This document appears to be a set of drawings and specifications for a 36-foot mirrored communications shelter that will be acquired through a federal solicitation. The key details are:

The Federal Aviation Administration (FAA) has a requirement for the procurement of pre-cast concrete shelters. The contractor shall provide all labor, materials, equipment, and other services necessary to perform the work described in the Scope of Work and other attachments. It is anticipated that a firm-fixed-price construction contract will be awarded. Proposals are due by 5:00 pm CST on September 2, 2024 and must be submitted to the Contract Specialist, Jason Fox, via email. The FAA reserves the right to communicate with offerors during the solicitation process and will not hold a public bid opening. The acquisition will be conducted under the FAA's Acquisition Management System rather than the Federal Acquisition Regulation.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:3

:1

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -g

.d w g

8 234567

H

G

F

E

D

C

A

B

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-G301

RCAG

STANDARD 36FT MIRROR

COVER SHEET

w a s d -d -r c a g -g

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 11/20/2023 FIELD REVISION

AW

36 FOOT SHELTER MIRRORED

COMMUNICATIONS ENGINEERING

NATIONAL DESIGN STANDARD

RCAG/RTR

A

T OF TRANSPO

R T A T

IO

N

M

E R

IC

A

OF

STATES

U N

IT

E D

D E P A R

TM

EN

AVIA

T

IO

N

LA

R

E

D E

F

TRAT

IO

N

SI

NI

M

D A

H V

A C

H V

A C

B

C

MPG

G F I

G F I

WORK

BENCH

(BY OTHERS)

BATTERIES

(BY OTHERS)

RF

JUNCTION

BOX

BOX

JUNCTION

RF

G F I

DC BUS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

G F I

PARTS

STORAGE

LOCKER

(BY OTHERS)

TELCO

GND

SUPP

GND

SPG

BENCH

GND

B

B

B

PWR

PNL A

MPG SPG MPG SPG

2 16

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

RADIO &

RACKS

(BY OTHERS)

SM

10PWR

PNL P

PWR

PNL A

MDP

PNL

MAIN

GND

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:2

:1

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -a

.d w g

8 234567

H

G

F

E

D

C

A

B

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

SCALE: 1/2" = 1'-0"

PLAN VIEW

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-A301

RCAG

STANDARD 36FT MIRROR

BUILDING LAYOUT

w a s d -d -r c a g -a

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

BETWEEN THE BUILDING AND THE FOUNDATION.

FOR THE SHELTER, INCLUDING DETAILS FOR THE CONNECTIONS

SHELTER MANUFACTURER IS TO PROVIDE FOUNDATION PLANS

OR BY CERTIFICATION OF AUTHORITY HAVING JURISDICTION.

BY STRUCTURAL PLANS AND CALCULATIONS

SHALL BE DEMONSTRATED TO MEET THE CODE REQUIREMENTS

THE STRUCTURAL DESIGN OF THE PRE-FABRICATED SHELTER

TO BE CONSTRUCTED BY THE CONSTRUCTION CONTRACTOR.

REQUIREMENTS. FOUNDATION AND UTILITY CONNECTIONS ARE

TO THE FINAL LOCATION WITH MINIMAL FABRICATION

SHELTER IS TO BE PRE-FABRICATED OFFSITE AND DELIVERED

FOR GROUNDING DETAIL

COVER RUBBER BASE. REFERENCE WASD-D-RCAG-E208 DETAIL 4

BUILDING FLOOR IS ESD APPLIED COATED CONCRETE WITH A 4"

AGGREGATE WITH TINTED SEALER AND PAINTED.

THE BUILDING EXTERIOR WALLS SHALL BE EXPOSED

WHERE THE BUILDING IS TO BE LOCATED.

STANDARD OF THE STATE AND LOCAL MUNICIPALITIES.

PREFABRICATED BUILDING SHALL MEET THE MINIMUM

ARE ALLOWED WITH PRIOR APPROVAL.

THE DIMENSIONS ARE APPROXIMATE. SLIGHT VARIANCES

PRECAST CONCRETE PREFABRICATED BUILDING. NOTE THAT

HVAC CONTROLLER

6"X6"X4" STAINLESS STEEL, NEMA 4X ENCLOSURE.

V4 ERMS PANEL (INSTALLED BY OTHERS).

BACK BOARD.

8'x4'x3/4" 1 HR FIRE RATED PLYWOOD AS TELEPHONE

4" PVC SLEEVE FOR 500 MCM GROUND CABLES.

ELECTRICAL BOX WITH COVER IN BUILDING INTERIOR.

BUSHINGS INTERIOR AND EXTERIOR. INSTALL 2" X 4" HANDY

1" RIGID GALVANIZED STEEL CONDUIT SLEEVE WITH GROUND

LOCATE RECEPTACLES 42" ABOVE FINISHED FLOOR.

200A, 30 CBs WITH TVSS & PNL A 100A, 30 CBs WITH TVSS.

POWER PANELS, PNL MDP 200A, 30 CBs WITH TVSS, PNL P

EXTERIOR LIGHT - PHOTOCELL CONTROLLED.

EMERGENCY EXIT SIGN WITH DUAL FLOOD LIGHTS.

BEST LOCK 7 TUMBLER (STAINLESS STEEL FINISH)

3'-6"x7'-0" DOOR. FIRE RATE FOR 1 HOURS WITH GOVERNMENT

4" RIGID STEEL WATER TIGHT SLEEVE WITH GND BUSHING.

36"X48"X12" MARINE GRADE ALUMINUM, NEMA 4X ENCLOSURE

HVAC DISCONNECT.

DEDICATED TELCO RECEPTACLES. TO BE INSTALLED BY OTHERS.

3 PER DOOR.

DOOR HINGES WITH NRP PINS WITH STAINLESS STEEL FINISH.

POWER DISTRIBUTION PANELS.

PENETRATION FOR 2 1/2" RGS TO WIREWAY ABOVE

NOTES:

H V

A C

H V

A C

B

C

MPG

WORK

BENCH

(BY OTHERS)

BATTERIES

(BY OTHERS)

RF

JUNCTION

BOX

BOX

JUNCTION

RF

PARTS

STORAGE

LOCKER

(BY OTHERS)

TELCO

GND

SPG

B

B

B

SPG MPG SPG

SM

1 TYP.

DC BUS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

BENCH

GND

MPG GND

SUPP

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:2

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -a

.d w g

8 234567

H

G

F

E

D

C

A

B

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-A302

RCAG

STANDARD 36FT MIRROR

REFLECTED CEILING PLAN

w a s d -d -r c a g -a

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

SCHEDULE.

4' LIGHT FIXTURE. SEE WASD-D-RCAG-E307, LIGHTING FIXTURE 1

NOTE:

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:2

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -a

.d w g

8 234567

H

G

F

E

D

C

A

B

BOX

JUNCTION

RF

(TYP)

(TYP)

FF = XXXX

3" SLOPE3" SLOPE

BOX

JUNCTION

RF

3" SLOPE 3" SLOPE

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

8 3

SCALE: 3/8" = 1'-0"

BACK VIEW

A303

A

SCALE: 3/8" = 1'-0"

RIGHT VIEW

A303

B

SCALE: 3/8" = 1'-0"

FRONT VIEW

A303

C

SCALE: 3/8" = 1'-0"

LEFT VIEW

A303

D

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-A303

RCAG

STANDARD 36FT MIRROR

EXTERIOR ELEVATIONS

w a s d -d -r c a g -a

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

2' 0 2' 6'

SCALE: 3/8" = 1'-0"

4'

NOTES:

EQUIVALENT.

ENCLOSURE. STEELINE ENCLOSURE M-S483612NFAL OR APPROVED

RF JUNCTION BOX 36"X48"X12" MARINE GRADE ALUMINUM NEMA 4X

COVER.

GFCI RECEPTACLE IN WEATHER PROOF ENCLOSURE WITH IN-USE

GROUND CABLE. PENETRATION SHOULD BE 4" PVC SLEEVE.

PENETRATION FOR MAIN AND SUPPLEMENTAL GROUND PLATES

2 1/2" RIGID STEEL PENETRATION SLEEVE.

STANDARDS.

4'X4'X6" ENTRY PAD. SHOULD COMPLY WITH OSHA AND ANSI

GROUND CABLE PENETRATION. 1 1/2" PVC SLEEVE.

BUILDING FOUNDATION, SITE SPECIFIC.

DISCONNECT SWITCH FOR HVAC UNITS.

3 TON EUBANK HEAT PUMP HVAC OR EQUIVALENT. PROVIDE EXTERNAL

BOX.

6"X6"X4" STAINLESS STEEL NEMA 4X. OBSTRUCTION LIGHT ELECTRICAL

TELECOMMUNICATIONS CABLE PENETRATION SLEEVE WITH J-BOX.

SCHEDULE.

EXTERIOR LIGHT FIXTURE SEE WASD-D-RCAG-E307, LIGHTING FIXTURE

MANUFACTURER.

PROVIDE AND INSTALL TIE-DOWN PLATES AS REQUIRED BY BUILDING

CANOPY PROVIDED AND INSTALLED BY BUILDING MANUFACTURER.

PRECAST PRE-FABRICATED BUILDING.1

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:2

:4

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -a

.d w g

8 234567

H

G

F

E

D

C

A

B

SCALE: 3/8" = 1'-0"

BACK WALL

A304

A

SCALE: 3/8" = 1'-0"

RIGHT VIEW

A304

B

SCALE: 3/8" = 1'-0"

FRONT WALL

A304

C

SCALE: 3/8" = 1'-0"

LEFT VIEW

A304

D

12 12

EXIT

WALLBOARD

TELCO

8'x4'

ERMS

TRAY

STBY

PNL

PWR

TVSS

MAIN

PNL

PWR

TVSSTVSS

MDP

PNL

PWR

TRAY

17x10

OPENING

RETURN AIR

17x10

OPENING

RETURN AIR

WIREWAY, NEMA 1

6X6" HINGED

21 20

3 4

(TYP)

FF= XXX

QUAD BOX RECEPTACLE.

LARGE ENOUGH FOR CONDUIT.

PENETRATION FOR MDP ELECTRICAL CONDUIT 2 1/2" RGSC. SLEEVE TO BE

INTERIOR.

OBSTRUCTION LIGHT PENETRATION WITH 2" X 4" HANDY ELECTRICAL BOX

500 MCM GROUND CONDUCTORS.

PENETRATION FOR MAIN AND SUPPLEMENTAL GROUND 4" PVC SLEEVE FOR

GROUND PLATE.

ELECTRICAL RECEPTACLE. 120V DUPLEX 20 AMP RECEPTACLE.

4 INCHES FROM FINISHED FLOOR.

NO HIGHER THAN 4 FEET HIGH OFF FINISHED FLOOR AND NO LOWER THAN

FIRE EXTINGUISHER CLASS ABC 10 LB WITH BRACKET HOLDER MOUNTED

FTI OUTLET RECEPTACLE. TO BE INSTALLED BY OTHERS.

1 HR FIRE RATED PLYWOOD.

SLEEVE TO BE LARGE ENOUGH FOR CONDUIT.

PENETRATION FOR FUTURE 4" RGSC & LB FOR TELECOMMUNICATIONS.

BATTERIES.

4" RIGID STEEL WATER TIGHT SLEEVE WITH GND BUSHING.

SEE SPECIFICATION SECTION XXXX.

FOR INTERIOR FLOOR, WALLS AND CEILING MATERIALS AND FINISHES.

SEE WASD-D-RCAG-E307, LIGHTING FIXTURE SCHEDULE.

EMERGENCY EXIT SIGN WITH DUAL FLOOD LIGHTS.

DOOR CLOSER/HOLDER.

DOCUMENT HOLDER.

HVAC CONTROLLER.

DESK OR WORKBENCH.

PARTS STORAGE LOCKER.

TELCO GROUND PLATE.

RCAG-E311 DETAIL A.

12"x3" GALVANIZED STEEL CABLE TRAY. FOR INSTALLATION SEE WASD-D-

ERMS (INSTALLED BY OTHERS)

SEE MECHANICAL DRAWING FOR A/C EQUIPMENT SCHEDULE.

PRECAST PREFABRICATED BUILDING.1

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-A304

RCAG

STANDARD 36FT MIRROR

INTERIOR ELEVATIONS

w a s d -d -r c a g -a

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

2' 0 2' 6'

SCALE: 3/8" = 1'-0"

4'

NOTE:

A005

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:4

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -a

.d w g

8 234567

H

G

F

E

D

C

A

0"

1 3/16"

2 3/8"

3 1/2"

4 1/4"

UP 90°

BEND

5 1/4"

(6")

R.250"

21/32" THRUØ4 X

7/32" THRUØ4 X

7/16"Ø4 X

/3

/3

/4

/4

/1

/4

/4

/2

/4

/1

/1

/4

/4

/3

(TYP)

(TYP)

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-A305

RCAG

RCAG FACILITY

DEMARC ENCLOSURES AT FACILITY

w a s d -d -r c a g -a

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

1' 0 1'

SCALE: 1 1/2" = 1'-0"

3"6"9"

1 5/8" UNISTRUT CHANNEL.

4" RGSC SLEEVE WITH GROUND BUSHINGS ON BOTH SIDES.

OTHERS.

POLYPHASER "IS-B50LN-C0" OR EQUAL (6 PLACES). PROVIDED BY

ENCLOSURE. USE #6 AWG GREEN INSULATED GROUND CONDUCTOR.

GROUND DEMARC ENCLOSURE DOOR TO THE BODY OF DEMARC

BACK PANEL TO BE PROVIDED WITH ENCLOSURE.

ARRESTOR GND PLATE AND THE RF JUNCTION BOX. BACK PANEL

INSTALL INSULATOR TO ENSURE ELECTRICAL ISOLATION BETWEEN THE

(ALT P/N 7000-3832-PF-10T TIN COATED OR EQUIVALENT.

INSTALL (2) 6" x 12 3/4" x 1/4" TIN COATED COPPER MOUNTING PLATE.

LOCKABLE.

APPROVED EQUIVALENT WITH BACKING PANEL. THE BOX IS TO BE PAD

RF JUNCTION BOX SHALL BE A LOCKABLE STEELINE M-S483612NFAL OR

NOTES:

ELEVATION

SCALE: 1 1/2" = 1'-0"A305

1 SECTION

SCALE: 1 1/2" = 1'-0"A305

NOT TO SCALE

BULKHEAD PLATE DETAIL

FORMED VIEWS

FLAT PATTERN

5. PROVIDE WITH COASTAL ENVIRONMENTAL PACKAGE FOR LOCATIONS WHERE UNITS MAY BE EXPOSED TO SALT WATER OR OTHER CORROSIVE ENVIRONMENTAL CONDITIONS

4. PROVIDE WITH ECONOMIZER OPTION

3. EER BASED ON 2ND STAGE COMPRESSOR OPERATION AT 95 DEG F D.B. OUTDOOR AIR AND 80 DEG F D.B. / 67 DEG F W.B. RETURN AIR

2. HEATING CAPACITY BASED ON OUTDOOR AIR TEMPERATURE OF 10 DEG F D.B.

1. COOLING CAPACITY BASED ON OUTDOOR AIR TEMPERATURE OF 95 DEG F D.B.

REMARKS:

1, 2, 3, 4, 5EUBANK 7AA2048H659218 X 24 X 1MERV 86038.5601208/23021SCROLL11.0R-410A5.310503/4121.10.256780175018,70036,00047,000

MOUNTED

WALL

RCAGOUTSIDEAC-2

1, 2, 3, 4, 5EUBANK 7AA2048H659218 X 24 X 1MERV 86038.5601208/23021SCROLL11.0R-410A5.310503/4121.10.256780175018,70036,00047,000

MOUNTED

WALL

RCAGOUTSIDEAC-1

QTYSIZE (INCH) (W X H X D)TYPEMOCPMCAHZPHVSTAGEQTYTYPEFLARPMHPQTYRLAW.B.D.B.SENSIBLETOTAL

NOTES

NUMBER OR EQUAL

MANUFACTURER, AND MODEL

BASIS OF DESIGN,

(LBS)

WEIGHT

NET

FILTERSELECTRICAL DATACOMPRESSOR

EERREFRIGERANT

EVAP. FAN MOTOR

MOTOR (EA)

CONDENSER

S.P.

EXT.

AIR

ENTERING

CFM

(BTUH)

CAPACITY

HEATING

(BTUH)

COOLING CAPACITY

TYPESERVESLOCATIONMARK

HEAT PUMP SCHEDULE

H V

A C

H V

A C

(BY OTHERS)

BENCH

WORK

(BY OTHERS)

BATTERIES

BOX

JUNCTION

RF

BOX

JUNCTION

RF

(BY OTHERS)

DC BUS

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

LOCKER

STORAGE

PARTS

GND

TELCO

GND

SUPP

SPG

GND

BENCH

MPG SPG MPG SPG

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

(BY OTHERS)

RACKS

RADIO &

SM

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

D

A T

E

T

IM

E

N

A M

E

DATE

APPROVED

F

IL

E S

8 234567

H

G

F

E

D

C

A

B

LAG UNIT WILL BE CALLED TO ENERGIZE.

OF 74°F (ADJUSTABLE). IF IT CANNOT MAINTAIN TEMPERATURE, THE

THE LEAD UNIT SHALL MAINTAIN SPACE TEMPERATURE HEATING MODE:

LAG UNIT WILL BE CALLED TO ENERGIZE.

OF 80°F (ADJUSTABLE). IF IT CANNOT MAINTAIN TEMPERATURE, THE

THE LEAD UNIT SHALL MAINTAIN SPACE TEMPERATURE COOLING MODE:

TO MAINTAIN EQUAL RUN TIME.

AUTOMATICALLY SWITCH/ROTATE THE LEAD/LAG UNITS EVERY 7 DAYS

DIRTY FILTER INDICATOR ALARM LIGHT. THE CONTROLLER SHALL

THERMOSTAT CONTROLLER. UNIT WILL NOT BE DE-ENERGIZED FOR

UNITS ARE CONTROLLED BY THE COMMSTAT4 GENERAL OPERATION:

SEQUENCE OF OPERATION:

SERVICE.

MANUALLY ALTERNATE THE LEAD/LAG UNITS FOR TECHNICIAN

EVERY SEVEN DAYS. A LEAD SWAP BUTTON IS PROVIDED TO

SET TO AUTOMATICALLY SWITCH/ROTATE THE LEAD/LAG UNITS

COOL, POWER, AND LEAD UNIT. LEAD/LAG OPERATION WILL BE

BACKLIT LCD DISPLAY ALONG WITH LED'S THAT INDICATE HEAT,

DETERMINE SPACE TEMPERATURE. THE COMSTAT3 INCLUDES A

REMOTE TEMPERATURE SENSORS WILL BE AVERAGED TO

TELECOMMUNICATIONS SHELTER. READINGS FROM THREE

FOR CONTROLLING REDUNDANT AIR CONDITIONERS IN A

HVAC CONTROLLER. THE COMSTAT3 IS SPECIFICALLY DESIGNED

AC UNITS ARE CONTROLLED BY THE COMMSTAT3 TELECOM

KEY NOTES:

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

SCALE: 1/2" = 1'-0"

MECHANICAL PLAN

M301

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-M301

RCAG

STANDARD 36FT MIRROR

MECHANICAL PLAN, EQUIPMENT SCHEDULE,

AND SEQUENCE OF OPERATION

w a s d -d -r c a g -m

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 03/12/2024 FIELD REVISION

AW

NOTES:

UNITS PERFORM AT OUTDOOR AMBIENT TEMPERATURE OF 105°F.

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

ARE SLEEVED AND WATERTIGHT.

THE SUPPLY AND RETURN PENETRATIONS THROUGH THE WALL

AND OFF POSITIONS.

SWITCHES, NEMA 4X MINIMUM. SHALL BE LOCKABLE IN THE ON

PROVIDE AND INSTALL HEAVY DUTY NON-FUSED DISCONNECT

PROVIDE AND INSTALL COMMSTAT 4 THERMOSTAT CONTROLLER.

CYCLE CONTROL AND HARD START KIT.

PROVIDE AND INSTALL FACTORY COMPRESSOR ANTI SHORT

DIRTY FILTER INDICATOR.

PROVIDE AND INSTALL AIR GRILLE, RETURN AIR GRILLE, AND

UNITS OPERATE IN LEAD-LAG CONFIGURATION.1

NEUTRAL CONDUCTOR

HOT CONDUCTOR

NUMBERS

HOMERUN CALLOUT INDICATING PANEL AND CIRCUIT

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:3

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -e

.d w g

8 234567

H

G

F

E

D

C

A

B

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E301

RCAG

STANDARD 36FT MIRROR

GENERAL NOTES

ELECTRICAL ABBREVIATIONS & SYMBOL LEGEND

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

G

L

EES

G

J

J

T

MOTOR CONNECTION

PANELBOARD

EL1-17, 19, 21

3W +18" A.F.F. (SUBSCRIPTS SAME AS ABOVE)

DOUBLE DUPLEX RECEPTACLE OUTLET 20A, 125V, 2P,

IG - ISOLATED GROUND (ORANGE)

WP - WEATHER PROOF

GFI - GROUND FAULT INTERRUPTER

+18" A.F.F. SUBSCRIPT INDICATES:

DUPLEX RECEPTACLE OUTLET 20A, 125V, 2P, 3W

CONNECTION POINT TO EQUIPMENT

COMBINATION MOTOR STARTER, MAGNETIC FVNR, UNO

TRANSFORMER

JUNCTION BOX, WALL MOUNTED 4" X 4" X 2" UNO

JUNCTION BOX, CEILING MOUNTED

MANUAL TRANSFER SWITCH

SMOKE DETECTOR

GENERATOR

TRANSFORMER

GROUND, GROUNDING ELECTRODE

OVERLOAD

FUSE

INDICATED

CIRCUIT BREAKER, THERMAL MAGNETIC, SIZE

CONTACT - NORMALLY CLOSED

CONTACT - NORMALLY OPEN

INDICATED

DISCONNECT SWITCH, FUSE AND FRAME SIZES

HORIZONTAL RUN OF WIRING IN WIREWAY

EXOTHERMIC WELDING CONNECTION

EARTH ELECTRODE SYSTEM CONDUCTOR

LIGHTNING CONDUCTOR, EXPOSED

GROUND CONDUCTOR, EXPOSED

CONDUIT CONCEALED OR UNDERGROUND

CONDUIT EXPOSED

FLEXIBLE METAL CONDUIT

ALL CASES.

CONDUCTORS. PROVIDE GROUND CONDUCTOR IN

HATCHES (IF USED) INDICATE NUMBER OF

IN 3/4" CONDUIT, UNO BY NOTE OR HATCHE.

CIRCUITS SHALL HAVE 2#12 WIRES PLUS 1#12 GND

WHERE CONDUIT IDENTIFIERS ARE NOT USED,

GP

TJB

PC

b

CONTROLS/EQUIPMENT/CONDUIT IDENTIFIER

POWER/EQUIPMENT/CONDUIT IDENTIFIER

FIXTURE TYPE, SEE SCHEDULE DWG - E023

M - MOTOR RATED TOGGLE SWITCH

PL - PILOT LIGHT

K - KEY OPERATED

2P - TWO-POLE

3 - THREE-WAY

a,b,c, - LIGHTING GROUP

WP - WEATHER PROOF

SUBSCRIPT INDICATES:

SINGLE POLE SWITCH +42", SURFACE MOUNTED

WALL - MOUNTED FIXTURE

PC - PHOTO CELL

WALLPACK FLOODLIGHT SUBSCRIPT INDICATES:

EGRESS (SWITCH) 4 FT. INDUSTRIAL FIXTURE

4 FT. INDUSTRIAL FIXTURE SURFACE MOUNTED

TWINHEAD EMERGENCY BATTERY PACK

TERMINAL JUNCTION BOX

GROUND PLATE, MAIN/SUPPLEMENT

GROUND PLATE, MULTIPOINT/SINGLEPOINT

GROUND ROD ACCESS TEST WELL

AIR TERMINAL (LIGHTNING PROTECTION)

AFF ABOVE FINISHED FLOOR

A, AMP AMPERE

AA AIR COOLED

AC ALTERNATING CURRENT

AS AMPERE OF SWITCH

CB CIRCUIT BREAKER

CKT CIRCUIT

CT CURRENT TRANSFORMER

DC DIRECT CURRENT

DISC DISCONNECT

E/G ENGINE GENERATOR

(E) EXIST/EXISTING

EQUIP EQUIPMENT

FAA FEDERAL AVIATION ADMINISTRATION

GFE GOVERNMENT FURNISHED EQUIPMENT

GND GROUND

HZ HERTZ

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

KCMIL THOUSAND CIRCULAR MILS (SAME AS MCM)

MCM THOUSAND CIRCULAR MILS (SAME AS KCMIL)

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NTS NOT TO SCALE

PH PHASE

PNL PANELBOARD

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

SPD SURGE PROTECTIVE DEVICE

V VOLT, VOLTAGE

W WATT

XFMR TRANSFORMER

EES EARTH ELECTRODE SYSTEM

GEC GROUNDING ELECTRODE CONDUCTOR

1. ALL WORK SHALL BE PERFORMED BY THE LATEST REVISION OF NEPA 70

(NEC), FAA-STD-019F (LIGHTNING AND SURGE PROTECTION, GROUNDING,

BONDING, SHIELDING REQUIREMENTS FOR FACILITIES AND ELECTRONIC

EQUIPMENT), AND FAA-C-1217H (ELECTRICAL WORK, PREMISES WIRING),

FAA-C-1391 INSTALLATION, TERMINATION, SPLICING AND TRANSIENT/SURGE

PROTECTION OF UNDERGROUND ELECTRICAL DISTRIBUTION SYSTEMS

POWER CABLES.

2. TORQUE ALL ELECTRICAL HARDWARE I.A.W. ELECTRICAL POWER

DISTRIBUTION EQUIPMENT AND SYSTEMS AND EQUIPMENT

MANUFACTURER'S REQUIREMENTS. RECORD ALL TORQUE SETTINGS.

3. MEG-OHM TEST ALL CABLES INSTALLED AND PULLED IN, AND RECORD ALL

MEGGER READINGS.

4. CONDUIT ROUTING IS DIAGRAMMATIC. THE ELECTRICAL CONTRACTOR

SHALL BE RESPONSIBLE FOR ACTUAL ROUTING AND MOUNTING SUPPORTS.

5. ALL EXTERIOR TEMPORARY CABLES WHERE EXPOSED TO POSSIBLE DAMAGE

SHALL BE PROTECTED OR CAUTION TAPE TO BE USED TO PREVENT ACCESS.

6. ALL WIRING CONNECTIONS TO EQUIPMENT AND CABLE CONNECTORS SHALL

BE DONE IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.

7. ALL INSULATED CONDUCTORS SHALL BE PROPERLY AND PERMANENTLY

IDENTIFIED AND COLOR CODED AT EACH END. IN EACH PULL BOX, AND

EVERY 3 FEET WHERE CONDUCTOR IS VISIBLE.

8. LABEL ALL NEW CABLES AND WIRES AT TERMINATION POINTS BY LABELING

ONE TERMINATION POINT WITH THE LOCATION OF THE NEXT POINT AND

VICE VERSA, USING ADHESIVE TYPE SELF LAMINATING LABELS.

9. NAMEPLATES SHALL BE NON-FERROUS METAL OR RIGID PLASTIC STAMPED,

EMBOSSED OR ENGRAVED WITH 3/8-INCH MINIMUM HEIGHT CHARACTERS,

OR AS SPECIFIED BY FAA-ISSUED DRAWINGS. ENGRAVED NAMEPLATES SHALL

HAVE WHITE LETTERS ON BLACK FACE. NAMEPLATES SHALL BE SECURED TO

EQUIPMENT WITH A WEATHER-PROOF BONDING MATERIAL (GLUE),

DOUBLE-SIDED TAPE, OR MINIMUM OF TWO SCREWS.

10. THE CONTRACTOR IS NOT REQUIRED TO OBTAIN PERMITS, SINCE THIS IS

FAA OWNED PROPERTY. THE RE WILL BE RESPONSIBLE TO OBTAIN ALL FAA

WORK PERMITS.

11. CONDUITS BETWEEN THE TVSS, PANELBOARDS OF DISCONNECT SWITCH

SHALL HAVE DUCT SEAL INSTALLED.

12. TEST ALL UNDERGROUND EXOTHERMIC WELDS WITH A 4 TERMINAL

MILLI-OHM OF MICRO-OHM METER. RECORD TEST RESULTS.

13. ALL TEST REPORTS SHALL BE ON CONTRACTOR LETTERHEAD AND INCLUDE

DATE TESTED, MANUFACTURER SPECIFICATIONS, TEST RESULTS OR

TORQUE, MAKE AND MANUFACTURER OF TESTING EQUIPMENT AND

CALIBRATION DATE.

14. INSTALL & TEST STATICWORX GROUNDWORX ULTRA 2 PART

FLOOR COATING IN ACCORDANCE WITH MANUFACTURER

RECOMMENDATIONS. COATING SHALL BE DISSIPATIVE PER

FAA-STD-019F, CHANGES TEST IAW ANSI/ESD STM 7.1.

1. THE REQUIREMENTS LISTED BELOW DESCRIBE SAFETY METHODS.

PROCEDURES AND RULES REQUIRED. OSHA 2202 WHICH REFERENCE 29 CFR PART

1926 "SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION" SHALL FORM A

PART OF THE OVERALL SAFETY PLAN.

CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT HIS/HER

EMPLOYEES HAVE APPROPRIATE PERSONAL SAFETY EQUIPMENT AND

PROTECTIVE CLOTHING AND THAT APPROPRIATE EMERGENCY EQUIPMENT

(INCLUDING FIRST AID KIT & MULTI-CLASS RATED FIRE EXTINGUISHER) IS

ON HAND AND THROUGHOUT THE COURSE OF THE PROJECT. MATERIAL

SAFETY DATA SHEETS SHALL BE MADE AVAILABLE UPON REQUEST.

2. THE CONTRACTOR'S ACCESS ONTO THE SITE THRU GATE. THE PROJECT SITE MAY

BE USED FOR CONTRACTOR STAGING, CONTRACTOR MATERIAL STORAGE, ETC.

UPON COMPLETION OF THE STAGING AREA, THE CONTRACTOR SHALL RESTORE

STAGING AREA INCLUDING THE REPAIR OF EXISTING FACILITIES, EXCEPT FOR

PAVEMENT. REMOVAL OF TEMPORARY UTILITIES, RE-GRADE AND SEED THE SITE AS

NECESSARY TO THE SATISFACTION OF THE RE.

3. CONTRACTOR SHALL PARTICIPATE IN A SCHEDULED PRE-CONSTRUCTION MEETING

TO GO OVER CONSTRUCTION SCHEDULING, , SAFETY, ACCESS, STORAGE, AND

OTHER SPECIFIC REQUIREMENTS WITH THE CONTRACTING OFFICER

REPRESENTATIVE (COR), AIRPORT AUTHORITY, AND LOCAL FAA PERSONNEL. THE

FAA SAFETY & HEALTH CHECKLIST (FORM 3900-18) IS TO BE REVIEWED & SIGNED

BY CONTRACTOR AT THAT TIME.

4. THE CONTRACTOR'S EMPLOYEES ASSIGNED TO WORK ON THE PROJECT SHOULD

OBTAIN THE NECESSARY APPROVALS PRIOR TO THE PRE-CONSTRUCTION MEETING

AND SUBSEQUENT NOTICE TO PROCEED (NTP).

5. PRIOR TO BEGINNING ANY EXCAVATION OR TRENCHING, THE CONTRACTOR

SHALL COORDINATE WITH THE AIRPORT AUTHORITY, LOCAL FAA AIRWAY

FACILITIES, AND UTILITY COMPANY TO HAVE ALL THEIR SURROUNDING

UNDERGROUND CABLE, CONDUITS, AND UTILITIES LOCATED. A THIRD PARTY

UTILITY LOCATE COMPANY SHALL BE HIRED BY THE CONTRACTOR TO

IDENTIFY UNDERGROUND UTILITIES NOT IDENTIFIED BY THE ABOVE. THE

CONTRACTOR SHALL HAND DIG WITHIN 5' AROUND ALL CABLES, ETC IDENTIFIED.

6. ALL EXTERIOR TEMPORARY CABLES SHALL BE PROTECTED.

7. ALL SHUTDOWNS/CUTOVERS MUST BE COORDINATED IN ADVANCE WITH THE FAA

FOR APPROVAL. THE CONTRACTOR SHALL DEVELOP A CUTOVER PLAN FOR

APPROVAL BY THE FAA PRIOR TO INSTALLING TEMPORARY POWER.

8. ONLY FAA PERSONNEL WILL OPERATE SWITCHES AND CIRCUIT BREAKERS.

9. ANY WORK THAT WILL CAUSE A LOSS OF POWER TO THE FACILITY SHALL BE

COORDINATE WITH THE RE AND LOCAL FAA PERSONNEL.

10. COORDINATE WITH THE UTILITY COMPANY TO DE-ENERGIZE THE UTILITY XFMR.

11. THE CONTRACTOR SHALL PROVIDE SUBMITTALS ON CONTRACTOR FURNISHED

EQUIPMENT TO THE FAA PROJECT ENGINEER FOR REVIEW AND APPROVAL PRIOR TO

INSTALLATION.

12. THE FAA SHALL PROVIDE A SIGNED FAA WORK PERMIT TO THE CONTRACTOR PRIOR

TO THE PRE-CONSTRUCTION MEETING.

13. THE FAA SHALL PERFORM THE CONSTRUCTION ACCEPTANCE INSPECTION (CAI)

WHILE THE CONTRACTOR IS ON-SITE AT THE END OF CONSTRUCTION.

1. ALL NON-CURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT SHALL

BE BONDED TOGETHER AND MADE ELECTRICALLY CONTINUOUS IAW FAA-STD-019F.

2. ALL GROUNDING SHALL BE SIZED IAW NFPA 70 (NEC) AND FAA-STD-019F.

3. GROUND CONNECTION TO ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE MADE

WITH APPROVED GROUNDING CONNECTIONS.

4. ALL RIGID GALVANIZED STEEL CONDUITS ENTERING ELECTRICAL EQUIPMENT MUST

CONTAIN A GROUNDING BUSHING AT BOTH ENDS AND BE GROUNDED AT THE POINT

OF ENTRY TO THE EQUIPMENT. BONDING JUMPER MUST BE SIZED AS LARGE AS THE

LARGEST EGC GOING THROUGH THE CONDUITS WITH THE GROUNDING BUSHINGS.

5. WHEN BONDING TO EQUIPMENT USING FIELD INSTALLED GROUND LUGS, REMOVE

PAINT AND OTHER COATINGS FROM THE MOUNTING SURFACE TO ENSURE A GOOD

BOND. APPLY A PROTECTIVE COATING TO MATCH EXISTING FINISH OVER ANY

EXPOSED METAL ONCE GROUNDING CONNECTION HAS BEEN MADE.

6. ALL UNDERGROUND CONNECTIONS SHALL BE EXOTHERMIC WELD.

7. ALL UNDERGROUND CONDUITS CROSSING THE EES SHALL BE BONDED TO THE EES

WITH A BARE #2 CONDUCTOR, EXOTHERMIC WELD.

SM

GENERAL NOTES

GROUNDING NOTES

INSTALLATION NOTES

ABBREVIATIONSSYMBOLS LEGENDSYMBOLS LEGEND

P-XXX

XX

C-XXX

JUMPER.

MAIN BONDING

#2AWG G.E.C. AND

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:3

:2

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -e

.d w g

8 234567

H

G

F

E

D

C

A

B

120/240V 1PH, 3W

SQUARE D, NQ, 100A MLO,

PANEL A

120-2S-M3-3-06-A

RAYVOSS

RCAG SHELTER 4

3W, NEMA1,

120/240V 1PH,

225A, 200A MB

SQUARE D, NQ,

PANEL 'MDP'

2P

200A

2P

60A

TVSS

HVAC 1 HVAC 2

120-2S-M3-3-06-A

RAYVOSS

4 4

P-010

P-007 P-008

1P

20A

REC.

REC.

INV.

INV.

DC BUS

2P

100A

P-011

120/240V, 1PH 3W

SQUARE D, NQ, 225A MLO

PANEL P

TVSS

TVSS

2P

150A

P-012

2P

100A

P-013

P-014

2P

100A

1P

20A

2P

20A

2P

20A

2P

60A

2P

100A

GTK0610C EQUIPMENT GROUND KIT

SN0610C SOLID NEUTRAL KIT

HU362DS

HD, 60A

SQUARE D

HVAC DISC 1

120-2S-M3-3-06-A

RAYVOSS

GTK0610C EQUIPMENT GROUND KIT

SN0610C SOLID NEUTRAL KIT

HU362DS

HD, 60A

SQUARE D

HVAC DISC 2

P-016 P-015

UTILITY

SECONDARY

120/240V, 1PH

TRANSFORMER

PADMOUNT UTILITY

EXISTING

E/G

MOBILE

SERVICE RACK

P/N GCP-N-0-2-200-1-1-3-6-SE

UNION CONNECTOR

CAM LOCK CONNECTORS

NEMA 4X, SERIES 16

200A, MAIN BREAKER

CONNECTION BOX

MOBIL E/G

TO UTILITY

P-001 1

P-002

P-005

P-006 5

WITH MAIN BREAKER

NEMA 4X

200A 1P,3W 120/240

UTILITY METER BASE

M

200A

TVSS

E/G

MOBILE

DT364UWK

EATON P/N

NEMA 4X

600VA AC

DOUBLE THROW

HEAVY DUTY

SWITCH

TRANSFER

MANUAL3

SWITCH

DISCONNECT

ENTRANCE

SERVICE

UTILITY

DISC. SWITCH

MOBILE E/G

200A, 1PH, 3W

MANUAL TRANSFER SWITCH

200A

N

G

EES

N G

G G

N

G

N

N G

N

G

E/G

MOBILE ENGINE GENERATOR

G

N

PANEL P

N G

PANEL MDP

N G

SWITCH

DISC.

TVSS

N G

G

N

PANEL A

N G

TVSSTVSS

N G

N NG G

N

G

P/N 120-2S-N1-3-06-A-SS

NEMA 4X RAYVOSS

TVSS

P-004

EQUIPMENT GROUND KIT PK0GTC2

RK5 FUSES-200A

SQUARE D P/N H364DS

600VAC, NEMA 4X

HEAVY DUTY, FUSIBLE

TVSS DISC. SWITCH 3

P-017

N G

G

N

TVSS

EES

JUMPER

MAIN BONDING

#2AWG G.E.C AND

P-018

CONDUIT#

SIZE/TYPE

CONDUIT

SIZE/TYPE

CABLE

(1)-2 1/2" RGSC

(1)-6AWG GND

(3)-6AWG THWN

(1)-2 1/2" RGSC

(1)-2AWG GND

(3)-3/0AWG

(1)-6AWG GND

(3)-6AWG THWN

(1)-2 1/2" RGSC

(1)-1" RGSC

(1)-1" RGSC

REMARKS

HVAC 1 DISCONNECT SW

HVAC 2 DISCONNECT SW

TRANSFORMER

UTILITY

PANEL MDP

PANEL MDP

METER BASE

TVSS DISC SWITCH

SWITCH

MANUAL TRANSFER

METER BASE

UTILITY SERVICE DISC

SUBCONTRACTOR SHALL PROVIDE PULL ROPE IN SERVICE CONDUIT.

SERVICE CONDUCTORS ARE FURNISHED AND INSTALLED BY UTILITIES.

(1)-2AWG GND

(3)-3/0AWG THWN

(1)-2AWG GND

(3)-3/0 AWG THWN

P-001

P-002

P-003

P-004

P-005

P-014

P-007

P-008

FROM TO

(1)-2" EMT

P-010

P-011

P-006

(1)-2 1/2" RGSC (1)-2AWG GND

(3)-3/0AWG THWN

MOBILE E/G DISC SWITCH

(1)-1 1/2" EMT

(1)-1 1/2" EMT

(1)-2AWG GND

(3)-2AWG THWN

(1)-2AWG GND

(3)-2AWG THWN

PANEL MDP

PANEL MDP

MDP TVSS

PANEL A

(1)-2AWG GND

(3)-1/0AWG

PANEL MDP PANEL P

P-012 (1)-1 1/2" EMT

(1)-2AWG GND

(3)-2AWG THWN PANEL P PANEL P TVSS

P-013 (1)-1 1/2" EMT

(1)-2AWG GND

(3)-2AWG THWN PANEL A PANEL A TVSS

(1)-2 1/2" RGSC

(1)-2AWG GND

(3)-3/0AWG THWN PANEL MDP

P-015

P-016

(1)-1" LIQUID TIGHT

(1)-1" LIQUID TIGHT

(1)-6AWG GND

(3)-6AWG THWN

(1)-6AWG GND

(3)-6AWG THWN

HVAC 1 DISC. SWITCH

HVAC 2 DISC. SWITCH

HVAC 1

HVAC 2

SWITCH

MANUAL TRANSFER

SWITCH

MANUAL TRANSFER

SWITCH

MANUAL TRANSFER

(1)-1" PVC (1)-2AWG GND METER BASE EES

P-017 (1)-2 1/2" RGSC

(1)-2AWG GND

(3)-3/0AWG THWN

TVSS DISC SWITCH

SWITCH

MANUAL TRANSFER

NOT TO SCALE

ONE-LINE DIAGRAM RCAG SITE

E304

A

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E304

RCAG

STANDARD 36FT MIRROR

ONE-LINE DIAGRAM

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

P-018 (1)-2AWG GND CONNECTION BOX

MOBILING EG

(1)-1" PVC EES

6 DC BUS SUPPLIED AND INSTALLED BY OTHERS.

FROM THE MANUAL TRANSFER SWITCH TO PANEL MDP.

STEEL LB. CONTRACTOR SHALL PROVIDE, INSTALL AND TERMINATE WIRING

NIPPLE AND THE CONTRACTOR SHALL PROVIDE THE RIGID GALVANIZED

PROVIDE A BUILDING PENETRATION WITH A THREADED RIGID GALVANIZED

GALVANIZED STEEL ABOVE GROUND. BUILDING MANUFACTURER SHALL

CONDUIT SHALL BE PVC COATED RIGID AND TRANSITION TO RIGID

TRANSFER SWITCH TO THE BUILDING EXTERIOR. EXTERIOR UNDERGROUND

CONTRACTOR SHALL PROVIDE AND INSTALL CONDUIT FROM THE MANUAL

AND INSTALLED BY SHELTER MANUFACTURER.

WORKMANSHIP, EXTERIOR HVAC AND HVAC DISCONNECTS ARE PROVIDED

RCAG/RTR SHELTER IS GFE. INTERIOR ELECTRICAL MATERIALS AND

TERMINATIONS REQUIRED.

ALL MOUNTING HARDWARE, GROUNDING, RACK STEEL/FOUNDATIONS, AND

FURNISHED AND CONTRACTOR INSTALLED. CONTRACTOR SHALL PROVIDE

DISCONNECT SWITCH AND TVSS DISCONNECT SWITCH ARE CONTRACTOR

SERVICE TVSS, METER BASE, MANUAL TRANSFER SWITCH, MOBILE E/G

METER BASE WITH UTILITY REPRESENTATIVE PRIOR TO ORDERING.

METER BASE SHALL MEET UTILITIES REQUIREMENTS. OBTAIN APPROVAL FOR

RCAG ELECTRICAL SERVICE TO SERVICE RACK.

WIRE, TERMINATIONS, AND METER BASE REQUIRED TO ESTABLISH NEW

UTILITIES REPRESENTATIVE. PROVIDE NEW RCAG SERVICE RACK, CONDUIT,

SUBCONTRACTOR SHALL COORDINATE NEW ELECTRIC SERVICE WITH

CONDUIT/CABLE SCHEDULE

(3) 12AWG [NOTE 2]

QUICK DISCONNECT

ANDERSON SB350

MAIN GROUND PLATE

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:3

:4

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -e

.d w g

8 234567

H

G

F

E

D

C

A

B

(1) 2AWG GREEN/ORANGE [NOTE 2]

X D

C W

IR

E

W A

Y

PANEL P

CB 2/4 20A

CB 6/8 20A

CB 10 20A

CB 12 20A

(3) 12AWG [NOTE 2]

(3) 12AWG[NOTE 2]

(3) 12AWG [NOTE 2]

(3) 12AWG [NOTE 2]

DC BUS SYSTEM

RECT 1 AC IN

RECT 2 AC IN

INVERTER 1 AC IN

INVERTER 2 AC IN

+24VDC

DC OUT

-48VDC

DC OUT

IB2 BOARD

DI1

J3-1

INVERTER 1 AC OUT

INVERTER 2 AC OUT

FRWK

CB 4.1 200A

PANEL ROW 4

BATTERY DISC

FRWK

ANC-A-DC BUS

GROUND BAR

(1

A W

G G

R E E

N

O R

A N

G E

N O

T E

(1

A W

G G

R E E

N

O R

A N

G E

N O

T E

(1) 2AWG GREEN/ORANGE[NOTE 2]

(1) 2AWG GREEN/ORANGE [NOTE 2]

(1) 2AWG GREEN/ORANGE[NOTE 2]

GRD

ERMS

GRD

(1) 4/0 FLEX [NOTE 2]

(1) 4/0 FLEX [NOTE 2]

FAA TEST EQUIPMENT ONLY

BUILT IN RECEPTACLE FOR

(3) 12AWG [NOTE 2]

(2 PER CIRCUIT) 12AWG [NOTE 2]

(2 PER CIRCUIT) 12AWG [NOTE 2]

TO STANDARD RADIO LOADS

TO FOTS LOADS

PULLBOX

12X12 AC

EQUIPMENT

TELCO/FIT

TO ERMS &

GNB 90GXX

BATTERY STRING A

+24V TERM PLATE

-24V TERM PLATE

FRWK

(1 G

R /O

R

N O

T E

R E F E

R E

N C

E G

R O

U N

D

(1 /0 G

R E E

N

N O

T E

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E306

RCAG

STANDARD 36FT MIRROR

RCAG DC BUS

TYPICAL ONE-LINE

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

1. ASSOCIATES DRAWINGS:

WASD-D-RCAG-E302 ELECTRICAL SITE PLAN

WASD-D-RCAG-E304 ELECTRICAL ONE-LINE DIAGRAM

2. WIRES, CABLES, CONDUIT OR WIRE DUCT TO BE RUN BY THE INSTALLER.

PWR

PNL A

MDP

PNL

G F I

MDP

MDP

MDP

MDP

MDP

MDP

MDP

MDP

MDP

MDP

5,7

GFI

MDP

MDP

9,11

MDP

MDP

G F I

MDP

MDP

H V

A C

H V

A C

C

E307

MDP

H V

A C

H V

A C

B

WORK

(BY OTHERS)

BATTERIES

BOX

JUNCTION

RF

BOX

JUNCTION

RF

(BY OTHERS)

DC BUS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

LOCKER

STORAGE

PARTS

GND

TELCO

SPG

GND

BENCH

B

B

B

MPG SPG MPG SPG

SM

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

A A A A

A A A A

A

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

GND

SUPP

PNL P

PWR

TVSS

TO CEILING

UNISTRUT MOUNTED

SUPPORT ON 1 5/8"

EQUIPMENT RACKS,

TRAY OVER ELECTRONIC

WIREWAY TO CABLE

4" HINGED, NEMA 1

(TYPICAL)

CONDUITS

BRANCH

TVSSTVSS

NEMA 1

WIREWAY,

HINGED

6X6"

A

PNL

PWR

P

PNL

PWR

MDP

PNL

PWR

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

D

A T

E

T

IM

E

N

A M

E

DATE

APPROVED

F

IL

E S

8 234567

H

G

F

E

D

C

A

B

NOT TO SCALES

PANEL SCHEDULES

E307

B

SCALE: 1/2" = 1'-0"

FACILITY ELECTRICAL PLAN

E307

A

NOT TO SCALES

INTERIOR ELECTRICAL PANELS

E307

C

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

PNL P (SQUARE D TYPE NQ OR APPROVED SUBSTITUTION, TYPE QOB BRANCH) PANEL P

MLO

DC BUS RECETIFIER 2

DC BUS INVERTER 1

SPARE

SPARE

BLANK

DC BUS RECETIFIER 1

RACK 1 - CONVENIENCE RECPT

RACK 1 - PRI

RACK 2 - PRI

RACK 2 - CONVENIENCE RECPT

COMM TOWER PRI-RECEPTACLE

COMM TOWER PRI-OB LIGHT GFCI

SPARE

BLANK BLANK

BLANK

BLANK

22,000 RMS SYM AMPS

PNL MDP (SQUARE D TYPE NQ OR APPROVED SUBSTITUTION, TYPE QOB BRANCH) PANEL MDP 200 AMP

LOCATION: RCAG SHELTER BUS AMPS: 225A, 1 PH, 3 WIRE

X

MCB

RATED SCI

FEEDBOT.

TOP FEED

C.B.

CIRCUIT DESCRIPTION

A POLE CKT PH PH CKT POLE A

1 A A

B B

20 1

EXTERIOR LIGHTS

INTERIOR LIGHTS

INTERIOR RECEPTACLES

EXTERIOR RECEPTACLES

EMERGENCY LIGHT

HVAC 1

HVAC 2

PANEL A

INTERIOR RECEPTACLES

SMOKE DETECTOR

DEMAND LOAD:

CONNECTED LOAD:

SURFACE MNT.

FLUSH MNT.

HVAC CONTROL

SPARE

RCAG SHELTER BUS AMPS: 100A, 1 PH, 3 WIRELOCATION:

RACK 1 - CONVENIENCE RECEPT

RACK 1 - ALT

RACK 2 - ALT

RACK 2 - CONVENIENCE RECEPT

COMM TOWER ALT-RECEPTACLE

COMM TOWER ALT-OB LIGHT GFCI

TVSS

TVSS100

DC BUS INVERTER 2

100 100

SPARE

X

X

CIRCUIT DESCRIPTION

SPARE

SPARE

SPARE

BLANK

BLANK

BLANK

PANEL P

SPARE

SPARE

SPARE

C.B.

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

LOCATION: RCAG SHELTER BUS AMPS: 225A, 1 PH, 3 WIRE

X

X

X

FEEDBOT.

TOP FEED

SURFACE MNT.

FLUSH MNT.

10,000 RMS SYM AMPS

RATED SCI

DEMAND LOAD:

CONNECTED LOAD:

CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION

C.B. C.B.

A POLE CKT PH PH CKT POLE A

1 A A

B B3

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

SPARE

SPARE

SPARE

BLANK

BLANK

BLANK

BLANK

PNL A (SQUARE D TYPE NQ OR APPROVED SUBSTITUTION, TYPE QOB BRANCH) PANEL A

MLO

X

10,000 RMS SYM AMPS

RATED SCI

DEMAND LOAD:

CONNECTED LOAD:

SURFACE MNT.

FLUSH MNT. X

FEEDBOT.

TOP FEED

CIRCUIT DESCRIPTION CIRCUIT DESCRIPTION

C.B. C.B.

A POLE CKT PH PH CKT POLE A

SPARE

SPARE

SPARE

SPARE

BLANK

BLANK

BLANK

BLANK

BLANK

SPARE

SPARE

SPARE

SPARE

SPARE

TVSS

BLANK

BLANK

BLANK

BLANK

BLANK

BLANK

BLANK

BLANK

1 A A

B B3

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

B B

A A

X

DESIGN BASIS (OR EQUAL)

WITH CUT OFF SHIELD

CSXW-LED-1-30B350/40-FT-120-PE-DNAXD

LITHONIA LIGHTING

STL4-48L-120V-50W-NX-LP840

LITHONIA LIGHTING

QUANTUM-LHQM-LED-RED

LITHONIAC

A

B

TYPE DESCRIPTION

LIGHTNING FIXTURE SCHEDULE

ACRYLIC LENSE

1'X4' SURFACE MOUNT, LED TYPE

LED TYPE, WITH INTEGRAL PHOTOCELL

EXTERIOR WALL MOUNT FIXTURE, INDIRECT LIGHT,

LED TYPE, DUAL HEAD, NICAD BATTERY PACK

EMERGENCY LIGHT & EXIT SIGN COMBINATION

DESIGN BASIS (OR EQUAL)

GENTEX CORP. 7139CS-CA

TYPE DESCRIPTION

SMOKE DETECTOR

CEILING MOUNT

120V, 9V BACKUP WITH FORM C RELAY CONTACT,

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E307

RCAG

STANDARD 36FT MIRROR

ELECTRICAL PLAN, PANEL SCHEDULES

AND INTERIOR ELECTRICAL PANELS

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

DEPENDENT ON BATTERY AMPACITY AND RUNTIME.

BATTERY CABINET WIDTH, HEIGHT AND DEPTH IS

1" SLEEVE

COVER.

PROOF GFCI DUPLEX RECEPTACLES WITH IN USE

EXTERIOR RECEPTACLES ARE TO BE WEATHER-

WALL MOUNTED HVAC CONTROLLER.

QUAD BOX RECEPTACLE.

ERMS PANEL (PROVIDED BY OTHERS).

WIRED SMOKE DETECTOR W/ BATTERY BACKUP.

4"x4" SQUARE D DUCT.

LOCATE WORK BENCH RECEPTACLES 3'-2" HIGH.

POWER PANELS WITH TVSS ON EACH.

AND CUTOFF SHIELDS.

EXTERIOR LIGHT WITH PHOTOCELL CONTROLLER

DUAL FLOOD LIGHTS.

EMERGENCY EXIT SIGN WITH

4" SLEEVE.1

EES

MULTI-POINT

SINGLE-POINTMAIN SUPPLEMENTAL

TELCO

BUILDING FLOOR

EES

BUILDING FLOOR

GROUND STRIP

COPPER

EES

MULTI-POINT MULTI-POINT MULTI-POINT

SINGLE-POINT SINGLE-POINT

WIREWAY COVER

WIREWAY SIDE

E308

COPPER

GROUND STRIP 4

E308

CABLE TRAY

ISOMETRIC VIEW

COVER

HINGED

1/2" PVC

6AWG IN

STRAP

COPPER GROUND

GROUNDWORX ULTRA

STATICWORX

FINISH FLOOR

PWR

PNL A

MDP

PNL

PNL P

PWR

H V

A C

H V

A C

B

WORK

(BY OTHERS)

BATTERIES

BOX

JUNCTION

RF

BOX

JUNCTION

RF

(BY OTHERS)

DC BUS

(BY OTHERS)

LOCKER

STORAGE

PARTS

GND

TELCO

GND

SUPP

SPG

GND

BENCH

B

B

B

MPG SPG MPG SPG

(BY OTHERS)

RADIO & RACKS

SM

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS (BY OTHERS)

RADIO & RACKS

GND

MAIN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

D

A T

E

T

IM

E

N

A M

E

DATE

APPROVED

F

IL

E S

8 234567

H

G

F

E

D

C

A

B

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

SCALE: 1/2" = 1'-0"

GROUNDING PLAN

E308

A

NOT TO SCALE

MULTI-POINT/SINGLE-POINT DETAIL

E308

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E308

RCAG

STANDARD 36FT MIRROR

SHELTER MULTI-POINT/SINGLE-POINT DETAILS

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 02/26/2024 FIELD REVISION

AW

MANUFACTURER IS STATICWORX, PRODUCT IS GROUNDWORX ULTRA.

AND SUPPLEMENTAL GROUND PLATES PER MANUFACTURER RECOMMENDATIONS.

INSTALL 2 COPPER GROUND STRAPS AND CONNECT TO THE MAIN

OF 12-TON COMPRESSION FORCE.

CONDUCTOR, 2 HOLE LUG HYDRAULICALLY CRIMPED WITH A MINIMUM

BOND EACH SECTION OF CABLE TRAY AND WIREWAY WITH A #6AWG

BE EXOTHERMIC WELDS.

MAIN, SUPPLEMENTAL AND TELCO CABLES TO EES CONDUCTORS SHALL

OR SHORTER THAN THE MAIN TO EES CONDUCTOR.

SUPPLEMENTAL TO EES CONDUCTOR SHALL BE 30% LONGER

NUMBER OF COMPRESSION WASHER ON EACH BOLT PER FAA STD-19F.

UTILITY 2 HOLE LUGS AT EACH PLATE INCLUDING THE APPROXIMATE

GND PLATE TO GROUND CABLE TRAY.

USE #2 AWG GREEN W/ORANGE TRACER TO MULTI-POINT

TELCO TO EES - GRN W/ RED TRACER

SUPPLEMENTAL TO EES - GRN W/RED TRACER

MAIN TO EES - GRN W/RED TRACER

MULTI-POINT TO MULTI-POINT GND - GRN/ORG TRACER

SUPPLEMENTAL TO MULTI-POINT GND - GRN W/ORG TRACER

MAIN TO SUPPLEMENTAL - GRN W/ORG TRACER

MAIN TO MULTI-POINT GND - GRN W/ORG TRACER

MAIN TO SINGLE-POINT GND - GRN W/YEL TRACER

COLOR CODE IS AS FOLLOWS:

SPRING WASHER ON EACH BOLT.

LUGS AT EACH PLATE. INCLUDE 3 COMPRESSION

USE #4/0 INSULATED COPPER CABLE WITH 2 HOLE1

NOTES:

NOT TO SCALE

WIREWAY DETAIL

E308

NOT TO SCALE

DETAIL

E308

NOT TO SCALE

CABLE TRAY BONDING

E308

2.0

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:4

:1

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -e

.d w g

8 234567

H

G

F

E

D

C

A

1. MATERIAL IS 1/4" COPPER BAR STOCK.

2. COPPER PLATE FOR MAIN GROUND, SUPPLEMENTAL GROUND.

3. COPPER PLATE FOR MULTIPOINT & GROUND PLATES.

(ALT P/N: 3832-8-12 MPG & 3832-8-12 SPG OR APPROVED EQUIVALENT)

4. COPPER PLATE FOR TELECOMMUNICATION GROUND

(ALT P/N: 3812-1-12 OR APPROVED EQUIVALENT).

MULTI-POINT GROUND PLATE SINGLE POINT GROUND PLATE

GROUND PLATE

SUPPLEMENTAL

MAIN GROUND PLATE

NOMENCLATURE, AS SHOWN IN DIAGRAM.3.

LETTERING ADD STRIPES AS SHOWN IN EACH DIAGRAM.2.

MATERIAL 3/16" PLEXIGLASS, CLEAR.1.

NOTES:

8 ORANGE 3/8" STRIPES.

3/8" SPACING BETWEEN

STRIPES AS SHOWN.

8 YELLOW 3/8" STRIPES.

3/8" SPACING BETWEEN

STRIPES AS SHOWN.

QTY

ITEM DESCRIPTION

WALL OR CABLE TRAY

1. TYPICAL BRACKET FOR MAIN GROUND, SUPPLEMENTAL GROUND,

MULTIPOINT GROUND & SINGLE POINT GROUND.

BRACKET ASSEMBLY PARTS LIST

NOTE:

M

IN

TO FIN. FLOOR

MAIN & SUPPLEMENTAL

GROUND PLATE,

SEE NOTE 1

500MCM GREEN

INSULATED STRANDED

COPPER GROUND, TO

BE INSTALLED BY

OTHERS.

PRECAST CONCRETE

WALL

NOTES:

1. GROUND PLATE IS SPACED AWAY FROM WALL WITH CHANNEL-STRUT

TO ALLOW AN 8" MINIMUM CABLE BENDING RADIUS.

2. PVC PIPE SIZE IS 4" FOR MAIN, SUPPLEMENTAL AND TELCO GROUND PENETRATIONS.

PENETRATION FOR PVC

PIPE & LB. PENETRATION

TO BE LARGE ENOUGH TO

ACCOMMODATE 4" PVC

.1

(TYP)

GROUND BAR

COPPER X

1/4" THICK

(TYP)

.1

MAIN GROUND & SUPPLEMENTAL GROUND PLATE MULTI-POINT & SINGLE POINT GROUND PLATE TELCO GROUND PLATE

MAIN GROUND PLATE SUPPLEMENTAL GROUND PLATE MULTI-POINT GROUND PLATE SINGLE POINT GROUND PLATE

8 GREEN 3/8" STRIPES.

3/8" SPACING BETWEEN

STRIPES AS SHOWN.

8 GREEN 3/8" STRIPES.

3/8" SPACING BETWEEN

STRIPES AS SHOWN.

LETTERS, ARIAL FONT

3/8" BLACK

LETTERS, ARIAL FONT

3/8" BLACK

LETTERS, ARIAL FONT

3/8" BLACK

LETTERS, ARIAL FONT

3/8" BLACK

0.32

4PL

0.32

16PL

0.44

0.32

0.32

6PL

0.27

6PL

0.27

GROUND BAR

COPPER X

1/4" THICK

0.32

4PL

0.44Ø

0.32

16PL

0.27

16PL

0.27Ø

4PL

0.32

0.320.27

NOTE 4

8xØ9/16" THRU 7/16"Ø2x

1/4"-20 x 1/2" S.S HEX BOLT

INSULATOR 2 1/2 " HIGH 1" DIA.

1/4"-20 x 1" S.S. ALL THREAD

GROUND PLATE LEG

6 1/2" x 3/16" x 1" STOCK

BRIGHT ZINC FINISH

NOTES:

PLEXIGLASS COVER

GROUND PLATE

BOLT & NUT

CHANNEL STRUT

STRUT

1 5/8" SQ. CHANNEL

3" 0 6" 9"

SCALE: 3" = 1'-0"

3"

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E309

RCAG

STANDARD 36FT MIRROR

GROUND PLATE DETAILS

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

SCALE: 3" = 1'-0"E309

SCALE: 3" = 1'-0"E309

NOT TO SCALEE309

NOT TO SCALEE309

GROUND PLATES

GROUND PLATE COVERS

GROUND PLATE BRACKET ASSEMBLY GROUND PLATE WALL PENETRATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/2

/2

:3

:5

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

w a s d -d -r c a g -e

.d w g

8 234567

H

G

F

E

D

C

A

B

ROD (TYP)

THREADEDØ3/8"

AND LOCK WASHERS (TYP.)

PROVIDE 3/8" BOLT, NUT,

3/8" CABLE TRAY CLAMPS

TRAY-SECURE WITH

STEEL LADDER CABLE

12"Wx3"D GALVANIZED

WORKING IN WIREWAY

STAY OPEN WHILE

DOWNWARD SO IT WILL

THAT THE COVER HINGES

WIREWAY MOUNTED SUCH

AND LOCK WASHERS.

WITH 5/16" BOLT, NUT,

PWR (TYP), SECURE

WIREWAY FOR AC

4" HINGED NEMA 1

CEILING LINE

WORKING IN WIREWAY

STAY OPEN WHILE

DOWNWARD SO IT WILL

THAT THE COVER HINGES

WIREWAY MOUNTED SUCH

AND LOCK WASHERS.

WITH 5/16" BOLT, NUT,

PWR (TYP), SECURE

WIREWAY FOR AC

4" HINGED NEMA 1

NEW RACKS

ROOF STRUCTURE

1 5/8" UNISTRUT

1 HR FIRE RATED

PLYWOOD

TELCO GROUND PLATE

E310

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-E310

RCAG

STANDARD 36FT MIRROR

SHELTER CABLE TRAY AND WIREWAY DETAILS

w a s d -d -r c a g -e

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 08/16/2023 FIELD REVISION

AW

NOT TO SCALE

CABLE TRAY INSTALLATION

E310

A

NOT TO SCALE

TELCO WALLBOARD

E310

B

1'-6 1/2" 1'-10"

E D

G E O

F W

A L L

C S

PL

IC

E

C SPLICE

4'- 0 1 /2"

3'- 6"

4'- 0"

L

1'-6 1/2"

1'-10"

L

C S

PL

IC

E

L

C S

PL

IC

E

L

C S

PL

IC

E

L

EDGE OF WALL

1"

C SPLICE

L

C SPLICE

L

C SPLICE

L

3'- 6"

'-7 1/

2"

1"

C S

PL

IC

E

L

C S

PL

IC

E

L

E D

G E O

F

1'-1 1/2" 2'-3"

W A

L L

NOTE

EDGE OF WALL

HORIZONTAL TEE FITTING

EATON B-LINE P/N 14P-12-HT12

OR EQUIVALENT

HORIZONTAL CROSS FITTING

OR EQUIVALENT

NOTE

NOTE

NOTE 1

NOTE 1

NOTE 1

CHANNEL STRUT HANGER

SEE DWG GKN-22008515-A002

FOR LOCATIONS

(TYP)

CABLE TRAY (NOTE 1)

EATON B-LINE P/N 14P-12-HX12

OR EQUIVALENT

EATON B-LINE P/N 14P-12-90VO12

OR EQUIVALENT

EATON B-LINE P/N 14P-12-90VO12

HORIZONTAL TEE FITTING

OR EQUIVALENT

EATON B-LINE P/N 14P-12-HT12

E D

G E O

F W

A L L

(TYP)

(6" RUNG SPACING)

(6" RUNG SPACING)

(6" RUNG SPACING)

(6" RUNG SPACING)

(6" RUNG SPACING)

NOT TO SCALE

CABLE TRAY

E310

12"X3" GALVANIZED STEEL CABLE LADDER.

EACH SPLICE ON EITHER SIDE OF LADDER SHALL HAVE A #6AWG GREEN INSULATED

BONDING WIRE ATTACHED WITH 2 HOLE LUGS.

#2 AWG GREEN INSULATED STRANDED COPPER GROUND CONDUCTOR WITH

ORANGE TRACER TO MULTIPOINT GROUND PLATE. LUG SHALL BE WITHIN 24" OF

EACH END OF CABLE TRAY.

1 HR FIRE RATED PLYWOOD.

PENETRATION IN WALL TO ACCOMMODATE 1 1/2" PVC SLEEVE FOR GROUND CABLE.

THIS PENETRATION TO BE 10" BELOW GROUND PLATE. CABLE TO BE INSTALLED BY

OTHERS.

PENETRATION FOR FUTURE 4" PVC CONDUIT & LB FOR TELECOMMUNICATIONS.

SLEEVE TO BE LARGE ENOUGH FOR CONDUIT.

EACH SECTION OF WIREWAY SHALL HAVE A #6AWG GREEN INSULATED BONDING WIRE

ATTACHED WITH 2 HOLE LUGS.

NOTES:

MDP

PNL

PNL P

PWR

H V

A C

H V

A C

B

WORK

(BY OTHERS)

BATTERIES

(BY OTHERS)

RF

JUNCTION

BOX

BOX

JUNCTION

RF

DC BUS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

PARTS

STORAGE

LOCKER

(BY OTHERS)

TELCO

GND

SPG

BENCH

GND

B

B

B

MPG SPG MPG SPG

SM

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

15 4

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

(BY OTHERS)

RADIO & RACKS

GND

SUPP

PNL A

PWR

GND

MAIN

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

D

A T

E

T

IM

E

N

A M

E

DATE

APPROVED

F

IL

E S

8 234567

H

G

F

E

D

C

A

B

SCALE: 1/2" = 1'-0"

GROUNDING PLAN

Q301

A

IS

S

U E

D F

O R

E D

M

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

DO

NOT

SI

GN

NATIONAL STANDARD

AWASD-D-RCAG-Q301

RCAG

STANDARD 36FT MIRROR

SHELTER TYPICAL FLOOR PLAN

w a s d -d -r c a g -q

.d w g

COMMUNICATIONS

FAA STANDARD WASHINGTON, DC

A 03/12/2024 FIELD REVISION

AW

1' 0 3' 5'

SCALE: 1/2" = 1'-0"

1' 2' 4'

ON BATTERY AMPACITY AND RUNTIME.

BATTERY CABINET WIDTH, HEIGHT AND DEPTH IS DEPENDENT

GND PLATE TO GROUND CABLE TRAY.

USE #2 AWG GREEN W/ORANGE TRACER TO MULTI-POINT

TRACER

SUPPLEMENTAL TO MULTI-POINT GND - GRN W/ORG

MAIN TO SUPPLEMENTAL - GRN W/RED TRACER

MAIN TO MULTI-POINT GND - GRN W/ORG TRACER

MAIN TO SINGLE-POINT GND - GRN W/YEL TRACER

MAIN TO BENCH GND - GRN W/YEL TRACER

COLOR CODE IS AS FOLLOWS:

SPRING WASHER ON EACH BOLT.

LUGS AT EACH PLATE. INCLUDE 3 COMPRESSION

USE #4/0 INSULATED COPPER CABLE WITH 2 HOLE

PRECAST PREFABRICATED BUILDING.

ERMS PANEL (INSTALLED BY OTHERS).

SMOKE DETECTOR.

HANGING 4"X4" SQUARE D DUCT.

HANGING 12"X3" GALVANIZED STEEL LADDER CABLE TRAY.

LOCATE RECEPTACLES 4' HIGH.

PANELBOARDS WITH TVSS.

NOT USED.

EXTERIOR LIGHT.

EMERGENCY EXIT SIGN WITH DUAL FLOOD LIGHTS.

HVAC DUCT OPENING PER MANUFACTURER SPECIFICATIONS.

4" SLEEVE.

36"X48"X12" MARINE GRADE ALUMINUM, NEMA 4 ENCLOSURE.

8'X4' TELCO WALLBOARD.

DEDICATED TELCO RECEPTACLES FROM INVERTED POWER.

6" X 6" X 4" STAINLESS STEEL NEMA 4X ENCLOSURE.

1" SLEEVE.

NOTES: