This document is a Request for SF330s (Standard Form 330) for an Architect/Engineer contract for a federal project. The Department of Veterans Affairs has a need to establish a single award, firm-fixed price, Architect/Engineer contract for Project #556-23-110 Building 133 Laboratory Renovation at the Captain James A. Lovell FHCC in North Chicago, IL. The project requires design, specification, and construction period services to renovate Building 133 Pathology and Laboratory Medicine Services spaces, including histology, cytology, microbiology, phlebotomy, and administration areas, and associated utilities.
The procurement is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) located within a 250-mile radius of the site. Firms must be certified as SDVOSBs by the SBA. Qualification factors include professional qualifications, specialized experience, capacity, past performance, location, claims history, use of small businesses, and construction period services experience. Firms must submit one electronic copy of the SF330 by 10:00am CDT on May 30, 2024. The VA may use the submitted SF330s for additional small design projects up to the simplified acquisition threshold.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building Year Built Last Renov Floors FCA GSF Current Function Hospital/Clinics
133 1961 1996 6 383,434 Proposed Function Hospital/Clinics
Details 133 Architectural Rec No Seq No Condition Useful Life FCA Risk Remain Life Correction $ Description
133 Accessibility 120241 2 D * 3 * 103,835.09$ Provide accessible counters at 133CA volunteer reception, prosthetics reception, In-Patient Pharmacy window, Primary clinics help desk, the library (3D-130), Legal-Travel, Sleep Lab 2D150 desk, Occupy. Health C2121 desk, 4th floor reception desk, Radiology, and Room BD111.
133 Pending Totals: D * 3 * 242,260.00$ Provide accessible counters at 133CA volunteer reception, prosthetics reception, In-Patient Pharmacy window, Primary clinics help desk, the library (3D-130), Legal-Travel, Sleep Lab 2D150 desk, Occupy. Health C2121 desk, 4th floor reception desk, Radiology, and Room BD111.
133 Accessibility 33889 1 C * * -$ Building is substantially compliant with most of the 1st and 2nd floors being fully compliant, and the rest is partially compliant.
* Handrail spacing meets 2004 ABA/ADA AG and 2006 IBC.
133 Pending Totals: C * * -$ Building is substantially compliant with most of the 1st and 2nd floors being fully compliant, and the rest is partially compliant.
* Handrail spacing meets 2004 ABA/ADA AG and 2006 IBC.
133 Accessibility 239817 3 D * 3 * 24,203.98$ Pharmacy, SPD locker and Basement floor drinking fountain are not accessible. Provide 4 accessible fountain.
133 Pending Totals: D * 3 * 32,565.00$ Pharmacy, SPD locker and Basement floor drinking fountain are not accessible. Provide 4 accessible drinking fountains.
133 Accessibility 239818 4 D * 3 * 36,305.98$ Basement lockers in rooms BC 105 A and B, BC 107, BD-133 & 134, 2D 122 and 123, and 3rd floor are not accessible. Provide 4 lockers two in each with lever handle.
133 Pending Totals: D * 3 * 59,965.00$ Basement lockers in rooms BC 105 A and B, BC 107, BD-133 & 134, 2D 122 and 123, and 3rd floor are not accessible. Provide 4 lockers two in each with lever handle.
133 Accessibility 279040 5 D * 3 * 189,920.60$ Many toilets are not completely complying. Verify door hardware, grab bars behind and aside toilets, correct heights of fixtures and accessories, insulation at lavatory hot water supply and drain pipes, sufficient floor clearance, jamb clearance, door swing interference, etc. Toilets include: 3A- 158, 3A-126, 2D-258, 2D151A, 2D-159, 2D-165A, 2A-122 and 123, 2B-120, 1B-104, BD-161B and BD-162S.
133 Accessibility 279041 6 D * 3 * 1,142.97$ Provide International Symbol of Accessibility at 133CA main (South) entrance when fully complying; provide information in building directory for location of nearest public accessible sanitary facilities.
133 Pending Totals: D * 3 * 4,654.00$ * Provide International Symbol of Accessibility at 133CA main (South) entrance when fully complying; provide information in building directory for location of nearest public accessible sanitary facilities. * 2022 UPDATE:
Project in works 556-22 currently for wayfinding.
133 Accessibility 279042 7 D * 3 * 92,580.24$ Sinks and countertops in staff break rooms, conference rooms, etc. must be 34 in. maximum AFF. 60 LF.
133 Exterior Walls 279043 3 C 100 75 -$ Brick and limestone panel exterior walls from 1991 CA addition are in above average condition.
133 Pending Totals: C 100 71 -$ Brick and limestone panel exterior walls from 1991 CA addition are in average condition.
133 Exterior Walls 279044 4 D 100 3 * 3,905,944.86$ Oculus/WJE Façade Study completed in Sept 2013 details several repairs divided into, D grade (will become unstable within 3 years) and B grade (recommendations). Refer to report for further details. Summary of repairs:
* Grade D: Rebuild areas of cracked and displaced masonry with new and replace cracked limestone sills.
* Grade B: Repair select corroded steel lintels and install vertical masonry expansion joints.
133 Pending Totals: D 100 3 * 5,070,204.00$ * Oculus/WJE Façade Study completed in Sept 2013 details several repairs Refer to report for further details. Summary of repairs:
* Rebuild areas of cracked and displaced masonry with new and replace cracked limestone sills.
* Repair select corroded steel lintels and install vertical masonry expansion joints.
133 Exterior Walls 163281 2 C 100 45 -$ Brick walls on original building (1961) generally in fair condition. 2001 repairs made to replace steel lintels and flashing, tuckpoint and replace cracked bricks, especially at outside bldg and window corners.
133 Pending Totals: C 100 42 -$ Brick walls on original building (1961) generally in fair condition. 2001 repairs made to replace steel lintels and flashing, tuckpoint and replace cracked bricks, especially at outside bldg and window corners.
133 Exterior Walls 363262 5 B+ 100 93 -$ FCA record added by Contractor - see detail/pending.
2010 EF addition exteriors in very good condition. 2010 EF addition exteriors in very good condition.
133 Pending Totals: B+ 100 90 -$ 2010 EF addition exteriors in very good condition.
133 Fixed Equipment 279045 4 D 15 3 exceeds 170,184.94$ At 4B Substation, CCU and ED: nurse stations are in poor condition, replace. 80 LF.
* SPS decontam casework is in poor condition. 25 LF ss casework.
133 Pending Totals: D 15 3 exceeds 255,063.00$ At 4B Substation, CCU and ED: nurse stations are in poor condition, replace. 80 LF.
* SPS decontam casework is in poor condition. 25 LF ss casework.
133 Fixed Equipment 33891 1 B 15 8 -$ Audio Labs, Radiology, Pharmacy, In-Patient Kitchen, Surgery equipment is generally in good condition.
133 Fixed Equipment 162498 2 C 15 4 -$ Lab, SPS and Nuclear Medicine fixed equipment is in fair condition.
133 Fixed Equipment 163094 3 B 15 10 -$ Dental equipment is in good condition.
133 Interior Finish/Door 120242 2 C 10 2 -$ Wing 2B, the ED and the Basement level is in average condition.
133 Interior Finish/Door 33892 1 B 10 5 -$ 4th Floor, Surgery, 2nd Floor Wings A, C, D and 1st Floor, Canteen and Kitchen: All in good condition.
133 Interior Finish/Door 279046 3 B 10 8 -$ Most finishes in Wing E & F : The Primary Clinic are in very good condition.
133 Pending Totals: B 10 5 -$ Most finishes in Wing E & F : The Primary Clinic are in good condition.
133 Interior Finish/Door 279047 4 D 10 3 exceeds 167,416.27$ At corridor between Imaging and Nuclear Medicine: provide handrails. 300
LF.
* Throughout building areas of concealed spline metal ceiling remain that is hard to access and maintain. Replace 30,000 SF. Include new radiant heat panels.
* Original metal checkerplate corridor expansion joints are tripping hazard.
Replace 8' wide floor EJ in corridors, 8 locations.
* Plastic laminate tops in clinic exam rooms throughout building delaminating at corners and damaged. Replace 500, 4' long tops with solid surface.
* Stair 3 interior columns (4) show signs of water infiltration at the base.
Repair 60 SF plaster damage and investigate source of moisture.
133 Interior Finish/Door 363263 5 A 10 10 -$ FCA record added by Contractor - see detail/pending.
3A and 3B renovated 2015 to 2017 and in like new condition.
* Part of Surgery renovations complete in 2017.
133 Interior Finish/Door 363264 6 D 10 3 * 1,177,765.88$ FCA record added by Contractor - see detail/pending.
* PT finishes in poor condition. Project underway to renovate. 12,000 SF.
* First floor In-Pat. Pharmacy finished in poor condition. Project underway to renovate 4800 SF.
* Basement Labs finishes poor. Renovate 19,000 SF.
* Flooring in SPS is not in good condition or not appropriate. Replace 700
SF.
133 Pending Totals: D 10 3 * 3,773,262.00$ * PT finishes replaced.
* First floor In-Patient Pharmacy finishes in poor condition. Project underway to renovate 4800 SF.
* Basement Labs finishes poor. Renovate 19,000 SF.
* Flooring in SPS is not in good condition or not appropriate. Replace 700 SF. Design project underway
133 Life Safety 279048 2 D * 5 * 28,103.52$ Provide complying panic hardware at all doors along paths of egress travel at exit stairwells. 30 doors.
* 1st Floor CA clinic cross corridor doors not wide enough for egress.
Rework plan and install new doors with 32" min clearance. 4 locations.
133 Life Safety 279049 3 D * 5 * 334,754.55$ Provide handrail extensions on outer and continuous inner rail per code at all (6 original) interior stairs.
* Stair 3 (open stair) has non-compliant guardrails (+ 4" gaps) and lacks handrails. Replace all from Level 1 to 2.
133 Pending Totals: D * 5 * 417,923.00$ * Provide handrail extensions on outer and continuous inner rail per code at all (6 original) interior stairs.
* Stair 3 (open stair) has non-compliant guardrails (+ 4" gaps) and lacks handrails. Replace all from Level 1 to 2.
133 Life Safety 33893 1 A * * -$ Sprinklered building. No problems observed.
133 Pending Totals: A * * -$ Sprinklered building.
133 Roof 33894 1 B 20 15 -$ Main entry and EF addition roof modified bitumen in very good condition.
133 Pending Totals: B 20 12 -$ Main entry and EF addition roof modified bitumen in good condition.
133 Roof 163095 2 D 20 3 exceeds 1,507,800.65$ Ballasted built-up roof. Wings A, B, C done in 1991. Roof is in poor condition. Needs replacement. 97,000 SF including flashings and copings.
133 Pending Totals: D 20 3 exceeds 3,505,589.00$ Ballasted built-up roof. Wings A, B, C done in 1991. Roof is in poor condition. Repaired in 2012 but still leaks. Needs replacement. 97,000 SF including flashings and copings.
133 Roof 279050 3 B 20 10 -$ Standing seam metal roof over South Clinic entry is in good condition.
133 Pending Totals: B 20 7 -$ Standing seam metal roof over South Clinic entry is in good condition.
133 Signage / Wayfindg 33895 1 B 10 6 -$ Signage system installed in 2004 and as suites renovated is in good condition.
133 Pending Totals: B 10 3 -$ * Signage system installed in 2004 and as suites renovated is in good condition.
* 2022 update: Wayfinding project underway for entire facility.
133 Windows 33896 1 B 30 23 -$ Aluminum double glazed windows with integral blinds installed in 2010 and 2010 EF addition aluminum double glazed curtain wall and fixed windows are in overall good condition.
133 Pending Totals: B 30 20 -$ Aluminum double glazed windows with integral blinds installed in 2010 and 2010 EF addition aluminum double glazed curtain wall and fixed windows are in overall good condition.
133 Windows 279051 2 C 30 10 -$ Aluminum double glazed curtain wall and fixed skylights from 1991 CA are average condition.
133 Pending Totals: C 30 7 -$ Aluminum double glazed curtain wall and fixed skylights from 1991 CA are average condition.
133 Windows 363265 3 D 30 5 * 33,616.64$ FCA record added by Contractor - see detail/pending.
Station reports that EF addition curtain wall and fixed windows as well as 2010 window replacement lacks proper thermal resistance to cold; affecting patient satisfaction. Provide study to determine exact cause and suggest remedial action.
133 Pending Totals: D 30 5 * 54,969.00$ FCA record added by Contractor - see detail/pending.
Station reports that EF addition curtain wall and fixed windows as well as 2010 window replacement lacks proper thermal resistance to cold; affecting patient satisfaction. Provide study to determine exact cause and suggest remedial action.
133 System Total Correction $7,773,576 System Replacement Cost $139,482,580 Ratio: 0.06
133 System Total Pending $13,416,454 [Row Count 31]
133 Electrical Rec No Seq No Condition Useful Life FCA Risk Remain Life Correction $ Description
133 Elec/Tele Closets 414462 3 D * 5 * 34,750.00$ Panel QP-B-G12 in room BD-170 in Building 133CA does not have code required working clearances.
133 Pending Totals: D * 5 * 34,750.00$ Panel QP-B-G12 in room BD-170 in Building 133CA does not have code required working clearances.
133 Elec/Tele Closets 33897 1 C * * -$ There are closets for panels and telecommunication. Fair condition with good space.
133 Pending Totals: C * * -$ There are closets for panels and telecommunication. Fair condition with good space.
133 Elec/Tele Closets 362215 2 D * 5 * 28,137.13$ Panel QP-B-G12 in room BD-170 in Building 133CA does not have code required working clearances.
133 Emerg Elec Sys. 362216 13 D 25 5 * 63,535.46$ Normal, life safety and critical circuit are not routed in separate raceway system per the requirements of the National Electrical Code in room 1D-181 in Building 133CA.
133 Emerg Elec Sys. 362217 14 D 25 5 * 9,984.14$ Fire alarm panel is served from a critical branch panel (CP-1-F9) in Building 133CA in lieu of a life safety panel.
133 Emerg Elec Sys. 362211 12 C 25 1 -$ "Building 133CA is served from three substation as indicated: USS-1:
substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution. USS-2: substation, 1000 kVA 4160-208/120 Volt oiled filled transformer, 3000A secondary distribution. USS-3: substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution.
Branch circuit lighting and receptacles loads are served from 120/208 Volt GE/Eaton (2008) panels located on each floor. Equipment loads are served from motor control centers at 480 Volt. Branch circuit panels are in fair condition."
133 Emerg Elec Sys. 362199 5 D 25 5 * 272,294.82$ Transfer switches (EPSS system) are in stalled in the same room as normal power service equipment, which is not in compliance with NFPA 110.
133 Pending Totals: D 25 5 * 289,581.00$ Transfer switches (EPSS system) are in stalled in the same room as normal power service equipment, which is not in compliance with NFPA 110.
133 Emerg Elec Sys. 362201 6 D 25 5 * 27,229.48$ It appears that a coordination study has not been performed for the emergency distribution system. Study should be preformed and corrective actions should be addressed. Cost indicated is for study only.
133 Pending Totals: D 25 5 * 28,958.00$ It appears that a coordination study has not been performed for the emergency distribution system. Study should be preformed and corrective actions should be addressed. Cost indicated is for study only.
133 Emerg Elec Sys. 414463 16 D 25 5 * 46,333.00$ Normal, life safety and critical circuit are not routed in separate raceway system per the requirements of the National Electrical Code in room 1D-181 in Building 133CA.
133 Pending Totals: D 25 5 * 46,333.00$ Normal, life safety and critical circuit are not routed in separate raceway system per the requirements of the National Electrical Code in room 1D-181 in Building 133CA.
133 Emerg Elec Sys. 414464 17 D 25 5 * 16,796.00$ Fire alarm panel is served from a critical branch panel (CP-1-F9) in Building 133CA in lieu of a life safety panel.
133 Pending Totals: D 25 5 * 16,796.00$ Fire alarm panel is served from a critical branch panel (CP-1-F9) in Building 133CA in lieu of a life safety panel.
133 Emerg Elec Sys. 414465 18 B 25 24 -$ Building 133CA contains 14 automatic transfer switches, 9 of which have bypass isolation. Switches are manufactured by GE Zenith and have amperage ratings as follows: (4) 100 Amp, (5) 260 Amp, (2) 400 Amp, (2) 600 Amp, (1) 800 Amp. All are in good condition and were installed around 2014.
133 Pending Totals: B 25 24 -$ Building 133CA contains 14 automatic transfer switches, 9 of which have bypass isolation. Switches are manufactured by GE Zenith and have amperage ratings as follows: (4) 100 Amp, (5) 260 Amp, (2) 400 Amp, (2) 600 Amp, (1) 800 Amp. All are in good condition and were installed around 2014.
133 Emerg Elec Sys. 414466 19 C 25 * -$ Emergency power for Building 133CA is fed from the generators in Building
192. ATS's are not identified on the type of emergency power systems.
Exit lights, without batteries, installed. Fair condition.
133 Pending Totals: C 25 * -$ Emergency power for Building 133CA is fed from the generators in Building
192. ATS's are not identified on the type of emergency power systems.
Exit lights, without batteries, installed. Fair condition.
133 Emerg Elec Sys. 414484 21 D 25 5 * 46,333.00$ It appears that a coordination study has not been performed for the emergency distribution system. Study should be preformed and corrective actions should be addressed. Cost indicated is for study only.
133 Pending Totals: D 25 5 * 46,333.00$ It appears that a coordination study has not been performed for the emergency distribution system. Study should be preformed and corrective actions should be addressed. Cost indicated is for study only.
133 Emerg Elec Sys. 414469 20 C 25 exceeds -$ * Building 133CA is served from three substation as indicated: USS-1:
substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution. USS-2: substation, 1000 kVA 4160-208/120 Volt oiled filled transformer, 3000A secondary distribution. USS-3: substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution.
* Branch circuit lighting and receptacles loads are served from 120/208 Volt GE/Eaton (2008) panels located on each floor. Equipment loads are served from motor control centers at 480 Volt. Branch circuit panels are in fair condition.
133 Pending Totals: C 25 exceeds -$ * Building 133CA is served from three substation as indicated: USS-1:
substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution. USS-2: substation, 1000 kVA 4160-208/120 Volt oiled filled transformer, 3000A secondary distribution. USS-3: substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution.
* Branch circuit lighting and receptacles loads are served from 120/208 Volt GE/Eaton (2008) panels located on each floor. Equipment loads are served from motor control centers at 480 Volt. Branch circuit panels are in fair condition.
133 Emerg Elec Sys. 414461 15 D 25 3 * 123,555.00$ ATS-9, which serves the elevators, is actually (3) 100 Amp ATS's that are commonly fed from one feeder. This should be separated into three (3) separately fed ATS's.
133 Pending Totals: D 25 3 * 123,555.00$ ATS-9, which serves the elevators, is actually (3) 100 Amp ATS's that are commonly fed from one feeder. This should be separated into three (3) separately fed ATS's.
133 Emerg Elec Sys. 362190 3 D 25 5 * 544,589.65$ Life Safety/Legally Required Standby branch panels on the ground and second floor of Building 133 and all floors in Building 133EF serve loads that are not allowed to be connected to Life Safety/Legally Required Standby.
133 Pending Totals: D 25 5 * 555,176.00$ Life Safety/Legally Required Standby branch panels on the ground and second floor of Building 133 and all floors in Building 133EF serve loads that are not allowed to be connected to Life Safety/Legally Required Standby.
133 Emerg Elec Sys. 362203 7 A 30 28 -$ The main electrical room in Building 133 contains 9 automatic transfer switches, 8 of which have bypass isolation. Switches are manufactured by GE Zenith and ASCO and have amperage ratings as follows: (1) 150 Amp,
(2) 225 Amp, (4) 400 Amp, (1) 600 Amp, (1) 800 Amp. All are in good condition and were installed around 2014.
133 Pending Totals: B 30 24 -$ The main electrical room in Building 133 contains 9 automatic transfer switches, 8 of which have bypass isolation. Switches are manufactured by GE Zenith and ASCO and have amperage ratings as follows: (1) 150 Amp,
(2) 225 Amp, (4) 400 Amp, (1) 600 Amp, (1) 800 Amp. All are in good condition and were installed around 2014.
133 Emerg Elec Sys. 362204 8 A 30 28 -$ "Building 133CA contains 14 automatic transfer switches, 9 of which have bypass isolation. Switches are manufactured by GE Zenith and have amperage ratings as follows: (4) 100 Amp, (5) 260 Amp, (2) 400 Amp, (2) 600 Amp, (1) 800 Amp. All are in good condition and were installed around 2014.
ATS-9, which serves the elevators, is actually (3) 100 Amp ATS's that are commonly fed from one feeder. This should be separated into three (3) separately fed ATS's."
133 Emerg Elec Sys. 362206 9 A 30 24 -$ Building 133EF contains 2 automatic transfer switches, Switches are manufactured by GE Zenith and rated for 600 Amp. The transfer switches are in good condition and were installed around 2010.
133 Emerg Elec Sys. 362207 10 A 25 * -$ Emergency power for Building 133, 133CA and 133EF is fed from the generators in Building 192. ATS have been segregated in critical, life safety and equipment branches. ATS's in D Wing are not identified on the type of emergency power systems. Small UPS in office for computer. Exit lights, without batteries, installed. Fair condition.
133 Pending Totals: C 25 * -$ Emergency power for Building 133, 133CA and 133EF is fed from the generators in Building 192. ATS have been segregated in critical, life safety and equipment branches. ATS's in D Wing are not identified on the type of emergency power systems. Exit lights, without batteries, installed.
Fair condition.
133 Emerg Elec Sys. 362208 11 C 30 9 -$ The penthouse in Building 133 contains one 225 Amp, automatic transfer switch, manufactured by GE Zenith. Transfer switch was installed in 1995 and is fair condition.
133 Pending Totals: C 30 5 -$ The penthouse in Building 133 contains one 225 Amp, automatic transfer switch, manufactured by GE Zenith. Transfer switch was installed in 1995 and is fair condition.
133 Fire Alarm 120243 2 F 15 5 exceeds 3,717,828.81$ [ Field Engineer Review Completed on 03/19/2018 by vhanchschilk.]
[ Auto Generated Project Pending on 01/10/2018 for Project Number 556- 12-127 created by vhanchschilk.]
"Alarm system is Simplex 4100, addressable, upgraded in 1999.
The fire alarm system is operable but nearing the end of its life expectancy.
Fire alarm strobe and manual pull station layout is inadequate and does not meet current code requirements."
133 Pending Totals: F 15 5 exceeds 4,441,406.00$ Alarm system is Simplex 4100, addressable, upgraded in 1999.
The fire alarm system is operable but nearing the end of its life expectancy.
Fire alarm strobe and manual pull station layout is inadequate and does not meet current code requirements.
133 Lighting & Power 33900 1 C 25 8 -$ "Approximately 90% of building lighting fixtures upgraded with T8 lamps and electronic ballasts. Fluorescent down lights, bed lights, and industrials.
ICU headwalls have critical receptacles. LED exit signs throughout. Good condition.
133 Pending Totals: B 25 18 -$ Approximately 50% of building lighting fixtures upgraded with LED lamps or fixtures. Fluorescent down lights, bed lights, and industrials. ICU headwalls have critical receptacles. LED exit signs throughout. Good condition.
133 Lighting & Power 239860 2 F 25 5 exceeds 456,843.48$ [ Field Engineer Review Completed on 02/15/2022 by VHANCHJohnsB2.]
[ Auto Generated Project Pending on 02/15/2022 for Project Number 556- 12-145 created by VHANCHJOHNSB2.]
[ Field Engineer Review Completed on 03/19/2018 by vhanchschilk.]
[ Auto Generated Project Pending on 01/10/2018 for Project Number 556- 12-127 created by vhanchschilk.]
"Upgrade approximately 10% of building lighting fixtures with T8 lamps and electronic ballasts.
133 Pending Totals: F 25 3 exceeds 592,188.00$ Upgrade approximately 50% of building lighting fixtures with LED lamps or fixtures.
133 Lightning Protect 33901 1 C 20 5 -$ Complete and operational. Fair condition.
133 Pending Totals: C 20 2 -$ Lightning protection system complete and operational. Fair condition.
133 Nurse Call/Int/TV 159584 2 B 15 7 -$ Intercom is installed outside of building. Good condition
133 Pending Totals: B 15 4 -$ Intercom is installed outside of building. Good condition
133 Nurse Call/Int/TV 31470 1 B 15 9 -$ Nurse call: EZ Care Vital touch system installed around 2015, Good condition.
133 Pending Totals: D 15 4 4 1,447,904.00$ Nurse call: EZ Care Vital touch system installed around 2015. Nurse call system does not support 2-way communication in all areas. Some of the remote nurse call phones are missing. Replace system with updated system.
133 Nurse Call/Int/TV 414468 3 D 15 5 4 231,665.00$ Nurse call: EZ Care Vital touch system installed around 2015. Nurse call system does not support 2-way communication in all areas. Some of the remote nurse call phones are missing. Replace system with updated system.
133 Pending Totals: D 15 5 4 231,665.00$ Nurse call: EZ Care Vital touch system installed around 2015. Nurse call system does not support 2-way communication in all areas. Some of the remote nurse call phones are missing. Replace system with updated system.
133 Secondary Dist. 414467 12 D 30 5 * 2,780.00$ Panel LP-1-G4 in Building 133CA is missing directory.
133 Pending Totals: D 30 5 * 2,780.00$ Panel LP-1-G4 in Building 133CA is missing directory.
133 Secondary Dist. 362193 3 D 30 5 * 36,305.98$ Ground buses in normal and emergency panels serving a common patient care area do not appear to be bonded together per the requirements of the National Electrical Code.
133 Pending Totals: D 30 5 * 34,750.00$ Ground buses in normal and emergency panels serving a common patient care area do not appear to be bonded together per the requirements of the National Electrical Code.
133 Secondary Dist. 362195 4 D 30 5 * 2,722.95$ USS-1 in Building 133 has a plastic sheet (taped on) covering breaker terminals. Plastic cover should be replaced with metal closure plates
133 Pending Totals: D 30 5 * 5,792.00$ USS-1 in Building 133 has a plastic sheet (taped on) covering breaker terminals. Plastic cover should be replaced with metal closure plates
133 Secondary Dist. 362196 5 D 30 5 * 907.65$ Panel P-B-K12 in main electrical room in Building 133 has rust all over cover. Rust should be removed and panel repainted.
133 Pending Totals: D 30 5 * 1,158.00$ Panel P-B-K12 in main electrical room in Building 133 has rust all over cover. Rust should be removed and panel repainted.
133 Secondary Dist. 362197 6 C 30 9 -$ Siemens Distribution equipment located within building 133 was installed in 1995 and is in good condition.
133 Pending Totals: C 30 5 -$ Siemens Distribution equipment located within building 133 was installed in 1995 and is in fair condition.
133 Secondary Dist. 348062 2 D 30 5 * 307,635.33$ "Correct deficiencies identified in Eaton Electrical Study (E26) dated December 2015.
Deficiencies include inadequate rating of the OCPD’s, mis-coordination between OCPD’s and NEC violations. For detail, refer to Section 10.0 Appendix C – Cost Estimates.
133 Pending Totals: D 30 5 * 579,162.00$ Correct remaining deficiencies identified in Eaton Electrical Study (E26) dated December 2015 and perform new electrical study, as they are required every 5 years.
Deficiencies include inadequate rating of the OCPD’s, mis-coordination between OCPD’s and NEC violations.
133 Secondary Dist. 362202 7 D 30 5 exceeds 13,343.12$ Panel CP-2-K116, Ericson, 150 Amp, in room 2A-103A in Building 133 is at the end of it rated life and should be replaced.
133 Pending Totals: D 30 5 exceeds 11,583.00$ Panel CP-2-K116, Ericson, 150 Amp, in room 2A-103A in Building 133 is at the end of it rated life and should be replaced.
133 Secondary Dist. 362212 9 A 30 24 -$ "Building 133EF is served from two substation which are connected together via a tie breaker. Each substation has two incoming medium voltage feeders, a 1500 kVA 4160-480/277 Volt dry type transformer, 2500A secondary distribution.
Branch circuit lighting and receptacles loads are served from 120/208 Volt panels located on each floor. Equipment loads are at 480 Volt.
All distribution in the building is manufactured by Square D and installed in 2010"
133 Secondary Dist. 362213 10 D 30 4 * 789.32$ Panel 3BHN1 in room 3E-206 of Building 133EF is missing lockset.
133 Secondary Dist. 362214 11 D 30 5 * 517.70$ Panel LP-1-G4 in Building 133CA is missing directory.
133 Secondary Dist. 362210 8 C 30 1 -$ "Building 133 is served from two substation as indicated: USS-1: GE substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution. USS-2: GE substation, 1000 kVA 4160-208/120 Volt oiled filled transformer, 2000A secondary distribution.
Branch circuit lighting and receptacles loads are served from 120/208 Volt Siemens (1995)/GE/Square D panels located on each floor. Equipment loads are served at 480 Volt. Branch circuit panels are in fair condition."
133 Pending Totals: C 30 exceeds -$ * Building 133 is served from two substationS as indicated: USS-1: GE substation, 1500 kVA 4160-480/277 Volt oiled filled transformer, 2000A secondary distribution. USS-2: GE substation, 1000 kVA 4160-208/120 Volt oiled filled transformer, 2000A secondary distribution.
* Branch circuit lighting and receptacles loads are served from 120/208 Volt Siemens (1995)/GE/Square D panels located on each floor. Equipment loads are served at 480 Volt. Branch circuit panels are in fair condition.
133 System Total Correction $5,984,877 System Replacement Cost $52,305,968 Ratio: 0.11
133 System Total Pending $8,489,870 [Row Count 39]
133 Mechanical Rec No Seq No Condition Useful Life FCA Risk Remain Life Correction $ Description
133 Air Handling Equip 414814 61 D 20 3 exceeds 21,866.00$ (Bldg. 133) AHU-3 Racan unit located in PENTHOUSE was installed in 1995, is in poor condition and past it's useful life. Unit should be replaced.
Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Pending Totals: D 25 3 exceeds 21,866.00$ (Bldg. 133) AHU-3 Racan unit located in PENTHOUSE was installed in 1995, is in poor condition and past it's useful life. Unit should be replaced.
Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Air Handling Equip 414815 62 B 20 16 -$ (Bldg. 133) 133-FCU-1 chilled water fan coil located in PENTHOUSE is in good condition.
133 Pending Totals: B 25 16 -$ (Bldg. 133) 133-FCU-1 chilled water fan coil located in PENTHOUSE is in good condition.
133 Air Handling Equip 414816 63 D 20 3 exceeds 21,866.00$ (Bldg. 133) AHU-4 Racan unit located in PENTHOUSE was installed in 1995, is in poor condition and is past it's useful life. Unit should be replaced. Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Pending Totals: D 25 3 exceeds 21,866.00$ (Bldg. 133) AHU-4 Racan unit located in PENTHOUSE was installed in 1995, is in poor condition and is past it's useful life. Unit should be replaced. Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Air Handling Equip 414818 64 D 20 3 * 567,579.00$ (Bldg 133) AHU-7 mounted high in PENTHOUSE is currently not operational. Unit should be replaced when Kitchen area renovation is initiated.
133 Pending Totals: D 25 3 * 567,579.00$ (Bldg 133) AHU-7 mounted high in PENTHOUSE is currently not operational. Unit should be replaced when Kitchen area renovation is initiated.
133 Air Handling Equip 414820 65 C 20 6 -$ (Bldg. 133) FCU-3 located in DUMBWAITER ELEVATOR MACHINE ROOM is in fair condition.
133 Pending Totals: C 25 6 -$ (Bldg. 133) FCU-3 located in DUMBWAITER ELEVATOR MACHINE ROOM is in fair condition.
133 Air Handling Equip 414821 66 B 20 17 -$ (Bldg 133) AHU-1 located on LOADING DOCK ROOF serves PHARMACY and was installed in 2013. Unit is in good condition.
133 Pending Totals: B 25 17 -$ (Bldg 133) AHU-1 located on LOADING DOCK ROOF serves PHARMACY and was installed in 2013. Unit is in good condition.
133 Air Handling Equip 347130 16 D 20 3 57,409.16$ "[ Auto Generated Project Pending on 06/21/2016 for Project Number 556- 16-017 created by vhanchjuhld.]
Steam Coil"
133 Air Handling Equip 338894 14 F 3 0 113,773.52$ "[ Auto Generated Project Pending on 02/11/2016 for Project Number 556- 15-014 created by vhanchjuhld.]
Replace chilled water coil in AHU# 3 of Building 133 with like-and-kind. Coil has failed and needs replacement as this AHU serves SPS, Pharmacy, and parts of the OR."
133 Pending Totals: A 20 24 -$ (Bldg. 133CA) AHU-3 located in RM 1D-244 serving SPS, Pharmacy and parts of OR has been replaced with Trane Climate Changer w/ electric humidifier in 2020 and is in excellent condition.
133 Air Handling Equip 347128 15 D 20 3 52,190.51$ [ Auto Generated Project Pending on 02/19/2016 for Project Number 556- 16-015 created by vhanchjuhld.]
Heating Coils
133 Air Handling Equip 280330 5 B 17 -$ AC-3, AHU-10 were installed in 2010. The units have steam heating coils, chilled water coils, return fan with VFD and supply fan with VFD and are in very good condition.
133 Pending Totals: C 20 6 -$ (Bldg. 133) AC-3 McQuay unit located in PENTHOUSE was installed in 2005 and is in fair condition.
* Pre-Filter & After-Filter
* Supply Fan (SF-3)
* Return Fan (RF-3)
133 Air Handling Equip 280331 6 C exceeds -$ AHU-2 and AHU-4 are Racan unit installed in 1996, consisting of a mixing section, economizer, prefilters, heating coil, cooling coil with UV disinfection, SWSI return fan and DWDI supply fan. Units are in fair condition.
133 Pending Totals: D 20 5 exceeds 542,819.00$ (Bldg. 133) AHU-2 Racan unit located in PENTHOUSE was installed in 1995 and is past it's useful life. Condensate pan is rusted out and leaking.
Fan housing is showing extensive rusting. Unit should be replaced.
Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Air Handling Equip 280332 7 D 5 13 49,058.79$ AHU-10 does not have after filters, but serves patient areas. Add final filters.
133 Air Handling Equip 280337 10 D 5 1 62,627.81$ AHU-6 is serving patient areas in the clinical addition, but does not have final filters. The supply fan section has exposed fiberglass insulation.
Provide final filters and provide solid panels in fan section.
133 Pending Totals: D 20 5 1 222,302.00$ (Bldg. 133CA) AHU-6 Temprol unit located in BD-130 serves primary care areas. Unit does not have final filters and supply fan section has exposed fiberglass insulation. Unit is past it's useful life and should be replaced.
Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 280339 11 B 30 25 -$ 1 McQuay air handling unit installed in 2012 in the hospital mechanical room and are good conditon. The units have internal return fans, economizers, mixing boxes, pre filters, one unit has final filters, heating coils, cooling coils and VFDs for the supply and return fans.
133 Pending Totals: B 30 10 -$ (Bldg 133) AHU-10 McQuay unit located in PENTHOUSE serves 4th floor B- Wing was installed in 2009 and is in good condition.
* Supply Fan (VFD)
* Return Fan (VFD)
* Economizer
* Mixing Box
* Pre-filter & After-Filter
* Steam pre-heating coil
* Chilled Water Cooling Coils
133 Air Handling Equip 280342 12 D 1 Exceeds 12,525.56$ AHU-14 and a small outdoor chiller have been abandoned. Remove equipment and patch walls and roof.
133 Pending Totals: D 20 1 * 16,989.00$ (Bldg. 133CA) AHU-14 located in PENTHOUSE PD-100 has been decommissioned and should be removed.
133 Air Handling Equip 280344 13 D 5 1 100,453.26$ AHU-12 in the clinical additon is serving the admin area, but does not have after filters. Provide after filter section, increase motor size to 50 HP and provide new VFD.
133 Pending Totals: D 20 5 * 222,302.00$ (Bldg. 133CA) AHU-12 located in PENTHOUSE serves administrative spaces. Unit does not have After Filters. Provide After Filter section and increase fan HP to accommodate increase static pressure.
133 Air Handling Equip 239904 3 B 20 15 -$ AHUs in operation room replaced in 2007 are in good condition.
133 Air Handling Equip 159396 2 B 20 15 -$ (3) Air handling units for OR installed in 2006 and are in good condition.
133 Pending Totals: A 20 24 -$ (Bldg. 133) AHU-5 by Air Flow Equipment, Inc. located in 3C-100 serving Surgical GI was replaced in 2021 and is in excellent condition.
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* Electric Steam Humidifier
133 Air Handling Equip 362218 17 C 20 17 -$ AHU-1 serving surgery is a Johnson-Marcraft custom AHU serving the surgical area
133 Pending Totals: B 20 8 -$ (Bldg 133) AHU-1 Marcraft custom AHU located in RM 3C-100 serves the surgical areas and is in good condition.
* Pre-Filter & After-Filter
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil (Glycol)
* In-Duct Humidifiers
133 Air Handling Equip 362221 18 C 20 17 -$ AHU-9 is a modular AHU with steam heating coils, chilled water coils, return fan with VFD and supply fan with VFD, final filters.
133 Pending Totals: C 20 10 -$ (Bldg. 133) AHU-9 McQuay unit located in PENTHOUSE serves 4th Floor A- Wing and is in fair condition.
* Supply Fan SF-9 ~ 7,400 CFM (VFD)
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* Return Fan (VFD)
* Pre-Filter and After Filter
133 Air Handling Equip 362222 19 D 20 1 exceeds 10,438.64$ AHU-1 is an indoor central station AHU, manufactured by RACAN and installed in 1996. It consists of a mixing section, economizer, heating coil, cooling coil with UV disinfection DWDI supply fan and SWSI return fan. The unit is in fair condition, but with minor air leaks around the access doors that should be repaired.
133 Pending Totals: D 20 5 exceeds 434,430.00$ (Bldg. 133) AHU-1 by RACAN located in penthouse serving ER/Dental Basement/BIOMED/ROI. Was installed in 1995, is in poor condition and is past it's useful life. Unit should be replaced with new. Estimate:
* 15,000 CFM W/ Duplex Supply Fans
* Return Fan (Separate Utility Set Type)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Clean-Steam Humidifier (60 KW)
133 Air Handling Equip 362223 20 D 20 5 10 504,713.58$ SF-1 is a modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 30 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 545,628.00$ (Bldg 133CA) AHU-1 Temprol unit located in BD-130 serves RECORDS, NORTH LAB & BASEMENT is in poor condition and should be replaced.
Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362224 21 D 20 5 10 472,442.95$ SF-2 is an modular AHU with a loose return/exhaust fan located in room BD-
130. SF-2 has internal lining. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 20 HP motor. The drain pan is in poor condition and needs to be replaced.Internal lining should be removed and unit externally lined, or unit should be replaced.
133 Pending Totals: D 20 5 exceeds 524,779.00$ (Bldg 133CA) AHU-2 Temprol unit located in BD-130 serves SOUTH LABS, BASEMENT & BLOOD LAB is in poor condition and should be replaced.
Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362225 22 C 20 10 -$ SF-6 is a modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Air Handling Equip 362226 23 C 20 10 -$ SF-6 is a modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Air Handling Equip 362227 24 D 20 5 10 472,442.95$ SF-7 is an modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 20 HP motor. The drain pan is in poor condition and needs to be replaced.This unit has internal lining. Internal lining should be removed and unit externally lined, or unit should be replaced.
133 Pending Totals: D 20 5 exceeds 545,628.00$ (Bldg 133CA) AHU-7 Temptrol unit located in BD-130 serves SOUTH LABS, BASEMENT & BLOOD LAB is in poor condition and should be replaced. Estimate:
* ~10,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362228 25 B 30 30 -$ 133-AHU-5 is a new Carrier Central station AHU.
133 Air Handling Equip 362229 26 D 20 5 N/A -$ [ Field Engineer Review Completed on 03/19/2018 by vhanchschilk.]
[ Auto Generated Project Pending on 01/10/2018 for Project Number 556- 12-127 created by vhanchschilk.]
133-AHU-5 is missing after-filters
133 Air Handling Equip 362230 27 D 20 5 10 -$ [ Field Engineer Review Completed on 02/15/2022 by VHANCHJohnsB2.]
[ Auto Generated Project Pending on 02/15/2022 for Project Number 556- 12-145 created by VHANCHJOHNSB2.]
SF-3 is a modular AHU with a loose return/exhaust fan. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced. The cooling coil should be cleaned.
133 Pending Totals: A 20 18 -$ (Bldg 133CA) AHU-3 located in 1D-244 was replaced with a Trane unit in 2020 and is in excellent condition:
* Supply Fan SF-3
* Return Fan RF-3: 5 HP
* Humidifier H-3
133 Air Handling Equip 362231 28 D 20 5 10 -$ [ Field Engineer Review Completed on 02/15/2022 by VHANCHJohnsB2.]
[ Auto Generated Project Pending on 02/15/2022 for Project Number 556- 12-145 created by VHANCHJOHNSB2.]
SF-4 is a modular AHU with a loose return/exhaust fan located. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced. The unit has internal lining that is falling off the unit in places. The cooling coil looks dirty.
133 Pending Totals: A 20 18 -$ (Bldg. 133CA) AHU-4 located in 1D-244 was replace in 2020 and is in excellent condition:
* Supply Fan SF-4
* Return Fan RF-4 (In-Line 10 HP)
* Electric Humidifier (H-4)
133 Air Handling Equip 362232 29 D 20 5 10 331,249.01$ SF-5 is a modular AHU with a loose return/exhaust fan located. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced. The does not have final filters. The cooling coils appear dirty.
133 Pending Totals: D 20 5 exceeds 408,946.00$ (Bldg. 133CA) AHU-5 Temptrol unit located in 1D-244 serves CANTEEN.
Unit is past useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362233 30 D 20 5 10 331,249.01$ SF-8 is is a modular AHU with a loose return/exhaust fan located in room BD-130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 408,946.00$ (Bldg. 133CA) AHU-8 Temptrol unit located in 1D-224 serving floors 1,2 & 3 N & W EMPLOYEE HEALTH, IMAGING, DIRECTOR'S SUITE is in poor condition, past it's useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362234 31 D 20 5 10 331,249.01$ SF-9 is a modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 10 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 408,946.00$ (Bldg. 133CA) AHU-9 Temprol unit located in 1D-222 serving floors 1,2, 3 & 5 West & IMAGING DIRECTOR's SUITE is in poor condition, past it's useful life and should be replaced. Estimate:
* ~10,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362235 32 D 20 5 10 561,133.07$ SF-10 is a modular AHU with a loose return/exhaust fan located in room BD-
130. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 40 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 631,344.00$ (Bldg. 133CA) AHU-10 Temprol unit located in PENTHOUSE PD-100 serving floors 2 & 3 NE IMAGING & LIBRARY is past it's useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* Electric Humidifier (60 KW)
133 Air Handling Equip 362236 33 D 20 5 10 561,146.52$ SF-11 is a modular AHU with a loose return/exhaust fan. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 40 HP motor. The drain pan is in poor condition and needs to be replaced. The unit has internal lining in poor condition
133 Pending Totals: D 20 5 exceeds 631,344.00$ (Bldg. 133CA) AHU-11 Temprol unit located in PENTHOUSE PD-102A serving floors 2 & 3 SE IMAGING & DIRECTOR'S SUITE is in poor condition, past it's useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* Electric Humidifier (60 KW)
133 Air Handling Equip 362237 34 D 20 5 10 471,252.92$ SF-12 is a modular AHU with a loose return/exhaust fan. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 15 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 515,512.00$ (Bldg. 133CA) AHU-12 Temptrol unit located in PENTHOUSE PD-100 serving SURGICAL ADMIN is in poor condition, past it's useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil
* Electric Humidifier (60 KW)
133 Air Handling Equip 362238 35 D 20 5 10 471,252.92$ SF-13 is a modular AHU with a loose return/exhaust fan. The unit is manufactured by Temptrol, has Yasgawa VFDs and includes a mixing box, economizer, mixing box, prefilter section, steam heating coil, and 15 HP motor. The drain pan is in poor condition and needs to be replaced.
133 Pending Totals: D 20 5 exceeds 515,512.00$ (Bldg. 133CA) AHU-13 Temprol unit located in PENTHOUSE serving ICU is in poor condition, past it's useful life and should be replaced. Estimate:
* ~8,000 CFM w/ Duplex Supply Fans
* Return Fan (Separate In-Line)
* Pre-Filters and After-Filters
* Steam Pre-Heat Coil
* Chilled Water Cooling Coil *UV Lights
* Electric Humidifier (60 KW)
133 Air Handling Equip 362239 36 C 30 20 -$ AH16 and AH 17 are Temptrol units with filter, Cooling Coil and filter. The units are reciculation units serving the Elevator MR rooms PD101 in the CC
133 Pending Totals: C 30 6 -$ (Bldg. 133CA) FCU-1 & FCU-2 located in PENTHOUSE serves Elevator machine rooms. Units are in fair condition.
133 Air Handling Equip 362240 37 C 20 5 -$ AHU-6 and AHU-7 are cabinet fans with filters and supplies OA to ductwork.
133 Pending Totals: C 20 6 -$ (Bldg 133) AHU-6 mounted high in PENTHOUSE is in fair condition.
133 Air Handling Equip 362241 38 D 20 5 377,311.88$ AH-9 is a semi-custom air handling unit with discolored internal insulation, drain pan that is flaking, and near failure. The associated Return fan is in fair condition.
133 Air Handling Equip 362242 39 D 20 5 11 104,379.68$ AH-11 is a modular air handling unit located in the CA. The unit is a 100% OA unit with prefilters, preheat coil, cooling coil, supply fan After Filters.
The unit is internally lined
133 Air Handling Equip 362243 40 D 20 5 11 104,379.68$ AH-10 is a 100% OA modular air handlin unit with prefilters, preheat coil, cooling coil, supply fan and after filters serving the Imaging and director's suite on the 2nd and 3rd floor of the CA. The unit has internal lining which should be covered with metal lines.
133 Air Handling Equip 362244 41 B 30 24 -$ AHU-B3: AirZone custom AHU with plenum fan, 30 HP, 17000 CFM.
Modular design includes intake, prefilter, heating coil, Cooling coil, UV lights, humdiifier, supply fan, after filters and discharge. Serves south basement
133 Air Handling Equip 362245 42 B 20 24 -$ AHU-B2: AirZone custom AHU with plenum fan, 20 HP, 11000 CFM.
Modular design includes intake, prefilter, heating coil, Cooling coil, UV lights, humidifier, supply fan, after filters and discharge. Serves NE basement
133 Air Handling Equip 362246 43 B 30 24 -$ AHU-B1: AirZone custom AHU…