This document is a clarifying questions response issued by Clackamas County, Oregon, Department of Public Health for RFP 2026-44 regarding UV disinfection equipment for wastewater applications at the Kellogg Creek Water Resource Recovery Facility. The RFP solicits a complete UV disinfection system consisting of two identical channels with three UV banks each, capable of delivering a minimum T1 bacteriophage Reduction Equivalent Dose of 24 mJ/cm2 at peak flow and treating flows up to 24 million gallons per day. The system must operate in outdoor conditions with temperature extremes from -3 to 116 degrees Fahrenheit and comply with Oregon Structural Specialty Code seismic requirements. All electronic controls must be compatible with the Siemens Simatic Step 7 TIA platform to integrate with the facility's existing logic control system. The proposal closing date is June 24, 2026, at 2:00 PM Pacific Time, with a deadline for clarifying questions of June 16, 2026, at 5:00 PM Pacific Time. The contract term extends from the effective date through May 31, 2028, with project phases including supplier selection and final design development in Spring-Summer 2026, contractor selection and price negotiations in Fall 2026, equipment submittals and lead time in Fall 2026-Spring 2027, and installation in Spring-Summer 2027.
The clarifying questions response addresses six technical and administrative inquiries from prospective bidders. Key determinations include: on-site installation service is mandatory with remote installation assistance not acceptable; a signed NDA is required before validation reports can be released; redundant CPU systems are not required provided UV banks default to 100% power upon CPU failure to ensure continued disinfection; deviations from technical specifications are permitted if clearly noted in proposals; alternative control system vendors such as ABB may be proposed with evaluation based on integration capability with the existing Siemens SCADA system; and alternative enclosure manufacturers such as Saginaw may be approved with proper deviation documentation. Proposers must demonstrate significant experience with at least ten operational municipal UV systems and provide independent third-party bioassay validation reports complying with NWRI and USEPA protocols. The procurement includes required insurance coverage of $1,000,000 professional liability per occurrence with $2,000,000 annual aggregate, $1,000,000 commercial general liability per occurrence with $2,000,000 annual aggregate, and $500,000 automobile liability per occurrence.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP 2026-44 Clarifying Questions 1.pdf | ||
| RFP 2026-44 UV Disinfection.pdf | ||
| B - Specifications.pdf | ||
| C - Drawings.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department
PH: 503-742-5400 WWW.CLACKAMAS.US
REQUEST FOR PROPOSALS #2026-44
UV DISINFECTION EQUIPMENT FOR WASTEWATER APPLICATIONS
RESPONSE TO CLARIFYING QUESTIONS
#2 Note that these are questions submitted by interested firms to the above referenced solicitation. The below answers are for clarification purposes only and in no way alter or amend the RFP as published.
1. 3.01.A – Please advise if remote installation assistance is an acceptable alternative.
A. Remote installation assistance is not acceptable. Supplier shall provide on-site installation service.
2. 1.02.B Please note that we require a signed NDA before validation report can be released.
A. No exceptions taken.
3. 2.04.L.7- We take exception. Cable entry will be at the side bottom of the PDP.
A. Deviation from the technical documents are allowed but need to be noted clearly. Refer to Section 5 on how to submit deviations from technical documents.
4. 2.05.A – Can you please confirm if a redundant CPU is required?
A. A redundant CPU is not required, provided that in the event of CPU failure the UV banks / modules default to 100% power, to ensure that disinfection continues even in the event controls/communication is lost.
5. 2.05.A.5.a - Please advise if ABB is an approved equal.
A. Deviation from the technical documents are allowed but need to be noted clearly. Refer to Section 5 on how to submit deviations from technical documents. Weight will be given to the proposed ABB system’s ability to interact with the facility’s existing Siemens-based SCADA system.
6. 2.06.B.1.c - Please allow for Saginaw to be an approved equal.
A. Deviation from the technical documents are allowed but need to be noted clearly. Refer to Section 5 on how to submit deviations from technical documents.
End of Clarifying Questions #2