RFB922300-01 - DOC CCF Kitchen & Laundry Addition - Drawings Part 2.pdf
PDF 20 MB Posted
- Attached to
- DOC CCF Kitchen & Laundry Addition
- Solicitation number
- RFB922300-01
- Issued by
- Polk County, Iowa
About this file
This file contains mechanical, plumbing, and fire protection drawings for the Clarinda Correctional Facility Kitchen & Laundry Addition project for the State of Iowa Department of Corrections, located at 2000 N 16th St, Clarinda, IA 51632. The project involves a comprehensive renovation and expansion of the facility's mechanical systems, including installation of new air handling units (AHU-1, DOAS-1), exhaust fans, terminal air boxes, refrigeration systems, water heaters, and associated ductwork and piping. The drawings are part of a bid set dated 11/18/2022, prepared by IMEG Corp., and cover mechanical, plumbing, and fire protection system designs for both Level 01 and Level 02 of the facility.
The project includes detailed specifications for mechanical equipment such as a pressure booster system, water softener, air compressor, and multiple condensing units. The mechanical systems are designed with energy efficiency and comprehensive monitoring in mind, with the facility management system (FMCS) capable of tracking detailed performance metrics for equipment like air handlers, refrigeration systems, and water heaters. The drawings specify emergency power considerations, with provisions for generator-powered operation of critical systems, and include extensive control sequences for different mechanical components. The project appears to be fully funded and is part of a state-level infrastructure improvement initiative for the Department of Corrections.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROBERT RIPPE & ASSOCIATES, INC. © 2011 ROBERT RIPPE
QUICK DISCONNECT
OFFSET
WALL
UTILITY OUT OF WALLUTILITY INLET
UTILITY INLET
FOODSERVICE
EQUIPMENT
FINISHED FLOOR
ELBOW BY MECHANICAL TRADES
FACE OF BUILDING WALL
FOODSERVICE EQUIPMENT
PLAN
SECTION
EXCEED 3 1/2"
NOT TO
SHUT-OFF VALVE BY
MECHANICAL TRADES
QUICK DISCONNECT HOSE
AND FITTING BY FSEC
WALL REINFORCING NOT BY FSEC
RESTRAINING CABLE BY FSEC
NOTE:
IF UTILITY INLET IS NOT AT HEIGHT SHOWN, MECHANICAL TRADES TO PROVIDE PIPING
WITH ELBOWS TO RAISE INLET.
A .F
.F V
F Y
A .F
.F V
F Y
CODE APPROVED,
BACKFLOW PREVENTER
BY PLUMBING TRADES
IN-WALL PIPING
SHUT-OFF VALVE
RECESSED CONTROL CABINET
PER SPEC. (REQUIRES MIN. 5"
RECESS DEPTH)
CHROME-PLATED
ESCHUTEON
HOSE REEL PER SPEC.
FLEXIBLE WATER
CONNECTOR
VERIFY NOZZLE TYPE
WITH SPEC.
DOOR SHOWN IN
OPEN POSITION
HOT & COLD
SUPPLY PIPING
NOTE:
DASHED PIPING AND BACKFLOW PREVENTER PROVIDED AND INSTALLED BY MECHANICAL
TRADES. ALL OTHER COMPONENTS SUPPLIED BY FOODSERVICE EQUIPMENT CONTRACTOR AND
INSTALLED BY PLUMBING TRADES.
MIXING
VALVES
CHECK VALVES
WATER HAMMER ARRESTOR
ROBERT RIPPE & ASSOCIATES, INC. © 2011 ROBERT RIPPE
HOSE REEL
ROBERT RIPPE & ASSOCIATES, INC. © 2011 ROBERT RIPPE
DISPOSER
PRE-RINSE*
VACUUM
BREAKER WITH
ANGLE FLANGES*
FLOW
CONTROL
VALVE*
SOLENOID
VALVE*
WASTE LINE
MIXING VALVE*
W/INTEGRAL
CHECK VALVES
SHUT-OFF
VALVES
DOUBLE WATER
INLET USED ONLY ON
18" BOWL SINKS
BOWL SINK*
WATER
INLET
ELBOW
BODY WATER
INLET* AT SINK
APPLICATIONS
DISPOSER*
RECOMMENDED INSTALLATION - MECHANICAL
NOTE:
ALL PIPE 1/2" MINIMUM
*THESE COMPONENTS FURNISHED BY FSEC. ALL OTHER
COMPONENTS AND INSTALLATION PROVIDED BY PLUMBING TRADES.
P E
R E
L E
V A
T
IO
N
P E
R E
L E
V A
T
IO
N
NOTE:
1. ELECTRICAL COMPONENTS AND INTERWIRING BY ELECTRICAL TRADES UNLESS NOTED OTHERWISE.
2. CONDUIT CONCEALED IN WALL WHEREVER POSSIBLE. EXPOSED CONDUIT TO BE CHROME-PLATED.
ROBERT RIPPE & ASSOCIATES, INC. © 2011 ROBERT RIPPE
WIRING DIAGRAM - ELECTRIC GAS VALVE
WET CHEMICAL FIRE PROTECTION SYSTEM
A .F
.F
A .F
.F
ELECTRICAL PANEL
WITH POWER SHUT-
OFF DEVICE(S) FOR
ELECTRIC COOKING
EQUIPMENT
MANUAL RESET
FURNISHED BY FSEC
FIRE PROTECTION
SYSTEM ENCLOSURE
BY FSEC, MOUNT
FLUSH WITH CEILING
CONDUIT BELOW
CEILING AND
OCTAGONAL
JUNCTION BOX
BY ELECTRICAL
TRADES
REMOTE MANUAL
PULL (VERIFY
LOCATION)
CEILING
LOCATE
GAS VALVE
PER LOCAL
CODE
JUNCTION
BOX
EMPTY
CONDUIT
ABOVE CEILING
BY FSEC
WIRING TO
SUPPLY FAN
WIRING TO POWER
SHUT-OFF DEVICE(S)
ELECTRICAL GAS
VALVE FURNISHED BY
FSEC INSTALLED BY
MECHANICAL TRADES
WIRING TO BUILDING
FIRE ALARM
POWER TO COOKING
EQUIPMENT
POWER
SUPPLY
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:0 :3
A
M FSM101
FOODSERVICE
EQUIPMENT
MECHANICAL
DETAILS
MM
EG/RB
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
EG/TP
BID SET
AH
AG
AF
AE
A2 A3 A4 A5
8B
B
8B
B
8C
C
8C
C
8D
D
8F
F
8G
G
CHEMICAL STORAGE AND LAUNDRYSUPERVISOR'S OFFICE
BAKERY REF.
BAKERY FRZ COLD FOOD
ISSUANCE
WALK-IN PRODUCE REFRIGERATOR
MEAT AND DAIRY WALK-IN REFRIGERATOR
COOK'S REF.
ISSUANCE
COOK'S FRZ.
ISSUANCE
WALK-IN TEMPERING
INGREDIENT AND DRY GOODS ISSUANCE
INGREDIENT ASSEMBLY
DRY STORAGE
DRY
BAKERY
STORAGE
TOOL CONTROL
ROOM
WALK-IN FREEZER
8E
E
8E
E
FD W/FUNNEL
FD W/FUNNEL
FD W/FUNNEL
FD W/FUNNEL
FD W/FUNNEL
CWR
GASG
MECHANICAL LEGEND
FLOOR SINK w/HALF GRATE
FLOOR SINK
FLOOR DRAIN
INDIRECT WASTE
AIR GAP WASTE
DIRECT WASTE
HOT WATER
COLD WATER
FSH
FS
FD
IW
AGW
W
HW
CW
S STEAM
CR CONDENSATE RETURN
COOLING TOWER /
CHILLED WATER SUPPLY/RETURN
EXHAUST
SUPPLY
TTFD TELL-TALE FLOOR DRAIN
AFF
CLG
DFA
FSEC
OOW
MT
PLBG
WC
ABOVE FINISHED FLOOR
CEILING
DOWN FROM ABOVE
FOODSERVICE EQUIPMENT CONTRACTOR
OUT OF WALL
MECHANICAL TRADES
PLUMBING
WATER COLUMN
A COMPRESSED AIR
CO2
AH
AG
A2 A3
CONDENSING UNITS ARE LOCATED
OUTSIDE ON THE ROOF. VERIFY EXACT
LOCATION WITH ARCHITECT/ENGINEER.
ROOF CURBS, AND ALL PENETRATIONS
FOR REFRIGERATION LINES AND UTILITIES
ARE NOT BY SECT. 114000 CONTRACTOR.
8A
A
WALK-IN WALLS BELOW
WALK-IN WALLS BELOW
B
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:0 :4
A
M FSM102
FOODSERVICE
EQUIPMENT
MECHANICAL PLAN -
AREA 1
MM
EG/RB
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
EG/TP
BID SET
1/4" = 1'-0"
1 FOODSERVICE MECHANICAL PLAN - AREA 1
1/4" = 1'-0"
2 FOODSERVICE MECHANICAL PLAN - ROOF
A1
AH
AG
A2
BAKERY
BAKERY REF.
BAKERY FRZ
DRY
BAKERY
STORAGE
OFFENDER BREAK AREA
RACK PARKING
TOOL CONTROL
ROOM
FSH
FD
FD
A
A
FSH
A
FD
CWR
GASG
MECHANICAL LEGEND
FLOOR SINK w/HALF GRATE
FLOOR SINK
FLOOR DRAIN
INDIRECT WASTE
AIR GAP WASTE
DIRECT WASTE
HOT WATER
COLD WATER
FSH
FS
FD
IW
AGW
W
HW
CW
S STEAM
CR CONDENSATE RETURN
COOLING TOWER /
CHILLED WATER SUPPLY/RETURN
EXHAUST
SUPPLY
TTFD TELL-TALE FLOOR DRAIN
AFF
CLG
DFA
FSEC
OOW
MT
PLBG
WC
ABOVE FINISHED FLOOR
CEILING
DOWN FROM ABOVE
FOODSERVICE EQUIPMENT CONTRACTOR
OUT OF WALL
MECHANICAL TRADES
PLUMBING
WATER COLUMN
A COMPRESSED AIR
CO2
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:0 :4
A
M FSM103
FOODSERVICE
EQUIPMENT
MECHANICAL PLAN -
AREA 2
MM
EG/RB
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
EG/TP
BID SET
1 FOODSERVICE MECHANICAL PLAN - AREA 2
B B
F
FF FF2 DR
R E
F
B B
F
FF FF2 DR
R E
F
A1
AF
AE
AD
AC
AB
PD
PE
A2 A3
A4
A
A
A
HOT FOOD PRODUCTION
COLD FOOD
PREPARATION
AND ASSEMBLY
POT AND PAN
WASHING
CHEMICAL STORAGE AND LAUNDRYSUPERVISOR'S OFFICE
DISHROOM
STAFF BREAK ROOM DIRECTOR'S OFFICE
TRAY CART ASSEMBLY
A
A
A
B
A
A
B
A
A
A
A
B
145 145
A
TRAY CART
PARKING
DURING
ASSEMBLY
TRAY
CART
PARKING
DURING
ASSEMBLY
FSH FSH
FSH FSH
FSH
FSH
187187
DRAIN TO STAND
PIPE IN WALL, VFY.
A
FD
104104
TTFD
A
B
A
A
FSH
FSH
155155
FSH
FSH
A
R1
A
L1
B
R1
B
L1
C
R1
C
L1
163163
163163
A
A
A
MOP SINK NOT
PROVIDED BY
SECTION 114000
FD
A
A
FSH
FSH
FSH FSH
CHASE FOR
VERTICAL VENTING
MAIN UTILITY CONNECTIONS IN
RISER, MECH. TRADES TO MAKE
FINAL CONNECTIONS FROM UDS
TO FOODSERVICE EQUIPMENT
B
150150150150
146146 146146
CWR
GASG
MECHANICAL LEGEND
FLOOR SINK w/HALF GRATE
FLOOR SINK
FLOOR DRAIN
INDIRECT WASTE
AIR GAP WASTE
DIRECT WASTE
HOT WATER
COLD WATER
FSH
FS
FD
IW
AGW
W
HW
CW
S STEAM
CR CONDENSATE RETURN
COOLING TOWER /
CHILLED WATER SUPPLY/RETURN
EXHAUST
SUPPLY
TTFD TELL-TALE FLOOR DRAIN
AFF
CLG
DFA
FSEC
OOW
MT
PLBG
WC
ABOVE FINISHED FLOOR
CEILING
DOWN FROM ABOVE
FOODSERVICE EQUIPMENT CONTRACTOR
OUT OF WALL
MECHANICAL TRADES
PLUMBING
WATER COLUMN
A COMPRESSED AIR
CO2
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:0 :5
A
M FSM104
FOODSERVICE
EQUIPMENT
MECHANICAL PLAN -
AREA 3
MM
EG/RB
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
EG/TP
BID SET
1 FOODSERVICE MECHANICAL PLAN - AREA 3
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
NO HATCH LIGHT HAZARD
ORDINARY GROUP 1
SPRINKLER - WALL MOUNTED
SPRINKLER
SPRINKLER - CONCEALED
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
SHUTOFF VALVE NORMALLY OPEN
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
AUTOMATIC DRAIN VALVE
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
CHECK VALVE
FLOW SWITCH
F
ROUTE TO DRAIN
AREA BOUNDARY
FIRE PROTECTION ABBREVIATION KEY
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTESUON
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
INDICATES A PLUMBING CONNECTION TO A FOOD SERVICE EQUIPMENT.
REFERENCE FOOD SERVICE DRAWINGS FOR ADDITIONAL INFORMATION IN
REGARDS TO TYPE OF EQUIPMENT, ROUGH-IN SIZES, AND ADDITIONAL
COMMENTS.
T101
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
LIFE SAFETY CODE: NFPA 101 2012 EDITION
ENERGY CONSERVATION CODE: IECC 2012
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
TECHNOLOGY
MIKE MCCARTY
MIKE MCCARTY
KRISTEN SPINA
DAMON DEEN
DESCRIPTION: PERSON:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
CIVIL CONTRACTORC.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE EQUIPMENT CONTRACTORFSEC
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
DRY WALL CONTRACTOR FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS,
ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE DRY WALL
CONTRACTOR OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.
17. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
18. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH THEIR WORK.
6. THIS CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,
CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK REQUIRED BY
THEIR WORK.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE
CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS
REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID
TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND
IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL
TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE
BASIS OF DESIGN.
3. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS
WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
SPRINKLER HEADS SHALL BE ALIGNED WITH OTHER SPRINKLER HEADS, LIGHTING,
DIFFUSERS, AND ANY OTHER FEATURES IN THE CEILING.
4. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK
RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
5. PROVIDE COVERAGE ABOVE AND BELOW ALL DUCTWORK GREATER THAN 48" WIDE.
6. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT
NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
7. ALL BUILDING AREAS SHALL BE FULLY SPRINKLERED INCLUDING CANOPIES, WALKWAYS,
OVERHANGS, SOFFITS, AND BUILDING PROJECTIONS. ALL ACCESSIBLE COMBUSTIBLE
CONCEALED SPACES SHALL BE FULLY PROTECTED BY THE SPRINKLER SYSTEM.
8. EACH RISER ASSEMBLY SHALL INCLUDE CHECK VALVE BUTTERFLY CONTROL VALVE
INDICATING "OPEN" OR "CLOSED" POSITION, TEST INSPECTION VALVE, FLOW SWITCH
AND PRESSURE GAUGES.
9. PROVIDE RISER ROOM IDENTIFICATION SIGNAGE OUTSIDE THE FIRE RISER ROOM.
COORDINATE EXACT SIGN LANGUAGE WITH AHJ.
10. WHERE FEASIBLE INSTALL PIPES HIGH AS POSSIBLE TO AVOID CONFLICT WITH OTHER
DISCIPLINES.
11. INSTALL SYSTEM DRAINS AT LOW POCKET AREAS CONTAINING FIVE GALLONS OF
WATER OR MORE, PROVIDE WITH ISOLATION VALVE AND THREADED HOSE
CONNECTION.
12. FOLLOW STRUCTURAL DETAILS WHEN PENETRATING OR PASSING THROUGH
STRUCTURAL ELEMENTS. ALTERNATE DESIGNS WILL NEED TO BE APPROVED THROUGH
THE STRUCTURAL ENGINEER.
13. PROVIDE INTERMEDIATE TEMPERATURE SPRINKLER HEADS WHERE REQUIRED BY NFPA
13 UNLESS OTHERWISE NOTED.
14. FINAL HEAD LOCATION, TYPE AND FINISH SHALL BE REVIEWED AND APPROVED BY THE
ARCHITECT.
15. THE OWNER MUST BE NOTIFIED PRIOR TO EACH AND EVERY DRAINING OR RECHARGING
OF THE SPRINKLER SYSTEM.
16. THE CONTRACTOR SHALL PREPARE A COORDINATED SET OF SHOP DRAWINGS AND
SHALL OBTAIN APPROVAL FROM THE AUTHORITIES HAVING JURISDICTION AND THE
LOCAL FIRE DEPARTMENT PRIOR TO ANY INSTALLATION.
17. DRAWING SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT,
ETC. AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
18. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW
ALL DRAWINGS. INCLUDING THOSE OF OTHER TRADES.
FIRE PROTECTION GENERAL NOTES:
FIRE PROTECTION SHEET INDEX
F0.0 FIRE PROTECTION COVERSHEET
F1.1 LEVEL 01 PLAN - AREA A - FIRE PROTECTION
F1.2 LEVEL 01 PLAN - AREA B - FIRE PROTECTION
F1.3 LEVEL 02 PLAN - AREA A - FIRE PROTECTION
F1.4 LEVEL 02 PLAN - AREA B - FIRE PROTECTION
F4.1 FIRE PROTECTION DETAILS & SCHEDULES
GRAND TOTAL: 6
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :3
A
M F0.0
FIRE PROTECTION
COVERSHEET
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
D
E
F
1 2 3 4 5 6 7 8 9
PA
PB
PC
P5 P4 P3
AA
AB
A1 A2 A3
HALL
DISHROOM
CHEMICAL
STORAGE
ELEC.
LAUNDRY
CORRIDOR
FOLDING
OFFENDER
RR
PASSAGE
VISITOR
ENTRANCE
RECEPTION
TOILET
TOILET
OFFICER
HALL
PERSONNEL
ENTRANCE
ADMINISTRATION
TOILET
OFFICE
TOILET
TOILET
MUSTER
ANTEROOM
SEGREGATION
A/C
1046RELEASE
SHAKEDOWN
PEDESTRIAN
SALLYPORT
FAMILY
WAITING
SEARCH
SEARCH
CONTACT
VISIT
VISITOR
TOILET
INMATE
TOILET
INMATE
SEARCH
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
NON-CONTACT
VISIT
TOILET
EVIDENCE
CAPTAIN'S
OFFICE
OFFICE
OFFICE
HALL
CORRIDOR
DRYER
CHASE
OPEN
BREAKROOM/
STORAGE
1062A
OFFICE
1062B
FP UP. REFER TO 1/F1.3
FOR CONTINUATION
F P
ZONE
1K
REFER TO 2/F4.1 FOR RATED FIRE
BARRIER PENETRATION DETAIL (TYP.).
AREA WILL BE UNHEATED WITH
INSULATED CEILING ABOVE
DRYERS. PROVIDE SIDE WALL DRY
TYPE SPRINKLERS (SPR-4).
FP
FP
WALL BOX/RECESSED BOX
IT-1
1"FP
AREA 'A'
AREA 'B'
HALL
DISHROOM
CHEMICAL
STORAGE
ELEC.
LAUNDRY
CORRIDOR
FOLDING
OFFENDER
RR
PASSAGE
VISITOR
ENTRANCE
RECEPTION
TOILET
TOILET
OFFICER
HALL
PERSONNEL
ENTRANCE
ADMINISTRATION
TOILET
OFFICE
TOILET
TOILET
MUSTER
ANTEROOM
SEGREGATION
A/C
1046RELEASE
SHAKEDOWN
PEDESTRIAN
SALLYPORT
FAMILY
WAITING
SEARCH
SEARCH
CONTACT
VISIT
VISITOR
TOILET
INMATE
TOILET
INMATE
SEARCH
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
PHONE
CONTACT
NON-CONTACT
VISIT
TOILET
EVIDENCE
CAPTAIN'S
OFFICE
OFFICE
OFFICE
HALL
CORRIDOR
DRYER
CHASE
OPEN
BREAKROOM/
STORAGE
1062A
OFFICE
1062B
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :4
A
M F1.1
LEVEL 01 PLAN -
AREA A - FIRE
PROTECTION
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
N O R
HT
1/8" = 1'-0"
LEVEL 01 PLAN - AREA A - FIRE PROTECTION
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
GENERAL NOTES:
1. REFER TO F4.1 FOR SPRINKLER USAGE
SCHEDULE AND FIRE PROTECTION MATERIAL LIST.
2. REFER TO DETAILS 1/F4.1, 2/F4.2 AND 3/F4.3 FOR
SPRINKLER MOUNTING DETAILS AND PIPING
THROUGH FIRE RATED WALL DETAIL.
3. REFER TO F0.0 FOR GENERAL FIRE PROTECTION
NOTES.
KEYNOTES:
1. CORE DRILL THROUGH EXISTING PRECAST
EXTERIOR WALL. CORES SHALL BE
COORIDNATED WITH EXISTING VERTICAL CABLING
IN WALL. REFER TO EXISTING WALL SCANNING
DATA FOUND ON STRUCTURAL PLANS.
COORDINATE NEW WALL OPENING WITH PRECAST
SUPPLIER SO CORE DRILLING IS NOT REQUIRED.
ALL OPENINGS SHALL BE COORDINATED PRIOR
TO ORDERING PRECAST AND COORDINATED TO
ALIGN WITH NEW CORES IN EXISTING PRECAST
WALL.
2. PIPING ROUTED TO EXISTING SPRINKLERS FOR
FIRST FLOOR WEST SPRINKLER ZONE.
3. REMOVE EXISTING EXPOSED FIRE PROTECTION
PIPE WITH INSPECTOR TEST SHUTOFF VALVE
LOCATED APPROXIMATELY 4 FT AFF. EXTEND
PIPING ABOVE CEILING TO EVIDENCE ROOM.
REMOVE EXISTING PIPING DOWNSTREAM OF
INSPECTOR TEST TO EXTERIOR DRAIN AND PATCH
EXTERIOR WALL OPENING.
4. ROUTE FIRE PROTECTION DRAIN PIPE ABOVE
CEILING AND DISCHARGE OUT EXTERIOR WALL.
COORDINATE NEW WALL OPENING WITH PRECAST
SUPPLIER SO CORE DRILLING IS NOT REQUIRED.
5. INSTALL NEW INSPECTOR TEST IN EVIDENCE
ROOM AT AN ACCESSIBLE LOCATION
ACCEPTABLE TO THE AHJ. INSTALL A 3/4" MANUAL
DRAIN VALVE AND PIPE ROUTED TO A LOCKABLE
RECESSED STAINLESS STEEL BOX LOCATED IN
TOILET 1061. PROVIDE A 3/4" HOSE BIBB
CONNECTION WITHIN THE RECESSED BOX TO
ALLOW FOR CONNECTION OF HOSE AND ROUTING
TO EXISTING FLOOR DRAIN FOR DRAINING
TRAPPED WATER IN PIPING AFTER OPERATION OF
THE INSPECTOR TEST. DURING FLOW OF
INSPECTOR TEST, WATER SHALL DISCHARGE
OUTSIDE.
PD
PE
P5
P4 P3
AB
AC
AD
AE
AF
AG
AH
A1 A2 A4 A5A3
HOT PRO &
ASSEMBLY
DISHROOM
P O
T
P A
N W
A S
H
POT & PAN
STOR
LNDRY &
CHEM
STOR
STAFF BREAK
RM
DIRECTOR
OFF
STAFF
RR
CART
WASH
1221A
OFFENDER
BREAK
SUPERVISOR
OFF.
OFFENDER
RR
C A
R T
P A
R K
IN
G
BAKERY
FREEZER
TEMPERING
MEAT & DAIRY
REF.
PRODUCE
REF
INGR & DRY
GOOD ISSUE
DRY STORAGE
RECEIVING
BAKERY
FRZR
BAKERY
REF
INGREDIENT
ASSEMBLY
CORRIDOR
MECH
COLD PRO &
ASSEMBLY
PASSAGE
PRODUCE
ISSUE
MEAT &
DAIRY
ISSUE
FRZR
ISSUE
STOR
JAN
TOOL
CONTROL
F P
F P
FP UP. REFER TO F1.4 FOR
CONTINUAITON
AREA 'A'
AREA 'B'
HOT PRO &
ASSEMBLY
DISHROOM
P O
T
P A
N W
A S
H
POT & PAN
STOR
LNDRY &
CHEM
STOR
STAFF BREAK
RM
DIRECTOR
OFF
STAFF
RR
CART
WASH
1221A
OFFENDER
BREAK
SUPERVISOR
OFF.
OFFENDER
RR
C A
R T
P A
R K
IN
G
BAKERY
FREEZER
TEMPERING
MEAT & DAIRY
REF.
PRODUCE
REF
INGR & DRY
GOOD ISSUE
DRY STORAGE
RECEIVING
BAKERY
FRZR
BAKERY
REF
INGREDIENT
ASSEMBLY
CORRIDOR
MECH
COLD PRO &
ASSEMBLY
PASSAGE
PRODUCE
ISSUE
MEAT &
DAIRY
ISSUE
FRZR
ISSUE
STOR
JAN
TOOL
CONTROL
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :5
A
M F1.2
LEVEL 01 PLAN -
AREA B - FIRE
PROTECTION
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
N O R
HT
1/8" = 1'-0"
LEVEL 01 PLAN - AREA B - FIRE PROTECTION
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
KEYNOTES:
1. PROVIDE DRY TYPE SPRINKLER (SPR-4) IN
COOLER OR FREEZER. F.S.C. SHALL PROVIDE
PENETRATION, TRIM RING AND SEAL AROUND
SPRINKLER. F.P.C. SHALL COORDINATE WITH
F.S.C. ON LOCATIONS WHERE PENETRATIONS ARE
REQUIRED.
2. ADD SUPPLEMENTAL DRAIN VALVE TO ALLOW
DRANING TO FLOOR SINK IN ROOM 1241.
ZONE
1K
GENERAL NOTES:
1. REFER TO F4.1 FOR SPRINKLER USAGE
SCHEDULE AND FIRE PROTECTION MATERIAL LIST.
2. REFER TO DETAILS 1/F4.1, 2/F4.2 AND 3/F4.3 FOR
SPRINKLER MOUNTING DETAILS AND PIPING
THROUGH FIRE RATED WALL DETAIL.
3. REFER TO F0.0 FOR GENERAL FIRE PROTECTION
NOTES.
A
A.5
B
C
D
E
F
1 2 3 4 5 6 7 8 9
PA
PB
PC
P5 P4 P3
A.8
AA
AB
A1 A2 A3
MECHANICAL
FUTURE
EXPANSION
VESTIBULE
MECHANICAL
OFFICE
EXISTING FIRE PUMP
AND JOCKEY PUMP
TIE-IN NEW FIRE PROTECTION PIPE
AND ADD ZONE VALVE INTO
EXISTING 6" MAIN. COORDINATE
SHUTDOWN AND TIE-IN OF FIRE
PROTECTION SYSTEM WITH
OWNER.
F P
BF-1
CK-1
FS-1
CONNECT TO EXISTING GALVANIZED STEEL VERTICAL DRAIN
PIPE LOCATED NEAR DOUBLE DOORS.
COORDINATE ROUTING WITH EXISTING
PIPING DUCTWORK, CONDUITS, ETC.
OFFSETS MAY BE REQUIRED.
EXISTING FIRE PUMP
CONTROLLER
DFP
ROOF - NO FP SCOPE.
FP FP
F P
IT-1
F P
F P
FP
MECHANICAL
FUTURE
EXPANSION
VESTIBULE
MECHANICAL
OFFICE
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :0
A
M F1.3
LEVEL 02 PLAN -
AREA A - FIRE
PROTECTION
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
N O R
HT
3/32" = 1'-0"
LEVEL 02 PLAN - AREA A - FIRE PROTECTION
GENERAL NOTES:
1. REFER TO F4.1 FOR SPRINKLER USAGE
SCHEDULE AND FIRE PROTECTION MATERIAL LIST.
2. REFER TO F0.0 FOR GENERAL FIRE PROTECTION
P5
P4 P3
AB
AC
AD
AE
AF
AG
AH
A1 A2 A4 A5A3
MECH
F P
MECH
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :0
A
M F1.4
LEVEL 02 PLAN -
AREA B - FIRE
PROTECTION
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
N O R
HT
3/32" = 1'-0"
LEVEL 02 PLAN - AREA B - FIRE PROTECTION
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
GENERAL NOTES:
1. REFER TO F4.1 FOR SPRINKLER USAGE
SCHEDULE AND FIRE PROTECTION MATERIAL LIST.
2. REFER TO F0.0 FOR GENERAL FIRE PROTECTION
FIRE SEALANT
FIRE SEALANT
NOTE 2
NOTE 3
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 4
PENETRATING ITEM
NOTE 2
NOTE 3
RATED WALL
(CONSTRUCTION
VARIES)
RATED FLOOR
(CONSTRUCTION
VARIES)
NOTES:
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR
FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL
MOVEMENT. REFER TO SPECIFICATION SECTION 07 84 00 FOR SELECTION OF THROUGH
PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL.
EACH CONTRACTOR FURNISHES SLEEVE TO DIVISION 3 OCNTRACTOR, COORDINATES
SLEEVE LOCATIONS AND DEBURS SLEEVE. DIVISION 3 CONTRACTOR 3 BUILDS SLEEVE
INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT
PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE.
SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP
SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE
STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION
LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF
PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATERTIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE
FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF
WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO
FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS.
MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
RETAINING FLANGE TO
PREVENT SPRINKLER
MOVEMENT
1" NIPPLE
1" x 1/2"
REDUCER
2-1/4" DIA OPENING IN CEILING
1/4" ADJUSTMENT
3/16"
SPRINKLER MAIN
PROVIDE TWO ELL'S FOR
ADJUSTING HEAD TO
CENTER OF CEILING TILE
PIPE SIZES SHALL MATCH -
GRAPHIC ENLARGED TO SHOW
DETAIL AT SPRINKLER/CEILING
INTERFACE.
SIMILAR INSTALLATION APPLIES
TO SIDEWALL APPLICATION
SPRINKLER
MAIN
PROVIDE TWO ELL'S FOR
ADJUSTING HEAD TO
CENTER OF CEILING TILE
LAY IN CEILING
CEILING PLATE
AUTOMATIC SPRINKLER HEAD.
REFER TO SPRINKLER HEAD
SCHEDULE FOR HEAD TYPE.
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/3
/2
:4 :1
A
M F4.1
FIRE PROTECTION
DETAILS &
SCHEDULES
MIKMCC
DELLLE
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
NO SCALE
FLOOR/WALL PENETRATION - RATED FIRE BARRIER
2NO SCALE
INSTITUTIONAL QUICK RESPONSE STANDARD
COVERAGE FLUSH PENDENT SPRINKLER DETAIL
1 NO SCALE
DRY SPRINKLER HEAD MOUNTING DETAIL
FIRE PROTECTION MATERIAL LIST
TAG NAME DESCRIPTION MANUFACTURER AND MODEL
BF-1 INDICATING BUTTERFLY VALVE, NORMALLY OPEN, 175 PSI WWP, GROOVED TYPE,
DUCTILE IRON BODY WITH PROTECTIVE COATING, ELECTROLESS NICKEL OR
EPDM COATED DUCTILE IRON DISC, STAINLESS STEEL STEM AND SCREWS,
CAST OR DUCTILE IRON HANDWHEEL, EPDM SEAT, INDICATOR FLAG, FACTORY
MOUNTED INTEGRAL MONITOR SWITCHES, UL/FM.
LUGGED OR WAFER VALVES ARE ACCEPTABLE PROVIDED THEY HAVE THE
FEATURES LISTED ABOVE.
NIBCO GD-4765-8N, VICTAULIC
SERIES 705, TYCO BFV-300,
KENNEDY G300, GLOBE
GLR300G, REL-BFG-300
CK-1 SWING CHECK VALVE, 300 PSI WWP, GROOVED/FLANGED TYPE, DUCTILE IRON
BODY, STAINLESS STEEL HINGE ASSOCIATED WITH RUBBER FACED CLAPPER,
BRASS SEAT RING, ACCESS COVER, 1/2" OR 3/4" TAPPED BOSSES, VALVE LISTED
FOR HORIZONTAL OR VERTICAL INSTALLATION, UL/FM.
FLANGED TYPE IS ACCEPTABLE PROVIDED VALVE HAS THE FEATURES LISTED
ABOVE.
VIKING G-1, TYCO CV-1F
FS-1 FLOW SWITCH - VANE TYPE, 450 PSI, FLOW SENSITIVITY OF 4-10 GPM, TWO
SINGLE POLE DOUBLE THROW SWITCHES, PNEUMATIC RETARD ADJUSTABLE
FROM 0-90 SECONDS WITH AUTOMATIC RESET, NEMA 4 INDOOR/OUTDOOR
RATED METAL HOUSING, UL/FM.
POTTER VSR, SYSTEM
SENSOR WFD
IT-1 COMBINATION INSPECTOR'S TEST AND DRAIN VALVE, 300 PSI, INTEGRAL SIGHT
GLASS, BALL VALVE PLATE INDICATING OFF-TEST-DRAIN POSITIONS,
FURNISHED WITH TEST ORIFICE GIVING FLOW EQUIVALENT TO ONE SPRINKLER
OF A TYPE HAVING THE SMALLEST ORIFICE INSTALLED ON THE SYSTEM,
PRESSURE RELIEF VALVE, UL/FM.
AGF M1011A, RELIABLE
MODEL TD, VICTAULIC
TESTMASTER, GLOBE UTD W/
MODEL ARV PRV
NOTES:
1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS.
2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT.
3. ALL SPRINKLERS SHALL BE UL LISTED.
4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13
REQUIREMENTS.
5. TAG NAME IS PRIMARILY FOR IDENTIFIYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS.
CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED.
6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES.
7. SPRINKLERS SHALL HAVE A 3mm QUICK RESPONSE BULB.
8. SPRINKLERS SPECIFIED WITHIN FIRE SPRINKLER USAGE SCHEDULE ARE STANDARD COVERAGE TYPE. EXTENDED COVERAGE
SPRINKLERS ARE PERMITTED PROVIDED SPRINKLERS MEET THE REQUIREMENTS OF UL.
FIRE SPRINKLER USAGE SCHEDULE
AREA TYPE
(NOTE 1 & 6)
AREA
HAZARD
SPRINKLER
TEMPERATURE
RATING
MANUFACTURER &
MODEL NOTES
TAG NAME
(NOTE 4 & 5) SPRINKLER TYPE
RESPONSE
CATEGORY FINISH
AREAS WITHOUT CEILING
UNLESS NOTED
OTHERWISE
SEE PLANS SPR-1 UPRIGHT QUICK ROUGH
BRASS
PER NFPA VIKING VK, RELIABLE
F1FR, TYCO TY-FRB,
VICTAULIC V2704
NOTE 2, 3, 7, 8
AREAS WITH CEILINGS
UNLESS NOTED
OTHERWISE
SEE PLANS SPR-2 INSTITUTIONAL PENDENT QUICK WHITE PER NFPA TYCO RAVEN, VIKING
VK426
NOTE 2, 3, 7, 8
SIDEWALL APPLICATIONS SEE PLANS SPR-3 INSTITUTIONAL SIDEWALL QUICK WHITE PER NFPA TYCO RAVEN, VIKING
VK427
NOTE 2, 3, 7, 8
COOLER AND FREEZER
AREAS, DRYER CHASE
SEE PLANS SPR-4 DRY CONCEALED W/
WHITE FLAT COVERPLATE
QUICK WHITE PER NFPA VIKING VK, RELIABLE
F3QR, VICTAULIC V3618
NOTE 2, 3, 7, 8
DRYER CHASE SEE PLANS SPR-5 DRY SIDEWALL QUICK ROUGH
BRASS
PER NFPA VIKING VK, RELIABLE
F3QR, TYCO DS,
VICTAULIC V3610
NOTE 2, 3, 7, 8
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
ACID VENTAV
ACID WASTEAW
COLD WATER - POTABLECW
DT DRAIN TILE
SANITARY DRAINAGE (GREASE SANITARY DRAINAGE)GSAN
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
NON-POTABLE COLD WATERNCW
NON-POTABLE HOT WATERNHW
PUMPED DISCHARGEPD
SANITARY DRAINAGESAN
SOFT COLD WATERSCW
SOFT HOT WATERSHW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
WASTE ANETHESIA GAS DISPOSALWAGD
GREASE VENTGV
COMPRESSED AIRCA
DEIONIZED WATERDI
PROPANE GASP
REVERSE OSMOSIS WATERRO
STW SOFT TEMPERED WATER
TW TEMPERED WATER
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
LAB VACUUMVAC
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
GRV GAS REGULATOR VENT
INSTRUMENT AIRIA
MEDICAL AIRMA
MEDICAL VACUUMMV
NITROGENN
NITROUS OXIDENO
OXYGENO
PURE WATERPW
SERVICE WATER - POTABLEW
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
BACKFLOW PREVENTER
MEDIUM PRESSURE GASMPG
EXPANSION JOINT
#.#" IS THE EXPANSION TRAVEL INCHESEJ-#
AIR ADMITTANCE VALVE
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
FLOOR SINKFS
GARBAGE DISPOSERGD
GREASE INTERCEPTORGI
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
MH MANHOLE
MIXING VALVEMV
NEUTRALIZATION TANKNT
OIL SEPARATOROS
ROOF DRAINRD
SHOWERSH
SINKSK
SERVICE SINKSS
TRENCH DRAINTD
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WASH FOUNTAINWF
WATER HEATERWH
WASHING MACHINE FIXTUREWMF
YARD CLEANOUTYCO
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTESUON
EXISTINGE
FLOW METERFM
WATER SOFTENERWS
WATER METERWM
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
DUCTILE IRONDI
UTILITY BOXUB
SHORT CIRCUIT CURRENT RATINGSCCR
FOOD SERVICE PLANSFSP
IW INDIRECT WASTE
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
INDICATES A PLUMBING CONNECTION TO A FOOD SERVICE EQUIPMENT.
REFERENCE FOOD SERVICE DRAWINGS FOR ADDITIONAL INFORMATION IN
REGARDS TO TYPE OF EQUIPMENT, ROUGH-IN SIZES, AND ADDITIONAL
COMMENTS.
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
CIVIL CONTRACTORC.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE EQUIPMENT CONTRACTORFSEC
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
TECHNOLOGY
MIKE MCCARTY
MIKE MCCARTY
KRISTEN SPINA
DAMON DEEN
DESCRIPTION: PERSON:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
DRY WALL CONTRACTOR FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS,
ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE DRY WALL
CONTRACTOR OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.
17. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
18. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH THEIR WORK.
6. THIS CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,
CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK REQUIRED BY
THEIR WORK.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE
BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL
APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
5. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY
ALL ELEVATIONS BEFORE BEGINNING WORK.
6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANY WORK.
7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.
8. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL
SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR
ADDITIONAL DEMOLITION INFORMATION.
9. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK
UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL
INFORMATION.
10. P.C. SHALL REFERENCE ALL PLANS WITHIN DRAWING SET FOR SCOPE OF WORK. P.C.
SHALL REVIEW FOOD SERVICE DRAWINGS FOR COORDINATION OF WORK BETWEEN P.C.
AND FSEC.
11. P.C. SHALL PROVIDE ALL NECESSARY SHUT-OFF VALVES, PRESSURE REGULATORS,
INDIVIDUAL EQUIPMENT SUPPLY STOPS, ETC. REQUIRED UPSTREAM OF FINAL SUPPLY
CONNECTION(S) TO FOOD SERVICE EQUIPMENT UNLESS NOTED OTHERWISE.
12. ALL INDIRECT WASTES FOR FOODSERVICE EQUIPMENT WILL BE EXTENDED TO FLOOR
DRAINS BY MECHANICAL TRADES, EXCEPT FOR THE WALK-IN REFRIGERATOR/FREEZER
BLOWER COIL DRAINLINES AND DRAINLINES WITHIN THE CUSTOM FABRICATED COUNTERS
WHICH WILL BE EXTENDED TO FLOOR DRAINS BY THE FSEC.
13. THE FSEC IS RESPONSIBLE FOR SETTING FOOD SERVICE EQUIPMENT IN PLACE. FINAL
CONNECTIONS AND INTERCONNECTIONS FOR THIS EQUIPMENT ARE THE RESPONSIBILITY
OF THE P.C.
14. SINK FAUCETS FURNISHED LOOSE BY FSEC FOR INSTALLATION BY P.C. SINK ROTARY DRAIN
& OVERFLOW FURNISHED AND INSTALLED BY FSEC; TAILPIECE, P-TRAP, ESCUTCHEON
PLATES AND DRAIN CONNECTION FURNISHED AND INSTALLED BY P.C. EXCEPT FOR
TAILPIECE AND P-TRAP FOR WALL MOUNTED HANDSINKS WHICH ARE PROVIDED BY FSEC
AND INSTALLED BY P.C.
15. HEALTH CODES REQUIRE THAT ALL PLUMBING BE ENCLOSED IN WALLS OR FLOOR AND
THAT EXPOSED PIPING RUNS BE AS SHORT AS POSSIBLE. GAS PIPING TO BE SLEEVED AND
VENTED PER CODE SO IT IS CONCEALED WITHIN THE WALL. EXPOSED HORIZONTAL PIPING
MUST BE 6” ABOVE THE FLOOR AND AT LEAST 1” OFF THE WALL. ANY EXPOSED HAND SINK
PIPING (BOTH DRAIN AND SUPPLY LINES) ARE TO BE CHROME PLATED.
16. RECOMMENDED HOT WATER TEMPERATURES FOR SINKS SHOULD BE AS FOLLOWS: POT &
PAN SINKS SET AT 120° F MAXIMUM, HAND SINKS SET AT 110° F MAXIMUM AND ALL OTHER
SINKS SET AT 110-120° F MAXIMUM. HOT WATER TEMPERATURES MUST CONFORM TO CODE
REQUIREMENTS.
17. FLOOR TROUGHS NOTED ON FOOD SERVICE PLANS SHALL BE PROVIDED BY FSEC,
INSTALLED BY P.C. REFER TO 6/FS300 FOR FLOOR TROUGH DETAIL.
PLUMBING GENERAL NOTES:
PLUMBING SLOPE REQUIREMENTS:
INTERIOR:
SANITARY WASTE: 1/4” PER FOOT
GREASE WASTE: 1/4” PER FOOT
CONDENSATE AND INDIRECT DRAINAGE: 1/8” PER FOOT
SANITARY AND GREASE VENT: NO SPECIFIC PITCH, PITCH TO FIXTURES
DOMESTIC WATER: NO SPECIFIC PITCH, PITCH TO FIXTURES
BASED ON PLUMBING CODE: UPC-2021
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
LIFE SAFETY CODE: NFPA 101 2012 EDITION
ENERGY CONSERVATION CODE: IECC 2012
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
WATER HEATER SIZING:
1. KITCHEN WATER HEATER DEMAND
A. 3000 MEALS PER DAY SERVED
B. ASHRAE APPLICATIONS, CHAPTER 51 FOR SERVICE WATER HEATING, FIG. 20 - FOOD
SERVICE INDICATES 1.5 GPH RECOVERY CAPACITY PER MAXIMUM MEALS PER HOUR
C. ESTIMATE 500 MEALS PER HOUR
D. 500*1.5 = 750 GPH RECOVERY CAPACITY REQUIRED FOR KITCHEN
2. LAUNDRY WATER HEATER DEMAND
A. AO SMITH ONLINE SIZING
B. COMMERCIAL LAUNDRY
C. (6) 100 LB WASHERS
D. PEAK DEMAND = 1,680 GPH
3. MAXIMUM SYSTEM DEMAND:
A. KITCHEN = 750 GPH
B. LAUNDRY = 1680 GPH
C. TOTAL…