S02 - 7 578-26-006 Room Plans.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25226B0012
About this file
This is a room plan and construction specification document for the repair of steam and condensate risers in Building 1 at a Department of Veterans Affairs facility (Contract N 578-26-006, Phase 2). The document provides detailed floor-by-floor layouts and construction notes for Floors 1 and 2 of A-Section Building 1, identifying existing riser locations and proposed new riser locations with corresponding asbestos survey data.
The primary work scope includes installing new steam and condensate risers at locations proximate to existing risers, reconnecting all existing radiator lines to the new risers, and installing new insulation on all newly installed pipe risers and fittings. The contractor is responsible for demolition and relocation of wall fixtures, equipment, cabinetry, and furniture as necessary to accommodate the new pipe chase, as well as the relocation of obstructing utilities including electric outlets, receptacles, data ports, wireless access points, gas nozzles, and equipment. Asbestos-containing material (ACM) is present throughout the project location, with most areas indicating 70% ACM content of chrysotile type with assumed positive friability and low disturbance potential located behind walls and ceilings. The contractor must create shop drawings for the new chase requiring approval from the Contracting Officer's Representative (COR) prior to construction commencement and must perform all work in accordance with general abatement and demolition notes.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-Section Bldg 1 – Floor 1, Existing Riser Locations
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
▪ New steam and condensate risers shall be installed at locations close to existing risers and reconnect all existing radiator lines to new risers
▪ Install new insulation on all newly installed pipe risers and fittings
▪ Demolition or relocation of wall fixtures, equipment, cabinetry, and all furniture as necessary to accommodate new pipe chase is the responsibility of the contractor
▪ Electric outlets, receptacles, data ports, and other utilities obstructing construction of new chase is the responsibility of the contractor and verified by electrician for proper relocation
▪ Contractor must create shop drawings for new chase to be installed and approved by COR prior to construction
▪ Perform all necessary tasks in accordance with the general abatement and demolition notes
Construction Notes
Bldg 1 – Floor 2, Existing Riser Locations
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Bldg 1 – Floor 2, A202A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey
Location Notes
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Wireless access point
• Relocate if obstructing new chase construction
Bldg 1 – Floor 2, A202A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Location Notes
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Equipment
• Relocate if
Bldg 1 – Floor 2, A202B
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Location Notes
Bldg 1 – Floor 2, A201
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Bldg 1 – Floor 2, A205
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Riser Asbestos Survey
Bldg 1 – Floor 2, A209
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Junction Box Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 2, A213A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Gas nozzle
• Relocate if obstructing new
Bldg 1 – Floor 2, A213A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Wireless Access Point
• Relocate if obstructing new
Bldg 1 – Floor 2, A227
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Data ports
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 2, A231
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 2, A235
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Fin Tube Radiator
• Shorten radiator to fit new chase
Bldg 1 – Floor 2, A235
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 2, A239
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 2, A241
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/WHT
& BRN STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 11 LF
Mat: Steam Friability: Y Disturbance: Low Loc: No change
Riser Asbestos Survey VFT Asbestos Survey
Wireless Access Point
• Relocate if obstructing new
Bldg 1 – Floor 2, A241A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 2, A206
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 11 LF
Mat: Steam Friability: Y Disturbance: Low
Bldg 1 – Floor 2, CORR
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Wireless Access Point
• Relocate if obstructing new
Bldg 1 – Floor 2, A214
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Wall switch
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Wall Hanging Cabinet
• Remove from wall and fit onto new chase or relocate to nearby location
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Wireless Access Point Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Wall accessories Cabinets Tabletop
• Cut/remove table and cabinet section as well as any obstructions to fit new chase
Bldg 1 – Floor 2, A224
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 11 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Fin Tube Radiator
• Divide/split existing radiator to fit new chase
Tabletop Cabinets
• Cut/remove table and drawer section to fit new chase
Bldg 1 – Floor 2, A228
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/WHT
& BRN STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Fine Tube Radiator
• Divide/split existing radiator to fit new chase
Data ports Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 2, A228
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey VFT Asbestos Survey Location Notes
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/WHT
& BRN STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Tabletop Cabinets
• Cut/remove table and drawer section to fit new chase
Bldg 1 – Floor 2, A230
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey Location Notes
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Low Space Piping
• Relocate if
Bldg 1 – Floor 2, A238
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/BLU
STRKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 3, Existing Riser Locations
N
Bldg 1 – Floor 3, A300
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey VFT Asbestos Survey
Location Notes
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: 1'X1' WHT W/BRN
CHNK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit
Bldg 1 – Floor 3, A300
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: 1'X1' WHT W/BRN
CHNK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Data Ports Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit
Bldg 1 – Floor 3, A300-1
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Wireless Access Point
• Relocate if obstructing new
Bldg 1 – Floor 3, A303
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT
W/GRY& BRN LG CHNK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey Valves Electric outlet
• Disconnect and reconnect any electric/gas utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit
Bldg 1 – Floor 3, A305
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT
W/GRY& BRN LG CHNK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 3, A309
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' GRN W/SM
GRN STRK
Friability: N Disturbance: Low
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit
Location Notes VFT Asbestos Survey
Bldg 1 – Floor 3, A315
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/BRN&
WHT MOT
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey Electric outlet
• Disconnect and reconnect any electric/gas utility after relocating onto new chase or nearby location
Wireless Access Point
• Relocate if obstructing new chase construction
VFT Asbestos Survey
Bldg 1 – Floor 3, A315
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/BRN&
WHT MOT
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey Data ports
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit new chase
Bldg 1 – Floor 3, A329
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 3, A329
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit new chase
Bldg 1 – Floor 3, A331
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: N/A
Type: N/A
QTY: 6 SF
Mat: 1'X1' WHITE W/
GREEN SPECK FT &
BLCK MSTC
Friability: N Disturbance: Low
Electric outlets Data ports
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 3, A333
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: N/A
Type: N/A
QTY: 6 SF
Mat: 1'X1' WHITE W/
GREEN SPECK FT &
BLCK MSTC
Friability: N Disturbance: Low
Data ports
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 3, A337
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 3, A341
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey Electric box Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Tabletop Cabinets
• Cut/remove table and cabinet section as necessary to fit new chase
Bldg 1 – Floor 3, A343
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 3, A306
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' GRN W/SM
GRN STRK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
Bldg 1 – Floor 3, CORR
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Proposed New Location
Bldg 1 – Floor 3, A312
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: 1'X1' TAN W/BRN&
WHT NOT
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 11 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey Sink Nozzles Tabletop Cabinets
• Cut/remove table and cabinet section as well as any sinks, gas fittings and valves/nozzles as necessary to fit new chase
Bldg 1 – Floor 3, A314
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' GRY W/BLU
& GRY NOT
Friability: N Disturbance: Low
Bldg 1 – Floor 3, A314
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' GRY W/BLU
& GRY NOT
Friability: N Disturbance: Low
Tabletop Cabinets
• Cut/remove table and cabinet to fit
Bldg 1 – Floor 3, A326
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Light switch Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey VFT Asbestos Survey
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y
Bldg 1 – Floor 3, A330
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Low Space Wireless Access Point
• Relocate if obstructing new chase construction
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N
Location Notes Riser Asbestos Survey VFT Asbestos Survey
Bldg 1 – Floor 3, A340
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT W/GRN
FLKS
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey VFT Asbestos Survey
Light switch Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 4, Existing Riser Locations
N
Bldg 1 – Floor 4, A400
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Riser Asbestos Survey
Location Notes
VFT Asbestos Survey
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 44 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Electric outlet
• Disconnect and reconnect any electric utility and all conduit after relocating onto new chase or nearby location
Wireless access point
• Relocate if
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 44 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 44 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Junction box Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 4, A401
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 4, A405
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N
Bldg 1 – Floor 4, A413
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: N/A
Type: N/A
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N
Bldg 1 – Floor 4, A415
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR
QTY: 44 LF
Mat: Steam Friability: Y Disturbance: Low
Bldg 1 – Floor 4, A417
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: N/A
Type: N/A
QTY: 6 SF
Mat: 9"X9" TAN W/ RED
FLOORTILE AND
MASTIC
Friability: N
Bldg 1 – Floor 4, A429
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
Piping
• Disconnect existing piping as necessary to refit onto new chase
Bldg 1 – Floor 4, A440
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: CHR
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
ACM%: 70
Type: CHR
QTY: 44 LF
Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A433
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 12
Type: CHR
QTY: 6 SF
Mat: 9"X9" LT BRN
W/BLU & BRN STRK
Friability: N Disturbance: Low
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A435
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A439
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A445
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, B401
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, CORR
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 4, A414
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A416
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 4, A418A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Low Space CO2 Chamber
Bldg 1 – Floor 4, A420
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A432
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N Disturbance: Low
Low Space Piping
• Disconnect existing piping as necessary to refit onto new chase
Radiator
• Remove existing cast iron radiator if space for chase is insufficient
Bldg 1 – Floor 4, A434A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
Riser Asbestos Survey
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A434B
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Location Notes
Piping
• Disconnect existing piping as necessary to refit onto new
Bldg 1 – Floor 4, A438
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 70
Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil
ACM%: 12
Type: N/A
QTY: 6 SF
Mat: 9"X9" LT BRN
W/BLU & BRN STRK
Friability: N
VFT Asbestos Survey Riser Asbestos Survey
Bldg 1 – Floor 4, A442
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 0
Type: N/A
QTY: 6 SF
Mat: BRN FLOOR
SHEET
Friability: N
B-Section Bldg 1 – Floor 1, B159
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 2
Type: CHR
QTY: 6 SF
Mat: 1'X1' BRN W/WHT
MOT
Friability: N Disturbance: Low
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' BLU W/WHT
& DK BLU FLKS
Friability: N Disturbance: Low
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' BRN W/DK
BRN MOT
Friability: N
VFT Asbestos Survey VFT Asbestos Survey VFT Asbestos Survey
Bldg 1 – Floor 2, B259
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 3, B355
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Location Notes
ACM%: 15
Type: CHR
QTY: 6 SF
Mat: 9"X9" GRY
W/BLKSTRK
Friability: N Disturbance: Low
ACM%: 25
Type: CHR
QTY: 6 SF
Mat: 9"X9" BLK
W/WHTSTRK
Friability: N
VFT Asbestos Survey VFT Asbestos Survey
Bldg 1 – Floor 4, B451
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
D-Section Bldg 1 – Floor 1,D129
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 2, D239
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Low space
Location Notes
ACM%: 25
Type: CHR
QTY: 6 SF
Mat: 9"X9" CONFETTI
GRN
Friability: N
Bldg 1 – Floor 3, D346A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Fin Tube Radiator
• Divide/split existing radiator to fit new
Bldg 1 – Floor 4, D410
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Data ports Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Location Notes
ACM%: 15
Type: CHR
QTY: 6 SF
Mat: 9"X9" GRY
W/BLKSTRK
Friability: N Disturbance: Low
ACM%: 25
Type: CHR
QTY: 6 SF
Mat: 9"X9" BLK
W/WHTSTRK
Friability: N
F-Section Bldg 1 – Floor 1, F158
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 2, F256
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Low space
Location Notes
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT
W/GRY& BRN
Friability: N
Bldg 1 – Floor 3, F356
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Low space
Location Notes
ACM%: 2
Type: CHR
QTY: 6 SF
Mat: 1'X1' BRN MOT Friability: N
Bldg 1 – Floor 4, F456
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Utilities
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
G-Section Bldg 1 – Floor 1, G100-I
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 1, G100J
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 8
Type: CHR
QTY: 6 SF
Mat: 1'X1' WHT
W/PNK& BRN STRK
Friability: N
Bldg 1 – Floor 2, G212
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Junction box Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location
Location Notes
ACM%: 7
Type: CHR
QTY: 6 SF
Mat: 2'X1' BLK BORDER Friability: N Disturbance: Low
ACM%: 15
Type: CHR
QTY: 56 SF
Mat: 9"X9" GRY
W/BLKSTRK
Friability: N Disturbance: Low
ACM%: 25
Type: CHR
QTY: 56 SF
Mat: 9"X9" BLK
W/WHTSTRK
Friability: N
VFT Asbestos Survey VFT Asbestos Survey VFT Asbestos Survey
Bldg 1 – Floor 2, G218
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: <1
Type: CHR
QTY: 6 SF
Mat: 1'X1' BRN W/BRN
WHT STRK
Friability: N
Bldg 1 – Floor 3, G312
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
ACM%: 15
Type: CHR
QTY: 6 SF
Mat: 9"X9" GRY
W/BLKSTRK
Friability: N Disturbance: Low
ACM%: 25
Type: CHR
QTY: 6 SF
Mat: 9"X9" BLK
W/WHTSTRK
Friability: N
Bldg 1 – Floor 3, G320A
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Bldg 1 – Floor 4, G415
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Electric outlet
• Disconnect and reconnect any electric utility after relocating onto new chase or nearby
Bldg 1 – Floor 4, G421
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Existing Riser Location
Proposed New Location
Radiator
• Replace cast iron radiator with new fin tubbed radiator
Attic Bldg 1 – Steam Line
N
578-26-006 Repair Building 1 Steam and Condensate Risers
Isolation Valve Horizontal Steam line
• Replace isolation valve and horizontal/vertical piping along with insulation
GLOSSARY
CHR: Chrysotile
N-ACC: Non-Accessible
ACM: Asbestos Containing Material
VFT: Floor Tile/Sheet
Y: Material that crumbled when hand pressure was applied, ranging from high friability—very soft material that crumbled with light hand pressure—to low friability—material that crumbled after exerting substantial hand pressure
N: Nonfriable material that could not be crumbled, lightly abraded, or powdered by exertion of hand pressure
Good: No apparent damage to the material
Low: The potential for contact with the ACM, influence of vibration, and potential for air erosion are assessed to be low.
SF: Square Feet
LF: Lineal Feet
| Slide 1: A-Section Bldg 1 – Floor 1, Existing Riser Locations |
| Slide 2: A-Section Bldg 1 – Floor 2, Existing Riser Locations |
| Slide 3: A-Section Bldg 1 – Floor 2, A202A |
| Slide 4: A-Section Bldg 1 – Floor 2, A202A |
| Slide 5: A-Section Bldg 1 – Floor 2, A202B |
| Slide 6: A-Section Bldg 1 – Floor 2, A201 |
| Slide 7: A-Section Bldg 1 – Floor 2, A205 |
| Slide 8: A-Section Bldg 1 – Floor 2, A209 |
| Slide 9: A-Section Bldg 1 – Floor 2, A213A |
| Slide 10: A-Section Bldg 1 – Floor 2, A213A |
| Slide 11: A-Section Bldg 1 – Floor 2, A227 |
| Slide 12: A-Section Bldg 1 – Floor 2, A231 |
| Slide 13: A-Section Bldg 1 – Floor 2, A235 |
| Slide 14: A-Section Bldg 1 – Floor 2, A235 |
| Slide 15: A-Section Bldg 1 – Floor 2, A239 |
| Slide 16: A-Section Bldg 1 – Floor 2, A241 |
| Slide 17: A-Section Bldg 1 – Floor 2, A241A |
| Slide 18: A-Section Bldg 1 – Floor 2, A206 |
| Slide 19: A-Section Bldg 1 – Floor 2, CORR |
| Slide 20: A-Section Bldg 1 – Floor 2, A214 |
| Slide 21: A-Section Bldg 1 – Floor 2, A214 |
| Slide 22: A-Section Bldg 1 – Floor 2, A214 |
| Slide 23: A-Section Bldg 1 – Floor 2, A224 |
| Slide 24: A-Section Bldg 1 – Floor 2, A228 |
| Slide 25: A-Section Bldg 1 – Floor 2, A228 |
| Slide 26: A-Section Bldg 1 – Floor 2, A230 |
| Slide 27: A-Section Bldg 1 – Floor 2, A238 |
| Slide 28: A-Section Bldg 1 – Floor 3, Existing Riser Locations |
| Slide 29: A-Section Bldg 1 – Floor 3, A300 |
| Slide 30: A-Section Bldg 1 – Floor 3, A300 |
| Slide 31: A-Section Bldg 1 – Floor 3, A300-1 |
| Slide 32: A-Section Bldg 1 – Floor 3, A303 |
| Slide 33: A-Section Bldg 1 – Floor 3, A305 |
| Slide 34: A-Section Bldg 1 – Floor 3, A309 |
| Slide 35: A-Section Bldg 1 – Floor 3, A315 |
| Slide 36: A-Section Bldg 1 – Floor 3, A315 |
| Slide 37: A-Section Bldg 1 – Floor 3, A329 |
| Slide 38: A-Section Bldg 1 – Floor 3, A329 |
| Slide 39: A-Section Bldg 1 – Floor 3, A331 |
| Slide 40: A-Section Bldg 1 – Floor 3, A333 |
| Slide 41: A-Section Bldg 1 – Floor 3, A337 |
| Slide 42: A-Section Bldg 1 – Floor 3, A341 |
| Slide 43: A-Section Bldg 1 – Floor 3, A343 |
| Slide 44: A-Section Bldg 1 – Floor 3, A306 |
| Slide 45: A-Section Bldg 1 – Floor 3, CORR |
| Slide 46: A-Section Bldg 1 – Floor 3, A312 |
| Slide 47: A-Section Bldg 1 – Floor 3, A314 |
| Slide 48: A-Section Bldg 1 – Floor 3, A314 |
| Slide 49: A-Section Bldg 1 – Floor 3, A326 |
| Slide 50: A-Section Bldg 1 – Floor 3, A326 |
| Slide 51: A-Section Bldg 1 – Floor 3, A326 |
| Slide 52: A-Section Bldg 1 – Floor 3, A330 |
| Slide 53: A-Section Bldg 1 – Floor 3, A340 |
| Slide 54: A-Section Bldg 1 – Floor 4, Existing Riser Locations |
| Slide 55: A-Section Bldg 1 – Floor 4, A400 |
| Slide 56: A-Section Bldg 1 – Floor 4, A400 |
| Slide 57: A-Section Bldg 1 – Floor 4, A400 |
| Slide 58: A-Section Bldg 1 – Floor 4, A401 |
| Slide 59: A-Section Bldg 1 – Floor 4, A405 |
| Slide 60: A-Section Bldg 1 – Floor 4, A413 |
| Slide 61: A-Section Bldg 1 – Floor 4, A415 |
| Slide 62: A-Section Bldg 1 – Floor 4, A417 |
| Slide 63: A-Section Bldg 1 – Floor 4, A429 |
| Slide 64: A-Section Bldg 1 – Floor 4, A440 |
| Slide 65: A-Section Bldg 1 – Floor 4, A433 |
| Slide 66: A-Section Bldg 1 – Floor 4, A435 |
| Slide 67: A-Section Bldg 1 – Floor 4, A439 |
| Slide 68: A-Section Bldg 1 – Floor 4, A445 |
| Slide 69: A-Section Bldg 1 – Floor 4, B401 |
| Slide 70: A-Section Bldg 1 – Floor 4, CORR |
| Slide 71: A-Section Bldg 1 – Floor 4, A414 |
| Slide 72: A-Section Bldg 1 – Floor 4, A416 |
| Slide 73: A-Section Bldg 1 – Floor 4, A418A |
| Slide 74: A-Section Bldg 1 – Floor 4, A420 |
| Slide 75: A-Section Bldg 1 – Floor 4, A432 |
| Slide 76: A-Section Bldg 1 – Floor 4, A434A |
| Slide 77: A-Section Bldg 1 – Floor 4, A434B |
| Slide 78: A-Section Bldg 1 – Floor 4, A438 |
| Slide 79: A-Section Bldg 1 – Floor 4, A442 |
| Slide 80: B-Section Bldg 1 – Floor 1, B159 |
| Slide 81: B-Section Bldg 1 – Floor 2, B259 |
| Slide 82: B-Section Bldg 1 – Floor 3, B355 |
| Slide 83: B-Section Bldg 1 – Floor 4, B451 |
| Slide 84: D-Section Bldg 1 – Floor 1,D129 |
| Slide 85: D-Section Bldg 1 – Floor 2, D239 |
| Slide 86: D-Section Bldg 1 – Floor 3, D346A |
| Slide 87: D-Section Bldg 1 – Floor 4, D410 |
| Slide 88: F-Section Bldg 1 – Floor 1, F158 |
| Slide 89: F-Section Bldg 1 – Floor 2, F256 |
| Slide 90: F-Section Bldg 1 – Floor 3, F356 |
| Slide 91: F-Section Bldg 1 – Floor 4, F456 |
| Slide 92: G-Section Bldg 1 – Floor 1, G100-I |
| Slide 93: G-Section Bldg 1 – Floor 1, G100J |
| Slide 94: G-Section Bldg 1 – Floor 2, G212 |
| Slide 95: G-Section Bldg 1 – Floor 2, G218 |
| Slide 96: G-Section Bldg 1 – Floor 3, G312 |
| Slide 97: G-Section Bldg 1 – Floor 3, G320A |
| Slide 98: G-Section Bldg 1 – Floor 4, G415 |
| Slide 99: G-Section Bldg 1 – Floor 4, G421 |
| Slide 100: Attic Bldg 1 – Steam Line |
| Slide 101: GLOSSARY |