RFB950100-01 - Drawings.pdf

PDF 4 MB Posted

Attached to
DOC NCCF Air Handler Replacement and Condenser Coils Unit A and B
Solicitation number
RFB950100-01
Issued by
Calhoun County, Iowa

About this file

This is a set of technical drawings and specifications for an HVAC air handler replacement project issued by the Iowa Department of Administrative Services (IDAS) for the North Central Community College Foundation (NCCF) facility located at 313 Lanedale, Rockwell City, Iowa. The project involves providing three new cooling-only DX fan coil units (FCU-1, FCU-2, and FCU-3) to replace two existing units and one unit to be salvaged and returned to the owner. Associated condensing units (CU-1, CU-2, and CU-3) will be replaced, with one existing condensing unit to be salvaged. The scope includes removal of old refrigerant piping, installation of new refrigerant piping and condensate drain lines, ductwork modifications, and electrical work including new disconnects and circuit breaker connections. The drawings are dated April 29, 2026, and indicate 100% Construction Documents (CD) phase with professional seals from mechanical engineer Evan Hammer and electrical engineer Tony DeLouis of IMEG Consultants Corp.

The project specifies Daikin DAQ12033 fan coil units rated at 4,100 CFM with R-32 refrigerant, 10-ton capacity, and 208V/3-phase electrical service requiring 13.8 FLA per unit. Daikin DC6TE120 condensing units are specified at 10 tons, 2-stage cooling with 16.4 IEER rating, also 208V/3-phase at 46 MCA. Equipment will be installed on existing concrete pads with new disconnect switches and circuit breakers provided through existing electrical panels (UA-P1 and UB-P2). The project incorporates applicable codes including IBC 2024, IFC 2024, IMC 2021, NFPA 70 (NEC) 2023, and IECC 2012. Testing, adjusting, and balancing (TAB) services are required both pre-demolition and post-construction to verify airflow and duct static pressure readings, with final reports due within 10 working days of field measurements. Fire alarm duct smoke detectors will be reinstalled, and all refrigerant reclamation must comply with authority having jurisdiction requirements.

View the file

Other files

File Type Posted
RFB950100-01 - Project Manual.pdf PDF
RFB950100-01 - Bid Form.pdf PDF
RFB950100-01 - Notice to Bidders.docx DOCX document
1389405-event.pdf PDF
Bidding Documents and Project Manual.html HTML file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

OSHPD #

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT DIRECTORY

CLIENT:

SCOPE OF WORK

PROVIDING THREE NEW COOLING ONLY, DX FAN COIL UNITS TO REPLACE

TWO OLD UNITS AND ONE UNIT THAT IS TO BE SALVAGED AND HANDED

OVER TO THE OWNER. CONDENSING UNITS SHALL BE REPLACED AND

SALVAGED AS NOTED ON PLAN.

MECHANICAL

ENGINEER:

APPLICABLE CODES DRAWING INDEX

BUILDING CODE: IBC 2024 EDITION

FIRE CODE: IFC 2024 EDITION

PLUMBING CODE: UPC 2024 EDITION

MECHANICAL CODE: IMC 2024 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION

LIFE SAFETY CODE: NFPA 101 2012 EDITION

ENERGY CONSERVATION CODE: IECC 2012

EVAN HAMMER

2882 106TH STREET

DES MOINES, IA 50322

PHONE: 515-334-7934

EMAIL:Evan.J.Hammer@imegcorp.com

ELECTRICAL

ENGINEER:

TONY DELOUIS

2882 106TH STREET

PHONE: 515-334-4317

EMAIL: Tony.E.DeLouis@imegcorp.com

VICINITY MAP

PROJECT #26001283.00

PROJECT VICINITY

PROJECT LOCATION

/2

/2

:2

:3

P

M

Iowa Department of Administratinve Services

G000

PROJECT COVERSHEET

Approver

Checker

Author

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

IDAS 9501.00 DOC NCCF AIR HANDLER REPLACEMENT

313 LANEDALE

ROCKWELL CITY, IOWA 50579

Iowa Department of Administratinve Services

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

Sheet List Number Name

PROJECT COVERSHEET

G000 PROJECT COVERSHEET

HVAC

M000 HVAC COVERSHEET

M100 BASEMENT DEMOLITION PLAN - HVAC

M101 LEVEL 01 DEMOLITION PLAN - HVAC

M102 LEVEL 02 DEMOLITION PLAN - HVAC

M210 BASEMENT PLAN - VENTILATION

M211 LEVEL 01 PLAN - VENTILATION

M212 LEVEL 02 PLAN - VENTILATION

M400 HVAC DETAILS

M500 HVAC SCHEDULES

ELECTRICAL

E000 ELECTRICAL COVERSHEET

E100 DEMOLITION FLOOR PLAN - ELECTRICAL

E200 NEW FLOOR PLAN - ELECTRICAL

E700 ELECTRICAL PANEL SCHEDULES

HVAC ABBREVIATION KEY

ABBR: DESCRIPTION:

ABOVE FINISHED FLOORAFF

NOT IN CONTRACTNIC

TYPICALTYP

UON UNLESS OTHERWISE NOTED

CO CLEANOUT

SCCR SHORT CIRCUIT CURRENT RATING

DN DOWN

1. UNLESS NOTED OTHERWISE, DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR

DIMENSIONS. MAINTAIN CLEAR DIMENSIONS INSIDE ANY LINING

2. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.

3. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING

DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE

VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.

4. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE

CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL

TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED

AS SPECIFIED FOR NEW DUCTWORK.

VENTILATION GENERAL NOTES:

1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.

2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT

MANUFACTURER RECOMMENDATIONS.

PIPING GENERAL NOTES:

1. BEFORE ANY DEMOLITION WORK IS BEGUN, AN AIR BALANCE TEST SHALL BE PERFORMED

BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR FOR EQUIPMENT AND

DEVICES AS INDICATED ON THE DRAWINGS.

2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS.

A. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS

INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE

TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT

TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW

READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT

TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL

INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL

MEASUREMENTS WERE TAKEN.

B. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT

TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB

REPORT.

3. TAB CONTRACTOR SHALL COMPILE AND SUBMIT THE FINAL PRE-DEMOLITION REPORT

WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB

REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL

INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

TAB PRE-DEMOLITION NOTES:

1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND

BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AS REQUIRED TO

ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.

2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-

BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED

(REFER TO THE FINAL PRE- DEMOLITION REPORT).

3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR

MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE

LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS

REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN

ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE

LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.

4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT

TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION

TAB REPORT.

5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-

CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.

6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE

SPECIFICATIONS.

TAB POST-CONSTRUCTION NOTES:

MECHANICAL GENERAL NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO VENTILATION, & PIPING.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE

DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.

DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,

AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE

INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING

CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. CATALOG AND MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN

AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR

IS RESPONSIBLE FOR THE COMPLETE DESCRIPTION OF MATERIAL SCHEDULED ON THESE

DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE

MATERIAL AND SCHEDULED PERFORMANCE TAKES PRECEDENCE OVER THE MODEL

NUMBER. THE FIRST MANUFACTURER SCHEDULED IS THE BASIS OF DESIGN.

3. DETERMINATION OF QUANTITIES OF MATERIAL AND EQUIPMENT REQUIRED SHALL BE MADE

BY THE CONTRACTOR FROM THE DOCUMENTS. WHERE MATERIAL AND/OR QUANTITY

DISCREPANCIES ARISE BETWEEN DRAWINGS, SCHEDULES AND/OR SPECIFICATIONS, THE

HIGHER QUALITY/ GREATER NUMBER SHALL GOVERN.

4. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM

ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR

PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

5. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE

CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO

VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO

VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES

OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING

WITH FABRICATION OR EQUIPMENT ORDERS.

6. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE

REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER

ACCESS.

7. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO

COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR

EXPENSE TO OTHERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL

CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF

DESIGN.

9. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,

FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS

RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

10. SEAL ALL FLOOR & WALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS

PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS SHALL BE SEALED AIRTIGHT WITH

WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED

OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL

RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

12. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT

MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND

REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,

PIPING, DUCTWORK, ETC.

13. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.

14. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL

EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT

LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,

TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.

15. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH

OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE

EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO

THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED

ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.

MECHANICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO VENTILATION & PIPING.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS

BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE

FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD

CONDITIONS.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF

WALLS AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

6. WHERE EXISTING MECHANICAL SYSTEMS DIFFER FROM THOSE SHOWN ON THE PROJECT

DRAWINGS AND CREATE CONFLICTS WITH NEW EQUIPMENT, PIPING, OR DUCTWORK

INSTALLATIONS, THE CONTRACTOR SHALL PROVIDE DETAILED DOCUMENTATION (SUCH AS

SKETCHES, PHOTOS, AND DIMENSIONS) ALONG WITH RECOMMENDATIONS TO RESOLVE

THE CONFLICT. THIS INFORMATION MUST BE SUBMITTED TO THE ENGINEER FOR REVIEW

AND APPROVAL. NO WORK RELATED TO THE CONFLICT SHALL PROCEED UNTIL AN

APPROVED RESOLUTION IS PROVIDED BY THE ENGINEER.

7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING

CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT

REMAIN ACTIVE.

8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY

REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW

SYSTEMS ARE INSTALLED.

9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR

TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND

CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY

DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT

THAT HAS BEEN REMOVED.

11. PROPERLY RECLAIM AND DISPOSE OF ALL REFRIGERANT IN REMOVED EQUIPMENT/

REFRIGERANT PIPING. RECLAIMED REFRIGERANT SHALL HAVE DOCUMENTATION AS

REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ).

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 KEYNOTE: INDICATES NOTE USED TO

DESCRIBE ADDITIONAL INFORMATION

ABOUT WORK REQUIRED, SPECIFIC

TO THE SHEET AND/OR DETAIL

N O R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

FIRE AND SMOKE SEPARATIONS ARE NOT SHOWN ON THESE DOCUMENTS. CONTRACTOR SHALL

REVIEW THE ARCHITECTURAL PLANS AND DETERMINE THE LOCATIONS OF ALL FIRE AND SMOKE

PARTITIONS, BARRIERS, AND WALLS. THIS INCLUDES FLOOR RATINGS. PRICING SHALL INCLUDE ALL MATERIALS AND LABOR REQUIRED TO MAINTAIN THE RATINGS OF ALL RATED SEPARATIONS, WHETHER SHOWN ON THE ENGINEERING PLANS OR NOT.

FIRE / SMOKE BARRIER DESIGNATIONS

BUILDING CODE: IBC 2024 EDITION

FIRE CODE: IFC 2024 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION

ENERGY CONSERVATION CODE: IECC 2012

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS

INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

NURSE CALL CONTRACTORN.C.C.

CIVIL CONTRACTORC.C.

ASBESTOS ABATEMENT CONTRACTOR

FIRE PROTECTION CONTRACTORF.P.C.

HEATING CONTRACTORH.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

CONSTRUCTION MANAGERC.M.

FOOD SERVICE CONTRACTORF.S.C.

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

NATE JACQUES

EVAN HAMMER

TONY DELOUIS

DESCRIPTION: PERSON:

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

As indicated

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M000

HVAC COVERSHEET

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

DUCT ABBREVIATION KEY

ABBR. DESCRIPTION

EA EXHAUST AIR

OA OUTSIDE AIR

SA SUPPLY AIR

SYMBOL LIST - PIPING SYSTEMS

SYMBOL DESCRIPTION º F FLUID TYPE

DPP DRAIN - PIPING

HWR HEATING WATER RETURN 150 Water

HWS HEATING WATER SUPPLY 180 Water

LIQ REFRIGERANT LIQUID 120 Water

SUC REFRIGERANT SUCTION 35 Water

HVAC SHEET INDEX

M000 HVAC COVERSHEET

M100 BASEMENT DEMOLITION PLAN - HVAC

M101 LEVEL 01 DEMOLITION PLAN - HVAC

M102 LEVEL 02 DEMOLITION PLAN - HVAC

M210 BASEMENT PLAN - VENTILATION

M211 LEVEL 01 PLAN - VENTILATION

M212 LEVEL 02 PLAN - VENTILATION

M400 HVAC DETAILS

M500 HVAC SCHEDULES

GRAND TOTAL: 9

04/29/2026

1 1/2"HWR

1/2"SUC

1/2"LIQ

2 1/2"HWS

1 1/2"DPP

1/2"LIQ

1/2"LIQ

1/2"SUC

1/2"SUC

2 1/2"HWS

2 1/2"HWS

1 1/2"HWR

1 1/2"DPP

1 1/2"HWR

2 1/2"HWS

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M100

BASEMENT DEMOLITION PLAN - HVAC

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

BASEMENT DEMOLITION PLAN - UNIT A - HVAC

N O R

HT

1/4" = 1'-0"2

BASEMENT DEMOLITION PLAN - UNIT B - HVAC

T

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

EG-E

8/150

EG-E

8/150

12x6 EA

8x8 EA

EF-2 (E)

BEFORE ANY DEMOLITION WORK IS

BEGUN, AN AIR BALANCE TEST SHALL BE

PERFORMED BY THE TESTING,

ADJUSTING AND BALANCING (TAB)

CONTRACTOR.

REMOVE, SALVAGE, &

PROTECT EXISTING FAN COIL &

TURN OVER TO OWNER.

REMOVE ASSOCIATED

REFRIGERANT PIPING & PIPING

HANGERS. EXISTING AHU

HANGERS TO REMAIN.

FCU-2-E

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

CU-2-E

SG-E

12x6/200

(TYP.)

x6

S A x6

S A

EXISTING STEAM COIL

TO REMAIN

SC-E

CU-3-E

REMOVE, SALVAGE, & PROTECT

EXISTING CONDENSING UNIT & TURN

OVER TO OWNER

REMOVE EXISTING

CONDENSING UNIT

RECOMMENDED

DUCT TRAVERSE

LOCATION

REMOVE EXISTING

THERMOSTAT AND CONTROL

WIRING. EXISTING CONDUITS

TO REMAIN.

1/2"DPP

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M101

LEVEL 01 DEMOLITION PLAN - HVAC

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

LEVEL 01 DEMOLITION PLAN - UNIT A - HVAC

KEYNOTES:

1. CONDENSING UNIT IS INSTALLED ON GRADE

ON PAD OUTSIDE OF BUILDING.

EXISTING LOUVER

EXISTING STEAM

COIL TO REMAIN

SG-E

12x6/200

(TYP.)

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

BEFORE ANY DEMOLITION WORK IS

BEGUN, AN AIR BALANCE TEST SHALL BE

PERFORMED BY THE TESTING,

ADJUSTING AND BALANCING (TAB)

CONTRACTOR.

REMOVE EXISTING FAN COIL,

CONDENSING UNIT, AND

ASSOCIATED REFRIGERANT

PIPING, AND PIPING

HANGERS. EXISTING AHU

HANGERS TO REMAIN.

MOD-E

FCU-3-E

2 1/2"HWS

1 1/2"HWR

1/2"SUC

1/2"SUC

SC-E

RECOMMENDED

DUCT TRAVERSE

LOCATION

REMOVE EXISTING

THERMOSTAT AND CONTROL

WIRING. EXISTING

CONDUITS TO REMAIN.

1/2"DPP

CU-1-E

EXISTING LOUVER1 1/2"HWR

2 1/2"HWS

1/2"SUC

1/2"LIQ

1/2"SUC

1/2"LIQ

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

SC-E

SG-E

12x6/200

(TYP.)

FCU-1 (E)

EG-E

8/150

EG-E

8/150

12x6 EA

12x6 EA

12x12 EA UP

REMOVE EXISTING FAN COIL,

CONDENSING UNIT, AND

ASSOCIATED REFRIGERANT

PIPING, AND PIPING

HANGERS. EXISTING AHU

HANGERS TO REMAIN

MOD-E

EXISTING STEAM COIL TO REMAIN

TO CU-1-E

RECOMMENDED

DUCT TRAVERSE

LOCATION

REMOVE EXISTING

THERMOSTAT AND CONTROL

WIRING. EXISTING

CONDUITS TO REMAIN.

CONDENSING

UNIT IS INSTALLED

ON GRADE ON

PAD OUTSIDE OF

BUILDING

1/2"DPP

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M102

LEVEL 02 DEMOLITION PLAN - HVAC

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

LEVEL 02 DEMOLITION PLAN - UNIT A - HVAC

N O R

HT

1/4" = 1'-0"2

LEVEL 02 DEMOLITION PLAN - UNIT B - HVAC

KEYNOTES:

1. RETURN AND OA DAMPERS ARE TO REMAIN.

1 1/2"HWR

2 1/2"HWS

1 1/2"DPP

ROUTE REFRIGERANT

PIPES TO NEW

CONDENSING UNIT

REUSE EXISTING

EXTERIOR WALL

PENETRATION

REFRIGERANT PIPES

UP TO FCU-3

REFRIGERANT PIPES

UP TO FCU-2

2 1/2"HWS

2 1/2"HWS

1 1/2"HWR

1 1/2"DPP

1 1/2"HWR

2 1/2"HWS

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M210

BASEMENT PLAN - VENTILATION

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

BASEMENT PLAN - UNIT A - VENTILATION

N O R

HT

1/4" = 1'-0"2

BASEMENT PLAN - UNIT B - VENTILATION

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

EG-E

8/150

EG-E

8/150

12x6 EA

8x8 EA

EF-2 (E)

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

SG-E

12x6/200

(TYP.)

CU-2

FCU-2

x6

S A x6

S A

SC-E

INSTALL NEW THERMOSTAT WITH

LOCKING COVER IN SAME LOCATION

AS PREVIOUSLY REMOVED

THERMOSTAT. REUSE EXSTING

CONDUIT.

CU-3

TO FCU-2

ROUTE REFRIGERANT

PIPES TO NEW

CONDENSING UNIT

REFRIGERANT PIPES

UP TO FCU-3

REFRIGERANT

PIPING ROUTED

FROM FCUS

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M211

LEVEL 01 PLAN - VENTILATION

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

LEVEL 01 PLAN - UNIT A - VENTILATION

KEYNOTES:

1. NEW DUCTWORK SHALL HAVE PAINT GRIP AND

BE PAINTED TO MATCH EXISTING DUCTWORK.

COORDINATE WITH NCCF FOR SAMPLE

MATCHING.

2. INSTALL CONDENSING UNIT ON EXISTING PAD

IN SAME LOCATION AS PREVIOUSLY REMOVED

CONDENSING UNIT.

3. ROUTE CONDENSATE PIPING UNDER UNIT

TIGHT TO UNDERSIDE OF UNIT. ROUTE PIPING

NEXT TO ANGLE SUPPORTING FCU.

4. TIE INTO EXISTING CONDENSATE PIPING.

EXISTING 5'-0" x 3'-0" LOUVER

SG-E

12x6/200

(TYP.)

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

2 1/2"HWS

1 1/2"HWR

SC-E

FCU-3

INSTALL NEW THERMOSTAT

WITH LOCKING COVER IN SAME

LOCATION AS PREVIOUSLY

REMOVED THERMOSTAT.

REUSE EXSTING CONDUIT.

1/2"DPP

x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A x1

S

A

SC-E

SG-E

12x6/200

(TYP.)

EXISTING 5'-0" x 3'-0"

LOUVER

EG-E

8/150

12x6 EA

12x6 EA

12x12 EA UP

EG-E

8/150

1 1/2"HWR

2 1/2"HWS

FCU-1 CU-1

TO CU-1

INSTALL NEW THERMOSTAT WITH

LOCKING COVER IN SAME LOCATION

AS PREVIOUSLY REMOVED

THERMOSTAT. REUSE EXSTING

CONDUIT.

INSTALL

CONDENSING

UNIT ON GRADE

ON PAD OUTSIDE

OF BUILDING

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/4" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M212

LEVEL 02 PLAN - VENTILATION

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/4" = 1'-0"1

LEVEL 02 PLAN - UNIT A - VENTILATION

N O R

HT

1/4" = 1'-0"2

LEVEL 02 PLAN - UNIT B - VENTILATION

KEYNOTES:

1. ROUTE REFRIGERANT PIPES TO NEW

CONDENSING UNIT. REUSE THE SAME

EXTERIOR WALL PENETRATION EXISTING SPLIT

SYSTEM USED.

2. NEW DUCTWORK SHALL HAVE PAINT GRIP AND

BE PAINTED TO MATCH EXISTING DUCTWORK.

COORDINATE WITH NCCF FOR SAMPLE

MATCHING.

3. ROUTE CONDENSATE PIPING UNDER UNIT

TIGHT TO UNDERSIDE OF UNIT. ROUTE PIPING

NEXT TO ANGLE SUPPORTING FCU.

4. TIE INTO EXISTING CONDENSATE PIPING.

RISER CLAMP:

CLAMP TO WALL

SEAL OPENING,

FIRESTOP IF REQUIRED.

FLOOR

THREADED ROD

CLEVIS HANGER

NOTES:

1. REFER TO SPECIFICATION SECTION 23 05 29.

CLEVIS HANGER

EXISTING THREADED RODS

UP TO STRUCTURE ABOVE

(TYP OF 4)

FLEXIBLE DUCT

CONNECTOR (TYP. AT

BOTH ENDS)

CONDENSATE DRAIN LINE.

SEE DETAIL 3/M400

REUSE EXISTING STEEL

SUPPORT ANGLES AND

ALL-THREAD (TYP. OF 2)

RETURN DUCT

(FCU-1 & FCU-3)

FILTER ACCESS

COIL SECTION FAN SECTION

SUPPLY DUCT

1" THICK NEOPRENE PAD

BETWEEN FCU AND

SUPPORT ANGLE (TYP. OF 4)

DO NOT BLOCK ACCESS TO

CIRCUIT BREAKER OR

CONTROL PANEL

REUSE EXISTING DUCT

SMOKE DETECTOR

NOTES:

1. DUCT SMOKE DETECTORS SHALL BE WIRED TO SHUT DOWN

UNIT UPON DETECTION OF SMOKE AND SHALL BE CONNECTED

TO THE BUILDING FIRE ALARM SYSTEM.

INSTALL ULINE ADHESIVE EDGE

GUARD H-10841 (OR SIMILAR

PRODUCT) FOR HEAD

PROTECTION (TYP. 2)

CLEANOUT PLUG (TYP.)

ROUTE AS INDICATED ON

PLAN.

FULL SIZE CONDENSATE

DRAIN, CONNECT TO DRAIN

PAN AS RECOMMENDED BY

MANUFACTURER.

.5

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

12" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M400

HVAC DETAILS

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

NO SCALE1

PIPE SUPPORT

NO SCALE2

FAN COIL UNIT SUPPORT

NO SCALE3

CONDENSATE TRAP - DRAW THROUGH COIL

AI

DI

DO

T CS

LD

PRE-

FILTER

FAN

STATUS

START /

STOP

FCU

SUPPLY

FAN

REF

REF

WALL MTD

TEMP SENSOR. TCC

SHALL PULL NEW WIRE

THROUGH EXISTING

CONDUITS. SEE PLANS

FOR LOCATION.

RETURN

AIR

SUPPLY

AIR

COOLING

COIL

PROVIDE UL508 WATER-

LEVEL DETECTION DEVICE

IN PRIMARY DRAIN PAN

SEQUENCE OF OPERATION:

SUPPLY FAN OPERATION SHALL BE CONTROLLED BY THE FMCS THROUGH A

CONTACTOR. THE UNIT SHALL MAINTAIN A ROOM AIR TEMPERATURE SETPOINT.

THE FMCS SHALL MODULATE THE CONDENSING UNIT OPERATION TO MAINTAIN

A SPACE TEMPERATURE SETPOINT OF 75°F (ADJ.) WITH 5°F (ADJ.) DEAD BAND

BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. SPACES

WITH ADJUSTABLE THERMOSTATS WILL ALLOW +/- 3°F (ADJ.) OFFSET FROM THE

DDC SETPOINT.

IF ROOM AIR TEMPERATURE IS MAINTAINED AND CONDENSING UNIT IS OFF, THE

SUPPLY FAN SHALL BE DE-ENERGIZED.

ALARMS, INTERLOCKS & SAFETIES:

WHEN THE FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, FCU

SHALL SHUTDOWN.

FMCS SHALL INDICATE AN ALARM TO THE FMCS OPERATOR WORKSTATION IF

THE FMCS COMMANDS ANY SUPPLY FAN TO OPERATE AND THE FAN CURRENT

RELAY DETECTS INSUFFICIENT CURRENT FLOW.

WHENEVER FCU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:

• SUPPLY FAN SHALL BE DE-ENERGIZED.

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

12" = 1'-0"

/2

/2

:0

:2

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

M500

HVAC SCHEDULES

NKJ

NKJ

EJH

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

NOTES:

1. COOLING ONLY UNIT. EXISTING STEAM COIL TO BE REUSED.

2. UNIT TO INTEGRATE INTO EXISTING BAS. REFER TO FCU-A ON THIS SHEET FOR LIMITED CONTROLS SCOPE.

INDOOR UNIT SCHEDULE

TAG

NAME

CFM

EXTERNAL STATIC

PRESSURE (IN. W.C.)

ASSOC

OUTDOOR

UNIT

REFRIGERANT

NOMINAL

TONS

ELECTRICAL FILTER MAXIMUM DIMENSIONS

WEIGHT

(LBS) MANUFACTURER MODEL NOTESDESIGN TYPE VOLTS PH FLA MCA

DISCONNECT CNTLR/STARTER

SCCR TYPE MERV WIDTH HEIGHT DEPTHBY [A] TYPE [B] BY [A] TYPE [C]

FCU-1 4,100 0.8 CU-1 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1

FCU-2 4,100 0.8 CU-2 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1

FCU-3 4,100 0.8 CU-3 R-32 10 208 3 13.8 15.5 EC NF MFR FV 5,000 DISPOSABLE 2" 8 48" 24" 60" 430 DAIKIN DAQ12033 NOTE 1

NOTES:

1. PLACE CONDENSING UNIT ON EXISTING CONDENSING UNIT PAD.

2. PROVIDE FILTER SCREEN ON CONDENSING UNIT PER PARAGRAPH 2.9 OF SECTION 23 62 13.

CONDENSING UNIT SCHEDULE - COOLING (CU)

TAG

NAME

AMBIENT

SUMMER DRY

BULB (°FDB)

ASSOC.

INDOOR

UNIT

REFRIGERAN

T TYPE

COOLING ELECTRICAL MAXIMUM DIMENSIONS

WEIGHT (LBS) MANUFACTURER MODEL NOTESTONS # OF STAGES IEER VOLTS PH MCA MOCP

DISCONNECT CNTLR/STARTER

SCCR WIDTH HEIGHT DEPTHBY [A] TYPE [B] BY [A] TYPE [C]

CU-1 95 FCU-1 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2

CU-2 95 FCU-2 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2

CU-3 95 FCU-3 R-32 10 2 16.4 208 3 46 60 EC NF MFR FV 5,000 36" 42" 36" 400 DAIKIN DC6TE120 NOTES 1&2

NO SCALE1

FAN COIL UNIT CONTROL - COOLING ONLY - FCU-A

1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

2. EMERGENCY BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS SHALL BE ROUTED IN

SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS. WIRING FOR EACH

BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING THE NORMAL

BRANCH.

3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND

REQUIREMENTS SPECIFIC TO FIRESTOPPING.

4. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF,

AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF

ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE

APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

5. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL

REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING

CONDITIONS AND REPORT CONFLICTS.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR

SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.

3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CONDUIT

RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE NECESSARY BECAUSE OF

EXISTING FIELD CONDITIONS.

4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY

TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,

AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,

PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY

COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.

5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF

APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC

CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER

TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.

INSTALLATION TYPE RMC EMT

X

X

X

X

INTERIOR LOCATIONS WITH FINISHED CEILING AND WALLS: CONCEALED

IN WALLS AND ABOVE FINISHED CEILINGS

INTERIOR LOCATIONS WITHOUT FINISHED CEILINGS: CONCEALED IN

WALL, EXPOSED ABOVE CEILINGS

EXISTING INTERIOR LOCATIONS WITH FINISHED CEILINGS AND WALLS:

CONCEALED IN WALLS AND ABOVE FINISHED CEILING UNLESS

OTHERWISE NOTED

X

X

X

ELECTRICAL MOUNTING SUBSCRIPT KEY:

SM SURFACE MOUNTED

+#" MOUNT AT #" TO CENTERLINE ABOVE FINISHED FLOOR

RECEPTACLE SUBSCRIPT KEY:

DEVICE

# = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

DEVICE KEY:

SHADED DEVICE INDICATES DEVICE IS CONNECTED TO AN EMERGENCY CIRCUIT.

DEVICE E

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 KEYNOTE: INDICATES NOTE USED TO

DESCRIBE ADDITIONAL INFORMATION

ABOUT WORK REQUIRED, SPECIFIC

TO THE SHEET AND/OR DETAIL

N O R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

NATE JACQUES

EVAN HAMMER

TONY DELOUIS

DESCRIPTION: PERSON:

BUILDING CODE: IBC 2024 EDITION

FIRE CODE: IFC 2024 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION

ENERGY CONSERVATION CODE: IECC 2012

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS

INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

ELECTRICAL SYMBOL LIST - POWER

SYMBOL

EQUIP

ABBREV

SPEC

SECTION

DESCRIPTION

E ECONN 26 05 33 ELECTRICAL CONNECTION - CEILING/SURFACE

-- -- EXISTING PANELBOARD - SURFACE MOUNT

MX-# 26 24 19

MANUAL SWITCH, REFER TO DISCONNECT AND

STARTER SCHEDULE

FDS-# 26 28 16

FUSIBLE DISCONNECT SWITCH, REFER TO

DISCONNECT AND STARTER SCHEDULE

ELECTRICAL SYMBOL LIST - RECEPTACLES

SYMBOL TAG EQUIP ABBREV

SPEC

SECTION

DESCRIPTION

W REC-DUP-WP 26 27 26

DUPLEX GFI WEATHERPROOF RECEPTACLE,

125V - NEMA 3R WHILE IN-USE COVER

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

As indicated

/2

/2

:0

:0

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

E000

ELECTRICAL COVERSHEET

TONDEL

SENDIZ

KYHIL

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

ELECTRICAL SHEET INDEX

E000 ELECTRICAL COVERSHEET

E100 DEMOLITION FLOOR PLAN - ELECTRICAL

E200 NEW FLOOR PLAN - ELECTRICAL

E700 ELECTRICAL PANEL SCHEDULES

GRAND TOTAL: 4

Joshua.K.Hill Snapshot

E

E

E

E

E E

E

PANEL UA-P3

EXISTING PANEL UA-P2EXISTING PANEL UA-P1

FACP

EXISTING PANEL UB-P2

PANEL UB-P1

PANEL UB-P3

FACP

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

CU-2-E

W

MX-FCU-2-E

CU-3-E

FDS-CU-3-E

FDS-CU-2-E

FCU-2-E

EF-2 (E)

UA3

UA3

UA3

UA3

13UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

FDS-FCU-3-E

FCU-3-E

FDS-FCU-1-E

FDS-CU-1-E

FCU-1-E

CU-1-E

LOCATED AT

GRADE

CU-E

FDS-CU-E

EXISTING

UNUSED BOX

LOCATED AT

GRADE

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/8" = 1'-0"

/2

/2

:0

:0

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

E100

DEMOLITION FLOOR PLAN -

ELECTRICAL

TONDEL

SENDIZ

KYHIL

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/8" = 1'-0"1

BASEMENT DEMOLITION PLAN -

UNIT A - ELECTRICAL

N O R

HT

1/8" = 1'-0"4

BASEMENT DEMOLITION PLAN -

UNIT B - ELECTRICAL

N O R

HT

1/8" = 1'-0"2

LEVEL 01 DEMOLITION PLAN -

UNIT A - ELECTRICAL

N O R

HT

1/8" = 1'-0"3

LEVEL 02 DEMOLITION PLAN -

UNIT A - ELECTRICAL

N O R

HT

1/8" = 1'-0"5

LEVEL 02 DEMOLITION PLAN -

UNIT B - ELECTRICAL

KEYNOTES:

1. REMOVE EXISTING ELECTRICAL DISCONNECT

AND CONNECTION TO EQUIPMENT. CIRCUIT

SHALL REMAIN AND BE UTILIZED FOR NEW

EQUIPMENT IN NEW WORK PHASE.

2. REMOVE AND STORE EXISTING FIRE ALARM DUCT

SMOKE DETECTOR AND CONTROL MODULE FROM

FCU. EXISTING FIRE ALARM SERVICE SHALL BE

MAINTAINED DURING CONSTRUCTION AND RE-

INSTALLED TO NEW EQUIPMENT IN NEW WORK

PHASE.

3. INDOOR/OUTDOOR FIRST FLOOR EQUIPMENT

DISCONNECTS ARE TO BE SALVAGED AND

TURNED OVER TO OWNER.

4. REMOVE THE ELECTRICAL BOX AND ASSOCIATED

CONDUIT ROUTED UP THE WALL. PATCH WALL

AND MATCH EXISTING FINISH. CONDUIT THAT

TRANSITIONS UNDERGROUND TO BE CAPPED.

E

E

E

E E

E

PANEL UA-P3

EXISTING PANEL UA-P2EXISTING PANEL UA-P1

FACP

EXISTING PANEL UB-P2

PANEL UB-P1

PANEL UB-P3

FACP

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

UA2

CU-3

CU-2

DS-CU-2

DS-CU-3

DS-FCU-2

FCU-2

EF-2 (E)

UA3

UA3

UA3

UA3

13UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

UA3

DS-FCU-3 FCU-3

DS-FCU-1

FCU-1

2 CU-1

DS-CU-1

LOCATED AT

GRADE

CU-E

FDS-CU-E

W

UB-P2-8

LOCATED AT

GRADE

INSTALL NEW

DEVICE AT 20"

ABOVE FINISHED

GRADE.

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

1/8" = 1'-0"

/2

/2

:0

:1

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

E200

NEW FLOOR PLAN - ELECTRICAL

TONDEL

SENDIZ

KYHIL

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

N O R

HT

1/8" = 1'-0"1

BASEMENT NEW PLAN - UNIT A -

ELECTRICAL

N O R

HT

1/8" = 1'-0"4

BASEMENT NEW PLAN - UNIT B -

ELECTRICAL

N O R

HT

1/8" = 1'-0"2

LEVEL 01 NEW PLAN - UNIT A -

ELECTRICAL

N O R

HT

1/8" = 1'-0"3

LEVEL 02 NEW PLAN - UNIT A -

ELECTRICAL

N O R

HT

1/8" = 1'-0"5

LEVEL 02 NEW PLAN - UNIT B -

ELECTRICAL

KEYNOTES:

1. PROVIDE NEW DISCONNECT AND CONNECT

EXISTING ELECTRICAL CONNECTION. EXTEND

CIRCUIT AS NECESSARY FOR RECONNECTION.

NEW WIRE AND CONDUIT SHALL MATCH

EXISTING. INSTALL NEW DISCONNECT AT

EXISTING DISCONNECT LOCATION.

2. CONNECT EXISTING FIRE ALARM DUCT SMOKE

DETECTOR AND CONTROL MODULE BACK TO

FCU CONTROLLER AND DUCTWORK.

3. PROVIDE NEW 3#12 & 1#12 EGC IN 3/4" C. FROM

UA-P1 TO NEW UNIT. PROVIDE NEW 20A/3P

BREAKER IN UA-P1.

SHEET NOTE:

1. NEW MECHANICAL EQUIPMENT TO BE

INSTALLED ON EXISTING CONCRETE PADS.

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2026 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908 www.imegcorp.com

KEY PLAN

AGENCY APPROVAL

REVISIONS

PROFESSIONAL SEAL

CONSULTANT

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #26001283.00

/2

/2

:0

:1

P

M

Iowa Department of Administratinve Services

313 LANEDALE

ROCKWELL CITY, IOWA 50579

IDAS 9501.00 DOC NCCF

AIR HANDLER

REPLACEMENT

E700

ELECTRICAL PANEL SCHEDULES

TONDEL

SENDIZ

KYHIL

26001283.00

4/29/2026

100% CD

ID

A

S

.0

D

O C

N C

C F

A

IR

H A

N D

L E

R R

E P

L A

C E

M E

N T

.0

CIRCUIT KEY NOTES: *NB = NEW BREAKER.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 13.8

TOTAL CONNECTED AMPS: 13.80 A

TOTAL ESTIMATED DEMAND LOAD: 4.972 kVA

TOTAL CONNECTED LOAD: 4.97 kVA

Power 4.972 kVA 100% 4.972 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 13.81 13.81 13.81

Total Load: 1.66 kVA 1.66 kVA 1.66 kVA

41 0 0 42

WEST DRYER 30 2

0 0 40

37 0 0

3 100 UA-P3

MIDDLE DRYER 30 2

0 0 36

33 0 0

2 50 WELDING REC

EAST DRYER 30 2

0 0 1 20 SPARE 32

29 SPARE 20 1 0 0 1 20 VENDING REC 30

27 SPARE 20 1 0 0 1 20 SPARE 28

25 VENDING REC 20 1 0 0 1 20 HALL OFFNET/BASEMENT... 26

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 SPACE -- 1 -- -- 1 -- SPACE 22

19 SPACE -- 1 -- -- 1 -- SPACE 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- -- 1 -- SPACE 16

13 SPACE -- 1 -- -- 1 -- SPACE 14

11 SPACE -- 1 -- -- 1 -- SPACE 12

9 SPACE -- 1 -- -- 1 -- SPACE 10

7 SPACE -- 1 -- -- 1 -- SPACE 8

5 1.66 -- 1 -- SPACE 6

3 1.66 -- 1 -- SPACE 4*NB

FCU-2 20 3 12 12 12 0.84

1.66 -- 1 -- SPACE 2

K E Y

CK

T

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CK

T

NO.

K E Y

NOTES:

BOLD INDICATES NEW WORK.

PANEL TOTALS ONLY SHOW NEW LOADS.

NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.

ISC UNKNOWN 0.00 kA

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 400 MLO

EXISTING PANEL UA-P1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 0

TOTAL CONNECTED AMPS: 0.00 A

TOTAL ESTIMATED DEMAND LOAD: 0.000 kVA

TOTAL CONNECTED LOAD: 0.00 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 0.00 0.00 0.00

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

23 0 0 24

21 0 0 22

1 ST FLOOR A/C 60 3

0 0

3 60 2ND FLOOR A/C

17 0 0 1 20 24 VAC CONTRL 18

15 0 0 1 20 STEAM VALVE 16

KITCHENETTE REC 20 3

0 0 1 20 EXHAUST FAN-BASEMENT 14

11 EXHAUST FAN 20 1 0 0 12

9 SPACE -- 1 -- 0

2 20 SPARE

7 FACP 20 1 0 0 8

5 0 0 6

3 0 0

3 20 KITCHENETTE REC

2 ND FLOOR AHU 20 3

0 -- 1 -- UNUSABLE 2

K E Y

CK

T

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CK

T

NO.

K E Y

NOTES:

BOLD INDICATES NEW WORK.

PANEL TOTALS ONLY SHOW NEW LOADS.

NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.

ISC UNKNOWN 0.00 kA

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 100 MCB

EXISTING PANEL UA-P2

CIRCUIT KEY NOTES: *NB = NEW BREAKER.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 0.5

TOTAL CONNECTED AMPS: 0.50 A

TOTAL ESTIMATED DEMAND LOAD: 0.180 kVA

TOTAL CONNECTED LOAD: 0.18 kVA

Receptacles 0.180 kVA 100% 0.180 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 1.50 0.00 0.00

Total Load: 0.18 kVA 0.00 kVA 0.00 kVA

23 0 0 24

21 0 0 22

SPARE 60 3

0 0

3 60 NEW AIR COND

17 SPARE 20 1 0 0 18

15 SPARE 20 1 0 0

2 20 WELD REC

13 0 0 1 20 SIEMENS CONTROL 14

SPARE 20 2

0 -- 1 -- SPACE 12

9 0 -- 1 -- SPACE 10

SPARE 20 2

0 0.18 0.27 12 12 12 1 20 OUTDOOR RECEPT. 8 *NB

5 SPARE 20 1 0 0 6

3 SPACE -- 1 -- 0 4

1 SPACE -- 1 -- 0

3 20 2ND FLOOR AHU

K E Y

CK

T

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CK

T

NO.

K E Y

NOTES:

BOLD INDICATES NEW WORK.

PANEL TOTALS ONLY SHOW NEW LOADS.

NEW CIRCUIT BREAKER CHARACTERISTICS SHALL MATCH EXISTING BREAKERS IN PANEL.

ISC UNKNOWN 0.00 kA

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 0/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 100 MCB

EXISTING PANEL UB-P2

AMS-ASSEMBLED MOTOR STARTER

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE MOTOR)

DISCONNECT TYPE: ACCESSORIES & OPTIONS

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING

VOLTAGE POLES

STARTER

ENCLOSURE

REQUIRED

ACCESSORIES &

OPTIONS COMMENTSTYPE RATING

TRIP

RATING

NEMA

SIZE TYPE

DS-CU-1 NF 60 208 3 NEMA 3R HL

DS-CU-2 NF 60 208 3 NEMA 3R HL

DS-CU-3 NF 60 208 3 NEMA 3R HL

DS-FCU-1 NF 30 208 3 NEMA 1 HL

DS-FCU-2 NF 30 208 3 NEMA 1 HL

DS-FCU-3 NF 30 208 3 NEMA 1 HL

Sheets
G000 - PROJECT COVERSHEET

File details come from the government source that posted it. Updated .