S02 - Attachment D2 - ITM Drawings.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25026Q0069
- Issued by
-
Department of Veterans Affairs
About this file
These are electrical engineering design drawings for the Aleda E. Lutz VA Medical Center located in Saginaw, Michigan, with the project number 655-26-201 for Electrical Maintenance and Testing. The comprehensive set of 38 drawings covers multiple aspects of the facility's electrical infrastructure, including:
The drawings detail medium voltage distribution (8.3kV), electrical site plans, one-line diagrams for normal and emergency power systems, and riser diagrams for multiple buildings (Buildings 1, 6, 9, 21, 22, 30, 35, 38). The electrical system includes multiple generators (GEN-1 through GEN-7 ranging from 350kW to 750kW), transformers with various capacities (45kVA to 1000kVA), and complex switchboard and distribution panel configurations across normal, emergency, critical, and life safety power branches. The designs show intricate electrical routing, grounding details, and power metering systems for the VA Medical Center's comprehensive electrical infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEISS STREET
EC
Weiss St
N M as on
S t
Davenport Ave
State St
Interstate 675
N M ic hi ga n
Av e
Sc ha ef er
S t
N
CAMPUS AREA MAP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
PROJECT NO. 655-26-501 BREAKER TESTING & MAINTENANCE
ALEDA E. LUTZ VA MEDICAL CENTER
DEPARTMENT OF VETERANS AFFAIRS
1500 WEISS ST. SAGINAW, MICHIGAN
VICINITY MAP
COVER SHEET
ELECTRICAL MAINTENANCE
& TESTING
655-26-201BID
G1.1
DRAWING SHEET INDEX
SHEET # SHEET TITLE SHEET DESCRIPTION
1 G1.1 COVER SHEET
2 G1.2 LEGEND & NOTES
3 ES-100 OVERALL ELECTRICAL SITE PLAN
4 ES-101 ENLARGED ELECTRICAL SITE PLAN - NORTH SECTION
5 ES-102 ENLARFED ELECTRICAL SITE PLAN - SOUTH SECTION
6 EP-100 BLDG. 20 & SITE 8.3KV MEDIUM VOLTAGE PRIM. ONE-LINE DIAGRAM
7 EP-101 BLDG. 20 & SITE 8.3KV MEDIUM VOLTAGE PRIM. ONE-LINE DIAGRAM
8 EP-102 BLDG. 1 NORMAL POWER SWBD-1 & SWBD-2 ONE-LINE DIAGRAM
9 EP-103 BLDG. 1 NORMAL POWER NSWBD & NSWBD-2 ONE-LINE DIAGRAM
10 EP-104 BLDG. 1 EM. POWER GEN-1, 2, 6, ESWBD, DP-E-2EC-C ONE-LINE DIAGRAM
11 EP-105 BLDG. 1 EM. POWER PANELS EMDP & DP-EQ-BA3-01 ONE-LINE DIAGRAM
12 EP-106 BLDG. 1 EM. POWER CRITICAL & LIFE SAFETY ONE-LINE DIAGRAM
13 EP-107 BLDG. 1 EM. POWER PANEL MDP, EP4, EQ2A1, EQ2D ONE-LINE DIAGRAM
14 EP-108 BLDG. 1 EM. POWER EB-E-1, MCC-P4D, EQBE-1 & 2 ONE-LINE DIAGRAM
15 EP-109 BLDG. 1 EM. POWER PANELS EQP-1, DP-EQ-6HB ONE-LINE DIAGRAM
16 EP-110 BLDG. 1 EM. POWER PANEL EMCC-E-BEC-C1 ONE-LINE DIAGRAM
17 EP-111 BLDG. 1 NORMAL POWER PANELS LDP & PDP ONE-LINE DIAGRAM
18 EP-112 BLDG. 1 NORMAL POWER (480V) PANELS NDP & DP-N-BA2-01 ONE-LINE DIAGRAM
19 EP-113 BLDG. 22 EM. POWER GENERATOR #3 ONE-LINE DIAGRAM
20 EP-114 BLDG. 22 EM. POWER PANELS DP-EMA, CDP, ELEV, LSD ONE-LINE DIAGRAM
21 EP-115 BLDG. 22 NORMAL POWER PANELS MDP-1 & MDP-2 ONE-LINE DIAGRAM
22 EP-116 BLDG. 22 NORMAL POWER PANELS MCC-B1, 1, 3, 4, M3, & M4 ONE-LINE DIAGRAM
23 EP-117 BLDG. 21 EM. & NORMAL POWER GEN. #7, EDP-21A, DP-21A ONE-LINE DIAGRAM
24 EP-118 BLDG. 21 EM. POWER PANELS EDP-21B ONE-LINE DIAGRAM
25 EP-119 BLDG. 9 & 35 EM. POWER DP-E-HBS1-09, DP-E-BS1-09 ONE-LINE DIAGRAM
26 EP-120 BLDG. 6 EM. POWER DP-E-H1N1-06, PB-E-H2N1-06 ONE-LINE DIAGRAM
27 EP-121 BLDG, 2, 3, 4, 30, 38 EM. POWER DP-E-H1N1-06, PB-E-H2N1-06 ONE-LINE DIAGRAM
28 EP-201 BUILDING 22 DISTRIBUTION RISER DIAGRAM
29 EP-202 BUILDING 22 EMERGENCY POWER RISER DIAGRAM
30 EP-203 BUILDING 22 NORMAL POWER RISER DIAGRAM
31 EP-204 BUILDING 22 CRITICAL & LIFE SAFETY RISER DIAGRAM
32 EP-205 BUILDING 1 EM. POWER EQUIPMENT SYSTEM RISER DIAGRAM
33 EP-206 BUILDING 1 NORMAL POWER RISER DIAGRAM
34 EP-301 MEDIUM VOLTAGE 8.3KV DISTRIBUTION LAYOUT
35 EP-302 BUILDING 20 8.3KV MEDIUM VOLTAGE POWER METERING
36 EP-303 BUILDING 20 8.3KV MEDIUM VOLTAGE LAYOUT
37 EP-304 8.3KV MEDIUM VOLTAGE TRANSFORMER DETAILS
38 EP-305 BUILDING 1 DISTRIBUTION LAYOUT
SAGINAW VA
MEDICAL CENTER
BUILDING KEY
1 MAIN HOSPITAL 17 GAS HOUSE 32 PUMP HOUSE
2 POLICE 19 GENERATOR BLDG. 33 WATER TOWER
3 ADMINISTRATIVE 20 MEDIUM VOLTAGE BLDG. 34 BACK FLOW PREVENTOR
4 ADMINISTRATIVE 21 GARAGE 35 PAVILION
6 ADMINISTRATIVE 22 CLC 38 TEMP. OFFICE TRAILER
9 WAREHOUSE 30 ADMINISTRATIVE EC ENERGY CENTER
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
LEGEND & NOTES
655-26-201BID
G1.2
GENERAL NOTES:
1. CONTRACTOR SHALL PERFORM REQUIRED INSPECTION, TESTING, AND MAINTENANCE IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA).
2. TRANSFORMERS AND ALL RELATED EQUIPMENT:
A. TRANSFORMERS ARE TO BE CLEANED EXTERIORLY, INSPECTED FOR SIGNS OF OVERHEATING
WITH INFRA-RED THERMAL DETECTING EQUIPMENT, AND INSPECTED FOR ANY DAMAGE TO THE
HOUSING, CONNECTION POINTS, OR INSULATION.
B. LIQUID COOLED TRANSFORMERS ARE TO HAVE THE COOLING LIQUID TESTED AND REPLACED, WHEN TESTS INDICATE THAT THE LIQUID NO LONGER MEETS MANUFACTURER'S SPECIFICATION.
THE LIQUID IS TO BE RE-FILLED TO MEET THE MANUFACTURER'S SPECIFICATION.
C. DRY TYPE TRANSFORMERS MUST BE THOROUGHY CLEANED EXTERIORLY AND INSPECTED FOR
OVERHEATING WITH INFRA-RED THERMAL DETECTING EQUIPMENT.
3. ELECTRICAL EQUIPMENT (INCLUDING, BUT NOT LIMITED TO LOOP SWITCHES, SWITCHGEARS, SWITCHBOARDS, DISTRIBUTION PANELS, MOTOR CONTROL CENTERS AND ALL RELATED
COMPONENTS):
A. USE LINT-FREE RAGS TO CLEAN CONDUCTORS, CONTACT POINTS BETWEEN THE CIRCUIT
BREAKERS AND MAIN BUSS BARS, BUSS BARS AND INTERIOR OF THE ELECTRICAL EQUIPMENT.
USE A VACUUM CLEANER TO REMOVE LARGE DEBRIS; COMPRESSED AIR IS NOT TO BE USED FOR
THIS PURPOSE. VISUALLY INSPECT FOR SIGNS OF OVERHEATING, MISALIGNED CONTACTS,
DAMAGED INSULATION, OR LOSE LUGS.
B. LUBRICATE ALL MOVING PARTS WITH MANUFACTURER'S APPROVED LUBRICANTS.
C. CIRCUIT BREAKERS 250 AMPS AND ABOVE SHALL BE TESTED AND EXERCISED TO ENSURE
OPERATION UNDER OVERLOAD, AND SHORT CIRCUIT CONDITIONS (WHERE APPLICABLE CIRCUIT
BREAKERS ARE TO BE TRIPPED USING SECONDARY INJECTION).
D. ALL MOLDED CASE CIRCUIT BREAKERS (INCLUDING FRAME SIZES 225 AMPS OR LESS) ARE TO BE
TESTED TO DETERMINE IF CONTACTS OPEN AND RECLOSE WHEN BREAKER IS MANUALLY
TRIPPED AND RESTORED.
E. TEST GROUND FAULT PROTECTION DEVICES FOR PROPER FUNCTION IF THEY ARE INSTALLED IN
THE FACILITY ELECTRICAL POWER SYSTEM.
F. INSPECT AND TIGHTEN GROUND CONNECTIONS. TEST GROUND RESISTANCE FOR THE ENTIRE
FACILITY GROUNDING SYSTEM. ANY METHOD OF GROUND RESISTANCE WILL BE CONSIDERED
ACCEPTABLE IF IT CAN VERIFY CONTINUITY AND QUANTIFY THE IMPEDANCE TO GROUND, TO
INCLUDE BUT NOT LIMITED TO FALL-OF-POTENTIAL, INDUCED FREQUENCY AND CLAMP ON
TESTING. IF INITIAL TESTS INDICATE A PROBLEM OR CONECERN, A MORE DETAILED TEST MUST
BE PERFORMED USING FALL-OF-POTENTIAL OR 3-POINT TEST.
G. IDENTIFY THE HOT SPOTS IN THE ELECTRICAL EQUIPMENT BY USING INFRA-RED THERMAL
DETECTING EQUIPMENT. TIGHTEN PROBLEM CONNECTIONS TO MEET EQUIPMENT
MANUFACTURERS' SPECIFICATION USING A TORQUE WRENCH OR OTHER APPROVED DEVICES.
H. CALIBRATE AND MAINTAIN ADJUSTABLE PROTECTIVE RELAYS.
I. TEST ALL CONTROL SYSTEMS EQUIPMENT FOR PROPER OPERATION AFTER MAINTENANCE IS
PERFORMED AND BEFORE PLACING THEM BACK IN NORMAL SERVICE.
4. ALL TESTING RESULTS ARE TO BE DOCUMENTED AND TURNED OVER TO THE ENGINEERING OFFICE.
ABBREVIATIONS
AFF ABOVE FINISHED FLOOR FBGC FURNISHED BY GENERAL CONTRACTOR NO NORMALLY OPEN
AFC ABOVE FINISHED CEILING FBO FURNISHED BY OTHERS PCB PRINTED CIRCUIT BOARD
ASC AUDIO SYSTEMS CONTRACTOR FT FOOT OR FEET PE PHOTO ELECTRIC
AVSC AUDIO-VISUAL SYSTEMS CONTRACTOR FV FIELD VERIFY PID PASSIVE INFRARED DETECTOR
BCF BELOW FINISHED CEILING GC GENERAL CONTRACTOR PS POWER SUPPLY
C CONDIT GND GROUND PTZ PAN, TILT, ZOOM
C.O. CONDUIT ONLY HT HEIGHT RF RADIO FREQUENCY
CATV COMMUNITY ANTENNA TV IC INTERCOM S SOUTH
CCT. CIRCUIT IR INFRARED SSC SECURITY SYSTEMS CONTRACTOR
CCTV CLOSED CIRCUIT TV JB JUNCTION BOX TV TELEVISION
CONT'D CONTINUED LPS LOCK POWER SUPPLY TVSC TELEVISION SYSTEMS CONTRACTOR
CWG COLD WATER GROUND MATV MASTER ANTENNA TV TYP TYPICAL
DWG DRAWING MAX MAXIMUM UON UNLESS OTHERWISE NOTED
E. EAST MIN MINIMUM W WEST
EC ELECTRICAL CONTRACTOR N NORTH W/ WITH
EL ELEVATION NC NORMALLY CLOSED W/O WITHOUT
EXT. EXTERNAL NEC NATIONAL ELECTRIC CODE W.P. WATERPROOF
FBEC FURNISHED BY ELECTRICAL CONTRACTOR NIC NOT IN CONTRACT
X
X X
X X
X X
X
WEISS STREET
X
X X
DUMPSTER
DUMPSTER
HH
EMH-105
EMH-103
EMH-102
EMH-99
EMH-101
EMH-100
EMH-171
EMH-114
EMH-174
EMH-176
EMH-175
EMH-179
EMH-182
EMH-118
EMH-112
EMH-111
EMH-119
EC
LOOP SWITCH-1
LOOP
SWITCH-5
LOOP SWITCH-6
T-8
500 KVA
T-7
750 KVA
T-1
750 KVA
T-10
750 KVA
T-11
750 KVA
T-2
500 KVA
T-3
1000 KVA
T-16
75 KVAT-13
225 KVA
T-12
750 KVA
T-35
150 KVA
T-29
45 KVA
T-9
225 KVA
T-14
1000 KVA
T-17
112.5 KVA
T-31
112.5 KVA
T-20
112.5 KVA
T-32
30 KVA
LOOP SWITCH-2
LS2-A NO
LOOP SWITCH-4
LOOP SWITCH-3
T-6
225 KVA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
OVERALL ELECTRICAL SITE PLAN
655-26-201BID
ES-100
AutoCAD SHX Text
EAST 1/4 CORNER SECTION 14 T. 12 N., R. 4 E. CITY OF SAGINAW
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
EX. LOW AREA
AutoCAD SHX Text
EX. LOW AREA
AutoCAD SHX Text X
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
WEISS STREET
AutoCAD SHX Text
CB
AutoCAD SHX Text S86°25'31"W 23.90' (M) S86°25'50"W (R)
AutoCAD SHX Text
BM
AutoCAD SHX Text
OHW
AutoCAD SHX Text
CITY OF SAGINAW
AutoCAD SHX Text
OHW
AutoCAD SHX Text
OHW
AutoCAD SHX Text
OHW
AutoCAD SHX Text
OHW
AutoCAD SHX Text 594'
AutoCAD SHX Text
CITY OF SAGINAW PROPERTY LINE
AutoCAD SHX Text
30' REAR
AutoCAD SHX Text
SETBACK
AutoCAD SHX Text
CITY OF SAGINAW PROPERTY LINE
AutoCAD SHX Text
OHW
AutoCAD SHX Text
OHW
AutoCAD SHX Text 48.46'
AutoCAD SHX Text 125.98'
AutoCAD SHX Text N89°46'20"W 545.98'
AutoCAD SHX Text 87.82'
AutoCAD SHX Text N89°46'20"W
AutoCAD SHX Text N01°06'20"W
AutoCAD SHX Text 33.01'
AutoCAD SHX Text
5'X8' LANDING
AutoCAD SHX Text
STEP
AutoCAD SHX Text
STEP
AutoCAD SHX Text
STEP
AutoCAD SHX Text
MAX SLOPE 1:12
AutoCAD SHX Text
4'X7'10" RAMP LANDING
AutoCAD SHX Text
MAX SLOPE 1:12
AutoCAD SHX Text
PEDESTRIAN GATE WHERE WATERMAIN CROSSES FENCE.
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text (E)P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
P
X X
X X
X X
X X
X
X
X X X
X
X
X
X X
X
X
X
DUMPSTER
DUMPSTER
LOOP
SWITCH
T-12
750 KVA
DP-21A
480V
T-13
225 KVA
BLDG 30
120/208V
T-8
500 KVA
MDP-2
120/208V T-7
750 KVA
MDP-1
480V
T-16
75 KVA
EDP-21B
120/208V
T-6
225 KVA
CB-N-HBS1-09
480V
LOOP
SWITCH
T-17
112.5 KVA
DP-E-BS2-09
120/208V
T-31
112.5 KVA
BLDG 35
120/208V
T-20
112.5 KVA
CONSTRUCTION
TRAILERS
120/208V
DISC-RTU-AC-21-107
DISC-103-0CU-101
DISC-B438-MINI-SPLIT-CU
DISC-B6 HU-1
DISC-B6 SF-1
DISC-B6 DX-1 (PB-E-H2N1-06)
DISC-B702A-22-CU-004
DISC-B6 RF-1
DISC-B6 EF-1
DISC-ECB-B6-DX-1-CP
DISC-B4-106A-4-CU-101
DISC-B4-CU-NW
DISC-ECB-B21-GHP-4 DISC-ECB-B21-GHP-5
DISC-B21-CU-101
FDS-BUILDING-30
FDS-E-H2-00
PB-E-2-00
DISC-B32-CU-1
DISC-B32-CU-2
DISC-GEN-7-LOAD-BANK-FAN
DISC-B21-GEN-7-RAD
DISC-B9-101-MINI-SPLIT-CU
DISC-B09-CU
CONSTRUCTION PANEL-1
CONSTRUCTION PANEL-2DISC-TRANSFORMER T-20
DISC-B1-THAW-BOX
DISC-B22-ACRCU-1
DISC-B22-ACRCU-2
DISC-B22-SOLAR-DC-INPUT
DISC-B22-EF-1-2
DISC-30-CU-101
DISC-B1-VEGGIE-FRIDGE
DISC-B1-COOKS -COOLER
DISC-B1-CHAPEL-RTU
DISC-B1-MAU-KETTLE-HOOD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
ENLARGED ELECTRICAL SITE
PLAN - NORTH SECTION
655-26-201BID
ES-101
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text X
AutoCAD SHX Text
EX. LOW AREA
AutoCAD SHX Text
EX. LOW AREA
AutoCAD SHX Text X
AutoCAD SHX Text
OHW
AutoCAD SHX Text
CITY OF SAGINAW
AutoCAD SHX Text
OHW
AutoCAD SHX Text
OHW
AutoCAD SHX Text 594'
AutoCAD SHX Text 600'
AutoCAD SHX Text
CITY OF SAGINAW PROPERTY LINE
AutoCAD SHX Text 87.82'
AutoCAD SHX Text N89°46'20"W
AutoCAD SHX Text N01°06'20"W
AutoCAD SHX Text 33.01'
AutoCAD SHX Text
5'X8' LANDING
AutoCAD SHX Text
STEP
AutoCAD SHX Text
STEP
AutoCAD SHX Text
STEP
AutoCAD SHX Text
MAX SLOPE 1:12
AutoCAD SHX Text
4'X7'10" RAMP LANDING
AutoCAD SHX Text
MAX SLOPE 1:12
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
SHEET ES-101
SHEET ES-102
X X
X X
X X
WEISS STREET
HH
EC
FUSE-UTILITY
CONSUMERS
ENERGY
FEEDER-3FEEDER-2FEEDER-1MV-MAIN
PANEL BUILDING-2
LOOP
SWITCH
LOOP
SWITCH
LOOP
SWITCH
LOOP
SWITCH
T-10
750 KVA
SWBD-2
MAIN-1
T-11
750 KVA
SWBD-2
MAIN-2
T-14
1000 KVA
NSWBD-2
480V
T-2
500 KVA
SWBD-1
MAIN-2
T-1
750 KVA
SWBD-1
MAIN-1
T-9
225 KVA
DP3
120/208V
T-8
500 KVA
MDP-2
120/208V T-7
750 KVA
MDP-1
480V
T-6
225 KVA
CB-N-HBS1-09
480V
LOOP
SWITCH
T-17
112.5 KVA
DP-E-BS2-09
120/208V
T-31
112.5 KVA
BLDG 35
120/208V
T-20
112.5 KVA
CONSTRUCTION
TRAILERS
120/208V
T-2
1000 KVA
NSWBD
480V
TAP EMH-123 JUNCTION A
TAP EMH-123 JUNCTION B
ELECTRICAL MANHOLE 123
DISC-1-ACCU-1 (SPS CU)
DISC-103-0CU-101
DISC-CU-3B
DISC-1114-MS-CU
DISC-B100-AREA-CU-8
DISC-B1-AREA-1100-CU-1C
DISC-2135-X-RAY-MS-CU
DISC-B1-AREA-B130
DISC-2145-CT-SCAN-MS-CU
DISC-2147-CT-CNTRL-MS-CU
DISC-B1-CU-1BDISC-B1-CU-1A
DISC-1200-WEST-MINI-SPLIT-CU
DISC-B210-MINI-SPLIT-CU
DISC-B200-MINI-MATE-1-CUDISC-B200-MINI-MATE-2-CU
DISC-B220 AREA-RTU
DISC-NUC-MED-ACC-1
DISC-B250-MINI-SPLIT-CU
DISC-2257-MS-CU
DISC-EC-OFFICE-MINI-SPLIT-CU
DISC-B1-RTU-2
DISC-ACC-4A DISC-ACC-4B
DISC-B338-MINI-SPLIT-CU
DISC-2300-1-AC-201
DISC-4305-1-CU-401
DISC-B1-MORGUE-CU
#1
DISC-2134-1-ACCU-9
DISC-1-ACCU-7
DISC-B1-EQ-HBC1
DISC-B1-EQ-HBC2
DISC-VFD-B1-EF1-1
DISC-VFD-B1-SF1-1
DISC-B1-ACCU-1
DISC-B201/B241-MINI-SPLIT-CU
DISC-B1-RTU-5
DISC-1360-VOL-SERV-CU
DISC-B1-AREA
1340-1351-RTU-7
DISC-B1-AHU-CANOPY
DISC-ECB-B1-ACC-1
DISC-2100-AREA-EF (LAB)
DISC-2100 AREA-ACCU-6 (LAB)
DISC-2100 AREA-AHU-6 (LAB)
DISC-B438-MINI-SPLIT-CU
DISC-B6 HU-1
DISC-B6 SF-1
DISC-B6 DX-1 (PB-E-H2N1-06)
DISC-B702A-22-CU-004
DISC-B6 RF-1
DISC-B6 EF-1
DISC-ECB-B6-DX-1-CP
DISC-ECB-B1-ACC-2
DISC-ECB-B1-CU-3A
DISC-B1-EF-2 DISC-ECB-RTU-3 ELEV
DISC-RTU-3 ELEV
DISC-PH4B RADIO ROOM CU
DISC-B03-CU
DISC-B102-3-CU-101
B4-CU-SOUTH
DISC-B4-106A-4-CU-101
DISC-B4-CU-SW
DISC-B4-CU-NW
DISC-B21-CU-101
DISC-B9-101-MINI-SPLIT-CU
CONSTRUCTION PANEL-1
CONSTRUCTION PANEL-2DISC-TRANSFORMER T-20
DISC-FRONT-DAKTRONICS-SIGN
DISC-100A-2-CU-101
DISC-GEN-3-RAD
DISC-B315-GIP-RM-RTU
DISC-1200-EAST-MS-CU
DISC-B1-EF-2LKR
DISC-B1-EF-STORAGE
DISC-B1-ACCU-5
DISC-EC-ACC-3
DISC-B1-FREZ-UNIT-3
DISC-B1-THAW-BOX
DISC-B22-CU-003
DISC-B22-ACRCU-1
DISC-B22-ACRCU-2
DISC-ECB-B22-ACRCU-2DISC-ECB-B22-ACRCU-1
DISC-B22-SOLAR-DC-INPUT
DISC-B22-EF-1-2
DISC-4100-AREA-CU
DISC-B1-VEGGIE-FRIDGE
DISC-B1-COOKS -COOLER
DISC-FREZ-UNIT-1
DISC-CANTEEN-HOOD-EF
DISC-GEN-2-RAD
DISC-GEN-1-RAD
DISC-ECB-B1-AREA-1100-CU-1C
DISC-FREZ-UNIT-2
DISC-B1-CHAPEL-RTU
DISC-B1-MAU-KETTLE-HOOD
DISC-B324-MINI-SPLIT-CU
DISC-RM-1331-33-MINI-SPLIT-CU
DISC-1314-MINI-SPLIT-CU
DISC-B22-CU-001DISC-B22-CU-002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
ENLARGED ELECTRICAL SITE
PLAN - SOUTH SECTION
655-26-201BID
ES-102
AutoCAD SHX Text
(66' WIDE)
AutoCAD SHX Text
EAST 1/4 CORNER SECTION 14 T. 12 N., R. 4 E. CITY OF SAGINAW
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
BM
AutoCAD SHX Text 48.46'
AutoCAD SHX Text 125.98'
AutoCAD SHX Text 87.82'
AutoCAD SHX Text N89°46'20"W
AutoCAD SHX Text N01°06'20"W
AutoCAD SHX Text 33.01'
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text (E)P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
SHEET ES-101
SHEET ES-102
S
S
P
S
P
S
P
S
P
S
P
SWBD-1 TIE
NO
SWBD-2 TIE
NSWBD-2 MAIN
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 5 (8000A)
STD 0.2 (I^s T Off)
INST 4 (6400A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T Off)
NSWBD-2 (EC)
480V, 1600A
CBL-NSWBD-2 110ft
(5) #500 CU
T-14 (EC)
1000kVA 8320V-480V 5.75%
FUSE T-14 (EC)
23000V, COOPER ELX, 8.3-23kV 100AF, 100AT, 50 AIC 100.0 Amps
CBL T-14 10ft (1) #1/0
CU
FUSE LS-5D (T-14)
12470V, S&C SMU-20, 14.4kV E-Rated
100AF, 100AT, 14 AIC 100
Amps
LS-5
8320V, 600A SCCR: 25kA
SCA: 5113A
LS5-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL LS-5A
10ft (1) #1/0 CU
NSWBD (BLDG 1)
480V, 1600A
NSWBD MCB
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 24
STPU 6 (4800A)
STD 0.2 (I^s T Off)
INST 15 (12000A)
GFP
GFPU (500-1200A) G (1040A)
GFD (0-0.4) 0.3 (I^s T Off)
CBL- NSWBD
50ft (5) #400 CU
T-3 (BLDG 1)
1000kVA 8320V-480V 5.75%
FUSE T-3 (BLDG 1)
15500V, COOPER
ELX, 8.3-23kV
40AF, 40AT, 50 AIC
40.0 Amps
S-T-3A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL T-3A
10ft (1) #1/0 CU
S-T-3B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
FUSE T-10 (BLDG 1)
15500V, COOPER
ELX, 8.3-23kV
40AF, 40AT, 50 AIC
40.0 Amps
T-10 (BLDG 1)
750kVA 8320V-208V 5.75%
CBL- SWBD-2 MAIN-1
20ft (6) #500 CU
SWBD-2 MAIN-1
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
3200AF, 3200AT, 3200AP
65 AIC
Phase
LTPU (A) 0.7 (2240A)
LTD 4
STPU 4 (8960A)
STD 0.4 (I^s T Off)
INST 8 (25600A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T Off)
SWBD-2 SECTION-1 (BLDG 1)
208V, 3200A
SWBD-2 SECTION-2 (BLDG 1)
208V, 3200A
SWBD-2 MAIN-2
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
3200AF, 3200AT, 3200AP
65 AIC
Phase
LTPU (A) 0.7 (2240A)
LTD 4
STPU 4 (8960A)
STD 0.4 (I^s T Off)
INST 15 (48000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T Off)
CBL- SWBD-2 MAIN-2
20ft (6) #500 CU
T-11 (BLDG 1)
750kVA 8320V-208V 5.75%
FUSE T-11 (BLDG 1)
15500V, COOPER
ELX, 8.3-23kV
40AF, 40AT, 50 AIC
40.0 Amps
CBL T-11
10ft (1) #1/0 CU
SWBD-1 SECTION-1 (BLDG 1)
208V, 1600A
SWBD-1 MAIN-1
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 6 (9600A)
STD 0.2 (I^s T Off)
INST 10 (16000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
CBL- SWBD-1 MAIN-1
50ft (5) #400 CU
T-1 (BLDG 1)
500kVA 8320V-208V 4.50%
FUSE T-1 (BLDG 1)
15500V, COOPER
NX (C-Rated), 15.5kV
65AF, 65AT, 50 AIC
65.0 Amps
SWBD-1 SECTION-2 (BLDG 1)
208V, 1600A
SWBD-1 MAIN-2
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 6 (9600A)
STD 0.2 (I^s T Off)
INST 10 (16000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
CBL- SWBD-1 MAIN-2
50ft (5) #400 CU
T-2 (BLDG 1)
500kVA 8320V-208V 4.50%
FUSE T-2 (BLDG 1)
15500V, COOPER
NX (C-Rated), 15.5kV
65AF, 65AT, 50 AIC
65.0 Amps
CBL T-2
10ft (1) #1/0 CU
LS5-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL LS-5B
10ft (1) #1/0 CU
CBL T-3B
10ft (1) #1/0 CU
CBL T-1
10ft (1) #1/0 CU
TAP EMH-13 JUNCTION-A
8320V, 0A SCCR: 0kA
SCA: 5118A
CBL EMH-123 (13P) JUNCTION-A
150ft (1) #4/0 CU
FUSE LS-2C (T-2,3,11,14, LS-5)
14400V, S&C SMU-20, 14.4kV E-Rated
125AF, 125AT, 14 AIC
125 Amps
CBL EMH-13 JUNCTION-B
150ft (1) #4/0 CU
FUSE LS-2D (T-1, 3, 10, LS-5)
14400V, S&C SMU-20, 14.4kV E-Rated
125AF, 125AT, 14 AIC
125 Amps
LS-2
8320V, 600A SCCR: 25kA
SCA: 5171A
LS2-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL LS-2A
580ft (1) #4/0 CU
LS4-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
LS2-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL MV FEEDER-1 (LS-2B)
220ft (1) #4/0 CU
MAIN SWITCHGEAR (FEEDER 1)
15000V, SQUARE D
VR
1200AF, 18 AIC
Phase Relay
PHASE O/C PICKUP 200 % (300A)
EXTREM INV 2
PHASE INST TRIP 15.0 (4500A)
GF Relay
GND O/C PICKUP 0.4 (60A)
VERY INV 2
GND INST TRIP 6.0 (360A)
LS-4
8320V, 600A SCCR: 25kA
SCA: 4923A
MAIN SWITCHGEAR
(BLDG. 20)
8320V, 1200A SCCR: 18kA
SCA: 5250A
MAIN MV SWITCHGEAR MCB
15000V, SQUARE D
VR
1200AF, 18 AIC
Phase Relay
PHASE O/C PICKUP 200 % (400A)
EXTREM INV 2
PHASE INST TRIP 14.0 (5600A)
GF Relay
PHASE O/C PICKUP 200 % (400A)
EXTREM INV 2
PHASE INST TRIP 14.0 (5600A)
CBL UTILITY
30ft (1) #4/0 CU
FUSE UTILITY
0V, 0AF, 0 AIC
UTILITY
Isc 3P 74 MVA Isc SLG 19 MVA
NONC
NO
CBL T-10
10ft (1) #1/0 CU
TAP EMH-123 (13P) JUNCTION-B
8320V, 0A SCCR: 0kA
SCA: 5116A
NO
NO
NC
(SEE SHEET EP-103) (SEE SHEET EP-103)
(SEE SHEET EP-102) (SEE SHEET EP-102)
(CONT. ON SHEET EP-101)
(CONT. ON SHEET EP-101)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
EP-100
BLDG. 20 & SITE
8.3KV MEDIUM VOLTAGE PRIM.
ONE-LINE DIAGRAM
ELECTRICAL MAINTENANCE
655-26-201BID
S
P
S
P
S
P
CBL T-6
20ft (1) #1/0 CU
NONE
T-6 (BLDG 9)
225kVA 8320V-480V 4.75%
CBL CB-N-HBS1-09
30ft (1) #600 CU
NONE
CB-N-HBS1-09
600V, SQUARE D
LA
400AF, 400AT, 400AP
22 AIC
Thermal Curve
INST LO (2000A)
ECB B09 CB-N-HBS1-09
480V, 400A
MDP-1 (BLDG 22)
480V, 1600A
MDP-1 MCB
480V, SQUARE D
PX, Micrologic
1600AF, 1600AT, 1600AP
100 AIC
Phase LTPU (0.5-1.0 x P) 1.0 (1600A) LTD (2-24 Sec.) 3.0 STPU (2-8 x P) 2.0 (3200A) STD (0.1-0.5 Sec.) .1 (I^s T On) INST (2.5-8 x P) 8.0 (12800A)
GFP
GFPU (0.2-0.75 x S) 0.2 (320A) GFD (0.1-0.5 Sec.) 0.5
CBL-MDP-1
60ft (3) #600 CU
T-7 SECONDARY
T-7 (BLDG 22)
750kVA 8320V-480V 5.75%
T-7 FUSE (BLDG 22)
15500V, COOPER
NX (C-Rated), 15.5kV
65AF, 65AT, 50 AIC
65.0 Amps
CBL T-7
200ft (1) #1/0 CU
FUSE LS-3C (T-7)
14400V, S&C SMU-20, 14.4kV E-Rated
80AF, 80AT, 14 AIC
80 Amps
LS4-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL LS-4B
490ft (1) #4/0 CU
LS3-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
LS-4
8320V, 600A SCCR: 25kA
SCA: 4923A
FUSE LS-3D (T-8)
14400V, S&C SMU-20, 14.4kV E-Rated
65AF, 65AT, 14 AIC
65 Amps
CBL T-8
200ft (1) #1/0 CU
FUSE T-8 (BLDG 22)
15500V, COOPER
NX (C-Rated), 15.5kV
65AF, 65AT, 50 AIC
65.0 Amps
T-8 (BLDG 22)
500kVA 8320V-208V 4.50%
CBL-MDP-2
40ft (4) #600 CU
T-8 SECONDARY
MDP-2 MCB
240V, SQUARE D
PX, Micrologic (Obs.)
1600AF, 1600AT, 1600AP
125 AIC
Phase STPU (2-8 x P) 2.0 (3200A) STD (Min-Max) MIN (I^s T On)
LTPU 1.0 (1600A)
LTD (Min-Max) INT
GFP
GFPU (1200AS) 0.2 (320A)
GFD (Inst-Max) MIN
MDP-2 (BLDG 22)
208V, 1600A
LS3-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
LS-3
8320V, 600A SCCR: 25kA
SCA: 5094A
CBL LS-3A
200ft (1) #4/0 CU
LS1-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
FUSE LS-1D (T-9)
14400V, S&C SMU-20, 14.4kV E-Rated
30AF, 30AT, 14 AIC
30 Amps
CBL T-9
40ft (1) #1/0 CU
FUSE T-9 (BLDG 3)
23000V, COOPER
ELX, 8.3-23kV
30AF, 30AT, 50 AIC
30.0 Amps
T-9 (BLDG 3)
225kVA 8320V-208V 3.80%
CBL-ECB BLDG-3
30ft (2) #600 CU
ECB BLDG-3
240V, SQUARE D
MA
1000AF, 800AT, 800AP
42 AIC
Thermal Curve
INST LO (4000A)
ECB B03 BLDG-3(S)
208V, 800A
LS1-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
CBL MV FEEDER-2 (LS1-B)
220ft (1) #4/0 CU
MAIN SWITCHGEAR (LS1-B)
FEEDER-2
15000V, SQUARE D
VR
1200AF, 18 AIC
Phase Relay
PHASE O/C PICKUP 125 % (187.5A)
EXTREM INV 3
PHASE INST TRIP 18.0 (3375A)
GF Relay
GND O/C PICKUP 0.4 (60A)
VERY INV 2
GND INST TRIP 4.0 (240A)
MAIN SWITCHGEAR
8320V, 1200A SCCR: 18kA
SCA: 5250A
MAIN SWITCHGEAR (LS6-A)
FEEDER-3
15000V, SQUARE D
VR
1200AF, 18 AIC
Phase Relay
PHASE O/C PICKUP 0.8 (120A)
EXTREM INV 3
PHASE INST TRIP 18.0 (2160A)
GF Relay
GND O/C PICKUP 0.4 (60A)
VERY INV 2
GND INST TRIP 4.0 (240A)
CBL MV FEEDER-3 (LS6-A)
795ft (1) #4/0 CU
LS6-A
15000V, GE
BreakMaster LIS
600AF, 25 AIC
LS6-B
15000V, GE
BreakMaster LIS
600AF, 25 AIC
FUSE LS-C (T-12)
14400V, S&C SMU-20, 14.4kV E-Rated
80AF, 80AT, 14 AIC
80 Amps
LS-6
8320V, 600A SCCR: 25kA
SCA: 4964A
CBL T-12
110ft (1) #2 CU
FUSE T-12 (BLDG 21)
23000V, COOPER
ELX, 8.3-23kV
80AF, 80AT, 50 AIC
80.0 Amps
T-12 (BLDG 21)
750kVA 8320V-480V 5.75%
CBL-DP-21A
30ft (4) #350 CU
T-12 SECONDARY
DP-21A MCB
480V, SQUARE D
Powerpact P-Frame PG, 5.0 & 6.0 A/P/H
1200AF, 1200AT, 1200AP
35 AIC
Phase
LTPU (A) 0.5 (600A)
LTD 2
STPU 3 (1800A)
STD 0.4 (I^s T On)
INST 3 (3600A)
GFP
GFPU (0.2-1.0 x S) D (600A) GFD (0-0.4) 0.3 (I^s T On)
PANEL DP-21A (BLDG 21)
480V, 1200A
LS4-C
15000V, GE
BreakMaster LIS
600AF, 25 AIC
FUSE LS-4C (T-6)
14400V, S&C SMU-20, 14.4kV E-Rated
30AF, 30AT, 14 AIC
30 Amps
LS-1
8320V, 600A SCCR: 25kA
SCA: 5167A
FUSE LS-1C (LS-6)
12000V, S&C SMU-20, 14.4kV E-Rated
150AF, 150AT, 14 AIC
150 Amps
CBL LS-6B
575ft (1) #4/0 CU
NO
NC
S
P
(CONT. ON SHEET EP-100)
(CONT. ON SHEET EP-100)
LS4-D
15000V, GE
BreakMaster LIS
600AF, 25 AIC
NO CONNECTION
LS6-C
15000V, GE
BreakMaster LIS
600AF, 25 AIC
NO CONNECTION
(SEE SHEET EP-117) (SEE SHEET EP-115) (SEE SHEET EP-115) (SEE SHEET EP-117) (SEE SHEET EP-117)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
EP-101
BLDG. 20 & SITE
8.3KV MEDIUM VOLTAGE PRIM.
ONE-LINE DIAGRAM
ELECTRICAL MAINTENANCE
E N
SWBD-1 SECTION-1 (BLDG 1)
208V, 1600A SCCR: 85kA
SCA: 24262A
SWBD-1 (SPARE)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 1000AT, 1000AP
100 AIC
Phase
LTPU (A) 1 (1000A)
LTD 24
STPU 10 (10000A)
STD 0.1 (I^s T Off)
INST 15 (15000A)
GFP
GFPU (0.3-1.0 x S) C (160A) GFD (0-0.4) 0.1 (I^s T Off)
CBL-ATS-A(E)
35ft (2) #4/0 CU
ESWBD (ATS-A)
CBL-ATS-A(N)
45ft (2) #4/0 CU
SWBD-1 (ATS-A)
ATS-A
480V, 400A 200.00kA SCCR
↑459A SCA
ATS A
208V, 0A SCCR: 0kA
SCA: 8134A
CBL-CDP
6ft (2) #4/0 CU
ATS A
PANEL CDP
208V, 400A SCCR: 200kA
SCA: 8047A
SWBD-1 (ATS-A)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 0.9 (360A)
LTD 24
STPU 10 (3600A)
STD 0.1 (I^s T Off)
INST 15 (6000A)
GFP
GFPU (0.3-1.0 x S) C (160A) GFD (0-0.4) 0.1 (I^s T Off)
SWBD-1 MAIN-1
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 6 (9600A)
STD 0.2 (I^s T Off)
INST 10 (16000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
SWBD-1 TIE
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 4 (6400A)
STD 0.3 (I^s T Off)
INST OFF
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
SWBD-1 MAIN-2
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
42 AIC
Phase
LTPU (A) 1 (1600A)
LTD 8
STPU 6 (9600A)
STD 0.2 (I^s T Off)
INST 10 (16000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
CBL-ATS-B(E)
35ft (2) #4/0 CU
ESWBD (ATS-B)
SWBD-1 (ATS-B)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 1 (400A)
LTD 4
STPU 8 (3200A)
STD 0.1 (I^s T On)
INST 12 (4800A)
GFP
GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)
CBL-ATS-B(N)
50ft (2) #4/0 CU
SWBD-1 (ATS-B)
ATS-B
480V, 400A 200.00kA SCCR
↑0A SCA
ATS B
208V, 0A SCCR: 0kA
SCA: 8067A
CBL-LSDP
6ft (2) #4/0 CU
ATS B
PANEL LSDP
208V, 400A SCCR: 200kA
SCA: 7969A
CBL-ATS-C(E)
40ft (3) #300 CU
ESWBD (ATS-C)
SWBD-1 (ATS-C)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 24
STPU 10 (8000A)
STD 0.1 (I^s T Off)
INST 15 (12000A)
GFP
GFPU (0.2-1.0 x S) C (320A) GFD (0-0.4) 0.1 (I^s T Off)
CBL-ATS-C(N)
30ft (3) #300 CU
SWBD-1 (ATS-C)
ATS-C
480V, 800A 200.00kA SCCR
↑0A SCA
ATS C
208V, 0A SCCR: 0kA
SCA: 8342A
CBL-EMDP
10ft (3) #300 CU
ATS C
PANEL EMDP
208V, 800A SCCR: 200kA
SCA: 8235A
SWBD-1 SECTION-2 (BLDG 1)
208V, 0A SCCR: 0kA
SCA: 24263A
E N E N
NO
SWBD-2 SECTION-1 (BLDG 1)
208V, 3200A SCCR: 65kA
SCA: 29503A SWBD-2 (LDP)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
100 AIC
Phase
LTPU (A) 0.625 (1000A)
LTD 8
STPU 4 (4000A)
STD 0.2 (I^s T Off)
INST 4 (6400A)
GFP
GFPU (500-1200A) A (500A)
GFD (0-0.4) 0.2 (I^s T Off)
CBL-LDP
35ft (3) #500 CU
SWBD-2 (LDP)
PANEL LDP
208V, 1200A SCCR: 200kA
SCA: 25621A
SWBD-2 (SPARE-1D)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 4 (3200A)
STD 0.2 (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
SWBD-2 (SPARE-2C)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
100 AIC
Phase
LTPU (A) 0.7 (1120A)
LTD 0.5
STPU 1.5 (1680A)
STD 0.1 (I^s T On)
INST 2 (3200A)
GFP
GFPU (500-1200A) A (500A)
GFD (0-0.4) 0.1 (I^s T Off)
SWBD-2 (SPARE-2D)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 4 (3200A)
STD 0.2 (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
SWBD-2 TIE
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
3200AF, 3200AT, 3200AP
65 AIC
Phase
LTPU (A) 0.7 (2240A)
LTD 4
STPU 4 (8960A)
STD 0.3 (I^s T Off)
INST 3 (9600A)
GFP
GFPU (500-1200A) E (880A)
GFD (0-0.4) 0.3 (I^s T Off)
CBL-ATS-E(E)
10ft (3) #500 CU
ESWBD (ATS-E)
SWBD-2 (ATS-E)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
100 AIC
Phase
LTPU (A) 0.5 (800A)
LTD 24
STPU 8 (6400A)
STD 0.2 (I^s T Off)
INST 6 (9600A)
GFP
GFPU (500-1200A) A (500A)
GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-E(N)
80ft (3) #500 CU
SWBD-2 (ATS-E)
ATS-E (MDP)
480V, 800A 200.00kA SCCR
↑307A SCA
ATS E (MDP)
208V, 0A SCCR: 0kA
SCA: 8692A
CBL-MDP
15ft (3) #300 CU
ATS E (MDP)
PANEL MDP
208V, 800A SCCR: 200kA
SCA: 8536A
SWBD-2 (SPARE-3C)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 4 (3200A)
STD 0.2 (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
SWBD-2 (PDP)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
1600AF, 1600AT, 1600AP
100 AIC
Phase
LTPU (A) 0.625 (1000A)
LTD 12
STPU 4 (4000A)
STD 0.1 (I^s T Off)
INST 3 (4800A)
GFP
GFPU (500-1200A) A (500A)
GFD (0-0.4) 0.1 (I^s T On)
CBL-PDP
45ft (3) #500 CU
SWBD-2 (PDP)
PDP MCB
240V, SQUARE D
Powerpact P-Frame PG/PK, 3.0 & 3.0A
1200AF, 1000AT, 1000AP
65 AIC
LTPU (A) 1 (1000A)
LTD 12
INST 4 (4000A)
PANEL PDP
208V, 1200A SCCR: 200kA
SCA: 24688A
SWBD-2 (SPARE-4D)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 4 (3200A)
STD 0.2 (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.2 (I^s T Off)
SWBD-2 SECTION-2 (BLDG 1)
208V, 3200A SCCR: 65kA
SCA: 29505A
SWBD-2 MAIN-2
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
3200AF, 3200AT, 3200AP
65 AIC
Phase
LTPU (A) 0.7 (2240A)
LTD 4
STPU 4 (8960A)
STD 0.4 (I^s T Off)
INST 15 (48000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T Off)
SWBD-2 MAIN-1
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
3200AF, 3200AT, 3200AP
65 AIC
Phase
LTPU (A) 0.7 (2240A)
LTD 4
STPU 4 (8960A)
STD 0.4 (I^s T Off)
INST 8 (25600A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T Off)
NO
FED FROM T-1
(SEE SHEET EP-100)
FED FROM T-2
(SEE SHEET EP-100)
FED FROM T-10
(SEE SHEET EP-100)
FED FROM T-11
(SEE SHEET EP-100)
FED FROM ESWBD
(SEE SHEET EP-104)
(SEE SHEET EP-106) (SEE SHEET EP-106)
FED FROM ESWBD
(SEE SHEET EP-104)
FED FROM ESWBD
(SEE SHEET EP-104)
(SEE SHEET EP-105)
(SEE SHEET EP-111)
FED FROM ESWBD
(SEE SHEET EP-104)
(SEE SHEET EP-107)
(SEE SHEET EP-111)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
EP-102
BLDG. 1 NORMAL POWER
SWBD-1 & SWBD-2
ONE-LINE DIAGRAM
ELECTRICAL MAINTENANCE
E NE N
P
E N E N
NSWBD (SPARE1)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 1 (400A)
LTD 4
STPU 4 (1600A)
STD 0.1 (I^s T Off)
INST 3 (1200A)
GFP
GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)
NSWBD (SPARE2)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 0.8 (320A)
LTD 4
STPU 4 (1280A)
STD 0.1 (I^s T Off)
INST 3 (1200A)
GFP
GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)
NSWBD (BA1)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 600AT, 600AP
100 AIC
Phase
LTPU (A) 1 (600A)
LTD 4
STPU 4 (2400A)
STD 0.1 (I^s T Off)
INST 15 (9000A)
GFP
GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)
CBL-BA1 (480V)
20ft (2) #350 CU
NSWBD (BA1)
NSWBD (NDP)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 0.9 (360A)
LTD 4
STPU 4 (1440A)
STD 0.1 (I^s T Off)
INST 15 (6000A)
GFP
GFPU (0.3-1.0 x S) F (280A) GFD (0-0.4) 0.1 (I^s T Off)
CBL-NDP
292ft (2) #500 CU
NSWBD (NDP)
NSWBD (XRAY GEN)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 250AT, 250AP
65 AIC
Phase
LTPU (A) 1 (250A)
LTD 16
STPU 10 (2500A)
STD 0.1 (I^s T Off)
INST 10 (2500A)
INST OR Fixed (24000A)
GFP
GFPU (0.3-1.0 x S) A (75A) GFD (0-0.4) 0.1 (I^s T On)
CBL-XRAY GEN
286ft (1) #3/0 CU
JB IN CORRIDOR
480V, 0A SCCR: 0kA
SCA: 6962A
CBL-XRAY GEN-1
256ft (1) #250 CU
ECB-XRAY GEN
600V, SQUARE D
FA
100AF, 100AT, 100AP
14 AIC
Fixed
ECB B01 XRAY GEN
480V, 100A SCCR: 10kA
SCA: 4342A
CBL-ATS-F(E)
160ft (2) #500 CU
DP-E-BEC-C (ATS-F)
NSWBD (DP-EQ-BA3-01)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 12
STPU 4 (3200A)
STD INST (I^s T Off)
INST OFF
GFP
GFPU (0.2-1.0 x S) G (640A) GFD (0-0.4) 0.2 (I^s T On)
CBL-ATS-F(N)
10ft (2) #500 CU
NSWBD (DP-EQ-BA3-01)
ATS-F (BYPASS ISO)
480V, 800A 200.00kA SCCR
↑791A SCA
ATS F
480V, 0A SCCR: 0kA
SCA: 9234A
CBL-DP-EQ-BA3-01
20ft (2) #500 CU
ATS F
NSWBD (DP-EQ-6HB)
508V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 600AT, 600AP
100 AIC
Phase
LTPU (A) 1 (600A)
LTD 16
STPU 8 (4800A)
STD 0.2 (I^s T On)
INST 8 (4800A)
GFP
GFPU (0.2-1.0 x S) E (360A) GFD (0-0.4) 0.2 (I^s T On)
CBL- ATS G(N)
20ft (2) #350 CU
NSWBD (DP-EQ-6HB)
ATS-G (BYPASS ISO)
0V, 0A 0.00kA SCCR
↑2127A SCA
ATS G PANEL DP-EQ-6HB
480V, 0A SCCR: 0kA
SCA: 17930A
CBL-DP-EQ-6HB
200ft (2) #350 CU
ATS G PANEL DP-EQ-6HB
DP-EQ-6HB MCB
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 600AT, 600AP
35 AIC
Thermal Curve
INST 8 (4800A)
INST OR (Fixed, No User-Adjustable Setting) Fixed (6000A)
PANEL DP-EQ-6HB
480V, 0A SCCR: 0kA
SCA: 14064A
NSWBD (BLDG 1)
480V, 1600A SCCR: 85kA
SCA: 18453A
NSWBD-2 (DP-N-BEC-A1)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 250AT, 250AP
85 AIC
Phase
LTPU (A) 0.8 (200A)
LTD 8
STPU 10 (2000A)
STD 0.1 (I^s T On)
INST 12 (3000A)
INST OR Fixed (24000A)
GFP
GFPU (0.3-1.0 x S) E (150A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-DP-N-BEC-A1
25ft (1) #250 CU
PANEL DP-N-BEC-A1
480V, 250A SCCR: 35kA
SCA: 14530A
DP-N-BEC-A1 (RP-N-BEC-A2)
480V, SQUARE D
EG
125AF, 125AT, 125AP
35 AIC
Fixed
CBL-T23 (RP-N-BEC-A2)
25ft (1) #1 CU
T-23 (RP-N-BEC-A2)
75kVA 480V-208V 3.58%
CBL-RP-N-BEC-A2
25ft (1) #4/0 CU
RP-N-BEC-A2 MCB
240V, SQUARE D
QD
225AF, 225AT, 225AP
25 AIC
Fixed
PANEL RP-N-BEC-A2
208V, 225A SCCR: 22kA
SCA: 4603A
RP-N-BEC-A2 (RP-N-2EC-A3)
240V, SQUARE D
QO-VH, 3-Pole
100AF, 100AT, 100AP
22 AIC
Fixed (730-8)
CBL-RP-N-2EC-A3
30ft (1) #2 CU
RP-N-2EC-A3 MCB
240V, SQUARE D
QD
100AF, 100AT, 100AP
25 AIC
Fixed
PANEL RP-N-2EC-A3
208V, 100A SCCR: 22kA
SCA: 3731A
NSWBD-2 (DP-N-1EC-A4)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 250AT, 250AP
85 AIC
Phase
LTPU (A) 0.8 (200A)
LTD 24
STPU 10 (2000A)
STD 0.2 (I^s T On)
INST 15 (3750A)
INST OR Fixed (24000A)
GFP
GFPU (0.3-1.0 x S) A (75A) GFD (0-0.4) 0.1 (I^s T On)
CBL-DP-N-1EC-A4
35ft (1) #3/0 CU
DP-N-1EC-A4 MCB
480V, SQUARE D
J-Frame, Powerpact
250AF, 175AT, 175AP
18 AIC
Thermal Curve INST (5-10 x Trip) High (1750A)
PANEL DP-N-1EC-A4
480V, 250A SCCR: 35kA
SCA: 13784A
DP-N-BEC-A4 (EC HU-3)
480V, SQUARE D
J-Frame, Powerpact
250AF, 175AT, 175AP
18 AIC
Thermal Curve INST (5-10 x Trip) High (1750A)
CBL-EC-H-3
50ft (1) #2/0 CU
NFDS-EC-H-3
600V, UL 98
DS
200AF, 10 AIC
DISC-EC-H-3
480V, 0A SCCR: 0kA
SCA: 11201A
NSWBD-2 (SPARE1)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase LTPU/LTD (A 0.4-1.0 x S) 0.7 (280A); 24 STPU (1.5-10 x LTPU) 10 (2800A) STD (INST-0.4) 0.2 (I^s T Off)
GFP
GFPU (0.3-1.0 x S) E (240A) GFD (0-0.4) 0.2 (I^s T Off)
NSWBD-2 (SPARE2)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 100AT, 100AP
65 AIC
Phase
LTPU (A) 1 (100A)
LTD 8
STPU 6 (600A)
STD 0.2 (I^s T Off)
GFP
GFPU (0.3-1.0 x S) J (100A) GFD (0-0.4) 0.2 (I^s T Off)
NSWBD-2 (SPARE3)
508V, SQUARE D
Masterpact NW, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 8 STPU (1.5-10 x LTPU) 6 (2400A) STD (INST-0.4) 0.2 (I^s T Off)
GFP
GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.2 (I^s T Off)
NSWBD-2 (ATS-1)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 1 (800A)
LTD 8
STPU 5 (4000A)
STD INST (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) G (480A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-1(E)
90ft (2) #350 CU
DP-E-BEC-C (ATS-1)
CBL-ATS-1(N)
30ft (2) #350 CU
NSWBD-2 (ATS-1)
ATS-1 (BYPASS ISO)
480V, 800A 200.00kA SCCR
↑2344A SCA
ATS 1
480V, 0A SCCR: 0kA
SCA: 9910A
CBL-ATS-2(E)
80ft (2) #500 CU
DP-E-BEC-C (ATS-2)
NSWBD-2 (ATS-2)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 1 (800A)
LTD 24
STPU 8 (6400A)
STD 0.2 (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) F (560A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-2(N)
120ft (2) #500 CU
NSWBD-2 (ATS-2)
ATS-2 (BYPASS ISO)
480V, 600A 200.00kA SCCR
↑0A SCA
ATS 2
480V, 0A SCCR: 0kA
SCA: 9666A
NSWBD-2 (EC)
480V, 1600A SCCR: 85kA
SCA: 15844A
CBL-EMCC-E-BEC-C2
160ft (2) #350 CU
DP-E-BEC-C (ATS-G)
DP-EQ-BA3-01 MCB
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 800AT, 800AP
35 AIC
Thermal Curve
INST 5 (4000A)
INST OR (Fixed, No User-Adj. Setting) Fixed (8000A)
PANEL DP-EQ-BA3-01
480V, 800A SCCR: 200kA
SCA: 9108A
(SEE SHEET EP-112) (SEE SHEET EP-112)
FED FROM ESWBD
(SEE SHEET EP-104)
FED FROM ESWBD
(SEE SHEET EP-104)
(SEE SHEET EP-105) (SEE SHEET EP-109)
FED FROM ESWBD
(SEE SHEET EP-104)
FED FROM ESWBD
(SEE SHEET EP-104)
(SEE SHEET EP-110) (SEE SHEET EP-108)
FED FROM T-3
(SEE SHEET EP-100)
FED FROM T-14
(SEE SHEET EP-100)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
EP-103
BLDG. 1 NORMAL POWER
NSWBD & NSWBD-2
ONE-LINE DIAGRAM
ELECTRICAL MAINTENANCE
GEN2-LOADBANK
GEN6-LOADBANK
E N E N E N
E N E N E N E N
E N
GEN-1
400kW/500kVA 208V
SCA: 9241A
GEN-1 CB
240V, MERLIN GERIN
Compact CK, STR 25DP
1200AF, 1200AT, 1000AP
65 AIC
LTPU (0.8-1.0 x P) 1 (1000A) LTD (Fixed) Fixed INST (1.5-10 x LTPU) 10 (10000A) INST Delay (Fixed) Fixed INST Override Fixed (14400A)
ECB B19 GEN-1
208V, 0A SCCR: 0kA
SCA: 9689A
CBL- B19 GEN-1-PUMP
5ft (1) #4 CU
FUSE-B19 GEN-1-PUMP
250V, BUSSMANN
DLN-R, 250V Class RK5
35AF, 35AT, 200 AIC
DISC-B19 GEN-1-PUMP
208V, 0A SCCR: 0kA
SCA: 9503A
CBL- ESWBD GEN-1
100ft (3) #500 CU
CBL- B19 GEN-1-RAD
30ft (1) #10 CU
FUSE-B19 GEN-1-RAD
250V, BUSSMANN
DLN-R, 250V Class RK5
35AF, 35AT, 200 AIC
START-B19 GEN-1-RAD
208V, 0A SCCR: 0kA
SCA: 8661A
CBL- DISC-B19 GEN-1-RAD
30ft (1) #10 CU
DISC-B19 GEN-1-RAD
208V, 0A SCCR: 0kA
SCA: 7812A
CB GEN1-LOADBANK
0V, 0AF, 0AP
0 AIC
CBL- GEN1-LOADBANK
30ft (3) #4/0 CU
GEN1-LOADBANK
ESWBD GEN-1
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 0.8 (640A)
LTD 8
STPU 10 (6400A)
STD 0.1 (I^s T Off)
INST 15 (12000A)
GFP
GFPU (500-1200A) C (720A)
GFD (0-0.4) 0.1 (I^s T Off)
ESWBD SECTION-1 (BLDG 1)
208V, 1600A SCCR: 85kA
SCA: 8667A ESWBD (ATS-A)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 1 (400A)
LTD 12
STPU 10 (4000A)
STD 0.1 (I^s T On)
INST 12 (4800A)
GFP
GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)
CBL-ATS-A(E)
35ft (2) #4/0 CU
ESWBD (ATS-A)
CBL-ATS-A(N)
45ft (2) #4/0 CU
SWBD-1 (ATS-A)
ATS-A
480V, 400A 200.00kA SCCR
↑459A SCA
ATS A
208V, 0A SCCR: 0kA
SCA: 8134A
ESWBD (ATS-B)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 400AT, 400AP
100 AIC
Phase
LTPU (A) 1 (400A)
LTD 4
STPU 8 (3200A)
STD 0.1 (I^s T On)
INST 12 (4800A)
GFP
GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)
CBL-ATS-B(E)
35ft (2) #4/0 CU
ESWBD (ATS-B)
CBL-ATS-B(N)
50ft (2) #4/0 CU
SWBD-1 (ATS-B)
ATS-B
480V, 400A 200.00kA SCCR
↑0A SCA
ATS B
208V, 0A SCCR: 0kA
SCA: 8067A
ESWBD TIE
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1000AT, 1000AP
42 AIC
Phase
LTPU (A) 1 (1000A)
LTD 0.5
STPU 1.5 (1500A)
STD 0.1 (I^s T Off)
INST 2 (2000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.3 (I^s T Off)
ESWBD (SPARE1)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 4 (3200A)
STD 0.1 (I^s T On)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)
ESWBD (ATS-E)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 16
STPU 5 (4000A)
STD INST (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)
CBL-ATS-E(E)
10ft (3) #500 CU
ESWBD (ATS-E)
ATS-E (MDP)
480V, 800A 200.00kA SCCR
↑307A SCA
ATS E (MDP)
208V, 0A SCCR: 0kA
SCA: 8692A
CBL-ATS-E(N)
80ft (3) #500 CU
SWBD-2 (ATS-E)
ESWBD (ATS-C)
254V, SQUARE D
Masterpact NW H3, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
100 AIC
Phase
LTPU (A) 1 (800A)
LTD 24
STPU 8 (6400A)
STD 0.1 (I^s T On)
INST 8 (6400A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)
CBL-ATS-C(E)
40ft (3) #300 CU
ESWBD (ATS-C)
CBL-ATS-C(N)
30ft (3) #300 CU
SWBD-1 (ATS-C)
ATS-C
480V, 800A 200.00kA SCCR
↑0A SCA
ATS C
208V, 0A SCCR: 0kA
SCA: 8342A
ESWBD SECTION-2 (BLDG 1)
208V, 1600A SCCR: 85kA
SCA: 8790A
ESWBD GEN-2
254V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
1600AF, 1000AT, 1000AP
42 AIC
Phase
LTPU (A) 1 (1000A)
LTD 24
STPU 8 (8000A)
STD 0.3 (I^s T On)
INST 8 (8000A)
GFP
GFPU (500-1200A) J (1200A)
GFD (0-0.4) 0.4 (I^s T On)
DISC-B19 GEN-2-PUMP
208V, 0A SCCR: 0kA
SCA: 9698A
FUSE-B19 GEN-2-PUMP
250V, BUSSMANN
DLN-R, 250V Class RK5
20AF, 20AT, 200 AIC
CBL- B19 GEN-2-PUMP
5ft (1) #12 CU
CBL- ESWBD GEN-2
100ft (3) #500 CU
CBL- B19 GEN-2-RAD
5ft (1) #6 CU
FUSE-B19 GEN-2-RAD
250V, BUSSMANN
DLN-R, 250V Class RK5
60AF, 60AT, 200 AIC
START-B19 GEN-2-RAD
208V, 0A SCCR: 0kA
SCA: 9698A
CBL- B19 GEN-2-RAD (DISC)
10ft (1) #10 CU
DISC-B19 GEN-2-RAD
208V, 0A SCCR: 0kA
SCA: 9331A
CB GEN2-LOADBANK
0V, 0AF, 0AP
0 AIC
CBL- GEN2-LOADBANK
25ft (3) #4/0 CU
ECB B19 GEN-2
208V, 0A SCCR: 0kA
SCA: 9890A
GEN-2 CB
480V, GE
SS, SH PowerBreak II, MVT Plus/PM
1600AF, 1000AT, 1000AP
65 AIC
LTPU (0.5-1.0 x P) 1 (1000A)
LTD (1-4) 4
INST (1.5-10 x P) 10 (10000A)
GEN-2
415kW/519kVA 208V
SCA: 9587A
GEN-6
750kW/938kVA 480V
SCA: 7508A
GEN-6 CB
480V, GE
SS, SH PowerBreak II, EGTU
1600AF, 1600AT, 1200AP
100 AIC
LTPU 0.95X (1140A)
LTD C-10
STPU 1.5X (1710A)
STD ST10-Int (I^s T Off)
INST ST(ON) 10X (12000A)
Override (HSIOC) Fixed (46000A)
CBL-DP-E-2EC-C
75ft (4) #350 CU
CBL- GEN6-LOADBANK
75ft (5) #4/0 CU
GENERATOR 6 BUS
480V, 0A SCCR: 0kA
SCA: 10535A
DP-E-BEC-C (ATS-2)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 1 (800A)
LTD 4
STPU 8 (6400A)
STD 0.1 (I^s T Off)
INST 3 (2400A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-2(E)
80ft (2) #500 CU
DP-E-BEC-C (ATS-2)
CBL-ATS-2(N)
120ft (2) #500 CU
NSWBD-2 (ATS-2)
ATS-2 (BYPASS ISO)
480V, 600A 200.00kA SCCR
↑0A SCA
ATS 2
480V, 0A SCCR: 0kA
SCA: 9666A
DP-E-BEC-C (ATS-1)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 1 (800A)
LTD 8
STPU 5 (4000A)
STD INST (I^s T Off)
INST 6 (4800A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-1(E)
90ft (2) #350 CU
DP-E-BEC-C (ATS-1)
CBL-ATS-1(N)
30ft (2) #350 CU
NSWBD-2 (ATS-1)
ATS-1 (BYPASS ISO)
480V, 800A 200.00kA SCCR
↑2344A SCA
ATS 1
480V, 0A SCCR: 0kA
SCA: 9910A
DP-E-BEC-C (ATS-F)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 800AT, 800AP
42 AIC
Phase
LTPU (A) 1 (800A)
LTD 12
STPU 4 (3200A)
STD 0.2 (I^s T On)
INST 4 (3200A)
GFP
GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)
CBL-ATS-F(E)
160ft (2) #500 CU
DP-E-BEC-C (ATS-F)
CBL-ATS-F(N)
10ft (2) #500 CU
NSWBD (DP-EQ-BA3-01)
ATS-F (BYPASS ISO)
480V, 800A 200.00kA SCCR
↑791A SCA
ATS F
480V, 0A SCCR: 0kA
SCA: 9234A
DP-E-BEC-C (ATS-G)
508V, SQUARE D
Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H
800AF, 600AT, 600AP
42 AIC
Phase
LTPU (A) 1 (600A)
LTD 16
STPU 8 (4800A)
STD 0.1 (I^s T Off)
INST 2 (1200A)
GFP
GFPU (0.2-1.0 x S) G (480A) GFD (0-0.4) 0.2 (I^s T On)
CBL-EMCC-E-BEC-C2
160ft (2) #350 CU
DP-E-BEC-C (ATS-G)
CBL- ATS G(N)
20ft (2) #350 CU
NSWBD (DP-EQ-6HB)
ATS-G (BYPASS ISO)
0V, 0A 0.00kA SCCR
↑2127A SCA
ATS G PANEL DP-EQ-6HB
480V, 0A SCCR: 0kA
SCA: 17930A
PANEL DP-E-2EC-C (EC)
480V, 1600A SCCR: 85kA
SCA: 10385A
G G
NO
G
FED FROM SWBD-1
(SEE SHEET EP-102)
FED FROM SWBD-1
(SEE SHEET EP-102)
FED FROM SWBD-2
(SEE SHEET EP-102)
FED FROM SWBD-1
(SEE SHEET EP-102)
FED FROM NSWBD-2
(SEE SHEET EP-103)
FED FROM NSWBD-2
(SEE SHEET EP-103)
FED FROM NSWBD
(SEE SHEET EP-103)
FED FROM NSWBD
(SEE SHEET EP-103)
(SEE SHEET EP-102) (SEE SHEET EP-102) (SEE SHEET EP-102) (SEE SHEET EP-102)
(SEE SHEET EP-103) (SEE SHEET EP-103) (SEE SHEET EP-103) (SEE SHEET EP-103)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
ALEDA E. LUTZ MEDICAL CTR.
Project Director
Issue date Chkd By JAJ Revisions: Date:
EP-104
BLDG. 1 EM. POWER
GEN-1, 2, 6, ESWBD, DP-E-2EC-C
ONE-LINE DIAGRAM
ELECTRICAL MAINTENANCE
EMDP (EQBD)
240V, SQUARE D
QD
150AF, 150AT, 150AP
25 AIC
Fixed
CBL-EQBD
277ft (1) #4/0 CU
PANEL EQBD
208V, 225A SCCR: 22kA
SCA: 3472AEQBD (B321 WASHER)
240V, SQUARE D
Q1 (Obs.)
30AF, 30AT, 30AP
5 AIC
Fixed
CBL-B321-WASHER
75ft (1) #10 CU
FUSE-B321 WASHER
250V, BUSSMANN
FRN-R, 250V Class RK5
20AF, 20AT, 200 AIC
DISC-B321 WASHER
208V, 0A SCCR: 0kA
SCA: 3000A
EQBD (B321 DRYER)
240V, SQUARE D
Q1 (Obs.)
100AF, 100AT, 100AP
5 AIC
Fixed
CBL-B321-DRYER
75ft (1) #2 CU
FUSE-321 DRYER
250V, BUSSMANN
FRN-R, 250V Class RK5
100AF, 100AT, 200 AIC
DISC-321-DRYER
208V, 0A SCCR: 0kA
SCA: 3000A
EQBD (B330 HUM.)
240V, SQUARE D
Q1 (Obs.)
30AF, 30AT, 30AP
5 AIC
Fixed
CBL-B330 HUMIDIFIER
75ft (1) #12 CU
B330 HUMIDIFIER
208V, 0A SCCR: 0kA
SCA: 3000A
EQBD (B1-DOCK LIFT)1
240V, SQUARE D
QO-VH, 3-Pole
20AF, 20AT, 20AP
22 AIC
Fixed (730-4, 20A)
CBL-B338-MINI-SPLIT-CU
75ft (1) #12 CU
NONE
DISC-B338-MINI-SPLIT-CU
208V, 0A SCCR: 0kA
SCA: 0A
DISC-B324-MINI-SPLIT-CU
208V, 0A SCCR: 0kA
SCA: 0A
CBL-B324-MINI-SPLIT-CU
75ft (1) #12 CU
NONE
EQBD (B324-MINI-SPLIT-CU)
240V, SQUARE D
QO-VH, 3-Pole
30AF, 30AT, 30AP
22 AIC
Fixed (730-5, 30A)
DISC-B1-DOCK-LIFT
208V, 0A SCCR: 0kA
SCA: 732A
CBL-B1-DOCK-LIFT
75ft (1) #12 CU
NONE
EQBD (B1-DOCK LIFT)
240V, SQUARE D
QO-VH, 3-Pole
20AF, 20AT, 20AP
22 AIC
Fixed (730-4, 20A)
CBL-DP-EQ-BA3-01
20ft (2) #500 CU
ATS F
DP-EQ-BA3-01 MCB
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 800AT, 800AP
35 AIC
Thermal Curve
INST 5 (4000A)
INST OR (Fixed, No User-Adjustable Setting) Fixed (8000A) PANEL DP-EQ-BA3-01
480V, 800A SCCR: 200kA
SCA: 9108ADP-EQ-BA3-01 (AIR CURTAIN)
480V, SQUARE D
HD
40AF, 40AT, 40AP
18 AIC
Fixed
CBL-AIR-CURTAIN
150ft (1) #8 CU
NONE
DISC-AIR-CURTAIN
480V, 0A SCCR: 0kA
SCA: 2083A
DP-EQ-BA3-01 (EQP-1)
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 600AT, 600AP
35 AIC
Thermal Curve
INST 4 (2400A)
CBL-EQP-1.
146ft (2) #350 CU
DP-EQ-BA3-01 (EQP-1)
EQP-1-MCB
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 600AT, 600AP
35 AIC
Thermal Curve
INST 4 (2400A)
DP-EQ-BA3-01 (B01 FRONT ELEV)
600V, SQUARE D
HG
100AF, 100AT, 100AP
18 AIC
Fixed
CBL-B01 FRONT ELEV
260ft (1) #4 CU
NONE
DISC-B01 FRONT ELEV
480V, 0A SCCR: 0kA
SCA: 2778A
CBL-EQH-BC-TAP-1
275ft (1) #350 CU
NONE
DP-EQ-BA3-01 (EQH-BC TAP)
480V, SQUARE D
MG w/ ET1.0, 2-8x Inst.
800AF, 300AT, 300AP
35 AIC
Thermal Curve
INST 4 (1200A)
CBL-B1-EQ-HBC
10ft (1) #4/0 CU
NONE
DISC-B1-EQ-HBC
480V, 0A SCCR: 0kA
SCA: 5921A
FUSE-B1-EQ-HBC
600V, BUSSMANN
FRS-R, 600V Class RK5
200AF, 200AT, 200 AIC
CBL-PANEL-EQ-HBC
6ft (1) #4/0 CU
NONE
PANEL EQ-HBC
480V, 0A SCCR: 0kA
SCA: 5869AEQ-HBC (B100 AREA AHU-8)
480V, SQUARE D
ED
15AF, 15AT, 15AP
18 AIC
Fixed
CBL-B100 AREA-AHU-8
100ft (1) #12 CU
NONE
DISC-B100 AREA-AHU-8
480V, 0A SCCR: 0kA
SCA: 1319A
DISC-B100 AREA-CU-8
480V, 0A SCCR: 0kA
SCA: 1921A
CBL-B100 AREA-CU-8
100ft (1) #10 CU
NONE
EQ-HBC (B100 AREA-CU-8)
480V, SQUARE D
ED
35AF, 35AT, 35AP
18 AIC
Fixed
START-B100 AREA-RF-8
480V, 0A SCCR: 0kA
SCA: 2693A
FUSE-B100 AREA-RF-8
0V, 0AF, 0 AIC
CBL-START-B100 AREA-RF-8
40ft (1) #12 CU
NONE
EQ-HBC (B100 AREA-RF-8)
480V, SQUARE D
ED
15AF, 15AT, 15AP
18 AIC
Fixed
TAP EQH-BC
480V, 0A SCCR: 0kA
SCA: 6008A
CBL-DISC-EQ-HBC1
50ft (1) #350 CU
NONE
DISC-B1-EQ-HBC1
480V, 0A SCCR: 0kA
SCA: 5647A
FUSE-DISC-B1-EQ-HBC1
600V, BUSSMANN
FRS-R, 600V Class RK5
300AF, 300AT, 200 AIC
CBL-DISC-B1-EQ-HBC2
50ft (1) #350 CU
NONE
DISC-B1-EQ-HBC2
480V, 0A SCCR: 0kA
SCA: 5485A
FUSE-B1-EQ-HBC2
600V, BUSSMANN
FRS-R, 600V Class RK5
100AF, 100AT, 200 AIC
CBL-TAP-B1-EQ-HBC2
150ft (1) #4 CU
NONE
TAP-B1-EQ-HBC2
480V, 0A SCCR: 0kA
SCA: 0AFUSE-B34-EQ-H1S2
600V, BUSSMANN
FRS-R, 600V Class RK5
40AF, 40AT, 200 AIC
CBL-TAP-B1-EQ-HBC3
10ft (1) #4 CU
NONE
DISC-B34-EQ-H1S2
480V, 0A SCCR: 0kA
SCA: 0A
T-32 225kVA 480V-208V 3.90%
PB-EQ-1S1-34
208V, 0A SCCR: 0kA
SCA: 7085A
CBL-DISC-B34-EQ-H1S1
1ft (1) #12 CU
NONE
DISC-B34-EQ-H1S3
480V, 0A SCCR: 0kA
SCA: 0A
FUSE-B34-EQ-H1S3
600V, BUSSMANN
FRS-R, 600V Class RK5
40AF, 40AT, 200 AIC
CBL-TAP-B1-EQ-HBC4
10ft (1) #4 CU
NONE
DISC-B34-EQ-H1S1
480V, 0A SCCR: 0kA
SCA: 0A
EMDP (EQBB2)
240V, SQUARE D
QD
200AF, 200AT, 200AP
25 AIC
Fixed
CBL-EQBB2
282ft (1) #250 CU
EQBB2 (B1-HTP-1-P1)
240V, SQUARE D
Q1 (Obs.)
20AF, 20AT, 20AP
5 AIC
Fixed
CBL-B1-HTP-1-P1
50ft (1) #12 CU
FUSE-B1-HTP-1-P1
250V, BUSSMANN
FRN-R, 250V Class RK5
15AF, 15AT, 200 AIC
DISC-VFD-B1-HTP-1-P1
208V, 0A SCCR: 0kA
SCA: 3235A
EQBB2 (B1-HTP-1-P2)
240V, SQUARE D
Q1 (Obs.)
30AF, 30AT, 30AP
5 AIC
Fixed
CBL-B1-HTP-1-P2
50ft (1) #12 CU
NONE
FUSE-B1-HTP-1-P2
250V, BUSSMANN
FRN-R, 250V Class RK5
15AF, 15AT, 200 AIC
DISC-VFD-B1-HTP-1-P2
208V, 0A SCCR: 0kA
SCA: 3235A
EQBB2-(MORGUE-AHU)
240V, SQUARE D
Q1 (Obs.)
30AF, 30AT, 30AP
5 AIC
Fixed
CBL-1B-MORGUE-AHU
50ft (1) #10 CU
FUSE-…