRADE TO ABOVE GRADE, WEATHER INDOORS OR OUTDOORS, BY INSTALLING A GRC NINETY DEGREE ELBOW AND THEN CONTINUING ABOVE SLAB OR GRADE UTILIZING GALVANIZED RIGID METAL CONDUIT. THIS APPLIES TO ALL RACEWAYS FOR ALL SYSTEMS INCLUDING DATA, UTILITY POWER AND/OR
EMERGENCY POWER, LIGHTING, & COMMUNICATIONS SYSTEMS.
14. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE PRIOR TO BIDDING TO VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS.
15. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR FURNISHING HIS SUBCONTRACTORS AND SUPPLIERS ALL THE NECESSARY CONTRACT DOCUMENTS TO ENSURE THEY INCLUDE ALL ITEMS IN THEIR BID THAT ARE WITHIN THEIR
DISCIPLINE.
16. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK REQUIRED AND PERFORMED TO CARRY OUT THE INTENT OF
THIS PROJECT; INCLUDING THAT WORK REQUIRED AND PERFORMED BY THE SUBCONTRACTORS.
17. THE GENERAL CONTRACTOR SHALL HAVE A RESPONSIBLE REPRESENTATIVE FROM THEIR COMPANY ON SITE AT ALL TIMES DURING HIS COMPANY'S WORK, OR THE WORK OF ONE OF THE SUBCONTRACTORS. THIS REPRESENTATIVE SHALL HAVE ON SITE, HIS OWN COPY OF THE CONTRACT SPECIFICATIONS, DRAWINGS AND DMVA APPROVED SHOP DRAWINGS.
18. DISCREPANCIES FOUND BETWEEN THE SPECIFICATIONS AND THE DRAWINGS SHALL BE SUBMITTED TO DMVA IN THE FORM
OF AN RFI FOR CLARIFICATION PRIOR TO ANY WORK INVOLVING THIS DISCREPANCY.
WILLIAMS INDOOR
PTS-24-L49-835-RA-DIM-UNV
WILLIAMS INDOOR
96-4-L62-840-HIAFR-(L55)-DIM-UNV
120V OPERATION
B
BE
1,2
1,2,3
120V OPERATION, 4000K COLOR TEMP.WILLIAMS INDOOR
PTS-24-L38-835-RA-DIM-UNV
120V OPERATION, 4000K COLOR TEMP.
SURFACE MOUNT TO CEILING
SURFACE MOUNT TO CEILINGWILLIAMS INDOOR
PTS-24-L38-835-RA-DIM-UNVLED 2'x4' SURFACE MOUNT WITH BATTERY BACKUP
LED 2'x4' SURFACE MOUNT
LED EXTERIOR WALL-MOUNT FIXTURE WITH BATTERY
BACKUP
1,2
1,2,3
120V OPERATION, 3000K COLOR TEMP.
120V OPERATION, 3000K COLOR TEMP.
SURFACE MOUNT TO CEILING
SURFACE MOUNT TO CEILING
WILLIAMS INDOOR
EXIT-R-EM-WHT SURFACE MOUNT TO WALL
BEGHELLIE
MUR-EM-DB-CL-PIR
J 1,2
1,2,3
120V OPERATION, 4000K COLOR TEMP.
120V OPERATION, 4000K COLOR TEMP.
SURFACE MOUNT TO CEILING
SURFACE MOUNT TO CEILINGJE
CE LED INDUSTRIAL STRIP FIXTURE W/ BATTERY BACKUP
WILLIAMS INDOOR
75R-4-L85-840-DIM-UNV 120V OPERATIONCHAIN-HANG 8'-0" AFF 1,2
LED CLOSET LIGHT W/ BUILT IN PIR MOTION SENSOR
LED ROUND LENS STRIP W/ BATTERY BACKUP
WILLIAMS INDOOR
76R-4-L85-840-DIM-UNV
WILLIAMS INDOOR
76R-4-L85-840-DIM-UNV
WILLIAMS INDOOR
PTS-14-L45-835-RA-DIM-UNV
WILLIAMS INDOOR
PTS-14-L45-835-RA-DIM-UNVLED 1'x4' SURFACE MOUNT WITH BATTERY BACKUP
LED 1'x4' SURFACE MOUNT
LIGHTING PLAN, SCHEDULES, AND DETAILS
NOTESTECHNOLOGYMANUFACTURER & CAT. NO.MARK MOUNTING LOCATION
CEILING MOUNT
OCCUPANCY SENSOR SCHEDULE
1, 2
DESCRIPTION
NEW OCCUPANCY
SENSOR DUAL TECHNOLOGYLEGRAND WATTSTOPPER
#LMDC-100-U
OC1
CEILING MOUNT 1, 2, & 3NEW OCCUPANCY
SENSOR DUAL TECHNOLOGYLEGRAND WATTSTOPPER
#DT-300-U
OC2
WATTS
3120V OPERATION, RED LETTERS 1,2,3
AutoCAD SHX Text 105N
AutoCAD SHX Text
AutoCAD SHX Text 103S
AutoCAD SHX Text 101S
AutoCAD SHX Text 100N
AutoCAD SHX Text 101N
AutoCAD SHX Text 103N
AutoCAD SHX Text 100N
AutoCAD SHX Text
105NA
AutoCAD SHX Text 102N
AutoCAD SHX Text 100S
AutoCAD SHX Text 104N
AutoCAD SHX Text 102S
AutoCAD SHX Text 104S
AutoCAD SHX Text 105S
AutoCAD SHX Text
105SA
AutoCAD SHX Text 106N
AutoCAD SHX Text 106S
AutoCAD SHX Text 100S
AutoCAD SHX Text R
AutoCAD SHX Text B
AutoCAD SHX Text W
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
BRIGADE ROAD
BASKETBALL
COURT
Q (5
Q (5
Q (4
Q (4
Q (5
Q (5
Q (5
M A
M A
M A
M A
7t h
S
TR
EE
T
S O
U
TH
526M528M53
M A53
M
A
3 3
BRIGADE ROAD
BASKETBALL
COURT
Q (5
Q (5
Q (4
Q (4
Q (5
Q (5
Q (5
M A
M A
M A
M A
7t h
S
TR
EE
T
S O
U
TH
526A
526M528M53
M A53
M
A
TWO EXISTING 4" UNDERGROUND
CONDUITS WITH EXISTING CABLESCC2
PB2
UTILITIES
989-344-6184
72 HOURS
(3 WORKING DAYS)
CALL Mr. Halcomb
BEFORE YOU DIGC.G.
MICHAEL HALCOMB
CAMP GRAYLING ENGINEERING
KAB'17
KNOW WHAT'S BELOW.
CALL BEFORE YOU DIG.
NOTE:
· SEE SHEET C-1 FOR SITE UTILITIES.
PROPOSED ELECTRICAL SITE POWER PLANE KEY NOTES X :
1. PROVIDE AND INSTALL NEW 3-POLE CIRCUIT BREAKER(S) IN THE EXISTING EXTERIOR SWICHBOARD P-538 FOR BUILDING 536Q (AND
534Q IF INCLUDED IN THIS PROJECT). UPGRADE MAIN BREAKER FROM 80% RATED TO 100% RATED ((MAIN CIRCUIT BREAKER BREAKER UPGRADE TO BE PERFORMED EVEN IF DEDUCT ALTERNATE NO. 1 IS ACCEPTED, DO NOT INCLUDE IN DEDUCT ALT. NO. 1 SCOPE.)
REFER TO SHEET E6 FOR CIRCUIT BREAKER SIZES.
2. PROVIDE AND INSTALL A NEW UNDERGROUND BUILDING ELECTRICAL FEEDER FROM SWICHBOARD P-538 TO BUILDING 536Q (AND 534Q
IF INCLUDED IN THIS PROJECT). REFER TO SHEET E6 FOR CONDUCTOR SIZE AND COUNT.
3. EXISTING UNDERGROUND FEEDERS TO EACH BUILDING SHOWN. CONTRACTOR SHALL DISCONNECT BOTH ENDS OF THE FEEDER TO BUILDING 536Q (AND 534Q IF INCLUDED IN THIS PROJECT), REMOVE FROM THE SWITCHBOARD P-538 AND EACH BUILDING, CUT 5 FEET
AWAY FROM THE SWITCHBOARD OR BUILDING AND ABANDON IN PLACE.
4. EXISTING UNDERGROUND FEEDER FROM SWITCHBOARD P-538 TO THIS BUILDING TO REMAIN.
HAND HOLE SCHEDULE
MARK
HH-A
DESCRIPTION BOX MANUFACTURER & CAT. NO. REMARKS NOTES
HAND HOLE SCHEDULE NOTES:
1. CONTRACTOR MAY SUBSTITUTE HAND HOLES BY OTHER MANUFACTURERS IF EQUAL IN ALL RESPECTS. SUBMIT SHOP DRAWING FOR ALL SUBSTITUTIONS.
PRECAST POLYMER CONCRETE ENCLOSURE QUAZITE #PG1730BA18 COVER SHALL HAVE "COMMUNICATIONS" LOGO 1
COVER MANUFACTURER & CAT. NO.
QUAZITE #PG1730HH00-12
ANSI TIER: 22 ANSI TIER: 22NOMINAL INTERIOR DIMENSIONS: 17"x30" BOX SHALL HAVE STRAIGHT SIDES HH-B PRECAST POLYMER CONCRETE ENCLOSURE QUAZITE #PC0608BA06 COVER SHALL HAVE "ELECTRIC" LOGO 1QUAZITE #PC0608HA00-17
ANSI TIER: 15 ANSI TIER: 15NOMINAL INTERIOR DIMENSIONS: 6"x8" BOX SHALL HAVE STRAIGHT SIDES
PROPOSED ELECTRICAL SITE POWER PLAN
SCALE 1" = 50'-0"
PROPOSED COMMUNICATIONS SITE PLAN
SCALE 1" = 50'-0"
PROPOSED COMMUNICATION SITE PLAN KEY NOTES X :
1. LOCATIONS OF THE EXISTING COMMUNICATIONS HAND HOLES AND JUNCTION BOXES ARE APPROXIMATE. CONTRACTOR SHALL VISIT THE
SITE AND FIELD VERIFY.
2. INSTALL (2) 2" CONDUITS UNDERGROUND FROM THE NEW HANDHOLE HH-A, TO MECHANICAL ROOM 107, TO A POINT UNDER THE NEW
COMMUNICATIONS RACK BACKBOARD AND NINETY-UP TO A POINT 3" ABOVE THE FINISH FLOOR LEVEL. INSTALL A METALLIC BUSHING
WITH INSULATED THROAT.
3. INSTALL NEW HH-A HANDHOLE FLUSH WITH GROUND. PULL EXISTING COPPER AND NEW FIBER CABLE THROUGH THIS HANDHOLE; NEW HANDHOLE TO BE PRECAST POLYMER CONCRETE ENCLOSURE WITH NOMINAL INTERIOR DIMENSIONS OF 17"X30". REFER TO THE "HAND
HOLE SCHEDULE", THIS SHEET. COIL-UP ANY EXTRA FIBER CABLE WITHIN THIS HANDHOLE.
4. PROVIDE AND INSTALL A NEW 12-STRAND FIBER CABLE; TYPE AS REQUIRED IN SPECIFICATION SECTION 270500. TERMINATE ALL 12 FIBERS IN BUILDING 536Q (AND 534Q IF PART OF THE CONTRACT). DIRECT BURY FIBER LINE FROM THE PULL BOX IDENTIFIED IN THE DRAWING ABOVE. ROUTE FIBER THROUGH THE NEW HH-A HAND HOLE ADJACENT TO EACH BUILDING AND TERMINATE THE FIBER IN THE FIBER EQUIPMENT INSIDE THE BUILDING. COORDINATE FIBER RUN LOCATIONS WITH CAMP GRAYLING TELECOMM/ENGINEERING
DEPARTMENT.
5. REINSTALL THE EXISTING UNDERGROUND TELEPHONE CABLE AND COMMSCOPE BEP ENCLOSURE THROUGH THE NEW HH-A HANDHOLE
AND INTO THE BUILDING WITHIN ONE OF THE NEW 2" CONDUITS.
6. APPROXIMATE ROUTE OF EXISTING UNDERGROUND FIBER OPTIC CABLE. CONTRACTOR SHALL COORDINATE THE INSTALLATION OF THE NEW CABLE RUNS WITH THE EXISTING. CONTACT BASE TELECOMM/ENGINEERING DEPARTMENTS FOR LOCATING.
7. RESTORE ALL DISTURBED AREAS PER SPECIFICATIONS.
8. COORDINATE WITH THE OTHER SITE PLANS; C1, C2 & C3.
9. JACK AND BORE NEW CABLES UNDER ALL CONCRETE WALKWAYS AND STAIRWAYS.
HH#
COMMUNICATIONS SYMBOL LEGEND
UNDERGROUND DUCT RUN
NEW OR EXISTING HAND HOLE
DESCRIPTIONSYMBOL
PB# EXISTING PULL BOX
CC# EXISTING CROSS CONNECT PEDESTAL
UNDERGROUND DIRECT BURY FIBER RUN
ELECTRICAL SYMBOL LEGEND
NEW POWER HAND HOLE, REFER TO NOTE
DESCRIPTIONSYMBOL
NEW UNDERGROUND POWER CIRCUIT
EXISTING EXTERIOR DISTRIBUTION PANEL
TRANSFORMER
EXISTING MEDIMUM VOLTAGE PADMOUNT
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
E-
JU
L
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND
BUILDING 534Q UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, SCHEDULES SHOWN ARE FOR 1
EACH BUILDING; CONTRACTOR SHALL BE RESPONSIBLE FOR
THE QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS
536Q AND 534Q ARE REMODELED.
ALL DETAILS WITHIN ARE FOR BOTH BUILDING 536Q AND BUILDING 534Q
UNLESS OTHERWISE NOTED. BASE BID INCORPORATES BOTH BUILDINGS
536Q & 534Q. CONTRACTOR SHALL BE RESPONSIBLE FOR THE
QUANTITIES NEEDED AND REQUIRED IF BOTH BUILDINGS 536Q AND 534Q
ARE REMODELED. IF PRICING IS TOO HIGH, BUILDING 534Q WILL BE
DROPPED FROM THE CONTRACT (DEDUCTIVE ALTERNATE) SO BIDDING
CONTRACTORs NEED TO DO THEIR TAKE-OFFs WITH THIS IN MIND.
NO SCALE
FINISHED GRADE
INSTALL HANDHOLES WITH HEAVY DUTY RATING AS
SPECIFIED. PROVIDE WITH STAINLESS STEEL BOLTS
AND A "COMMUNICATIONS" OR "ELECTRIC" LOGO IN A
HEAVY DUTY COVER
PROVIDE HAND HOLES
WITH OPEN BOTTOMSOR CRUSHED STONE
6" TO 8" OF GRAVEL
30°
HAND HOLE INSTALLATION DETAIL
GRAVEL BASE TO
EXTEND 4" PAST
THE SIDE OF THE
HAND HOLE, ON
ALL SIDES.
HAND HOLE INSTALLATION NOTES:
1. REFER TO SHEET E4 FOR HAND HOLE LOCATIONS.
2. REFER TO THE HAND HOLE SCHEDULE ON SHEET E4 FOR SIZE AND MANUFACTURER
INFORMATION.
ELECTRICAL SITE PLANS, DETAIL, AND SCHEDULES
HH-BHH-B
HH-A HH-A
AutoCAD SHX Text 115'
AutoCAD SHX Text 42'
AutoCAD SHX Text 20'
AutoCAD SHX Text 20'
AutoCAD SHX Text 57'
AutoCAD SHX Text 79'
AutoCAD SHX Text 32'
AutoCAD SHX Text 20'
AutoCAD SHX Text 67'
AutoCAD SHX Text 49'
AutoCAD SHX Text
SWALE
AutoCAD SHX Text
T-538 EXISTING PADMOUNT TRANSFORMER 500KVA 3 PHASE 208/120
AutoCAD SHX Text 87'
AutoCAD SHX Text
T-540 SN05A132074 500KVA 3 PHASE 208/120
AutoCAD SHX Text 52'
AutoCAD SHX Text
EXISTING SWITCHBOARD P-538
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
TUEBOR
AutoCAD SHX Text U
AutoCAD SHX Text S
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text
KAB
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text U
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text
PRELIMINARY
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
FINAL RECORD
AutoCAD SHX Text
DATE
AutoCAD SHX Text
ISSUED FOR
AutoCAD SHX Text
INDEX CODE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
IDENTIFICATION NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
AutoCAD SHX Text
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
AutoCAD SHX Text
ADAM LACH RA, DIRECTOR
AutoCAD SHX Text
JDJ
AutoCAD SHX Text
AJP
AutoCAD SHX Text
KAB
AutoCAD SHX Text
KAB
AutoCAD SHX Text
BURIAL DEPTHS BELOW GRADE*
AutoCAD SHX Text *FOR ALL CAMP ELECTRICAL & COMMUNICATIONS SYSTEMS, THESE MEASUREMENTS ARE BELOW FINISHED GRADE. *TO BE USED FOR NEW INSTALLATIONS ONLY, VERIFY ALL EXISTING DEPTHS AND LOCATIONS
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text 40"
AutoCAD SHX Text 36"
AutoCAD SHX Text
TELEPHONE
AutoCAD SHX Text 30"
AutoCAD SHX Text
CATV
AutoCAD SHX Text 30"
AutoCAD SHX Text
FIBER OPTIC
AutoCAD SHX Text 30"
AutoCAD SHX Text
PRIMARY
AutoCAD SHX Text
ELECTRICAL
SECONDARY
BUILDING
CENTERLINE
180'-0"
S
S S
S S
F F
F
F
F
FF
F
F
F
S S S
S S
SF
NOTE 1
NOTE 1
F
NOTE 1
F
NOTE 1
F
NOTE 12, 14
S
D
S AHU-2
D
SAHU-1
AHU-2
FACP
MDP
H A
F S
F
F
SSS
SSS
SSS
SSS
S S
H H
F
MDP-21
S
S
FLOW AND TAMPER
SWITCHES, SEE
NOTE 13
FIRE SUPPRESSION
SYSTEM HORN &
STROBE, NOTE 13
'-4
C
C
C C
C
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
ST
AT
E O
F M
IC
H
IG
AN
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
B1
E-
AP
R
R
EN
O
VA
TE
B
U
IL
D
IN
G
Q
/5
Q C
AM
P
G R
AY
LI
N G
J O
IN
T
M
AN
EU
VE
R T
R
AI
N
IN
G C
EN
AY
LI
N G
, M
IC
H
IG
AN
PROPOSED FIRE ALARM PLAN NOTES:
1. MOUNT THE HORN/STROBE 12" BELOW THE CEILING AND THE MANUAL PULL STATION DIRECTLY BELOW THE HORN/STROBE UNIT AT 48" AFF TO THE PULL HANDLE.
2. PROVIDE AND INSTALL THREE (3) RATE OF RISE HEAT DETECTORS IN THE ATTIC SPACE, ONE IN EACH OF THE THREE FIRE RATED AREAS. PROVIDE THESE THREE HEAT
DETECTORS WITH A REMOTE ALARM INDICATING LED OUTPUT OPTION. REMOTE LEDS SHALL BE LOCATED IN AN ENCLOSURE NEXT TO THE FIRE ALARM CONTROL PANEL
IN ROOM 107.
3. PROVIDE AND INSTALL A REMOTE HEAT DETECTOR MONITORING UNIT WITH LEDS TO INDICATE WHEN THE ATTIC HEAT DETECTORS ARE IN ALARM.
4. COORDINATE CEILING MOUNTED FIRE ALARM DEVICES WITH LIGHTING FIXTURES AND HVAC DIFFUSER LOCATIONS.
5. ALL FIRE ALARM WIRING SHALL BE IN CONDUIT, 3/4" MINIMUM.
6. WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT FOR IN AND OUT CONNECTIONS .
7. POINT AND COMMON ANNUNCIATION SHALL NOT BE USED. NON-ADDRESSABLE CIRCUITS T-TAPPING IS NOT ALLOWED.
8. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURER'S SPECIFICATIONS.
9. WALL-MOUNTED STROBES SHALL HAVE THEIR BOTTOMS NOT LESS THAN 80" AFF AND NO GREATER THAN 96" AFF.
10. ALL JUNCTION BOXES IN THE ATTIC SHALL BE SECURED TO A TRUSS AND MOUNTED ABOVE THE INSULATION LINE.
11. ALL EXPOSED FIRE ALARM CONDUIT SHALL BE PAINTED TO MATCH THE WALLS/CEILINGS FINISH COLOR. EXPOSED CONDUIT IS ALLOWED ON THE CEILINGS. UTILIZE
COMPRESSION FITTINGS (COUPLINGS & CONNECTORS) FOR THESE RACEWAYS.
12.STACK FIRE ALARM CONTROL PANEL AND BATTERY CABINETS IF MULTIPLE CABINETS ARE REQUIRED. DO NOT PLACE SIDE-BY-SIDE.
13.FIRE SUPPRESSION EQUIPMENT. CONTRACTOR SHALL PROVIDE AND INSTALL THE CONNECTION OF FIRE SUPPRESSION EQUIPMENT TO THE FIRE ALARM CONTROL PANEL
CONSISTING OF THREE BUTTERFLY VALVE TAMPER SWITCHES, ONE AIR COMPRESSOR, TWO FLOW SWITCHES, ONE EXTERIOR MOUNTED HORN & STROBE UNIT, AND ONE
ELECTRIC BELL.
14.ROUTE ONE CAT-6 CABLE IN 3/4" CONDUIT FROM THE DATA RACK TO THE NEW FIRE ALARM PANEL. TERMINATE BOTH ENDS SUCH THAT THE FIRE ALARM PANEL CAN BE
CONNECTED TO THE CAMP'S DATA NETWORK.
FIRE ALARM NOTES
1. PROVIDE AND INSTALL ALL FIRE ALARM DEVICES AS REQUIRED PER THE CURRENT EDITION IN
EFFECT OF NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
2. FINAL LAYOUT TO BE DESIGNED BY A LICENSED AND CERTIFIED FIRE ALARM SYSTEM PROFESSIONAL.
FIRE ALARM SHOP DRAWINGS MUST BE SUBMITTED BY THE CONTRACTOR TO…