S06 - QA101 - POOL STRUCTURAL NOTES AND DETAILS.pdf
PDF 460 KB Posted
- Attached to
- Y1DZ--556-24-122 B132 Pool and HVAC Replacement
- Solicitation number
- 36C25226B0032_01
About this file
This document is a set of pool structural notes and repair specifications from construction documents for a pool renovation project. The document establishes design standards, reinforced concrete requirements, and concrete repair procedures to guide contractor execution.
The design adheres to the 2018 International Building Code, ACI 318-14 for concrete, and ACI 350-06 for pool-specific requirements. All concrete must meet a minimum 4000 psi 28-day compressive strength with 6% air entrainment and a water-to-cementitious material ratio limited to 0.42. Reinforcing steel shall be shop-fabricated to ASTM A615 Grade 60 and detailed per ACI 318-05, ACI 315-05, and CRSI MSP-1-01, with specified clearances of 2 inches for pool walls and slabs, 3 inches for surfaces cast against earth, and 5/8 inches for 40-bar diameter lap splices. Pool concrete requires wet curing using hoses and polyethylene covering. Concrete repair work must comply with ACI 318, ACI 315, ACI 301, and the ACI Concrete Repair Manual (4th Edition). Prior to bidding, contractors must verify repair types, extents, quantities, and locations. All surface preparation, application, finishing, and curing shall follow manufacturer recommendations, with unbonded paint and coatings removed before repair work. Unsound, loose, or delaminated concrete must be removed to sound material, with repair areas extending a minimum of six inches beyond delamination points. Design team inspection of prepared surfaces is required before repair material placement, and repair configurations should avoid re-entrant corners and maintain simple, preferably square or rectangular shapes.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WATER LEVEL
+0'-0"
WATER LEVEL
+0'-0"
TYPICAL ABBREVIATIONS
A.B.
A.F.F.
ADDL.
ALT.
ARCH.
B.C.E.
B.O.
BLDG.
BM.
BOTT.
BRG.
BSMT.
BTWN.
CANT.
CMU
COL.
CONC.
CONN.
CONT.
CTRD.
DWG.
E.F.
E.O.D.
E.O.S.
E.W.
EA.
EL.
ELEV.
EMBED.
EQ.
EQUIP.
EWB
EX.
EXIST.
EXP.
EXT.
FDN.
FIN.
FLR.
FT.
FTG.
GA.
GALV.
H.P.
HORIZ.
I.F.
IN.
INFO.
INT.
JT.
L.P.
L.W.
LLH
LLV
LWB
M.E.P.
M.S.T.
MAX.
MECH.
MEZZ.
MFR.
MIN.
MISC.
N.T.S.
N.W.
o/c
PC
PSF
PSI
PTN.
REINF.
REQ'D.
RET'G.
S.F.
S.O.G.
SCHED.
SECT.
SIM.
SPECS.
STIFF.
STRUCT.
SWB
T&B
T.
T.O.
T.O.C.
T.O.S.
T.S.
TCELE
TCERE
TDS
THK.
TYP.
U.N.O.
V.I.F.
VERT.
W.R.T.
w/
WWF
ANCHOR BOLT
ABOVE FINISH FLOOR
ADDITIONAL
ALTERNATE
ARCHITECT
BOTTOM CHORD EXTENSION
BOTTOM OF
BUILDING
BEAM
BOTTOM
BEARING
BASEMENT
BETWEEN
CENTERLINE
CANTILEVER
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONTINUOUS
CENTERED
DIAMETER
DRAWING
EACH FACE
EDGE OF DECK
EDGE OF SLAB
EACH WAY
EACH
ELEVATION
ELEVATOR
EMBEDMENT
EQUAL
EQUIPMENT
EACH WAY BOTTOM
EXISTING
EXISTING
EXPANSION
EXTERIOR
FOUNDATION
FINISH
FLOOR
FEET
FOOTING
GAGE
GALVANIZED
HIGH POINT
HORIZONTAL
INSIDE FACE
INCHES
INFORMATION
INTERIOR
JOINT
LOW POINT
LIGHT WEIGHT
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONG WAY BOTTOM
MECHANICAL ELECTRICAL PLUMBING
METAL STUD TRUSS
MAXIMUM
MECHANICAL
MEZZANINE
MANUFACTURER
MINIMUM
MISCELLANEOUS
NOT TO SCALE
NORMAL WEIGHT
ON CENTER
PLATE
PILE CAP
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PARTITION
REINFORCEMENT
REQUIRED
RETAINING
STEP FOOTING
SLAB ON GRADE
SCHEDULE
SECTION
SIMILAR
SPECIFICATIONS
STIFFENER
STRUCTURAL
SHORT WAY BOTTOM
TOP AND BOTTOM
TOP
TOP OF
TOP OF CONCRETE
TOP OF STEEL
THICKENED SLAB
TOP CHORD EXTENSION LEFT END
TOP CHORD EXTENSION RIGHT END
TURN DOWN SLAB
THICK OR THICKENED
TYPICAL
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
VERTICAL
WOOD ROOF TRUSS
WITH
WELDED WIRE FABRIC
EWT EACH WAY TOP
P/C PRECAST
P.A.F. POWDER ACTUATED FASTENER
BP_ BEARING PLATE
GB_ GRADE BEAM
k KIP k-ft KIP-FEET
MP_ MASONRY PIER
NBL NON BEARING LINTEL
WP WALL PLATE
WC WET COLUMN
Ø
GENERAL POOL STRUCTURAL NOTESGENERAL POOL STRUCTURAL NOTES
PG1. Building Codes:
Model: International Building Code 2018
Concrete: American Concrete Institute ACI 318-14 American Concrete Institute ACI 350-06
PG2. The construction documents indicate design of a completed reinforced concrete structure.
The structural details have been prepared based on cast-in-place concrete methods. If alternate means and methods of concrete placement are employed that may alter the completed project, the contractor must submit proposed revisions and signed/sealed calculations to the Architect/Engineer for approval prior to fabrication or construction.
PG3. The pool structure renovations have been designed to withstand all anticipated loadings under both full and empty conditions in accordance with the criteria of ACI 350.
PG4. The pool shell renovations have not been designed to withstand any surcharge loading from adjacent structures. Inform engineer immediately if adjacent structures are close to the pool shell.
PG5. Adequacy of the existing pool shell elements have not been evaluated and are not covered in the scope of these construction documents.
REINFORCED CONCRETE NOTESREINFORCED CONCRETE NOTES
PC1. Pool shell modifications to be cast-in-place concrete.
PC2. All concrete shall be 4000 psi minimum 28 day compressive strength with 6% air entrainment. Limit water to cementitious material ratio (w/c) to 0.42.
PC3. All reinforcing steel shall be detailed, supplied and placed in accordance with these construction documents and with ACI 318-05, ACI 315-05, and CRSI MSP-1-01.
PC4. All reinforcing steel shall be shop fabricated to conform to ASTM A615, Grade 60.
PC5. All pool concrete shall be "wet" cured using hoses and polyethylene covering.
PC6. Reinforcing clearance: 2" Pool walls, surge tank walls 2" Pool bottom slabs, surge tank slabs 3" All surfaces cast or shot against earth
1 1/2" CLR. TYP.
SEE PLAN FOR
ACTUAL REINF.
#4 x 1'-6"
#4 x 1'-6"
1/ 2" C
LR
T Y P
TYPICAL REINF. AT EMBEDDED ITEMS
5/8"
49 BAR DIA. LAP
3'-0" 3'-0"
4"
2" C
LR
2" C
LR
ALL HORIZONTAL REINF. IS
CONT. THRU JOINT POOL SIDEPOOL SIDE
WATERPROOF SEALANT
6" RIBBED PVC
WATERSTOPMATCH WALL
REINFORCING
SIZE & SPACING
8" WALL8" WALL
12" AND THICKER WALL12" AND THICKER WALL
TYP. CONCRETE WALL CONSTRUCTION JOINT
5/8"
49 BAR DIA. LAP
2" C
LR
ALL HORIZONTAL REINF. IS
CONT. THRU JOINT POOL SIDEPOOL SIDE
WATERPROOF SEALANT
6" RIBBED PVC
WATERSTOPMATCH WALL
REINFORCING
SIZE & SPACING
2" C
LR
5/8"
40 BAR DIA. LAP
3'-0" 3'-0"
4" 8"
2" C
LR
2" C
LR
ALL HORIZONTAL REINF. IS
CONT. THRU JOINT POOL SIDEPOOL SIDE
WATERPROOF SEALANT
6" RIBBED PVC
WATERSTOPMATCH SLAB
REINFORCING
SIZE & SPACING
8" SLAB8" SLAB
12" AND THICKER SLAB12" AND THICKER SLAB
TYP. CONCRETE SLAB CONSTRUCTION JOINT
5/8"
40 BAR DIA. LAP
2" C
LR
ALL HORIZONTAL REINF. IS
CONT. THRU JOINT POOL SIDEPOOL SIDE
WATERPROOF SEALANT
6" RIBBED PVC
WATERSTOPMATCH SLAB
REINFORCING
SIZE & SPACING
2" C
LR
T H
IC
K N E S S
BAR DEVELOPMENT & BAR DEVELOPMENT &
SPLICE LENGTHSSPLICE LENGTHS
BAR
TENSION
DEVELOPMENT
SPLICES
* USE TOP BAR LENGTHS WHEN BARS ARE
PLACED SUCH THAT THERE IS MORE THAN
1'-0" OF CONCRETE BELOW BAR
#3
#4
#5
#6
#7
#8
#9
#10
#11
18"
24"
30"
35"
51"
59"
66"
74"
82"
14"
18"
23"
27"
40"
45"
51"
57"
64"
23"
30"
38"
49"
67"
76"
86"
96"
107"
8"
24"
30"
35"
51"
59"
66"
74"
82"
TOP BAR* OTHER TOP BAR* OTHER
TYP.
8"
CERTIFIED COVER/GRATE
WITH FRAME AND FASTENERS
(SEE POOL DWGS.)
SEE POOL DRAWINGS FOR
DRAIN DIMENSIONS AND
PIPE CONFIGURATIONS
SEE PLAN FOR BASE
SLAB REINFORCEMENT
SLOPE SLAB TO DRAINSLOPE SLAB TO DRAIN
BUILDING
STRUCTURE
(TYP.) DRAIN
(SEE POOL DWGS.)
8"
1'-0" 1'-0"
#4 x @ 12"
1.
a.
b.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
POOL CONCRETE REPAIRPOOL CONCRETE REPAIR
CONCRETE REPAIR SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING CODES:
THE LATEST ACI BUILDING CODE (ACI 318), THE ACI DETAILING MANUAL (ACI 315),
AND THE SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301).
“CONCRETE REPAIR MANUAL”, AMERICAN CONCRETE INSTITUTE AND INTERNATIONAL
CONCRETE REPAIR INSTITUTE, 4th EDITION
PRIOR TO SUBMITTING BID, VERIFY REPAIR TYPES, EXTENTS OF REPAIRS, QUANTITY
OF REPAIRS, AND LOCATIONS INDICATED. REFERENCE TYPICAL AND ATYPICAL REPAIR
DETAILS.
PROBE AND SOUND CONCRETE SURFACES TO VERIFY EXTENT OF REQUIRED REPAIRS.
DURING AND AFTER DEMOLITION, PERFORM SUPPLEMENTAL PROBES, SOUNDING, AND
EVALUATION TO DETERMINE ALL DELETERIOUS OR DEFICIENT MATERIAL IS REMOVED.
AREAS WITH MINERAL DEPOSITS SHALL BE CLEANED AND CONCRETE REPAIRS SHALL BE
MADE AS DICTATED BY EXPOSED FIELD CONDITIONS.
PERFORM ALL SURFACE PREPARATION, APPLICATION, FINISHING, AND CURING IN STRICT
ACCORDANCE WITH THE PRODUCT MANUFACTURER ’S RECOMMENDATIONS AND
REQUIREMENTS.
REMOVE UNBONDED PAINT AND COATING MATERIALS FROM CONCRETE AT REPAIR
LOCATIONS TO ALLOW SOUNDING OF CONCRETE.
REMOVE UNSOUND, LOOSE AND/OR DELAMINATED CONCRETE/AGGREGATE DOWN TO
SOUND MATERIAL.
NOTIFY DESIGN TEAM TO SCHEDULE INSPECTIONS OF THE PREPARED SURFACES PRIOR
TO PLACING REPAIR MATERIAL. REINFORCING SHALL BE SPLICED AS APPROVED BY
THE DESIGN TEAM.
REPAIR AREAS SHOULD EXTEND A MINIMUM OF 6 INCHES BEYOND THE ACTUAL
DELAMINATED CONCRETE. SAWCUT AT PERIMETER OF DELAMINATED AREAS AS
INDICATED IN NOTES AND/OR ON DOCUMENTS.
MINIMIZE AND AVOID REPAIR CONFIGURATIONS WITH RE-ENTRANT CORNERS. REPAIR
CONFIGURATIONS SHALL BE KEPT AS SIMPLE AS POSSIBLE, PREFERABLY SQUARE OR
RECTANGULAR WITH SQUARE (90 DEGREE) CORNERS. PROVIDING ADEQUATE REPAIR
CONFIGURATIONS MAY RESULT IN THE REMOVAL OF SOUND CONCRETE. VERIFY
REMOVAL CONFIGURATIONS WITH DESIGN TEAM PRIOR TO PREPARING FOR REPLACEMENT
OF MATERIALS.
UNDERCUT EXPOSED REINFORCING STEEL. PROVIDE A MINIMUM OF 3/4 INCH CLEARANCE
BETWEEN EXPOSED REINFORCING AND SURROUNDING CONCRETE OR 1/4 INCH LARGER
THAN THE COARSE AGGREGATE OF THE REPAIR MATERIAL, WHICHEVER IS LARGER.
USE CRSI-APPROVED CHAIRS, ETC., AS NECESSARY. SOUND CONCRETE MAY HAVE TO
BE REMOVED TO PROVIDE PROPER CLEARANCE AROUND REINFORCING STEEL.
CONCRETE REMOVAL SHALL EXTEND ALONG THE REINFORCING STEEL UNTIL THERE IS NO
DELAMINATION, CRACKING, OR SIGNIFICANT CORROSION AND THE REINFORCING STEEL IS
WELL BONDED TO SURROUNDING CONCRETE.
PROVIDE UNIFORM HORIZONTAL SURFACE DEPTH OF DEMOLITION BETWEEN ADJACENT
BARS OR WIRES WHEN CAVITY ENCOMPASSES MORE THAN ONE BAR OR WIRE TO
REDUCE SHRINKAGE CRACKING AT THESE LOCATIONS.
PREPARE SUBSTRATE AND PROVIDE CONCRETE SURFACE PROFILE IN ACCORDANCE WITH
REPAIR MATERIAL MANUFACTURER GUIDELINES.
NOTIFY ENGINEER WHEN REINFORCING STEEL HAS LOST CROSS SECTIONAL AREA LARGER
THAN 10%. REPAIR DAMAGED/DETERIORATED REINFORCING STEEL BY REPLACEMENT
WITH COMPATIBLE REINFORCEMENT OF EQUIVALENT SIZE, SHAPE, AND STRENGTH OR
ADDING EQUIVALENT ADDITIONAL REINFORCEMENT TO MATCH THE SAME CROSS-
SECTIONAL AREA.
PROVIDE PROPOSED REPAIR MATERIALS FOR REVIEW AND APPROVAL PRIOR TO
PURCHASE OR APPLICATION OF MATERIALS.
SHAPE AND FINISH REPAIRS TO MATCH EXISTING SURFACES. IF A COATING IS TO BE
APPLIED, COORDINATE FINISHING TECHNIQUES WITH COATING MANUFACTURER
REQUIREMENTS. CONCRETE REPAIRS IN COATED SURFACES SHALL BE COATED TO
MATCH ADJACENT AREAS
AFTER APPLYING REPAIR MATERIAL, AND AFTER CURING, PERFORM ASTM C1583
TENSILE TESTING OF REPAIRS TO VERIFY BOND OF REPAIRS.
CHIP CONCRETE AS REQUIRED
TO REMOVE STEEL RING - DO
NOT CUT REINFORCING STEEL
CONT. SYNKO-FLEX
WATERSTOP AROUND
PERIMETER OF
OPENING
(4) #3 AT QUADRANTS OF
OPENING EMBED 3" INTO
EXIST. CONC. w/ HILTI
HIT-HY 200 V3 ADHESIVE
INFILL WITH 4,000
PSI NON-SHRINK
CEMENTITOUS
GROUT
APPLY CORROSION INHIBITOR
TO ANY EXPOSED
REINFORCING STEEL AND
PATCH CHIPPED AREAS
PRIOR TO INFILL
TYPICAL LIGHT NICHE INFILL
450 EAST 96th STREET SUITE 175
INDIANAPOLIS, INDIANA 46240
PHONE: 317.580.0402
WWW.O-N.COM
ph: 314.894.1245 www.chh2o.com
COUNSILMAN HUNSAKER
AQUATICS FOR LIFE
8910 Purdue Road, Suite 320 Indianapolis, IN 46268 Phone: 317.931.9800
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project : 23022.018
DESIGNER OF RECORDCONSULTANT
U.S. Department of Veterans Affairs
7020.0280.00 GSN KLS
100% Construction Documents 06/20/2025
Au to de sk
D oc s:
//7
0.
.0 0/
.0
0.
-S tru ct O
N -2
4.
rv t
8/
/2
9:
:0
AM
QA101
POOL STRUCTURAL NOTES AND
DETAILS
B132 POOL AND HVAC
REPLACEMENT
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-122
06/20/2025
100% Construction Documents
Detail
QA101
1 Detail
QA101
2 Detail
QA101
Section
QA101
Revisions: Date:
Addendum #2 08/20/2026
Detail
QA101
06-18-2025
EXP: 11-30-2026
FIRM NO. 184-004792-0003
File details come from the government source that posted it. Updated .