S02 - 7 578-26-006 Room Plans.pdf

PDF 8 MB Posted

Attached to
Z1DA--578-26-006 - Repair Steam and Condensate Risers Building 1 - Phase 2 (CON)
Solicitation number
36C25226B0012
Issued by

About this file

This is a room plan and construction specification document for the repair of steam and condensate risers in Building 1 at a Department of Veterans Affairs facility (Contract N 578-26-006, Phase 2). The document provides detailed floor-by-floor layouts and construction notes for Floors 1 and 2 of A-Section Building 1, identifying existing riser locations and proposed new riser locations with corresponding asbestos survey data.

The primary work scope includes installing new steam and condensate risers at locations proximate to existing risers, reconnecting all existing radiator lines to the new risers, and installing new insulation on all newly installed pipe risers and fittings. The contractor is responsible for demolition and relocation of wall fixtures, equipment, cabinetry, and furniture as necessary to accommodate the new pipe chase, as well as the relocation of obstructing utilities including electric outlets, receptacles, data ports, wireless access points, gas nozzles, and equipment. Asbestos-containing material (ACM) is present throughout the project location, with most areas indicating 70% ACM content of chrysotile type with assumed positive friability and low disturbance potential located behind walls and ceilings. The contractor must create shop drawings for the new chase requiring approval from the Contracting Officer's Representative (COR) prior to construction commencement and must perform all work in accordance with general abatement and demolition notes.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A-Section Bldg 1 – Floor 1, Existing Riser Locations

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

▪ New steam and condensate risers shall be installed at locations close to existing risers and reconnect all existing radiator lines to new risers

▪ Install new insulation on all newly installed pipe risers and fittings

▪ Demolition or relocation of wall fixtures, equipment, cabinetry, and all furniture as necessary to accommodate new pipe chase is the responsibility of the contractor

▪ Electric outlets, receptacles, data ports, and other utilities obstructing construction of new chase is the responsibility of the contractor and verified by electrician for proper relocation

▪ Contractor must create shop drawings for new chase to be installed and approved by COR prior to construction

▪ Perform all necessary tasks in accordance with the general abatement and demolition notes

Construction Notes

Bldg 1 – Floor 2, Existing Riser Locations

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Bldg 1 – Floor 2, A202A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey

Location Notes

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Wireless access point

• Relocate if obstructing new chase construction

Bldg 1 – Floor 2, A202A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Location Notes

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Equipment

• Relocate if

Bldg 1 – Floor 2, A202B

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Location Notes

Bldg 1 – Floor 2, A201

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Bldg 1 – Floor 2, A205

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Riser Asbestos Survey

Bldg 1 – Floor 2, A209

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Junction Box Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 2, A213A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Gas nozzle

• Relocate if obstructing new

Bldg 1 – Floor 2, A213A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Wireless Access Point

• Relocate if obstructing new

Bldg 1 – Floor 2, A227

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Data ports

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 2, A231

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 2, A235

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Fin Tube Radiator

• Shorten radiator to fit new chase

Bldg 1 – Floor 2, A235

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 2, A239

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 2, A241

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/WHT

& BRN STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 11 LF

Mat: Steam Friability: Y Disturbance: Low Loc: No change

Riser Asbestos Survey VFT Asbestos Survey

Wireless Access Point

• Relocate if obstructing new

Bldg 1 – Floor 2, A241A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 2, A206

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 11 LF

Mat: Steam Friability: Y Disturbance: Low

Bldg 1 – Floor 2, CORR

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Wireless Access Point

• Relocate if obstructing new

Bldg 1 – Floor 2, A214

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Wall switch

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Wall Hanging Cabinet

• Remove from wall and fit onto new chase or relocate to nearby location

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Wireless Access Point Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Wall accessories Cabinets Tabletop

• Cut/remove table and cabinet section as well as any obstructions to fit new chase

Bldg 1 – Floor 2, A224

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 11 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Fin Tube Radiator

• Divide/split existing radiator to fit new chase

Tabletop Cabinets

• Cut/remove table and drawer section to fit new chase

Bldg 1 – Floor 2, A228

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/WHT

& BRN STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Fine Tube Radiator

• Divide/split existing radiator to fit new chase

Data ports Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 2, A228

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey VFT Asbestos Survey Location Notes

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/WHT

& BRN STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Tabletop Cabinets

• Cut/remove table and drawer section to fit new chase

Bldg 1 – Floor 2, A230

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey Location Notes

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Low Space Piping

• Relocate if

Bldg 1 – Floor 2, A238

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/BLU

STRKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 3, Existing Riser Locations

N

Bldg 1 – Floor 3, A300

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey VFT Asbestos Survey

Location Notes

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: 1'X1' WHT W/BRN

CHNK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit

Bldg 1 – Floor 3, A300

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: 1'X1' WHT W/BRN

CHNK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Data Ports Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit

Bldg 1 – Floor 3, A300-1

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Wireless Access Point

• Relocate if obstructing new

Bldg 1 – Floor 3, A303

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT

W/GRY& BRN LG CHNK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey Valves Electric outlet

• Disconnect and reconnect any electric/gas utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit

Bldg 1 – Floor 3, A305

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT

W/GRY& BRN LG CHNK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 3, A309

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' GRN W/SM

GRN STRK

Friability: N Disturbance: Low

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit

Location Notes VFT Asbestos Survey

Bldg 1 – Floor 3, A315

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/BRN&

WHT MOT

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey Electric outlet

• Disconnect and reconnect any electric/gas utility after relocating onto new chase or nearby location

Wireless Access Point

• Relocate if obstructing new chase construction

VFT Asbestos Survey

Bldg 1 – Floor 3, A315

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/BRN&

WHT MOT

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey Data ports

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit new chase

Bldg 1 – Floor 3, A329

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 3, A329

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit new chase

Bldg 1 – Floor 3, A331

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: N/A

Type: N/A

QTY: 6 SF

Mat: 1'X1' WHITE W/

GREEN SPECK FT &

BLCK MSTC

Friability: N Disturbance: Low

Electric outlets Data ports

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 3, A333

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: N/A

Type: N/A

QTY: 6 SF

Mat: 1'X1' WHITE W/

GREEN SPECK FT &

BLCK MSTC

Friability: N Disturbance: Low

Data ports

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 3, A337

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 3, A341

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey Electric box Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Tabletop Cabinets

• Cut/remove table and cabinet section as necessary to fit new chase

Bldg 1 – Floor 3, A343

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 3, A306

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' GRN W/SM

GRN STRK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

Bldg 1 – Floor 3, CORR

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Proposed New Location

Bldg 1 – Floor 3, A312

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: 1'X1' TAN W/BRN&

WHT NOT

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 11 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey Sink Nozzles Tabletop Cabinets

• Cut/remove table and cabinet section as well as any sinks, gas fittings and valves/nozzles as necessary to fit new chase

Bldg 1 – Floor 3, A314

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' GRY W/BLU

& GRY NOT

Friability: N Disturbance: Low

Bldg 1 – Floor 3, A314

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' GRY W/BLU

& GRY NOT

Friability: N Disturbance: Low

Tabletop Cabinets

• Cut/remove table and cabinet to fit

Bldg 1 – Floor 3, A326

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Light switch Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey VFT Asbestos Survey

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y

Bldg 1 – Floor 3, A330

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Low Space Wireless Access Point

• Relocate if obstructing new chase construction

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N

Location Notes Riser Asbestos Survey VFT Asbestos Survey

Bldg 1 – Floor 3, A340

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT W/GRN

FLKS

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey VFT Asbestos Survey

Light switch Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 4, Existing Riser Locations

N

Bldg 1 – Floor 4, A400

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Riser Asbestos Survey

Location Notes

VFT Asbestos Survey

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 44 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Electric outlet

• Disconnect and reconnect any electric utility and all conduit after relocating onto new chase or nearby location

Wireless access point

• Relocate if

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 44 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 44 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Junction box Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 4, A401

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 4, A405

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N

Bldg 1 – Floor 4, A413

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: N/A

Type: N/A

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N

Bldg 1 – Floor 4, A415

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR

QTY: 44 LF

Mat: Steam Friability: Y Disturbance: Low

Bldg 1 – Floor 4, A417

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: N/A

Type: N/A

QTY: 6 SF

Mat: 9"X9" TAN W/ RED

FLOORTILE AND

MASTIC

Friability: N

Bldg 1 – Floor 4, A429

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

Piping

• Disconnect existing piping as necessary to refit onto new chase

Bldg 1 – Floor 4, A440

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: CHR

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

ACM%: 70

Type: CHR

QTY: 44 LF

Mat: Steam Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A433

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 12

Type: CHR

QTY: 6 SF

Mat: 9"X9" LT BRN

W/BLU & BRN STRK

Friability: N Disturbance: Low

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A435

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A439

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A445

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, B401

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, CORR

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 4, A414

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A416

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 4, A418A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Low Space CO2 Chamber

Bldg 1 – Floor 4, A420

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A432

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N Disturbance: Low

Low Space Piping

• Disconnect existing piping as necessary to refit onto new chase

Radiator

• Remove existing cast iron radiator if space for chase is insufficient

Bldg 1 – Floor 4, A434A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

Riser Asbestos Survey

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A434B

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Location Notes

Piping

• Disconnect existing piping as necessary to refit onto new

Bldg 1 – Floor 4, A438

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 70

Type: CHR Mat: N-ACC Assumed Pos Friability: Y Disturbance: Low Loc: Behind walls/ceil

ACM%: 12

Type: N/A

QTY: 6 SF

Mat: 9"X9" LT BRN

W/BLU & BRN STRK

Friability: N

VFT Asbestos Survey Riser Asbestos Survey

Bldg 1 – Floor 4, A442

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 0

Type: N/A

QTY: 6 SF

Mat: BRN FLOOR

SHEET

Friability: N

B-Section Bldg 1 – Floor 1, B159

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 2

Type: CHR

QTY: 6 SF

Mat: 1'X1' BRN W/WHT

MOT

Friability: N Disturbance: Low

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' BLU W/WHT

& DK BLU FLKS

Friability: N Disturbance: Low

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' BRN W/DK

BRN MOT

Friability: N

VFT Asbestos Survey VFT Asbestos Survey VFT Asbestos Survey

Bldg 1 – Floor 2, B259

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 3, B355

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Location Notes

ACM%: 15

Type: CHR

QTY: 6 SF

Mat: 9"X9" GRY

W/BLKSTRK

Friability: N Disturbance: Low

ACM%: 25

Type: CHR

QTY: 6 SF

Mat: 9"X9" BLK

W/WHTSTRK

Friability: N

VFT Asbestos Survey VFT Asbestos Survey

Bldg 1 – Floor 4, B451

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

D-Section Bldg 1 – Floor 1,D129

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 2, D239

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Low space

Location Notes

ACM%: 25

Type: CHR

QTY: 6 SF

Mat: 9"X9" CONFETTI

GRN

Friability: N

Bldg 1 – Floor 3, D346A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Fin Tube Radiator

• Divide/split existing radiator to fit new

Bldg 1 – Floor 4, D410

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Data ports Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Location Notes

ACM%: 15

Type: CHR

QTY: 6 SF

Mat: 9"X9" GRY

W/BLKSTRK

Friability: N Disturbance: Low

ACM%: 25

Type: CHR

QTY: 6 SF

Mat: 9"X9" BLK

W/WHTSTRK

Friability: N

F-Section Bldg 1 – Floor 1, F158

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 2, F256

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Low space

Location Notes

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT

W/GRY& BRN

Friability: N

Bldg 1 – Floor 3, F356

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Low space

Location Notes

ACM%: 2

Type: CHR

QTY: 6 SF

Mat: 1'X1' BRN MOT Friability: N

Bldg 1 – Floor 4, F456

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Utilities

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

G-Section Bldg 1 – Floor 1, G100-I

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 1, G100J

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 8

Type: CHR

QTY: 6 SF

Mat: 1'X1' WHT

W/PNK& BRN STRK

Friability: N

Bldg 1 – Floor 2, G212

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Junction box Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby location

Location Notes

ACM%: 7

Type: CHR

QTY: 6 SF

Mat: 2'X1' BLK BORDER Friability: N Disturbance: Low

ACM%: 15

Type: CHR

QTY: 56 SF

Mat: 9"X9" GRY

W/BLKSTRK

Friability: N Disturbance: Low

ACM%: 25

Type: CHR

QTY: 56 SF

Mat: 9"X9" BLK

W/WHTSTRK

Friability: N

VFT Asbestos Survey VFT Asbestos Survey VFT Asbestos Survey

Bldg 1 – Floor 2, G218

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: <1

Type: CHR

QTY: 6 SF

Mat: 1'X1' BRN W/BRN

WHT STRK

Friability: N

Bldg 1 – Floor 3, G312

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

ACM%: 15

Type: CHR

QTY: 6 SF

Mat: 9"X9" GRY

W/BLKSTRK

Friability: N Disturbance: Low

ACM%: 25

Type: CHR

QTY: 6 SF

Mat: 9"X9" BLK

W/WHTSTRK

Friability: N

Bldg 1 – Floor 3, G320A

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Bldg 1 – Floor 4, G415

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Electric outlet

• Disconnect and reconnect any electric utility after relocating onto new chase or nearby

Bldg 1 – Floor 4, G421

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Existing Riser Location

Proposed New Location

Radiator

• Replace cast iron radiator with new fin tubbed radiator

Attic Bldg 1 – Steam Line

N

578-26-006 Repair Building 1 Steam and Condensate Risers

Isolation Valve Horizontal Steam line

• Replace isolation valve and horizontal/vertical piping along with insulation

GLOSSARY

CHR: Chrysotile

N-ACC: Non-Accessible

ACM: Asbestos Containing Material

VFT: Floor Tile/Sheet

Y: Material that crumbled when hand pressure was applied, ranging from high friability—very soft material that crumbled with light hand pressure—to low friability—material that crumbled after exerting substantial hand pressure

N: Nonfriable material that could not be crumbled, lightly abraded, or powdered by exertion of hand pressure

Good: No apparent damage to the material

Low: The potential for contact with the ACM, influence of vibration, and potential for air erosion are assessed to be low.

SF: Square Feet

LF: Lineal Feet

Slide 1: A-Section Bldg 1 – Floor 1, Existing Riser Locations
Slide 2: A-Section Bldg 1 – Floor 2, Existing Riser Locations
Slide 3: A-Section Bldg 1 – Floor 2, A202A
Slide 4: A-Section Bldg 1 – Floor 2, A202A
Slide 5: A-Section Bldg 1 – Floor 2, A202B
Slide 6: A-Section Bldg 1 – Floor 2, A201
Slide 7: A-Section Bldg 1 – Floor 2, A205
Slide 8: A-Section Bldg 1 – Floor 2, A209
Slide 9: A-Section Bldg 1 – Floor 2, A213A
Slide 10: A-Section Bldg 1 – Floor 2, A213A
Slide 11: A-Section Bldg 1 – Floor 2, A227
Slide 12: A-Section Bldg 1 – Floor 2, A231
Slide 13: A-Section Bldg 1 – Floor 2, A235
Slide 14: A-Section Bldg 1 – Floor 2, A235
Slide 15: A-Section Bldg 1 – Floor 2, A239
Slide 16: A-Section Bldg 1 – Floor 2, A241
Slide 17: A-Section Bldg 1 – Floor 2, A241A
Slide 18: A-Section Bldg 1 – Floor 2, A206
Slide 19: A-Section Bldg 1 – Floor 2, CORR
Slide 20: A-Section Bldg 1 – Floor 2, A214
Slide 21: A-Section Bldg 1 – Floor 2, A214
Slide 22: A-Section Bldg 1 – Floor 2, A214
Slide 23: A-Section Bldg 1 – Floor 2, A224
Slide 24: A-Section Bldg 1 – Floor 2, A228
Slide 25: A-Section Bldg 1 – Floor 2, A228
Slide 26: A-Section Bldg 1 – Floor 2, A230
Slide 27: A-Section Bldg 1 – Floor 2, A238
Slide 28: A-Section Bldg 1 – Floor 3, Existing Riser Locations
Slide 29: A-Section Bldg 1 – Floor 3, A300
Slide 30: A-Section Bldg 1 – Floor 3, A300
Slide 31: A-Section Bldg 1 – Floor 3, A300-1
Slide 32: A-Section Bldg 1 – Floor 3, A303
Slide 33: A-Section Bldg 1 – Floor 3, A305
Slide 34: A-Section Bldg 1 – Floor 3, A309
Slide 35: A-Section Bldg 1 – Floor 3, A315
Slide 36: A-Section Bldg 1 – Floor 3, A315
Slide 37: A-Section Bldg 1 – Floor 3, A329
Slide 38: A-Section Bldg 1 – Floor 3, A329
Slide 39: A-Section Bldg 1 – Floor 3, A331
Slide 40: A-Section Bldg 1 – Floor 3, A333
Slide 41: A-Section Bldg 1 – Floor 3, A337
Slide 42: A-Section Bldg 1 – Floor 3, A341
Slide 43: A-Section Bldg 1 – Floor 3, A343
Slide 44: A-Section Bldg 1 – Floor 3, A306
Slide 45: A-Section Bldg 1 – Floor 3, CORR
Slide 46: A-Section Bldg 1 – Floor 3, A312
Slide 47: A-Section Bldg 1 – Floor 3, A314
Slide 48: A-Section Bldg 1 – Floor 3, A314
Slide 49: A-Section Bldg 1 – Floor 3, A326
Slide 50: A-Section Bldg 1 – Floor 3, A326
Slide 51: A-Section Bldg 1 – Floor 3, A326
Slide 52: A-Section Bldg 1 – Floor 3, A330
Slide 53: A-Section Bldg 1 – Floor 3, A340
Slide 54: A-Section Bldg 1 – Floor 4, Existing Riser Locations
Slide 55: A-Section Bldg 1 – Floor 4, A400
Slide 56: A-Section Bldg 1 – Floor 4, A400
Slide 57: A-Section Bldg 1 – Floor 4, A400
Slide 58: A-Section Bldg 1 – Floor 4, A401
Slide 59: A-Section Bldg 1 – Floor 4, A405
Slide 60: A-Section Bldg 1 – Floor 4, A413
Slide 61: A-Section Bldg 1 – Floor 4, A415
Slide 62: A-Section Bldg 1 – Floor 4, A417
Slide 63: A-Section Bldg 1 – Floor 4, A429
Slide 64: A-Section Bldg 1 – Floor 4, A440
Slide 65: A-Section Bldg 1 – Floor 4, A433
Slide 66: A-Section Bldg 1 – Floor 4, A435
Slide 67: A-Section Bldg 1 – Floor 4, A439
Slide 68: A-Section Bldg 1 – Floor 4, A445
Slide 69: A-Section Bldg 1 – Floor 4, B401
Slide 70: A-Section Bldg 1 – Floor 4, CORR
Slide 71: A-Section Bldg 1 – Floor 4, A414
Slide 72: A-Section Bldg 1 – Floor 4, A416
Slide 73: A-Section Bldg 1 – Floor 4, A418A
Slide 74: A-Section Bldg 1 – Floor 4, A420
Slide 75: A-Section Bldg 1 – Floor 4, A432
Slide 76: A-Section Bldg 1 – Floor 4, A434A
Slide 77: A-Section Bldg 1 – Floor 4, A434B
Slide 78: A-Section Bldg 1 – Floor 4, A438
Slide 79: A-Section Bldg 1 – Floor 4, A442
Slide 80: B-Section Bldg 1 – Floor 1, B159
Slide 81: B-Section Bldg 1 – Floor 2, B259
Slide 82: B-Section Bldg 1 – Floor 3, B355
Slide 83: B-Section Bldg 1 – Floor 4, B451
Slide 84: D-Section Bldg 1 – Floor 1,D129
Slide 85: D-Section Bldg 1 – Floor 2, D239
Slide 86: D-Section Bldg 1 – Floor 3, D346A
Slide 87: D-Section Bldg 1 – Floor 4, D410
Slide 88: F-Section Bldg 1 – Floor 1, F158
Slide 89: F-Section Bldg 1 – Floor 2, F256
Slide 90: F-Section Bldg 1 – Floor 3, F356
Slide 91: F-Section Bldg 1 – Floor 4, F456
Slide 92: G-Section Bldg 1 – Floor 1, G100-I
Slide 93: G-Section Bldg 1 – Floor 1, G100J
Slide 94: G-Section Bldg 1 – Floor 2, G212
Slide 95: G-Section Bldg 1 – Floor 2, G218
Slide 96: G-Section Bldg 1 – Floor 3, G312
Slide 97: G-Section Bldg 1 – Floor 3, G320A
Slide 98: G-Section Bldg 1 – Floor 4, G415
Slide 99: G-Section Bldg 1 – Floor 4, G421
Slide 100: Attic Bldg 1 – Steam Line
Slide 101: GLOSSARY

File details come from the government source that posted it. Updated .