S02 - Attachment 3 - Basic Guidance - 208V Power Distribution White Paper.pdf
PDF 253 KB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrades - MPD (VA-21-00024176) Federal contract opportunity
- Solicitation number
- 36C77621R0074
About this file
This document provides details for a federal contract opportunity to upgrade infrastructure for the Electronic Health Records Modernization program at the VA Palo Alto Health Care System. The Department of Veterans Affairs seeks to award a single firm-fixed-price design-build contract to provide all labor, materials, tools and equipment, and services necessary to design, pre-construction, construct, and closeout a project involving the relocation or remodel of approximately 49 existing telecommunications rooms and 3 data centers to meet VA Office of Information and Technology and EHRM infrastructure standards while maintaining IT services. The solicitation will be issued as a request for proposal conducted in accordance with FAR Part 36.3 procedures and evaluated based on the criteria in the solicitation. The opportunity is set aside as a total Service-Disabled Veteran-Owned Small Business set-aside with a North American Industry Classification System code of 236220 and size standard of $39.5 million. The period of performance is approximately 739 calendar days from notice to proceed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 3.pdf | ||
| 36C77621R0074 0001.docx | DOCX document | |
| Attachment 2.docx | DOCX document | |
| Attachment 1.pdf | ||
| S02 - Attachment 9 - SOCAMES 6 Design Alert 4.pdf | ||
| S02 - Attachment 6 - SOCAMES 6 Design Alert 1.pdf | ||
| S02 - Attachment 5 - 00 VA OEHRM Site Infrastructure Requirements v2.0.pdf | ||
| S02 - Attachment 7 - SOCAMES 6 Design Alert 2.pdf | ||
| S02 - Attachment 4 - Basic Guidance - Zone PDU Power Distribution.pdf | ||
| S02 - Attachment 8 - SOCAMES 6 Design Alert 3.pdf | ||
| S02 - Attachment 12 - Wage Determination - Services.pdf | ||
| S02 - Attachment 11 - Wage Determination - Construction.pdf | ||
| S02 - Attachment 10 - VA Menlo Park EHRM Project Manual Final.pdf | ||
| S02 - Attachment 2 - VA Menlo Park EHRM SPECS - Final.pdf | ||
| 36C77621R0074_1.docx | DOCX document | |
| S02 - Attachment 1 - VA Menlo Park EHRM Narrative - FINAL.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Basic Guidance: 208V Power Distribution White Paper
VA standards for power distribution in telecommunications spaces specify the use of 3-phase 208V power at the IT equipment enclosure.
All modern IT equipment is equipped with auto-ranging power supply units (PSUs) that allow a range of voltage inputs, typically from 100V to 240V. This equipment functions more efficiently at higher voltages.
There is a 1 to 2 percent improvement in power supply efficiency when using 208V distribution over 120V distribution. In order to supply the same number of Watts to a server, a 120V circuit has to push more amperage than a 208V circuit. The more current carried, the more resistive heat generated, and the harder the server fans and overall data center cooling systems have to work. Less power is consumed when using the higher voltage.
The Solution Delivery (SD) Data Center & Infrastructure Engineering team has developed this guidance as a supplementary narrative to the OIT Design Guide Templates in order to provide additional detail for field OIT and FMS staff, A/Es, and implementing contractors and VA staff. Please contact the Data Center & Infrastructure Engineering team for additional detail as necessary.
mailto:%20VAITESEDatacenterEngineering2@va.gov?subject=RE:%20Single-Rack%20TR%20Design%20&%20Outfitting
Unless otherwise specified, some servers and switches are shipped with 120V power cords.
Using IEC-60320 208V power cords (“couplers”) allows us to use the 208V banks in the standard 3-phase Rack PDUs specified in the Infrastructure Standard for Telecommunications Spaces, and to deliver up to either 15A (C13-Type E) or 20A (C19-Type I) to the IT equipment at the higher voltage. Specification of the IEC-60320 power cord option when ordering active equipment is necessary. (Note: The C13-Type E power cord is typically referred to as a C13-C14 power cord by retailers.)
The standard 3-phase Rack PDUs required for IT equipment enclosures in the data center and in Telecommunications Rooms (TRs) have Type F and Type J outlets (receptacles) typically grouped into three banks.
Each bank is provided from a different pair of the single-phase 120V phases. These may be grouped together, color-coded, or both.
The use of the 3-phase distribution equipment also simplifies power management within the telecommunications space, as phase balancing can be accomplished simply by relocating a power cord from one bank to another.
Practically speaking, 208V distribution requires the use of 3-pole circuit breakers on 120/208V circuit breaker panelboards, and circuits with 5 wires (A phase, B phase, C phase, neutral, and ground, or L+L+L+N+G). The power distribution equipment connected to these circuits – typically a Rack PDU – then supplies 208V power as the difference between the voltages on any pair of the phase wiring (A & B, B & C, or C & A). (Phases A, B, and C may also be called lines 1, 2, and 3, or L1, L2 ,and L3.)
Where the voltage on each individual phase or line varies between 0 and 120 volts, following a sine wave that repeats 60 times each second (60Hz), the resultant of combining two of these phases gives us a sine wave with a voltage that varies between 0 and 208 volts. This is shown graphically below.
References:
VA OIT Infrastructure Standards for Telecommunications Spaces:
https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdsTelecommSpaces.pdf VA OIT Design Guide Templates:
https://www.cfm.va.gov/til/dGuide/OIT-DGTemplates-CriticalTelecommSpaces.pdf
-240 -210 -180 -150 -120
-90 -60 -30
0 90 180 270 360 450 540 630 720
Vo lta ge (V
208V Power from (2) 120V 60Hz phases
Phase A Phase B 208V Resultant https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdsTelecommSpaces.pdf https://www.cfm.va.gov/til/dGuide/OIT-DGTemplates-CriticalTelecommSpaces.pdf