Academic Village Cooling Tower
Solicitation number
PSPW-25-10
Issued by
Broward County, Florida

About this file

This document is a structural engineering design sheet (S-1.0) for the Academic Village Cooling Tower Replacement project for the City of Pembroke Pines, located at 8300 South Palm Road in Pembroke Pines, Florida. The sheet provides detailed technical specifications for concrete restoration and removal geometry, including ground level plans, anchor placement details, and repair strategies for various structural elements such as corner walls, side walls, and top of slab areas. The design is prepared by J. Marc Sauve, a licensed Professional Engineer in Florida, and focuses on the replacement of existing cooling towers that have reached the end of their functional lifecycle.

The engineering document includes specific technical details for concrete restoration, with bid quantities listed for walls measuring 1 to 4 feet in length. The sheet provides comprehensive repair procedures, including notes on demolition methods, concrete preservation techniques, and structural reinforcement strategies. The drawings illustrate multiple view perspectives including ground level plans, anchor placement details, and cross-sectional views of proposed repair work. The technical specifications aim to guide contractors in executing a precise and systematic approach to replacing the cooling tower infrastructure while maintaining structural integrity and adherence to applicable building codes.

View the file

Other files

File Type Posted
Academic_Village_Cooling_Tower_(Addendum_#6_Revision).pdf PDF
1000_Ton_Cooling_Tower_RSCT1000F2_Spec_Sheet_Draft(Reymsa).pdf PDF
Sikagard_7600_VG.pdf PDF
Pictures.pdf PDF
Academic_Village_Cooling_Tower.pdf PDF
Standard_Release_of_Lien.pdf PDF
Standard_Release_of_Lien.pdf PDF
Sample_Insurance_Certificate.pdf PDF
Specimen_Contract_-_Construction_Agreement.pdf PDF
Sample_Insurance_Certificate.pdf PDF
Specimen_Contract_-_Construction_Agreement.pdf PDF
Attachment_A_-_Cooling_Tower_Specifications_&_Instructions.pdf PDF
Attachment_B_-_Plans.pdf PDF
Attachment_A_-_Cooling_Tower_Specifications_&_Instructions.pdf PDF
Attachment_B_-_Plans.pdf PDF
S-1.0.pdf PDF
S-0.0.pdf PDF
S-0.0.pdf PDF
M-1-DEMOLITION_PLAN.pdf PDF
M-1-DEMOLITION_PLAN.pdf PDF
M-2-MECHANICAL_FLOOR_PLAN.pdf PDF
M-2-MECHANICAL_FLOOR_PLAN.pdf PDF
Cooling_Tower_Instructions.pdf PDF
Cooling_Tower_Instructions.pdf PDF
Submittal_Package_Merged_Quote090609_-_Revision_002_Line_100_-S3E_-_S3E-1222-06N-2_2025-03-04_13-22_EN.pdf PDF
Submittal_Package_Merged_Quote090609_-_Revision_002_Line_100_-S3E_-_S3E-1222-06N-2_2025-03-04_13-22_EN.pdf PDF
Specimen_Contract_-_Contractual_Services_Agreement.pdf PDF
Specimen_Contract_-_Professional_Services_(CCNA_Non-Continuing_Services).pdf PDF
HUD's_Davis-Bacon_and_Labor_Standards_Contractor_Guide_Addendum.pdf PDF
HUD's_Davis-Bacon_and_Labor_Standards_Contractor_Guide_Addendum.pdf PDF
Specimen_Contract_-_Professional_Services_(CCNA_Non-Continuing_Services).pdf PDF
Specimen_Contract_-_Contractual_Services_Agreement.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FL, PE # 57585

J Sauve, P.E.

FL, CA # 30123

TO

T H E

BE

ST

O F

TH

E

EN

G

IN

EE

R S

KN

O W

LE

D G E, T H

ES

E

PL

AN

S

AN

D

SP

EC

IF

IC

AT

IO

N S C O M

PL

Y W

IT

H T H E

AP

PL

IC

AB

LE

M

IN

IM

U M B U

IL

D

IN

G C O D

ES

STRUCTURAL ENGINEERS

5397 Orange Drive.

Suite 203 Davie, FL 33314 Ph: (954) 316-9001 J. Marc Sauve, State of Florida, Professional Engineer, License No. 57585. This item has been digitally signed by J Marc Sauve, P.E. on the date indicated here using a SHA authentication code. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED! This digital signature and the SHA authentication code must be verified on any electronic copies.

DRAWN BY:

CHECKED BY:

PROJECT NUMBER:

ISSUE DATE:

REV DATE DESCRIPTION

DESIGN

DELIVERABLE:

SHEET TITLE

SHEET TITLE

S-1.0

Ac ad em ic Vi lla ge

C oo lin g T ow er R ep lac em en t

C ity o f P em br ok e Pi ne s

S ou th P al m R oa d Pe m br ok e Pi ne s, F lo rid a

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

SECTION THROUGH

AutoCAD SHX Text

CONCRETE MEMBER

AutoCAD SHX Text

OXIDIZED (CORRODED) BARS

AutoCAD SHX Text

3/4" MIN. CLEARANCE REFER TO NOTE #7

AutoCAD SHX Text

UNOXIDIZED & TIGHTLY BONDED BARS, REFER TO NOTE #9.

AutoCAD SHX Text

PREPARED CONCRETE SURFACE TO RECEIVE PATCH. SEE MANUF. SPECIFICATION

AutoCAD SHX Text

%%UGENERAL REMOVAL GEOMETRY AND NOTES

AutoCAD SHX Text SAW-CUT 1/4" - 1/2" DEEP AND AS PER MANUF. RECOMMENDATIONS ALONG REPAIR AREA TYP.

AutoCAD SHX Text

2" OF "GOOD" UNCORRODED REINF. BAR BEYOND POINT OF CORROSION /SCALY RUST

AutoCAD SHX Text

SEPARATE BARS 1/4" AND CLEAN CONTACT AREA

AutoCAD SHX Text

1. ALL TILE/TOPPING SHALL BE REMOVED PRIOR TO CONCRETE RESTORATION BEGINS ON SLABS OR BEAMS. ALL TILE/TOPPING SHALL BE REMOVED PRIOR TO CONCRETE RESTORATION BEGINS ON SLABS OR BEAMS. 2. TOP OF SLAB REPAIRS WITH AN OVERHEAD SLAB REPAIR DIRECTLY UNDERNEATH SHALL BE REMOVED AS A TOP OF SLAB REPAIRS WITH AN OVERHEAD SLAB REPAIR DIRECTLY UNDERNEATH SHALL BE REMOVED AS A FD REPAIR. 3. CRACKS THROUGH STRUCTURAL ELEMENTS THAT HAVE NO VISIBLE RUST/CORROSION BLEEDING FROM THEM OR CRACKS THROUGH STRUCTURAL ELEMENTS THAT HAVE NO VISIBLE RUST/CORROSION BLEEDING FROM THEM OR SPALLS SHALL BE SEALED BY EPOXY INJECTION. 4. COLUMN REPAIRS: A MAXIMUM 4" X 4" X FULL HEIGHT REPAIR MAY BE PERFORMED WITHOUT SHORING THE COLUMN REPAIRS: A MAXIMUM 4" X 4" X FULL HEIGHT REPAIR MAY BE PERFORMED WITHOUT SHORING THE COLUMN UNLESS RECOMMENDED BY A PROFESSIONAL ENGINEER. 5. REMOVE LOOSE OR DELAMINATED CONCRETE ABOVE OXIDIZED REINFORCING STEEL. ONCE INITIAL REMOVALS REMOVE LOOSE OR DELAMINATED CONCRETE ABOVE OXIDIZED REINFORCING STEEL. ONCE INITIAL REMOVALS ARE MADE, PROCEED WITH THE UNDERCUTTING OF ALL EXPOSED OXIDIZED (CORRODED) BARS. UNDERCUTTING WILL PROVIDE CLEARANCE FOR UNDER BAR CLEANING, FULL BAR CIRCUMFERENCE BONDING TO SURROUNDING CONCRETE, AND WILL SECURE THE PATCH STRUCTURALLY. 6. PROVIDE MINIMUM 3/4" CLEARANCE BETWEEN EXPOSED REARS AND SURROUNDING CONCRETE OR 1/4" LARGER PROVIDE MINIMUM 3/4" CLEARANCE BETWEEN EXPOSED REARS AND SURROUNDING CONCRETE OR 1/4" LARGER THAN LARGEST AGGREGATE IN REPAIR MORTAR, WHICH EVER IS GRATER. 7. CONCRETE REMOVALS SHALL EXTEND ALONG THE BARS TO LOCATIONS ALONG THE BAR FREE OF BOND CONCRETE REMOVALS SHALL EXTEND ALONG THE BARS TO LOCATIONS ALONG THE BAR FREE OF BOND INHIBITING CORROSION, AND WHERE THE BAR IS WELL BONDED TO SURROUNDING CONCRETE. 8. IF UNOXIDIZED REINFORCING STEEL IS EXPOSED DURING THE UNDERCUTTING PROCESS, CARE SHALL BE TAKEN IF UNOXIDIZED REINFORCING STEEL IS EXPOSED DURING THE UNDERCUTTING PROCESS, CARE SHALL BE TAKEN NOT TO DAMAGE THE BAR'S BOND TO SURROUNDING CONCRETE. IF BOND BETWEEN BAR AND CONCRETE IS BROKEN, UNDERCUTTING OF THE BAR SHALL BE REQUIRED. 9. ALL SCALE AND HEAVY RUST SHALL BE REMOVED FROM REBAR BY BLAST CLEANING PRIOR TO APPLICATION ALL SCALE AND HEAVY RUST SHALL BE REMOVED FROM REBAR BY BLAST CLEANING PRIOR TO APPLICATION OF REPAIR MORTAR. 10. REINFORCING STEEL THAT HAS LOST MORE THAN 25% OF IT'S ORIGINAL CROSS SECTION (20% IF TWO OR MORE REINFORCING STEEL THAT HAS LOST MORE THAN 25% OF IT'S ORIGINAL CROSS SECTION (20% IF TWO OR MORE CONSECUTIVE PARALLEL BARS ARE AFFECTED), SHALL HAVE A NEW BAR ADDED NEXT TO IT WITH 30 BAR DIAMETERS LAP EXTENDING BEYOND CORRODED AREA IN QUESTION (EPOXY DOWEL MAY BE USED IF ADEQUATE SPLICE LENGTH IS NOT AVAILABLE.). 11. UPON COMPLETION OF THE ABOVE PREPARATION PROCEDURES AND PRIOR PLACEMENT OF REPAIR MORTAR, UPON COMPLETION OF THE ABOVE PREPARATION PROCEDURES AND PRIOR PLACEMENT OF REPAIR MORTAR, A REPRESENTATIVE FROM CSW STRUCTURAL ENGINEERS SHALL INSPECT THE PREPARED AREAS. 12. NO CONCRETE REPAIRS ARE PERMITTED WITHOUT AN ACCURATE MEASURING DEVICE USED TO ADD ANY WATER NO CONCRETE REPAIRS ARE PERMITTED WITHOUT AN ACCURATE MEASURING DEVICE USED TO ADD ANY WATER TO MIXES. ALL MORTAR/CONCRETE WITH WATER CONTENT IN EXCESS OF THE MANUFACTURER RECOMMENDATIONS SHALL BE REJECTED. 13. THE FOLLOWING PRODUCTS SET THE STANDARD FOR CONCRETE RESTORATION. NO SUBMITTAL IS REQUIRED THE FOLLOWING PRODUCTS SET THE STANDARD FOR CONCRETE RESTORATION. NO SUBMITTAL IS REQUIRED FOR THESE PRODUCTS: A. MASTEREMACO P 124- BONDING AGENT A. MASTEREMACO P 124- BONDING AGENT MASTEREMACO P 124- BONDING AGENT MASTEREMACO N425 (GEL PATCH) - FOR VERTICAL & OVERHEAD REPAIRS MASTEREMACO N425 (GEL PATCH) - FOR VERTICAL & OVERHEAD REPAIRS MASTEREMACO T302 - HORIZONTAL REPAIRS FROM 1/8" TO 2" THICK MASTEREMACO T302 - HORIZONTAL REPAIRS FROM 1/8" TO 2" THICK SIKAEMACO 440 - HORIZONTAL REPAIRS FROM 2" TO FULL DEPTH SIKAEMACO 440 - HORIZONTAL REPAIRS FROM 2" TO FULL DEPTH CORROSION INHIBITOR FOR VERITCAL & OVERHEAD REPAIRS B. PROVIDE SUBMITTAL-DESIGN MIX: f'c 4,000 PSI MIN; .4 W/C RATION, CORROSION INHIBITING ADMIXTURE, B. PROVIDE SUBMITTAL-DESIGN MIX: f'c 4,000 PSI MIN; .4 W/C RATION, CORROSION INHIBITING ADMIXTURE, 5" SLUMP (+/-1") NOTE: ADMIXTURE MAY BE USED TO ACHIEVE A HIGHER SLUMP. C. RAWL POWER FAST EPOXY FOR REINFORCING EPOXY DOWELS. USE 1" EMBEDMENT MIN PER BAR # C. RAWL POWER FAST EPOXY FOR REINFORCING EPOXY DOWELS. USE 1" EMBEDMENT MIN PER BAR # RAWL POWER FAST EPOXY FOR REINFORCING EPOXY DOWELS. USE 1" EMBEDMENT MIN PER BAR # (#5 BAR REQUIRES 5" EMBEDMENT) 14. REPAIRS SHALL BE FINISHED TO THEIR ORIGINAL CONDITION. REPAIRS SHALL BE FINISHED TO THEIR ORIGINAL CONDITION. A. CONCRETE SHALL HAVE SAME DEPTH, AREA SECTION, AS APPLICABLE A. CONCRETE SHALL HAVE SAME DEPTH, AREA SECTION, AS APPLICABLE CONCRETE SHALL HAVE SAME DEPTH, AREA SECTION, AS APPLICABLE B. STUCCO SHALL BE APPLIED AS REQUIRED B. STUCCO SHALL BE APPLIED AS REQUIRED STUCCO SHALL BE APPLIED AS REQUIRED C. REINFORCING REMOVED FROM STRUCTURAL CONCRETE SHALL BE REPLACED IN ITS ENTIRETY. C. REINFORCING REMOVED FROM STRUCTURAL CONCRETE SHALL BE REPLACED IN ITS ENTIRETY. REINFORCING REMOVED FROM STRUCTURAL CONCRETE SHALL BE REPLACED IN ITS ENTIRETY. MINIMUM SPLICE LENGTH SHALL REMAIN PROTRUDING FROM SLAB TO LAP & TIE WITH NEW STEEL. 15. BEFORE STARTING REMOVALS, PROVIDE SHORING OF ALL MEMBERS REQUIRING REPAIR AS REQUIRED. BEFORE STARTING REMOVALS, PROVIDE SHORING OF ALL MEMBERS REQUIRING REPAIR AS REQUIRED. 16. NOTATION FOR REPAIRS: NOTATION FOR REPAIRS: - EOS = EDGE OF SLAB - EOS = EDGE OF SLAB = EDGE OF SLAB - EP = EPOXY DOWELS = EPOXY DOWELS = EPOXY DOWELS - FD = FULL DEPTH SLAB = FULL DEPTH SLAB - FDB = FULL DEPTH BEAM REPAIR = FULL DEPTH BEAM REPAIR - FDC = FULL DEPTH COLUMN REPAIR = FULL DEPTH COLUMN REPAIR - NR = STAIR NOSING REPAIR = STAIR NOSING REPAIR - OVHD = PARTIAL DEPTH ON UNDER SIDE OF SLAB = PARTIAL DEPTH ON UNDER SIDE OF SLAB - PDB = PARTIAL DEPTH ON BEAM REPAIR = PARTIAL DEPTH ON BEAM REPAIR - PDC = PARTIAL DEPTH COLUMN REPAIR = PARTIAL DEPTH COLUMN REPAIR - PDW = PARTIAL DEPTH WALL REPAIR = PARTIAL DEPTH WALL REPAIR - PO = "POP OUT" - 3" X 3" X 1 1/2" DEEP REPAIR = "POP OUT" - 3" X 3" X 1 1/2" DEEP REPAIR - TOS = PARTIAL DEPTH ON TOP OF SLAB - TOS = PARTIAL DEPTH ON TOP OF SLAB = PARTIAL DEPTH ON TOP OF SLAB 17. COMPLETED REPAIRS THAT ARE HOLLOW SOUNDING OR WITH DEBONDED EDGES OR EDGES THAT HAVE COMPLETED REPAIRS THAT ARE HOLLOW SOUNDING OR WITH DEBONDED EDGES OR EDGES THAT HAVE VISIBLY PULLED AWAY FROM THE EXISTING CONCRETE AFTER CURING SHALL BE REMOVED AND REPLACED AT NO COST TO THE OWNER. 18. ANY QUANTITY WITH GREATER THAN 5% INCREASE OF ORIGINAL CONTRACT AMOUNT SHALL BE APPROVED BY ANY QUANTITY WITH GREATER THAN 5% INCREASE OF ORIGINAL CONTRACT AMOUNT SHALL BE APPROVED BY OWNER AND ENGINEER PRIOR TO PROCEEDING. 19. REPAIR AREAS IN SLAB SHALL NOT EXCEED 4'x4' PER AREA NOR 20% OF AREA BETWEEN COLUMNS WITHOUT REPAIR AREAS IN SLAB SHALL NOT EXCEED 4'x4' PER AREA NOR 20% OF AREA BETWEEN COLUMNS WITHOUT SHORING OR APPROVAL FROM ENGINEER. REPAIR PROCEDURE & INSPECTION SCHEDULE: INSPECTION 1: PRELIMINARY INSPECTION / MEETING WITH CONTRACTOR PRIOR TO START OF CONSTRUCTION. 1: PRELIMINARY INSPECTION / MEETING WITH CONTRACTOR PRIOR TO START OF CONSTRUCTION. 2: REMOVE ALL LOOSE CONCRETE AT ALL MARKED AREAS OR AS INDICATED ON DRAWINGS. IF AREAS IF AREAS ARE NOT MARKED IN FIELD NOTIFY CSW FOR INSPECTION TO MARK AREAS IN NEED OF REPAIR. 3: PERFORM ADDITIONAL CHIPPING IF REQUIRED BY CSW AFTER INSPECTION 2. 4: AFTER STEP TWO AND THREE ARE APPROVED, PROPERLY PREPARE ALL EXISTING CONCRETE SURFACES PER TYPICAL DETAILS AND NOTES. PROPERLY CLEAN ALL EXPOSED REBAR. PROPERLY CLEAN ALL EXPOSED REBAR. 5: FINAL OBSERVATION OF PREPARED AREAS. IF ADDITIONAL CLEANING OR PREPARATION IS REQUIREDIF ADDITIONAL CLEANING OR PREPARATION IS REQUIRED REINSPECTION IS NEEDED. 6: OBSERVATION OF BONDING AGENT APPLIED AS APPLICABLE. OBSERVATION OF BONDING AGENT APPLIED AS APPLICABLE. 7: OBSERVATION OF COMPLETED CONCRETE IN PLACE. ANY UNBONDED OR CRACKED CONCRETE MUSTANY UNBONDED OR CRACKED CONCRETE MUST BE REMOVED AND REPAIRED PER PREVIOUS STEPS.

AutoCAD SHX Text

EXISTING CONC. SLAB

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SEE SECTION 1

AutoCAD SHX Text

EXISTING CONC. SLAB

AutoCAD SHX Text

EXISTING CONC. WALL

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SEE SECTION 1

AutoCAD SHX Text

EXISTING CONC. WALL

AutoCAD SHX Text

TOP OF SLAB REPAIR

AutoCAD SHX Text

TYPICAL DETAIL

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1" = 1'-0"

AutoCAD SHX Text

SEE SECTION 1

AutoCAD SHX Text

AutoCAD SHX Text 1" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 1" = 1'-0"

AutoCAD SHX Text

CORNER WALL REPAIR

AutoCAD SHX Text

TYPICAL DETAIL

AutoCAD SHX Text

SIDE WALL REPAIR

AutoCAD SHX Text

TYPICAL DETAIL

AutoCAD SHX Text

EXISTING CONC. WALL

AutoCAD SHX Text 3/4"~ x8" EMBEDMENT S.S. ADHESIVE ANCHOR. LOCATED PER MANUFACTURER SPECIFICATIONS

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SECTION

AutoCAD SHX Text

AutoCAD SHX Text 1 1/2" = 1'-0"

AutoCAD SHX Text

EXISTING CONC. WALL

AutoCAD SHX Text

NEW COOLING TOWER

AutoCAD SHX Text 24'-2"

AutoCAD SHX Text

AutoCAD SHX Text S-1.0

AutoCAD SHX Text 24"

AutoCAD SHX Text 24"

AutoCAD SHX Text 24"

AutoCAD SHX Text 16"

AutoCAD SHX Text

AutoCAD SHX Text S-1.0

AutoCAD SHX Text

EXISTING CONC. SLAB

AutoCAD SHX Text

EXISTING CONC. WALL

AutoCAD SHX Text 24"

AutoCAD SHX Text 24"

AutoCAD SHX Text S-1.0

AutoCAD SHX Text 4&5

AutoCAD SHX Text 11'-0"

AutoCAD SHX Text 36"

AutoCAD SHX Text

AutoCAD SHX Text S-1.0

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

COOLING TOWER GROUND LEVEL CONCRETE RESTORATION PLAN

AutoCAD SHX Text CONTRACTOR TO SURVEY & AS BUILT SIZE OF CONCRETE SUPPORT THAT BEARS ON COOLING TOWER

AutoCAD SHX Text S-1.0

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S-1.0

AutoCAD SHX Text

NEW CONC. PIER E.A. SIDE

AutoCAD SHX Text

EXISTING WALLS TO REMAIN

AutoCAD SHX Text 24"

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text 1/4" = 1'-0"

AutoCAD SHX Text

COOLING TOWER ANCHORS ATTACHMENT PLAN

AutoCAD SHX Text

EDGE OF NEW COOLING TOWER

AutoCAD SHX Text 21'-6 1/2"

AutoCAD SHX Text 23'-10"

AutoCAD SHX Text

AutoCAD SHX Text S-1.0

AutoCAD SHX Text

CONTRACTOR TO LOCATE BOLTS PRIOR TO PLACEMENT OF NEW COOLING TOWER

AutoCAD SHX Text

MATCH EXISTING

AutoCAD SHX Text

EXISTING WALLS TO REMAIN

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SECTION

AutoCAD SHX Text

AutoCAD SHX Text 1 1/2" = 1'-0"

AutoCAD SHX Text

EXIST. CONC. WALL

AutoCAD SHX Text #3@8"o.c. AS SHOWN EPOXY DOWELED

AutoCAD SHX Text

REMOVE LAITANCE ,ROUGHEN SURFACE TO 3/16" MAGNITUDE

AutoCAD SHX Text

NEW BOLTS LOCATED PER MANUFACTURER SPECIFICATIONS

AutoCAD SHX Text NEW 6000 psi PIER W/ (3)#5 VERT. EPOXY DOWEL W/ 3" EMBEDMENT. PROVIDE HOOK @ TOP OF BARS

AutoCAD SHX Text 3"

AutoCAD SHX Text

WALL

AutoCAD SHX Text C O N C R E T E R E S T A U R A T I O N B I D Q U A N T.

AutoCAD SHX Text T.O.S

AutoCAD SHX Text ; 12'-4"

AutoCAD SHX Text ; 4'-0"

Sheets and Views
S-1.0
2025-07-08T16:14:46-0400
J M Sauve