RFB950100-01 - Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- RFB950100-01
- Issued by
- Calhoun County, Iowa
About this file
This is a set of technical drawings and specifications for an HVAC air handler replacement project issued by the Iowa Department of Administrative Services (IDAS) for the North Central Community College Foundation (NCCF) facility located at 313 Lanedale, Rockwell City, Iowa. The project involves providing three new cooling-only DX fan coil units (FCU-1, FCU-2, and FCU-3) to replace two existing units and one unit to be salvaged and returned to the owner. Associated condensing units (CU-1, CU-2, and CU-3) will be replaced, with one existing condensing unit to be salvaged. The scope includes removal of old refrigerant piping, installation of new refrigerant piping and condensate drain lines, ductwork modifications, and electrical work including new disconnects and circuit breaker connections. The drawings are dated April 29, 2026, and indicate 100% Construction Documents (CD) phase with professional seals from mechanical engineer Evan Hammer and electrical engineer Tony DeLouis of IMEG Consultants Corp.
The project specifies Daikin DAQ12033 fan coil units rated at 4,100 CFM with R-32 refrigerant, 10-ton capacity, and 208V/3-phase electrical service requiring 13.8 FLA per unit. Daikin DC6TE120 condensing units are specified at 10 tons, 2-stage cooling with 16.4 IEER rating, also 208V/3-phase at 46 MCA. Equipment will be installed on existing concrete pads with new disconnect switches and circuit breakers provided through existing electrical panels (UA-P1 and UB-P2). The project incorporates applicable codes including IBC 2024, IFC 2024, IMC 2021, NFPA 70 (NEC) 2023, and IECC 2012. Testing, adjusting, and balancing (TAB) services are required both pre-demolition and post-construction to verify airflow and duct static pressure readings, with final reports due within 10 working days of field measurements. Fire alarm duct smoke detectors will be reinstalled, and all refrigerant reclamation must comply with authority having jurisdiction requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB950100-01 - Project Manual.pdf | ||
| RFB950100-01 - Bid Form.pdf | ||
| RFB950100-01 - Notice to Bidders.docx | DOCX document | |
| 1389405-event.pdf | ||
| Bidding Documents and Project Manual.html | HTML file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
OSHPD #
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT DIRECTORY
CLIENT:
SCOPE OF WORK
PROVIDING THREE NEW COOLING ONLY, DX FAN COIL UNITS TO REPLACE
TWO OLD UNITS AND ONE UNIT THAT IS TO BE SALVAGED AND HANDED
OVER TO THE OWNER. CONDENSING UNITS SHALL BE REPLACED AND
SALVAGED AS NOTED ON PLAN.
MECHANICAL
ENGINEER:
APPLICABLE CODES DRAWING INDEX
BUILDING CODE: IBC 2024 EDITION
FIRE CODE: IFC 2024 EDITION
PLUMBING CODE: UPC 2024 EDITION
MECHANICAL CODE: IMC 2024 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
LIFE SAFETY CODE: NFPA 101 2012 EDITION
ENERGY CONSERVATION CODE: IECC 2012
EVAN HAMMER
2882 106TH STREET
DES MOINES, IA 50322
PHONE: 515-334-7934
EMAIL:Evan.J.Hammer@imegcorp.com
ELECTRICAL
ENGINEER:
TONY DELOUIS
2882 106TH STREET
PHONE: 515-334-4317
EMAIL: Tony.E.DeLouis@imegcorp.com
VICINITY MAP
PROJECT #26001283.00
PROJECT VICINITY
PROJECT LOCATION
/2
/2
:2
:3
P
M
Iowa Department of Administratinve Services
G000
PROJECT COVERSHEET
Approver
Checker
Author
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
IDAS 9501.00 DOC NCCF AIR HANDLER REPLACEMENT
313 LANEDALE
ROCKWELL CITY, IOWA 50579
Iowa Department of Administratinve Services
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
Sheet List Number Name
PROJECT COVERSHEET
G000 PROJECT COVERSHEET
HVAC
M000 HVAC COVERSHEET
M100 BASEMENT DEMOLITION PLAN - HVAC
M101 LEVEL 01 DEMOLITION PLAN - HVAC
M102 LEVEL 02 DEMOLITION PLAN - HVAC
M210 BASEMENT PLAN - VENTILATION
M211 LEVEL 01 PLAN - VENTILATION
M212 LEVEL 02 PLAN - VENTILATION
M400 HVAC DETAILS
M500 HVAC SCHEDULES
ELECTRICAL
E000 ELECTRICAL COVERSHEET
E100 DEMOLITION FLOOR PLAN - ELECTRICAL
E200 NEW FLOOR PLAN - ELECTRICAL
E700 ELECTRICAL PANEL SCHEDULES
HVAC ABBREVIATION KEY
ABBR: DESCRIPTION:
ABOVE FINISHED FLOORAFF
NOT IN CONTRACTNIC
TYPICALTYP
UON UNLESS OTHERWISE NOTED
CO CLEANOUT
SCCR SHORT CIRCUIT CURRENT RATING
DN DOWN
1. UNLESS NOTED OTHERWISE, DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR
DIMENSIONS. MAINTAIN CLEAR DIMENSIONS INSIDE ANY LINING
2. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.
3. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING
DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE
VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.
4. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE
CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL
TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED
AS SPECIFIED FOR NEW DUCTWORK.
VENTILATION GENERAL NOTES:
1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.
2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
1. BEFORE ANY DEMOLITION WORK IS BEGUN, AN AIR BALANCE TEST SHALL BE PERFORMED
BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR FOR EQUIPMENT AND
DEVICES AS INDICATED ON THE DRAWINGS.
2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS.
A. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS
INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE
TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT
TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW
READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT
TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL
INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL
MEASUREMENTS WERE TAKEN.
B. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT
TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB
REPORT.
3. TAB CONTRACTOR SHALL COMPILE AND SUBMIT THE FINAL PRE-DEMOLITION REPORT
WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB
REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL
INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
TAB PRE-DEMOLITION NOTES:
1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND
BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AS REQUIRED TO
ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.
2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-
BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED
(REFER TO THE FINAL PRE- DEMOLITION REPORT).
3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR
MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE
LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS
REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN
ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE
LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.
4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT
TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION
TAB REPORT.
5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-
CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.
6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE
SPECIFICATIONS.
TAB POST-CONSTRUCTION NOTES:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO VENTILATION, & PIPING.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. CATALOG AND MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN
AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR
IS RESPONSIBLE FOR THE COMPLETE DESCRIPTION OF MATERIAL SCHEDULED ON THESE
DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE
MATERIAL AND SCHEDULED PERFORMANCE TAKES PRECEDENCE OVER THE MODEL
NUMBER. THE FIRST MANUFACTURER SCHEDULED IS THE BASIS OF DESIGN.
3. DETERMINATION OF QUANTITIES OF MATERIAL AND EQUIPMENT REQUIRED SHALL BE MADE
BY THE CONTRACTOR FROM THE DOCUMENTS. WHERE MATERIAL AND/OR QUANTITY
DISCREPANCIES ARISE BETWEEN DRAWINGS, SCHEDULES AND/OR SPECIFICATIONS, THE
HIGHER QUALITY/ GREATER NUMBER SHALL GOVERN.
4. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
5. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
6. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
7. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
9. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
10. SEAL ALL FLOOR & WALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS
PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS SHALL BE SEALED AIRTIGHT WITH
WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
12. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
13. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.
14. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
15. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO VENTILATION & PIPING.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
WALLS AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
6. WHERE EXISTING MECHANICAL SYSTEMS DIFFER FROM THOSE SHOWN ON THE PROJECT
DRAWINGS AND CREATE CONFLICTS WITH NEW EQUIPMENT, PIPING, OR DUCTWORK
INSTALLATIONS, THE CONTRACTOR SHALL PROVIDE DETAILED DOCUMENTATION (SUCH AS
SKETCHES, PHOTOS, AND DIMENSIONS) ALONG WITH RECOMMENDATIONS TO RESOLVE
THE CONFLICT. THIS INFORMATION MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW
AND APPROVAL. NO WORK RELATED TO THE CONFLICT SHALL PROCEED UNTIL AN
APPROVED RESOLUTION IS PROVIDED BY THE ENGINEER.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
11. PROPERLY RECLAIM AND DISPOSE OF ALL REFRIGERANT IN REMOVED EQUIPMENT/
REFRIGERANT PIPING. RECLAIMED REFRIGERANT SHALL HAVE DOCUMENTATION AS
REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ).
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
FIRE AND SMOKE SEPARATIONS ARE NOT SHOWN ON THESE DOCUMENTS. CONTRACTOR SHALL
REVIEW THE ARCHITECTURAL PLANS AND DETERMINE THE LOCATIONS OF ALL FIRE AND SMOKE
PARTITIONS, BARRIERS, AND WALLS. THIS INCLUDES FLOOR RATINGS. PRICING SHALL INCLUDE ALL MATERIALS AND LABOR REQUIRED TO MAINTAIN THE RATINGS OF ALL RATED SEPARATIONS, WHETHER SHOWN ON THE ENGINEERING PLANS OR NOT.
FIRE / SMOKE BARRIER DESIGNATIONS
BUILDING CODE: IBC 2024 EDITION
FIRE CODE: IFC 2024 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
ENERGY CONSERVATION CODE: IECC 2012
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
NATE JACQUES
EVAN HAMMER
TONY DELOUIS
DESCRIPTION: PERSON:
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
As indicated
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M000
HVAC COVERSHEET
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
DUCT ABBREVIATION KEY
ABBR. DESCRIPTION
EA EXHAUST AIR
OA OUTSIDE AIR
SA SUPPLY AIR
SYMBOL LIST - PIPING SYSTEMS
SYMBOL DESCRIPTION º F FLUID TYPE
DPP DRAIN - PIPING
HWR HEATING WATER RETURN 150 Water
HWS HEATING WATER SUPPLY 180 Water
LIQ REFRIGERANT LIQUID 120 Water
SUC REFRIGERANT SUCTION 35 Water
HVAC SHEET INDEX
M000 HVAC COVERSHEET
M100 BASEMENT DEMOLITION PLAN - HVAC
M101 LEVEL 01 DEMOLITION PLAN - HVAC
M102 LEVEL 02 DEMOLITION PLAN - HVAC
M210 BASEMENT PLAN - VENTILATION
M211 LEVEL 01 PLAN - VENTILATION
M212 LEVEL 02 PLAN - VENTILATION
M400 HVAC DETAILS
M500 HVAC SCHEDULES
GRAND TOTAL: 9
04/29/2026
1 1/2"HWR
1/2"SUC
1/2"LIQ
2 1/2"HWS
1 1/2"DPP
1/2"LIQ
1/2"LIQ
1/2"SUC
1/2"SUC
2 1/2"HWS
2 1/2"HWS
1 1/2"HWR
1 1/2"DPP
1 1/2"HWR
2 1/2"HWS
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M100
BASEMENT DEMOLITION PLAN - HVAC
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
BASEMENT DEMOLITION PLAN - UNIT A - HVAC
N O R
HT
1/4" = 1'-0"2
BASEMENT DEMOLITION PLAN - UNIT B - HVAC
T
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
EG-E
8/150
EG-E
8/150
12x6 EA
8x8 EA
EF-2 (E)
BEFORE ANY DEMOLITION WORK IS
BEGUN, AN AIR BALANCE TEST SHALL BE
PERFORMED BY THE TESTING,
ADJUSTING AND BALANCING (TAB)
CONTRACTOR.
REMOVE, SALVAGE, &
PROTECT EXISTING FAN COIL &
TURN OVER TO OWNER.
REMOVE ASSOCIATED
REFRIGERANT PIPING & PIPING
HANGERS. EXISTING AHU
HANGERS TO REMAIN.
FCU-2-E
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
CU-2-E
SG-E
12x6/200
(TYP.)
x6
S A x6
S A
EXISTING STEAM COIL
TO REMAIN
SC-E
CU-3-E
REMOVE, SALVAGE, & PROTECT
EXISTING CONDENSING UNIT & TURN
OVER TO OWNER
REMOVE EXISTING
CONDENSING UNIT
RECOMMENDED
DUCT TRAVERSE
LOCATION
REMOVE EXISTING
THERMOSTAT AND CONTROL
WIRING. EXISTING CONDUITS
TO REMAIN.
1/2"DPP
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M101
LEVEL 01 DEMOLITION PLAN - HVAC
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
LEVEL 01 DEMOLITION PLAN - UNIT A - HVAC
KEYNOTES:
1. CONDENSING UNIT IS INSTALLED ON GRADE
ON PAD OUTSIDE OF BUILDING.
EXISTING LOUVER
EXISTING STEAM
COIL TO REMAIN
SG-E
12x6/200
(TYP.)
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
BEFORE ANY DEMOLITION WORK IS
BEGUN, AN AIR BALANCE TEST SHALL BE
PERFORMED BY THE TESTING,
ADJUSTING AND BALANCING (TAB)
CONTRACTOR.
REMOVE EXISTING FAN COIL,
CONDENSING UNIT, AND
ASSOCIATED REFRIGERANT
PIPING, AND PIPING
HANGERS. EXISTING AHU
HANGERS TO REMAIN.
MOD-E
FCU-3-E
2 1/2"HWS
1 1/2"HWR
1/2"SUC
1/2"SUC
SC-E
RECOMMENDED
DUCT TRAVERSE
LOCATION
REMOVE EXISTING
THERMOSTAT AND CONTROL
WIRING. EXISTING
CONDUITS TO REMAIN.
1/2"DPP
CU-1-E
EXISTING LOUVER1 1/2"HWR
2 1/2"HWS
1/2"SUC
1/2"LIQ
1/2"SUC
1/2"LIQ
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
SC-E
SG-E
12x6/200
(TYP.)
FCU-1 (E)
EG-E
8/150
EG-E
8/150
12x6 EA
12x6 EA
12x12 EA UP
REMOVE EXISTING FAN COIL,
CONDENSING UNIT, AND
ASSOCIATED REFRIGERANT
PIPING, AND PIPING
HANGERS. EXISTING AHU
HANGERS TO REMAIN
MOD-E
EXISTING STEAM COIL TO REMAIN
TO CU-1-E
RECOMMENDED
DUCT TRAVERSE
LOCATION
REMOVE EXISTING
THERMOSTAT AND CONTROL
WIRING. EXISTING
CONDUITS TO REMAIN.
CONDENSING
UNIT IS INSTALLED
ON GRADE ON
PAD OUTSIDE OF
BUILDING
1/2"DPP
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M102
LEVEL 02 DEMOLITION PLAN - HVAC
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
LEVEL 02 DEMOLITION PLAN - UNIT A - HVAC
N O R
HT
1/4" = 1'-0"2
LEVEL 02 DEMOLITION PLAN - UNIT B - HVAC
KEYNOTES:
1. RETURN AND OA DAMPERS ARE TO REMAIN.
1 1/2"HWR
2 1/2"HWS
1 1/2"DPP
ROUTE REFRIGERANT
PIPES TO NEW
CONDENSING UNIT
REUSE EXISTING
EXTERIOR WALL
PENETRATION
REFRIGERANT PIPES
UP TO FCU-3
REFRIGERANT PIPES
UP TO FCU-2
2 1/2"HWS
2 1/2"HWS
1 1/2"HWR
1 1/2"DPP
1 1/2"HWR
2 1/2"HWS
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M210
BASEMENT PLAN - VENTILATION
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
BASEMENT PLAN - UNIT A - VENTILATION
N O R
HT
1/4" = 1'-0"2
BASEMENT PLAN - UNIT B - VENTILATION
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
EG-E
8/150
EG-E
8/150
12x6 EA
8x8 EA
EF-2 (E)
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
SG-E
12x6/200
(TYP.)
CU-2
FCU-2
x6
S A x6
S A
SC-E
INSTALL NEW THERMOSTAT WITH
LOCKING COVER IN SAME LOCATION
AS PREVIOUSLY REMOVED
THERMOSTAT. REUSE EXSTING
CONDUIT.
CU-3
TO FCU-2
ROUTE REFRIGERANT
PIPES TO NEW
CONDENSING UNIT
REFRIGERANT PIPES
UP TO FCU-3
REFRIGERANT
PIPING ROUTED
FROM FCUS
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M211
LEVEL 01 PLAN - VENTILATION
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
LEVEL 01 PLAN - UNIT A - VENTILATION
KEYNOTES:
1. NEW DUCTWORK SHALL HAVE PAINT GRIP AND
BE PAINTED TO MATCH EXISTING DUCTWORK.
COORDINATE WITH NCCF FOR SAMPLE
MATCHING.
2. INSTALL CONDENSING UNIT ON EXISTING PAD
IN SAME LOCATION AS PREVIOUSLY REMOVED
CONDENSING UNIT.
3. ROUTE CONDENSATE PIPING UNDER UNIT
TIGHT TO UNDERSIDE OF UNIT. ROUTE PIPING
NEXT TO ANGLE SUPPORTING FCU.
4. TIE INTO EXISTING CONDENSATE PIPING.
EXISTING 5'-0" x 3'-0" LOUVER
SG-E
12x6/200
(TYP.)
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
2 1/2"HWS
1 1/2"HWR
SC-E
FCU-3
INSTALL NEW THERMOSTAT
WITH LOCKING COVER IN SAME
LOCATION AS PREVIOUSLY
REMOVED THERMOSTAT.
REUSE EXSTING CONDUIT.
1/2"DPP
x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A x1
S
A
SC-E
SG-E
12x6/200
(TYP.)
EXISTING 5'-0" x 3'-0"
LOUVER
EG-E
8/150
12x6 EA
12x6 EA
12x12 EA UP
EG-E
8/150
1 1/2"HWR
2 1/2"HWS
FCU-1 CU-1
TO CU-1
INSTALL NEW THERMOSTAT WITH
LOCKING COVER IN SAME LOCATION
AS PREVIOUSLY REMOVED
THERMOSTAT. REUSE EXSTING
CONDUIT.
INSTALL
CONDENSING
UNIT ON GRADE
ON PAD OUTSIDE
OF BUILDING
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/4" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M212
LEVEL 02 PLAN - VENTILATION
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/4" = 1'-0"1
LEVEL 02 PLAN - UNIT A - VENTILATION
N O R
HT
1/4" = 1'-0"2
LEVEL 02 PLAN - UNIT B - VENTILATION
KEYNOTES:
1. ROUTE REFRIGERANT PIPES TO NEW
CONDENSING UNIT. REUSE THE SAME
EXTERIOR WALL PENETRATION EXISTING SPLIT
SYSTEM USED.
2. NEW DUCTWORK SHALL HAVE PAINT GRIP AND
BE PAINTED TO MATCH EXISTING DUCTWORK.
COORDINATE WITH NCCF FOR SAMPLE
MATCHING.
3. ROUTE CONDENSATE PIPING UNDER UNIT
TIGHT TO UNDERSIDE OF UNIT. ROUTE PIPING
NEXT TO ANGLE SUPPORTING FCU.
4. TIE INTO EXISTING CONDENSATE PIPING.
RISER CLAMP:
CLAMP TO WALL
SEAL OPENING,
FIRESTOP IF REQUIRED.
FLOOR
THREADED ROD
CLEVIS HANGER
NOTES:
1. REFER TO SPECIFICATION SECTION 23 05 29.
CLEVIS HANGER
EXISTING THREADED RODS
UP TO STRUCTURE ABOVE
(TYP OF 4)
FLEXIBLE DUCT
CONNECTOR (TYP. AT
BOTH ENDS)
CONDENSATE DRAIN LINE.
SEE DETAIL 3/M400
REUSE EXISTING STEEL
SUPPORT ANGLES AND
ALL-THREAD (TYP. OF 2)
RETURN DUCT
(FCU-1 & FCU-3)
FILTER ACCESS
COIL SECTION FAN SECTION
SUPPLY DUCT
1" THICK NEOPRENE PAD
BETWEEN FCU AND
SUPPORT ANGLE (TYP. OF 4)
DO NOT BLOCK ACCESS TO
CIRCUIT BREAKER OR
CONTROL PANEL
REUSE EXISTING DUCT
SMOKE DETECTOR
NOTES:
1. DUCT SMOKE DETECTORS SHALL BE WIRED TO SHUT DOWN
UNIT UPON DETECTION OF SMOKE AND SHALL BE CONNECTED
TO THE BUILDING FIRE ALARM SYSTEM.
INSTALL ULINE ADHESIVE EDGE
GUARD H-10841 (OR SIMILAR
PRODUCT) FOR HEAD
PROTECTION (TYP. 2)
CLEANOUT PLUG (TYP.)
ROUTE AS INDICATED ON
PLAN.
FULL SIZE CONDENSATE
DRAIN, CONNECT TO DRAIN
PAN AS RECOMMENDED BY
MANUFACTURER.
.5
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
12" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M400
HVAC DETAILS
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
NO SCALE1
PIPE SUPPORT
NO SCALE2
FAN COIL UNIT SUPPORT
NO SCALE3
CONDENSATE TRAP - DRAW THROUGH COIL
AI
DI
DO
T CS
LD
PRE-
FILTER
FAN
STATUS
START /
STOP
FCU
SUPPLY
FAN
REF
REF
WALL MTD
TEMP SENSOR. TCC
SHALL PULL NEW WIRE
THROUGH EXISTING
CONDUITS. SEE PLANS
FOR LOCATION.
RETURN
AIR
SUPPLY
AIR
COOLING
COIL
PROVIDE UL508 WATER-
LEVEL DETECTION DEVICE
IN PRIMARY DRAIN PAN
SEQUENCE OF OPERATION:
SUPPLY FAN OPERATION SHALL BE CONTROLLED BY THE FMCS THROUGH A
CONTACTOR. THE UNIT SHALL MAINTAIN A ROOM AIR TEMPERATURE SETPOINT.
THE FMCS SHALL MODULATE THE CONDENSING UNIT OPERATION TO MAINTAIN
A SPACE TEMPERATURE SETPOINT OF 75°F (ADJ.) WITH 5°F (ADJ.) DEAD BAND
BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SPACES
WITH ADJUSTABLE THERMOSTATS WILL ALLOW +/- 3°F (ADJ.) OFFSET FROM THE
DDC SETPOINT.
IF ROOM AIR TEMPERATURE IS MAINTAINED AND CONDENSING UNIT IS OFF, THE
SUPPLY FAN SHALL BE DE-ENERGIZED.
ALARMS, INTERLOCKS & SAFETIES:
WHEN THE FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, FCU
SHALL SHUTDOWN.
FMCS SHALL INDICATE AN ALARM TO THE FMCS OPERATOR WORKSTATION IF
THE FMCS COMMANDS ANY SUPPLY FAN TO OPERATE AND THE FAN CURRENT
RELAY DETECTS INSUFFICIENT CURRENT FLOW.
WHENEVER FCU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:
• SUPPLY FAN SHALL BE DE-ENERGIZED.
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
12" = 1'-0"
/2
/2
:0
:2
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
M500
HVAC SCHEDULES
NKJ
NKJ
EJH
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
NOTES:
1. COOLING ONLY UNIT. EXISTING STEAM COIL TO BE REUSED.
2. UNIT TO INTEGRATE INTO EXISTING BAS. REFER TO FCU-A ON THIS SHEET FOR LIMITED CONTROLS SCOPE.
INDOOR UNIT SCHEDULE
TAG
NAME
CFM
EXTERNAL STATIC
PRESSURE (IN. W.C.)
ASSOC
OUTDOOR
UNIT
REFRIGERANT
NOMINAL
TONS
ELECTRICAL FILTER MAXIMUM DIMENSIONS
WEIGHT
(LBS) MANUFACTURER MODEL NOTESDESIGN TYPE VOLTS PH FLA MCA
DISCONNECT CNTLR/STARTER
SCCR TYPE MERV WIDTH HEIGHT DEPTHBY [A] TYPE [B] BY [A] TYPE [C]
FCU-1 4,100 0.8 CU-1 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1
FCU-2 4,100 0.8 CU-2 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1
FCU-3 4,100 0.8 CU-3 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1
NOTES:
1. PLACE CONDENSING UNIT ON EXISTING CONDENSING UNIT PAD.
2. PROVIDE FILTER SCREEN ON CONDENSING UNIT PER PARAGRAPH 2.9 OF SECTION 23 62 13.
CONDENSING UNIT SCHEDULE - COOLING (CU)
TAG
NAME
AMBIENT
SUMMER DRY
BULB (°FDB)
ASSOC.
INDOOR
UNIT
REFRIGERAN
T TYPE
COOLING ELECTRICAL MAXIMUM DIMENSIONS
WEIGHT (LBS) MANUFACTURER MODEL NOTESTONS # OF STAGES IEER VOLTS PH MCA MOCP
DISCONNECT CNTLR/STARTER
SCCR WIDTH HEIGHT DEPTHBY [A] TYPE [B] BY [A] TYPE [C]
CU-1 95 FCU-1 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2
CU-2 95 FCU-2 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2
CU-3 95 FCU-3 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2
NO SCALE1
FAN COIL UNIT CONTROL - COOLING ONLY - FCU-A
1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
2. EMERGENCY BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS SHALL BE ROUTED IN
SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS. WIRING FOR EACH
BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING THE NORMAL
BRANCH.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND
REQUIREMENTS SPECIFIC TO FIRESTOPPING.
4. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF,
AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF
ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE
APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
5. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL
REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
CONDITIONS AND REPORT CONFLICTS.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CONDUIT
RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE NECESSARY BECAUSE OF
EXISTING FIELD CONDITIONS.
4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,
AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,
PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY
COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF
APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC
CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER
TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC EMT
X
X
X
X
INTERIOR LOCATIONS WITH FINISHED CEILING AND WALLS: CONCEALED
IN WALLS AND ABOVE FINISHED CEILINGS
INTERIOR LOCATIONS WITHOUT FINISHED CEILINGS: CONCEALED IN
WALL, EXPOSED ABOVE CEILINGS
EXISTING INTERIOR LOCATIONS WITH FINISHED CEILINGS AND WALLS:
CONCEALED IN WALLS AND ABOVE FINISHED CEILING UNLESS
OTHERWISE NOTED
X
X
X
ELECTRICAL MOUNTING SUBSCRIPT KEY:
SM SURFACE MOUNTED
+#" MOUNT AT #" TO CENTERLINE ABOVE FINISHED FLOOR
RECEPTACLE SUBSCRIPT KEY:
DEVICE
# = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
DEVICE KEY:
SHADED DEVICE INDICATES DEVICE IS CONNECTED TO AN EMERGENCY CIRCUIT.
DEVICE E
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
NATE JACQUES
EVAN HAMMER
TONY DELOUIS
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2024 EDITION
FIRE CODE: IFC 2024 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
ENERGY CONSERVATION CODE: IECC 2012
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
ELECTRICAL SYMBOL LIST - POWER
SYMBOL
EQUIP
ABBREV
SPEC
SECTION
DESCRIPTION
E ECONN 26 05 33 ELECTRICAL CONNECTION - CEILING/SURFACE
-- -- EXISTING PANELBOARD - SURFACE MOUNT
MX-# 26 24 19
MANUAL SWITCH, REFER TO DISCONNECT AND
STARTER SCHEDULE
FDS-# 26 28 16
FUSIBLE DISCONNECT SWITCH, REFER TO
DISCONNECT AND STARTER SCHEDULE
ELECTRICAL SYMBOL LIST - RECEPTACLES
SYMBOL TAG EQUIP ABBREV
SPEC
SECTION
DESCRIPTION
W REC-DUP-WP 26 27 26
DUPLEX GFI WEATHERPROOF RECEPTACLE,
125V - NEMA 3R WHILE IN-USE COVER
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
As indicated
/2
/2
:0
:0
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
E000
ELECTRICAL COVERSHEET
TONDEL
SENDIZ
KYHIL
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
ELECTRICAL SHEET INDEX
E000 ELECTRICAL COVERSHEET
E100 DEMOLITION FLOOR PLAN - ELECTRICAL
E200 NEW FLOOR PLAN - ELECTRICAL
E700 ELECTRICAL PANEL SCHEDULES
GRAND TOTAL: 4
Joshua.K.Hill Snapshot
E
E
E
E
E E
E
PANEL UA-P3
EXISTING PANEL UA-P2EXISTING PANEL UA-P1
FACP
EXISTING PANEL UB-P2
PANEL UB-P1
PANEL UB-P3
FACP
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
CU-2-E
W
MX-FCU-2-E
CU-3-E
FDS-CU-3-E
FDS-CU-2-E
FCU-2-E
EF-2 (E)
UA3
UA3
UA3
UA3
13UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
FDS-FCU-3-E
FCU-3-E
FDS-FCU-1-E
FDS-CU-1-E
FCU-1-E
CU-1-E
LOCATED AT
GRADE
CU-E
FDS-CU-E
EXISTING
UNUSED BOX
LOCATED AT
GRADE
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/8" = 1'-0"
/2
/2
:0
:0
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
E100
DEMOLITION FLOOR PLAN -
ELECTRICAL
TONDEL
SENDIZ
KYHIL
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/8" = 1'-0"1
BASEMENT DEMOLITION PLAN -
UNIT A - ELECTRICAL
N O R
HT
1/8" = 1'-0"4
BASEMENT DEMOLITION PLAN -
UNIT B - ELECTRICAL
N O R
HT
1/8" = 1'-0"2
LEVEL 01 DEMOLITION PLAN -
UNIT A - ELECTRICAL
N O R
HT
1/8" = 1'-0"3
LEVEL 02 DEMOLITION PLAN -
UNIT A - ELECTRICAL
N O R
HT
1/8" = 1'-0"5
LEVEL 02 DEMOLITION PLAN -
UNIT B - ELECTRICAL
KEYNOTES:
1. REMOVE EXISTING ELECTRICAL DISCONNECT
AND CONNECTION TO EQUIPMENT. CIRCUIT
SHALL REMAIN AND BE UTILIZED FOR NEW
EQUIPMENT IN NEW WORK PHASE.
2. REMOVE AND STORE EXISTING FIRE ALARM DUCT
SMOKE DETECTOR AND CONTROL MODULE FROM
FCU. EXISTING FIRE ALARM SERVICE SHALL BE
MAINTAINED DURING CONSTRUCTION AND RE-
INSTALLED TO NEW EQUIPMENT IN NEW WORK
PHASE.
3. INDOOR/OUTDOOR FIRST FLOOR EQUIPMENT
DISCONNECTS ARE TO BE SALVAGED AND
TURNED OVER TO OWNER.
4. REMOVE THE ELECTRICAL BOX AND ASSOCIATED
CONDUIT ROUTED UP THE WALL. PATCH WALL
AND MATCH EXISTING FINISH. CONDUIT THAT
TRANSITIONS UNDERGROUND TO BE CAPPED.
E
E
E
E E
E
PANEL UA-P3
EXISTING PANEL UA-P2EXISTING PANEL UA-P1
FACP
EXISTING PANEL UB-P2
PANEL UB-P1
PANEL UB-P3
FACP
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
UA2
CU-3
CU-2
DS-CU-2
DS-CU-3
DS-FCU-2
FCU-2
EF-2 (E)
UA3
UA3
UA3
UA3
13UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
UA3
DS-FCU-3 FCU-3
DS-FCU-1
FCU-1
2 CU-1
DS-CU-1
LOCATED AT
GRADE
CU-E
FDS-CU-E
W
UB-P2-8
LOCATED AT
GRADE
INSTALL NEW
DEVICE AT 20"
ABOVE FINISHED
GRADE.
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
1/8" = 1'-0"
/2
/2
:0
:1
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
E200
NEW FLOOR PLAN - ELECTRICAL
TONDEL
SENDIZ
KYHIL
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
N O R
HT
1/8" = 1'-0"1
BASEMENT NEW PLAN - UNIT A -
ELECTRICAL
N O R
HT
1/8" = 1'-0"4
BASEMENT NEW PLAN - UNIT B -
ELECTRICAL
N O R
HT
1/8" = 1'-0"2
LEVEL 01 NEW PLAN - UNIT A -
ELECTRICAL
N O R
HT
1/8" = 1'-0"3
LEVEL 02 NEW PLAN - UNIT A -
ELECTRICAL
N O R
HT
1/8" = 1'-0"5
LEVEL 02 NEW PLAN - UNIT B -
ELECTRICAL
KEYNOTES:
1. PROVIDE NEW DISCONNECT AND CONNECT
EXISTING ELECTRICAL CONNECTION. EXTEND
CIRCUIT AS NECESSARY FOR RECONNECTION.
NEW WIRE AND CONDUIT SHALL MATCH
EXISTING. INSTALL NEW DISCONNECT AT
EXISTING DISCONNECT LOCATION.
2. CONNECT EXISTING FIRE ALARM DUCT SMOKE
DETECTOR AND CONTROL MODULE BACK TO
FCU CONTROLLER AND DUCTWORK.
3. PROVIDE NEW 3#12 & 1#12 EGC IN 3/4" C. FROM
UA-P1 TO NEW UNIT. PROVIDE NEW 20A/3P
BREAKER IN UA-P1.
SHEET NOTE:
1. NEW MECHANICAL EQUIPMENT TO BE
INSTALLED ON EXISTING CONCRETE PADS.
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2026 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #26001283.00
/2
/2
:0
:1
P
M
Iowa Department of Administratinve Services
313 LANEDALE
ROCKWELL CITY, IOWA 50579
IDAS 9501.00 DOC NCCF
AIR HANDLER
REPLACEMENT
E700
ELECTRICAL PANEL SCHEDULES
TONDEL
SENDIZ
KYHIL
26001283.00
4/29/2026
100% CD
ID
A
S
.0
D
O C
N C
C F
A
IR
H A
N D
L E
R R
E P
L A
C E
M E
N T
.0
CIRCUIT KEY NOTES: *NB = NEW BREAKER.
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 13.8
TOTAL CONNECTED AMPS: 13.80 A
TOTAL ESTIMATED DEMAND LOAD: 4.972 kVA
TOTAL CONNECTED LOAD: 4.97 kVA
Power 4.972 kVA 100% 4.972 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 13.81 13.81 13.81
Total Load: 1.66 kVA 1.66 kVA 1.66 kVA
41 0 0 42
WEST DRYER 30 2
0 0 40
37 0 0
3 100 UA-P3
MIDDLE DRYER 30 2
0 0 36
33 0 0
2 50 WELDING REC
EAST DRYER 30 2
0 0 1 20 SPARE 32
29 SPARE 20 1 0 0 1 20 VENDING REC 30
27 SPARE 20 1 0 0 1 20 SPARE 28
25 VENDING REC 20 1 0 0 1 20 HALL OFFNET/BASEMENT... 26
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPACE -- 1 -- -- 1 -- SPACE 12
9 SPACE -- 1 -- -- 1 -- SPACE 10
7 SPACE -- 1 -- -- 1 -- SPACE 8
5 1.66 -- 1 -- SPACE 6
3 1.66 -- 1 -- SPACE 4*NB
FCU-2 20 3 12 12 12 0.84
1.66 -- 1 -- SPACE 2
K E Y
CK
T
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
A B C VD
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CK
T
NO.
K E Y
NOTES:
BOLD INDICATES NEW WORK.
PANEL TOTALS ONLY SHOW NEW LOADS.
NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.
ISC UNKNOWN 0.00 kA
SCCR: 10 kA
LOCATION: WIRE: 4
FED FROM: 0/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE SINGLE TUB MAIN: 400 MLO
EXISTING PANEL UA-P1
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 0
TOTAL CONNECTED AMPS: 0.00 A
TOTAL ESTIMATED DEMAND LOAD: 0.000 kVA
TOTAL CONNECTED LOAD: 0.00 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 0.00 0.00 0.00
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA
23 0 0 24
21 0 0 22
1 ST FLOOR A/C 60 3
0 0
3 60 2ND FLOOR A/C
17 0 0 1 20 24 VAC CONTRL 18
15 0 0 1 20 STEAM VALVE 16
KITCHENETTE REC 20 3
0 0 1 20 EXHAUST FAN-BASEMENT 14
11 EXHAUST FAN 20 1 0 0 12
9 SPACE -- 1 -- 0
2 20 SPARE
7 FACP 20 1 0 0 8
5 0 0 6
3 0 0
3 20 KITCHENETTE REC
2 ND FLOOR AHU 20 3
0 -- 1 -- UNUSABLE 2
K E Y
CK
T
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
A B C VD
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CK
T
NO.
K E Y
NOTES:
BOLD INDICATES NEW WORK.
PANEL TOTALS ONLY SHOW NEW LOADS.
NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.
ISC UNKNOWN 0.00 kA
SCCR: 10 kA
LOCATION: WIRE: 4
FED FROM: 0/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE SINGLE TUB MAIN: 100 MCB
EXISTING PANEL UA-P2
CIRCUIT KEY NOTES: *NB = NEW BREAKER.
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 0.5
TOTAL CONNECTED AMPS: 0.50 A
TOTAL ESTIMATED DEMAND LOAD: 0.180 kVA
TOTAL CONNECTED LOAD: 0.18 kVA
Receptacles 0.180 kVA 100% 0.180 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 1.50 0.00 0.00
Total Load: 0.18 kVA 0.00 kVA 0.00 kVA
23 0 0 24
21 0 0 22
SPARE 60 3
0 0
3 60 NEW AIR COND
17 SPARE 20 1 0 0 18
15 SPARE 20 1 0 0
2 20 WELD REC
13 0 0 1 20 SIEMENS CONTROL 14
SPARE 20 2
0 -- 1 -- SPACE 12
9 0 -- 1 -- SPACE 10
SPARE 20 2
0 0.18 0.27 12 12 12 1 20 OUTDOOR RECEPT. 8 *NB
5 SPARE 20 1 0 0 6
3 SPACE -- 1 -- 0 4
1 SPACE -- 1 -- 0
3 20 2ND FLOOR AHU
K E Y
CK
T
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
A B C VD
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CK
T
NO.
K E Y
NOTES:
BOLD INDICATES NEW WORK.
PANEL TOTALS ONLY SHOW NEW LOADS.
NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.
ISC UNKNOWN 0.00 kA
SCCR: 10 kA
LOCATION: WIRE: 4
FED FROM: 0/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE SINGLE TUB MAIN: 100 MCB
EXISTING PANEL UB-P2
AMS-ASSEMBLED MOTOR STARTER
FS - FUSED SWITCH
MX - MANUAL SWITCH
MS - MANUAL STARTER
SS - SOLID STATE
RV - REDUCED VOLTAGE AUTOXFMR
SW - 2 SPEED, 1 WINDING
TW - 2 SPEED, 2 WINDING
RE - REVERSING HL - HANDLE PADLOCK HASP
YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR
FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.
STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS
*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR
CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR
NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)
FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE MOTOR)
DISCONNECT TYPE: ACCESSORIES & OPTIONS
NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.
DISCONNECT AND STARTER SCHEDULE
ITEM
DISCONNECT TYPE &
RATING
VOLTAGE POLES
STARTER
ENCLOSURE
REQUIRED
ACCESSORIES &
OPTIONS COMMENTSTYPE RATING
TRIP
RATING
NEMA
SIZE TYPE
DS-CU-1 NF 60 208 3 NEMA 3R HL
DS-CU-2 NF 60 208 3 NEMA 3R HL
DS-CU-3 NF 60 208 3 NEMA 3R HL
DS-FCU-1 NF 30 208 3 NEMA 1 HL
DS-FCU-2 NF 30 208 3 NEMA 1 HL
DS-FCU-3 NF 30 208 3 NEMA 1 HL
| Sheets |
| G000 - PROJECT COVERSHEET |