This file contains a solicitation for roof replacement work at the McAllen Air Traffic Control Tower (ATCT) in McAllen, TX. The project includes multiple components spanning civil/architectural and mechanical work.

The civil/architectural scope includes replacing PVC roof membrane systems on both the Cab Roof and Tower Catwalk, replacing vinyl sidings above and below Cab windows, constructing stud structural framing and Exterior Insulation Finishing System (EIFS), constructing a perimeter foundation beam for EIFS, replacing the front exterior storefront door, reconstructing concrete sidewalk, relocating existing HVAC/electrical utilities and conduits, and abating lead paint at the building entrance and windows. The mechanical scope requires replacing an HVAC packaged unit on the 4th floor, installing a mini split air conditioning unit in the 4th floor Telecom room, and installing a common fresh air intake duct for the CAB HVAC units on the 4th floor. All work must be performed according to provided specifications, drawings, and manufacturer guidelines. The contracting agency is the Department of Transportation Federal Aviation Administration Southwestern Region.

View the file

Other files for this federal contract opportunity

Other files attached to Roof replacement at MFE ATCT (McAllen, TX), newest first.
File Type Posted
697DCK-25-R-00056-0008.pdf PDF
Factor 6 Cost Proposal Breakdown.xlsx XLSX spreadsheet
697DCK-25-R-00056-0007.pdf PDF
Questions and Answers.docx DOCX document
697DCK-25-R-00056-0005.pdf PDF
697DCK-25-R-00056-0004.pdf PDF
697DCK-25-R-00056-0003.pdf PDF
MFE - Revised Specifications 1 of 2.pdf PDF
QA Attachment 01 - Original Drawings part 2 of 2.pdf PDF
QA Attachment 01 - Original Drawings part 1 of 2.pdf PDF
697DCK-25-R-00056-0006.pdf PDF
QA Attachment 02 - PreBid Attendance Sheets.pdf PDF
697DCK-25-R-00056-0002.pdf PDF
697DCK-25-R-00056-0001.pdf PDF
Attachment 01 - Specifications.pdf PDF
697DCK-25-R-00056.pdf PDF
Attachment 01a - Drawings.pdf PDF
Attachment 02 - Wage Determination_TX20230255.pdf PDF
Attachment 04 - Past Performance Questionnaire.pdf PDF
Attachment 03 - Uniform Bipartisan Infrastructure Law Data Report.xlsx XLSX spreadsheet
Attachment 01b - EOSH.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FAA-STD-019G

5.4.6 Interior Wiring, Conductors, and Cables

Permanent single conductors, cables and wiring shall be in ferrous raceway systems, such as RGS conduit, intermediate metal conduit (IMC), electrical metallic tubing (EMT) conduit, cable tray, or wireway, except when prohibited by NEC. Flexible metal conduit (FMC) is permitted when installed in accordance with FAA-C-1217.

Cable tray systems comprising single rail or wire construction are permitted where the installation of conventional ladder cable tray is impractical, provided the cable tray system meets the following requirements:

a. Suitable for use and classified by UL as an EGC.

b. Installed in accordance with manufacturer instructions to maintain the UL classification.

5.4.6.1 Metal-Clad Cable - Type MC

Type MC cable is permitted when installed in accordance with FAA-C-1217 and where all of the following conditions are met:

a. The MC cable shall include a steel armor of interlocking metal tape or sheath construction to form a ferrous magnetic exterior shield. MC cable with an aluminum exterior shield is prohibited.

b. Both ends of the MC cable shall be terminated using UL-listed compression fittings recommended by the OPR of this document.

c. The MC cable shall include a separate internal equipment grounding conductor or wire.

When MC cables are installed in MC cable tray, the following conditions shall be met:

a. The MC cable shall be UL-listed and marked suitable for use in metallic cable tray (hereinafter referred to as MC cable tray).

b. The MC cable tray shall be used exclusively for MC cable and type UL-listed raceways for power distribution.

c. The MC cable tray shall be separated from all other cable trays that transport non-axial communications, signal, and/or control cables or conductors by at least 12 in. The MC cable tray shall not carry more than 90 individual power branch circuits.

d. The MC cable bend radius shall be in accordance with the NEC and cable manufacturer installation instructions, but not less than 8 in.

5.5 Single Point Ground System (SPG) – Special Conditions

5.5.1 General

An SPG shall be provided when required by the electronic equipment or requested by the electronic equipment vendor. FAA facilities that do not use single-point-ground equipment are not required to install an SPG. The SPG shall be isolated from the power grounding system, the lightning protection system, MPG, or SRGG and SRGP systems, except at the main ground plate. The SPG shall be terminated at the main ground plate or to the EES, whichever is closer.

The SPG shall be configured to minimize conductor lengths. Conductive loops shall be avoided by maintaining a trunk and branch arrangement as shown in Figure 22.

Figure 22. Single-Point Ground System Installation – Illustrative Example

5.5.2 Isolation between SPG and Other SRS Systems

The minimum resistance between the SPG and the MPG, SRGG, or SRGP systems shall be 10 MΩ. The resistance shall be measured after the complete network is installed and before connection to the EES or SRS system at the main ground plate.

5.5.3 Resistance of Bonds

The maximum resistance of a bond connection from a conductor to a ground plate shall not be greater than 1 mΩ.

5.5.4 SPG - Ground Plates

Main, branch, and feeder ground plates shall be copper and at least 4 in. wide and 1/4 in. thick.

The plates shall be mounted to nonconductive material of sufficient cross-section to rigidly support the plates after all conductors are connected. Bolts or other devices used to secure the plates in place shall be insulated or shall be of a nonconducting material. The plates shall be mounted in a manner that provides ready accessibility for inspection and maintenance.

See Table 4 for the single ground plate installation requirements.

5.5.5 SPG - Ground Conductors

Ground conductors shall be insulated copper conductors color-coded green with a yellow tracer.

5.5.5.1 Main SPG Conductor

Where an SPG is established directly from the EES, the SPG main conductor shall be an insulated 500 kcmil copper conductor not exceeding 50 ft in length. The main ground conductor shall be connected to the EES by an exothermic weld in accordance with paragraph 4.2.3.1.

5.5.5.2 Trunk and Branch Ground Conductors

Provide an insulated trunk ground conductor to interconnect all branch ground plates to the main ground plate as illustrated in Figure 22. Provide insulated copper branch ground conductors to interconnect feeder plates to branch ground plates. Conductor insulation shall be green with yellow tracer. Trunk and branch conductors shall be connected to ground plates by exothermic welds or UL-listed double-bolted connections in accordance with paragraph 4.2.3.4, and shall be mounted as shown on the facility drawings.

Trunk and branch conductors shall be routed using the shortest possible path.

a. Conductors Shorter than 400 ft. Trunk conductors shall be 4/0 AWG insulated copper conductors where the conductor length to the farthest feeder plate in the system is no more than 400 ft from the EES via the conductor runs.

b. Conductors Longer than 400 ft. For longer runs, select a conductor size to provide a cross-sectional area of 500 cmil per linear foot of conductor, but in no case that the conductor is smaller than 250 kcmil.

5.5.5.3 Electronic Equipment SPG Conductors

The conductor from the feeder ground plate (branch ground plate when there are no feeder ground plates in the conductor run) shall be connected to the isolated ground terminal or bus on the electronic equipment. This conductor shall be sized in accordance with Table 3.

5.5.5.4 Interconnections

Connections to the SPG shall be made on ground plates or buses. Split bolts and other connections to existing conductors are not allowed.

5.5.6 Labeling

The SPG shall be clearly labeled to preserve its identity as described in the following paragraphs.

5.5.6.1 Conductor Identification

SPG conductors shall be labeled in accordance with paragraph 4.7.3.1.6.

5.5.6.2 Ground Plate Labeling

Ground plates shall be installed according to Table 4.

5.5.7 Protection

Provide protection for conductors in the SPG subject to physical damage by use of conduit, floor trenches, routing behind permanent structural members, or other approved means. Single-point ground conductors shall be isolated from contact with any metal elements.

5.6 NAS Electronic Equipment – Interface and Procurement Requirements

5.6.1 General

This section provides detailed performance and interface requirements for installation and procurement of NAS electronic equipment. Electronic equipment installed in NAS facilities shall comply with the requirements herein that address the following:

a. Electronic Signal Lines and Cables – Shielding

b. Signal, Control, and Data Line Entrance – Transient Protection

c. Equipment Power Entrance – Transient Protection

d. Electronic Equipment – Grounding and Bonding

e. Equipment – Signal Grounding and Bonding

f. Equipment Shielding Requirements

g. Circuit and Equipment ESD Design Requirements

5.6.2 Electronic Signal Lines and Cables - Shielding

Electronic signal lines shall be shielded twisted pairs with an insulated covering. Cables consisting of multiple twisted pairs shall have the individual shields isolated from each other.

Cables shall have an overall shield with an overall insulated covering.

5.6.2.1 Electronic Signal Return Path

The electronic signal return path shall be routed with the circuit conductor. For axial circuits, the shield serves this purpose. The electronic equipment case and SRS shall not be used as a signal return conductor.

5.6.2.2 Termination of Individual Shields

Termination of individual shields shall be in accordance with paragraph 4.8.3.2.

5.6.2.3 Termination of Overall Shields

Termination of overall shields shall be in accordance with paragraph 4.8.3.3.

5.6.3 Signal, Control, and Data Line Entrance – Transient Protection Procurement organizations are responsible for ensuring that electronic equipment, such as radars, NAVAIDS, and transmitters shall be provided with transient protection to reduce surges and transients to below the equipment transient susceptibility level. Signal, control, data line, and antenna cabling entrance transient protection shall be provided at the facility entrance point and at electronic equipment. Equipment SPDs shall be an integral part of the equipment, installed either internally or on the exterior of the equipment. Coordination of these protectors shall be addressed and completed in the system design stage and should not be delegated to field personnel during construction.

Equipment susceptibility level is defined as the transient level on the signal, control, or data lines that cause damage, degradation, or upset to electronic circuitry connected to the line. Transient protection for these lines is in addition to the facility transient protection levels specified in paragraphs 5.7.2 through 5.7.4. Procurement organizations are responsible for ensuring that testing is performed to establish voltage, current, and energy levels that will damage components, shorten operating life, or cause operational upset to the equipment. These tests shall include electrical and electronic equipment components exposed to the effects of surges or transients.

The procurement organization shall ensure that facility and electronic equipment entrance transient protection is coordinated to limit transients at the equipment to below the equipment susceptibility level. Requirements of this paragraph shall be included in the comprehensive control and test plans included in paragraph 5.9.2. The following characteristics shall be evaluated:

a. Component Damage Threshold. The component damage threshold is the transient level that renders the component nonfunctional or operationally deficient. Voltage is usually the relevant parameter for solid-state components.

b. Component Degradation Level. The component degradation level is the transient voltage or energy level that shortens the useful life of the component.

c. Operational Upset Level. The operational upset level is the transient voltage or energy level that causes an unacceptable change in operating characteristics for longer than 10 milliseconds for analog equipment or a change of logic state for digital equipment.

5.6.3.1 Lines and Cables Requiring Protection

Surge protective devices shall be placed on both ends of signal, data, antenna, and control lines and cables longer than 10 ft where connecting pieces of electronic equipment are not located and bonded to the same SRS, or where the SRS ground system is located in different rooms or on different building floor levels, as illustrated in Figure 23. Electronic equipment shall be protected as specified in paragraph 5.6.3.

Figure 23. Lines and Cables Requiring Protection

5.6.4 Equipment Power Entrance – Transient Protection

SPDs, components, or circuits for the protection of electronic equipment power lines shall be provided by the equipment manufacturer as an integral part of electronic equipment mounted internally or on the exterior of the equipment at the cable entrance point. These devices shall be located at the ac power conductor entrance to electronic equipment housed in a shielded, compartmentalized enclosure. SPDs at equipment shall provide a clamping level less than the equipment operational upset susceptibility level as defined in paragraph 5.6.3c and shall conform to Tables 9, 10, and 11 in the paragraphs that follow.

a. Maximum Continuous Operating Voltage (MCOV). The MCOV is the maximum rms voltage an SPD can withstand while operating continuously at maximum temperature without degradation or change to any of its parameters greater than +/-10 percent. The MCOV shall be at least 10 percent above the nominal system voltage, and leakage current, as defined below, shall not be exceeded.

b. Leakage Current. The dc leakage current shall be less than 1 mA for voltages at or below the dc voltage value of 1.414 x MCOV.

c. Clamping Discharge Voltage (CDV). The CDV is the maximum voltage that appears across an SPD output terminal while conducting surge currents. To ensure performance in the linear region without impacting the device lifetime performance, the CDV values measured at 3 kA for an 8/20 μs current impulse waveform shall not change more than 10 percent over the operating life of the SPD as defined in Table 9.

d. Overshoot Voltage. Overshoot voltage is the surge voltage level that appears across the SPD terminals before the device turns on and clamps the surge to the specified voltage level.

Overshoot voltage shall not exceed two times the SPD clamping voltage for more than 10 ns.

e. Self-restoring Capability. The SPD shall automatically return to its off state after surge dissipation when line voltage returns to normal.

f. Operating Lifetime. The SPD shall safely dissipate the number and amplitude of surges listed in Table 9.

g. Fusing. The SPD overcurrent protection shall not increase the clamp voltage of the SPD and shall pass the surge current levels listed in Table 9 up to the 20 kA level without opening.

Fusing shall be coordinated with the power source overcurrent protection scheme.

Table 9. Electronic Equipment Power Entrance SPD – Surge Current Lifetime Rating

Surge Current Level Amplitude with an 8/20 μs

Waveform (see note 1)

( kA )

Number of Surges Lifetime

1 100 10 25 20 1

Note:

1. Each level of surge current and the number of lifetime surges required represents a single lifetime of the SPD.

5.6.4.1 Slope Resistance

The purpose of this parameter is to establish a system that ensures SPD device coordination for equipment protection. The slope resistance Rslope, as calculated by the formula below, shall comply with Table 10:

Rslope = (V10 - V1)/9000

Where V10 is the clamping voltage measured at 10 kA for an 8/20 μs waveform and V1 is the clamping voltage measured at 1 kA for an 8/20 μs waveform.

The values of V10 and V1 shall be based on actual measured values of SPD performance testing and not calculated values.

Table 10. Electronic Equipment Power Entrance SPD - Slope Resistance (Rslope)

Location Slope Resistance Value Electronic equipment power entrance 60 mΩ minimum

5.6.4.2 SPD Voltage Protection Rating - V3

SPD voltage protection rating shall be based on actual measured values of SPD performance testing and not calculated values. Voltages to be achieved during testing at 3 kA for an 8/20 μs current impulse waveform are shown in Table 11. All voltages shall be measured at the device terminals. The 8/20 μs waveform shall not lead or lag the voltage waveform by more than 30 degrees.

Table 11. Electronic Equipment Power Entrance SPD - Voltage Protection Rating (V3)

Location System Voltage (V)

SPD Voltage Protection Rating

(V3 per mode) Limit

Electronic equipment power entrance

120/208 or 120/240 550 L-N, L-G 850 L-L Minimum

277/480 850 L-N, L-G 1350 L-L Minimum

380 Delta 1350 L-L, L-G Minimum 480 Delta 1350 L-L, L-G Minimum

5.6.4.3 Electronic Equipment dc Power Supplies – Transient Protection Procurement organizations are responsible for ensuring that equipment power supplies that use 60 Hz power to derive dc operating voltages for solid-state electronic equipment supporting the NAS shall have transient suppression components installed for each power supply output line.

The suppression components shall be bonded to the protection equipment chassis. The chassis side of the suppressor enclosure shall be bonded to the rectifier output ground connection. The suppressor should be located as close as possible to the rectifier grounding connection.

Suppression components for power supply’s rectifier output lines shall comply with following operating characteristics:

a. Operating Lifetime. Transient suppressors shall safely dissipate 1,000 surges at 200 A amplitude for a 1.2/50 µs current impulse waveform. Methods of testing shall be in accordance with the guidance in IEEE C62.45.

b. Limiting Voltage. Voltage shall be limited to a point 20 percent below the maximum peak inverse voltage (PIV) of the dc rectifier.

5.6.5 NAS Electronic Equipment Enclosures and Assemblies - Grounding and Bonding Bonding connections for electronic equipment enclosures and assemblies shall be prepared and completed in accordance with the installation conditions and requirements provided herein.

5.6.5.1 Electronic Equipment Cabinets, Racks, and Cases

Cabinets, racks, and cases shall be provided with a grounding terminal or bus assembly whereby a bonding jumper or wire can be mechanically connected through an electrically conductive surface to the chassis frame. The metal enclosure of each individual unit or piece of electronic equipment shall be bonded to its cabinet, rack, or directly to the SRS or MPG system. Electronic equipment shall be provided with an external grounding pad to allow 2-hole grounding lugs per NEBS. In the event the equipment is not equipped with grounding pads, a specially designed installation shall be required.

5.6.5.2 Equipment Enclosures - Isolated Grounding Receptacles Isolated receptacles installed in accordance with the NEC are permitted for reduction of electrical noise. Isolated EGCs used for these receptacles shall be color-coded green with red and yellow tracers at each termination, and where passing through an enclosure without termination.

5.6.5.3 Portable Equipment (with Grounding Conductor)

Portable electrical or electronic equipment cases, enclosures, and housings shall be considered to be effectively grounded for fault protection through the EGC of the power cord, if positive continuity is provided between the case, enclosure or housing, and the receptacle ground terminal. The power cord EGC shall not be used for signal grounding.

5.6.5.4 Alternating Current Power Filters

Filter cases shall be bonded directly to the equipment case or enclosure in accordance with paragraph 5.6.5.5. Filter leakage current shall not exceed 5 mA per filter. Transient suppression devices, components, or circuits shall be installed in accordance with paragraph 4.6.3.

5.6.5.5 Electronic Equipment Enclosure Bonding

Where subassemblies and equipment are in physical contact with the equipment enclosure, they shall be bonded directly with the enclosure and mounting surfaces.

5.6.5.5.1 Enclosure Subassemblies for Equipment Mounting

Use the maximum possible contact area when bonding subassemblies to the equipment chassis.

Raceway penetrations, filters, and connectors shall be bonded at the periphery to the subassembly enclosure to maintain shield effectiveness. Enclosure covers and mounting trim shall be securely fastened to the enclosure. COTS equipment is considered a sealed unit and does not require additional internal bonding for the purposes of this requirement.

Electronic equipment shall be provided with an external grounding pad to allow two-hole grounding lugs per the Network Equipment Building System (NEBS). In the event the equipment is not equipped with grounding pads, a special design installation shall be required.

5.6.5.5.2 Electronic Equipment Grounding Point

The equipment chassis components shall be bonded together and directly to the rack, frame, or cabinet to which they are mounted. Refer to Section 5.6.5.1.

Clean flange surfaces and the bonding contact surface in accordance with paragraph 4.2.4.1.

Grounding lugs shall maintain sufficient pressure to ensure surface contact to meet the bond resistance requirements in paragraph 4.2.1.1. Captive nuts, sheet metal screws, and tapping screws shall not be used for fasteners. If equipment operation is necessary when partially or completely withdrawn from its mounted position, the bond shall be maintained by an effective area of direct metal-to-metal contact or by the use of a flexible bonding strap.

Mechanical designs shall employ direct bonding, without bonding jumpers, whenever possible.

Exception. If approved, self-drilling (tapping) metal screws are permitted to make a physical connection between metal back panels within equipment cabinet/enclosures for conditions where equipment access is not available to the opposite side of the bond connection.

5.6.5.5.3 Connector Mounting

Connectors shall be mounted so that electrical contact is maintained between the connector body and the metal mounting panel. The connector flange shall be fastened to equipment enclosure to ensure direct contact between components for effective bonding. The connector flange surface and the enclosure contact area shall be cleaned in accordance with paragraph 4.2.4.1.

Nonconductive material shall be removed from the contact area as illustrated in Figure 24. After mounting each connector, the completed bond shall be sealed and finished for corrosion protection in accordance with paragraph 4.2.4.3.

Note:

The connection detail depicts an illustrative example and is exaggerated for clarity.

Figure 24. Bonding of Connectors to Mounting Surface

5.6.5.5.4 Shield Terminations

Cable shields shall be terminated in accordance with paragraphs 4.8.3.2 and 4.8.3.3. Axial cable shields shall be fastened to the cable connector shell with a compression fitting. A soldered connection is permitted to improve conductivity of the shielding joints in accordance with paragraph 4.2.3f. The cable shall withstand the anticipated use without degradation in shielding efficiency performance. Axial cable connectors shall be corrosion resistant in accordance with FAA-G-2100. Low frequency shields shall be soldered in place or, if solderless terminals are used, the compressed fitting shall afford maximum contact between the shield and the terminal sleeve. The cable shield casing shall be exposed less than 1 in. from the internal conductors of the cable as illustrated in Figure 13.

5.6.5.5.5 RF Gaskets

Conductive gaskets shall be corrosion resistant, electrically conductive to meet the resistance requirements of paragraph 4.2.1.1, and resilient to ensure the shielding effectiveness of the bond.

Surfaces in contact with the gasket shall be smooth and free of insulating films, corrosion, moisture, and paint. The gasket shall be firmly affixed to the bonding surface by conductive cement and screw fasteners, a milled slot or other means that do not interfere with the effectiveness of the gasket. These methods shall prevent lateral movement or dislodging of the gasket when the bond is disassembled. Gaskets shall be a minimum of 1/8-in. wide. The gasket and the contact surfaces shall be protected from corrosion.

5.6.6 NAS Electronic Equipment – Equipment Grounding and Bonding

5.6.6.1 Equipment Input and Output Electronic Signals

If a common signal reference is used, low-frequency analog input and output signals shall be balanced with respect to the signal reference. Maintain complete isolation between the SPG and the MPG, SRGG or SRGP system, except at the main ground plate or EES.

5.6.6.2 Multipoint Grounding of Electronic Equipment

Where permitted by circuit design requirements, internal ground references shall be bonded directly to the chassis and the equipment case. Where mounted in a rack, cabinet, or enclosure, the electronic equipment case shall be bonded to the racks, cabinet, or enclosure in accordance with paragraph 5.6.5.1. The dc resistance between any two points within a chassis or electronic equipment cabinet serving as ground shall be less than 25 mΩ total and not more than 2.5 mΩ per joint. Shields shall be provided where required for personnel protection and EMI reduction.

5.6.6.2.1 Prevention of Resonance in Bonding Straps

Due to resonance from a single bonding strap, two widely spaced straps of unequal length shall be used to connect equipment to the multipoint grounding bus in the equipment cabinet.

Bonding connections shall be as short as possible and sized in accordance with Table 3.

5.6.6.3 Single-Point Grounding of Electronic Equipment

If electronic equipment performance necessitates an isolated SPG system for proper operation, then equipment and installation shall comply with the following:

a. SPG System. The SPG or plane shall be isolated from the electronic equipment case. If a metal chassis is used as the SPG, the chassis shall be floated relative to the case. The SPG system shall be designed such that electronic equipment SPG may be interfaced with other electronic equipment without compromising the system. Provide filtering if this SPG is required to be isolated from high frequencies.

b. SPG Conductor and Plate System. The system shall not form a conductive ground loop and it should be set up as a signal drain.

5.6.6.3.1 Single-Point Isolation of Input and Output Signal Requirements The “high” and “low” sides of input and output signals shall be isolated from the electronic equipment case and balanced with respect to the signal reference. Operating and adjusting controls, readouts, indicating devices, protective devices, monitoring jacks, and signal connectors shall be designed to isolate both the high and low side of the signal from the case.

5.6.6.3.2 Single-Point Isolation of Case Requirements

The isolation between the SPG terminals and the case shall be 10 MΩ or greater with external power, signal, and control lines disconnected from the electronic equipment.

5.6.6.3.3 Equipment Power Input Isolation Requirements

The isolation between the SPG terminal and each power conductor (including ac neutral) shall be 10 MΩ or greater with the equipment power switch in the “on” position and the equipment disconnected from its power source.

5.6.6.3.4 Equipment Single-Point Ground Terminals

An insulated SPG terminal shall be provided on each electronic equipment case where an isolated signal reference is required. The SPG reference for the internal circuits shall be connected to the SPG terminal. This terminal shall be used to terminate cable shields as appropriate, and to connect the isolated signal ground of the electronic equipment to the SPG in the facility. A connector pin, screw, terminal strip, insulated stud, jack or feed-through, or an insulated wire are acceptable terminations if each terminal is clearly marked, labeled, or coded in a manner that does not interfere with its function. These marks, codes, or labels shall be permanently affixed and use green identification with yellow stripes. Wire insulation shall be green with a yellow tracer.

5.6.6.3.5 Connection of Electronic Equipment to the SPG

Each equipment SPG terminal shall be connected to the facility SPG in accordance with the following:

a. Individually Mounted Equipment. Individual units or pieces of electronic equipment that should not be mounted with other electronic equipment due to their location or function shall have an insulated copper conductor bonded from SPG terminal as specified in paragraph

5.6.6.3.4 to the nearest SPG system. This conductor shall be sized in accordance with Table 3.

b. SPG Bus Bar. If two or more units or pieces of electronic equipment are mounted together in a rack or cabinet, then a single-point ground bus bar shall be installed as shown in Figure 25. The bus bar shall be copper and shall provide a minimum cross-sectional area of 125,000 cmils, e.g., a 1x1/8-in. bus bar. The bus bar shall be drilled and tapped for No. 10 screws, and the holes shall be located as required by the relative location of the isolated SPG terminals on the electronic equipment. The bus bar shall be mounted on insulating supports that provide at least 10 MΩ resistance between the bus bar and the rack or cabinet.

c. Interconnecting SPG Terminals to SPG Bus Bar. Each electronic equipment isolated SPG terminal shall be interconnected to the SPG bus bar by means of a solid conductor of sufficient cross-sectional area to provide a maximum resistance of 5 mΩ, or a flexible tinned copper bond jumper sized in accordance with Table 3. The bond jumper shall be insulated or mounted in such a manner to maintain the required degree of isolation between the reference conductor and the enclosure. The bond jumper shall be connected to the equipment SPG bus bar at a point nearest the equipment SPG terminal in order to minimize the conductor length. An insulated copper conductor shall be installed from the equipment SPG bus bar to the nearest SPG grounding system as illustrated in Figure 25.

Note:

1. The conductor wire size for bonding conductors from electronic equipment to internal cabinet SPG bus bar shall be based on Table 3.

Figure 25. Single-Point Ground Bus Bar Installation in Rack or Cabinet

5.6.7 Equipment Shielding Requirements

5.6.7.1 Control of Apertures

Unnecessary apertures shall be avoided. Only those shield openings required to achieve proper functioning and operation of the equipment may be provided. Controls, switches, and fuse holders shall be mounted such that metal-to-metal contact is maintained between the cover housing of the devices and the case. Metal control shafts shall be grounded in accordance with paragraph 5.6.7.2. Close-fitting metal sleeves peripherally bonded to the case shall be provided only where nonconductive control shafts are necessary. The length of the sleeve shall be no less than four times its diameter. Lights shall be filtered or shielded as needed to maintain the required degree of shielding effectiveness. Openings provided for enclosure ventilation and moisture drainage shall be configured to maintain the effectiveness of the overall enclosure shielding.

5.6.7.2 Metal Control Shafts

Metal control shafts shall be grounded to equipment cases through a low impedance path provided by close-fitting conductive gaskets, metal finger stock, or grounding nuts.

5.6.7.3 Shielded Compartments

Shields shall be bonded to the chassis for fault protection in accordance with section 4.2.

5.6.7.4 Gaskets for Shielding Systems

Conductive gaskets conforming to paragraph 5.6.5.5.5 may be provided at joints, seams, access covers, removable partitions, and other shield discontinuities to the extent necessary to provide interference-free operation of the equipment under normal use and environmental conditions.

Finger stock used on doors, covers, or other closures subject to frequent openings shall be installed in a manner that permits routine cleaning and maintenance.

5.6.7.5 Filter Integration

Filters on power, control, and signal lines shall be installed in a manner that maintains the integrity of the shield. Alternating current power filters shall be shielded completely with the filter case grounded in accordance with paragraph 5.6.5.4. Filters for control and signal lines shall be placed as close as possible to the point of penetration of the case to avoid long, unprotected paths inside the equipment.

5.6.8 NAS Electronic Equipment - Electrostatic Discharge Protection ESD protection shall be provided in accordance with section 5.8.

a. Equipment Circuit Design and Layout. The design, layout, and packaging of assemblies, circuits, and components integrated into electrical and electronic equipment shall incorporate methods and techniques to reduce susceptibility to ESD.

b. Component Protection. External protection shall be provided for integrated circuits, discrete components, and other parts not having internal ESD protection that are inherently susceptible to ESD. Protective components shall be installed as close as possible to the ESD susceptible item.

c. ESD Withstand Requirements. In the installed and operational configuration equipment such as cabinets, enclosures, racks, controls, meters, displays, test points, and interfaces shall withstand a static discharge of 15,000 V in accordance with ANSI/ESDA/JEDECD JS-001, Standard for ESD Sensitivity Testing – Human Body Model (HBM). To successfully pass ESD testing requirements, the tested equipment shall not incur any operational upset, component, or assembly damage.

5.6.9 Secure Facilities

In areas of facilities required to maintain communications security, equipment and power systems shall be grounded in accordance with NACSIM-5203 and MIL-HDBK-232A.

5.6.10 High RF Field Bonding Requirements

FAA facilities that are located in proximity to other facilities that generate high RF levels need additional shielding to protect personnel and sensitive equipment from these external RF sources.

When a determination is made that the signal level is sufficient to cause concern, incorporate the following requirements:

Metal building components and attachments such as walls, roofs, floors, door and window frames, gratings and other metallic architectural features shall be bonded directly to structural steel or to reinforcing bar if structural steel is not present. Where direct bonding is not possible, indirect bonds with copper conductor shall be used. Removable or adjustable parts and objects shall be grounded with an appropriate type of bond strap. Metal building components with a maximum dimension of 3 ft or less are exempt from the requirements of this paragraph.

5.7 Surge Protective Device (SPD) – Equipment Specification Requirements

5.7.1 General

This section provides SPD performance requirements.

5.7.2 Surge Protective Device (SPD) for Power Distribution Equipment Protection The SPD installation shall comply with the following:

a. Application Listing. The SPD shall be listed in accordance with the latest UL 1449 Standard for SPDs.

b. Integral Unit Mounted Assemblies. Panelboards and switchgear equipment with integral unit mounted SPD enclosures are permitted if the SPD and panelboard or switchgear integrated components are UL listed and recognized as an assembly.

c. Enclosure Rating. The SPD components shall be housed in a single steel enclosure, and classified by NEMA as type-12 for indoor use, or type-4 for indoor or outdoor use.

d. Enclosure Door Hardware. The enclosure door shall be hinged and electrically bonded with a bonding jumper connected to the enclosure. The internal components of the SPD, such as fusing, indicator lights, wiring, and protection elements, shall be accessible for inspection and replacement. The manufacturer’s installation and maintenance instructions shall be provided with each SPD unit.

e. SPD Accessories. Indicator lamps shall be provided for each power phase on the SPD enclosure cover. The lamps shall indicate visually the normal condition when power is applied to the SPD with the component fusing intact. Lamps shall be provided at a minimum service life of 50,000 hours, otherwise two lamps per phase shall be provided.

f. Potting Material. The SPD enclosure shall be sealed at the power entry points with potting material in accordance with paragraph 4.6.2.3. The use of potting material within SPD components is prohibited, such that all SPD components are accessible at all times for visual inspection, evaluation, maintenance, or replacement by qualified FAA personnel.

g. Conductor Terminations. Provide heavy-duty screw terminal studs or lugs for input and output conductor connections. The SPD phase and neutral terminals, when not connected, shall be electrically isolated from the enclosure by a minimum of 10 MΩ resistance measured at 100 Vdc.

5.7.2.1 SPD - Operational Requirements

The SPD equipment performance shall conform to Table 12, Table 13, and Table 14, and the following parameters:

a. Maximum Continuous Operating Voltage. The MCOV is the maximum rms voltage an SPD can withstand while operating continuously at maximum temperature without degradation or change to any of its parameters greater than +/-10 percent. The MCOV shall be at least 10 percent above the nominal system voltage. Leakage current, as defined below, shall not be exceeded.

b. Leakage Current. The dc leakage current shall be less than 1 mA for voltages at or below the dc voltage value of 1.414 x MCOV.

c. Clamping Discharge Voltage. The CDV is the maximum voltage that appears across an SPD output terminal while conducting surge currents. To ensure performance in the linear region without impacting the device’s lifetime performance, the CDV values measured at 3 kA for an 8/20 μs current impulse waveform shall not change more than 10 percent over the operating life of the SPD as defined in Table 12.

d. Overshoot Voltage. Overshoot voltage is the surge voltage level that appears across the SPD terminals before the device turns on and clamps the surge to the specified voltage level.

Overshoot voltage shall not exceed two times the SPD clamping voltage for more than 10 ns.

e. Self-restoring Capability. The SPD shall automatically return to its off state after surge dissipation when line voltage returns to normal.

f. Operating Lifetime. The SPD shall safely dissipate the number and amplitude of surges listed in Table 11.

g. In-line Inductors. In-line inductance is not permitted, except from the inductance normally created by the power connection conductors.

h. Overcurrent Protection. Fuses or circuit breakers that are part of an SPD installation shall be able to pass the surge currents specified in Table 12 without opening.

i. Short Circuit Current Rating. The SPD short circuit current rating shall be greater than the power distribution system available short circuit current where the equipment is applied in the power distribution system.

5.7.2.1.1 SPD Equipment Performance Data - Surge Current Levels Table 12 defines the line-to-ground, line-to-neutral, neutral-to-ground, and line-to-line surge current values, and number of surge occurrences for ac power distribution SPD equipment operating below 600 V. The 8/20 µs waveform defines a transient reaching peak value in 8 µs and decaying to 50 percent of peak value 20 µs after inception. These devices shall be able to tolerate surges of shorter duration without malfunction.

Table 12. Power Distribution Equipment SPD – Surge Current Lifetime Rating

Surge Current Level Amplitude with an 8/20 μs

Waveform, See Note 1

( kA )

Number of Surges Lifetime for Any Facility

Entrance SPD

Number of Surges Lifetime for

Feeder and Branch Panelboard SPDs

10 1500 1000 20 700 500 30 375 250 40 50 25 50 8 1 60 6 N/A 70 4 N/A 100 2 N/A 200 1 N/A

Note:

Each level of surge current and the number of lifetime surges required represents a single lifetime of the SPD.

The following performance change measurements define SPD device failure modes. For the listed parameters, the clamping voltages for each device and assembly are measured at 1 kA and 10 kA for an 8/20 μs current impulse waveform.

a. Change in Clamping Voltage. Any change greater than 10 percent in the 8/20 μs clamping voltage at 3 kA during service or when the pre-life service test and post-life or in-service test results are compared is a device failure. The pre-life test value shall be taken as the 100 percent value.

b. Change in rms Voltage. Any change greater than 10 percent in the rms voltage required to drive 1 mA of rms current through the device when the pre-life service test and post-life or in-service test results are compared is a device failure. The pre-life test value will be taken as the 100 percent value.

c. Change in dc Voltage. Any change greater than 10 percent in the dc voltage required to drive 1 mA dc through the device when the pre-life service test and the post-life or in-service test results are compared is a device failure. The pre-life test value will be taken as the 100 percent value.

5.7.2.1.2 SPD - Slope Resistance

The purpose of this parameter is to establish a system that ensures SPD device coordination for equipment protection. The slope resistance Rslope, as calculated by the formula below shall comply with Table 13:

Rslope = (V10 - V1)/9000 Where V10 is the clamping voltage measured at 10 kA for an 8/20 μs waveform and V1 is the clamping voltage measured at 1 kA for an 8/20 μs waveform.

The values of V10 and V1 shall be based on actual measured values of SPD performance testing and not calculated values.

Table 13. Power Distribution Equipment SPD - Slope Resistance (Rslope)

Location Slope Resistance Value Any Facility Entrance 8 mΩ Maximum Feeder and Branch Panelboards 30 mΩ +/- 15 mΩ

5.7.2.1.3 SPD - Voltage Protection Rating V3

SPD voltage protection rating shall be based on actual measured values of SPD performance testing and not calculated values. Voltages to be achieved during testing at 3 kA for an 8/20 μs current impulse waveform are shown in Table 14. All voltages shall be measured at the device terminals. The 8/20 μs waveform shall not lead or lag the voltage waveform by more than 30 degrees.

Table 14. Power Distribution SPD Voltage (V3) Protection Rating

Location System Voltage (V)

SPD Voltage Protection Rating

(V3 per mode) Limit

Facility Entrances

120/208 120/240

400 L-N, L-G 700 L-L Maximum

277/480 700 L-L, L-G Maximum 380 Delta 1200 L-L,L-G Maximum 480 Delta 1200 L-L, L-G Maximum

Feeder and Branch Panelboards

120/208 120/240

475 L-N, L-G 775 L-L

+/- 45 V

277/480 775 L-N, L-G 1275 L-L +/- 45 V

380 Delta 1275 L-L, L-G +/- 45 V 480 Delta 1275 L-L, L-G +/- 45 V

5.7.3 SPDs for NAS Electronic Equipment – Design and Procurement Requirements Provide surge protection for NAS electronic equipment in accordance with paragraph 5.6.3.

5.7.4 SPD - Design Specification for Axial Cable Protection

The design analysis for axial-type cable transient protection shall address the critical RFs and cable insertion losses. Axial cable protection shall comply with the following:

a. Testing. Performance testing shall be conducted to ensure that suppression components do not degrade signals or cause disruption to the electronic equipment.

b. RF Signal Testing Criteria. The analyses shall address cable impedance, insertion loss, phase distortion, and system voltage standing wave ratio.

c. Transient Protection for Electronic Equipment. SPD protection for coaxial, tri-axial, and twin-axial cables shall be provided at the facility entrance point and at the electronic equipment.

The transient suppression shall be provided for each axial conductor and for shields that are not bonded directly to the electronic equipment chassis.

5.8 Electrostatic Discharge (ESD) Protection – Interface and Specification Requirements

5.8.1 General

This section provides performance and interface requirements for installation of ESD protective systems. ESD controlled areas shall be provided for operations, storage, repair, and maintenance spaces used for electrical and electronic equipment or subassemblies that are subject to damage from static electricity or ESD. NAS electrical and electronic equipment, subassemblies, and components subject to damage from exposure to electrostatic fields or ESD shall be protected as indicated herein. Approval of any exception to the guidance herein shall be by the OPR.

The requirements of this section are designed to reduce frequency and minimize effects of ESD events. Electronic circuitry that contains miniaturized or solid-state components shall be considered ESD susceptible.

5.8.2 Electrostatic Discharge (ESD) Sensitivity Classification Classification of items as ESD sensitive shall be in accordance with the HBM testing procedures and requirements of ANSI/ESDA/JEDECD JS-001. Electronic parts, components, and assemblies shall be classified as either sensitive or supersensitive. Items that fail from ESD at 1,000 to 16,000 V shall be classified as ESD sensitive. Items that fail below 1,000 V shall be classified as supersensitive. Devices with a sensitivity of less than +/- 200 V require additional ESD protection measures beyond those specified in this standard. ESD susceptible items shall not be exposed to an electrostatic field greater than 100 V/m, nor located within 24 in. from known static generators or nonessential insulated materials.

5.8.3 Classification of Materials

Most materials and products that are used to control and prevent ESD are classified by their resistive properties as conductive or static dissipative. Antistatic materials are classified by their ability to avoid generating static electricity from triboelectric charging.

Materials used for construction of ESD protected areas (with the exception of antistatic materials) shall meet the resistive properties specified for type and use of the material.

5.8.3.1 Static Conductive Materials

Those materials with a surface resistivity less than 1.0 x 105 ohms per square when tested per ANSI/ESD STM11.11 shall be considered conductive. Conductive ESD control materials shall not be used for ESD control work surfaces, tabletop mats, floor mats, flooring, or carpeting where the risk of personnel contact with energized electrical or electronic equipment exists.

Conductive ESD control materials shall not be used in any other application where their use could result in EMI or radio frequency interference (RFI) that would be created by rapid, high-voltage ESD spark discharges.

5.8.3.2 Electrostatic Shielding Materials

Electrostatic shielding materials are a subset of conductive materials with a surface resistance equal to or less than 1.0 x 103 ohms when tested per ANSI/ESD STM11.11. Electrostatic shielding materials are permitted as barriers for protection of ESD sensitive items from electrostatic fields.

5.8.3.3 Electromagnetic Shielding Materials

Electromagnetic shielding materials with highly conductive surfaces less than 10 ohms, or composite materials that absorb and reflect electromagnetic radiation over a broad range of frequencies, are permitted for protection of ESD sensitive items from electromagnetic fields.

5.8.3.4 Static Dissipative Materials

Materials with a surface resistivity greater than 1.0 x 105 ohms per square but less than or equal to 1.0 x 1012 ohms per square when tested per ANSI/ESD STM11.11 are classified as static dissipative materials. Static dissipative materials with a surface resistance less than or equal to

1.0 x 109 ohms shall provide controlled bleed-off of accumulated static charges in ESD controlled areas. Static dissipative materials with a surface resistance of greater than 1.0 x 109 ohms are not permitted for applications where controlled bleed-off of accumulated static charges is required.

5.8.3.5 Antistatic Materials

Materials that inhibit or have a low propensity to generate static electricity from triboelectric charging shall be considered antistatic. Antistatic ESD control items and materials used for construction of ESD controlled areas shall not tribocharge to greater than +/-200 V when being used for their intended application. Antistatic materials with a surface resistance greater than 1 x 109 ohms shall not be used for ESD protective work at surfaces, tabletop mats, floor mats, flooring, and carpeting when charge dissipation is the primary consideration. If the surface resistance (Rtt) of an antistatic material is greater than 1012 ohms, it shall be considered too resistive for use in ESD controlled areas. Use of antistatic items and materials that use hygroscopic surfactants that depend on ambient humidity to promote absorption of water is discouraged. Only antistatic materials that are intrinsically antistatic and retain their antistatic properties shall be used in ESD controlled areas.

5.8.3.6 Static-Generative Materials, Nonconductors, and Insulators Materials having a surface resistance greater than 1.0 x 1012 ohms (ANSI/ESD STM11.11) shall be considered to be insulators and a potential source of triboelectric charging. These materials include common plastics, Plexiglas, Styrofoam, Teflon, nylon, rubber, untreated polyethylene, and polyurethane. Use of these materials shall be minimized where ESD sensitive items are located.

5.8.4 Hard and Soft Grounds

5.8.4.1 Hard Grounds

Any item, material, or product that is a part of the ESD control system that is intentionally or unintentionally connected to an ESD ground, or connected directly to any SRS in the area served, but not to an SPG system, shall be considered to be hard grounded. Unless specified otherwise or approved by the OPR, all items that comprise the ESD control system shall be hard grounded, such as worksurfaces, cabinets, flooring, carpeting, and test equipment.

5.8.4.2 Soft Grounds

A soft ground is an intentional connection to ground through a series current limiting resistor.

Soft grounding shall only be used for personnel grounding skin contact devices, such as wrist straps, leg or ankle straps, conductive shoes, and heel or toe grounders. The nominal resistance of the resistor used for soft grounding of personnel shall be greater than 1.0 x 106 ohms unless otherwise approved by the OPR. All other elements of the ESD control system shall be hard grounded.

5.8.5 Protection of Electrostatic Discharge (ESD) Susceptible and Sensitive Items

5.8.5.1 Static Protected Zone

A static protected zone shall be a volume or area where there is no direct contact between unprotected ESD sensitive items and electrostatic potentials greater than +/-200 V, electrostatic fields greater than 100 V/m, or radiated EMI and RFI produced by rapid high-voltage ESD spark discharges. Static protected zones shall be incorporated into the construction of ESD special protection areas, ESD protected storage areas, and ESD protected workstations.

5.8.5.2 ESD Special Protection Areas

Special protection areas shall be designated areas that require the following ESD control measures:

a. Minimize triboelectric charging.

b. Control bleed-off and dissipation of accumulated static charges.

c. Neutralize charges.

d. Minimize the effects of e-fields, h-fields, and EMI/RFI from ESD spark discharges.

Areas within a facility that shall be designated as ESD special protection areas are:

a. Air Traffic Operations Areas. These include tower cab, TRACON, ARTCC control rooms, and automated flight service station (AFSS) areas.

b. Electronic Equipment Rooms.

c. Storage Areas. Areas to store ESD-susceptible components such as subassemblies and circuit cards.

d. Computer/LAN Interface Areas. Areas that contain personal computers and LANs that are connected to or interface directly with NAS electronic equipment.

e. Other Locations. Locations where jacks, plug-in connectors, or interfaces of ESD sensitive electronic equipment are exposed and vulnerable to ESD damage by direct human contact.

5.8.6 ESD Controls Required for ESD Special Protection Areas

The following ESD control measures shall be implemented in areas designated as ESD special protection areas.

5.8.6.1 ESD Groundable Point (GP)

Each ESD control material, surface, or item…