S02 - Attachment D2 - ITM Drawings.pdf

PDF 5 MB Posted

Attached to
J061--Electrical Inspection, Testing & Maintenance Follow on Base | Start: 11/1/25
Solicitation number
36C25026Q0069
Issued by

About this file

These are electrical engineering design drawings for the Aleda E. Lutz VA Medical Center located in Saginaw, Michigan, with the project number 655-26-201 for Electrical Maintenance and Testing. The comprehensive set of 38 drawings covers multiple aspects of the facility's electrical infrastructure, including:

The drawings detail medium voltage distribution (8.3kV), electrical site plans, one-line diagrams for normal and emergency power systems, and riser diagrams for multiple buildings (Buildings 1, 6, 9, 21, 22, 30, 35, 38). The electrical system includes multiple generators (GEN-1 through GEN-7 ranging from 350kW to 750kW), transformers with various capacities (45kVA to 1000kVA), and complex switchboard and distribution panel configurations across normal, emergency, critical, and life safety power branches. The designs show intricate electrical routing, grounding details, and power metering systems for the VA Medical Center's comprehensive electrical infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WEISS STREET

EC

Weiss St

N M as on

S t

Davenport Ave

State St

Interstate 675

N M ic hi ga n

Av e

Sc ha ef er

S t

N

CAMPUS AREA MAP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

PROJECT NO. 655-26-501 BREAKER TESTING & MAINTENANCE

ALEDA E. LUTZ VA MEDICAL CENTER

DEPARTMENT OF VETERANS AFFAIRS

1500 WEISS ST. SAGINAW, MICHIGAN

VICINITY MAP

COVER SHEET

ELECTRICAL MAINTENANCE

& TESTING

655-26-201BID

G1.1

DRAWING SHEET INDEX

SHEET # SHEET TITLE SHEET DESCRIPTION

1 G1.1 COVER SHEET

2 G1.2 LEGEND & NOTES

3 ES-100 OVERALL ELECTRICAL SITE PLAN

4 ES-101 ENLARGED ELECTRICAL SITE PLAN - NORTH SECTION

5 ES-102 ENLARFED ELECTRICAL SITE PLAN - SOUTH SECTION

6 EP-100 BLDG. 20 & SITE 8.3KV MEDIUM VOLTAGE PRIM. ONE-LINE DIAGRAM

7 EP-101 BLDG. 20 & SITE 8.3KV MEDIUM VOLTAGE PRIM. ONE-LINE DIAGRAM

8 EP-102 BLDG. 1 NORMAL POWER SWBD-1 & SWBD-2 ONE-LINE DIAGRAM

9 EP-103 BLDG. 1 NORMAL POWER NSWBD & NSWBD-2 ONE-LINE DIAGRAM

10 EP-104 BLDG. 1 EM. POWER GEN-1, 2, 6, ESWBD, DP-E-2EC-C ONE-LINE DIAGRAM

11 EP-105 BLDG. 1 EM. POWER PANELS EMDP & DP-EQ-BA3-01 ONE-LINE DIAGRAM

12 EP-106 BLDG. 1 EM. POWER CRITICAL & LIFE SAFETY ONE-LINE DIAGRAM

13 EP-107 BLDG. 1 EM. POWER PANEL MDP, EP4, EQ2A1, EQ2D ONE-LINE DIAGRAM

14 EP-108 BLDG. 1 EM. POWER EB-E-1, MCC-P4D, EQBE-1 & 2 ONE-LINE DIAGRAM

15 EP-109 BLDG. 1 EM. POWER PANELS EQP-1, DP-EQ-6HB ONE-LINE DIAGRAM

16 EP-110 BLDG. 1 EM. POWER PANEL EMCC-E-BEC-C1 ONE-LINE DIAGRAM

17 EP-111 BLDG. 1 NORMAL POWER PANELS LDP & PDP ONE-LINE DIAGRAM

18 EP-112 BLDG. 1 NORMAL POWER (480V) PANELS NDP & DP-N-BA2-01 ONE-LINE DIAGRAM

19 EP-113 BLDG. 22 EM. POWER GENERATOR #3 ONE-LINE DIAGRAM

20 EP-114 BLDG. 22 EM. POWER PANELS DP-EMA, CDP, ELEV, LSD ONE-LINE DIAGRAM

21 EP-115 BLDG. 22 NORMAL POWER PANELS MDP-1 & MDP-2 ONE-LINE DIAGRAM

22 EP-116 BLDG. 22 NORMAL POWER PANELS MCC-B1, 1, 3, 4, M3, & M4 ONE-LINE DIAGRAM

23 EP-117 BLDG. 21 EM. & NORMAL POWER GEN. #7, EDP-21A, DP-21A ONE-LINE DIAGRAM

24 EP-118 BLDG. 21 EM. POWER PANELS EDP-21B ONE-LINE DIAGRAM

25 EP-119 BLDG. 9 & 35 EM. POWER DP-E-HBS1-09, DP-E-BS1-09 ONE-LINE DIAGRAM

26 EP-120 BLDG. 6 EM. POWER DP-E-H1N1-06, PB-E-H2N1-06 ONE-LINE DIAGRAM

27 EP-121 BLDG, 2, 3, 4, 30, 38 EM. POWER DP-E-H1N1-06, PB-E-H2N1-06 ONE-LINE DIAGRAM

28 EP-201 BUILDING 22 DISTRIBUTION RISER DIAGRAM

29 EP-202 BUILDING 22 EMERGENCY POWER RISER DIAGRAM

30 EP-203 BUILDING 22 NORMAL POWER RISER DIAGRAM

31 EP-204 BUILDING 22 CRITICAL & LIFE SAFETY RISER DIAGRAM

32 EP-205 BUILDING 1 EM. POWER EQUIPMENT SYSTEM RISER DIAGRAM

33 EP-206 BUILDING 1 NORMAL POWER RISER DIAGRAM

34 EP-301 MEDIUM VOLTAGE 8.3KV DISTRIBUTION LAYOUT

35 EP-302 BUILDING 20 8.3KV MEDIUM VOLTAGE POWER METERING

36 EP-303 BUILDING 20 8.3KV MEDIUM VOLTAGE LAYOUT

37 EP-304 8.3KV MEDIUM VOLTAGE TRANSFORMER DETAILS

38 EP-305 BUILDING 1 DISTRIBUTION LAYOUT

SAGINAW VA

MEDICAL CENTER

BUILDING KEY

1 MAIN HOSPITAL 17 GAS HOUSE 32 PUMP HOUSE

2 POLICE 19 GENERATOR BLDG. 33 WATER TOWER

3 ADMINISTRATIVE 20 MEDIUM VOLTAGE BLDG. 34 BACK FLOW PREVENTOR

4 ADMINISTRATIVE 21 GARAGE 35 PAVILION

6 ADMINISTRATIVE 22 CLC 38 TEMP. OFFICE TRAILER

9 WAREHOUSE 30 ADMINISTRATIVE EC ENERGY CENTER

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

LEGEND & NOTES

655-26-201BID

G1.2

GENERAL NOTES:

1. CONTRACTOR SHALL PERFORM REQUIRED INSPECTION, TESTING, AND MAINTENANCE IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA).

2. TRANSFORMERS AND ALL RELATED EQUIPMENT:

A. TRANSFORMERS ARE TO BE CLEANED EXTERIORLY, INSPECTED FOR SIGNS OF OVERHEATING

WITH INFRA-RED THERMAL DETECTING EQUIPMENT, AND INSPECTED FOR ANY DAMAGE TO THE

HOUSING, CONNECTION POINTS, OR INSULATION.

B. LIQUID COOLED TRANSFORMERS ARE TO HAVE THE COOLING LIQUID TESTED AND REPLACED, WHEN TESTS INDICATE THAT THE LIQUID NO LONGER MEETS MANUFACTURER'S SPECIFICATION.

THE LIQUID IS TO BE RE-FILLED TO MEET THE MANUFACTURER'S SPECIFICATION.

C. DRY TYPE TRANSFORMERS MUST BE THOROUGHY CLEANED EXTERIORLY AND INSPECTED FOR

OVERHEATING WITH INFRA-RED THERMAL DETECTING EQUIPMENT.

3. ELECTRICAL EQUIPMENT (INCLUDING, BUT NOT LIMITED TO LOOP SWITCHES, SWITCHGEARS, SWITCHBOARDS, DISTRIBUTION PANELS, MOTOR CONTROL CENTERS AND ALL RELATED

COMPONENTS):

A. USE LINT-FREE RAGS TO CLEAN CONDUCTORS, CONTACT POINTS BETWEEN THE CIRCUIT

BREAKERS AND MAIN BUSS BARS, BUSS BARS AND INTERIOR OF THE ELECTRICAL EQUIPMENT.

USE A VACUUM CLEANER TO REMOVE LARGE DEBRIS; COMPRESSED AIR IS NOT TO BE USED FOR

THIS PURPOSE. VISUALLY INSPECT FOR SIGNS OF OVERHEATING, MISALIGNED CONTACTS,

DAMAGED INSULATION, OR LOSE LUGS.

B. LUBRICATE ALL MOVING PARTS WITH MANUFACTURER'S APPROVED LUBRICANTS.

C. CIRCUIT BREAKERS 250 AMPS AND ABOVE SHALL BE TESTED AND EXERCISED TO ENSURE

OPERATION UNDER OVERLOAD, AND SHORT CIRCUIT CONDITIONS (WHERE APPLICABLE CIRCUIT

BREAKERS ARE TO BE TRIPPED USING SECONDARY INJECTION).

D. ALL MOLDED CASE CIRCUIT BREAKERS (INCLUDING FRAME SIZES 225 AMPS OR LESS) ARE TO BE

TESTED TO DETERMINE IF CONTACTS OPEN AND RECLOSE WHEN BREAKER IS MANUALLY

TRIPPED AND RESTORED.

E. TEST GROUND FAULT PROTECTION DEVICES FOR PROPER FUNCTION IF THEY ARE INSTALLED IN

THE FACILITY ELECTRICAL POWER SYSTEM.

F. INSPECT AND TIGHTEN GROUND CONNECTIONS. TEST GROUND RESISTANCE FOR THE ENTIRE

FACILITY GROUNDING SYSTEM. ANY METHOD OF GROUND RESISTANCE WILL BE CONSIDERED

ACCEPTABLE IF IT CAN VERIFY CONTINUITY AND QUANTIFY THE IMPEDANCE TO GROUND, TO

INCLUDE BUT NOT LIMITED TO FALL-OF-POTENTIAL, INDUCED FREQUENCY AND CLAMP ON

TESTING. IF INITIAL TESTS INDICATE A PROBLEM OR CONECERN, A MORE DETAILED TEST MUST

BE PERFORMED USING FALL-OF-POTENTIAL OR 3-POINT TEST.

G. IDENTIFY THE HOT SPOTS IN THE ELECTRICAL EQUIPMENT BY USING INFRA-RED THERMAL

DETECTING EQUIPMENT. TIGHTEN PROBLEM CONNECTIONS TO MEET EQUIPMENT

MANUFACTURERS' SPECIFICATION USING A TORQUE WRENCH OR OTHER APPROVED DEVICES.

H. CALIBRATE AND MAINTAIN ADJUSTABLE PROTECTIVE RELAYS.

I. TEST ALL CONTROL SYSTEMS EQUIPMENT FOR PROPER OPERATION AFTER MAINTENANCE IS

PERFORMED AND BEFORE PLACING THEM BACK IN NORMAL SERVICE.

4. ALL TESTING RESULTS ARE TO BE DOCUMENTED AND TURNED OVER TO THE ENGINEERING OFFICE.

ABBREVIATIONS

AFF ABOVE FINISHED FLOOR FBGC FURNISHED BY GENERAL CONTRACTOR NO NORMALLY OPEN

AFC ABOVE FINISHED CEILING FBO FURNISHED BY OTHERS PCB PRINTED CIRCUIT BOARD

ASC AUDIO SYSTEMS CONTRACTOR FT FOOT OR FEET PE PHOTO ELECTRIC

AVSC AUDIO-VISUAL SYSTEMS CONTRACTOR FV FIELD VERIFY PID PASSIVE INFRARED DETECTOR

BCF BELOW FINISHED CEILING GC GENERAL CONTRACTOR PS POWER SUPPLY

C CONDIT GND GROUND PTZ PAN, TILT, ZOOM

C.O. CONDUIT ONLY HT HEIGHT RF RADIO FREQUENCY

CATV COMMUNITY ANTENNA TV IC INTERCOM S SOUTH

CCT. CIRCUIT IR INFRARED SSC SECURITY SYSTEMS CONTRACTOR

CCTV CLOSED CIRCUIT TV JB JUNCTION BOX TV TELEVISION

CONT'D CONTINUED LPS LOCK POWER SUPPLY TVSC TELEVISION SYSTEMS CONTRACTOR

CWG COLD WATER GROUND MATV MASTER ANTENNA TV TYP TYPICAL

DWG DRAWING MAX MAXIMUM UON UNLESS OTHERWISE NOTED

E. EAST MIN MINIMUM W WEST

EC ELECTRICAL CONTRACTOR N NORTH W/ WITH

EL ELEVATION NC NORMALLY CLOSED W/O WITHOUT

EXT. EXTERNAL NEC NATIONAL ELECTRIC CODE W.P. WATERPROOF

FBEC FURNISHED BY ELECTRICAL CONTRACTOR NIC NOT IN CONTRACT

X

X X

X X

X X

X

WEISS STREET

X

X X

DUMPSTER

DUMPSTER

HH

EMH-105

EMH-103

EMH-102

EMH-99

EMH-101

EMH-100

EMH-171

EMH-114

EMH-174

EMH-176

EMH-175

EMH-179

EMH-182

EMH-118

EMH-112

EMH-111

EMH-119

EC

LOOP SWITCH-1

LOOP

SWITCH-5

LOOP SWITCH-6

T-8

500 KVA

T-7

750 KVA

T-1

750 KVA

T-10

750 KVA

T-11

750 KVA

T-2

500 KVA

T-3

1000 KVA

T-16

75 KVAT-13

225 KVA

T-12

750 KVA

T-35

150 KVA

T-29

45 KVA

T-9

225 KVA

T-14

1000 KVA

T-17

112.5 KVA

T-31

112.5 KVA

T-20

112.5 KVA

T-32

30 KVA

LOOP SWITCH-2

LS2-A NO

LOOP SWITCH-4

LOOP SWITCH-3

T-6

225 KVA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

OVERALL ELECTRICAL SITE PLAN

655-26-201BID

ES-100

AutoCAD SHX Text

EAST 1/4 CORNER SECTION 14 T. 12 N., R. 4 E. CITY OF SAGINAW

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

EX. LOW AREA

AutoCAD SHX Text

EX. LOW AREA

AutoCAD SHX Text X

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

WEISS STREET

AutoCAD SHX Text

CB

AutoCAD SHX Text S86°25'31"W 23.90' (M) S86°25'50"W (R)

AutoCAD SHX Text

BM

AutoCAD SHX Text

OHW

AutoCAD SHX Text

CITY OF SAGINAW

AutoCAD SHX Text

OHW

AutoCAD SHX Text

OHW

AutoCAD SHX Text

OHW

AutoCAD SHX Text

OHW

AutoCAD SHX Text 594'

AutoCAD SHX Text

CITY OF SAGINAW PROPERTY LINE

AutoCAD SHX Text

30' REAR

AutoCAD SHX Text

SETBACK

AutoCAD SHX Text

CITY OF SAGINAW PROPERTY LINE

AutoCAD SHX Text

OHW

AutoCAD SHX Text

OHW

AutoCAD SHX Text 48.46'

AutoCAD SHX Text 125.98'

AutoCAD SHX Text N89°46'20"W 545.98'

AutoCAD SHX Text 87.82'

AutoCAD SHX Text N89°46'20"W

AutoCAD SHX Text N01°06'20"W

AutoCAD SHX Text 33.01'

AutoCAD SHX Text

5'X8' LANDING

AutoCAD SHX Text

STEP

AutoCAD SHX Text

STEP

AutoCAD SHX Text

STEP

AutoCAD SHX Text

MAX SLOPE 1:12

AutoCAD SHX Text

4'X7'10" RAMP LANDING

AutoCAD SHX Text

MAX SLOPE 1:12

AutoCAD SHX Text

PEDESTRIAN GATE WHERE WATERMAIN CROSSES FENCE.

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text (E)P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

P

X X

X X

X X

X X

X

X

X X X

X

X

X

X X

X

X

X

DUMPSTER

DUMPSTER

LOOP

SWITCH

T-12

750 KVA

DP-21A

480V

T-13

225 KVA

BLDG 30

120/208V

T-8

500 KVA

MDP-2

120/208V T-7

750 KVA

MDP-1

480V

T-16

75 KVA

EDP-21B

120/208V

T-6

225 KVA

CB-N-HBS1-09

480V

LOOP

SWITCH

T-17

112.5 KVA

DP-E-BS2-09

120/208V

T-31

112.5 KVA

BLDG 35

120/208V

T-20

112.5 KVA

CONSTRUCTION

TRAILERS

120/208V

DISC-RTU-AC-21-107

DISC-103-0CU-101

DISC-B438-MINI-SPLIT-CU

DISC-B6 HU-1

DISC-B6 SF-1

DISC-B6 DX-1 (PB-E-H2N1-06)

DISC-B702A-22-CU-004

DISC-B6 RF-1

DISC-B6 EF-1

DISC-ECB-B6-DX-1-CP

DISC-B4-106A-4-CU-101

DISC-B4-CU-NW

DISC-ECB-B21-GHP-4 DISC-ECB-B21-GHP-5

DISC-B21-CU-101

FDS-BUILDING-30

FDS-E-H2-00

PB-E-2-00

DISC-B32-CU-1

DISC-B32-CU-2

DISC-GEN-7-LOAD-BANK-FAN

DISC-B21-GEN-7-RAD

DISC-B9-101-MINI-SPLIT-CU

DISC-B09-CU

CONSTRUCTION PANEL-1

CONSTRUCTION PANEL-2DISC-TRANSFORMER T-20

DISC-B1-THAW-BOX

DISC-B22-ACRCU-1

DISC-B22-ACRCU-2

DISC-B22-SOLAR-DC-INPUT

DISC-B22-EF-1-2

DISC-30-CU-101

DISC-B1-VEGGIE-FRIDGE

DISC-B1-COOKS -COOLER

DISC-B1-CHAPEL-RTU

DISC-B1-MAU-KETTLE-HOOD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

ENLARGED ELECTRICAL SITE

PLAN - NORTH SECTION

655-26-201BID

ES-101

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text X

AutoCAD SHX Text

EX. LOW AREA

AutoCAD SHX Text

EX. LOW AREA

AutoCAD SHX Text X

AutoCAD SHX Text

OHW

AutoCAD SHX Text

CITY OF SAGINAW

AutoCAD SHX Text

OHW

AutoCAD SHX Text

OHW

AutoCAD SHX Text 594'

AutoCAD SHX Text 600'

AutoCAD SHX Text

CITY OF SAGINAW PROPERTY LINE

AutoCAD SHX Text 87.82'

AutoCAD SHX Text N89°46'20"W

AutoCAD SHX Text N01°06'20"W

AutoCAD SHX Text 33.01'

AutoCAD SHX Text

5'X8' LANDING

AutoCAD SHX Text

STEP

AutoCAD SHX Text

STEP

AutoCAD SHX Text

STEP

AutoCAD SHX Text

MAX SLOPE 1:12

AutoCAD SHX Text

4'X7'10" RAMP LANDING

AutoCAD SHX Text

MAX SLOPE 1:12

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

SHEET ES-101

SHEET ES-102

X X

X X

X X

WEISS STREET

HH

EC

FUSE-UTILITY

CONSUMERS

ENERGY

FEEDER-3FEEDER-2FEEDER-1MV-MAIN

PANEL BUILDING-2

LOOP

SWITCH

LOOP

SWITCH

LOOP

SWITCH

LOOP

SWITCH

T-10

750 KVA

SWBD-2

MAIN-1

T-11

750 KVA

SWBD-2

MAIN-2

T-14

1000 KVA

NSWBD-2

480V

T-2

500 KVA

SWBD-1

MAIN-2

T-1

750 KVA

SWBD-1

MAIN-1

T-9

225 KVA

DP3

120/208V

T-8

500 KVA

MDP-2

120/208V T-7

750 KVA

MDP-1

480V

T-6

225 KVA

CB-N-HBS1-09

480V

LOOP

SWITCH

T-17

112.5 KVA

DP-E-BS2-09

120/208V

T-31

112.5 KVA

BLDG 35

120/208V

T-20

112.5 KVA

CONSTRUCTION

TRAILERS

120/208V

T-2

1000 KVA

NSWBD

480V

TAP EMH-123 JUNCTION A

TAP EMH-123 JUNCTION B

ELECTRICAL MANHOLE 123

DISC-1-ACCU-1 (SPS CU)

DISC-103-0CU-101

DISC-CU-3B

DISC-1114-MS-CU

DISC-B100-AREA-CU-8

DISC-B1-AREA-1100-CU-1C

DISC-2135-X-RAY-MS-CU

DISC-B1-AREA-B130

DISC-2145-CT-SCAN-MS-CU

DISC-2147-CT-CNTRL-MS-CU

DISC-B1-CU-1BDISC-B1-CU-1A

DISC-1200-WEST-MINI-SPLIT-CU

DISC-B210-MINI-SPLIT-CU

DISC-B200-MINI-MATE-1-CUDISC-B200-MINI-MATE-2-CU

DISC-B220 AREA-RTU

DISC-NUC-MED-ACC-1

DISC-B250-MINI-SPLIT-CU

DISC-2257-MS-CU

DISC-EC-OFFICE-MINI-SPLIT-CU

DISC-B1-RTU-2

DISC-ACC-4A DISC-ACC-4B

DISC-B338-MINI-SPLIT-CU

DISC-2300-1-AC-201

DISC-4305-1-CU-401

DISC-B1-MORGUE-CU

#1

DISC-2134-1-ACCU-9

DISC-1-ACCU-7

DISC-B1-EQ-HBC1

DISC-B1-EQ-HBC2

DISC-VFD-B1-EF1-1

DISC-VFD-B1-SF1-1

DISC-B1-ACCU-1

DISC-B201/B241-MINI-SPLIT-CU

DISC-B1-RTU-5

DISC-1360-VOL-SERV-CU

DISC-B1-AREA

1340-1351-RTU-7

DISC-B1-AHU-CANOPY

DISC-ECB-B1-ACC-1

DISC-2100-AREA-EF (LAB)

DISC-2100 AREA-ACCU-6 (LAB)

DISC-2100 AREA-AHU-6 (LAB)

DISC-B438-MINI-SPLIT-CU

DISC-B6 HU-1

DISC-B6 SF-1

DISC-B6 DX-1 (PB-E-H2N1-06)

DISC-B702A-22-CU-004

DISC-B6 RF-1

DISC-B6 EF-1

DISC-ECB-B6-DX-1-CP

DISC-ECB-B1-ACC-2

DISC-ECB-B1-CU-3A

DISC-B1-EF-2 DISC-ECB-RTU-3 ELEV

DISC-RTU-3 ELEV

DISC-PH4B RADIO ROOM CU

DISC-B03-CU

DISC-B102-3-CU-101

B4-CU-SOUTH

DISC-B4-106A-4-CU-101

DISC-B4-CU-SW

DISC-B4-CU-NW

DISC-B21-CU-101

DISC-B9-101-MINI-SPLIT-CU

CONSTRUCTION PANEL-1

CONSTRUCTION PANEL-2DISC-TRANSFORMER T-20

DISC-FRONT-DAKTRONICS-SIGN

DISC-100A-2-CU-101

DISC-GEN-3-RAD

DISC-B315-GIP-RM-RTU

DISC-1200-EAST-MS-CU

DISC-B1-EF-2LKR

DISC-B1-EF-STORAGE

DISC-B1-ACCU-5

DISC-EC-ACC-3

DISC-B1-FREZ-UNIT-3

DISC-B1-THAW-BOX

DISC-B22-CU-003

DISC-B22-ACRCU-1

DISC-B22-ACRCU-2

DISC-ECB-B22-ACRCU-2DISC-ECB-B22-ACRCU-1

DISC-B22-SOLAR-DC-INPUT

DISC-B22-EF-1-2

DISC-4100-AREA-CU

DISC-B1-VEGGIE-FRIDGE

DISC-B1-COOKS -COOLER

DISC-FREZ-UNIT-1

DISC-CANTEEN-HOOD-EF

DISC-GEN-2-RAD

DISC-GEN-1-RAD

DISC-ECB-B1-AREA-1100-CU-1C

DISC-FREZ-UNIT-2

DISC-B1-CHAPEL-RTU

DISC-B1-MAU-KETTLE-HOOD

DISC-B324-MINI-SPLIT-CU

DISC-RM-1331-33-MINI-SPLIT-CU

DISC-1314-MINI-SPLIT-CU

DISC-B22-CU-001DISC-B22-CU-002

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

ENLARGED ELECTRICAL SITE

PLAN - SOUTH SECTION

655-26-201BID

ES-102

AutoCAD SHX Text

(66' WIDE)

AutoCAD SHX Text

EAST 1/4 CORNER SECTION 14 T. 12 N., R. 4 E. CITY OF SAGINAW

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

BM

AutoCAD SHX Text 48.46'

AutoCAD SHX Text 125.98'

AutoCAD SHX Text 87.82'

AutoCAD SHX Text N89°46'20"W

AutoCAD SHX Text N01°06'20"W

AutoCAD SHX Text 33.01'

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text (E)P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

SHEET ES-101

SHEET ES-102

S

S

P

S

P

S

P

S

P

S

P

SWBD-1 TIE

NO

SWBD-2 TIE

NSWBD-2 MAIN

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 5 (8000A)

STD 0.2 (I^s T Off)

INST 4 (6400A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T Off)

NSWBD-2 (EC)

480V, 1600A

CBL-NSWBD-2 110ft

(5) #500 CU

T-14 (EC)

1000kVA 8320V-480V 5.75%

FUSE T-14 (EC)

23000V, COOPER ELX, 8.3-23kV 100AF, 100AT, 50 AIC 100.0 Amps

CBL T-14 10ft (1) #1/0

CU

FUSE LS-5D (T-14)

12470V, S&C SMU-20, 14.4kV E-Rated

100AF, 100AT, 14 AIC 100

Amps

LS-5

8320V, 600A SCCR: 25kA

SCA: 5113A

LS5-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL LS-5A

10ft (1) #1/0 CU

NSWBD (BLDG 1)

480V, 1600A

NSWBD MCB

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 24

STPU 6 (4800A)

STD 0.2 (I^s T Off)

INST 15 (12000A)

GFP

GFPU (500-1200A) G (1040A)

GFD (0-0.4) 0.3 (I^s T Off)

CBL- NSWBD

50ft (5) #400 CU

T-3 (BLDG 1)

1000kVA 8320V-480V 5.75%

FUSE T-3 (BLDG 1)

15500V, COOPER

ELX, 8.3-23kV

40AF, 40AT, 50 AIC

40.0 Amps

S-T-3A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL T-3A

10ft (1) #1/0 CU

S-T-3B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

FUSE T-10 (BLDG 1)

15500V, COOPER

ELX, 8.3-23kV

40AF, 40AT, 50 AIC

40.0 Amps

T-10 (BLDG 1)

750kVA 8320V-208V 5.75%

CBL- SWBD-2 MAIN-1

20ft (6) #500 CU

SWBD-2 MAIN-1

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

3200AF, 3200AT, 3200AP

65 AIC

Phase

LTPU (A) 0.7 (2240A)

LTD 4

STPU 4 (8960A)

STD 0.4 (I^s T Off)

INST 8 (25600A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T Off)

SWBD-2 SECTION-1 (BLDG 1)

208V, 3200A

SWBD-2 SECTION-2 (BLDG 1)

208V, 3200A

SWBD-2 MAIN-2

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

3200AF, 3200AT, 3200AP

65 AIC

Phase

LTPU (A) 0.7 (2240A)

LTD 4

STPU 4 (8960A)

STD 0.4 (I^s T Off)

INST 15 (48000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T Off)

CBL- SWBD-2 MAIN-2

20ft (6) #500 CU

T-11 (BLDG 1)

750kVA 8320V-208V 5.75%

FUSE T-11 (BLDG 1)

15500V, COOPER

ELX, 8.3-23kV

40AF, 40AT, 50 AIC

40.0 Amps

CBL T-11

10ft (1) #1/0 CU

SWBD-1 SECTION-1 (BLDG 1)

208V, 1600A

SWBD-1 MAIN-1

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 6 (9600A)

STD 0.2 (I^s T Off)

INST 10 (16000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

CBL- SWBD-1 MAIN-1

50ft (5) #400 CU

T-1 (BLDG 1)

500kVA 8320V-208V 4.50%

FUSE T-1 (BLDG 1)

15500V, COOPER

NX (C-Rated), 15.5kV

65AF, 65AT, 50 AIC

65.0 Amps

SWBD-1 SECTION-2 (BLDG 1)

208V, 1600A

SWBD-1 MAIN-2

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 6 (9600A)

STD 0.2 (I^s T Off)

INST 10 (16000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

CBL- SWBD-1 MAIN-2

50ft (5) #400 CU

T-2 (BLDG 1)

500kVA 8320V-208V 4.50%

FUSE T-2 (BLDG 1)

15500V, COOPER

NX (C-Rated), 15.5kV

65AF, 65AT, 50 AIC

65.0 Amps

CBL T-2

10ft (1) #1/0 CU

LS5-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL LS-5B

10ft (1) #1/0 CU

CBL T-3B

10ft (1) #1/0 CU

CBL T-1

10ft (1) #1/0 CU

TAP EMH-13 JUNCTION-A

8320V, 0A SCCR: 0kA

SCA: 5118A

CBL EMH-123 (13P) JUNCTION-A

150ft (1) #4/0 CU

FUSE LS-2C (T-2,3,11,14, LS-5)

14400V, S&C SMU-20, 14.4kV E-Rated

125AF, 125AT, 14 AIC

125 Amps

CBL EMH-13 JUNCTION-B

150ft (1) #4/0 CU

FUSE LS-2D (T-1, 3, 10, LS-5)

14400V, S&C SMU-20, 14.4kV E-Rated

125AF, 125AT, 14 AIC

125 Amps

LS-2

8320V, 600A SCCR: 25kA

SCA: 5171A

LS2-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL LS-2A

580ft (1) #4/0 CU

LS4-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

LS2-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL MV FEEDER-1 (LS-2B)

220ft (1) #4/0 CU

MAIN SWITCHGEAR (FEEDER 1)

15000V, SQUARE D

VR

1200AF, 18 AIC

Phase Relay

PHASE O/C PICKUP 200 % (300A)

EXTREM INV 2

PHASE INST TRIP 15.0 (4500A)

GF Relay

GND O/C PICKUP 0.4 (60A)

VERY INV 2

GND INST TRIP 6.0 (360A)

LS-4

8320V, 600A SCCR: 25kA

SCA: 4923A

MAIN SWITCHGEAR

(BLDG. 20)

8320V, 1200A SCCR: 18kA

SCA: 5250A

MAIN MV SWITCHGEAR MCB

15000V, SQUARE D

VR

1200AF, 18 AIC

Phase Relay

PHASE O/C PICKUP 200 % (400A)

EXTREM INV 2

PHASE INST TRIP 14.0 (5600A)

GF Relay

PHASE O/C PICKUP 200 % (400A)

EXTREM INV 2

PHASE INST TRIP 14.0 (5600A)

CBL UTILITY

30ft (1) #4/0 CU

FUSE UTILITY

0V, 0AF, 0 AIC

UTILITY

Isc 3P 74 MVA Isc SLG 19 MVA

NONC

NO

CBL T-10

10ft (1) #1/0 CU

TAP EMH-123 (13P) JUNCTION-B

8320V, 0A SCCR: 0kA

SCA: 5116A

NO

NO

NC

(SEE SHEET EP-103) (SEE SHEET EP-103)

(SEE SHEET EP-102) (SEE SHEET EP-102)

(CONT. ON SHEET EP-101)

(CONT. ON SHEET EP-101)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

EP-100

BLDG. 20 & SITE

8.3KV MEDIUM VOLTAGE PRIM.

ONE-LINE DIAGRAM

ELECTRICAL MAINTENANCE

655-26-201BID

S

P

S

P

S

P

CBL T-6

20ft (1) #1/0 CU

NONE

T-6 (BLDG 9)

225kVA 8320V-480V 4.75%

CBL CB-N-HBS1-09

30ft (1) #600 CU

NONE

CB-N-HBS1-09

600V, SQUARE D

LA

400AF, 400AT, 400AP

22 AIC

Thermal Curve

INST LO (2000A)

ECB B09 CB-N-HBS1-09

480V, 400A

MDP-1 (BLDG 22)

480V, 1600A

MDP-1 MCB

480V, SQUARE D

PX, Micrologic

1600AF, 1600AT, 1600AP

100 AIC

Phase LTPU (0.5-1.0 x P) 1.0 (1600A) LTD (2-24 Sec.) 3.0 STPU (2-8 x P) 2.0 (3200A) STD (0.1-0.5 Sec.) .1 (I^s T On) INST (2.5-8 x P) 8.0 (12800A)

GFP

GFPU (0.2-0.75 x S) 0.2 (320A) GFD (0.1-0.5 Sec.) 0.5

CBL-MDP-1

60ft (3) #600 CU

T-7 SECONDARY

T-7 (BLDG 22)

750kVA 8320V-480V 5.75%

T-7 FUSE (BLDG 22)

15500V, COOPER

NX (C-Rated), 15.5kV

65AF, 65AT, 50 AIC

65.0 Amps

CBL T-7

200ft (1) #1/0 CU

FUSE LS-3C (T-7)

14400V, S&C SMU-20, 14.4kV E-Rated

80AF, 80AT, 14 AIC

80 Amps

LS4-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL LS-4B

490ft (1) #4/0 CU

LS3-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

LS-4

8320V, 600A SCCR: 25kA

SCA: 4923A

FUSE LS-3D (T-8)

14400V, S&C SMU-20, 14.4kV E-Rated

65AF, 65AT, 14 AIC

65 Amps

CBL T-8

200ft (1) #1/0 CU

FUSE T-8 (BLDG 22)

15500V, COOPER

NX (C-Rated), 15.5kV

65AF, 65AT, 50 AIC

65.0 Amps

T-8 (BLDG 22)

500kVA 8320V-208V 4.50%

CBL-MDP-2

40ft (4) #600 CU

T-8 SECONDARY

MDP-2 MCB

240V, SQUARE D

PX, Micrologic (Obs.)

1600AF, 1600AT, 1600AP

125 AIC

Phase STPU (2-8 x P) 2.0 (3200A) STD (Min-Max) MIN (I^s T On)

LTPU 1.0 (1600A)

LTD (Min-Max) INT

GFP

GFPU (1200AS) 0.2 (320A)

GFD (Inst-Max) MIN

MDP-2 (BLDG 22)

208V, 1600A

LS3-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

LS-3

8320V, 600A SCCR: 25kA

SCA: 5094A

CBL LS-3A

200ft (1) #4/0 CU

LS1-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

FUSE LS-1D (T-9)

14400V, S&C SMU-20, 14.4kV E-Rated

30AF, 30AT, 14 AIC

30 Amps

CBL T-9

40ft (1) #1/0 CU

FUSE T-9 (BLDG 3)

23000V, COOPER

ELX, 8.3-23kV

30AF, 30AT, 50 AIC

30.0 Amps

T-9 (BLDG 3)

225kVA 8320V-208V 3.80%

CBL-ECB BLDG-3

30ft (2) #600 CU

ECB BLDG-3

240V, SQUARE D

MA

1000AF, 800AT, 800AP

42 AIC

Thermal Curve

INST LO (4000A)

ECB B03 BLDG-3(S)

208V, 800A

LS1-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

CBL MV FEEDER-2 (LS1-B)

220ft (1) #4/0 CU

MAIN SWITCHGEAR (LS1-B)

FEEDER-2

15000V, SQUARE D

VR

1200AF, 18 AIC

Phase Relay

PHASE O/C PICKUP 125 % (187.5A)

EXTREM INV 3

PHASE INST TRIP 18.0 (3375A)

GF Relay

GND O/C PICKUP 0.4 (60A)

VERY INV 2

GND INST TRIP 4.0 (240A)

MAIN SWITCHGEAR

8320V, 1200A SCCR: 18kA

SCA: 5250A

MAIN SWITCHGEAR (LS6-A)

FEEDER-3

15000V, SQUARE D

VR

1200AF, 18 AIC

Phase Relay

PHASE O/C PICKUP 0.8 (120A)

EXTREM INV 3

PHASE INST TRIP 18.0 (2160A)

GF Relay

GND O/C PICKUP 0.4 (60A)

VERY INV 2

GND INST TRIP 4.0 (240A)

CBL MV FEEDER-3 (LS6-A)

795ft (1) #4/0 CU

LS6-A

15000V, GE

BreakMaster LIS

600AF, 25 AIC

LS6-B

15000V, GE

BreakMaster LIS

600AF, 25 AIC

FUSE LS-C (T-12)

14400V, S&C SMU-20, 14.4kV E-Rated

80AF, 80AT, 14 AIC

80 Amps

LS-6

8320V, 600A SCCR: 25kA

SCA: 4964A

CBL T-12

110ft (1) #2 CU

FUSE T-12 (BLDG 21)

23000V, COOPER

ELX, 8.3-23kV

80AF, 80AT, 50 AIC

80.0 Amps

T-12 (BLDG 21)

750kVA 8320V-480V 5.75%

CBL-DP-21A

30ft (4) #350 CU

T-12 SECONDARY

DP-21A MCB

480V, SQUARE D

Powerpact P-Frame PG, 5.0 & 6.0 A/P/H

1200AF, 1200AT, 1200AP

35 AIC

Phase

LTPU (A) 0.5 (600A)

LTD 2

STPU 3 (1800A)

STD 0.4 (I^s T On)

INST 3 (3600A)

GFP

GFPU (0.2-1.0 x S) D (600A) GFD (0-0.4) 0.3 (I^s T On)

PANEL DP-21A (BLDG 21)

480V, 1200A

LS4-C

15000V, GE

BreakMaster LIS

600AF, 25 AIC

FUSE LS-4C (T-6)

14400V, S&C SMU-20, 14.4kV E-Rated

30AF, 30AT, 14 AIC

30 Amps

LS-1

8320V, 600A SCCR: 25kA

SCA: 5167A

FUSE LS-1C (LS-6)

12000V, S&C SMU-20, 14.4kV E-Rated

150AF, 150AT, 14 AIC

150 Amps

CBL LS-6B

575ft (1) #4/0 CU

NO

NC

S

P

(CONT. ON SHEET EP-100)

(CONT. ON SHEET EP-100)

LS4-D

15000V, GE

BreakMaster LIS

600AF, 25 AIC

NO CONNECTION

LS6-C

15000V, GE

BreakMaster LIS

600AF, 25 AIC

NO CONNECTION

(SEE SHEET EP-117) (SEE SHEET EP-115) (SEE SHEET EP-115) (SEE SHEET EP-117) (SEE SHEET EP-117)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

EP-101

BLDG. 20 & SITE

8.3KV MEDIUM VOLTAGE PRIM.

ONE-LINE DIAGRAM

ELECTRICAL MAINTENANCE

E N

SWBD-1 SECTION-1 (BLDG 1)

208V, 1600A SCCR: 85kA

SCA: 24262A

SWBD-1 (SPARE)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 1000AT, 1000AP

100 AIC

Phase

LTPU (A) 1 (1000A)

LTD 24

STPU 10 (10000A)

STD 0.1 (I^s T Off)

INST 15 (15000A)

GFP

GFPU (0.3-1.0 x S) C (160A) GFD (0-0.4) 0.1 (I^s T Off)

CBL-ATS-A(E)

35ft (2) #4/0 CU

ESWBD (ATS-A)

CBL-ATS-A(N)

45ft (2) #4/0 CU

SWBD-1 (ATS-A)

ATS-A

480V, 400A 200.00kA SCCR

↑459A SCA

ATS A

208V, 0A SCCR: 0kA

SCA: 8134A

CBL-CDP

6ft (2) #4/0 CU

ATS A

PANEL CDP

208V, 400A SCCR: 200kA

SCA: 8047A

SWBD-1 (ATS-A)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 0.9 (360A)

LTD 24

STPU 10 (3600A)

STD 0.1 (I^s T Off)

INST 15 (6000A)

GFP

GFPU (0.3-1.0 x S) C (160A) GFD (0-0.4) 0.1 (I^s T Off)

SWBD-1 MAIN-1

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 6 (9600A)

STD 0.2 (I^s T Off)

INST 10 (16000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

SWBD-1 TIE

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 4 (6400A)

STD 0.3 (I^s T Off)

INST OFF

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

SWBD-1 MAIN-2

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

42 AIC

Phase

LTPU (A) 1 (1600A)

LTD 8

STPU 6 (9600A)

STD 0.2 (I^s T Off)

INST 10 (16000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

CBL-ATS-B(E)

35ft (2) #4/0 CU

ESWBD (ATS-B)

SWBD-1 (ATS-B)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 1 (400A)

LTD 4

STPU 8 (3200A)

STD 0.1 (I^s T On)

INST 12 (4800A)

GFP

GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)

CBL-ATS-B(N)

50ft (2) #4/0 CU

SWBD-1 (ATS-B)

ATS-B

480V, 400A 200.00kA SCCR

↑0A SCA

ATS B

208V, 0A SCCR: 0kA

SCA: 8067A

CBL-LSDP

6ft (2) #4/0 CU

ATS B

PANEL LSDP

208V, 400A SCCR: 200kA

SCA: 7969A

CBL-ATS-C(E)

40ft (3) #300 CU

ESWBD (ATS-C)

SWBD-1 (ATS-C)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 24

STPU 10 (8000A)

STD 0.1 (I^s T Off)

INST 15 (12000A)

GFP

GFPU (0.2-1.0 x S) C (320A) GFD (0-0.4) 0.1 (I^s T Off)

CBL-ATS-C(N)

30ft (3) #300 CU

SWBD-1 (ATS-C)

ATS-C

480V, 800A 200.00kA SCCR

↑0A SCA

ATS C

208V, 0A SCCR: 0kA

SCA: 8342A

CBL-EMDP

10ft (3) #300 CU

ATS C

PANEL EMDP

208V, 800A SCCR: 200kA

SCA: 8235A

SWBD-1 SECTION-2 (BLDG 1)

208V, 0A SCCR: 0kA

SCA: 24263A

E N E N

NO

SWBD-2 SECTION-1 (BLDG 1)

208V, 3200A SCCR: 65kA

SCA: 29503A SWBD-2 (LDP)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

100 AIC

Phase

LTPU (A) 0.625 (1000A)

LTD 8

STPU 4 (4000A)

STD 0.2 (I^s T Off)

INST 4 (6400A)

GFP

GFPU (500-1200A) A (500A)

GFD (0-0.4) 0.2 (I^s T Off)

CBL-LDP

35ft (3) #500 CU

SWBD-2 (LDP)

PANEL LDP

208V, 1200A SCCR: 200kA

SCA: 25621A

SWBD-2 (SPARE-1D)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 4 (3200A)

STD 0.2 (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

SWBD-2 (SPARE-2C)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

100 AIC

Phase

LTPU (A) 0.7 (1120A)

LTD 0.5

STPU 1.5 (1680A)

STD 0.1 (I^s T On)

INST 2 (3200A)

GFP

GFPU (500-1200A) A (500A)

GFD (0-0.4) 0.1 (I^s T Off)

SWBD-2 (SPARE-2D)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 4 (3200A)

STD 0.2 (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

SWBD-2 TIE

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

3200AF, 3200AT, 3200AP

65 AIC

Phase

LTPU (A) 0.7 (2240A)

LTD 4

STPU 4 (8960A)

STD 0.3 (I^s T Off)

INST 3 (9600A)

GFP

GFPU (500-1200A) E (880A)

GFD (0-0.4) 0.3 (I^s T Off)

CBL-ATS-E(E)

10ft (3) #500 CU

ESWBD (ATS-E)

SWBD-2 (ATS-E)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

100 AIC

Phase

LTPU (A) 0.5 (800A)

LTD 24

STPU 8 (6400A)

STD 0.2 (I^s T Off)

INST 6 (9600A)

GFP

GFPU (500-1200A) A (500A)

GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-E(N)

80ft (3) #500 CU

SWBD-2 (ATS-E)

ATS-E (MDP)

480V, 800A 200.00kA SCCR

↑307A SCA

ATS E (MDP)

208V, 0A SCCR: 0kA

SCA: 8692A

CBL-MDP

15ft (3) #300 CU

ATS E (MDP)

PANEL MDP

208V, 800A SCCR: 200kA

SCA: 8536A

SWBD-2 (SPARE-3C)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 4 (3200A)

STD 0.2 (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

SWBD-2 (PDP)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

1600AF, 1600AT, 1600AP

100 AIC

Phase

LTPU (A) 0.625 (1000A)

LTD 12

STPU 4 (4000A)

STD 0.1 (I^s T Off)

INST 3 (4800A)

GFP

GFPU (500-1200A) A (500A)

GFD (0-0.4) 0.1 (I^s T On)

CBL-PDP

45ft (3) #500 CU

SWBD-2 (PDP)

PDP MCB

240V, SQUARE D

Powerpact P-Frame PG/PK, 3.0 & 3.0A

1200AF, 1000AT, 1000AP

65 AIC

LTPU (A) 1 (1000A)

LTD 12

INST 4 (4000A)

PANEL PDP

208V, 1200A SCCR: 200kA

SCA: 24688A

SWBD-2 (SPARE-4D)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 4 (3200A)

STD 0.2 (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.2 (I^s T Off)

SWBD-2 SECTION-2 (BLDG 1)

208V, 3200A SCCR: 65kA

SCA: 29505A

SWBD-2 MAIN-2

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

3200AF, 3200AT, 3200AP

65 AIC

Phase

LTPU (A) 0.7 (2240A)

LTD 4

STPU 4 (8960A)

STD 0.4 (I^s T Off)

INST 15 (48000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T Off)

SWBD-2 MAIN-1

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

3200AF, 3200AT, 3200AP

65 AIC

Phase

LTPU (A) 0.7 (2240A)

LTD 4

STPU 4 (8960A)

STD 0.4 (I^s T Off)

INST 8 (25600A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T Off)

NO

FED FROM T-1

(SEE SHEET EP-100)

FED FROM T-2

(SEE SHEET EP-100)

FED FROM T-10

(SEE SHEET EP-100)

FED FROM T-11

(SEE SHEET EP-100)

FED FROM ESWBD

(SEE SHEET EP-104)

(SEE SHEET EP-106) (SEE SHEET EP-106)

FED FROM ESWBD

(SEE SHEET EP-104)

FED FROM ESWBD

(SEE SHEET EP-104)

(SEE SHEET EP-105)

(SEE SHEET EP-111)

FED FROM ESWBD

(SEE SHEET EP-104)

(SEE SHEET EP-107)

(SEE SHEET EP-111)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

EP-102

BLDG. 1 NORMAL POWER

SWBD-1 & SWBD-2

ONE-LINE DIAGRAM

ELECTRICAL MAINTENANCE

E NE N

P

E N E N

NSWBD (SPARE1)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 1 (400A)

LTD 4

STPU 4 (1600A)

STD 0.1 (I^s T Off)

INST 3 (1200A)

GFP

GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)

NSWBD (SPARE2)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 0.8 (320A)

LTD 4

STPU 4 (1280A)

STD 0.1 (I^s T Off)

INST 3 (1200A)

GFP

GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)

NSWBD (BA1)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 600AT, 600AP

100 AIC

Phase

LTPU (A) 1 (600A)

LTD 4

STPU 4 (2400A)

STD 0.1 (I^s T Off)

INST 15 (9000A)

GFP

GFPU (0.3-1.0 x S) G (320A) GFD (0-0.4) 0.1 (I^s T Off)

CBL-BA1 (480V)

20ft (2) #350 CU

NSWBD (BA1)

NSWBD (NDP)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 0.9 (360A)

LTD 4

STPU 4 (1440A)

STD 0.1 (I^s T Off)

INST 15 (6000A)

GFP

GFPU (0.3-1.0 x S) F (280A) GFD (0-0.4) 0.1 (I^s T Off)

CBL-NDP

292ft (2) #500 CU

NSWBD (NDP)

NSWBD (XRAY GEN)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 250AT, 250AP

65 AIC

Phase

LTPU (A) 1 (250A)

LTD 16

STPU 10 (2500A)

STD 0.1 (I^s T Off)

INST 10 (2500A)

INST OR Fixed (24000A)

GFP

GFPU (0.3-1.0 x S) A (75A) GFD (0-0.4) 0.1 (I^s T On)

CBL-XRAY GEN

286ft (1) #3/0 CU

JB IN CORRIDOR

480V, 0A SCCR: 0kA

SCA: 6962A

CBL-XRAY GEN-1

256ft (1) #250 CU

ECB-XRAY GEN

600V, SQUARE D

FA

100AF, 100AT, 100AP

14 AIC

Fixed

ECB B01 XRAY GEN

480V, 100A SCCR: 10kA

SCA: 4342A

CBL-ATS-F(E)

160ft (2) #500 CU

DP-E-BEC-C (ATS-F)

NSWBD (DP-EQ-BA3-01)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 12

STPU 4 (3200A)

STD INST (I^s T Off)

INST OFF

GFP

GFPU (0.2-1.0 x S) G (640A) GFD (0-0.4) 0.2 (I^s T On)

CBL-ATS-F(N)

10ft (2) #500 CU

NSWBD (DP-EQ-BA3-01)

ATS-F (BYPASS ISO)

480V, 800A 200.00kA SCCR

↑791A SCA

ATS F

480V, 0A SCCR: 0kA

SCA: 9234A

CBL-DP-EQ-BA3-01

20ft (2) #500 CU

ATS F

NSWBD (DP-EQ-6HB)

508V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 600AT, 600AP

100 AIC

Phase

LTPU (A) 1 (600A)

LTD 16

STPU 8 (4800A)

STD 0.2 (I^s T On)

INST 8 (4800A)

GFP

GFPU (0.2-1.0 x S) E (360A) GFD (0-0.4) 0.2 (I^s T On)

CBL- ATS G(N)

20ft (2) #350 CU

NSWBD (DP-EQ-6HB)

ATS-G (BYPASS ISO)

0V, 0A 0.00kA SCCR

↑2127A SCA

ATS G PANEL DP-EQ-6HB

480V, 0A SCCR: 0kA

SCA: 17930A

CBL-DP-EQ-6HB

200ft (2) #350 CU

ATS G PANEL DP-EQ-6HB

DP-EQ-6HB MCB

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 600AT, 600AP

35 AIC

Thermal Curve

INST 8 (4800A)

INST OR (Fixed, No User-Adjustable Setting) Fixed (6000A)

PANEL DP-EQ-6HB

480V, 0A SCCR: 0kA

SCA: 14064A

NSWBD (BLDG 1)

480V, 1600A SCCR: 85kA

SCA: 18453A

NSWBD-2 (DP-N-BEC-A1)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 250AT, 250AP

85 AIC

Phase

LTPU (A) 0.8 (200A)

LTD 8

STPU 10 (2000A)

STD 0.1 (I^s T On)

INST 12 (3000A)

INST OR Fixed (24000A)

GFP

GFPU (0.3-1.0 x S) E (150A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-DP-N-BEC-A1

25ft (1) #250 CU

PANEL DP-N-BEC-A1

480V, 250A SCCR: 35kA

SCA: 14530A

DP-N-BEC-A1 (RP-N-BEC-A2)

480V, SQUARE D

EG

125AF, 125AT, 125AP

35 AIC

Fixed

CBL-T23 (RP-N-BEC-A2)

25ft (1) #1 CU

T-23 (RP-N-BEC-A2)

75kVA 480V-208V 3.58%

CBL-RP-N-BEC-A2

25ft (1) #4/0 CU

RP-N-BEC-A2 MCB

240V, SQUARE D

QD

225AF, 225AT, 225AP

25 AIC

Fixed

PANEL RP-N-BEC-A2

208V, 225A SCCR: 22kA

SCA: 4603A

RP-N-BEC-A2 (RP-N-2EC-A3)

240V, SQUARE D

QO-VH, 3-Pole

100AF, 100AT, 100AP

22 AIC

Fixed (730-8)

CBL-RP-N-2EC-A3

30ft (1) #2 CU

RP-N-2EC-A3 MCB

240V, SQUARE D

QD

100AF, 100AT, 100AP

25 AIC

Fixed

PANEL RP-N-2EC-A3

208V, 100A SCCR: 22kA

SCA: 3731A

NSWBD-2 (DP-N-1EC-A4)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 250AT, 250AP

85 AIC

Phase

LTPU (A) 0.8 (200A)

LTD 24

STPU 10 (2000A)

STD 0.2 (I^s T On)

INST 15 (3750A)

INST OR Fixed (24000A)

GFP

GFPU (0.3-1.0 x S) A (75A) GFD (0-0.4) 0.1 (I^s T On)

CBL-DP-N-1EC-A4

35ft (1) #3/0 CU

DP-N-1EC-A4 MCB

480V, SQUARE D

J-Frame, Powerpact

250AF, 175AT, 175AP

18 AIC

Thermal Curve INST (5-10 x Trip) High (1750A)

PANEL DP-N-1EC-A4

480V, 250A SCCR: 35kA

SCA: 13784A

DP-N-BEC-A4 (EC HU-3)

480V, SQUARE D

J-Frame, Powerpact

250AF, 175AT, 175AP

18 AIC

Thermal Curve INST (5-10 x Trip) High (1750A)

CBL-EC-H-3

50ft (1) #2/0 CU

NFDS-EC-H-3

600V, UL 98

DS

200AF, 10 AIC

DISC-EC-H-3

480V, 0A SCCR: 0kA

SCA: 11201A

NSWBD-2 (SPARE1)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase LTPU/LTD (A 0.4-1.0 x S) 0.7 (280A); 24 STPU (1.5-10 x LTPU) 10 (2800A) STD (INST-0.4) 0.2 (I^s T Off)

GFP

GFPU (0.3-1.0 x S) E (240A) GFD (0-0.4) 0.2 (I^s T Off)

NSWBD-2 (SPARE2)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 100AT, 100AP

65 AIC

Phase

LTPU (A) 1 (100A)

LTD 8

STPU 6 (600A)

STD 0.2 (I^s T Off)

GFP

GFPU (0.3-1.0 x S) J (100A) GFD (0-0.4) 0.2 (I^s T Off)

NSWBD-2 (SPARE3)

508V, SQUARE D

Masterpact NW, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase LTPU/LTD (A 0.4-1.0 x S) 1 (400A); 8 STPU (1.5-10 x LTPU) 6 (2400A) STD (INST-0.4) 0.2 (I^s T Off)

GFP

GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.2 (I^s T Off)

NSWBD-2 (ATS-1)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 1 (800A)

LTD 8

STPU 5 (4000A)

STD INST (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) G (480A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-1(E)

90ft (2) #350 CU

DP-E-BEC-C (ATS-1)

CBL-ATS-1(N)

30ft (2) #350 CU

NSWBD-2 (ATS-1)

ATS-1 (BYPASS ISO)

480V, 800A 200.00kA SCCR

↑2344A SCA

ATS 1

480V, 0A SCCR: 0kA

SCA: 9910A

CBL-ATS-2(E)

80ft (2) #500 CU

DP-E-BEC-C (ATS-2)

NSWBD-2 (ATS-2)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 1 (800A)

LTD 24

STPU 8 (6400A)

STD 0.2 (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) F (560A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-2(N)

120ft (2) #500 CU

NSWBD-2 (ATS-2)

ATS-2 (BYPASS ISO)

480V, 600A 200.00kA SCCR

↑0A SCA

ATS 2

480V, 0A SCCR: 0kA

SCA: 9666A

NSWBD-2 (EC)

480V, 1600A SCCR: 85kA

SCA: 15844A

CBL-EMCC-E-BEC-C2

160ft (2) #350 CU

DP-E-BEC-C (ATS-G)

DP-EQ-BA3-01 MCB

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 800AT, 800AP

35 AIC

Thermal Curve

INST 5 (4000A)

INST OR (Fixed, No User-Adj. Setting) Fixed (8000A)

PANEL DP-EQ-BA3-01

480V, 800A SCCR: 200kA

SCA: 9108A

(SEE SHEET EP-112) (SEE SHEET EP-112)

FED FROM ESWBD

(SEE SHEET EP-104)

FED FROM ESWBD

(SEE SHEET EP-104)

(SEE SHEET EP-105) (SEE SHEET EP-109)

FED FROM ESWBD

(SEE SHEET EP-104)

FED FROM ESWBD

(SEE SHEET EP-104)

(SEE SHEET EP-110) (SEE SHEET EP-108)

FED FROM T-3

(SEE SHEET EP-100)

FED FROM T-14

(SEE SHEET EP-100)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

EP-103

BLDG. 1 NORMAL POWER

NSWBD & NSWBD-2

ONE-LINE DIAGRAM

ELECTRICAL MAINTENANCE

GEN2-LOADBANK

GEN6-LOADBANK

E N E N E N

E N E N E N E N

E N

GEN-1

400kW/500kVA 208V

SCA: 9241A

GEN-1 CB

240V, MERLIN GERIN

Compact CK, STR 25DP

1200AF, 1200AT, 1000AP

65 AIC

LTPU (0.8-1.0 x P) 1 (1000A) LTD (Fixed) Fixed INST (1.5-10 x LTPU) 10 (10000A) INST Delay (Fixed) Fixed INST Override Fixed (14400A)

ECB B19 GEN-1

208V, 0A SCCR: 0kA

SCA: 9689A

CBL- B19 GEN-1-PUMP

5ft (1) #4 CU

FUSE-B19 GEN-1-PUMP

250V, BUSSMANN

DLN-R, 250V Class RK5

35AF, 35AT, 200 AIC

DISC-B19 GEN-1-PUMP

208V, 0A SCCR: 0kA

SCA: 9503A

CBL- ESWBD GEN-1

100ft (3) #500 CU

CBL- B19 GEN-1-RAD

30ft (1) #10 CU

FUSE-B19 GEN-1-RAD

250V, BUSSMANN

DLN-R, 250V Class RK5

35AF, 35AT, 200 AIC

START-B19 GEN-1-RAD

208V, 0A SCCR: 0kA

SCA: 8661A

CBL- DISC-B19 GEN-1-RAD

30ft (1) #10 CU

DISC-B19 GEN-1-RAD

208V, 0A SCCR: 0kA

SCA: 7812A

CB GEN1-LOADBANK

0V, 0AF, 0AP

0 AIC

CBL- GEN1-LOADBANK

30ft (3) #4/0 CU

GEN1-LOADBANK

ESWBD GEN-1

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 0.8 (640A)

LTD 8

STPU 10 (6400A)

STD 0.1 (I^s T Off)

INST 15 (12000A)

GFP

GFPU (500-1200A) C (720A)

GFD (0-0.4) 0.1 (I^s T Off)

ESWBD SECTION-1 (BLDG 1)

208V, 1600A SCCR: 85kA

SCA: 8667A ESWBD (ATS-A)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 1 (400A)

LTD 12

STPU 10 (4000A)

STD 0.1 (I^s T On)

INST 12 (4800A)

GFP

GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)

CBL-ATS-A(E)

35ft (2) #4/0 CU

ESWBD (ATS-A)

CBL-ATS-A(N)

45ft (2) #4/0 CU

SWBD-1 (ATS-A)

ATS-A

480V, 400A 200.00kA SCCR

↑459A SCA

ATS A

208V, 0A SCCR: 0kA

SCA: 8134A

ESWBD (ATS-B)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 400AT, 400AP

100 AIC

Phase

LTPU (A) 1 (400A)

LTD 4

STPU 8 (3200A)

STD 0.1 (I^s T On)

INST 12 (4800A)

GFP

GFPU (0.3-1.0 x S) J (400A) GFD (0-0.4) 0.1 (I^s T On)

CBL-ATS-B(E)

35ft (2) #4/0 CU

ESWBD (ATS-B)

CBL-ATS-B(N)

50ft (2) #4/0 CU

SWBD-1 (ATS-B)

ATS-B

480V, 400A 200.00kA SCCR

↑0A SCA

ATS B

208V, 0A SCCR: 0kA

SCA: 8067A

ESWBD TIE

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1000AT, 1000AP

42 AIC

Phase

LTPU (A) 1 (1000A)

LTD 0.5

STPU 1.5 (1500A)

STD 0.1 (I^s T Off)

INST 2 (2000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.3 (I^s T Off)

ESWBD (SPARE1)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 4 (3200A)

STD 0.1 (I^s T On)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)

ESWBD (ATS-E)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 16

STPU 5 (4000A)

STD INST (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)

CBL-ATS-E(E)

10ft (3) #500 CU

ESWBD (ATS-E)

ATS-E (MDP)

480V, 800A 200.00kA SCCR

↑307A SCA

ATS E (MDP)

208V, 0A SCCR: 0kA

SCA: 8692A

CBL-ATS-E(N)

80ft (3) #500 CU

SWBD-2 (ATS-E)

ESWBD (ATS-C)

254V, SQUARE D

Masterpact NW H3, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

100 AIC

Phase

LTPU (A) 1 (800A)

LTD 24

STPU 8 (6400A)

STD 0.1 (I^s T On)

INST 8 (6400A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.1 (I^s T On)

CBL-ATS-C(E)

40ft (3) #300 CU

ESWBD (ATS-C)

CBL-ATS-C(N)

30ft (3) #300 CU

SWBD-1 (ATS-C)

ATS-C

480V, 800A 200.00kA SCCR

↑0A SCA

ATS C

208V, 0A SCCR: 0kA

SCA: 8342A

ESWBD SECTION-2 (BLDG 1)

208V, 1600A SCCR: 85kA

SCA: 8790A

ESWBD GEN-2

254V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

1600AF, 1000AT, 1000AP

42 AIC

Phase

LTPU (A) 1 (1000A)

LTD 24

STPU 8 (8000A)

STD 0.3 (I^s T On)

INST 8 (8000A)

GFP

GFPU (500-1200A) J (1200A)

GFD (0-0.4) 0.4 (I^s T On)

DISC-B19 GEN-2-PUMP

208V, 0A SCCR: 0kA

SCA: 9698A

FUSE-B19 GEN-2-PUMP

250V, BUSSMANN

DLN-R, 250V Class RK5

20AF, 20AT, 200 AIC

CBL- B19 GEN-2-PUMP

5ft (1) #12 CU

CBL- ESWBD GEN-2

100ft (3) #500 CU

CBL- B19 GEN-2-RAD

5ft (1) #6 CU

FUSE-B19 GEN-2-RAD

250V, BUSSMANN

DLN-R, 250V Class RK5

60AF, 60AT, 200 AIC

START-B19 GEN-2-RAD

208V, 0A SCCR: 0kA

SCA: 9698A

CBL- B19 GEN-2-RAD (DISC)

10ft (1) #10 CU

DISC-B19 GEN-2-RAD

208V, 0A SCCR: 0kA

SCA: 9331A

CB GEN2-LOADBANK

0V, 0AF, 0AP

0 AIC

CBL- GEN2-LOADBANK

25ft (3) #4/0 CU

ECB B19 GEN-2

208V, 0A SCCR: 0kA

SCA: 9890A

GEN-2 CB

480V, GE

SS, SH PowerBreak II, MVT Plus/PM

1600AF, 1000AT, 1000AP

65 AIC

LTPU (0.5-1.0 x P) 1 (1000A)

LTD (1-4) 4

INST (1.5-10 x P) 10 (10000A)

GEN-2

415kW/519kVA 208V

SCA: 9587A

GEN-6

750kW/938kVA 480V

SCA: 7508A

GEN-6 CB

480V, GE

SS, SH PowerBreak II, EGTU

1600AF, 1600AT, 1200AP

100 AIC

LTPU 0.95X (1140A)

LTD C-10

STPU 1.5X (1710A)

STD ST10-Int (I^s T Off)

INST ST(ON) 10X (12000A)

Override (HSIOC) Fixed (46000A)

CBL-DP-E-2EC-C

75ft (4) #350 CU

CBL- GEN6-LOADBANK

75ft (5) #4/0 CU

GENERATOR 6 BUS

480V, 0A SCCR: 0kA

SCA: 10535A

DP-E-BEC-C (ATS-2)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 1 (800A)

LTD 4

STPU 8 (6400A)

STD 0.1 (I^s T Off)

INST 3 (2400A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-2(E)

80ft (2) #500 CU

DP-E-BEC-C (ATS-2)

CBL-ATS-2(N)

120ft (2) #500 CU

NSWBD-2 (ATS-2)

ATS-2 (BYPASS ISO)

480V, 600A 200.00kA SCCR

↑0A SCA

ATS 2

480V, 0A SCCR: 0kA

SCA: 9666A

DP-E-BEC-C (ATS-1)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 1 (800A)

LTD 8

STPU 5 (4000A)

STD INST (I^s T Off)

INST 6 (4800A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-1(E)

90ft (2) #350 CU

DP-E-BEC-C (ATS-1)

CBL-ATS-1(N)

30ft (2) #350 CU

NSWBD-2 (ATS-1)

ATS-1 (BYPASS ISO)

480V, 800A 200.00kA SCCR

↑2344A SCA

ATS 1

480V, 0A SCCR: 0kA

SCA: 9910A

DP-E-BEC-C (ATS-F)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 800AT, 800AP

42 AIC

Phase

LTPU (A) 1 (800A)

LTD 12

STPU 4 (3200A)

STD 0.2 (I^s T On)

INST 4 (3200A)

GFP

GFPU (0.2-1.0 x S) J (800A) GFD (0-0.4) 0.2 (I^s T Off)

CBL-ATS-F(E)

160ft (2) #500 CU

DP-E-BEC-C (ATS-F)

CBL-ATS-F(N)

10ft (2) #500 CU

NSWBD (DP-EQ-BA3-01)

ATS-F (BYPASS ISO)

480V, 800A 200.00kA SCCR

↑791A SCA

ATS F

480V, 0A SCCR: 0kA

SCA: 9234A

DP-E-BEC-C (ATS-G)

508V, SQUARE D

Masterpact NW N1/H1/H2, 5.0 & 6.0 A/P/H

800AF, 600AT, 600AP

42 AIC

Phase

LTPU (A) 1 (600A)

LTD 16

STPU 8 (4800A)

STD 0.1 (I^s T Off)

INST 2 (1200A)

GFP

GFPU (0.2-1.0 x S) G (480A) GFD (0-0.4) 0.2 (I^s T On)

CBL-EMCC-E-BEC-C2

160ft (2) #350 CU

DP-E-BEC-C (ATS-G)

CBL- ATS G(N)

20ft (2) #350 CU

NSWBD (DP-EQ-6HB)

ATS-G (BYPASS ISO)

0V, 0A 0.00kA SCCR

↑2127A SCA

ATS G PANEL DP-EQ-6HB

480V, 0A SCCR: 0kA

SCA: 17930A

PANEL DP-E-2EC-C (EC)

480V, 1600A SCCR: 85kA

SCA: 10385A

G G

NO

G

FED FROM SWBD-1

(SEE SHEET EP-102)

FED FROM SWBD-1

(SEE SHEET EP-102)

FED FROM SWBD-2

(SEE SHEET EP-102)

FED FROM SWBD-1

(SEE SHEET EP-102)

FED FROM NSWBD-2

(SEE SHEET EP-103)

FED FROM NSWBD-2

(SEE SHEET EP-103)

FED FROM NSWBD

(SEE SHEET EP-103)

FED FROM NSWBD

(SEE SHEET EP-103)

(SEE SHEET EP-102) (SEE SHEET EP-102) (SEE SHEET EP-102) (SEE SHEET EP-102)

(SEE SHEET EP-103) (SEE SHEET EP-103) (SEE SHEET EP-103) (SEE SHEET EP-103)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

ALEDA E. LUTZ MEDICAL CTR.

Project Director

Issue date Chkd By JAJ Revisions: Date:

EP-104

BLDG. 1 EM. POWER

GEN-1, 2, 6, ESWBD, DP-E-2EC-C

ONE-LINE DIAGRAM

ELECTRICAL MAINTENANCE

EMDP (EQBD)

240V, SQUARE D

QD

150AF, 150AT, 150AP

25 AIC

Fixed

CBL-EQBD

277ft (1) #4/0 CU

PANEL EQBD

208V, 225A SCCR: 22kA

SCA: 3472AEQBD (B321 WASHER)

240V, SQUARE D

Q1 (Obs.)

30AF, 30AT, 30AP

5 AIC

Fixed

CBL-B321-WASHER

75ft (1) #10 CU

FUSE-B321 WASHER

250V, BUSSMANN

FRN-R, 250V Class RK5

20AF, 20AT, 200 AIC

DISC-B321 WASHER

208V, 0A SCCR: 0kA

SCA: 3000A

EQBD (B321 DRYER)

240V, SQUARE D

Q1 (Obs.)

100AF, 100AT, 100AP

5 AIC

Fixed

CBL-B321-DRYER

75ft (1) #2 CU

FUSE-321 DRYER

250V, BUSSMANN

FRN-R, 250V Class RK5

100AF, 100AT, 200 AIC

DISC-321-DRYER

208V, 0A SCCR: 0kA

SCA: 3000A

EQBD (B330 HUM.)

240V, SQUARE D

Q1 (Obs.)

30AF, 30AT, 30AP

5 AIC

Fixed

CBL-B330 HUMIDIFIER

75ft (1) #12 CU

B330 HUMIDIFIER

208V, 0A SCCR: 0kA

SCA: 3000A

EQBD (B1-DOCK LIFT)1

240V, SQUARE D

QO-VH, 3-Pole

20AF, 20AT, 20AP

22 AIC

Fixed (730-4, 20A)

CBL-B338-MINI-SPLIT-CU

75ft (1) #12 CU

NONE

DISC-B338-MINI-SPLIT-CU

208V, 0A SCCR: 0kA

SCA: 0A

DISC-B324-MINI-SPLIT-CU

208V, 0A SCCR: 0kA

SCA: 0A

CBL-B324-MINI-SPLIT-CU

75ft (1) #12 CU

NONE

EQBD (B324-MINI-SPLIT-CU)

240V, SQUARE D

QO-VH, 3-Pole

30AF, 30AT, 30AP

22 AIC

Fixed (730-5, 30A)

DISC-B1-DOCK-LIFT

208V, 0A SCCR: 0kA

SCA: 732A

CBL-B1-DOCK-LIFT

75ft (1) #12 CU

NONE

EQBD (B1-DOCK LIFT)

240V, SQUARE D

QO-VH, 3-Pole

20AF, 20AT, 20AP

22 AIC

Fixed (730-4, 20A)

CBL-DP-EQ-BA3-01

20ft (2) #500 CU

ATS F

DP-EQ-BA3-01 MCB

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 800AT, 800AP

35 AIC

Thermal Curve

INST 5 (4000A)

INST OR (Fixed, No User-Adjustable Setting) Fixed (8000A) PANEL DP-EQ-BA3-01

480V, 800A SCCR: 200kA

SCA: 9108ADP-EQ-BA3-01 (AIR CURTAIN)

480V, SQUARE D

HD

40AF, 40AT, 40AP

18 AIC

Fixed

CBL-AIR-CURTAIN

150ft (1) #8 CU

NONE

DISC-AIR-CURTAIN

480V, 0A SCCR: 0kA

SCA: 2083A

DP-EQ-BA3-01 (EQP-1)

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 600AT, 600AP

35 AIC

Thermal Curve

INST 4 (2400A)

CBL-EQP-1.

146ft (2) #350 CU

DP-EQ-BA3-01 (EQP-1)

EQP-1-MCB

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 600AT, 600AP

35 AIC

Thermal Curve

INST 4 (2400A)

DP-EQ-BA3-01 (B01 FRONT ELEV)

600V, SQUARE D

HG

100AF, 100AT, 100AP

18 AIC

Fixed

CBL-B01 FRONT ELEV

260ft (1) #4 CU

NONE

DISC-B01 FRONT ELEV

480V, 0A SCCR: 0kA

SCA: 2778A

CBL-EQH-BC-TAP-1

275ft (1) #350 CU

NONE

DP-EQ-BA3-01 (EQH-BC TAP)

480V, SQUARE D

MG w/ ET1.0, 2-8x Inst.

800AF, 300AT, 300AP

35 AIC

Thermal Curve

INST 4 (1200A)

CBL-B1-EQ-HBC

10ft (1) #4/0 CU

NONE

DISC-B1-EQ-HBC

480V, 0A SCCR: 0kA

SCA: 5921A

FUSE-B1-EQ-HBC

600V, BUSSMANN

FRS-R, 600V Class RK5

200AF, 200AT, 200 AIC

CBL-PANEL-EQ-HBC

6ft (1) #4/0 CU

NONE

PANEL EQ-HBC

480V, 0A SCCR: 0kA

SCA: 5869AEQ-HBC (B100 AREA AHU-8)

480V, SQUARE D

ED

15AF, 15AT, 15AP

18 AIC

Fixed

CBL-B100 AREA-AHU-8

100ft (1) #12 CU

NONE

DISC-B100 AREA-AHU-8

480V, 0A SCCR: 0kA

SCA: 1319A

DISC-B100 AREA-CU-8

480V, 0A SCCR: 0kA

SCA: 1921A

CBL-B100 AREA-CU-8

100ft (1) #10 CU

NONE

EQ-HBC (B100 AREA-CU-8)

480V, SQUARE D

ED

35AF, 35AT, 35AP

18 AIC

Fixed

START-B100 AREA-RF-8

480V, 0A SCCR: 0kA

SCA: 2693A

FUSE-B100 AREA-RF-8

0V, 0AF, 0 AIC

CBL-START-B100 AREA-RF-8

40ft (1) #12 CU

NONE

EQ-HBC (B100 AREA-RF-8)

480V, SQUARE D

ED

15AF, 15AT, 15AP

18 AIC

Fixed

TAP EQH-BC

480V, 0A SCCR: 0kA

SCA: 6008A

CBL-DISC-EQ-HBC1

50ft (1) #350 CU

NONE

DISC-B1-EQ-HBC1

480V, 0A SCCR: 0kA

SCA: 5647A

FUSE-DISC-B1-EQ-HBC1

600V, BUSSMANN

FRS-R, 600V Class RK5

300AF, 300AT, 200 AIC

CBL-DISC-B1-EQ-HBC2

50ft (1) #350 CU

NONE

DISC-B1-EQ-HBC2

480V, 0A SCCR: 0kA

SCA: 5485A

FUSE-B1-EQ-HBC2

600V, BUSSMANN

FRS-R, 600V Class RK5

100AF, 100AT, 200 AIC

CBL-TAP-B1-EQ-HBC2

150ft (1) #4 CU

NONE

TAP-B1-EQ-HBC2

480V, 0A SCCR: 0kA

SCA: 0AFUSE-B34-EQ-H1S2

600V, BUSSMANN

FRS-R, 600V Class RK5

40AF, 40AT, 200 AIC

CBL-TAP-B1-EQ-HBC3

10ft (1) #4 CU

NONE

DISC-B34-EQ-H1S2

480V, 0A SCCR: 0kA

SCA: 0A

T-32 225kVA 480V-208V 3.90%

PB-EQ-1S1-34

208V, 0A SCCR: 0kA

SCA: 7085A

CBL-DISC-B34-EQ-H1S1

1ft (1) #12 CU

NONE

DISC-B34-EQ-H1S3

480V, 0A SCCR: 0kA

SCA: 0A

FUSE-B34-EQ-H1S3

600V, BUSSMANN

FRS-R, 600V Class RK5

40AF, 40AT, 200 AIC

CBL-TAP-B1-EQ-HBC4

10ft (1) #4 CU

NONE

DISC-B34-EQ-H1S1

480V, 0A SCCR: 0kA

SCA: 0A

EMDP (EQBB2)

240V, SQUARE D

QD

200AF, 200AT, 200AP

25 AIC

Fixed

CBL-EQBB2

282ft (1) #250 CU

EQBB2 (B1-HTP-1-P1)

240V, SQUARE D

Q1 (Obs.)

20AF, 20AT, 20AP

5 AIC

Fixed

CBL-B1-HTP-1-P1

50ft (1) #12 CU

FUSE-B1-HTP-1-P1

250V, BUSSMANN

FRN-R, 250V Class RK5

15AF, 15AT, 200 AIC

DISC-VFD-B1-HTP-1-P1

208V, 0A SCCR: 0kA

SCA: 3235A

EQBB2 (B1-HTP-1-P2)

240V, SQUARE D

Q1 (Obs.)

30AF, 30AT, 30AP

5 AIC

Fixed

CBL-B1-HTP-1-P2

50ft (1) #12 CU

NONE

FUSE-B1-HTP-1-P2

250V, BUSSMANN

FRN-R, 250V Class RK5

15AF, 15AT, 200 AIC

DISC-VFD-B1-HTP-1-P2

208V, 0A SCCR: 0kA

SCA: 3235A

EQBB2-(MORGUE-AHU)

240V, SQUARE D

Q1 (Obs.)

30AF, 30AT, 30AP

5 AIC

Fixed

CBL-1B-MORGUE-AHU

50ft (1) #10 CU

FUSE-…