S02. RFI 003 PA_Response.pdf
PDF 168 KB Posted
- Attached to
- Y1DA--RENOVATE RADIATION THERAPY Federal contract opportunity
- Solicitation number
- 36C25021B0003_1Amend1
About this file
This document contains responses to a Request for Information related to a federal contract opportunity to renovate the radiation therapy department at a Department of Veterans Affairs medical center. The solicitation seeks clarification on the height from floor to underside of an existing deck for stud length and confirmation that sheet A-601 of the drawings correctly reflects no 2-hour rated partitions. The response provides the height as approximately 14 feet and directs the requester to life safety plan G-102 for the locations of rated partitions.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06. 36C25021B0003 0001.pdf | ||
| S02. RFI 001_Response.pdf | ||
| S02. RFI 001 (VA Rad Therapy Sebesta Report) 2020-02-22.pdf | ||
| S02. RFI 001 (Asbestos Survey)_Response.pdf | ||
| S02. RFI 004 (Privacy Curtain Track)_Response.pdf | ||
| S02. RFI 002_Response.pdf | ||
| S02. RFI 002 (Corridor Off Hours Work)_Response.pdf | ||
| S02. RFI 005 (Substitution Request - Koroseal Wall Protection)_Response.pdf | ||
| S02. Encl 1-2 ICRAMatrixofPrecautions.pdf | ||
| S02. RFI 003 (Rubber Tile Banding)_Response.pdf | ||
| S02. RFI 004_Response.pdf | ||
| S02. RFI 005_Response.pdf | ||
| S02. RFI 006 (Cornert Guards Not Shown)_Response.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
TO: Stanley Burdine, Contracting Specialist
RFI NO.: 003 DATE: 4/21/2021 REFERENCE:
REPLY NEEDED BY:
INFORMATION NEEDED:
* What is the approx. height from floor to underside of existing deck for stud length?
* Wall types on sheet A-601 do not reflect any 2 hour rated partitions. Confirm that this is correct as fire alarm information references 2 hour partition.
REPLY:
REPLY FROM: DATE:
ATTACHMENTS: COPY TO:
PROJECT NUMBER: 541-20-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the
Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: Renovate Radiation Therapy
PROJECT LOCATION: Department of Veterans Affairs
VA Medical center
SUBMITTED BY: Philip S. Ozan / Firewatch Contracting City/State: Cleveland, Ohio
PHONE NO.: 216-644-7316 cell
Height from floor to underside of existing first floor deck is approximately 14 feet.
See Life Safety Plan G-102 for rated partitions.
Tim Huffman 4/23/21