S02 - 556-24-122 Drawings.pdf
PDF 23 MB Posted
- Attached to
- Y1DZ--556-24-122 B132 Pool and HVAC Replacement
- Solicitation number
- 36C25226B0032_01
About this file
This file is a comprehensive set of 100% construction documents (drawing sheets) for the B132 Pool and HVAC Replacement project at Captain James A. Lovell Federal Health Care Center in North Chicago, Illinois. The project, identified as VA Contract Number 36C25224N0467 and Task Number 556-24-122, requires the general contractor to provide all labor, materials, equipment, qualified supervision, and related items to renovate the therapeutic pool, replace the HVAC system, modernize pool plumbing and associated systems, make staff and patient locker rooms ADA/ABA compliant, and demolish and replace the existing elevated air handling unit with a new exterior pad-mounted unit.
The construction documents include detailed drawings across multiple disciplines: architectural plans showing floor layouts, demolition plans, finish schedules, and life safety/infection control phasing; structural plans with reinforced concrete and masonry details; civil site development and erosion control plans; mechanical plans covering HVAC ductwork, piping, and controls; electrical plans with power, lighting, and low-voltage systems; plumbing plans; fire protection systems; aquatic system schematics; and hazardous materials surveys documenting asbestos and lead-based paint locations. The project is organized in three construction phases with temporary infection control barriers and smoke-rated wall construction required per NFPA 241. Key construction requirements include concrete mix designs with minimum 4,000 PSI compressive strength, reinforced masonry walls, control joint specifications, housekeeping pads for equipment, coordination of pipe penetrations, and compliance with special inspection schedules for concrete and masonry work. The documents specify that work shall be performed without damage to retained existing construction, with above-ceiling work restricted to 5:00 PM to 5:00 AM hours and vibration/noise work similarly restricted.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet
Number -
Sheet Name Sheet Name
General
G000 COVER SHEET
HAZARDOUS MATERIALS ELEMENTS
HM100 BASEMENT LEVEL FLOOR PLAN - OVERALL - ASBESTOS
HM101 FIRST LEVEL FLOOR PLAN - OVERALL - ASBESTOS
HM102 BASEMENT LEVEL FLOOR PLAN - OVERALL - LEAD-BASED PAINT
HM103 FIRST LEVEL FLOOR PLAN - OVERALL - LEAD-BASED PAINT
Civil
CI101 CIVIL GENERAL NOTES
CS101 SITE DEVELOPMENT PLAN
CJ101 EROSION CONTROL PLAN
CS501 MISCELLANEOUS DETAILS
Structural
SI001
STRUCTURAL ABBREVIATIONS, SYMBOLS, & GENERAL
NOTES
SB101 STRUCTURAL FIRST FLOOR PLAN
EP100 BASEMENT FLOOR PLAN -POWER
EP101 FIRST FLOOR PLAN -POWER
EV100 BASEMENT FLOOR PLAN -LOW VOLTAGE
EV101 FIRST FLOOR PLAN -LOW VOLTAGE
EP600 ELECTRICAL DETAILS
EP601 ELECTRICAL DETAILS
EP700 ELECTRICAL SCHEDULES
EP701 ELECTRICAL SCHEDULES
SB501 STRUCTURAL SECTIONS & DETAILS
SB901 STRUCTURAL ISOMETRIC VIEW
Architectural
GC101 FIRST FLOOR INFECTION CONTROL/ PHASING PLAN
GI101 LIFE SAFETY PLAN
AE001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS
AE002 WALL TYPES
AD101 FIRST FLOOR DEMOLITION PLAN
AE101 FIRST FLOOR ARCHITECTURAL PLAN
AE401 ENLARGED PLANS
AE601 DOOR SCHEDULE
AI101 FINISH PLAN
AI201 ENLARGED INTERIOR PLANS & ELEVATIONS
AI601 FINISH SCHEDULES
Aquatics
QA000 POOL REFERENCE PLAN
QA001 POOL DEMOLITION PLAN
QA100 POOL PLAN & SECTION
QA200 POOL MECHANICAL DEMOLITION AND RENOVATION PLANS
QA201 SURGE TANK PLAN & SECTIONS
QA202 POOL MECHANICAL DETAILS
QA203 POOL MECHANICAL DETAILS
QA500 POOL SYSTEMS SCHEMATIC
Mechanical
FX000 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
FX100 BASEMENT FLOOR PLAN -FIRE PROTECTION
FX101 FIRST FLOOR PLAN -FIRE PROTECTION
MH000 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD100 BASEMENT FLOOR PLAN -MECHANICAL -DEMOLITION
MD101 FIRST FLOOR PLAN -MECHANICAL -DEMOLITION
PP100 BASEMENT FLOOR PLAN -PLUMBING
PP101 FIRST FLOOR PLAN -PLUMBING
P400 MECHANICAL ROOM -PLUMBING -ENLARGED PLAN
P500 PLUMBING DETAILS & SCHEDULES
Electrical
EP000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
ED100 BASEMENT FLOOR PLAN -ELECTRICAL -DEMOLITION
ED101 FIRST FLOOR PLAN -ELECTRICAL -DEMOLITION
EL101 FIRST FLOOR PLAN -LIGHTING
EL201 FIRST FLOOR PLAN -LIGHTING CONTROL
MH101 FIRST FLOOR PLAN -DUCTWORK
MP100 BASEMENT FLOOR PLAN -PIPING
MP101 FIRST FLOOR PLAN -PIPING
M500 MECHANICAL DETAILS
M501 MECHANICAL CONTROLS
M502 MECHANICAL CONTROLS
M600 MECHANICAL SCHEDULES
M601 MECHANICAL SCHEDULES
PD100 BASEMENT FLOOR PLAN -PLUMBING -DEMOLITION
PP000 PLUMBING SYMBOLS AND ABBREVIATIONS
PD101 FIRST FLOOR PLAN -PLUMBING -DEMOLITION
ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
06/20/25
A u to d e s k D o c s /2
.0
V A
L o v e ll
B
P o o l a n d H
V A
C R e p la c e m e n t/
-1
.G
R
.r v t
/1
/2
:4
:0
P
M
G000
COVER SHEET B132 POOL AND HVAC
REPLACEMENT
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 MS AEA
23022.018
100% CONSTRUCTION
DOCUMENTS
3001 Green Bay Rd, North Chicago, IL 60064
556-24-122
Base Bid:
The General Contractor shall provide labor, material, and equipment at Captain James A. Lovell FHCC, North Chicago, IL to renovate the pool, HVAC system, all pool systems, and staff/patient locker rooms in building 132 to meet the latest standards for aquatic therapy pools and VA accessibility requirements.
N
FACILITY NAME:
Captain James A. Lovell Federal Health Care Center (FHCC)
PROJECT NAME:
B132 Pool and HVAC Replacement
SITE ADDRESS:
VA PROJECT NUMBER:
36C252-23-D-0061
VA CONTRACT NUMBER:
36C25224N0467
VA TASK NUMBER:
SITE MAP:
VICINITY MAP:
Revisions: Date:
W/D
DN
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
CODE ANALYSIS LEGEND
FE
FIRE EXTINGUISHER
10 9 8 7 6 5 4 3 2 1
G
F
E
D
C
B
GA
GE
GD
GC
GB
9267 SF
2290 SF
A-3
2419 SF
A-3
2456 SF
A-3
EXIT
EXIT
EXIT
EXIT EXIT
EXITEXIT
EXIST.
FEC
EXIST.
FE
EXIST.
FE
D
IA
G O
N A
L D
IS
TA
N C
E
4"
EXIT S
EPERATIO
N = 75' - 7"
PATH OF EGRESS = 75'-0"
PRIMARY PATH OF EGRESS = 73'-5"
MEN'S LOCKER
ROOM
TOWEL ROOM
MEN'S SHOWER
WOMEN'S SHOWER
WOMEN'S LOCKER
ROOM
MEN'S STAFF
LOCKER
WOMEN'S STAFF
LOCKER
CORRIDOR
WOMEN'S
RESTROOM
MEN'S RESTROOM
THERAPEUTIC POOL
OFFICE
SUPPLY ROOM
EQUIPMENT ROOM
STAIR
EXERCISE AREA
CORRIDOR
JANITOR
CONNECTING
CORRIDOR
S E
C O
N D
A R
Y P
A T
H O
F E
G R
E S
S
'-0
CHANGING RM
ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
A u to d e s k D o c s /2
.0
V A
L o v e ll B
P o o l a n d H
V A
C R e p la c e m e n t/
.1
.0
A v
.r v t
/1
/2
:2
:0
P
M
GI101
LIFE SAFETY PLAN B132 POOL AND HVAC
REPLACEMENT
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 JF TAA
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/8" = 1'-0"GI101
5 FIRST FLOOR LIFE SAFETY PLAN
N
5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
Revisions: Date:
zedeng.com 23022.018
W/D
DN
DN
10 9 8 7 6 5 4 3 2 1
G
F
E
D
C
B
GA
GE
GD
GC
GB
553 SF
MEN'S LOCKER
ROOM
TLTS1
83 SF
TOWEL ROOM
UCCL1
81 SF
MEN'S SHOWER
TLTS1
55 SF
WOMEN'S SHOWER
TLTS1
151 SF
WOMEN'S LOCKER
ROOM
TLTS1
128 SF
MEN'S STAFF
LOCKER
TLTU1
133 SF
WOMEN'S STAFF
LOCKER
TLTU1
439 SF
CORRIDOR
237 SF
WOMEN'S
RESTROOM
TLTS1
70 SF
MEN'S RESTROOM
TLTS1
4614 SF
THERAPEUTIC POOL
RTTP2
255 SF
OFFICE
OFA09
162 SF
SUPPLY ROOM
SRLW1
268 SF
EQUIPMENT ROOM
SRE01
82 SF
STAIR
8377 SF
EXERCISE AREA
PTEA1
104 SF
CORRIDOR
18 SF
JANITOR
JANC1
EXIST
FEC
921 SF
CONNECTING
CORRIDOR
CONTINUOUS FIRESAFE SEALANT
TOP AND BOTTOM, & BOTH SIDES
3 1/2" SOUND ATTENUATION BATT.
5/8" TYPE X GYPSUM BOARD, BOTH SIDES
3 5/8" METAL STUD @ 16" O.C. WITH
RUNNER CHANNELS ALONG TOP
AND BOTTOM
CONSTRUCTION
SIDE
PUBLIC
SIDE
6 MIL. FIRE RETARDANT VISQUEEN
MEMBRANE. CONTINUOUSLY ADHERE
TO THE STRUCTURAL DECK ABOVE AND
TO THE FLOOR BELOW WITH TAPE.
UNDERSIDE OF STRUCTURAL DECK
UL LISTING: U465
COORDINATE WITH EXISTING CEILING
PUBLIC
SIDE
1 HOUR FIRE RATED METAL DOOR ASSEMBLY
AND FRAME WITH SEALS, CARD READER OR
CONTRACTOR CORE PER OWNER'S
PREFERENCE, HARDWARE AND CLOSER
AIR PRESSURE MONITOR
HAND SANITIZER
SEAL ALL EDGES WITH TAPE
SEAL ALL EDGES WITH TAPE
REFER TO TEMPORARY BARRIER TYPE FOR
REQUIRED CONDITION TO STRUCTURE ABOVE
VA / OSHA TEMPORARY SIGNAGE
TEMPORARY WALLS. SEE PLAN AND PLAN NOTES
TEMPORARY CONSTRUCTION ACCESS DOORS
REFERENCE AREA FOR ABOVE CEILING
WORK ON FLOOR BELOW.
RE: ENGINEERING DRAWINGS FOR FULL
SCOPE OF WORK
BEYOND PROJECT BOUNDARY
PROJECT BOUNDARY
IC / PHASING LEGEND
CONSTRUCTION ACTIVITY - INFECTION RISK: // TYPE A, B, C AND D //
PATIENT RISK GROUP: // LOW, MEDIUM, HIGH OR HIGHEST //
CLASS OF PRECAUTION MATRIX: // I, II, III OR IV //
1. PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION PER NFPA 241. REFER TO DETAIL 2/GC101.
2. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH
CARD READER ACCESS. REFER TO ELEVATION 3/GC101.
3. EXISTING DOOR TO SERVE AS TEMPORARY INFECTION CONTROL BARREIR.
PROVIDE A 24"X36" STICKY WALK OFF MAT AND HAND SANITIZER AT EACH
TEMPORARY DOOR LOCATION.
A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED
BY CLASS IN SPECIFICATION 010110 AND ADDITIONAL INFORMATION.
B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE
FOR ADDITIONAL INFORMATION.
C. PROJECT SHALL BE COMPLETED IN A TWO PHASES.
D. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE
CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
E. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER
WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR
AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY
IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE
APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA
PROTOCOLS AND PLAN IS APPROVED.
F. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR
AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE
PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR
PROVIDED CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW
THE FLOOR PLATE OF THE PROJECT BOUNDARY.
G. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM
AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE
CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED
IN A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED
AND BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.
H. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED
DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF
OPERATION.
I. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN
THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO
KEEP NOISE AND VIBRATION TO A MINIMUM.
J. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"
STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR
LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY
K. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH
TEMPORARY DOOR LOCATION.
L. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,
MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE
LIQUIDS UP TO 30 GALLONS.
M. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED
WITH 4 MIL. POLY SHEET.
N. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT
BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED
ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED
WITH A LID.
O. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY
STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE
MATERIALS SHALL NOT BE STORED IN THE FACILITY.
P. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE
PROJECT BOUNDARY.
A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT
CONSTRUCTION.
B. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION
FOR EACH PHASE AND AREA OF WORK.
PHASING GENERAL NOTES
INFECTION CONTROL PLAN NOTES
INFECTION CONTROL GENERAL NOTES
INFECTION CONTROL PROJECT INFORMATION
PHASE 1. STAFF LOCKER ROOMS TO BE RENOVATED.
MEN'S AND WOMEN'S LOCKER ROOMS AND CORRIDOR 100
TO REMIAN OPERATIONAL DURING CONSTRUCTION.
EXERCISE AREA WILL BE OCCUPIED BY STAFF AND
VETERANS THROUGHOUT CONSTRUCTION. RENOVATION OF
STAFF LOCKER ROOMS MUST BE COMPLETED PRIOR TO
START OF PHASE 2.
PHASE 2. RENOVATION OF MEN'S AND WOMEN'S LOCKER
ROOM. CORRIDOR 100 AND STAFF LOCKER ROOMS TO
REMIAN OPERATIONAL DURING CONSTRUCTION. EXERCISE
AREA WILL BE OCCUPIED BY STAFF AND VETERANS
THROUGHOUT CONSTRUCTION.
PHASE 3. RENOVATION OF THE POOL AREA CAN OCCUR AT
ANY POINT DURING CONSTRUCTION. EXERCISE AREA WILL
BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT
CONSTRUCTION.
PHASING LEGEND
ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
A u to d e s k D o c s /2
.0
V A
L o v e ll B
P o o l a n d H
V A
C R e p la c e m e n t/
.1
.0
A v
.r v t
/1
/2
:2
:0
P
M
GC101
FIRST FLOOR INFECTION
CONTROL/ PHASING PLAN
B132 POOL AND HVAC
REPLACEMENT
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 JF TAA
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/8" = 1'-0"GC101
1 FIRST FLOOR PLAN INFECTION CONTROL/PHASING
SCALE: 1 1/2" = 1'-0"GC101
2 TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL CONSTRUCTION NFPA 241
SCALE: 1/4" = 1'-0"GC101
3 TEMPORARY WALL CONSTRUCTION ELEVATION
N
5 5 10 15 20
1/8" = 1'-0"
FEETSCALE
Revisions: Date:
zedeng.com 23022.018
CRAWL
SPACE
MECHANICAL
M01
CRAWL
SPACE
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
CHEMICAL
STORAGE
132-PNL-002-M01
132-MDP-001-M01
132-PNL-001-M01
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
-1 -2
:2
:5
A u to d e s k D o c s
/2
.0
V
A L o v e ll A rc F la s h S tu d y /5
-1
.B u ild in g
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
Revisions: Date: ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
STAMP
www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com
ASBESTOS
BASEMENT LEVEL FLOOR PLAN -
OVERALL - ASBESTOS
B132 Pool and HVAC Replacement
556-24-122
HM100
ACPB
ASBESTOS LEGEND
ASBESTOS SAMPLE LOCATIONS
ASBESTOS LOCATIONS
NONE
ASBESTOS SOIL SAMPLE LOCATIONS NONE
Location
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
3/32" = 1'-0"
B132 - FIRST LEVEL FLOOR PLAN - OVERALL -
N
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
ASBESTOS
100% CONSTRUCTION
DOCUMENTS
06/20/2025
06/20/2025100% CONSTRUCTION DOCUMENTS
SURVAY SAMPLY LOCATIONS
EXERCISE
GYMNASIUM
JAN I
TOR
TOWEL
SERVICE
WOMENS
STAFF
LOCKERS
CORRIDOR
CO-1-01
OFFICE
MENS
STAFF
LOCKERS
CHANGING
ROOM
103A
TOILET
SHOWERS
TOILET
THERAPEUTIC
POOL
SHOWERS
MENS
LOCKER
EQUIPMENT
ROOM
104A
TRAMWAY
CORRIDOR
STAIRS
SW-1-01 132-PNL-002-105
132-PNL-001-105
132-PNL-001-CO101
132-PNL-001-101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
-1 -2
:2
:5
A u to d e s k D o c s
/2
.0
V
A L o v e ll A rc F la s h S tu d y /5
-1
.B u ild in g
.E
R
.r v t
3/32" = 1'-0"
B132 - FIRST LEVEL FLOOR PLAN - OVERALL -
N
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com
23022.018
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
Revisions: Date:
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
Revisions: Date: ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
STAMP
www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com Location
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
ASBESTOS
FIRST LEVEL FLOOR PLAN -
OVERALL - ASBESTOS
B132 Pool and HVAC Replacement
556-24-122
HM101
ACPB
ASBESTOS LEGEND
ASBESTOS SAMPLE LOCATIONS
ASBESTOS LOCATIONS
NONE
100% CONSTRUCTION
DOCUMENTS
06/20/2025
CRAWL
SPACE
MECHANICAL
M01
CRAWL
SPACE
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
CHEMICAL
STORAGE
132-PNL-002-M01
132-MDP-001-M01
132-PNL-001-M01
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
-1 -2
:2
:5
A u to d e s k D o c s
/2
.0
V
A L o v e ll A rc F la s h S tu d y /5
-1
.B u ild in g
.E
R
.r v t
3/32" = 1'-0"
B132 - BASEMENT LEVEL FLOOR PLAN - OVERALL -
N
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com
23022.018
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
Revisions: Date:
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
Revisions: Date: ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
STAMP
www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com
LEAD-BASED PAINT
BASEMENT LEVEL FLOOR PLAN -
OVERALL - LEAD-BASED PAINT
B132 Pool and HVAC Replacement
556-24-122
HM102
ACPB
NONE
LEAD-BASED PAINT LOCATIONSLEAD-BASED PAINT LEGEND
LEAD-BASED PAINT SAMPLE LOCATIONS (XRF)
Location
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
100% CONSTRUCTION
DOCUMENTS
06/20/2025
EXERCISE
GYMNASIUM
JAN I
TOR
TOWEL
SERVICE
WOMENS
STAFF
LOCKERS
CORRIDOR
CO-1-01
OFFICE
MENS
STAFF
LOCKERS
CHANGING
ROOM
103A
TOILET
SHOWERS
TOILET
THERAPEUTIC
POOL
SHOWERS
MENS
LOCKER
EQUIPMENT
ROOM
104A
TRAMWAY
CORRIDOR
STAIRS
SW-1-01 132-PNL-002-105
132-PNL-001-105
132-PNL-001-CO101
132-PNL-001-101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
-1 -2
:2
:5
A u to d e s k D o c s
/2
.0
V
A L o v e ll A rc F la s h S tu d y /5
-1
.B u ild in g
.E
R
.r v t
3/32" = 1'-0"
B132 - FIRST LEVEL FLOOR PLAN - OVERALL -
N
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com
23022.018
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
Revisions: Date:
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
25% SCHEMATIC DESIGN 11/20/2024
50% DESIGN DEVELOPMENT 01/31/2025
Revisions: Date: ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
STAMP
www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
1197 Farnsworth Rd. Suite E Waterville, OH 43566 castlehillassociates.com Location
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
LEAD-BASED PAINT
FIRST LEVEL FLOOR PLAN -
OVERALL - LEAD-BASED PAINT
B132 Pool and HVAC Replacement
556-24-122
HM103
ACPB
LEAD-BASED PAINT LEGEND
LEAD-BASED PAINT SAMPLE LOCATIONS (XRF)
LEAD-BASED PAINT LOCATIONS
METAL ROOF TRUSSES - POOL AND GYM
METAL BEAMS AND COLUMNS - POOL AND GYM
METAL TRUSSES ABOVE CEILING TILE - 1ST FLOOR
HALLWAY
METAL PASSAGE DOORS AND DOOR FRAMES - POOL
WOOD FLOOR BOARDS - GYM AHU LOFT FLOOR
METAL HVAC GRILLES - POOL WALLS
METAL DUCTS AT CEILING LEVEL - POOL CATWALK
GLAZED WALL BLOCKS - POOL WALLS
100% CONSTRUCTION
DOCUMENTS
06/20/2025
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
Au to de sk
D oc s:
//2
.0
VA
L ov el l B
Po ol a nd
H
VA
C R ep la ce m en t/2
3.
.0
1_ A_ v2 2.
rv t
/2
0/
:5 9:
P
M
B132 POOL AND HVAC
REPLACEMENT
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 CMB AWB
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
CI101
CIVIL GENERAL NOTES
GENERAL
1. FOR VIEWING CLARITY OF THESE PLANS, THE PIPES OR STRUCTURES
MAY NOT BE DRAWN TO SCALE.
2. THE UTILITIES INDICATED ON THESE PLANS MAY NOT BE A COMPLETE
INVENTORY OF ALL UTILITIES CURRENTLY ON OR NEAR THE SITE. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING PUBLIC AND/OR
PRIVATE UTILITY LOCATING SERVICES PRIOR TO STARTING
CONSTRUCTION.
3. THE SIZE AND LOCATIONS OF THE UTILITIES INDICATED ON THESE
PLANS ARE APPROXIMATE. THE CONTRACTOR IS TO DETERMINE AND
FIELD VERIFY ALL HORIZONTAL AND VERTICAL LOCATIONS PRIOR TO
STARTING CONSTRUCTION ACTIVITIES.
4. ANY DISCREPANCIES OR CONFLICTS WHICH BECOME APPARENT
BEFORE OR DURING CONSTRUCTION SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD AND COR PRIOR TO
CONSTRUCTION SO THAT REDESIGN OR CLARIFICATION MAY OCCUR.
DEMOLITION
1. ALL DEMOLISHED MATERIAL TO BECOME THE PROPERTY OF THE
CONTRACTOR, UNLESS OTHERWISE NOTED, AND SHALL BE LEGALLY
DISPOSED OF OFFSITE.
2. CONDUCT DEMOLITION AND CONSTRUCTION ACTIVITIES IN SUCH A
MANNER TO PROVIDE MINIMUM TRAFFIC DISRUPTIONS. CONTRACTOR
TO INSTALL TRAFFIC CONTROL DEVICES PER THE MANUAL ON UNIFORM
TRAFFIC CONTROL DEVICES (MUTCD), LATEST EDITION, AS NECESSARY.
3. ALL EXISTING TREES TO REMAIN SHALL BE PRESERVED AND
PROTECTED.
4. CONTRACTOR SHALL COORDINATE ALL WORK ASSOCIATED WITH THE
REMOVAL, RELOCATION, AND DEMOLITION OF EXISTING UTILITIES WITH
THE VA COR WELL IN ADVANCE OF NEED.
5. CONTRACTOR TO MAINTAIN PROPER DRAINAGE IN DEMOLITION AREAS.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING DAMAGE TO
EXISTING BUILDINGS AND/OR SITE ENTITIES THAT ARE TO REMAIN.
7. CONCRETE TO BE SAWCUT SHALL BE SAWCUT TO THE NEAREST
CONCRETE JOINT BEYOND THE LIMITS ILLUSTRATED.
SITE PLAN
1. ALL DIMENSIONS ARE TO THE BACK OF CURB. WHEN CURBS ARE NOT
PRESENT, DIMENSION ARE TO THE EDGE OF PAVEMENT.
2. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS ON THE SITE PRIOR
TO CONSTRUCTION AND IDENTIFY DISCREPANCIES TO THE ENGINEER
OF RECORD AND COR.
3. SEE SHEET CS501 FOR PROPOSED SITE IMPROVEMENT DETAILS
REFERENCED.
4. WHERE WORK IS DONE IN EXISTING AREAS, THE EXISTING FINISHED
CONDITIONS SHALL BE REPAIRED OR REPLACED IF DAMAGED. IF
REPAIRS ARE REQUIRED NEW FINISHED CONDITIONS SHALL MATCH
EXISTING CONDITIONS, UNLESS OTHERWISE NOTED.
GRADING
1. CONTRACTOR SHALL ENSURE THAT POSITIVE DRAINAGE IN IMPROVED
AREAS IS ACHIEVED. CONTRACTOR TO TEST AND CORRECT ANY “BIRD
BATH” CONDITIONS.
2. ALL SLOPES SHALL BE 3:1 OR FLATTER, UNLESS OTHERWISE SHOWN.
3. ALL GRADES AT THE PROJECT BOUNDARY OR PROPERTY LINE SHALL
MEET EXISTING GRADES.
4. PAVED AREAS DESIGNATED FOR FILL SHALL BE CONSTRUCTED OF
SUITABLE FILL MATERIAL AND COMPACTED PER SPECIFICATIONS. ALL
FILL AREAS ARE TO BE STRIPPED OF TOPSOIL PRIOR TO PLACEMENT OF
FILL.
5. ANY EXCESS SOIL MATERIAL SHALL BE EXPORTED FROM THE SITE
AFTER CONSTRUCTION IS COMPLETE.
UTILITIES
1. CONTRACTOR TO MAINTAIN ALL EXISTING UTILITIES TO STAY IN SERVICE
DURING CONSTRUCTION.
2. WHERE CONSTRUCTION IS IN THE VICINITY OF EXISTING PIPING, THE
LOCATION AND ELEVATION OF THE EXISTING PIPING AND STRUCTURES
SHALL BE FIELD VERIFIED BY THE CONTRACTOR. IF ANY DISCREPANCIES
ARE FOUND, THEN THE VA COR SHALL BE NOTIFIED IMMEDIATELY.
3. MEASUREMENTS AND SLOPES SHOWN ARE FROM CENTER OF
STRUCTURE TO CENTER OF STRUCTURE.
4. QUANTITIES PROVIDED ARE ESTIMATES AND SHALL BE CONFIRMED BY
THE CONTRACTOR.
EROSION CONTROL
1. EROSION AND SEDIMENTATION CONTROL DEVICES TO BE INSTALLED
PRIOR TO BEGINNING CONSTRUCTION.
2. STABILIZATION MEASURES SHALL BE INITIATED AS SOON AS
PRACTICABLE IN PORTIONS OF THE SITE WHERE CONSTRUCTION
ACTIVITIES HAVE TEMPORARILY OR PERMANENTLY CEASED, BUT IN NO
CASE MORE THAN SEVEN (7) DAYS AFTER WORK HAS CEASED, UNLESS
ACTIVITY IN THAT PART OF THE SITE WILL RESUME WITHIN TWENTY-ONE
(21) DAYS.
3. PROVIDE SILT FENCE AND/OR OTHER CONTROL DEVICES, AS MAY BE
REQUIRED, TO CONTROL SOIL EROSION DURING UTILITY
CONSTRUCTION. ALL DISTURBED AREAS SHALL BE CLEANED, GRADED,
AND STABILIZED WITH GRASSING IMMEDIATELY AFTER THE UTILITY
INSTALLATION.
4. EROSION CONTROL AND SEDIMENTATION CONTROL DEVICES TO BE
MAINTAINED SUCH THAT THEY FUNCTION AS INTENDED. AFTER
COMPLETION OF THE PROJECT THE CONTRACTOR SHALL REMOVE ALL
DEVICES WHERE A GOOD STAND OF GRASS HAS BEEN ESTABLISHED
AND EROSION IS NO LONGER EVIDENT. REMOVAL OF THE REMAINING
DEVICES SHALL OCCUR AS OTHER AREAS ARE ESTABLISHED.
5. EROSION CONTROL MEASURES SHALL BE INSPECTED EVERY SEVEN (7)
DAYS OR AFTER EACH RAINFALL OCCURRENCE THAT EXCEEDS
ONE-HALF (1/2) INCH. DAMAGED OR INEFFECTIVE DEVICES SHALL BE
REPAIRED OR REPLACED IMMEDIATELY.
6. ALL AREAS DISTURBED BY GRADING, EXCAVATION, AND GENERAL
CONSTRUCTION SHALL BE SEEDED, MULCHED, AND RESTORED IN
ACCORDANCE WITH THE SPECIFICATIONS.
7. THE CONTRACTOR MUST TAKE NECESSARY ACTION TO PREVENT
TRACKING OF SOIL ONTO PAVED ROADWAYS. THE CONTRACTOR SHALL
IMMEDIATLY REMOVE MUD/SOIL FROM PAVEMENT.
8. SEE SHEET CJ501 FOR PROPOSED EROSION AND SEDIMENT CONTROL
DETAILS REFERENCED.
AC ACRE
ABC AGGREGATE BASE COURSE
ADA AMERICANS WITH DISABILITIES ACT
AGGR AGGREGATE
ALT ALTERNATE
APPROX APPROXIMATE
ARV AIR RELEASE VALVE
ASPH ASPHALT
ASSY ASSEMBLY
BC BACK OF CURB
BFP BACKFLOW PREVENTER
BLDG BUILDING
BLT BUILT
BM BENCHMARK
BNRY BOUNDARY
BO BLOW OFF
C/C CENTER TO CENTER
CB CATCH BASIN
CCTV CLOSED CIRCUIT TELEVISION
CFS CUBIC FEET PER SECOND
CHKV CHECK VALVE
CI CAST IRON
CIR CIRCULAR
CJ CONSTRUCTION JOINT OR CONTROL
JOINT
CL CENTER LINE
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CO CLEANOUT
COMM COMMUNICATION
CONC CONCRETE
CONST CONSTRUCT OR CONSTRUCTION
COR CORNER
CTR CENTER
CTRL CONTROL
CTV CABLE TELEVISION
CF CUBIC FEET
CY CUBIC YARD
CV CONTROL VALVE
DA DRAINAGE AREA
DAT DATUM
DBL DOUBLE
DDCV DOUBLE DETECTOR CHECK VALVE
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DI DROP INLET
DIA DIAMETER
DIFF DIFFERENCE OR DIFFERENTIAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DIST DISTANCE
DOM DOMESTIC
DOT DEPARTMENT OF TRANSPORTATION
DS DOWNSPOUT
DW DOMESTIC WATER
EA EACH
EC EDGE OF CURB
EG EXISTING GRADE
EJ EXPANSION JOINT
ELEV ELEVATION
EP EDGE OF PAVEMENT (PAVING)
EPA ENVIRONMENTAL PROTECTION AGENCY
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ES EDGE OF SHOULDER
ESMT EASEMENT
EW END WALL
EX EXISTING
EXP EXPANSION
F/F FACE TO FACE
FDC FIRE DEPARTMENT CONNECTION
FES FLARED END SECTION
FFE FINISH FLOOR ELEVATION
FHA FIRE HYDRANT ASSEMBLY
FNC FENCE
FOC FACE OF CURB
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPW FIRE PROTECTION WATER SUPPLY
FSP FIRE STANDPIPE
FT FEET OR FOOT
G NATURAL GAS OR GAS LINE
GA GAGE
GAL GALLON
GEN GENERATOR
GPD GALLONS PER DAY
GT GREASE TRAP
GV GATE VALVE
GUT GUTTER
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HANDICAP OR HANDICAPPED
HDPE HIGH DENSITY POLYETHYLENE
HDWL HEADWALL
HH HAND HOLE
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
HV HOSE VALVE
HWY HIGHWAY
HYD HYDRANT
IE INVERT ELEVATION
INCL INCLUDED
INFO INFORMATION
INV INVERT
IW IRRIGATION WATER
LAT LATITUDE
LF LINEAR FEET (FOOT)
LOC LOCATION
LONG LONGITUDE OR LONGITUDINAL
LOS LINE OF SIGHT
LP LOW POINT OR LIGHT POLE
LT LEFT
MAX MAXIMUM
MB MAIL BOX
MEG MEET EXISTING GRADE
MEMO MEMORANDUM
MFG MANUFACTURED OR MANUFACTURE
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MJ MECHANICAL JOINT
MOD MODIFY
MOT MAINTENANCE OF TRAFFIC
MULT MULTIPLE
MUNIC MUNICIPAL
MUTCD MANUAL ON UNIFORM TRAFFIC
CONTROL DEVICES
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NORM NORMAL
NRCP NON-REINFORCED CONCRETE PIPE
NTP NOTICE TO PROCEED
NTS NOT TO SCALE
OC ON CENTER
PAR PARALLEL
PAVT PAVEMENT
PB PULL BOX
PC POINT OF CURVE
PCC POINT OF COMPOUND CURVE
PCCP CONCRETE PAVEMENT
PE POLYETHYLENE (PLASTIC)
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PG PROFILE GRADE
PH PHASE
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PL PROPERTY LINE
PP POWER POLE OR POLYPROPYLENE
PR PROPOSED
PREV PREVIOUS
PRC POINT OF REVERSE CURVE
PRKG PARKING
PROJ PROJECT
PROP PROPERTY
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PSL PIPE SLEEVE
PT POINT OF TANGENCY
PVC POLYVINYL CHLORIDE (PLASTIC)
R RADIUS
RC REINFORCED CONCRETE
RCB REINFORCED CONCRETE BOX
RCP REINFORCED CONCRETE PIPE
RD ROAD OR ROOF DRAIN
RDC REDUCER
REQ REQUIRE OR REQUIRED
RFI REQUEST FOR INFORMATION
ROW RIGHT OF WAY
RR RAILROAD
RT RIGHT
SAN SANITARY
SB SPLASH BLOCK
SCH SCHEDULE
SD STORM DRAIN
SDL SADDLE
SECT SECTION
SEP SEPARATE
SF SQUARE FOOT (FEET)
SGL SINGLE
SHLDR SHOULDER
SOV SHUT OFF VALVE
SPEC SPECIFICATION
SF SQUARE FEET
SS SANITARY SEWER
STA STATION
STD STANDARD
STM STEAM
SURF SURFACE
SURV SURVEY
SW SIDEWALK
SY SQUARE YARD
T TELEPHONE
TBM TEMPORARY BENCHMARK
TB-XX TEST BORING-XX (E.G., TB-01)
TD TRENCH DRAIN
TE TOP ELEVATION
TEMP TEMPORARY
THK THICKNESS
TOB TOP OF BANK
TOC TOP OF CURB
TOPO TOPOGRAPHY
TOS TOE OF SLOPE
TP TELEPHONE POLE
TYP TYPICAL
TW TOP OF WALL
UD UNDERDRAIN
UP UTILITY POLE
UTIL UTILITY
USGS U.S. GEOLOGICAL SURVEY
VAR VARIES
VB VALVE BOX
VC VERTICAL CURVE
VERT VERTICAL
VIF VERIFY IN FIELD
VOL VOLUME
W WATER LINE
WM WATER METER OR WATER MAIN
WT WATER TABLE
WTR WATER
WW WASTE WATER
WWF WELDED WIRE FABRIC
XFMR TRANSFORMER
LIGHT DUTY
ASPHALT LIMITS
CONCRETE LIMITS
GRAVEL LIMITS
CONSTRUCTION FENCE
TREE PROTECTION
SANITARY SEWER
UNDERGROUND ELECTRIC
STORM SEWER
WATER MAIN
UE
UNDERGROUND
COMMUNICATIONS
DIRECTION OF FLOW
MATCH EXISTING GRADE
TOP OF CURB
GUTTER
SF
INLET PROTECTION
TEMPORARY SEEDING
CONCRETE WASHOUT AREA
CONSTRUCTION STAGING
AREA
TC 643.50
GU 643.00
640.00
M.E.G.
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
SANITARY FORCE MAIN >
SANITARY STRUCTURE
STORM STRUCTURES
SILT FENCE
BUILDING LIMITS
ASPHALT RESURFACING
LIMITS
LIGHT POLE
SIGN
XX LF OF XX" WM
XX LF OF XX" PVC
WATER TEE, BENDS
WATER MAIN VALVE
HEAVY DUTY
ASPHALT LIMITS
SPOT ELEVATION
CLEANOUT
FIRE HYDRANT
FIRE MAIN FM
GAS MAIN G
FIBER OPTIC FO
ROOF DRAIN RD
CENTERLINE
FEMA FLOOD ZONE PARKING BUMPER
SECTION NAME
SECTION LOCATED ON SHEET NO.
WATER MAIN REDUCER
TP TP
UNDER DRAIN UD
CLCOIR LOG
TOP OF CURB
EDGE OF PAVEMENT
TC 643.50
EP 643.00
CS501
CO
IP
XX LF OF XX" RCP
@ X.XX%
@ X.XX%
S
D
UT
CHILLED WATER MAIN CHW
TRAMWAY
TRAMWAY
TR
AM
W
AY
TR
AM
W
AY
EXISTING BRICK
BUILDING
(BLDG 132)
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CHW
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CHW
CH
W
CHW
SWIMMING
POOL
TR
AM
W
AY
D
D
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
D
SD
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE UE UE UE UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
UE
TRAMWAY
CH
W
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
10'
TAP TO EXIST. WTR.
MAIN. VERIFY EXACT
LOCATION IN FIELD.
CONTINUE WATER LINES
INTO BASEMENT AS PER
MECHANICAL PLANS
REPLACE ANY DAMAGED
CONCRETE CURB AND GUTTER
UPON PROJECT COMPLETION.
VERIFY LENGTH IN FIELD
16' V.I.F.
CONTINUE WATER LINES
INTO TRAMWAY PER
MECHANICAL PLANS
20'
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
Au to de sk
D oc s:
//2
.0
VA
L ov el l B
Po ol a nd
H
VA
C R ep la ce m en t/2
3.
.0
1_ A_ v2 2.
rv t
/2
0/
:5 9:
P
M
B132 POOL AND HVAC
REPLACEMENT
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 CMB AWB
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
SITE DEVELOPMENT PLAN KEYNOTES
0 2010
N
1. CONCRETE EQUIPMENT PAD
2. AWWA C900 DR18, 6-INCH DIA. CHILLED WATER PIPE, SUPPLY
3. AWWA C900 DR18, 6-INCH DIA. CHILLED WATER PIPE, RETURN
CS101
SITE DEVELOPMENT PLAN
TRAMWAY
TR
AM
W
AY
TR
AM
W
AY
EXISTING BRICK
BUILDING
(BLDG 132)
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CHW
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CHW
CH
W
CHW
CHW
SWIMMING
POOL
TR
AM
W
AY
D
D
D
TRAMWAY
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
CL
20'
CH
W
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CH
W
CH
W
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
CHW
MIN. LENGTH: 50'
12'
SF
SF
SF
SF
SF
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
Au to de sk
D oc s:
//2
.0
VA
L ov el l B
Po ol a nd
H
VA
C R ep la ce m en t/2
3.
.0
1_ A_ v2 2.
rv t
/2
0/
:5 9:
P
M
B132 POOL AND HVAC
REPLACEMENT
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 CMB AWB
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
EROSION & SEDIMENT CONTROL KEYNOTES
0 2010
N
CJ101
EROSION CONTROL PLAN
1. SILT FENCE
2. CONCRETE WASHOUT
3. STAGING AREA
4. CONSTRUCTION ENTRANCE
5. COIR LOG
SF
CL CL
RESTORE ALL DISTURBED
GRASS UPON COMPLETION
OF CONSTRUCTION.
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
Au to de sk
D oc s:
//2
.0
VA
L ov el l B
Po ol a nd
H
VA
C R ep la ce m en t/2
3.
.0
1_ A_ v2 2.
rv t
/2
0/
:5 9:
P
M
B132 POOL AND HVAC
REPLACEMENT
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 CMB AWB
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
CS501
MISCELLANEOUS DETAILS
CONCRETE EQUIPMENT PAD SECTION
10" 10"6"
1"R
SIZE PER
EQUIPMENT
MANUFACTURER'S
REQUIREMENTS
4000 PSFI, FIBER
REINFORCED CONCRETE
EXISTING
GRADE
COMPACTED SUBGRADE
2"
COMPACTED AGGREGATE
BASE COURSE
#4 REBAR, 12" O.C.
EACH WAY
6"
PLASTIC PIPE (PVC & HDPE) TRENCH DETAIL
GREATER THAN 5' FROM EDGE OF PAVEMENT
MIN. 1.25 Bc+12"
THAN 5'
REGULAR BACKFILL
4"
Bc
NOTES:
1. ALL BEDDING & INITIAL BACKFILL SHALL BE INSTALLED
IN 6" TO 12" BALANCED LIFTS.
2. A MINIMUM 9" CLEARANCE SHALL BE PROVIDED ON EACH
LEGEND
Bc = OUTSIDE DIAMETER
D = INSIDE DIAMETER
d = DEPTH OF BEDDING
MATERIAL BELOW PIPE
SIDE OF THE INSTALLED PIPE.
MIN.
12"
GREATER
EDGE OF PAVEMENT,
CURB, GUTTER, OR
SIMILAR STRUCTURE
IN THE PUBLIC R/W
FOR TRENCH WIDTHS EXCEEDING 4' [1219mm] REFER TO VA STANDARD
DETAIL 32 12 16-02 "TYPE 2 UTILITY TRENCH PATCH".
FOR TRENCH WHERE PORTLAND CEMENT CONCRETE (PCC) PAVEMENT
EXISTS, REFER TO 32 12 16-03 "TYPE 3 UTILITY TRENCH PATCH".
2" [50mm] MINIMUM OR THICKNESS OF EXISTING PAVEMENT WHICHEVER
IS GREATER.
BITUMINOUS SURFACE TREATMENT (CHIPSEAL) REQUIRED ONLY FOR
LONGITUDINAL TRENCHES WITH WIDTHS GREATER THAN 6' [1829mm].
4" [100mm] MINIMUM ABC OR THICKNESS OF EXISTING GRANULAR BASE
COURSE MATERIALS (E.G. ABC & SELECT MATERIAL) WHICHEVER IS
GREATER.
REFER TO VA STANDARD DETAIL 32 12 16-04 "UTILITY TRENCH
PAVEMENT PATCH NOTES" FOR ADDITIONAL INFORMATION.
TYPE 1 UTILITY TRENCH PATCH
4'-0" MAX.
1'-0" MAX.1'-0" MAX.
TRENCH
BACKFILL
ABC 100% MIN.
COMPACTION
ASPHALTIC CONCRETE
SAW CUT EXISTING.
ASPHALT FULL DEPTH
BOTH SIDESTACK COAT (TYP.)
EXISTING
PAVEMENT
MIN. 6" TOPSOIL
TO ENSURE
GRASS GROWTH
#8 CRUSHED STONE OR
APPROVED EQUIV. CLASS I
BEDDING MATERIAL HAND
TAMPED OR WALKED INTO
PLACE
STAPLES
(2 PER BALE)
STRAW BALE
10 mil PLASTIC LINING
NATIVE MATERIAL
(OPTIONAL)
WOOD OR
METAL STAKES
(2 PER BALE)
BINDER WIRE
CONCRETE WASHOUT
NOTES
1. ACTUAL LAYOUT TO BE DETERMINED IN THE FIELD.
2. A CONCRETE WASHOUT SIGN SHALL BE INSTALLED WITHIN 30' OF THE TEMPORARY CONCRETE
WASHOUT FACILITY.
3. MATERIALS USED TO CONSTRUCT TEMPORARY CONCRETE WASHOUT FACILITIES SHALL BE
REMOVED FROM THE SITE OF THE WORK AND DISPOSED OF OR RECYCLED.
4. HOLES, DEPRESSIONS OR OTHER GROUND DISTURBANCE CAUSED BY THE REMOVAL OF THE
TEMPORARY CONCRETE WASHOUT FACILITY SHALL BE BACKFILLED, REPAIRED, AND
STABILIZED TO PREVENT EROSION.
PLYWOOD
48"X24"
PAINTED WHITE
BLACK LETTERS
6" HEIGHT
LAG SCREWS
WOOD POST
3.5"X3.5"X8'
CONCRETE
WASHOUT
8"
2"
1.12" DIA
STEEL WIRE
STAPLE DETAI
SIGN DETAI
10' MINIMUM
VA
R
IE
S
10 mil PLASTIC LINING
TYPE "ABOVE GRADE" WITH STRAW BALES
STRAW BALE (TYP)
TYPE "BELOW GRADE"
BERM
10 mil PLASTIC LINING
SECTION A-A
PLAN
SANDBAG
10 mil PLASTIC LINING
LATH AND
FLAGGING ON
3-SIDES
BERM
3'
10' MINIMUM
VA
R
IE
S
SANDBAG
10 mil PLASTIC LINING
STAKE
(TYP)
TWO-STACKED
2"X12" ROUGH
WOOD FRAME
10' MINIMUM
VA
R
IE
S
10 mil
PLASTIC
LINING
WOOD FRAME SECURELY
FASTENED AROUND
ENTIRE PERIMETER
WITH TWO STAKES
TYPE "ABOVE GRADE" WITH WOOD
PLANKS
SLOPE
8" M
IN
4"
" M
IN
" M
IN
TEMPORARY SILT BARRIER
POST
SPACED
6' O.C.
FILTER FABRIC
COMPACTED
SOIL
EX. SUBGRADE12' M
INIMUM
AS REQUIRED
PUBLIC ROAD
50' MIN
6" MIN
CONSTRUCTION ENTRANCE
NOTES
A. GRAVEL PAD TO BE 12'x50' AND 6" THICK MINIMUM
B. TURNING RADIUS SUFFICIENT TO ACCOMMODATE LARGE TRUCKS
IS TO BE PROVIDED.
C. ENTRANCE(S) SHOULD BE LOCATED TO PROVIDE FOR MAXIMUM
UTILITY BY ALL CONSTRUCTION VEHICLES.
D. MUST BE MAINTAINED IN A CONDITION WHICH WILL PREVENT
TRACKING OR DIRECT FLOW OF MUD ONTO STREETS. PERIODIC
TOPDRESSING WITH STONE WILL BE NECESSARY; KEEP SOME
HANDY.
E. ANY MATERIAL WHICH STILL MAKES IT ONTO THE ROAD MUST BE
CLEANED UP IMMEDIATELY.
NOTES
APPLICABLE AT ALL POINTS OF INGRESS &
EGRESS UNTIL SITE IS STABLIZED. FREQUENT
CHECKS OF THE DEVICE AND TIMELY
MAINTTENANCE MUST BE PROVIDED.
COARSE AGGREGATE
2-3"
STEP 1: STAGGER 30" ATRA ANCHORS, OR APPROVED EQUAL, AT
2' O.C. ON EACH SIDE OF THE COIR LOG, DRIVING THE
ATRA ANCHOR INTO THE GROUND UNTIL THE TOP OF THE
ANCHOR IS NEARLY EVEN WITH THE COIR LOG OR UNTIL
REFUSAL.
STEP 2: USE TP-93 TENDON, OR APPROVED EQUAL, AS SPECIFIED TO LASH
ANCHORS AND LOGS TOGETHER USING THE ANCHOR HEAD. TIE A KNOT IN
THE ROPE LASHING AT EVERY ANCHOR HEAD AND EVERY 2.0' TO
PROPERLY SECURE THE SYSTEM.
STEP 3: DRIVE ANCHORS INTO SOIL SUCH THAT THE TENDON IS
TAUGHT AND THE ANCHORS REST EVEN WITH THE
UNDERLYING SOIL SURFACE.
PLAN VIEW
CROSS SECTIONAL VIEW
N.T.S.
N.T.S.
COIR LOG ANCHORING
COIR LOG END SECURING OPTION 2:
PLACE ADDITIONAL 30" ATRA GFRP ANCHORS AT END
SECTIONS OF D2 COIR LOGS AND LASH TOGETHER AS
SHOWN.
COIR LOG END SECURING OPTION 1:
LACE THE END SECTIONS OF THE D2 COIR LOGS TOGETHER
USING TENDON. MAINTAINS CONTINUOUS STAKING PATTERN.
COIR LOG END SECURING DETAIL
2'-0"
6"
*6 "12
1"
NTS
CONCRETE CURB AND GUTTER
2"R
TOPSOIL
7"
6"
1"R
* REVERSE
SLOPE
GUTTER 3
4"R
NOTE:
EXPANSION JOINT REQUIRED AT CHANGES IN DIRECTION
AND CONTRACTION JOINTS EVERY 20'-0"
4000 PSI, AIR ENTRAINED CONCRETE
SCHEDULE OF SPECIAL INSPECTIONS
MATERIAL / ACTIVITY SERVICE Y/N FREQUENCY
INSPECTION OF FABRICATORS
VERIFY FABRICATION / QC PROCEDURES
STEEL CONSTRUCTION
IN-PLANT REVIEW Y CONTINUOUS
HIGH-STRENGTH BOLTS, NUTS AND WASHERS REVIEW MATERIAL MARKINGS AND
CERTIFICATES OF COMPLIANCE Y PERIODIC
Y PERIODIC
Y PERIODIC
Y PERIODIC
WELD FILLER MATERIALS
INSPECTION OF ANCHOR RODS
STRUCTURAL STEEL WELDING
INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE WITH CONSTRUCTION
DOCUMENTS AND APPROVED SHOP DRAWINGS
REVIEW MATERIAL MARKINGS AND
CERTIFICATES OF COMPLIANCE
FIELD INSPECTION
FIELD INSPECTION
SHOP AND FIELD INSPECTIONS
N
CONCRETE CONSTRUCTION
Y CONTINUOUSINSPECTION OF REINFORCING STEEL INSTALLATION FIELD INSPECTION
Y CONTINUOUSVERIFICATION OF REQUIRED CONCRETE MIX DESIGN REVIEW SUBMITTALS
Y PERIODICFRESH CONCRETE SAMPLING FIELD TESTING
Y PERIODICCONCRETE PLACEMENT
Y CONTINUOUSCONCRETE CURING OPERATIONS FIELD REVIEW
FIELD REVIEW
Y CONTINUOUSEVALUATION OF CONCRETE STRENGTH FIELD TESTING AND REVIEW OF
LABORATORY REPORTS
1.
2.
3.
4.
5.
THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTOR(S) TO PROVIDE INSPECTIONS DURING CONSTRUCTION LISTED IN THIS SECTION. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE IN THE INSPECTIONS BEING PERFORMED TO THE SATISFACTION OF THE ENGINEER OF RECORD AND THE BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL HAVE EXPERIENCE WITH AT LEAST FIVE OTHER PROJECTS SIMILAR
IN NATURE.
THE PURPOSE OF THE INSPECTIONS SHALL BE TO ENFORCE COMPLIANCE WITH THE CONSTRUCTION DRAWINGS, SPECIFICATIONS, AND STATE AND LOCAL
BUILDING CODES IN EFFECT.
SPECIAL INSPECTORS SHALL KEEP RECORD OF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL AND TO THE ENGINEER OF RECORD. REPORTS SHALL INDICATE THAT THE WORK INSPECTED WAS PERFORMED IN CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. ANY CORRECTIONS THAT WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE ENGINEER OF RECORD. IF DISCREPANCIES ARE NOT CORRECTED BY THE CONTRACTOR, SPECIAL INSPECTOR SHALL ISSUE A NOTIFICATION OF NON-COMPLIANCE (NNC)
TO THE ENGINEER OR RECORD.
THE SPECIAL INSPECTOR SHALL VERIFY THAT THE FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES THAT PROVIDE A BASIS FOR INSPECTION CONTROL OF THE WORKMANSHIP. IF FABRICATOR IS ENROLLED IN A NATIONALLY ACCEPTED INSPECTIONS PROGRAM (SATISFACTORY TO THE ENGINEER AND BUILDING OFFICIAL), THIS IS NOT REQUIRED. ANY CORRECTIONS THAT WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE ENGINEER OF RECORD.
EACH SPECIAL INSPECTOR IS RESPONSIBLE TO REVIEW THE PLANS THOROUGHLY AND SUFFICIENTLY AHEAD OF THE CONSTRUCTION TO ESTABLISH IF HE CAN INSPECT THOSE ITEMS ENTRUSTED TO HIM. ALL AMBIGUITIES OR OMISSIONS IN THE APPROVED PLANS THAT CREATE ANY FORM OF DOUBT FOR THE SPECIAL INSPECTOR SHALL BE RESOLVED THROUGH THE PROPER CHANNELS PRIOR TO CONSTRUCTION.
NOTES:
PERIODIC
MASONRY VENEER LINTEL SCHEDULE
MASONRY VENEER
OPENING SIZE LINTEL DESCRIPTION DIAGRAM (SEE NOTE 4)
0' - 0" TO 5' - 0"
GREATER THAN 5' - 0"
TO 7' - 0" L6x4x5/16 (LLV)
GREATER THAN 7' - 0"
TO 10' - 0" L7x4x3/8 (LLV)
L4x4x5/16
1.
2.
3.
4.
NOTES:
PROVIDE 1" OF BEARING PER FOOT OF SPAN WITH MINIMUM 8" EACH
END OF LINTELS, UNLESS NOTED OTHERWISE.
ALL EXPOSED STEEL SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123.
WHERE LINTELS ARE NOT SPECIFICALLY SHOWN OR NOTED ON THE
STRUCTURAL OR ARCHITECTURAL DRAWINGS, PROVIDE THE
FOLLOWING LINTELS OVER ALL OPENINGS AND RECESSES IN BOTH
INTERIOR AND EXTERIOR NON-LOAD-BEARING WALLS.
LINTEL SHALL BE A DOUBLE ANGLE AT 8" NOMINAL CONCRETE BLOCK
AND A SINGLE ANGLE AT 4" NOMINAL MASONRY VENEER.
BAR SIZE TENSION DEVELOPMENT
LENGTH
DEVELOPMENT LENGTH IN
THICK CONCRETE
#3 1' - 3" 1' - 7" 1' - 7"
#4 1' - 7" 2' - 1"
#5 2' - 0" 2' - 7"
#6 2' - 5" 3' - 1"
#7 3' - 6" 4' - 6"
NOTES:
1.
2.
3.
THICK CONCRETE IS DEFINED AS A HORIZONTAL BAR WITH MORE THAN 12" OF FRESH CONCRETE CAST BELOW A
FOOTING, SLAB, WALL, OR OTHER CONCRETE MEMBER
ALL REINFORCING BARS ARE TO BE SPLICED WITH A CLASS B LAP SPLICE, U.N.O.
CONCRETE CLEAR COVER > NOMINAL BAR DIAMETER
TYPICAL LAP SPLICE
LENGTH
f'c 4,000 PSI CONCRETE CONSTRUCTION DEVELOPMENT
AND CLASS B LAP SPLICE LENGTHS
2' - 1"
2' - 9"
3' - 5"
4' - 1"
5' - 11"
LAP SPLICE LENGTH IN
THICK CONCRETE
#8 4' - 0" 5' - 2"
#9 4' - 6" 5' - 10"
6' - 9"
8' - 6"
2' - 1"
2' - 7"
3' - 1"
4' - 6"
5' - 2"
5' - 10"
MISCELLANEOUS SYMBOLS
NORTH ARROW
GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
GRAVEL
Name Elevation
FLOOR DRAIN
FD
N
CONCRETE WASH
PIPE PENETRATION THRU FDN WALL.
COORD. LOCATION & INVERT ELEV. W/
APPROPRIATE TRADE. SEE Sxxx DETAIL.
ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
100% CONSTRUCTION DOCUMENTS 06/20/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
Au to de sk
D oc s:
//2
.0
VA
L ov el l B
Po ol a nd
H
VA
C R ep la ce m en t/2
3.
.0
1_ A_ v2 2.
rv t
6/
/2
2:
:0
PM
SI001
STRUCTURAL ABBREVIATIONS,
SYMBOLS, & GENERAL NOTES
B132 POOL AND HVAC
REPLACEMENT
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025 ESB DSE
100% CONSTRUCTION
DOCUMENTS
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH AQUATICS, CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION OF SUPPLIER.
COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
MIXING WATER PROPORTION AND SOURCE.
ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
DESIGN SLUMP RANGE.
DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD DEVIATION"
DETERMINATION OUTLINED IN ACI 318.
1.
2.
3.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS
SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
CONCRETE MIX
CONCRETE REINFORCEMENT
MISCELLANEOUS STRUCTURAL STEEL
1.
2.
3.
4.
5.
6.
7.
8.
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
FIBER REINFORCEMENT FOR CONCRETE
CONCRETE REINFORCEMENT
CONCRETE CURING COMPOUND
CONCRETE JOINT SEALANT
WATER STOPS
EXPANSION ANCHORS
ADHESIVE ANCHORS
NON-SHRINK GROUT
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A
DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR TYPE II, UNO. CEMENTITIOUS MATERIAL CONTENT SHALL BE ADEQUATE FOR THE SPECIFIED REQUIREMENTS FOR STRENGTH, WATER-CEMENT RATIO, DURABILITY, AND FINISHABILITY.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT EXCEED 25 PERCENT. MAXIMUM COMPLEMENTARY CEMENTING MATERIALS (EX. FLY ASH, SLAG, SILICA FUME) AS A PERCENTAGE OF TOTAL WEIGHT OF CEMENTITIOUS MATERIAL SHALL BE 50 PERCENT. WATER/CEMENT RATIO SHALL BE BASED ON TOTAL CEMENTITIOUS MATERIAL, INCLUDING COMPLEMENTARY CEMENTING MATERIALS.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33. ALL CONCRETE SHALL BE NORMAL WEIGHT UNLESS NOTED
OTHERWISE.
LIGHTWEIGHT AGGREGATES SHALL CONFORM TO ASTM C330. LIGHTWEIGHT AGGREGATES SHALL BE PRE-SOAKED TO SATURATED-
SURFACE-DRY (SSD) CONDITION PRIOR TO MIXING.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494. THE USE OF WATER REDUCERS AND SUPER PLASTICIZERS IS ALLOWED, BUT NOT REQUIRED. ALL ADMIXTURES SHALL BE CHLORIDE FREE UNLESS OTHERWISE APPROVED BY THE ENGINEER.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW.
THE CONTRACTOR SHALL MEASURE SLUMP. IF CONCRETE IS PUMPED, SLUMP SHALL BE MEASURED AT…
This is the start of the file's text. The full file is on GovTribe.