S. CBOC Room Data Sheets.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24525R0070
About this file
This is a room data sheet document for the Hagerstown CBOC (Community Based Outpatient Clinic) lease RFP, detailing the technical specifications for various rooms in the planned VA medical facility. The document provides comprehensive specifications for 66+ rooms including exam rooms, offices, storage areas, toilets, and corridors. For each room, it specifies architectural requirements (flooring, walls, ceiling height, doors), HVAC requirements, plumbing and medical gas specifications, electrical/lighting requirements (lighting levels, outlet types, emergency lighting), and communications infrastructure needs.
Key details include requirements for medical exam rooms with specific sink and plumbing configurations, sound-insulated walls (STC 42), specialized rooms for audiology with sound booths (Eckles S-123 LP2 Model), eye clinic lanes from Eye-Designs, and nurse call systems throughout clinical areas. The facility requires multiple security features including card readers, 7-PIN IC cores on doors, and emergency lighting. Common specifications across rooms include 9'-0" to 10'-6" ceiling heights, LED lighting (typically 50 FC), data connectivity, and specific flooring materials (LVT-1, ceramic tile CT-1/CT-2 in wet areas). The document is part of RFP No. 36C24525R0070 for a lease procurement by the VA Medical Center in Martinsburg.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Veterans Affairs HAGERSTOWN CBOC Medical Center - Martinsburg LEASE - RFP Name
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 1 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
VESTIBULE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
Recessed mat/CPT-2
WT-1/Storefront
RB-1
WT-2
10’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
(4)3’-0”x 8’-0” (SLIDING), Alum. Storefront
ADO, 7-PIN IC Large Core.
Mag-lock w/ REX at check-in
Aluminum
Thumb-Turn Lock on each door
Notes: Supply/Exhaust grills to be powder coating to be similar to ceiling color
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Notes:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 fc
6” Recessed
Voice:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
LEASE NO. 36C24525L0005
LESSOR________ GOVERNMENT________
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 2 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
WAITING
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1/ LVT-2/ CPT-3
GWB/ WT-3, STC 42
RB
WT-3
10’-0”
SS-1, 6 LF
MW-1, 6 LF
Full height 3FORM glazing panel in front of reception desk, 14 LF
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
8’-0”x3’-0”, SCW, SV-1
7-PIN IC Large Core, Card reader.
HM
As needed
Roller shades at windows
Notes: Supply/Exhaust grills to be powder coating to be similar to ceiling color
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Notes:
EWC w/Bottle Filler w/ Filter on EWC
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
2x2 LED
Dimmable 6” Recessed
Voice:
Data:
Yes
Yes
A/V:
Notes:
COAX/POWER/DATA for ceiling MTD. TV’S
‘Logison’ surface mounted sound masking w/ music/paging module
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 3 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
RECEPTION
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB/ WT-3, STC 42
RB-1
GWB/ WT-3
10’-0”
84 LF, SS-1
24 LF Base, MW-1
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Notes:
3’-0”x 8’-0”, SCW/ SV-1
Office function
7-PIN IC large core
HM
3M Staggered glazing along desk w/ top hung sliding glass panels, lockable.
Notes: Supply/Exhaust grills to be powder coating to be similar to ceiling color
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
Single tube LED
Bulkhead continuous cove lighting
Tube LED to sit within slat ceiling system
Voice:
Data:
Yes
Yes
A/V:
Notes:
‘Logison’ surface mounted sound masking w/ music/paging module
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 4 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
RECEPTION SUPPORT
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
103A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
GWB/ WT-3
10’-0”
24 LF, SS-1
24 LF Base/ Upper, MW-1
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Notes:
3’-0”x 8’-0”, SCW/ SV-1
Office function, Card reader
7-PIN IC large core
HM
Notes: Supply/Exhaust grills to be powder coating to be similar to ceiling color
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
Single Tube LED
Tube LED to sit within slat ceiling system
Voice:
Data:
Yes
Yes
A/V:
Notes:
‘Logison’ surface mounted sound masking w/ music/paging module
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 5 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
PT/OT
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB
ACT-1
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, Card reader 7-PIN IC Large core
HM
Roller shades at window.
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
2x2 LED
6” Recessed
All lights to be dimmable
Voice:
Data:
Yes
A/V:
Notes:
Coax at TV Location
‘Logison’ surface mounted sound masking w/ music/paging module
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 6 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
PT/OT EXAM ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
104A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB
ACT-1
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
2x2 LED
6” Recessed
All lights to be dimmable
Voice:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 7 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
PT/OT STORAGE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
104B
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Storage function, 7-PIN IC Large core
HM
Notes: -
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
2x2 LED
Lights on motion sensor
Voice:
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 8 of 80
NET AREA:
HAGERSTOWN CBOC
MH GROUP ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
10 LF, SS-1
10 LF, Base/ MW-1
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storeroom function, Card Reader 7-PIN IC Large Core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes, Stainless Steel, Deep
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
6” Recessed
All lights to be dimmable
Data:
Yes
A/V:
Notes:
Coax at TV Location
‘Logison’ surface mounted sound masking w/ music/paging module
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 9 of 80
NET AREA:
HAGERSTOWN CBOC
MH GROUP RM, STORAGE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
105A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
(2) 3’-0”x 8’-0”, SCW/ VT-1
Storeroom function, 7-PIN IC Large Core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 10 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
WOMENS TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Push/ Pull Plates
HM
Frameless mirror above sinks
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
6” RECESSED
Trough light along wet wall, sconce fixtures at mirrors
Nurse call dome light outside of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 11 of 80
NET AREA:
HAGERSTOWN CBOC
MENS TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Push/ Pull Plates
HM
Frameless mirror above sinks
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes
6” RECESSED
Trough light along wet wall, sconce fixtures at mirrors
Nurse call dome light outside of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 12 of 80
NET AREA:
HAGERSTOWN CBOC
LAB
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
18 LF, SS-1
18 LF Upper/Base, MW-1
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Note:
Yes
Handsfree eye-wash station at one sink
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 13 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
LAB TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
108A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-1/CT-2, STC 42
CERAMIC TILE, CT-1
GWB
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
BATHROOM FUNCTION
HM
Mirror above sink
Stainless steel specimen pass-thru at wall
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
6” Recessed
Scone at mirror
Nurse call dome light outside of room
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 14 of 80
NET AREA:
HAGERSTOWN CBOC
SOCIAL WORK
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
3’-0”X’-8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Roller shades at windows
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Shower:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
All lighting dimmable
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
ROOM DATA SHEET 613-LS-200
HAGERSTOWN CBOC LEASE- RFP Page 15 of 80 12/02/24
ARCHITECTURAL
HVAC (HEATING/ VENTILATION/ AIR CONDITIONING)
PLUMBING AND MEDICAL GASES
ELECTRICAL POWER AND LIGHTING
COMMUNICATIONS
DEPARTMENT:
ROOM NAME:
NET AREA:
HAGERSTOWN CBOC
PSYCHOLOGIST
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Door Size & Type:
Door Hardware:
Frame:
Fire Rating:
Furnishings:
Notes:
3’-0”X’-8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Roller shades at windows
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Shower:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Emergency Lighting/Exit:
Yes
Lighting Level:
General Lights:
Accent Lights:
Power Notes:
Lighting Notes:
50 FC
2x2 LED
6” Recessed
All lighting dimmable
Voice:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 16 of 80
NET AREA:
HAGERSTOWN CBOC
PCMHI
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Office function 7-PIN IC Large core
HM
Roller shades at windows
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Shower:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 17 of 80
NET AREA:
HAGERSTOWN CBOC
TELE-PSYCH
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Office function 7-PIN IC Large core
HM
Roller shades at windows
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Shower:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 18 of 80
NET AREA:
HAGERSTOWN CBOC
TELE MH
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE,CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Office function 7-PIN IC Large core
HM
Roller shades at windows
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Shower:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 19 of 80
NET AREA:
HAGERSTOWN CBOC
TELE-CVT
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
3 LF, SS-1
2 LF DIRTT, PPE/ VT-1
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Notes - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 20 of 80
NET AREA:
HAGERSTOWN CBOC
TELE-PODIATRY
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Notes - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 21 of 80
NET AREA:
HAGERSTOWN CBOC
TELE-RETINAL
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Notes - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 22 of 80
NET AREA:
HAGERSTOWN CBOC
SCALE ALCOVE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Recessed floor scale
Furnishings:
Notes:
Floor scale shall be ‘Cardinal’ solace in-floor
Notes - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 23 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
Card reader
Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Hinge actuated light
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 24 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 25 of 80
NET AREA:
HAGERSTOWN CBOC
SCALE ALCOVE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Recessed floor scale
Furnishings:
Notes:
Floor scale shall be ‘Cardinal’ solace in-floor
Notes - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 26 of 80
NET AREA:
HAGERSTOWN CBOC
MENS TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/ vacant-occupied indicator
Soap, paper towel, toilet paper dispenser
Frameless mirror above sink
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes
Sconce light at mirrors
Nurse call dome light outside of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 27 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/ paper dispenser
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 28 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 29 of 80
NET AREA:
HAGERSTOWN CBOC
BIO-MED CLOSET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 30 of 80
NET AREA:
HAGERSTOWN CBOC
PHARMACIST OFFICE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 31 of 80
NET AREA:
HAGERSTOWN CBOC
HUDVASH/HBPC
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 32 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
126A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 33 of 80
NET AREA:
HAGERSTOWN CBOC
OIT
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
Sealed concrete
GWB
RB-1
GWB
10’-0”
8’ high plywood on 3 walls
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core, closer
HM
CARD READER/KEYPAD
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Power for components to be located on rack.
Voice:
Data:
Yes
Yes
A/V:
Notes:
Cable tray above rack
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 34 of 80
NET AREA:
HAGERSTOWN CBOC
COORDINATOR OFFICE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 35 of 80
NET AREA:
HAGERSTOWN CBOC
HOTELING OFFICE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 36 of 80
NET AREA:
HAGERSTOWN CBOC
HOTELING/ INTERN OFF.
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 37 of 80
NET AREA:
HAGERSTOWN CBOC
DIETICIAN OFFICE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SWC/ VT-1
Office function, 7-PIN IC Large core
HM
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes, small
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 38 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 1
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 39 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM ROOM 2
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 40 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM 2 -TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
133A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 41 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM ROOM 3
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 42 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM 3 -TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
134A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 43 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 4
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 44 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM ROOM 5
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 45 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM 5 -TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
136A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 46 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM ROOM 6
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 47 of 80
NET AREA:
HAGERSTOWN CBOC
WOMENS EXAM 6 -TOILET
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
137A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CT-2/ CT-3, STC 42
CERAMIC TILE
GWB
9’-0”
Bathroom function w/
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes of room.
Voice:
Data:
Nurse call
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 48 of 80
NET AREA:
HAGERSTOWN CBOC
PACT TEAM 1 & 2
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Card reader
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
6’ L indirect pendants
Data:
Yes
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 49 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
138A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
Carpet Tile, CPT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
(2) 3’-0”x 8’-0”, SCW/ VT-1
Top hung sliding doors
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 50 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 7
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 51 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 8
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 52 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 9
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 53 of 80
NET AREA:
HAGERSTOWN CBOC
MEDICATION ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
CARD READER
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Motion sensor
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 54 of 80
NET AREA:
HAGERSTOWN CBOC
SPD STORAGE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
CARD READER
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 55 of 80
NET AREA:
HAGERSTOWN CBOC
CLEAN UTILITY STORAGE
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function 7-PIN IC Large core
HM
CARD READER
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 56 of 80
NET AREA:
HAGERSTOWN CBOC
SOILED UTILITY ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CERAMIC TILE, CT-1
CERAMIC TILE, CT-2
CERAMIC TILE
GWB
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Storage function, 7-PIN IC Large core
HM
CARD READER
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Yes
Motion sensor
Voice:
Data:
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 57 of 80
NET AREA:
HAGERSTOWN CBOC
PACT TEAM 3
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Office function 7-PIN IC Large core
HM
Card reader
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria.
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
6’ L indirect pendants
Data:
Yes
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 58 of 80
NET AREA:
HAGERSTOWN CBOC
STORAGE ROOM
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
146A
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
CARPET TILE, CPT-1
GWB
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
(2) 3’-0”x 8’-0”, SCW/ VT-1
Top hung sliding doors
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
EXHIBIT S
RLP NO. 36C24525R0070
HAGERSTOWN CBOC LEASE- RFP Page 59 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 10
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Data:
Yes
A/V:
Notes:
HAGERSTOWN CBOC LEASE- RFP Page 60 of 80
NET AREA:
HAGERSTOWN CBOC
EXAM ROOM 11
- NSF
PROJECT NUMBER:
ROOM NUMBER:
OCCUPANCY LOAD:
613-LS-200
Floor:
Wall:
Base:
Ceiling:
Ceiling Height:
Countertops:
Cabinets:
Specialties:
LVT-1
GWB, STC 42
RB-1
ACT-1
9’-0”
Furnishings:
Notes:
3’-0”x 8’-0”, SCW/ VT-1
Thumb Turn 7-PIN IC Large core
Aluminum
Door Assa-Abloy, Slide-Rite
Notes: - Design Notes: Refer VA HVAC Design Manual for design criteria
Cold Water:
Hot Water:
Lab Air (Hi-Lo):
Lab Vacuum:
Sanitary Drain:
Deionized Water:
Yes
Yes
Yes
Medical air:
Medical Vacuum:
Oxygen:
Natural Gas:
Lavatory:
Water Closets:
Yes
Duplex Receptacle:
Special Receptacle:
GFI Receptacle:
Clock Receptacle:
Isolated Circuit:
Power No
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .