S02 - Building 133 Report Narrative 12_19_11.pdf

PDF 7 MB Posted

Attached to
C1DA--0007: A/E Bldg 133 Lab Service Renovation 556-23-110 (VA-24-00009483)
Solicitation number
36C25224Q0414
Issued by

About this file

This document is a Request for Standard Form (SF) 330s, not a Request for Proposal (RFP), issued by the Department of Veterans Affairs (VA) for a single award, firm-fixed price Architect/Engineer contract for Project #556-23-110 Building 133 Laboratory Renovation at the Captain James A. Lovell Federal Health Care Center in North Chicago, IL.

The contract requires design, specification, and construction period services for the renovation of Building 133 laboratory spaces, including histology, cytology, microbiology, phlebotomy, and administration areas, and associated utilities. This procurement is set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) located within a 250-mile radius of the project site. Respondents must submit one electronic PDF copy of the SF 330 by 10:00 AM CDT on May 30, 2024. The VA will evaluate submissions based on factors such as qualifications, specialized experience, capacity, past performance, local knowledge, and commitment to using small businesses as subcontractors. After evaluations, the VA will hold discussions/interviews with at least the top 3 firms before selecting the most preferred firm for contract negotiations.

View the file

Other files

File Type Posted
36C25224Q0414 0007.docx DOCX document
36C25224Q0414 0006.docx DOCX document
36C25224Q0414 0005.docx DOCX document
S06 - 556-B55 HVAC Record Dwgs Part 2.pdf PDF
S06 - 556-B55 HVAC Record Dwgs Part 1.pdf PDF
S06 - 556-B55 HVAC As-Built Dwgs Part 2.pdf PDF
36C25224Q0414 0004.docx DOCX document
S06 - 556-B55 HVAC As-Built Dwgs Part 3.pdf PDF
S06 - 556-B55 HVAC As-Built Dwgs Part 1.pdf PDF
36C25224Q0414 0003.docx DOCX document
S06 - VA Medical Center Alterations Volume 2.pdf PDF
S06 - VA Medical Center Alterations Volume 1.pdf PDF
S06 - 556-B55 Electrical Record Dwgs Part 1.pdf PDF
S06 - 556-B55 Electrical Record Dwgs Part 2.pdf PDF
36C25224Q0414 0002.docx DOCX document
S02 - 556-B55 Architectural Record Dwgs Part 1.pdf PDF
36C25224Q0414 0001.docx DOCX document
S02 - 556-B55 Architectural Record Dwgs Part 2.pdf PDF
S02 - 556-B55 Structural STD Record Dwgs.pdf PDF
S02 - Building 133.pdf PDF
S02 - 556-B55 Structural Record Dwgs.pdf PDF
S02 - 556-B55 Site Utilities Record Dwgs.pdf PDF
36C25224Q0414.docx DOCX document
S02 - Attachment 1 FHCC Specs.pdf PDF
S02 - 556-B55 Plumbing Record Dwgs.pdf PDF
S02 - FCA Review Report Bldg 133.pdf PDF
S02 - 556-23-110 Laboratory Services Renovation AE SOW 8DEC23.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Tropical Environmental, Inc.

10976 Fairbluff Ave.

Huntley, IL. 60142

(224) 569-3277 (224) 569-3278 fax www.TropicalEnvironmental.com

December 15, 2011

Mr. Royal Eckstein Captain James A. Lovell FHCC 3001 Green Bay Road North Chicago, Illinois 60064

RE: U.S. Department of Veterans Affairs (VA)

Captain James A. Lovell Federal Health Care Center Building # 133

Dear Mr. Eckstein:

Tropical Environmental, Inc. (Tropical) performed a limited asbestos assessment of the above referenced location in general accordance with:

• The Commercial and Public Buildings Asbestos Abatement Act (225 ILCS 207) enforced by the Illinois Department of Public Health (IDPH)

• The Asbestos Hazard Emergency Response Act (40 CFR 763) enforced by the U.S.

Environmental Protection Agency (USEPA), and

• The Asbestos Hazard Communication requirements (29 CFR 1910.1001(i) enforced by the U.S. Occupational Safety and Health Administration (OSHA).

Tropical performed the limited survey to identify and sample suspect asbestos-containing materials (ACM) in the facility. Samples of suspect asbestos-containing material (ACM) were submitted to a National Voluntary Laboratory Accreditation Program (NVLAP) certified laboratory for analysis. Laboratory results indicate that some of the suspect material contains asbestos. Please refer to the attached report for details on the survey.

Please feel free to contact me at (224) 269-3277 or by email at info@tropicalenvironmental.com with any comments or questions regarding Tropical’s investigation and this report.

Sincerely, Mark Haines President mailto:info@tropicalenvironmental.com

Table of Contents Page

Executive Summary

1.1 Project Purpose and Background

2.0 Asbestos Survey

2.1 Asbestos Survey Methodology

2.2 Asbestos Results

2.3 Applicable Regulations

3.0 Findings and Recommendations

4.0 Limitations

5.0 References & Definitions

Appendices

Appendix A: Asbestos Survey Analytical Summary Table Appendix B: Asbestos Laboratory Results, Laboratory Certifications and Chain-of-Custodies Appendix C: Tropical Employee Certifications Appendix D: Material/Sample Location Drawings Appendix E: Photographs of ACM Positives

Asbestos Survey

Building # 133 North Chicago, IL www.TropicalEnvironmental.com

Executive Summary

Tropical Environmental, Inc. (Tropical) was retained by the VA to provide an Asbestos Survey of all buildings, as defined by VA representatives, located on the Captain James A. Lovell Federal Health Care Center Campus in North Chicago, IL. The field assessment and sampling was performed from July 19, 2011 to October 5, 2011.

Building 133 is a brick clad, five story structure with a basement. The building was constructed in 1961 and is used for hospital and clinics. The building has approximately 384,000 square feet of floor space.

Tropical performed a visual survey of building materials and collected representative samples of homogeneous suspect ACM, in accordance with EPA requirements, guidelines and standard industry practices. The samples were submitted to a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory for bulk analysis.

This report addresses the asbestos survey completed for Building #133.

Based on the bulk sampling and laboratory analyses, suspect materials were reported to contain asbestos, including the following:

HSA

Sample #

Material Description

Material Condition

Material Quantity Material Location Laboratory

Results

BM1

EXPOSED BLACK

MASTIC

NONFRIABLE

16 SF ROOM BA131 1.1%-1.4%

CHRYSOTILE

BT1

BLACK

TAR/TAPE

50 SF ROOM 3C-100A 10%

CHRYSOTILE

CA6

GREY CARPET

ADHESIVE

2800 SF 1C-100 ROOM

GROUPING

1.2%-1.3%

CHRYSOTILE

LN4

BLUE SPLOTCHY

LINOLEUM

~350 SF

TRHOUGHOUT

EMERGENCY

ROOM AND

WEST

HALLWAYS

ASSUMED

http://www.tropicalenvironmental.com/

Building # 133 www.TropicalEnvironmental.com

HSA

Sample #

Material Description

Material Condition

Material Quantity Material Location Laboratory

Results

LN5

PURPLE

SPLOTCHY

LINOLEUM

~200 SF

EMERGENCY

ROOM WAITING

ROOM AND

WEST

HALLWAYS

ASSUMED

LN9

GREEN

SPLOTCHY

LINOLEUM

NONFRIABLE ~250 SF 2ND FLOOR NE

THROUGHOUT ASSUMED

LN11

OLIVE GREEN

W/WHITE

SPECKLES

LINOLEUM

NONFRIABLE ~25000 SF

SURGERY

HALLS, 2ND

FLOOR

THROUGHOUT

ASSUMED

LN12

YELLOW

W/BLACK

SPECKLES

LINOLEUM

NONFRIABLE ~250 SF SURGERY HALLS

THROUGHOUT ASSUMED

LN13

WHITE W/BLACK

SPECKLES

LINOLEUM

NONFRIABLE ~250 SF SURGERY HALLS

THROUGHOUT ASSUMED

Based on the bulk sampling and laboratory analyses, suspect materials were reported to contain asbestos at less than 1%, including the following:

HSA

Sample #

Material Description

Material Condition

Material Quantity

Material Location

Laboratory Results

FT1

(MASTIC)

LT. TAN

MASTIC

ASSOCIATED

WITH

12”X12” OFF

WHITE

W/BROWN

STREAK

FLOOR TILE

NONFRIABLE ~200000

SF THROUGHOUT 0.5%

CHRYSOTILE

Building # 133 www.TropicalEnvironmental.com

HSA

Sample #

Material Description

Material Condition

Material Quantity

Material Location

Laboratory Results

FT5

(MASTIC)

BLACK

MASTIC

ASSOCIATED

W/12”X12”

ORANGE

FLOOR TILE

150 SF ROOM 1A-

100G <0.25%

CHRYSOTILE

VB2

6” TAN

VINYL

BASEBOARD

NONFRIABLE 2000 LF

STAIRWAY

AND

CORRIDOR;

C1-157, C2219

AND C2222

<0.25%

CHRYSOTILE

VB8

(MASTIC)

TAN MASTIC

ASSOCIATED

WITH 4”

DARK BLUE

BASEBOARD

NONFRIABLE 150 LF ID-108 <0.25%

CHRYSOTILE

VF1

BROWN

VINYL

FLOORING

NONFRIABLE 500 SF LANDING IN

STAIRWAYS

TRACE

CHRYSOTILE

VST1

BROWN

VINYL STAIR

TREADS

NONFRIABLE 500 SF STAIRWAYS 0.25%

CHRYSOTILE

Photographs of the ACM are included in Appendix E.

Every attempt was made to thoroughly evaluate and assess the presence and condition of suspect ACM throughout the building. Any suspect ACM identified during renovation that is not specifically listed in this report should be assumed positive until it can be thoroughly evaluated, assessed, sampled, and analyzed prior to disturbance, in accordance with applicable regulatory standards.

Building # 133 www.TropicalEnvironmental.com

1.0 Introduction

Tropical Environmental, Inc. (Tropical) was retained by the VA to provide an Asbestos Survey of all buildings, as defined by VA representatives, located on the Captain James A. Lovell Federal Health Care Center Campus in North Chicago, IL. The field assessment and sampling was performed from July 19, 2011 to October 5, 2011.

This report addresses the asbestos survey completed for Building #133.

The asbestos survey was performed by Illinois Department of Public Health (IDPH) licensed asbestos inspectors Mr. Mark Haines, license #100-00919, and Ms. Terri Lewis, license #100- 07366.

1.1 Project Purpose and Background

The asbestos survey was conducted to identify accessible asbestos containing materials in the building.

1.2 Scope of Work

Tropical performed an asbestos survey to determine and quantify ACM in accessible areas. The ACM survey included the following activities:

• Visual inspection of all accessible areas of the building, as identified by VA representatives to be included in the scope of this project.

• Collection of bulk samples of identified suspect ACM per homogeneous materials in accessible areas of the building.

• NVLAP accredited laboratory analysis of suspect ACM bulk samples by polarized light microscopy (PLM) to first positive result per homogeneous material.

• Preparation of a final report that includes sample locations of representative ACM and the laboratory’s analytical report.

Building # 133 www.TropicalEnvironmental.com

2.0 Asbestos Survey

2.1 Asbestos Survey Methodology

Only currently certified and licensed inspector(s) and (if appropriate) trainee(s) were utilized for this inspection.

The inspector(s) first reviewed supplied building documents, if applicable, which may have included the asbestos management plan, previous inspection reports, blue prints, and as built drawings, etc. A property/structure(s) walk-thru was then conducted to locate, identify, measure and separate previously identified asbestos containing materials and suspect asbestos containing materials into homogeneous areas. The material’s current condition was also evaluated during the walk-thru. Material conditions were evaluated utilizing the following terminology, Good, Damaged & Significantly Damaged.

Samples were collected using EPA approved methods specifically designed for sample collection. Samples were taken utilizing the randomly distributive manner method while simultaneously applying amended water. Samples were immediately placed in a pre-labeled re-sealable plastic bag. To prevent accidental exposure, sample containers are made of a durable plastic designed to provide and airtight seal. The sampling instrument was subsequently wiped with a clean moist cloth to decontaminate the tool, prevent the potential release of asbestos fibers, and prevent cross contamination of subsequent samples. Following the collection of each sample, the sample location was patched as appropriate. Sample areas were touched to determine friability.

The following chart, as detailed by 40 CFR 763.86, is typically used (and in certain cases, required) for sampling surfacing building materials for asbestos content:

< 1000 s/f 3 samples 1000 – 5000 s/f 5 samples >5000 s/f 7 samples

9 samples are recommended by the EPA for all samples

A group letter or combination of letter and number was assigned to each homogenous material.

This combination serves as a prefix to identify materials of similar composition, texture, color, and date of installation. Each sample was then assigned a sample number such as 01, 02, 03, etc.

All samples were identified on a signed and dated Chain-of-Custody document, which accompanied the samples to the laboratory.

Building # 133

To ensure both quality and objectivity, an independent laboratory was used. Laboratories are selected based on their current accreditations. The laboratory chosen participates in the National Voluntary Laboratory Accreditation Program (NVLAP) for quality control procedures (NVLAP Lab Code: 101202-0). As specified in 40 CFR Chapter I (1-1-87 edition) Part 763, Subpart F, Appendix A.

Suspected asbestos samples were analyzed using polarized light microscopy (PLM) / dispersion staining techniques in accordance with the EPA Method documents “US EPA 600/M4-82-020, 1982” & “US EPA 600/R-93/118, 1993”. Detection limits for this type of analysis are approximately one percent (by volume). All samples were analyzed by International Asbestos Testing Laboratories of Mt. Laurel, New Jersey (IATL), a National Voluntary Laboratory Accreditation Program (NVLAP) accredited asbestos laboratory. Laboratory accreditations are provided in Appendix B.

Some materials may not be accurately identified and/or quantified by PLM. As an example, the original fabrication of vinyl floor tile routinely involved milling of asbestos fibers to extremely small sizes. As a result, these fibers may go undetected under the standard PLM method.

Transmission Electron Microscopy (TEM) is required for a more definitive analysis of these materials. These types of flooring materials that are reported by laboratory analysis to be non-asbestos by PLM analysis are routinely submitted to an accredited laboratory for analysis under TEM for verification of asbestos content. Two hundred and seventeen (217) samples were tested with TEM analysis for this building.

2.2 Asbestos Results

ASBESTOS CONTAINING MATERIALS

Suspect asbestos containing materials were identified and sampled in accordance with the above-referenced survey methodology. Laboratory results for suspect materials that were identified and sampled are included in Appendix A, entitled “Table I, Asbestos Survey Analytical Summary.”

Please reference the material location included on the drawings provided in Appendix D.

According to the AHERA Model Accreditation Plan, non-suspect material such as fiberglass, foam rubber and plastics do not warrant sampling.

2.3 Applicable Regulations

EPA's National Emission Standard for Hazardous Air Pollutants (NESHAP) (40 CFR 61, Building # 133 www.TropicalEnvironmental.com

Subpart M) categorizes asbestos-containing thermal system insulation (TSI) and sprayed-on or troweled-on asbestos as regulated ACM (RACM). Miscellaneous materials (floor tile and floor tile mastic) are classified as Category I Non-Friable Asbestos; and transite material is classified as Category II Non-Friable Asbestos, unless the material is made friable during demolition.

Friable ACM is material that can be crumbled, pulverized, or reduced to a powder by hand.

NESHAP requires at least ten working days’ notification prior to any renovation or demolition activity that will disturb greater than 160 square feet or 260 linear feet of ACM materials. ACM removed during abatement must be disposed of at a landfill approved by the EPA to receive asbestos wastes. NESHAP states that regulated asbestos-containing material (RACM), including friable ACM and non-friable ACM that has become or has a high probability of becoming friable, present in quantities exceeding 260 lineal feet on pipes or 160 square feet on facility components must be removed prior to the commencement of any demolition activities.

NESHAP also states that Category 1 non-friable ACM does not need to be removed prior to demolition if it is not in poor condition and has become friable. Friable materials (with the exception of roofing products) and transite are typically required to be removed prior to a demolition. Asbestos containing floor tile and mastic are typically required to be removed from concrete prior to recycling. Agencies such as Cook County require all asbestos containing materials be removed prior to demolition. If a facility is demolished by intentional burning, all regulated asbestos containing materials including Category I and Category II non-friable ACM must be removed before burning.

The Occupational Safety and Health Administration (OSHA) Construction Industry Standard (29 CFR 1926.1101) categorizes the removal of asbestos containing materials by “class” of material.

Specific requirements for the removal of OSHA classified materials include, but are not limited to, regulated work areas, air monitoring, engineering controls, work practices, personal protective equipment, notification and training.

The U.S. Department of Transportation (DOT) requires special procedures for packaging, labeling and transportation of asbestos wastes to disposal facilities. Other regulations may apply depending upon the contractor’s means and methods.

Tropical recommends the use of certified and licensed asbestos personnel for all planned disturbance of known and suspect asbestos containing products. In accordance with IDPH, IEPA, U.S.EPA and OSHA regulations asbestos containing materials must be removed by and disposed of by a certified/licensed asbestos abatement personnel/contractor.

Building # 133

3.0 Findings and Recommendations

Suspect materials identified, sampled and analyzed as part of this survey were reported to contain asbestos in regulated quantities.

Materials identified in this report as ACM must be handled in accordance with applicable regulations as provided herein, and must be abated if they will be impacted by any planned renovation activity.

The owner or operator of a demolition or renovation activity and prior to the commencement of the demolition or renovation shall thoroughly inspect the affected facility or part of the facility where the demolition or renovation operation will occur for the presence of asbestos, including Category I and Category II non-friable ACM.

It shall be at the owner’s discretion that a copy of this report is provided to any contractor bidding on work in the area(s) covered by this assessment. The owner may also elect to provide a copy of the report to the contractor on site during any renovation and/or demolition activities.

Contractors should use caution and be advised and directed that during renovation or demolition of a structure that concealed materials may be discovered, therefore, should suspect materials not identified in this inspection become exposed or made aware, you should cease operations that may disturb, dislodge or disrupt the material until it is sampled and analyzed for its possible asbestos content.

Although the efforts and intentions of our inspector(s) are always to sample all suspect materials, due to the nature of sampling, (destructive sampling, limited sample locations, visual assumption, etc.) some materials (such as floor tile/linoleum mastic/adhesive) may be excluded from the sampling process. These materials shall be assumed positive for asbestos unless sampled and analyzed otherwise. The client assumes and retains all responsibility and authority to conduct further sampling and analysis at their expense.

If additional suspect asbestos containing materials are identified during the renovation, those materials should be assumed to be positive for asbestos until they can be assessed, sampled, and analyzed by a NVLAP accredited laboratory.

Building # 133 www.TropicalEnvironmental.com

4.0 Limitations

The conclusions of this report are Tropical’s professional opinions, based solely upon visual site observations and interpretations of laboratory analyses, as described in this report. The opinions presented herein apply to the site conditions existing at the time of Tropical’s investigation and interpretation of current regulations pertaining to asbestos. Therefore, Tropical’s opinions and recommendations may not apply to future conditions that may exist at the site, which we have not had the opportunity to evaluate. It should be noted that conditions change and that materials constantly degrade. All applicable federal, state and local regulations should always be verified prior to any work that will disturb or dislodge materials confirmed, assumed or presumed to contain asbestos, Tropical’s assessment was limited to observation, sampling and the analysis of suspect asbestos containing products in accessible portions of the area(s) covered by this survey. Materials in the building that are not considered building materials, are unusual or de minimis, or were inaccessible, due to common construction techniques, to the inspector were excluded from the inspection. As a result, additional asbestos containing building materials may be present in inaccessible areas (e.g. between walls, ceiling spaces enclosed by wallboard, interior of fire doors, etc.) of the structure that were not observed during the survey.

This inspection report is designed to assist the client in the understanding of the regulations regarding asbestos, however, it should not be used as a substitution for obtaining and familiarizing yourself with, including the compliance of, all asbestos related regulations including, but not limited to, 40 CFR, Chapter 61, Subpart M (National Emission Standard for Asbestos) prior to the start of any renovation or demolition activity that will disturb or dislodge asbestos containing materials or suspect/assumed asbestos containing materials.

This report has been prepared for the exclusive use of the intended client, for the specific application to the defined property as addressed in this report. Any additional user of this report shall determine the suitability of the material contained herein for their intended use, and any such user assumes all risks and liability in connection therewith. No claim is made that these findings will remain applicable to future site activities and conditions. Interpretations by any such user from information contained in this report or the drawing of conclusions by any such user from information contained in this report shall be undertaken solely at the risk of said party.

At all times during the performance of the inspection, safety was a priority. Due to the emphasis on safety, there were no injuries, there was no building contamination, and there were no asbestos exposures to either Tropical Environmental, Inc personnel or building occupants.

Building # 133 www.TropicalEnvironmental.com

The asbestos survey was conducted in a manner consistent with that level of care and skill ordinarily exercised by members of the environmental profession under similar conditions. No other warranty or guarantee, express or implied, is included or intended in this Report or otherwise.

Building # 133 www.TropicalEnvironmental.com

5.0 References & Definitions

Illinois Department of Public Health (IDPH)

Asbestos Abatement Act, 105 ILCS 105

Asbestos Abatement for Public and Private Schools and Commercial and Public Buildings in Illinois, 77 Illinois Administrative Code 855

Commercial and Public Building Asbestos Abatement Act, 225 ILCS 207

United States Environmental Protection Agency (USEPA)

Asbestos Hazard Emergency Response Act (AHERA), 40 CFR, Part 763

National Emission Standards for Hazardous Air Pollutants (NESHAP), Asbestos, 40 CFR, Part 61, November 20, 1990

Guidance for Controlling Asbestos-Containing Materials in Buildings (EPA 560/5-85/024), June

Illinois Environmental Protection Agency (IEPA)

Emission Standards and Limitations for Stationary sources, Asbestos 35 IAC, Part 228

United States Occupational Safety and Health Administration (OSHA)

Occupational Exposure to Asbestos, Final Rule, 29 CFR, Pars 1910 and 1926 (August 10, 1994)

Cook County Department of Environmental Control (CCDEC)

Cook County Environmental Control Act

Asbestos Containing Products means, according to the U.S. EPA Method 600/R-93/116, Regulated Asbestos Containing Materials (RACM) are those materials found to contain greater than 1% asbestos per volume of bulk material sampled, by PLM. The term is not intended to include de minimis or inaccessible materials that do not present a risk of harm to public health and that generally would not be the subject of enforcement actions if brought to the attentions of appropriated regulatory agencies.

Building # 133

Asbestos Types are Chrysotile (white asbestos making up approximately 95% of all asbestos used in the United States), Amosite (brown asbestos making up approximately 5% of all asbestos used in the United States), Crocidolite (blue asbestos making up approximately less than 5% of all asbestos used in the United States), and rarely found in buildings are Anthophyllite, Tremolite & Actinolite.

Category I Non-friable Asbestos-Containing Material (ACM) means asbestos-containing packing, gaskets, resilient floor covering, and asphalt roofing products containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy.

Category II Non-friable ACM means any material, excluding Category I nonfriable ACM containing more than 1 percent asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

Damaged means less than 25% localized damage or less than10% distributed damage.

Demolition means the wrecking or taking out of any load-supporting structural member of a facility together with any related handling operations or the intentional burning (i.e. practice burns) of any facility.

Facility means any institutional, commercial, public, industrial, or residential structure, installation, or building (including any structure, installation, or building containing condominiums or individual dwelling units operated as a residential cooperative, but excluding residential buildings having four or fewer dwelling units); any ship; and any active or inactive waste disposal site. For purposes of this definition, any building, structure, or installation that contains a loft used as a dwelling is not considered a residential structure, installation, or building. Any structure, installation, or building that was previously subject to the Asbestos NESHAP is not excluded, regardless of its current use or function.

Friable Asbestos Material means any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 section 1, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

Homogeneous Area -- an area of surfacing materials, thermal surface insulation, or miscellaneous material that is uniform in color and texture and has the same installation date.

Miscellaneous Material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.

Multi-layered Material means a material that has a presence of discrete individual layers. EPA does not

Building # 133 www.TropicalEnvironmental.com regard a sheet of “plasterboard,” sheetrock,” “wallboard,” or “gypsum board” by itself a multi-layered material.

Polarized Light Microscopy means an optical microscopy technique for analyzing bulk samples for asbestos in which the sample is illuminated with polarized light (light which vibrates in only one plane) to distinguish between different types of asbestos fibers by their shape and unique optical properties.

Potential Significant Damage means circumstances in which:

1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.

2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.

3) The material is subject to major or continuing disturbance, due to factors including, but not limited to, accessibility or, under certain circumstances, vibration or air erosion.

Regulated Asbestos-Containing Material (RACM), as defined in 40 CFR 61.141, means

(a) Friable asbestos material,

(b) Category I non-friable ACM that has become friable,

(c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or

(d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations.

Renovation means altering a facility or one or more facility components in any way, including the stripping or removal of Regulated Asbestos Containing Materials (RACM) from a facility component. A renovation could be, but not limited to, any interior renovation or remodel not affecting load-supporting structural members or a roof replacement.

Significantly Damaged means 25% (or greater) localized damage or 10% (or greater) distributed damage.

Surfacing means any material that was sprayed-on or troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.

Thermal Systems Insulation means material applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.

Building # 133 www.TropicalEnvironmental.com

Transmission Electron Microscopy means a method of microscopic analysis, which utilizes an electron beam that is focused onto a thin sample. As the beam penetrates (transmits) through the sample, the difference densities produces an image on a fluorescent screen from which samples can be identified and counted. Also used for analyzing air samples for asbestos.

Key to Common Asbestos Related Abbreviations

ACM ........................................ Asbestos-Containing Material

ACBM ................................. Asbestos-Containing Building Material

AHERA............................. Asbestos Hazard Emergency Response Act

CFR ..........................................Code of Federal Regulations

DOT ......................................... Department of Transportation

EPA ..................................... Environmental Protection Agency

FR ................................................... Federal Register

HEPA ....................................... High Efficiency Particulate Air

HVAC ....................... Heating, Ventilating and Air Conditioning Systems

IDPH ................................... Illinois Department of Public Health

LEA ............................................. Local Education Agency

MAP ............................................ Model Accreditation Plan

NESHAP ............... National Emission Standards for Hazardous Air Pollutants

NIOSH ...................... National Institute of Occupational Safety and Health

NIST .......................... National Institute for Standards and Technology

NVLAP .................... National Voluntary Laboratory Accreditation Program

OSHA .......................... Occupational Safety and Health Administration

Building # 133 www.TropicalEnvironmental.com

PACM ................................ Presumed Asbestos Containing Material

PCM .......................................... Phase Contrast Microscopy

PLM .......................................... Polarized Light Microscopy

RACM ................................ Regulated Asbestos Containing Material

TEM .................................... Transmission Electron Microscopy

TSI .......................................... Thermal Systems Insulation

TWA ............................................. Time Weighted Average

APPENDIX A

Asbestos Survey Analytical Summary

INSPECTORS: Terri Lewis and Mark Haines

DATE: 7/27/2011

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

1 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

Corridor CB142

Corridor C1-162

Corridor C2206

Chrysotile - PC 1.4%

Chrysotile - PC 1.1%

Chrysotile - PC 1.2%

NAD

Chrysotile - 10%

Chrysotile - 10%

Room BA137

Room BA112

Room BA110A

Room BA130B

Room BA128

Room BA115

Room BA138

Room BA141A

Room BA141C

Room BA104

2 Room BA110A

3 Room BA109

X 5XX

XX

X 5

5X

X X

XX 5

X XX

X

X XX

X X X 5

NAD

50 sf

NAD

NAD

NADCarpet adhesive, blue dots carpet

Black mastic (exposed)

MM

Room 1A-104

CA4 MM NAD

CA3 MM Carpet adhesive, square carpet tiles, brown stripes carpet

Carpet adhesive, gray, green & black woven carpet

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

Room 3C-100A

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

MM Black tar/tapeBT1

BC1

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

MATERIAL TYPE Notes

FRIABILITY

CA1

Room BA131 16 sf

MM Brown caulk

BM1 MM

CA2 MM Carpet adhesive, blue squares carpet

Room BA141B

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

2 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

MATERIAL TYPE Notes

FRIABILITY

Room 1C-100 NAD

Room 1C-100J Chrysotile - PC 1.2%

Room 1C-100H Chrysotile - PC 1.3%

Room 1C-100B Chrysotile - PC 1.2%

Chrysotile - PC 1.2%

Chrysotile - PC 1.3%

Room 2A125

Room 2A158

Room 2A157

Room C4-113

X

5XX

5XX

X

X

X

X

5XX

X

5XX

X X 5X

NAD

NAD

NAD

NAD

CA11

Carpet adhesive, gray carpetCA6

CA7 MM

MM Carpet adhesive, large square pattern w/ peach & tan stripes carpet NADX X

CA10 MM Carpet adhesive, brown/tan mini square pattern carpet Room 4A-128

MM Carpet adhesive, stripes w/ flower pattern carpet

MM

CA9

CA8

Room 2A117

MM Carpet adhesive, gray w/ square pattern carpet

Carpet adhesive, blue & purple stripes carpet Room 1C-100E

5X

Room 1C-100A

X 2800 sf

CA5 MM Carpet adhesive, squiggly green & purple carpet Room 1A-100G NAD

Room C4-119

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

3 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

BB101C

Emergency room waiting room

Room 1B128D

Room 1B139

Room 1C173

Room 1A-146H

Room 3A-143

QAQC

Corridor CB132

BA101

Corridor C2219

BB101H

BB101A

BA100

BB101F Closet

QAQC

Room 1A-136A

Room 1A-136D

Room 1C-102H

X X X

XXX

X

5XXX

XX NAD

NAD

NAD5

NAD

CT4 MM Ceiling tile, 2x4 , white, smooth

MMCT2

CT3 MM Ceiling tiles, 2x4 (2x2 pattern), white

Ceiling tile, 2x2 , white Room adjacent to Room BB101F

CT1 MM Ceiling tile, 2x2 , white, fissured

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

4 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Room 2A117

Room 2A116

Room 2A117

Corridor C4-107

Corridor C4-110

Corridor C4-117

Room BA119A

White joint compound

Drywall

White joint compound

Drywall

White joint compound

Drywall

White joint compound

Drywall

White joint compound

Drywall

White joint compound

Closet adjacent to Corridor CB-144

Room 1A-119

Room 2A-127

XX

XXX

X X X 5

X XX

NAD

Drywall

NAD

Room 1B131

Room 2A127

2 Closet adjacent to Corridor CB-144

Room BC106

Room 1C-101

Room 1A-119

NAD

NAD

CT6 MM Ceiling tile, 2x2, white, holes

CT5 MM Ceiling tile, 2x2, white, smooth

FS1 MM Fire stopping caulk, red

DW1 MM

Corridor C4-124

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

5 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Room 2B118

Lt. tan mastic Chrysotile - Trace Detected @ 0.50% - Per TEM report

Corridor C2219

Corridor C3-136

Corridor C3-130

Floor tile,12x12, blue w/ grey streaks

Black mastic

Floor tile,12x12, blue w/ grey streaks

Black mastic

Floor tile,12x12, blue w/ grey streaks

Black mastic

Floor tile,12x12, blue w/ grey streaks

Black mastic

Floor tile,12x12, blue w/ grey streaks

Black mastic

Floor tile,12x12, blue w/ grey streaks

Tan/grey mastic/leveling compound

Floor tile,12x12, blue w/ grey streaks

Tan/grey mastic/leveling compound

Floor tile, 12x12 , off white w/ brown streaks

Floor tile, 12x12 , off white w/ brown streaks

4 Room 2B122

NAD

NAD

5X

FT2 MM

FT1 200000 sf

Coffee shop office

5XX

Corridor CB138

MM

NAD

Room adjacent to Room BA115

Corridor CB133

Room across from elevators in Corridor CB132

Coffee shop

Outside Room BA137A

X

X

South stairwell @ BA109

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

6 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Room BA103

Room BA102B

Room BA101

Room BA102A

Room BA102A

Black mastic

Floor tile, 12x12, orange splotchy

Black mastic

Floor tile, 12x12, orange splotchy

Black mastic Chrysotile - Trace Detected @ <0.25%; Per TEM report

Floor tile, 12x12, orange splotchy

Black mastic

X XX

X 5XX

Floor tile, 12x12, tan w/ splotches

NAD

NAD

NAD

150 sf

XX

FT5 MM

NAD

NAD

FT4 MM Corridor C1-159

Floor tile, 12x12, tanFT3

Interior window caulk

Room 1A-100G

IWC MM

MM

X 5

Interior windows

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

7 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Linoleum, 2.5x2.5, light blue, pebble pattern

Tan mastic

Linoleum, 2.5x2.5, light blue, pebble pattern

Tan mastic

Linoleum, 2.5x2.5, light blue, pebble pattern

Tan mastic

Linoleum, gray splotchy

Tan mastic

Grey leveling compound

Linoleum, gray splotchy

Tan mastic

Grey leveling compound

Linoleum, gray splotchy

Tan mastic

Grey leveling compound

X

NAD

Room 1C177

NAD

NAD

~350 sf assumed positive; no samples collected of seemless floorAssumedX 5LN4 MM Linoleum, blue splotchy N/A Emergency room waiting room, Halls west of room X

LN2 MM

LN3 MM

5XXX

X

Linoleum, tan splotchy Room 1A-116

LN1 MM Room BB101H

Room 1C173

Room 1C171

2 X 5XX

5XX

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

8 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Linoleum, 2x2, blue, layin

Tan mastic

Linoleum, 2x2, blue, layin

Tan mastic

Room 1A-136A

Tan mastic

Linoleum, 2x2, blue, layin

Tan mastic

Linoleum, white w/ grey speckles

Yellow mastic

White caulk

Linoleum, white w/ grey speckles

Yellow mastic

Linoleum, white w/ grey speckles

Yellow mastic

White caulk

NAD

Room 1A-136

Room 1A-136E

Linoleum, 2x2, blue, layin

NAD

2 Room 2A149

Room 3A-118

Emergency room waiting room, Halls west of room X ~200 sfXMM Linoleum, purple splotchy N/A assumed positive; no samples collected of seemless floorX 5 Assumed

X

LN6

XMM

LN5

LN7

Room 1A-136I

Room 1A-136L

Room 1A-136J

MM

X

5XXX

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

9 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Linoleum, orange splotchy

Lt. tan/grey mastic/leveling compound

Linoleum, orange splotchy

Lt. tan/grey mastic/leveling compound

Linoleum, orange splotchy

Lt. tan/grey mastic/leveling compound

X

1 Lobby adjacent to Room 2A120

2 Room 2A120

Room 2A124

X

5 Assumed

5 Assumed

NAD5

~25000 sfXLN11 MM Linoleum - olive green with white speckles N/A

LN10 MM

LN9 MM Linoleum, green splotchy

Surgery Halls- 2C-111, 22-110

N/A 2nd Floor NE (pattern)

X assumed positive; no samples collected of seemless floor

~250 sf assumed positive; no samples collected of seemless floor

X

X

XX

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

10 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Cannot verify presence

Material possibly behind walls and above ceilings. 110 l/f of insulation/ fittings abated in 2nd floor recovery area in 2005.

PF1 TSI Pipe fitting insulation NA Unable to quantify assumed positive; no samples collected of seemless floor

Assumed5

LN13 MM Linoleum white with black speckles N/A XXSurgery Halls- border 2C-108 X 5 ASSUMED

Surgery Halls- center of square patterns XLN12 MM Linoleum yellow with black speckles N/A

~250 sf

~250 sf assumed positive; no samples collected of seemless floorX X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

11 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

White plaster

Brown plaster

White plaster

Brown plaster

White plaster

Brown plaster

White plaster

Brown plaster

White plaster

Brown plaster

White plaster

Brown plaster

White plaster

Brown plaster

X

5X

Room 1A-119

Corridor C1-159

7 Room 2B118

XRoom 1A-133

Room BA115

Cannot verify presence Material possibly behind walls and above ceilings. PI1 TSI Pipe fitting Insulation N/A

Room adjacent to Room BA120

Unable to quantify

Room BA131

NADMMPL1

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

12 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Room BB101

Room BB101A

Room BB101C

QAQC

Building has an addition built in

5XXX

XX

2XXX

NAD

NAD

NAD

Boiler Room

UE1

Spray applied fireproofing

Unexcavated earth

VB1

Crawlspace under pipe (basement)MM

SF1 MM

MM Vinyl baseboard, 4", light brown 5X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

13 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

B Ward halls Chrysotile - Trace Detected @ <0.25%; Per TEM report

Stairway adjacent to Corridor C1-157

3A halls

Tan mastic

Vinyl baseboard, 6", tan

Tan mastic

Vinyl baseboard, 6", tan

Tan mastic

Room BA109B

Room BA110A

Room BA128

Vinyl baseboard, 4", tan

Tan mastic

Corridor CB134

Corridor CB133

Corridor CB138

X

5XXX

NAD

NAD

NAD

Room 3B-109

NAD5XX

Corridor C2219

Stairway adjacent to Room BA109

Vinyl baseboard, 4", tan

MM

Corridor C2222

Corridor CB135

Vinyl baseboard, 6", tan

VB4

MMVB5 5XXX

VB3

VB2 MM 2000 lf

MM Vinyl baseboard, 4", dark gray

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

14 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

Corridor CB139

Corridor 1C167

Corridor 1C171

Room 1C-100J

Room 1C-102C

Vinyl baseboard, 4", dark blue NAD

Tan mastic Chrysotile - Trace Detected @ <0.25%; Per TEM report

Off-white joint compound

Vinyl baseboard, 4", white

Tan mastic

Vinyl baseboard, 4", white

Tan mastic

Vinyl baseboard, 4", white

Tan mastic

NAD

150 lf

XX

X X X 5

5XXX

X X

XXX

NAD

Room 1A-100G 5

Room 1A-100D

NAD

NAD

NAD

NAD

NAD

Room C1-173

ID-108

MM

VB6 MM Vinyl baseboard, 6", gray

Vinyl baseboard, 4", brown

Vinyl baseboard, 4", dark blue

VB9

VB10 MM Vinyl baseboard,6", light green

VB11

VB7 MM

VB8 MM

Room BA106

MM Vinyl baseboard, 6", dark brown Stairway across from elevators adjacent to Corridor CB132

5XX X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 133

15 OF 17 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

ACCESS

ASSESSMENT

CATEGORY QuantityASBESTOS RESULTSHSA ID

CONDITION

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

This is the start of the file's text. The full file is on GovTribe.