S02 Attachment-Final Drawings 37PGS - Copy (1).pdf

PDF 12 MB Posted

Attached to
Z2DA--589A7-25-503 Prepare Site for Cath Lab Equipment FY26 NRM
Solicitation number
36C25526R0142_1
Issued by

About this file

Contract Document Summary

These are 100% Contract Documents for Bidding consisting of 37 sheets of architectural, mechanical, electrical, and plumbing construction drawings for the "Prepare Site for Cath Lab Equipment" project at Robert J. Dole VA Medical Center in Wichita, Kansas. The project (VA Project Number 589A7-25-503, Building 2) involves demolition and renovation of approximately 1,938 square feet on the second floor to prepare existing space for installation of new cardiac catheterization laboratory equipment.

Key Project Requirements and Scope: The general contractor must perform Class IV Infection Control and Risk Assessment (ICRA) work, including installation of negative pressure barriers, HEPA filtration, and dust control systems during all demolition and construction activities. Demolition includes removal of existing walls, doors, frames, casework, mechanical systems, and finishes in specified areas. New work encompasses installation of new partitions, doors, flooring, ceiling systems, wall finishes, medical gas piping, HVAC ductwork, electrical circuits, and Philips imaging equipment support infrastructure. The project must maintain two-phase phasing to allow continued operation of adjacent clinical areas. Lead-lined gypsum board removal and installation is required due to existing radiation shielding. All work must comply with 2024 NFPA 101 Life Safety Code, 2021 IBC standards, VA design standards, and ADA accessibility requirements. Work must be performed under negative pressure with weekly environmental monitoring, daily cleaning protocols, and coordination with VA infection control and safety personnel. The facility remains fully operational during construction with restricted access through designated contractor entrances and specific traffic routes. Vendor equipment drawings from Philips are incorporated by reference for equipment base plate installation and infrastructure coordination.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3 4 5 6

7 8 10

A

B

C

D

E

F

4 5 6 7 8 10

C

D

E

F

8'-0"

8'-0"

8'-0"

8'-0" 8'-0"

8'-0"

8'-0"

10'-2"

CONF

OFFICE

OFFICE

OFFICE

SERVING

D1

D1

D1

D1

D1

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE CONSTRUCTION

DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL CONSTRUCTION

DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE SAVAHCS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW CONSTRUCTION.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED BY HIS

WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN FLOOR TO

CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO EXISTING

CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN "NOT IN SCOPE" AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER.

9. REFER TO GI-100 FOR ICRA CONSTRUCTION DETAILS AND ADDITIONAL ICRA INFORMATION.

10. REFER TO PHASING PLANS FOR ICRA BARRIER LOCATIONS.

GENERAL DEMOLITION NOTES

EXISTING DOOR & FRAME TO BE

DEMOLISHED IN ITS ENTIRETY

DEMOLITION FLOOR PLAN LEGEND

EXISTING WALL TO BE

DEMOLISHED IN ITS ENTIRETY

EXISTING DOOR & FRAME TO

REMAIN, PROTECT.

EXISTING CASEWORK TO BE

DEMOLISHED

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

AREA WITH LIMITED SCOPE

OF WORK

NOTE: ALL SYMBOLS MAY NOT BE USED

EXISTING LIGHT FIXTURES TO BE

DEMOLISHED

EXISTING MECHANICAL

DEVICES TO BE DEMOLISHED

EXISTING MECHANICAL

DEVICES TO BE DEMOLISHED

3 4 5 6 7 8 10

C

D

E

F

SERVING

CONF

OFFICE

OFFICE

OFFICE

D11

D12

D12

D11

D11

D11 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:4 :3

P

M

AD-100

DEMOLITION PLANS- FIRST FLOOR

JDA

6 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 3/16" = 1'-0"

LEVEL 1 - DEMO RCP

Scale: 1" = 40'-0"

KEY PLAN

DEMOLITION KEYNOTES

D1 REMOVE EXISTING CEILING TILES FOR ACCESS TO COMPLETE SCOPE OF WORK ABOVE FIRST FLOOR CEILING AND BELOW SECOND FLOOR SLAB. REPLACE ALL HOLD DOWN CLIPS THAT ARE DAMAGED IN

THE REMOVAL OF CEILING TILES. TYPICAL.

D2 REMOVE EXISTING EQUIPMENT, SERVICES, ETC.REMOVE SECTION OF FLOORING

D3 EXISTING PARTITION TO BE PARTLY REMOVED AS INDICATED.

D4 EXISTING MED GAS OUTLETS UNDER FLOOR TO BE DEMOLISHED. COORIDNATE WITH MEG GAS

DRAWINGS

D5 REMOVE EXISTING SHEET GOODS / WELDED SEAM FLOORING TO EXTENTS SHOWN. REMOVE TO

BARE SUBSTRATE. PREP FOR NEW SHEET GOODS WITH WELDED SEAM.

D6 EXISTING PANEL TO BE DEMOLISHED. REFER TO ELECTRICAL DRAWINGS

D7 REMOVE MODULAR CASEWORK. EXISTING RACEWAY TO REMAIN

D8 REMOVE EXISTING POCKET DOOR, PREP FOR NEW SWING DOOR

D9 REMOVE ALL CEILING MOUNTED DEVICES AND GYPSUM BOARD FOR NEW EQUIPMENT PREP

D11 AREA EFFECTED BY ABOVE CEILING WORK AND ACCESS TO MED GAS. SEE MEG GAS FOR

ADDITIONAL INFORMATION

D12 NEW ISO CENTER LOCATION ABOVE, FOR REFERENCE

D13 EXISTING SPEAKER TO BE RELOCATED. SEE NEW WORK RCP FOR ADDITIONAL INFORMATION

D14 REMOVE EXISTING DOOR AND FRAME IN IT ENTIRETY, SALVAGE HARDWARE FOR REINSTALLATION

D15 REMOVE EXISTING LAYER OF NON LEAD LINED GYSPUM BOARD. PREP FOR NEW LEAD LINED

GYSPUM BOARD

Scale: 1/4" = 1'-0"

LEVEL 1 - EXISTING FLOOR PLAN - CULINARY SERVICES

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

R E AF YI EN RN SEJ

03/17/26

3 4 5 6

7 8 10

A

B

C

D

E

F

3 4 5 6 7 8 10

C

D

E

F

CORRIDOR

C-2-3

CATH LAB 1

218-2

CLEAN UTILITY

217A-2

PT TOILET

211-2

CATH LAB 2

216-2

HK

210-2

ELEC

201-2

WAITING

200-2

CORRIDOR

C-2-1

STERILE SUPPLIES

215-2

CONTROL ROOM

217-2

EQUIPMENT ROOM

216A-2

D2

D7

D3 D3

1'-10 5/8" 11'-7 5/8" 1'-10"

D4

D5

D6 D6

D2

2'-8 3/4" 11'-10" 1'-8 7/8"

D4

D5

D7

D7

D7

D8

UTILITY

204A-2

UPS/COMP

203A-2

CONTROL

203-2

COM

202-2

UPS/BATTERY

209A-2

WORK

209-2

RECOVERY

212-2

HOLDING/PREP

214-2

CORRIDOR

207A-26

'-6

'-0

'-0

/4

'-0

D14D14

D15

D15

D15

D15

MENS TOILET

207A-2

WOMENS TOILET

208A-2

WOMENS LOCKER

208-2

MENS LOCKER

207-2

CORRIDOR

207A-26

NURSE OFFICE

205-2

PHYSICIANS OFFICE

206-2

3 4 5 6 7 8 10

C

D

E

F

8'-5"

9'-0"

9'-0"

9'-0"

9'-0"

8'-5"

9'-0"

9'-0"

9'-0"

9'-0"

7'-6"

7'-6"

CLEAN UTILITY

217A-2

MENS LOCKER

207-2

CORRIDOR

C-2-3

WAITING

200-2

ELEC

201-2

HK

210-2

CORRIDOR

C-2-1

PT TOILET

211-2

CATH LAB 1

218-2

EQUIPMENT ROOM

216A-2

CATH LAB 2

216-2

STERILE SUPPLIES

215-2

UPS/COMP

203A-2

UTILITY

204A-2

WORK

209-2

UPS/BATTERY

209A-2

WOMENS TOILET

208A-2

WOMENS LOCKER

208-2

NURSE OFFICE

205-2

CONTROL

203-2

RECOVERY

212-2

D9 D9

D13

D11

PHYSICIANS OFFICE

206-2

MENS TOILET

207A-2

COM

202-2

D13

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE CONSTRUCTION

DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL CONSTRUCTION

DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE SAVAHCS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW CONSTRUCTION.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED BY HIS

WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN EXISTING

SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN FLOOR TO

CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO EXISTING

CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE

PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN "NOT IN SCOPE" AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT

NEED TO BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER.

9. REFER TO GI-100 FOR ICRA CONSTRUCTION DETAILS AND ADDITIONAL ICRA INFORMATION.

10. REFER TO PHASING PLANS FOR ICRA BARRIER LOCATIONS.

GENERAL DEMOLITION NOTES

EXISTING DOOR & FRAME TO BE

DEMOLISHED IN ITS ENTIRETY

DEMOLITION FLOOR PLAN LEGEND

EXISTING WALL TO BE

DEMOLISHED IN ITS ENTIRETY

EXISTING DOOR & FRAME TO

REMAIN, PROTECT.

EXISTING CASEWORK TO BE

DEMOLISHED

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

AREA WITH LIMITED SCOPE

OF WORK

NOTE: ALL SYMBOLS MAY NOT BE USED

EXISTING LIGHT FIXTURES TO BE

DEMOLISHED

EXISTING MECHANICAL

DEVICES TO BE DEMOLISHED

EXISTING MECHANICAL

DEVICES TO BE DEMOLISHED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/7

/2

:2

:5

A

M

AD-101

DEMOLITION PLANS - SECOND FLOOR

JDA

7 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/4" = 1'-0"

SECOND FLOOR - DEMOLITION PLAN

Scale: 3/16" = 1'-0"

SECOND FLOOR - DEMO RCP

1" = 40'-0"

KEY PLAN

DEMOLITION KEYNOTES

D1 REMOVE EXISTING CEILING TILES FOR ACCESS TO COMPLETE SCOPE OF WORK ABOVE FIRST FLOOR

CEILING AND BELOW SECOND FLOOR SLAB. REPLACE ALL HOLD DOWN CLIPS THAT ARE DAMAGED IN

THE REMOVAL OF CEILING TILES. TYPICAL.

D2 REMOVE EXISTING EQUIPMENT, SERVICES, ETC.REMOVE SECTION OF FLOORING

D3 EXISTING PARTITION TO BE PARTLY REMOVED AS INDICATED.

D4 EXISTING MED GAS OUTLETS UNDER FLOOR TO BE DEMOLISHED. COORIDNATE WITH MEG GAS

DRAWINGS

D5 REMOVE EXISTING SHEET GOODS / WELDED SEAM FLOORING TO EXTENTS SHOWN. REMOVE TO

BARE SUBSTRATE. PREP FOR NEW SHEET GOODS WITH WELDED SEAM.

D6 EXISTING PANEL TO BE DEMOLISHED. REFER TO ELECTRICAL DRAWINGS

D7 REMOVE MODULAR CASEWORK. EXISTING RACEWAY TO REMAIN

D8 REMOVE EXISTING POCKET DOOR, PREP FOR NEW SWING DOOR

D9 REMOVE ALL CEILING MOUNTED DEVICES AND GYPSUM BOARD FOR NEW EQUIPMENT PREP

D11 AREA EFFECTED BY ABOVE CEILING WORK AND ACCESS TO MED GAS. SEE MEG GAS FOR

ADDITIONAL INFORMATION

D12 NEW ISO CENTER LOCATION ABOVE, FOR REFERENCE

D13 EXISTING SPEAKER TO BE REMOVED.

D14 REMOVE EXISTING DOOR AND FRAME IN IT ENTIRETY, SALVAGE HARDWARE FOR REINSTALLATION

D15 REMOVE EXISTING LAYER OF NON LEAD LINED GYSPUM BOARD. PREP FOR NEW LEAD LINED

GYSPUM BOARD

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

3 4 5 6

7 8 10

A

B

C

D

E

F

UP

4 5 6

7 8 10

C

D

E

F

210 SF

HOLDING/PREP

214-2

305 SF

CORRIDOR

C-2-3

95 SF

STERILE SUPPLIES

215-2

410 SF

CATH LAB 2

216-2

68 SF

CLEAN UTILITY

217A-2

432 SF

CATH LAB 1

218-2

91 SF

CORRIDOR

C-2-1

100 SF

STAIR

211-3

99 SF

EQUIPMENT ROOM

216A-2

203 SF

CONTROL ROOM

217-2

PER VA SURGICAL AND ENDOVASCULAR SERVICES

DESIGN GUIDE APRIL 2016 (rev 08/23) Absolute Minimum for Existing Facilities*: 810 net square feet (75.25 net square meters) (24’-0” x 33’-9”), 24’-0” min dimension

PER VA SURGICAL AND ENDOVASCULAR SERVICES

DESIGN GUIDE APRIL 2016 (rev 08/23) Absolute Minimum for Existing Facilities*: 810 net square feet (75.25 net square meters) (24’-0” x 33’-9”), 24’-0” min dimension

* Note: The Philips Flexmove FD 20 Imaging Modality requires a minimum 28’-8“ surgical procedure room width so as to provide sufficient room for the circulator to pass by when the C-Arm is positioned perpendicular to the procedure table.

PER VA SURGICAL AND ENDOVASCULAR SERVICES

DESIGN GUIDE APRIL 2016 (rev 08/23) 220 net square feet preferred, 150 NSF minimum

PER VA SURGICAL AND ENDOVASCULAR SERVICES

DESIGN GUIDE APRIL 2016 (rev 08/23) Equipment Room: Minimum 150 net square feet and accessible from the Control Room or the restricted corridor and not accessible from the procedure room

17'-5 5/8"

'-2

/8

16'-3 5/8"

'-2

/8

LOW

RETURN

LOW

RETURN

LOW

RETURN

LOW

RETURN

C1

C1

C1

1. INFORMATION PROVIDED TO BE REVIEWED AND ACCEPTED PRIOR TO RELEASE ON 100% CONSTRUCTION DOCUMENTS.

A. UNABLE TO MEET MINIMUM ROOM REQUIREMENTS PER VA SURGICAL AND ENDOVASCULAR SERVICES DESIGN GUIDE APRIL 2016 (rev 08/23) FOR MINIMUM ROOM SIZE AS SCOPED AND BUDGETED.

B. UNABLE TO MEET MINIMUM LOWER RETURNS PER VA SURGICAL AND ENDOVASCULAR SERVICES DESIGN GUIDE APRIL 2016 (rev 08/23). WAIVER REQUIRED.

C. UNABLE TO ACCESS COMPONENT (EQUIPMENT ROOM) FROM AREA OTHER THAN PROCEDURE ROOM PER VA SURGICAL AND ENDOVASCULAR SERVICES DESIGN GUIDE APRIL 2016 (rev 08/23)

D. UNABLE TO MEET THE REQUIRED MINIMUM OF 4'-0" AROUND ALL PATIENT ACCESS PER FGI 2018 WITHIN THE EXISTING

CONDITIONS.

E. FULL EQUIPMENT RANGE OF MOTION CANNOT BE ACHIVED WITH CURRENT EXISTING CONDITIONS.

GENERAL REFERENCE NOTES / COMPLIANCE

Scale: 1" = 40'-0"

KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:4 :4

P

M

AE-100

REFERENCE AND COMPLIANCE PLAN

JDA

8 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/4" = 1'-0"

LEVEL 2 - REFERENCE PLAN

Scale: 12" = 1'-0"

PHYSICIST REPORT - FOR REFERENCE

COMPLIANCE KEYNOTES

C1 GC TO CORE DRILL AND VERIFY LEAD THICKNESS OF EXISTING WALLS. MINIMUM REQUIRED IS 1/16"

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

UP

3 4 5 6

7 8 10

A

B

C

D

E

F

3 4 5 6

7 8 10

A

B

C

D

E

F

WORK

209-2

UPS/BATTERY

209A-2

HK

210-2 PT TOILET

211-2

RECOVERY

212-2

HOLDING/PREP

214-2

MECHAINCIAL

ACCESS

213-2

CORRIDOR

C-2-3

STERILE SUPPLIES

215-2

CATH LAB 2

216-2

PT TOILET

211-2

CLEAN UTILITY

217A-2CATH LAB 1

218-2

WAITING

200-2

UPS/COMP

203A-2

UTILITY

204A-2

CORRIDOR

C-2-1

HK

210-2

CONTROL

203-2

ELEC

201-2

STAIR

211-3

9'-8 1/8"

/2

9'-9 5/8" 7'-8"

9' -8

/8

4'

-9

EXISTING ROOF

A1

A1

A2

1' -3

/4

1' -3

/4

A2

217A-2

EQUIPMENT ROOM

216A-2

CONTROL ROOM

217-2

CORRIDOR

207A-26

COM

202-2

A3

A3

A4

A4

A4

A4

A4 A4 A4 A4 A4

A4

A4

A4

A4 A4

A5

A6

A6

A8

A9

1'-6" 1'-6"

3'-0"

1' -2

4'

-2

R

'-9

AE-104

4 2

A10

AE-104

AE-104

A7A7 5'-9" 5'-9"

3' -8

/8

A11

2' -8

2'-6"

R 5'-1 0"

R 2 '-6

A9

EXISTING ROOF

217A-2A 217A-2B

A12A12

A12

A12

FLOOR PLAN LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

NEW DOOR & FRAME IN

EXISTING WALL

NEW WALLS

EXISTING DOOR & FRAME TO

REMAIN, PROTECT.

NEW CASEWORK

EXISTING WALLS TO REMAIN

AREA NOT IN CONTRACT

EXISTING WINDOWS TO

REMAIN

DESCRIPTIVE PLAN NOTE

UNDERSIDE STRUCTURE

1 LAYER 5/8" TYPE X 1/16" LEAD

LINED GYPSUM BOARD ON 3 5/8"

METAL STUDS @ 16" O.C. W/

CONTINUOUS TOP AND BOTTOM

RUNNERS.

WALL TYPE A3

FULL HEIGHT WALL - NON-RATED

CONTINOUS SEALANT FIRE TOP

BOTH SIDES

CONTINOUS FIRE STOP SEALANT

4 1/4"ACTUAL

1. NOT ALL PARTITION TYPES SHOWN HERE MAY BE USED. REFER TO PLANS FOR LOCATION AND TYPES

OF EACH PARTITION.

2. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES OF ALL FIRE AND

SMOKE WALLS DESIGNATING THE PARTITION RATING INDICATED ON THE LIFE SAFETY PLAN.

3. REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF ALL WALL TILE.

PROVIDE AND INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GYPSUM WALL BOARD AT ALL SCHEDULED TILE LOCATIONS. UNLESS NOTED OTHERWISE, TILE SHALL BE INSTALLED PER TILE COUNCIL OF AMERICA LATEST STANDARDS FOR EACH TYPE OF BACKING MATERIAL REPRESENTED IN

WALL/PARTITION.

4. ALL SUSPENDED WALLS AND PARTITIONS SHALL HAVE GYPSUM WALL BOARD THAT EXTENDS A MINIMUM OF 6" ABOVE THE SUSPENDED CEILING UNLESS SHOWN AND/OR NOTED OTHERWISE BY THE

ARCHITECT.

5. REFER TO STRUCTURAL DRAWINGS FOR ALL LOAD BEARING WALL CONDITIONS IN REGARDS TO

STRUCTURAL REQUIREMENTS.

6. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, I.E. WALLS, JAMBS, ETC. SHALL ALIGN

ACROSS VOIDS AND JOINTS.

7. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS NOTED

OTHERWISE) WHERE DRYWALL CONTINUES ABOVE CEILING AND ABOVE THE CEILING LEVEL UP TO

THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL HAVE CORNER BEADS MINIMUM

FLOOR TO CEILING. ALL PENETRATIONS IN DRYWALL CONSTRUCTION ABOVE FINISHED CEILING SHALL BE EFFECTIVELY SEALED TO PREVENT SOUND LEAKAGE AND FIRE STOPPING TAPE/CAULK AT ALL

RATED PARTITIONS.

8. ALL MECHANICAL CHASES AND OTHER NOTED CHASES ARE TO EXTEND UP TO THE UNDERSIDE OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS OTHERWISE NOTED, SHALL EXTEND

ABOVE THE HIGHEST ADJOINING CEILING AND BE BRACED TO STRUCTURE.

9. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL BE SUPPORTED

BY STRUCTURAL COMPONETS.

10. COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF BLOCKING IN WALLS/PARTITIONS. ALL

WOOD BLOCKING IS TO BE FIRE RETARDANT TREATED.

11. IMPACT RESISTANT GWB, WHERE NOTED, IS OPTIONAL ABOVE 8' AFF AND BEHIND LOCKERS.

12. SEAL THE TOP AND BOTTOM OF WALL AS WELL AS ALL PENETRATIONS WHERE SMOKE PARTITIONS

ARE DESIGNATED ON THE LIFE SAFETY PLAN TO ELIMINATE THE PASSAGE OF SMOKE.

13. USE DEFLECTION TRACKS WHERE STUD WALLS ATTACH DIRECTLY TO METAL DECK

GENERAL PARTITION NOTES:

GYPSUM WALL BOARD

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

HOLLOW METAL

DOOR AND FRAME

@STANDARD DOOR HEAD

JAMB (SIM)

METAL STUD

SEALANT, COLOR TO

MATCH ADJACENT WALL

LEAD LINES HOLLOW

METAL DOOR AND/OR

FRAME

LEAD LINED GYSPUM

WALL BOARD

@ LEAD LINED DOOR

HEAD

JAMB (SIM)

L-1 M-1

HARDWARE SET: DOOR 217 A-2

HW-1 - DOOR 217 A-2

3 HINGES A8112 4.5" X 4.5" 652

1 LOCKSET F07 45H-7D15H PATD 630AM

1 CLOSER C02211 689

1 KICK PLATE J102 10"X2" LDW B4E CS 630

1 WALL BUMPER L02101 630

1 GASKETING R0Y154

HW-2 - DOORS 217A-2A/2B

1 CONTINUOUS HINGE

REAMIANING EXISTING HARDWARE TO BE SALVAGED AND REUSED

A. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL (MEP) DRAWINGS AND SPECIFICATIONS FOR DELINEATION OF ASSEMBLIES AND SYSTEMS TO BE PROVIDED WITHIN THEIR RESPECTIVE PORTIONS

OF THE WORK.

B. CONTRACTOR SHALL COORDINATE DEMOLITION WORK WITH ALL TRADES, FOR ITEMS SHOWN TO BE REMOVED ON THE DEMOLITION PLANS AS WELL AS NEW WORK PLANS FOR OTHER TRADES IN THIS

SET. GENERAL CONTRACTOR SHALL ALSO COORDINATE WITH ALL TRADES, THE REMOVAL

REINSTALLATION, AND/OR REWORKING OF THE EXISTING FINISHES AND EQUIPMENT AND FIXTURES

AS REQUIRED FOR THE ROUTING OF EXISTING/NEW SERVICES INTO THE PROJECT AREA.

C. CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES AND EQUIPMENT SUPPLIERS INVOLVED

WITH AND WORKING ON THE PROJECT.

D. CONTRACTOR TO VERIFY THE EXISTING SITE CONDITIONS AND IMMEDIATELY NOTIFY THE COR OF ANY DISCREPANCY BETWEEN EXISTING CONDITIONS SHOWN AND CONFIGURATIONS SHOWN BY THE

CONSTRUCTION DOCUMENTS.

E. CONTRACTOR SHALL THOROUGHLY CLEAN ALL WORK AREAS BEFORE TURNING OVER TO VAMC.

F. CONTRACTOR SHALL PATCH AND REPAIR EXISTING CONCRETE SLAB THROUGHOUT SCOPE AREA.

PROVIDE SELF LEVELING AS REQUIRED. INFILL ALL ABANDONED WALL AND FLOOR PENETRATIONS.

G. CONTRACTOR SHALL EMPLOY ONLY THOSE TRADE CONTRACTORS WITH SUFFICIENT EXPERIENCE IN THE PERFORMANCE OF WORK WITHIN A HOSPITAL ENVIRONMENT. VAMC RESERVES THE RIGHT TO REQUEST REMOVAL OF ANY PARTICULAR TRADE CONTRACTOR IF THEIR WORK OR BEHAVIOR AT THE FACILITY PUTS AT RISK THE PROJECT’S TIMELY COMPLETION, QUALITY OF THE WORK, OR THE

SAFETY OF THEMSELVES, PERSONS WORKING AROUND THEM OR VAMC EMPLOYEES, PATIENTS OR

VISITORS.

H. PRIOR TO BIDDING ON THE WORK, THE CONTRACTOR SHALL VISIT THE FACILITY TO THOROUGHLY FAMILIARIZE THEMSELVES WITH THE SCOPE OF WORK, THE EXISTING CONDITION OF THE SITE AND THE LOGISTICS REQUIRED IN PERFORMING THE WORK WITHIN A FULLY OPERATIONAL HEALTHCARE

FACILITY.

I. PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL WALK THE SPACE WITH THE COR TO

IDENTIFY ANY ITEMS TO BE REMOVED BY THE GC AND TURNED OVER TO THE GOVERNMENT.

J. REMOVE AND STORE ALL EXISTING EQUIPMENT AS REQUIRED FOR NEW CONSTRUCTION.

COORDINATE TEMPORARY STORAGE LOCATION WITH VAMC.

K. CONTRACTOR TO AVOID DISRUPTION OF EXISTING HOSPITAL SERVICES AT ALL TIMES.

L. CONTRACTOR MUST COORDINATE IN ADVANCE ANY OPERATIONS THAT WILL CREATE DISRUPTIVE NOISE OR VIBRATION WITH THE COR 48 HOURS IN ADVANCE OF BEGINNING SUCH WORK. WRITTEN

NOTICE TO COR IS REQUIRED 48 HOURS PRIOR TO PERFORMANCE OF SUCH WORK UNLESS

OTHERWISE AGREED TO BY COR.

M. INTERRUPTIONS TO EXISTING UTILITY SERVICES TO THE BUILDING OR AREAS OF THE SITE WILL ONLY BE ALLOWED UNDER EXTREME CIRCUMSTANCES AND FOR LIMITED PERIODS IF REQUIRED BY THE

SCOPE OF WORK. COORDINATE ANY ANTICIPATED SHUTDOWN OF ANY UTILITY AFFECTING THE

OCCUPANCY/USE OF THE FACILITY WITH THE COR AT LEAST 2 WEEKS IN ADVANCE OF ITS PROPOSED OCCURRENCE. NOTICE MUST BE GIVEN IN WRITING TO THE COR OF ANY/ALL SUCH OCCURRENCE(S)

THROUGHOUT THE CONSTRUCTION PERIOD. WRITTEN NOTICE OF PROPOSED SHUTDOWNS MUST

INCLUDE A TIME CERTAIN WHEN SERVICES WILL BE RESTORED.

N. REFER TO SPECIFICATION SECTION 01 00 00; GENERAL REQUIREMENTS FOR SAFETY AND OTHER

CONSIDERATIONS IN PROGRESSION OF WORK UNDER THIS CONTRACT.

O. REFER TO EQUIPMENT PLAN SHEET FOR LAYOUT OF ALL NEW EQUIPMENT PROVIDED AND INSTALLED

BY GC AND VA AS DESIGNATED.

P. ANY ITEMS DAMAGED BY THE CONTRACTOR OR BY PERSONS UNDER THE SUPERVISION OF THE

CONTRACTOR THAT ARE NOT INDICATED TO BE REMOVED OR DEMOLISHED SHALL BE

REPAIRED/REPLACED TO LIKE NEW CONDITION AT THE CONTRACTOR'S EXPENSE.

Q. GENERAL CONTRACTOR SHALL PROVIDE CONSTRUCTION AND WARNING SIGNS AS PER THE

SPECIFICATIONS AND DETAILS SHOWN IN THIS SET.

R. CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATERTIGHT STATE THROUGHOUT CONSTRUCTION. ROOF WORK SHALL NOT BE LEFT EXPOSED OR SUBJECT TO ROOF DRAINAGE INTO

OPENINGS OR AREAS LEFT OPEN.

S. EXISTING SPRINKLER SYSTEM SHALL REMAIN LIVE AND FUNCTIONAL DURING ALL PHASES OF CONSTRUCTION. CONTRACTOR SHALL TAKE GREAT CARE TO NOT DAMAGE ANY EXISTING HEADS OR

PIPING. COORDINATE WORK WITH FIRE PROTECTION DRAWINGS.

T. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO FABRICATION AND INSTALLATION OF ITEMS.

EXISTING PORTION OF PLANS ARE FROM LIMITED FIELD OBSERVATIONS, WHICH SHOULD BE

CONSIDERED APPROXIMATE, SATISFACTORY FOR BIDDING PURPOSES, BUT MAY NOT REFLECT

EXACT AS-BUILT CONDITIONS OR DIMENSIONS. IF ANY DISCREPANCIES ARE FOUND BETWEEN WHAT IS SHOWN ON THE PLANS AND WHAT EXISTS IN THE FIELD, CONTACT THE OWNER'S CONSTRUCTION

MANAGER TO DETERMINE WHAT SHOULD BE DONE TO MATCH EXISTING CONDITIONS AS

REQUIRED. BEGINNING OF CONSTRUCTION MEANS ACCEPTANCE OF EXISTING CONDITIONS. SEE

SPECIFICATIONS FOR MORE INFORMATION.

U. GRID LINES SHOWN ARE FOR PLAN LOCATION REFERENCE ASSISTANCE BETWEEN FLOOR AND ROOF

PLANS AND MAY NOT REFLECT OVERALL EXISTING BUILDING GRID SYSTEM.

V. SCOPE OF CONSTRUCTION WORK IS NOT LIMITED TO WORK SHOWN ON CONSTRUCTION DRAWINGS.

W. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT WALL

UNLESS NOTED OTHERWISE.

X. REFER TO THIS SHEET FOR STANDARD WALL PARTITION DETAILS.

Y. ALL WALLS ARE DIMENSIONED FROM FACE OF FINISHED WALL, UNLESS NOTED OTHERWISE.

Z. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW TOLERANCE

FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

AA. FURR AROUND ALL COLUMN PROTRUSIONS AS REQUIRED UNLESS NOTED OTHERWISE.

GENERAL NEW WORK PLAN NOTES

HOLLOW METAL

FRAME

2" 3'-0" 2"

M1

M1

FLUSH SOLID CORE

WOOD DOOR

# 217A-2

F

LEAD LINED HOLLOW

METAL FRAME

2" 3'-0" 2"

L1

L1

FLUSH SOLID CORE LEAD

LINED WOOD DOOR

# 217A-2A / # 217A-2B

F-L

Scale: 1/4" = 1'-0"

LEVEL 2 - NEW WORK PLAN Scale: 1" = 40'-0"

KEY PLAN

RENOVATION KEYNOTES

A1 PHILIPS EQUIPMENT ISO CENTER - REFER TO VENDOR DRAWINGS FOR ADDITIONAL INFORMATION

A2 NEW LOW RETURNS, REFER TO MECHANICAL FOR ADDITIONAL INFORMATION

A3 3" RADIUSED CORNER AT COUNTER TOPS, TYPICAL

A4 EXISTING MEDICAL EQUIPMENT STORAGE CABINETS TO REMAIN. PROTECT.

A5 NEW SWING DOOR AND FRAME

A6 NEW PHILIPS AD7 BASE PLATE. SEE PHILIPS DRAWINGS FOR ADDITIONAL INFORMATION

A7 NEW GASKETING AT EXISTING DOOR FRAME, INSTALL PER MANUFACTURERS RECOMMENDATIONS

A8 NEW PHILIPS POLY G BASE PLATE. SEE PHILIPS DRAWINGS FOR ADDITIONAL INFORMATION

A9 PHILIPS EQUIPMENT REQUIRED FLOOR LEVELNESS OF +/- 1/8" (3MM) WITHIN THIS AREA, UNISTRUT

SHALL BE SET AT 9'-6 1/2" ABOVE HIGH POINT WITHIN THIS AREA

A10 NEW PLASTIC LAMINATE COUNTER TOP

A11 NEW PHILIPS CLEA FLOOR PLATE. SEE PHILIPS DRAWINGS FOR ADDITIONAL INFORMATION

A12 NEW LEAD LINED GYSPUM BOARD OVER EXISTING STUDS, COORDINATE EXTENTS WITH NEW

CONSTRUCTION

Scale: 1 1/2" = 1'-0"

PARTITION TYPES

Scale: 3" = 1'-0"

DOOR FRAME DETAILS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:4 :4

P

M

AE-101

NEW WORK PLAN

JDA

9 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/4" = 1'-0"

DOOR AND FRAME TYPES

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

3 4 5 6

7 8 10

A

B

C

D

E

F

3 4 5 6 7 8 10

C

D

E

F

STERILE SUPPLIES

215-2

CLEAN UTILITY

217A-2

PT TOILET

211-2 CATH LAB 1

218-2 CATH LAB 2

216-2

CORRIDOR

C-2-3

WOMENS LOCKER

208-2

CORRIDOR

C-2-1

WAITING

200-2

ELEC

201-2

HK

210-2 PT TOILET

211-2

RECOVERY

212-2

HOLDING/PREP

214-2

STAIR

211-3

ISO CENTER

ISO CENTER

P.AVOX2

P.MB

P.MA P.ME P.ME P.MA P.MB

P.DB P.DB

P.SHP.SH

P.ATY

P.CY

P.CR1

P.UPS

P.SBO

P.AVOX1

P.AUX1

P.AUX2

P.AUX3

P.INT

P.AVOE1

P.PG

P.AD71

P.TV2

P.UPS

M3150

M3165

M3165

M3165

M3165

M3165 M3165 M3165

M3165

M3165

M3165M3165 M3150

CE040CE050

M8825M8810 M3175 M3109

CE040 CE040

F2020

A5104

M4811

M3165

E0954

M3070

P.FJB1

P.SYNC

CONTROL ROOM

217-2

EQUIPMENT ROOM

216A-2

P.AD72

P.CF

P.AD72

P.ATY

P.AUX1

P.AUX2

P.AUX3

P.INT

P.SYNC

P.SBO

P.CR1

A5104

P.CY

P.TV2

P.AVOE1

P.AVOX2

BUILDING 3

1A

BUILDING 1

19 BUILDING 2

AREA OF WORK

1. REFER TO PHILIPS SIT EPREPARATION SUPPORT DOCUMENTS IN THE PH

SHEETS SERIES.

2. REFER TO DRAWING SERIES GI-001 GENERAL INFORMATION FOR MOUNTING

HEIGHTS AND ADDITIONAL NOTES.

3. G.C. TO PROVIDE CONDUIT UP TO 6" ABOVE CEILING FROM EACH RECEPTACLE.

OWNER TO PROVIDE COVER PLATES FOR DATA RECEPTACLES.

4. G.C. TO COORDINATE ALL EQUIPMENT; INSTALL PER MANUFACTURER'S

SPECIFICATIONS AND INSTALLATION REQUIREMENTS.

5. G.C. TO COODINATION MEP AND PROVIDE ALL UTILITIES AS REQUIRED FOR NEW

WORK.

6. G.C. TO COORDINATE WITH OWNER'S SECURITY VENDOR AS NEEDED FOR

SECURITY DEVICES AND EQUIPMENT.

7. CONTRACTOR TO PROVIDE UTILITY AND BLOCKING AS REQUIRED FOR

SUPPORT OF ALL CONTRACTOR AND OWNER-PROVIDED ITEMS. CUT AND

PATCH EXISTING CONSTRUCTION WHERE NECESSARY FOR INSTALLATION.

8. SHARPS DISPOSAL CONTAINERS ARE TO BE MOUNTED AS CLOSE AS POSSIBLE

TO THE IMMEDIATE AREA WHERE SHARPS ARE USED OR ARE ANTICIPATED TO

BE FOUND. COORDINATE FINAL LOCATION WITH CLINICAL STAFF.

GENERAL EQUIPMENT PLAN NOTES

LEGEND

C/C = CONTRACTOR PROVIDED, CONTRACTOR INSTALLED

V/V = VA PROVIDED, VA INSTALLED

V/C = VA PROVIDED, CONTRACTOR INSTALLED

PHI/PHI = PHILIPS PROVIDED, PHILIPS INSTALLED

PHI/C = PHILIPS PROVIDED, CONTRACTOR INSTALLED

SHOWN ON CEILING

LAB 1:

P.MAV = CEILING TRACK WITH RADIATION SHIELD AND LED SURGICAL LIGHT

P.AVOX2 = AUXILIARY VIDEO OUTPUT

LAB 2:

P.MAV = CEILING TRACK WITH RADIATION SHIELD AND LED SURGICAL LIGHT

P.AVOX2 = AUXILIARY VIDEO OUTPUT

5 6 7 8 10

C

D

E

F

P.FVXL

P.AUX12

P.AUX11 P.MAV

P.FVXL

P.AUX12P.MAV

P.AUX11

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/7

/2

:4

:1

A

M

AE-102

EQUIPMENT PLAN

JDA

10 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/4" = 1'-0"

LEVEL 2 - EQUIPMENT PLAN

Scale: 1" = 40'-0"

KEY PLAN

Scale: 1/64" = 1'-0"

PHILIPS EQUIPMENT ROUTE

EQUIPMENT SCHEDULE

TAG NAME ACQ/INS

A5077 DISPENSER, HAND SANITIZER, HANDS FREE- EXISTING V/V

A5104 CART, WASTE DISPOSAL, MOBILE W/FOOT PEDAL - EXISTING V/V

A5107 DISPENSER, GLOVE, SUGICAL/EXAMINATION WALL MTND - EXISTING V/V

CE040 CABINET, SLOPING TOP - EXISTING V/V

CE050 CABINET, SLOPING TOP - EXISTING V/V

E0954 CART, EMERGENCY, MOBILE 66"H X 32" W X 22"D - EXISTING V/V

F2020 CAN, TRASH, 44 GALLON V/V

M3070 HAMPER, LINEN, MOBILE W/LID - EXISTING V/V

M3109 ELECTROSURGICAL COAGULATOR V/V

M3150 DISTRIBUTION SYSTEM, MEDICATION, AUTOMATIC -EXISTING V/V

M3165 CABINET, INVENTORY , CATHERTER STORAGE - EXISTING V/V

M3175 ELECTROSURGICAL UNIT, DUAL OUTPUT V/V

M4811 INTRA-AORTIC BALLON PUMP V/V

M8810 STAND, MAYO V/V

M8825 TABLE, INSTRUMENT/DRESSING, CRS, APPROX. 36X20X24 V/V

P.AD71 PHILIPS - ANGIO DIAGNOSTIC 7 PREMIUM TILT AND CRADLE TABLE PHI/PHI

P.AD72 PHILIPS - ANGIO DIAGNOSTIC 7 PREMIUM TILT AND CRADLE TABLE PHI/PHI

P.ATY PHILIPS - EXAM ROOM AUXILIARY BOX PHI/PHI

P.AUX1 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AUX2 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AUX3 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AUX4 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AUX11 PHILIPS - AUXILIARY EQUIPMENT ADAPTER PHI/PHI

P.AUX12 PHILIPS - AUXILIARY EQUIPMENT ADAPTER PHI/PHI

P.AVOE1 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AVOX1 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.AVOX2 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.CF PHILIPS - CLEA FLOOR PHI/PHI

P.CR1 PHILIPS - CONTROL ROOM EQUIPMENT ADAPTER PHI/PHI

P.CY PHILIPS - CONTROL ROOM JUNCTION BOX PHI/PHI

P.DB PHILIPS - DOCUMENTATION BOX - MOUNTED ON WHEELS PHI/PHI

P.FJB1 PHILIPS - AUXILIARY VIDEO OUTPUT PHI/PHI

P.FVXL PHILIPS - 65" FLEXVISION XL + (2) 27" LCD MONITOR PHI/PHI

P.INT PHILIPS - INTRASIGHT WORKSTATION PHI/PHI

P.MA PHILIPS - MAIN 40E CABINET PHI/PHI

P.MAV PHILIPS - AUXILIARY EQUIPMENT ADAPTER PHI/PHI

P.MB PHILIPS - IMAGE 40E CABINET PHI/PHI

P.ME PHILIPS - CERTERAY iX GENERATOR CABINET PHI/PHI

P.PG PHILIPS - POLY G STAND (FLOOR VERSION) PHI/PHI

P.SBO PHILIPS - SIGNALING BOX OPTION (FOR UPS) PHI/C

P.SH PHILIPS - SERVICE HUB PHI/PHI

P.SYNC PHILIPS - SYNC VISION PHI/PHI

P.TV2 PHILIPS - SINGLE MONITOR ON STAND PHI/PHI

P.UPS SOCOMEC - COMPACT FULL LOAD UPS PHI/C

Scale: 3/16" = 1'-0"

LEVEL 2 - RCP EQUIPMENT PLAN

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

3 4 5 6

7 8 10

A

B

C

D

E

F

EXIT LIGHT

2' x 2' ACOUSTICAL CEILING

CEILING HEIGHT, ABOVE

FINISH FLOOR

00'-00"

REFLECTED CEILING PLAN LEGEND

RETURN AIR GRILLE

SUPPLY AIR DIFFUSER

EXHAUST AIR GRILLE

2 X 4 LIGHT FIXTURE

RE: ELECTRICAL

GYPSUM BOARD CEILING

CONTROL JOINT IN GYPSUM

BOARD CEILING

CEILING HEIGHT, ABOVE

FINISH FLOOR

00'-00"

CJ SPEAKERS

NOTE: ALL SYMBOLS MAY NOT BE USED

1. WHERE EXISTING CEILING PANELS ARE REMOVED AND REPLACED WITH NEW, THE GENERAL

CONTRACTOR SHALL COORDINATE THE REMOVAL AND REINSTALLATION OF ALL CEILING MOUNTED

DEVICES (CUBICLE CURTAIN TRACKS, IV TRACKS, DETECTORS, SPEAKERS, ETC.)

2. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION ON THE ROUTING OF

NEW SERVICES ABOVE THE CEILING.

3. HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.

GENERAL REFLECTED CEILING PLAN NOTES

3 4 5 6 7 8 10

C

D

E

F

9'-0"

9'-0"

8'-5"

9'-0"

9'-0"

9'-0"

9'-0"

7'-6"

7'-6"

CATH LAB 2

216-2CATH LAB 1

218-2

CORRIDOR

C-2-3

WAITING

200-2

ELEC

201-2

HK

210-2

CORRIDOR

C-2-1

PT TOILET

211-2

EQUIPMENT ROOM

216A-2

CLEAN UTILITY

217A-2

STERILE SUPPLIES

215-2

ISO CENTER

5'-0" 5'-0"

4' -0

4'

-4

3' -8

9'-6 1/2"

9'-6 1/2"

CONTROL ROOM

217-2

STAIR

211-3

RECOVERY

212-2

HOLDING/PREP

214-2

C1

ISO CENTER

C1

5'-0" 5'-0"

UPS/BATTERY

209A-2

WORK

209-2

UTILITY

204A-2

UPS/COMP

203A-2

WAITING

200-2

CONTROL

203-2

COM

202-2

CORRIDOR

207A-26

C3

C3

C4 C4

C2

C2

1' -6

6"

4"

4' -5

/8

3'

-1

1/ 4"

3' -1

1/

4" 3'

-7

/4

4' -1

1/

4"

2'-5 1/4" 5'-3" 4'-5"

4' -3

/2

3'

-1

3/ 4"

4' -4

4'

-0

4' -2

5'-2 1/2" 5'-2 1/2" 1'-7 5/8"

1 1/2" C.R. STEEL

CHANNEL @ 4'-0" O.C.

(MAX.)

5/8" GYPSUM BOARD PN 7/8"

METAL FURRING CHANNEL

@ 2'-0" O.C.(MAX.)

HANGER RODS @ 4'-0" O.C.

(MAX.), BOTH DIRECTIONS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/7

/2

:4

:4

A

M

AE-103

REFLECTED CEILING PLANS

JDA

11 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1" = 40'-0"

KEY PLAN

Scale: 1/4" = 1'-0"

LEVEL 2 - RCP

REFLECTED CEILING PLAN KEYNOTES

C1 NEW CEILING AT 9'-6 1/2" PER PHILIPS REQUIREMENTS.

C2 CEILING BOX, FLUSH MOUNTED, REFER TO PHILIPS VENDOR SITE SPECIFIC FOR ADDITIONAL

INFORMATION

C3 NEW MEDICAL GASES AT CEILING WITH HOSE RETRACTOR

C4 NEW/RELOCATED UNISTRUT (TYPICAL) FOR EQUIPMENT SUPPORT. REFER TO STRUCTURAL

DRAWINGS AND COORDIANTE WITH VENDOR SITE SPECIFIC INSTALLATION DRAWINGS.

Scale: 3/4" = 1'-0"

SUSPENDED GYPSUM CEILING

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

3 4 5 6

7 8 10

A

B

C

D

E

F

E

AE-104

CONTROL ROOM

217-2

A3

A3

2' -6

4"

NEW SS1 COUNTER TOP

EXISTING WALL

MOUNTED RACEWAY

TO REMAIN

2'-0"

V.I.F.

8'-7 3/8"2'-0"

ETR

P.INT P.INT

NEW SS1 COUNTER TOP

EXISTING WALL

MOUNTED RACEWAY

TO REMAIN

2' -6

4"

AE-104

V.I.F.

6'-10 7/8"

EXISTING LEAD LINED

WINDOW TO REMAIN,

PROTECT

ETR

P.CY

2' -6

V.I.F.

6'-10 7/8"

4"

NEW SS1 COUNTER TOP

EXISTING LEAD LINED

WINDOW TO REMAIN,

PROTECT

EXISTING WALL

MOUNTED RACEWAY

TO REMAIN

AE-104

ETR

P.CY

1. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION OF MILLWORK.

2. COORDINATE LOCATION OF RECEPTACLES WITH ELECTRICAL DRAWINGS.

3. WHERE FURR DOWNS ARE CALLED FOR OVER UPPER CABINETS, EXTEND

FURR DOWN 1" MIN. PAST FRONT EDGE OF MILLWORK - TYPICAL.

4. NO PLASTIC HARDWARE, BRACKETS OR CLIPS WILL BE ACCEPTED.

5. ALL DRAWERS SHALL BE ON HEAVY DUTY FULL EXTENSION METAL GLIDES

WITH SOFT CLOSERS UNLESS NOTED OTHERWISE.

6. USE CONCEALED CABINET HINGES UNLESS NOTED OTHERWISE.

7. MILLWORK SHALL BE PRE THE QUALITY AND GRADE CONSTRUCTION

STANDARDS AS SPECIFIED IN THE PROJECT MANUAL. STRICT ADHERENCE TO

THIS STANDARD SHALL BE ENFORCED. ANY DEVIATIONS FROM THIS BASE

STANDARD, IF NOT SPECIFICALLY SHOWN WITHIN THESE DRAWINGS WILL NOT

BE ACCEPTED.

8. ALL SURFACES EXPOSED TO VIEW, INCLUDING THOSE SURFACES EXPOSED

TO VIEW WHILE IN A SEATED POSITION, SHALL HAVE A FINISHED SURFACE TO

MATCH OTHER ADJACENT FINISHED SURFACES.

9. ALL CABINETS TO HAVE CABINET LINERS ON ALL SURFACES.

10. REFER TO ENLARGED FLOOR PLANS FOR TOILET ACCESSORIES WHERE

APPLICABLE.

GENERAL MILLWORK NOTES

ETR

ETR

P.AVOX2

ETR

EXISTING STORAGE

CABINETS

ETR

M3150

EXISTING

LEAD LINED

WINDOW

TO REMAIN

ETR

217A-2B

M3150

ETR ETR

ETR

ETR

EXISTING LEAD

LINED WINDOW

TO REMAIN

217A-2A

P.ATY

ETR

P.AVOX2

M3150

NON-COMBUSTIBLE

BLOCKING

COUNTERTOP W/ 4"

BACKSPLASH

S E

E E

LE

V

A T

IO

N

S

2'-1"

GROMMET. PROVIDE MIN. ONE @

4'-0" O.C. AT OPEN COUNTERS ONLY.

INSTALL AFTER INSTALLATION OF

COUNTERTOP IS COMPLETE.

COODRINATE FINAL LOCATION IN

FIELD WITH END USER.

STEEL SUPPORT BRACKETS

@ 42" MAX. O.C.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:4 :5

P

M

AE-104

ENLARGED PLAN, INTERIOR

ELEVATIONS

JDA

12 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/2" = 1'-0"

LEVEL 2 - ENLARGED CONTROL ROOM

Scale: 3/8" = 1'-0"

CONTROL ROOM

Scale: 3/8" = 1'-0"

CONTROL ROOM

Scale: 3/8" = 1'-0"

CONTROL ROOM

Scale: 3/8" = 1'-0"

CATH LAB 2

Scale: 3/8" = 1'-0"

CATH LAB 2

Scale: 3/8" = 1'-0"

CATH LAB 2

Scale: 3/8" = 1'-0"

CATH LAB 2

Scale: 1" = 40'-0"

KEY PLAN

Scale: 3/8" = 1'-0"

CATH LAB 1

Scale: 3/8" = 1'-0"

CATH LAB 1

Scale: 3/8" = 1'-0"

CATH LAB 1

Scale: 3/8" = 1'-0"

CATH LAB 1

Scale: 3/4" = 1'-0"

CASEWORK - COUNTER

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

3 4 5 6

7 8 10

A

B

C

D

E

F

LVT1 (LUXURY VINYL TILE)

RSF1 (RESILIENT SHEET FLOORING)

PT1 (SLIP RESISTANT PORCELAIN TILE)

LVT2 (LUXURY VINYL TILE)

CPT1 (CARPET TILE)

SC (SEALED CONCRETE)

WCPT1 (WALK OFF CARPET TILE)

SV1 (WELDED SHEET VINYL)

ST (RUBBER STAIR TREAD)

FLOOR FINISHES LEGEND

NOTE: ALL SYMBOLS MAY NOT BE USED

HANDRAIL/BUMPER GUARD / FINISH: HR/BG

CG2

CORNER GUARD / EXISTING STAINLESS STEEL

CORNER GUARD / NEW - FINISH: STAINLESS STEEL

NOTE: ALL SYMBOLS MAY NOT BE USED

WALL ACCESSORIES LEGEND

1. ALL WALLS TO BE PAINTED P1, U.N.O.

2. ALL UPPER CABINETS TO HAVE A MIN. 30° SLOPED TOP. REF. MILLWORK

DETAILS

3. ALL COUNTERTOPS AND BACKSPLASH TO BE PL1.

4. ALL VINYL BASE TO BE VB1 U.N.O.

5. ALL CORNER GUARDS TO BE CG1 U.N.O

6. ALL WOOD-LOOK PLANKS TO BE LAID IN THE SAME DIRECTION AS THE LONGEST

DIMENSION OF THE ROOM.

7. ALL CONSTRUCTION SHALL CONFORM TO THE AMERICANS WITH DISABILITIES

ACT, ACCESSIBILITY GUIDELINES (ADAAG), LOCAL GOVERNING FIRE, SAFETY,

AND BUILDING CODES, REQUIREMENTS AND REGULATIONS, 2015 IBC, ANSI

A117.1-2003.

8. ALL DIMENSIONS ARE TO THE FACE OF CONCRETE OR MASONRY, FACE OR

CENTERLINE OF STUD WALLS, OR CENTERLINE OF COLUMNS UNLESS NOTED

OTHERWISE.

9. ASBESTOS OR ASBESTOS CONTAINING PRODUCTS ARE NOT ALLOWED IN ANY

ASPECT OF THIS CONSTRUCTION.

10. COORDINATE ALL DISCIPLINES AND ALL ASPECTS OF WORK. CONFLICTS AND

DISCREPENCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT

IMMEDIATELY.

11. ALL CONCRETE SURFACES WHICH RECEIVE A SPECIAL FINISH, FLOOR

COVERING, COATINGS, HARDENERS, ETC. SHALL BE CONSTRUCTED IN

ACCORDANCE WITH THE SPECIFIC FINISH MANUFACTURER'S SPECIFICATIONS

AND INSTRUCTIONS. PRIOR TO APPLICATION OF A SPECIAL FINISH, A WRITTEN

ACCEPTANCE OF THE SURFACE SHALL BE SUBMITTED TO THE ARCHITECT BY

THE GENERAL CONTRACTOR.

12. REFER TO STRUCTURAL FOR RECESSED SLAB LOCATIONS, SLOPED SLABS AND

DIMENSIONS.

13. REMOVE ALL FLOOR FINISHES AND ADHESIVES AND STRIP FLOOR DOWN TO

EXISTING CONCRETE. PREP FLOOR FOR INSTALLATION OF NEW FLOOR

FINISHES AS SHOWN.

GENERAL FINISH NOTES

STERILE SUPPLIES

215-2

CORRIDOR

C-2-3

CLEAN UTILITY

217A-2

CATH LAB 1

218-2

CATH LAB 2

216-2

4' -2

'-6

'-8

11'-10"

5'-11 1/4" 5'-10 3/4" 5'-10" 5'-10"

11'-8"

9' -6

/2

9'

-6

/4

'-0

/4

CONTROL ROOM

217-2

SCRIBE TO COUNTER TOP FROM

FIRST PHASE TO PROVIDE A

CONTINUOUS FLUSH SURFACE

FLOORSFINISH PRODUCT INFORMATION NOTES

WALLSFINISH

WSV1

PNT1

PNT2

WELDED SHEET VINYL

PAINT (FIELD)

PAINT (DOOR/WINDOW FRAME/TRIM)

OTHERFINISH

SS1 SOLID SURFACE (COUNTER TOP)

CEILINGFINISH

GWB-1 GYP-1 (PAINT WHITE)

ARMSTRONG - MEDINTONE -

CALMING GRAY: H2006

SHERWIN WILLIAMS - DRIFT

OF MIST SW9166

SHERWIN WILLIAMS - DRIFT

OF MIST SW9166

CORIAN - DESIGNER WHITE

WELDING RODS AND CAP STRIPS SHALL

MATCH FLOORING CALMING GREY

EGGSHELL FINISH

SEMI-GLOSS FINISH

FINISH MATERIALS SCHEDULE

SHERWIN WILLIAMS -

CEILING WHITE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

ARCHITECT:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/7

/2

:4

:4

A

M

AF-701

FINISH FLOOR PLANS

JDA

13 37

DW

100% CONTRACT DOCUMENTS FOR BIDDING

PREPARE SITE FOR CATH LAB

EQUIPMENT

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218 02-

Scale: 1/4" = 1'-0"

LEVEL 2 - FINISH PLAN

ROOM FINISH SCHEDULE

ROOM # ROOM NAME

FLOOR FINISHES WALL FINISHES

CEILING

MATERIAL BASE NORTH EAST SOUTH WEST

215-2 STERILE SUPPLIES ETR ETR ETR ETR ETR ETR ETR

216-2 CATH LAB 2 SV1 / ETR ETR PNT1 PNT1 PNT1 PNT1 GYP1

217-2 CONTROL ROOM ETR ETR PNT1 PNT1 PNT1 PNT1 PNT1

217A-2 CLEAN UTILITY ETR ETR PNT1 PNT1 PNT1 PNT1 GYP1

218-2 CATH LAB 1 SV1 / ETR ETR PNT1 PNT1 PNT1 PNT1 GYP1

C-2-3 CORRIDOR ETR ETR ETR ETR ETR ETR ETR

Scale: 1" = 40'-0"

KEY PLAN

K SAN AS

NSE EC DIL

A8404

A TR CC EH TI

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218

PREPARE SITE FOR CATH LAB

EQUIPMENT

ARCHITECT:

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218

PREPARE SITE FOR CATH LAB

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218

PREPARE SITE FOR CATH LAB

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218

PREPARE SITE FOR CATH LAB

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS AFFAIRS

ROBERT J. DOLE VA MEDICAL CENTER

5500 KELLOGG DR. WICHITA, KS 67218

PREPARE SITE FOR CATH LAB

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

Revision: Date:

U.S. Department of Veteran Affairs

MOON TREE, LLC

1808 Deep Creek Rd Oklahoma City, OK 73131

(405) 509-5254

STRUCTURAL / CIVIL

ENGINEER

MOON TREE, LLC

1808 DEEP CREEK ROAD

OKLAHOMA CITY, OK 73131

(405) 509-5254

MECHANICAL / ELECTRICAL /

PLUMBING / TECHNICAL ENGINEER

FIRE PROTECTION

ENGINEER

F U

L L

Y S

P R

IN

K

L E

R E

D

BOWMAN FOSTER & ASSOCIATES, INC

6353 CENTER DRIVE, #101

NORFOLK, VA 23502

(757) 466-7400

/1

/2

:3

:5

P

M

100% CONTRACT DOCUMENTS FOR BIDDING

03/17/2026

589A7-25-503

DEPARTMENT OF VETERANS…