This file contains drawings related to a federal solicitation for upgrades to elevators at three buildings on the Memphis VA Medical Center campus. The solicitation number is 36C24924R0024 and seeks to upgrade elevators in Buildings 1, 1A, and 7. The work includes modernizing elevator equipment and controls, replacing elevator cab interiors, and ensuring compliance with all applicable safety codes. Bids are due by June 22, 2023, and the contract is expected to be awarded by August 2023. The Veterans Health Administration within the Department of Veterans Affairs is the contracting agency.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYMBOLS LEGEND

RIGID INSULATION

WOOD ROUGH (CONTINUOUS)

WOOD ROUGH (SPACED)

EARTH

CONCRETE

BLOCK WALL/VENEER

GYPSUM BOARD

PLYWOOD

BATT INSULATION

NEW CONSTRUCTION

EXISTING CONSTRUCTION TO

BE REMOVED

DIMENSION LINE

BREAK LINE

DETAIL INDICATOR

X

X-XX

DETAIL INDICATOR

X

X-XX

X

X-XX

BUILDING SECTION INDICATOR

X

X-XX

X

X-XX

ELEVATION INDICATOR, EXTERIOR

ELEVATION INDICATOR

CENTER LINE

ELEVATION INDICATOR, INTERIOR,X-XX

X

X-XX

X

X

X

X

NORTH ARROW

CG

CORNER GUARD

FEC FIRE EXTINGUISHER CABINET

XX KEYNOTE

A GRID LINES

XXX

ROOM

ROOM NAME AND NUMBER

XX

FURNITURE, FIXTURE, & EQUIPMENT

INDICATOR

XXX

DOOR OPENING/BORROWED LIGHT

IDENTIFIER

XX DRAWING BLOCK TITLE,

TYPICAL

DRAWING TITLE

XX=XX

XX INTERIOR PARTITION TYPES

NORTH

VICINITY MAP

NOTE: CONTRACTOR ACCESS AND STAGING AREA TO BE COORDINATED WITH COR FOLLOWING AWARD OF CONTRACT.

BID ITEMS

REFERENCE SECTION 010000 GENERAL REQUIREMENTS ITEM 1.3 STATEMENT OF BID ITEMS.

A. ITEM I, BASE BID: Replacement of the existing traction elevators in the designated buildings. The work of replacement is specialized at each bank of elevators, as shown in Bid Documents, but includes:

1. Building 1 – Demolition of existing elevator cab, platform and doors at shafts and all elevator equipment, controls and cabling located in penthouse. Install all new elevator cab, platform and doors at shafts and all elevator equipment, controls and cabling located in penthouse, within the existing shafts. Works to be only on elevators marked S2, S3, P5 and P6 in Building 1.

2. Building 1A – Demolition of existing traction elevator controls and cabling located in penthouse. Install all new controls and cabling located in penthouse, within the existing shafts. Works to be only on elevators marked S32, S33 and S34

3. Building 7 – Demolition of existing hydraulic elevator cabs, platform and doors at shafts and all elevator equipment, controls and cabling located in penthouse. Install all new elevator cab, platform and doors at shafts and all elevator equipment, controls and cabling located in penthouse, within the existing shafts. Works to be only on elevators marked P22, P23, P24, P25, P26, S27.

B. BID DEDUCT NO.1: Delete all works related to Building 1A, controls replacement, as described in the Bid Documents and item A-2 above. Delete all general conditions, phasing, protection barriers, mechanical, electrical and plumbing related to works in Building 1A.

SHEET INDEX

01 - GENERAL

G-000 COVER SHEET

G-001 ACCESSIBILITY DETAILS

G-002 LIFE SAFETY CODE REVIEW PLANS

G-003 PHASE 1 PLANS

G-004 PHASE 2 PLANS - ELEVATOR 1A

G-005 PHASE 2 PLANS - ELEVATOR 1 & ELEVATOR 7

G-006 PHASE 3 PLANS

05 - ARCHITECTURAL DEMOLITION

AD-101 BUILDING 1 DEMOLITION ELEVATOR FLOOR PLANS

AD-102 BUILDING 1 DEMOLITION ELEVATOR FLOOR PLANS

AD-103 BUILDING 1 DEMOLITION ELEVATOR FLOOR PLANS

AD-110 BUILDING 1A DEMOLITION ELEVATOR FLOOR PLANS

AD-111 BUILDING 1A DEMOLITION ELEVATOR FLOOR PLANS

AD-112 BUILDING 1A DEMOLITION ELEVATOR FLOOR PLANS

AD-120 BUILDING 7 ELEVATOR S27 DEMOLITION PLANS

AD-121 BUILDING 7 ELEVATORS P22, P23, & P24 DEMOLITION PLANS

AD-122 BUILDING 7 ELEVATORS P22, P23, & P24 DEMOLITION PLANS

AD-123 BUILDING 7 ELEVATORS P25 & P26 DEMOLITION PLANS

06 - ARCHITECTURAL

A-101 BUILDING 1 ELEVATOR FLOOR PLANS

A-102 BUILDING 1 ELEVATOR FLOOR PLANS

A-103 BUILDING 1 ELEVATOR FLOOR PLANS

A-104 BUILDING 1 ELEVATOR SECTIONS

A-110 BUILDING 1A ELEVATOR PLANS - ELEVATORS S32, S33, & S34

A-111 BUILDING 1A ELEVATOR PLANS - ELEVATORS S32, S33, & S34

A-112 BUILDING 1A ELEVATOR PLANS - ELEVATORS S32, S33, & S34

A-120 BUILDING 7 ELEVATOR S27 PLANS AND SECTIONS

A-121 BUILDING 7 ELEVATORS P22, P23, & P24 PLANS AND SECTIONS

A-122 BUILDING 7 ELEVATORS P22, P23, & P24 PLANS AND SECTIONS

A-123 BUILDING 7 ELEVATOR P25 & P26 PLANS

A-124 BUILDING 7 ELEVATOR P25 & P26 SECTIONS

A-201 BUILDINGS 1A & 1 - ELEVATOR LOBBY ELEVATIONS

A-202 BUILDING 7 - ELEVATOR LOBBY ELEVATIONS

A-450 ELEVATOR CAB INTERIOR ELEVATIONS - BUILDINGS 1 & 1A

A-451 ELEVATOR CAB INTERIOR ELEVATIONS - BUILDING 7

A-501 DETAILS AND FINISH SCHEDULE

10 - MECHANICAL

M-000 MECHANICAL SYMBOLS AND ABBREVIATIONS

MD-102 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 MECHANICAL DEMO

MD-112 BUILDING 1A ELEVATOR PLANS S32, S33, & S34 MECHANICAL DEMO

MD-121 BUILDING 7 ELEVATOR PLANS P22, P23, & P24 MECHANICAL DEMO

MD-122 BUILDING 7 ELEVATOR PLANS P25, P26 MECHANICAL DEMO

MD-123 BUILDING 7 ELEVATOR PLANS S27 MECHANICAL DEMO

M-101 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 MECHANICAL

M-102 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 MECHANICAL

M-111 BUILDING 1A ELEVATOR PLANS S32, S33, & S34 MECHANICAL

M-112 BUILDING 1A ELEVATOR PLANS S32, S33, S34 MECHANICAL

M-121 BUILDING 7 ELEVATOR PLANS P22, P23, P24 MECHANICAL

M-122 BUILDING 7 ELEVATOR PLANS P25, P26 MECHANICAL

M-123 BUILDING 7 ELEVATOR PLANS S27 MECHANICAL

M-600 MECHANICAL DETAILS AND CONTROLS

M-700 MECHANICAL SCHEDULES

11 - ELECTRICAL

E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

ED-101 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 ELECTRICAL DEMO

ED-102 BUILDING 1 ELEVATOR FLOOR PLANS S2, S3 & P6, P7 ELECTRICAL DEMO

ED-111 BUILDING 1A ELEVATOR PLANS S32, S33, & S34 ELECTRICAL DEMO

ED-112 BUILDING 1A ELEVATOR PLANS S32, S33, S34 ELECTRICAL DEMO

ED-113 BUILDING 1A ELEVATOR PLANS S32, S33, S34 ELECTRICAL DEMO

ED-120 BUILDING 7 ELEVATOR PLANS P22, P23, P24 ELECTRICAL DEMO

ED-122 BUILDING 7 ELEVATOR PLANS P25, P26 ELECTRICAL DEMO

ED-123 BUILDING 7 ELEVATOR PLANS S27 ELECTRICAL DEMO

E-101 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 ELECTRICAL

E-102 BUILDING 1 ELEVATOR PLANS S2, S3 & P6, P7 ELECTRICAL

E-111 BUILDING 1A ELEVATOR PLANS S32, S33, S34 ELECTRICAL

E-112 BUILDING 1A ELEVATOR PLANS S32, S33, S34 ELECTRICAL

E-113 BUILDING 1A ELEVATOR PLANS S32, S33, S34 ELECTRICAL

E-120 BUILDING 7 ELEVATOR PLANS P22, P23, P24 ELECTRICAL

E-122 BUILDING 7 ELEVATOR PLANS P25 & P26 ELECTRICAL

E-123 BUILDING 7 ELEVATOR PLANS S27 ELECTRICAL

E-201 ELEVATOR ELEVATIONS - BUILDING 1, 1A

E-202 ELEVATOR ELEVATIONS - BUILDING 7

E-600 ELEVATOR DETAILS

E-700 ELECTRICAL SCHEDULES

TOTAL SHEET COUNT: 70

PROJECT

LOCATION

1030 Jefferson Ave, Memphis, TN 38104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

10360 Ellison Circle Omaha, NE 68134 402-991-5520

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:0

A M

G-000

COVER SHEET VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

ELEVATOR UPGRADE IN BUILDINGS 1, 1A, & 7

MEMPHIS VA MEDICAL CENTER

DEPT OF VETERANS AFFAIRS

1030 JEFFERSON AVE, MEMPHIS, TN 38104

BID DOCUMENTS

VA PROJECT #614-22-105

06/09/23

ABBREVIATIONS

THK THICKNESS

THRU THROUGH

TKBD TACKBOARD

TL TILE

TO TOP OF

TOB TOP OF BEAM

TOC TOP O F CONCRETE/CURB

TOD TOP OF DECK

TOF TOP OF FOOTING (FOUNDATION)

TOJ TOP OF JOIST

TOM TOP OF MASONRY

TOP TOP OF PIER

TOS TOP OF SLAB/STEEL

TOW TOP OF WALL

TPD TOILET PAPER DISPENSER

TPO THERMOPLASTIC POLYOLEFIN

TPTN TOILET PARTITION

TRANS TRANSVERSE

TS TUBE STEEL

TYP TYPICAL

U

UG UNDERGROUND

UH UNIT HEATER

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

UTIL UTILITY

V

V SHEAR

VAR VARIES

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VR VAPOR RETARDER

VWC VINYL WALL COVERING

W

W WEST/WIDTH

W/ WITH

W//O WITHOUT

WA WEDGE ACHOR

WB WOOD BASE

WC WATER CLOSET

WD WOOD/WOODWORK

WDW WINDOW

WF (W) WIDE FLANGE

WG WALL GUARD

WH WATER HEATER

WI WROUGHT IRON

WL WIND LOAD

WP WATERPROOF (ING)

WR WATER RESISTANT

WSCT WAINSCOT

WT WEIGHT / WINDOW TREATMENT

WWF WELDED WIRE FABRIC

ABBREVIATIONS

REINF REINFORC (D), (ING), (MENT)

REQ REQUIRE

REQD REQUIRED

RES RESILIENT FLOORING

RET RETURN

REV REVISION (S), REVISED

RFG ROOFING

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RL RIDGE LINE

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RVS REVERSE (SIDE)

RWL RAIN WATER LEADER

S

S SOUTH

SB SPLASH BACK

SC SOLID CORE

SCHED SCHEDULE

SCR SHOWER CURTAIN ROD

SCT SECTION

SD SOAP DISPENSER

SF SQUARE FOOT

SHT SHEET

SHTHG SHEATHING

SIM SIMILAR

SLDG SLIDING

SLNT SEALANT

SND SANITARY NAPKIN DISPENSER

SNX SANIARY NAPKIN DISPOSAL

SOG SLAB ON GRADE

SPEC SPECIFICATION (S)

SQ SQUARE

SSM SOLID SURFACE MATERIAL

SST STAINLESS STEEL

ST STREET

STC SOUND TRANSMISSION CLASS

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

SV SHEET VINYL

SW SHEARWALL

SYM SYMMETRICAL

T

T TREAD

T&B TOP & BOTTOM

T&G TOUNGE AND GROOVE

TB TOWEL BAR

TBD TO BE DETERMINED

TEMP TEMPORARY / TEMPERED

TER TERRAZZO

TFE TOP FOOTING ELEVATION

THD THREAD (ED) (S)

ABBREVIATIONS

MR MIRROR

MTL METAL

N

(N) NEW

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED / CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED / OWNER INSTALLED

OH OVERHEAD

OPG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

OZ OUNCE

P

PAR PARALLEL

PCF POUNDS PER CUBIC FOOT

PED PEDISTAL

PERF PERFORATED

PERP PERPENDICULAR

PL PLATE

PLAM PLASTIC LAMINATE

PLMG PLUMBING

PLYWD PLYWOOD

PNL PANEL

PR PAIR / PROPOSAL REQUEST

PRCST PRECAST

PREFAB PREFABRICATE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT / PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PTR PAPER TOWEL RECEPTICAL

PVC POLYVINYL CHOLORIDE

Q

QT QUARRY TILE

R

R RADIUS / RISER

RB RUBBER BASE

RBR RUBBER

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REBAR REINFORCING BAR

REC RECESSED

REF REFERENCE / REFRIGERATOR

ABBREVIATIONS

HD HEAVY DUTY

HDBD HARDBOARD

HDR HEADER

HM HOLLOW METAL

HORZ HORIZONTAL

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION, AIRCONDITIONING

I

IBC INTERNATIONAL BUILDING CODE

ICC INTERNATIONAL CODE COUNCIL

ID INSIDE DIAMETER/DIMENSION

IFC INTERNATIONAL FIRE CODE

IN INCH (ES)

INCL INCLUDE (D), INCLUDING

INFO INFORMATION

INSP INSPECTION

INSTR INSTRUCTION (S)

INSUL INSULATE (D), INSULATION

INT INTERIOR

J

JAN JANITOR

JST JOIST

JT JOINT

K

KCJ KEYED CONSTRUCTION JOINT

KO KNOCK OUT

L

L LENGHT / ANGLE

LAB LABORATORY

LAM LAMINATE (D)

LAV LAVATORY

LB POUND

LF LINEAR FEET

LH LEFT HAND

LKR LOCKER

LOC LOCATION

LONG LONGITUDINAL

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MEZZ MEZZANINE

MFR MANUFACTURE (R)

MIN MINIMUM

MISC MISCELLANEOUS

MNTG MOUNTING

MO MASONRY OPENING

ABBREVIATIONS

EOP EDGE OF PAVEMENT

EPDM ETHYLENE PROPYLENE DIENE TERPOLYMER

MEMBRANE

EPS EXPANDED POLYSTYRENE BOARD

EPT EPOXY PAINT

EQ EQUAL

EQUIP EQUIPMENT

ES EACH SIDE

EST ESTIMATE

ETC ETCETERA

ETR EXISTING TO REMAIN

EW EACH WAY

EWC ELECTRIC WATER COOLER

EXC EXCAVATE/EXCAVATION

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION/EXPOSED

EXT EXTERIOR

F

FA FIRE ALARM

FAB FABRICATE/FABRICATION

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FLOOR

FFE FINISHED FLOOR ELEVATION

FIN FINISH (ED)

FLR FLOOR (ING)

FLUOR FLUORESCENT

FO FACE OF

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FR FIRE RESISTANT/FRAME

FRP FIBERGLASS REINFORCED PANEL

FS FLOOR SINK

FT FOOR, FEET/FIRE TREATED

FTG FOOTING

FURN FURNISH

FUT FUTURE

G

GA GAGE, GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GI GALVANIZED IRON

GL GLASS

GLU LAM GLUE LAMINATED (BEAM)

GWB GYPSUM WALL BOARD

GYP BD GYPSUM

H

HB HOSE BIB

HC HANDICAP / HOLLOW CORE

ABBREVIATIONS

CEM CEMENT

CF CUBIC FEET OR FOOT

CG CORNER GUARD

CH CHANNEL

CIPC CAST-IN-PLACE CONCRETE

CJ CONTROL/CONSTRUCTION JOINT

CL CENTER LINE

CLKG CAULKING

CLO CLEAR, CLEARANCE

CMU CONCRETE MASONRY UNIT

CO CHANGE ORDER/CLEANOUT

COL COLUMN

COMB COMBINATION

COMP COMPOSITE/COMPOSITION

CONC CONCRETE

CONN CONNECT (ION)

CONST CONSTRUCTION

CONT CONTINUOUS, CONTINUE

CONTR CONTRACT (OR)

COORD COORDINATE

CORR CORRUGATED/CORRIDOR

CPPT CARPET TILE

CPT CARPET

CSMT CASEMENT

CT CERAMIC TILE

CTB CARPET TILE BASE

CTR CENTER

D

D DEPTH

DBL DOUBLE

DEMO DEMOLITION, DEMOLISH

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DISP DISPENSER

DN DOWN

DR DOOR

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING (S)

DWR DRAWER

DWTR DUMBWAITER

E

(E) EXISTING

E EAST

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELVE ELEVATOR

EMER EMERGENCY

ENGR ENGINEER

ENL ENLARGED

ABBREVIATIONS

SYMBOLS

# POUND OR NUMBER

& AND

< ANGLE

<< DOUBLE ANGLE

@ AT

d PENNEY

Ø ROUND OR DIAMETER

A

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

ABV ABOVE

AC ASPHALTIC CONCRETE/AIR CONDITIONER

ACC ACCESSIBLE

ACM ALUMINUM COMPOSITE MATERIAL

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADD ADDENDUM

ADH ADHESIVE

ADJ ADJUSTABLE, ADJACENT, ADJOINING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATIVE

ALUM ALUMINUM

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APC ACOUSTICAL PANEL CEILING

APPROX APPROXIMATE

ARCH ARCHITECT (URAL)

ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTIONS

B

BD BOARD

BEV BEVELED

BFF BELOW FINISH FLOOR

BL BRICK LEDGE

BLDG BUILDING

BLKG BLOCK (ING)

BM BEAM

BO BOTTOM OF

BOC BOTTOM OF CONCRETE

BOF BOTTOM OF FOOTING

BOT BOTTOM

BRG BEARING

BRK BRICK

BRKT BRACKET

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT UP ROOFING

C

C CHANNEL/CELSIUS

CAB CABINET

CB CERAMIC BASE

CCW COUNTER CLOCKWISE

CD CONSTRUCTION DOCUMENTS

Revision# Description Date:

Figure 302.2 Carpet Pile Height

Figure 303.2 Vertical Change in Level

Figure 303.3 Beveled Change in Level

Figure 304.3.1 Circular Turning Space

Figure 304.3.2 T-Shaped Turning Space

Figure 305.3 Clear Floor or Ground Space

Figure 305.5 Position of Clear Floor or Ground Space

Figure 305.7.1 Maneuvering Clearance in an

Alcove, Forward Approach

Figure 305.7.2 Maneuvering Clearance in an

Alcove, Parallel Approach

Figure 306.2 Toe Clearance

Figure 306.3 Knee Clearance

Figure 308.3.1 Unobstructed Side

Reach

Figure 308.3.2 Unobstructed High Side

Reach

Figure 308.2.2 Obstructed High Forward Reach

Figure 308.2.1 Unobstructed Forward Reach

Figure 307.2 Limits of Protruding Objects

Figure 307.4 Vertical Clearance

Figure 307.3 Post-Mounted Protruding Objects

Figure 302.3 Elongated Openings in Floor or

Ground Surfaces

Figure 403.5.2 Clear Width at Turn

Figure 403.5.1 Clear Width of an Accessible Route

Figure 404.2.4.3 Maneuvering Clearance at Recessed Doors and Gates

Figure 404.2.4.2 Maneuvering Clearance at Sliding and Folding Doors

Figure 407.4.1 Elevator Car Door Sizes

Figure 408.4.1 Limited Use/Limited Application (LULA) Elevator Car and Door Sizes

Figure 404.2.4.1 Maneuvering Clearance at Manual Swinging Doors and Gates

Figure 404.2.3 Clear Width of Doorways

Figure 404.2.6 Doors in Series and Gates in Series

Figure 407.2.2.2 Visible Hall Signals

Figure 407.2.3.1 Floor Designations on

Jambs of Elevator Hoistway Entrances

Figure 407.2.3.2 Car Designations on Jambs of Destination-Oriented Elevator

Hoistway Entrances

Figure 407.2.1.1 Height of Elevator Call Buttons

Figure 409.4.6.2 Location of Private Residence

Elevator Control Panels

Figure 410.6 Platform Lift Doors and Gates

A C

C E

S S

IB

L

E R

O U

T E

S B

U

IL

D

IN

G B

L O

C K

S

1/2 max

1/4 max

6.4

1/4

6.4

1/4

6.4 1/2

1/2

60 min

60 min m in m in

36 min

12 min

12 min

24 min ar m ar m base

48 min m in m in

30 min m in

48 min

36 min

60 min

X

X

6 max

17-25

430-635 m in

11 min

9 min

8 min m in m in

25 max

(b) plan

(a) elevation

(b) plan

(a) elevation m ax m in

10 max

>10 - 24 max

255 - 610 m ax m ax m ax

10 max m ax m ax

> 20 - 25 max

510 - 635

20 max m ax

(a) (b) (b)(a) m ax m in

X

4 max

X

X m ax m in m ax

4 max (typ.)

X > 12

X > 12

4 max

4 max

5-

(a) (b) dominant direction of travel long dimension perpendicular to dominant direction of travel

1/2 max m in

20 60 m in

42 min

42 min

X < 48

X < 48

36 min

36 min

36 min

32 min

32 min

36 min m ax m ax m in m in

18 min

X > 8

X > 8

X > 8

12 min m in m in m in m in m in m in

65 24 min

22 min

80 min

68 min m in m in m in m in

42 min

36 min

36 min

60 min

54 min m in m in m in

36 min

36 min

36 min

51 min

42 min m in m in m in

36 min

32 min

(a) centered door

(b) side (off-centered) door

(c) any door location

(d) any door location

(e) Exception existing elevator car configuration

(b) Exception 1

(c) Exception 2

(a) new construction m in m in m in m in

18 min

12 min*

36 min

42 min m in

(e) hinge approach, pull side

(j) latch approach, push side

(k) latch approach, push side

*48 min if door provided with closer

(i) latch approach, pull side

*54 min if door provided with closer

(h) latch approach, pull side

(f) hinge approach, push side

(g) hinge approach, push side

*if door provided with both closer and latch ** 48 min if both closer and latch provided

(b) front approach, push side

(c) front approach, push side

*if door provided with both closer and latch

(a) front approach, pull side

(a) hinged door

(b) sliding door

(c) folding door

(d) doorways without doors

(a) pull side

(b) push side

(c) push side, door provided with both closer and latch (a) front approach

(b) side approach

*48 min at front approach

(c) pocket or hinge approach

(d) stop or latch approach

(d) hinge approach, pull side

24 min

22 min

12 min* m in m in

24 min

60 min m in

48 min

48 min

48 min

(a)

(c)

(b)

(d)

2 1/2 min

2 1/2 min m in m in m in

32 min m in platform lif t m ec h an is m

12 min

-4

0-

36 min

32 min

32 min

32 min

(a) 180 degree turn

(b) 180 degree turn

(Exception)

15 sq ft min

1.4 m²

16 sq ft min

1.5 m²

90.

(a) forward

(b) parallel front approach symbol

Figure 703.2.5 Height of Raised

Characters

Figure 703.3.1 Braille Measurement

Figure 703.3.2 Position of Braille

Figure 704.2.1.1 Parallel Approach to

Telephone

Figure 704.2.1.2 Forward Approach to

Telephone

Figure 703.4.1 Height of Tactile Characters

Above Floor or Ground

Figure 703.4.2 Location of Tactile Signs at Doors

Figure 703.6.1 Pictogram Field

Figure 705.1 Size and Spacing of Truncated Domes

Figure 707.6.2 Numeric Key Layout

Figure 703.7.2.1 International Symbol of Accessibility

Figure 703.7.2.2 International TTY Symbol

Figure 703.7.2.3 Volume-Controlled Telephone

Figure 703.7.2.4 International Symbol of Access for

Hearing Loss

C O

M M

U N

IC

A

T

IO

N E

L E

M E

N T

S A

N D

F E

A T

U R

E S distance between corresponding dots in adjacent cells distance between dots in the same cell distance between corresponding dots from one cell directly below distance between dots in the same cell single braille cell blank cell space between words raised dot base diameter no raised dot m ax m in

AREA OF

REFUGE

18 min

18 min centered on tactile characters

AREA OF

REFUGE

20 max

10 max

1.6-2.4

41-61

1.6-2.4

41-61

0.65 min

17base diameter of 0.9-1.4 (23-36mm) top diameter of 50%-65% of the base diameter

0.2

5.1

(a) elevation (enlarged)

(b) plan

(a) 12-key ascending

(b) 12-key descending

1 2 3

4 5 6

7 8 9

* 0 #

7 8 9

4 5 6

1 2 3

* 0 # m in

MEN not in pictogram field

5/

-5

AREA OF

REFUGE

3/8 min 9.5

3/8 min 9.5

LIBRARY

.00

CL CLCL

CL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:0

A M

G-001

ACCESSIBILITY DETAILS VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

DN

UP

UP

UP

UP

DN

DN UP

DN

CODE PLAN LEGEND

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

RATED WALL KEY

1-HOUR WALL

2-HOUR WALL

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. SMOKE SEALS ON ALL RATED DOORS.

C. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

GENERAL CODE PLAN NOTES:

LIFE SAFETY LEGEND

2HR FIRE WALL

2HR FIRE / SMOKE BARRIER

1HR FIRE / SMOKE BARRIER

1HR SMOKE BARRIER

SMOKE RESISTIVE HAZARDOUS ROOM

ENCLOSURE

SMOKE ZONE BARRIER

2HR FIRE BARRIER

1HR FIRE BARRIER

NON-RATED SMOKE ZONE

PARTITION

HEALTH CARE OCCUPANCY

CORRIDORS

SHAFT

SHAFT

ELEVATOR

S2

ELEVATOR

S3

SHAFT

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SHAFT

SHAFT

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SVC

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SHAFTSHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

DW

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

RTU-1A-1

ELEVATOR S32

MACHINE

PENTHOUSE RM

ELEVATOR

S32

ELEVATOR

S27

ELEVATOR

S27

ELEVATOR

P22

ELEVATOR

P23

ELEVATOR

P24

ELEVATOR

P22

ELEVATOR

P23

ELEVATOR

P24

ELEVATOR

P22

ELEVATOR

P23

ELEVATOR

P24

ELEVATOR

P25

ELEVATOR

P26

ELEVATOR

P25

ELEVATOR

P26

ELEVATOR

P25

ELEVATOR

P26

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:0

A M

G-002

LIFE SAFETY CODE REVIEW

PLANS

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/16" = 1'-0" F1

BUILDING 1 -

GROUND LEVEL CODE PLAN -

ELEVATORS S2, S3, P6 & P7

1/16" = 1'-0" E1

BUILDING 1 -

FIRST LEVEL CODE PLAN -

ELEVATORS S2, S3, P6 & P7

1/16" = 1'-0" D1

BUILDING 1 -

SECOND AND THIRD LEVELS CODE

PLANS - ELEVATORS S2, S3, P6 & P7

1/16" = 1'-0" C1

BUILDING 1 -

FOURTH LEVEL CODE PLAN -

ELEVATORS S2, S3, P6, & P7

1/16" = 1'-0" B1

BUILDING 1 -

FIFTH LEVEL PENTHOUSE CODE PLAN

- ELEVATORS S2, S3, P6 & P7

1/16" = 1'-0" F3

BUILDING 1A -

GROUND LEVEL CODE PLAN -

ELEVATORS S32, S33, & S34

1/16" = 1'-0" E3

BUILDING 1A -

FIRST LEVEL CODE PLAN -

ELEVATORS S32, S33, & S34

1/16" = 1'-0" D3

BUILDING 1A -

SECOND THROUGH FIFTH LEVEL CODE

PLANS - ELEVATORS S32, S33, & S34

1/16" = 1'-0" C3

BUILDING 1A -

SIXTH LEVEL CODE PLAN -

ELEVATORS S32, S33, & S34

1/16" = 1'-0" B3

BUILDING 1A -

SEVENTH LEVEL / PENTHOUSE CODE

PLAN - ELEVATORS S32, S33, & S34

1/16" = 1'-0" F4

BUILDING 7 -

GROUND LEVEL CODE PLAN -

ELEVATOR S27

1/16" = 1'-0" E4

BUILDING 7 -

FIRST LEVEL CODE PLAN -

ELEVATOR S27

1/16" = 1'-0" F6

BUILDING 7 -

BASEMENT / GROUND LEVEL CODE

PLAN - ELEVATORS P22, P23, & P24

1/16" = 1'-0" E6

BUILDING 7 -

FIRST LEVEL CODE PLAN -

ELEVATORS P22, P23, & P24

1/16" = 1'-0" D6

BUILDING 7 -

SECOND LEVEL CODE PLAN -

ELEVATORS P22, P23, & P24

1/16" = 1'-0" F7

BUILDING 7 -

GROUND LEVEL CODE PLAN -

ELEVATORS P25 & 26

1/16" = 1'-0" E7

BUILDING 7 -

FIRST LEVEL CODE PLAN -

ELEVATORS P25 & P26

1/16" = 1'-0" D7

BUILDING 7 -

SECOND LEVEL CODE PLAN -

ELEVATORS P25 & 26

UP

ELEVATOR

P22

ELEVATOR

P23

ELEVATOR

P24

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

CODE PLAN LEGEND

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

RATED WALL KEY

1-HOUR WALL

2-HOUR WALL

LIFE SAFETY LEGEND

2HR FIRE WALL

2HR FIRE / SMOKE BARRIER

1HR FIRE / SMOKE BARRIER

1HR SMOKE BARRIER

SMOKE RESISTIVE HAZARDOUS ROOM

ENCLOSURE

SMOKE ZONE BARRIER

2HR FIRE BARRIER

1HR FIRE BARRIER

NON-RATED SMOKE ZONE

PARTITION

NON-RATED SMOKE ZONE

PARTITION

BUILDING 1: ELEVATORS S2 & S3

BUILDING 7: ELEVATORS P22, P23 & P24

PHASING PLANS:

PHASE 1:

BUILDING 1: ELEVATORS P6 & P7

BUILDING 1A: ELEVATOR S32, S33, & S34

*COMPLETE ELEVATOR S34 FIRST;

ELEVATOR S33 SECOND;

AND ELEVATOR S32 LAST.

BUILDING 7: ELEVATORS P25 & P26

PHASE 2:

BUILDING 7: ELEVATOR S27

PHASE 3:

1. TEMPORARY CONSTRUCTION PARTITION BARRIERS FOR INFECTION CONTROL AND TO MAINTAIN

1HR FIRE BARRIER ASSEMBLIES AS REQUIRED.

2. CONSTRUCT TEMPORARY CONSTRUCTION BARRIERS AS APPLICABLE, COORDINATE FINAL

LOCATION OF BARRIERS WITH COR.

3. COORDINATE ANY TEMPORARY INTERIOR FINISHES, POWER, HVAC, AND PLUMBING WITH OWNER.

4. COORDINATE WITH OWNER WHEN A SHUT DOWN OF ANY SYSTEMS WILL OCCUR TO MINIMIZE

DISRUPTION OF EXISTING SERVICES.

5. GC RESPONSIBLE FOR MAINTAINING ICRA, SEE SPECIFICATIONS SECTION 01 35 26, SAFETY

REQUIREMENTS FOR MORE INFORMATION.

6. CONTRACTOR ACCESS AND STAGING AREA TO BE COORDINATED WITH COR FOLLOWING AWARD OF

CONTRACT.

GENERAL CONSTRUCTION NOTES:

ELEVATOR

P22

ELEVATOR

P23

ELEVATOR

P24

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SHAFTSHAFT

T Y

P

5' -0

M

IN

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

SHAFT

SHAFT

ELEVATOR

S2

ELEVATOR

S3

SHAFT

ELEVATOR

P6

ELEVATOR

P7

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

SHAFT

SHAFT

SHAFT

ELEVATOR

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SVC

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:1

A M

G-003

PHASE 1 PLANS VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/8" = 1'-0" D1

BUILDING 7 - PHASE 1 -

BASEMENT / GROUND LEVEL PLAN -

ELEVATORS P22, P23, & P24

1/8" = 1'-0" B1

BUILDING 7 - PHASE 1 -

FIRST LEVEL PLAN -

ELEVATORS P22, P23, & P24

PHASE 1

BUILDING 1 AND

BUILDING 7

1/8" = 1'-0" B4

BUILDING 1 - PHASE 1 -

FOURTH LEVEL PLAN -

ELEVATORS S2 & S3

1/8" = 1'-0" F4

BUILDING 1 - PHASE 1 -

GROUND LEVEL PLAN -

ELEVATORS S2 & S3

1/8" = 1'-0" E4

BUILDING 1 - PHASE 1 -

FIRST LEVEL PLAN -

ELEVATORS S2 & S3

1/8" = 1'-0" C4

BUILDING 1 - PHASE 1 -

SECOND AND THIRD LEVELS PLANS -

ELEVATORS S2 & S3

CODE PLAN LEGEND

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

RATED WALL KEY

1-HOUR WALL

2-HOUR WALL

BUILDING 1: ELEVATORS S2 & S3

BUILDING 7: ELEVATORS P22, P23 & P24

PHASING PLANS:

PHASE 1:

BUILDING 1: ELEVATORS P6 & P7

BUILDING 1A: ELEVATOR S32, S33, & S34

*COMPLETE ELEVATOR S34 FIRST;

ELEVATOR S33 SECOND;

AND ELEVATOR S32 LAST.

BUILDING 7: ELEVATORS P25 & P26

PHASE 2:

BUILDING 7: ELEVATOR S27

PHASE 3:

1. TEMPORARY CONSTRUCTION PARTITION BARRIERS FOR INFECTION CONTROL AND TO MAINTAIN

1HR FIRE BARRIER ASSEMBLIES AS REQUIRED.

2. CONSTRUCT TEMPORARY CONSTRUCTION BARRIERS AS APPLICABLE, COORDINATE FINAL

LOCATION OF BARRIERS WITH COR.

3. COORDINATE ANY TEMPORARY INTERIOR FINISHES, POWER, HVAC, AND PLUMBING WITH OWNER.

4. COORDINATE WITH OWNER WHEN A SHUT DOWN OF ANY SYSTEMS WILL OCCUR TO MINIMIZE

DISRUPTION OF EXISTING SERVICES.

5. GC RESPONSIBLE FOR MAINTAINING ICRA, SEE SPECIFICATIONS SECTION 01 35 26, SAFETY

REQUIREMENTS FOR MORE INFORMATION.

6. CONTRACTOR ACCESS AND STAGING AREA TO BE COORDINATED WITH COR FOLLOWING AWARD OF

CONTRACT.

GENERAL CONSTRUCTION NOTES:

LIFE SAFETY LEGEND

2HR FIRE WALL

2HR FIRE / SMOKE BARRIER

1HR FIRE / SMOKE BARRIER

1HR SMOKE BARRIER

SMOKE RESISTIVE HAZARDOUS ROOM

ENCLOSURE

SMOKE ZONE BARRIER

2HR FIRE BARRIER

1HR FIRE BARRIER

NON-RATED SMOKE ZONE

PARTITION

NON-RATED SMOKE ZONE

PARTITION

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION BARRIER

REGULATE NEGATIVE AIR PRESSURE

VERIFIED BY GAUGES FOR DUST

CONTROL. SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION BARRIER

REGULATE NEGATIVE AIR

PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION

BARRIER REGULATE

NEGATIVE AIR PRESSURE

VERIFIED BY GAUGES

FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

TEMP. CONSTRUCTION BARRIER

REGULATE NEGATIVE AIR

PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:1

A M

G-004

PHASE 2 PLANS - ELEVATOR 1A VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

PHASE 2

BUILDING 1A

1/8" = 1'-0" F1

BUILDING 1A - PHASE 2 -

GROUND LEVEL PLAN -

ELEVATORS S34

1/8" = 1'-0"

F4

BUILDING 1A - PHASE 2 -

GROUND LEVEL PLAN -

ELEVATORS S33

1/8" = 1'-0"

F7

BUILDING 1A - PHASE 2 -

GROUND LEVEL PLAN -

ELEVATOR S32

1/8" = 1'-0" C4

BUILDING 1A - PHASE 2 - SECOND

THROUGH FIFTH LEVEL PLANS -

ELEVATOR S33

1/8" = 1'-0"

C7

BUILDING 1A - PHASE 2 - SECOND

THROUGH FIFTH LEVEL PLANS -

ELEVATOR S32

1/8" = 1'-0"

C1

BUILDING 1A - PHASE 2 - SECOND

THROUGH FIFTH LEVEL PLANS -

ELEVATOR S34

1/8" = 1'-0" E1

BUILDING 1A - PHASE 2 -

FIRST LEVEL PLAN -

ELEVATOR S32

1/8" = 1'-0" B1

BUILDING 1A - PHASE 2 -

SIXTH LEVEL PLAN -

ELEVATOR S32

1/8" = 1'-0" E4

BUILDING 1A - PHASE 2 -

FIRST LEVEL PLAN -

ELEVATOR S33

1/8" = 1'-0"

E7

BUILDING 1A - PHASE 2 -

FIRST LEVEL PLAN -

ELEVATOR S34

1/8" = 1'-0" B4

BUILDING 1A - PHASE 2 -

SIXTH LEVEL PLAN -

ELEVATOR S33

1/8" = 1'-0"

B7

BUILDING 1A - PHASE 2 -

SIXTH LEVEL PLAN -

ELEVATOR S34

DEDUCT ALTERNATE BID G-1:

DELETE ALL WORK RELATED

TO BUILDING 1A

UP

UP

DN

SHAFT

SHAFT

SHAFT

ELEVATOR

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SHAFTSHAFT

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

SHAFT

SHAFT

ELEVATOR

S2

ELEVATOR

S3

SHAFT

ELEVATOR

P6

ELEVATOR

P7

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

SVC

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

P25

ELEVATOR

P26

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

ELEVATOR

P25

ELEVATOR

P26

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

CODE PLAN LEGEND

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

RATED WALL KEY

1-HOUR WALL

2-HOUR WALL

BUILDING 1: ELEVATORS S2 & S3

BUILDING 7: ELEVATORS P22, P23 & P24

PHASING PLANS:

PHASE 1:

BUILDING 1: ELEVATORS P6 & P7

BUILDING 1A: ELEVATOR S32, S33, & S34

*COMPLETE ELEVATOR S34 FIRST;

ELEVATOR S33 SECOND;

AND ELEVATOR S32 LAST.

BUILDING 7: ELEVATORS P25 & P26

PHASE 2:

BUILDING 7: ELEVATOR S27

PHASE 3:

1. TEMPORARY CONSTRUCTION PARTITION BARRIERS FOR INFECTION CONTROL AND TO MAINTAIN

1HR FIRE BARRIER ASSEMBLIES AS REQUIRED.

2. CONSTRUCT TEMPORARY CONSTRUCTION BARRIERS AS APPLICABLE, COORDINATE FINAL

LOCATION OF BARRIERS WITH COR.

3. COORDINATE ANY TEMPORARY INTERIOR FINISHES, POWER, HVAC, AND PLUMBING WITH OWNER.

4. COORDINATE WITH OWNER WHEN A SHUT DOWN OF ANY SYSTEMS WILL OCCUR TO MINIMIZE

DISRUPTION OF EXISTING SERVICES.

5. GC RESPONSIBLE FOR MAINTAINING ICRA, SEE SPECIFICATIONS SECTION 01 35 26, SAFETY

REQUIREMENTS FOR MORE INFORMATION.

6. CONTRACTOR ACCESS AND STAGING AREA TO BE COORDINATED WITH COR FOLLOWING AWARD OF

CONTRACT.

GENERAL CONSTRUCTION NOTES:

LIFE SAFETY LEGEND

2HR FIRE WALL

2HR FIRE / SMOKE BARRIER

1HR FIRE / SMOKE BARRIER

1HR SMOKE BARRIER

SMOKE RESISTIVE HAZARDOUS ROOM

ENCLOSURE

SMOKE ZONE BARRIER

2HR FIRE BARRIER

1HR FIRE BARRIER

NON-RATED SMOKE ZONE

PARTITION

NON-RATED SMOKE ZONE

PARTITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:2

A M

G-005

PHASE 2 PLANS - ELEVATOR 1

& ELEVATOR 7

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/8" = 1'-0" E1

BUILDING 1 - PHASE 2 -

FIRST LEVEL PLAN -

ELEVATORS P6 & P7

1/8" = 1'-0" B1

BUILDING 1 - PHASE 2 -

FOURTH LEVEL PLAN -

ELEVATORS P6 & P7

1/8" = 1'-0" F1

BUILDING 1 - PHASE 2 -

GROUND LEVEL PLAN -

ELEVATORS P6 & P7

1/8" = 1'-0" C1

BUILDING 1 - PHASE 2 -

SECOND AND THIRD LEVELS PLANS -

ELEVATORS P6 & P7

1/8" = 1'-0"

C5

BUILDING 7 - PHASE 2 -

FIRST AND SECOND LEVEL PLANS -

ELEVATORS P25 & P26

1/8" = 1'-0" E5

BUILDING 7 - PHASE 2 -

GROUND LEVEL PLAN -

ELEVATORS P25 & 26

DEDUCT ALTERNATE BID G-1:

DELETE ALL WORK RELATED

TO BUILDING 1A

PHASE 2

BUILDING 1

AND

BUILDING 7

ELEVATOR

S27

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

CODE PLAN LEGEND

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

RATED WALL KEY

1-HOUR WALL

2-HOUR WALL

BUILDING 1: ELEVATORS S2 & S3

BUILDING 7: ELEVATORS P22, P23 & P24

PHASING PLANS:

PHASE 1:

BUILDING 1: ELEVATORS P6 & P7

BUILDING 1A: ELEVATOR S32, S33, & S34

*COMPLETE ELEVATOR S34 FIRST;

ELEVATOR S33 SECOND;

AND ELEVATOR S32 LAST.

BUILDING 7: ELEVATORS P25 & P26

PHASE 2:

BUILDING 7: ELEVATOR S27

PHASE 3:

1. TEMPORARY CONSTRUCTION PARTITION BARRIERS FOR INFECTION CONTROL AND TO MAINTAIN

1HR FIRE BARRIER ASSEMBLIES AS REQUIRED.

2. CONSTRUCT TEMPORARY CONSTRUCTION BARRIERS AS APPLICABLE, COORDINATE FINAL

LOCATION OF BARRIERS WITH COR.

3. COORDINATE ANY TEMPORARY INTERIOR FINISHES, POWER, HVAC, AND PLUMBING WITH OWNER.

4. COORDINATE WITH OWNER WHEN A SHUT DOWN OF ANY SYSTEMS WILL OCCUR TO MINIMIZE

DISRUPTION OF EXISTING SERVICES.

5. GC RESPONSIBLE FOR MAINTAINING ICRA, SEE SPECIFICATIONS SECTION 01 35 26, SAFETY

REQUIREMENTS FOR MORE INFORMATION.

6. CONTRACTOR ACCESS AND STAGING AREA TO BE COORDINATED WITH COR FOLLOWING AWARD OF

CONTRACT.

GENERAL CONSTRUCTION NOTES:

LIFE SAFETY LEGEND

2HR FIRE WALL

2HR FIRE / SMOKE BARRIER

1HR FIRE / SMOKE BARRIER

1HR SMOKE BARRIER

SMOKE RESISTIVE HAZARDOUS ROOM

ENCLOSURE

SMOKE ZONE BARRIER

2HR FIRE BARRIER

1HR FIRE BARRIER

NON-RATED SMOKE ZONE

PARTITION

NON-RATED SMOKE ZONE

PARTITION

ELEVATOR

S27

TEMP. CONSTRUCTION

BARRIER REGULATE NEGATIVE

AIR PRESSURE VERIFIED BY

GAUGES FOR DUST CONTROL.

SEE DETAIL /F7 A-501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:2

A M

G-006

PHASE 3 PLANS VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/8" = 1'-0" F7

BUILDING 7 - PHASE 3 -

GROUND LEVEL PLAN -

ELEVATOR S27

1/8" = 1'-0" C7

BUILDING 7 - PHASE 3 -

FIRST LEVEL PLAN -

ELEVATOR S27

PHASE 3

BUILDING 7

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

SHAFT

FLOOR ABOVE

FLOOR ABOVE

FLOOR ABOVE

FLOOR ABOVE

2.15

2.15

SHAFT

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEC CLOSET

SHAFT

SVC ELEVATOR LOBBY

CWC 44

PASSENGER ELEVATOR LOBBY

CWC 45

STAIR 1

STORAGE

PATHOLOGY/LAB

EMS STORAGE

CWG12

TEL

CLOS

SIGN

CLOS

TELECOM MED WASH

CWG 53

UNIFORM STORAGE

CWG 52

CONFERENCE ROOM

CWG15D

EEO OFFICE

CWG 15C

WASH RM

CWG 51

CORRIDOR

BW-C6

2.172.17

2.172.17

2.092.09

2.14

2.09 2.09

2.14

A. PROTECT ALL EXISTING UTILITIES.

B. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

C. PATCH REMAINING EXISTING CONSTRUCTION, AFFECTED BY DEMOLITION, TO MATCH EXISTING

U.O.N.

D. EXISTING ITEMS TO REMAIN ARE SHOWN AS HALFTONE.

E. DEMO ITEMS ARE SHOWN AS DASHED.

F. INFILL OF THE PENETRATIONS IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

G. COORDINATE RELOCATION OF SALVAGED ITEMS WITH THE OWNER.

H. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION RELEVANT TO

DEMOLITION & PATCHING.

GENERAL DEMOLITION PLAN NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:3

A M

AD-101

BUILDING 1 DEMOLITION

ELEVATOR FLOOR PLANS

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/4" = 1'-0" F1

BUILDING 1 DEMOLITION PLAN -

ELEVATOR PIT LEVEL -

ELEVATORS S2, S3, P6 & P7

1/4" = 1'-0" C1

BUILDING 1 DEMOLITION PLAN -

GROUND LEVEL PLAN -

ELEVATORS S2, S3, P6 & P7

SGA KEYNOTES

Key Value Keynote Text

2.09 REMOVE EXISTING ELEVATOR EQUIPMENT, CAR AND PLATFORM (EXCLUDING GUIDE RAILS) IN

IT'S ENTIRETY IN PREPARATION FOR NEW OVERHEAD TRACTION ELEVATOR

2.14 REMOVE EXISTING ELEVATOR CALL BUTTONS AND FLOOR INDICATOR PANELS

2.15 REMOVE EXISTING ELEVATOR HOISTWAY LIGHTING AT PIT AND TOP OF HOISTWAY.

2.17 REMOVE EXISTING HOISTWAY DOOR AND PREP FOR INSTALLATION OF NEW DOOR. EXISTING

FRAME TO REMAIN AND BE REFURBISHED IN-PLACE.

BUILDING 1 KEY PLAN

NORTH

NORTH

DNUP

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEC CLOSET

11 SHAFT

ELECTRICAL

CW 197

BREAK RM

CW195

EXAM

CW194B

CLINICAL PHARMACY

EDUCATIONAL CO-ORDINATOR

CW163

OPTOMETRY

OFFICE

CW164

STAIR 1

SHAFT

TC

TC

EC TC

ELEVATOR

SHAFT

STORAGE

CW 196

STORAGE CW 196A

2.17 2.14 2.17

2.09 2.09

2.172.17

2.09 2.09

2.14

SHAFT

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEC CLOSET

SHAFT

CORRIDOR

CW 267

CORRIDOR

CW 270

SHAFT SHAFT

SVC LOBBY

HAC SVC

SOIL UTIL

TRAY LINE

STAIR 1

CW 269A

CANTEEN OFFICE

CW 269

COUNTING

OFFICE

2.09

2.17 2.14 2.17

2.09

2.17 2.14 2.17

2.092.09

A. PROTECT ALL EXISTING UTILITIES.

B. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

C. PATCH REMAINING EXISTING CONSTRUCTION, AFFECTED BY DEMOLITION, TO MATCH EXISTING

U.O.N.

D. EXISTING ITEMS TO REMAIN ARE SHOWN AS HALFTONE.

E. DEMO ITEMS ARE SHOWN AS DASHED.

F. INFILL OF THE PENETRATIONS IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

G. COORDINATE RELOCATION OF SALVAGED ITEMS WITH THE OWNER.

H. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION RELEVANT TO

DEMOLITION & PATCHING.

GENERAL DEMOLITION PLAN NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:4

A M

AD-102

BUILDING 1 DEMOLITION

ELEVATOR FLOOR PLANS

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/4" = 1'-0" F1

BUILDING 1 DEMOLITION PLAN -

FIRST LEVEL PLAN -

ELEVATORS S2, S3, P6 & P7

1/4" = 1'-0" C1

BUILDING 1 DEMOLITION PLAN -

SECOND AND THIRD LEVEL PLANS -

ELEVATORS S2, S3, P6 & P7

SGA KEYNOTES

Key Value Keynote Text

2.09 REMOVE EXISTING ELEVATOR EQUIPMENT, CAR AND PLATFORM (EXCLUDING GUIDE RAILS) IN

IT'S ENTIRETY IN PREPARATION FOR NEW OVERHEAD TRACTION ELEVATOR

2.14 REMOVE EXISTING ELEVATOR CALL BUTTONS AND FLOOR INDICATOR PANELS

2.17 REMOVE EXISTING HOISTWAY DOOR AND PREP FOR INSTALLATION OF NEW DOOR. EXISTING

FRAME TO REMAIN AND BE REFURBISHED IN-PLACE.

BUILDING 1 KEY PLAN

NORTH

T

T

T

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEC

CW11

CORRIDOR

CW 267

CORRIDOR

CW 270

TELL COM

CW 463

EPRS CLINICAL

OFFICES

CW 402

MED SVC

CONFERENCE ROOM

CW 449

WOMEN'S

TOILET

CW 423

SHAFT

SHAFTSHAFT

SHAFT

STAIR 1

2.17 2.17

2.09 2.09

2.09 2.09

2.172.142.17

2.152.15

2.152.15

2.14

ELEVATOR

S2

ELEVATOR

S3

ELEVATOR

P6

ELEVATOR

P7

ELEVATOR MECHANICAL

ROOM

STORAGE

2.19 2.19

2.19 2.19

2.19 2.19

2.19 2.19

STAIR 2

ROOF

ROOF

ROOF

A. PROTECT ALL EXISTING UTILITIES.

B. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

C. PATCH REMAINING EXISTING CONSTRUCTION, AFFECTED BY DEMOLITION, TO MATCH EXISTING

U.O.N.

D. EXISTING ITEMS TO REMAIN ARE SHOWN AS HALFTONE.

E. DEMO ITEMS ARE SHOWN AS DASHED.

F. INFILL OF THE PENETRATIONS IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

G. COORDINATE RELOCATION OF SALVAGED ITEMS WITH THE OWNER.

H. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION RELEVANT TO

DEMOLITION & PATCHING.

GENERAL DEMOLITION PLAN NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:4

A M

AD-103

BUILDING 1 DEMOLITION

ELEVATOR FLOOR PLANS

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

1/4" = 1'-0" F1

BUILDING 1 DEMOLITION PLAN -

FOURTH LEVEL PLAN -

ELEVATORS S2, S3, P6, & P7

1/4" = 1'-0" C1

BUILDING 1 DEMOLITION PLAN - FIFTH

LEVEL / PENTHOUSE LEVEL PLAN -

ELEVATORS S2, S3, P6, & P7

SGA KEYNOTES

Key Value Keynote Text

2.09 REMOVE EXISTING ELEVATOR EQUIPMENT, CAR AND PLATFORM (EXCLUDING GUIDE RAILS) IN

IT'S ENTIRETY IN PREPARATION FOR NEW OVERHEAD TRACTION ELEVATOR

2.14 REMOVE EXISTING ELEVATOR CALL BUTTONS AND FLOOR INDICATOR PANELS

2.15 REMOVE EXISTING ELEVATOR HOISTWAY LIGHTING AT PIT AND TOP OF HOISTWAY.

2.17 REMOVE EXISTING HOISTWAY DOOR AND PREP FOR INSTALLATION OF NEW DOOR. EXISTING

FRAME TO REMAIN AND BE REFURBISHED IN-PLACE.

2.19 REMOVE EXISTING ELEVATOR EQUIPMENT AND CONTROLS FROM PENTHOUSE ELEVATOR

MACHINE ROOM IN IT'S ENTIRETY IN PREPARATION OF NEW OVERHEAD TRACTION ELEVATOR

BUILDING 1 KEY PLAN

NORTH

A. PROTECT ALL EXISTING UTILITIES.

B. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

C. PATCH REMAINING EXISTING CONSTRUCTION, AFFECTED BY DEMOLITION, TO MATCH EXISTING

U.O.N.

D. EXISTING ITEMS TO REMAIN ARE SHOWN AS HALFTONE.

E. DEMO ITEMS ARE SHOWN AS DASHED.

F. INFILL OF THE PENETRATIONS IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

G. COORDINATE RELOCATION OF SALVAGED ITEMS WITH THE OWNER.

H. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION RELEVANT TO

DEMOLITION & PATCHING.

GENERAL DEMOLITION PLAN NOTES:

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

FLOOR ABOVE

2.15

2.15

2.15

PASS ELEVATOR

LOBBY

CB1-1A

SERVICE ELEVATOR

LOBBY

CB1-11

DW

DB1108

DW

STAIR 14

ELEVATOR

S32

ELEVATOR

S33

ELEVATOR

S34

PHARMACY

DB1102

2.14

2.05

2.14

2.05

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

A/E:

STAMPCONSULTANTS

321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t

MECHANICAL / ELECTRICAL: STRUCTURAL:

6 SOUTH OLD ORCHARD

ST. LOUIS, MISSOURI 63119

314.918.8383

1110 BENFIELD BLVD. SUITE K

MILLERSVILLE, MD 21108

410-766-4600

15 SUNNEN DRIVE SUITE 104

ST. LOUIS, MO 63143

314-645-1132

ELEVATOR CONSULTANT:

C

S G

A R e v it L o c a l\

V A

M e m p h is

U p g ra d e E le v a to rs

A

C

E N

T R

A L je s s ic a jR

N Q

F G

.r v t

/6

/2

:1

:4

A M

AD-110

BUILDING 1A DEMOLITION

ELEVATOR FLOOR PLANS

VA MEMPHIS ELEVATOR

UPGRADE IN BUILDINGS 1, 1A, & 7

1030 Jefferson Ave, Memphis, TN 38104

1, 1A, & 7

06/09/23 JK JJ

BID DOCUMENTS

SGA #211955

VA #614-22-105

SGA KEYNOTES

Key Value Keynote Text

2.05 REMOVE EXISTING CARD READER AND MEDICAL EMERGENCY OVERRIDE AND PREPARE FOR

REPLACEMENT

2.14 REMOVE EXISTING ELEVATOR CALL BUTTONS AND FLOOR INDICATOR PANELS

2.15 REMOVE EXISTING ELEVATOR HOISTWAY LIGHTING AT PIT AND TOP OF HOISTWAY.

BUILDING 1A KEY PLAN

1/4" = 1'-0" F1

BUILDING 1A DEMOLITION PLAN -

ELEVATOR PIT LEVEL PLAN -

ELEVATORS S32, S33, & S34

1/4" =…