1000_Ton_Cooling_Tower_RSCT1000F2_Spec_Sheet_Draft(Reymsa).pdf
PDF 643 KB Posted
- Attached to
- Academic Village Cooling Tower
- Solicitation number
- PSPW-25-10
- Issued by
- Broward County, Florida
About this file
This specification sheet outlines the technical specifications for a 1000-ton cooling tower model RSCT1000F2, relevant to the City of Pembroke Pines' cooling tower replacement project at the Pembroke Pines Charter School Academic Village Campus in Florida. The cooling tower features a two-cell induced draft counterflow design with eight fans per cell, direct drive EC fan motors, reinforced fiberglass construction with UV protection, and a seamless cold water basin. Key mechanical specifications include two 8-inch Victaulic inlet connections and two 10-inch Victaulic outlet connections, with a maximum inlet water temperature of 130°F. The unit measures 48 feet 4 inches in length, 8 feet 6 inches in width, and 13 feet 6 inches in height, with an operating weight of 54,600 pounds including trailer. Electrical requirements specify 480V, 3-phase, 60Hz power with a 300-amp circuit breaker style disconnect, minimum circuit ampacity of 180 amps, and maximum overcurrent protection of 280 amps. The tower includes a complete controls package, mechanical float makeup water valve, two 8kW basin heaters, and capabilities for independent or combined cell operation, with sound levels of 75.9 dBA at 5 feet and 60.3 dBA at 30 feet.
The specification sheet includes a cooling capacity table demonstrating performance across various water inlet temperatures (85°F to 130°F), outlet temperatures, wet bulb temperatures (66°F to 80°F), and flow rates ranging from approximately 1,955 to 4,599 gallons per minute. The tower requires minimum clearances of 6 feet front and back and 5 feet on the sides, with the unit not removable from its trailer. Installation features include minimal setup required for quick installation and startup, with water connections available on both sides of the tower and independent cell operation capabilities. This equipment specification directly supports the City of Pembroke Pines' procurement for the Academic Village cooling tower replacement project, which carries an estimated project cost of approximately $448,000 and requires completion within 75 calendar days from the Notice to Proceed.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENTAL SERVICES
1-800-755-5115
1000 Ton Cooling Tower General – RSCT1000F2
Nominal Cooling Tons – 10001
Number of Electrical Circuits – 1
Number of Cells – 2
Number of Fans/Cell – 8 1 – Nominal Cooling Tower Tons are determined at 3 GPM/Ton, 85/95 across tower at 78°F Wetbulb Temperature
Electrical Data – Circuit Breaker Style Disconnect(300 Amp) Voltage – 480V 3 Phase
Frequency – 60Hz
Wire Connection Type – Series 16 Cam Type Only
SCCR – 65000A
Minimum Circuit Ampacity(MCA) – 180A
Maximum Overcurrent Protection(MOP) – 280A
Basin Heater Qty/FLA – (4) 9.63A Each
Fan Motor Qty/FLA – (16) 4.7 Each
Mechanical Data Inlet Connection Qty/Size/Type – (2) 8” Victaulic
Outlet Connection Qty/Size/Type – (2) 10” Victaulic
Make-up Connection Qty/Size/Type – (2) 1 ½” FPT
Drain Connection Qty/Size/Type – (2) 2” FPT
Overflow Connection Qty/Size/Type – (2) 2” FPT
Drive Type – Direct Drive EC Fan
Maximum Inlet Water Temp – 130°F
Features
• Minimal Setup Required for Quick Installation/Startup
• Induced Draft Counterflow
• Complete Controls Package Included
• EC Fan Motors for Capacity Modulation
• Reinforced Fiberglass Construction w/ Permanently Bonded
UV Protection
• Seamless Cold Water Basin
• Water Connections on both sides of tower
• (2) 8kW Basin Heaters
• Cells can run independently of each other or together
• Mechanical Float Make Up Water Valve
Dimension and Weights
Length 48’ 4” Width 8’ 6” Height 13’ 6” Shipping Weight w/ Trailer 30,000 lbs
Operating Weight w/ Trailer 54,600 lbs
Trailer Weight 10,100 lbs
Lifting Device : None – Not removable from trailer
Installed Clearances2
Front/Back – 6’
Sides – 5’ 2Clearances assume three walls surround tower with one open end. See IOM for additional clearances while operating multiple towers in close proximity of each other.
Sound Data Free-Field S.P.L at 5 ft(dBA) – 75.9
Free-Field S.P.L at 30 ft(dBA) – 60.3
Free-Field S.P.L at 50 ft(dBA) – 55.9
RENTAL SERVICES
1-800-755-5115
Cooling Tower Capacity (GPM)
Water Temperature Wet Bulb Temperature (°F) In(°F) Out(°F) 66 68 70 72 75 78 80
95 85 4599 4237 3650 3000 2481 103 85 3679 3483 3274 3052 2687 2273 1955 105 85 3735 3483 3302 3110 2904 2566 2180 120 90 3884 3699 3566 3426 3276 3031 2756 130 90 3341 3229 3110 2982 2771 2553 2354
Unit Drawings
| 1000 Ton CT(RSCT1000F2)_Page_1 |
| 1000 Ton CT(RSCT1000F2)_Page_2 |
File details come from the government source that posted it. Updated .