RFB922300-01 - DOC CCF Kitchen & Laundry Addition - Addendum #1.pdf
PDF 8 MB Posted
- Attached to
- DOC CCF Kitchen & Laundry Addition
- Solicitation number
- RFB922300-01
- Issued by
- Polk County, Iowa
About this file
This document is Addendum Number 1.0 for the Clarinda Correctional Facility Kitchen & Laundry Addition project, issued by the State of Iowa Department of Corrections on December 22, 2022. The addendum modifies various technical drawings and specifications for the project, including updates to the civil, structural, architectural, foodservice equipment, plumbing, mechanical, and electrical plans. The bid is due on January 19, 2023 at 2:00 PM local time through the IMPACS Electronic Procurement System, with bidders required to acknowledge receipt of this addendum on their bid form.
The addendum includes several key modifications, such as adding a temporary security shed and job trailer locations, revising door frame and door hardware installation instructions, adjusting mechanical equipment layout and flue details, and updating plumbing and electrical specifications. The total building area is 22,250 square feet with a building height of 28'-6", located at 2000 N 16th St in Clarinda, Iowa. The project involves multiple engineering and architectural firms, including Farnsworth Group (architect), Bishop Engineering, KPFF Consulting Engineers, IMEG, and Rippe Associates, indicating a complex, multi-disciplinary infrastructure improvement project for the correctional facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum
14225 University Avenue, Suite 110 | Waukee, IA 50263 | p 515.225.3469 | www.f-w.com
ENGINEERS | ARCHITECTS | SURVEYORS | SCIENTISTS
Addendum Number: 1.0
Addendum Issue Date: December 22, 2022 Owner: State of Iowa Department of Corrections – Clarinda
Correctional Facility
Project Name: Clarinda Correctional Facility – Kitchen & Laundry
RFB Number: 922300-01
Containing: 3 Pages; 8 Drawings; 0 Specifications
This addendum amends the drawings and specifications of the above reference project and is hereby incorporated into the contract documents as part thereof. Bidders must acknowledge receipt of this Addendum in the space provided on the Bid Form. FAILURE TO DO SO MAY SUBJECT BIDDER TO DISQUALIFICATION.
Drawings:
Item No. 1. COVER SHEET
1. REPLACE Cover sheet with attached, updated Cover sheet.
Civil:
Item No. 2. C2.1 – LAYOUT PLAN
1. ADD temporary Security Shed at the west side of the Construction Access.
2. ADD temporary Job Trailer Locations at gravel staging area.
Item No. 3. C4.1 – UTILITY PLAN
1. ADD Notes/Callouts for Contractor to install power to the Temporary Security Shed and Job Trailers per MEP Plans.
Structural:
Item No. 4. S1.1 – FOUNDATION PLAN – AREA ‘A’
Reference view 1 – FOUNDATION PLAN – AREA ‘A’
1. ADD thickened slabs under washing machines.
2. ADD section cuts for new detail D1/S5.1.
Item No. 5. S5.1 – STRUCTURAL DETAILS
1. ADD detail D1 showing thickened slab construction under washing machines.
Architectural:
Item No. 6. A7.2 – DOOR SCHEDULE, ELEVATIONS AND DETAILS
Reference – DOOR SCHEDULE NOTES:
Farnsworth Group, Inc.
1. REVISE item 3. to read as follows: “DOOR FRAME, DOOR, DOOR HARDWARE AND ALL ASSOCATIED
ELEMENTS SHALL BE OWNER FURNISHED AND OWNER INSTALLED PRIOR TO THE START OF
CONSTRUCTION”
Foodservice Equipment:
Item No. 7. FS401 – FOODSERVICE EQUIPMENT STANDARD DETAILS
Reference view – SD-188 WALK-IN FLOOR – FLOORLESS W/ HIGH SCREEDS, INSUL. W/ HEAT
1. Clarification: Conduit and heat cable are installed in a 1” mortar bed below the vapor barrier and insulation.
Fire Protection: NA
Plumbing:
Item No. 8. P6.2 – PLUMBING SCHEDULES
Reference View – PLUMBING MATERIAL LIST CONTINUED
1. ADD Willoughby and Metcraft to WC-2 as acceptable manufacturers for the water closet. No change to flush valve manufacturers.
Mechanical:
Item No. 9. M1.4 – LEVEL 02 PLAN – AREA B – MECHANICAL
Reference view 1 – LEVEL 02 PLAN – AREA B - MECHANICAL
1. REVISE DOAS-1 and AHU-1 layout locations and modify DOAS-1 to show enlarged burner section.
Item No. 10. M3.0 – ENLARGED PLAN - MECHANICAL
Reference view 1 – LEVEL 02 PLAN – AREA B – MEHCNAICAL ENLARGED PLAN
1. REVISE DOAS-1 and AHU-1 layout locations and modify DOAS-1 to show enlarged burner section.
2. REVISE keynote 9 to callout two 10” diameter flues.
Reference view 2 – SECTION – DOAS-1
3. REVISE DOAS-1 section to show two 10” diameter flues.
Item No. 11. M4.3 – MECHANICAL DETAILS
Reference view 1 – LEVEL 02 PLAN – AREA B – MECHANICAL ENLARGED PLAN
1. REVISE DOAS-1 detail for enlarged burner section.
2. REVISE keynote 11 to callout burner damper locations.
Electrical:
Item No. 12. E1.7 – LEVEL 02 PLAN – AREA B - POWER
Reference view – LEVEL 02 PLAN – AREA B - POWER
1. REVISE location of VFD-7.5 and VFD-20 to south to coordinate with DOAS-1 duct and required service clearances.
Technology: NA
Farnsworth Group, Inc.
Specifications:
Item No. 13. Section 11 4000 - FOODSERVICE EQUIPMENT
Reference – Article 3.06 Item Specifications - Item #20 – FLOOR TROUGH
1. REVISE quantity to “One”
Reference – Article 3.06 Item Specifications - Item #188 – HOSE REEL SECURITY CABINET
2. REVISE item name to read “HOSE STATION SECURITY CABINET”
3. REVISE quantity to “One”
Item No. 14. Section 23 7313 – INDOOR MODULAR AIR HANDLING UNITS
Section 2.01 – MODULAR INDOOR AIR HANDLING UNITS – Article I. Burner and Heat Exchanger – Item 1.
1. ADD the following verbiage at the end of the item “Dampers shall be controlled by burner controller based on modulating input signal for firing rate.”
Product Approvals:
The following manufacturers are approved as substitute products of the named Base Bid manufacturer(s). Approval is contingent upon manufacturers fulfilling all specification requirements, tangible and intangible, equally as well as specified product.
References/Item Manufacturer/Supplier
Bids are Due: January 19, 2023 / 2:00 PM local time to IMPACS Electronic Procurement System.
END OF ADDENDUM
Issued By:
FARNSWORTH GROUP, INC.
Kelsey Vetter, AIA
Project Architect
Attachments:
Drawings: COVER, C2.1, C4.1, S1.1, S5.1, M1.4, M3.0, M4.3
Specifications: NA
Other: NA
PROJECT NO.: DATE:
PROFESSIONAL REGISTRATIONS
LOCATION MAP
PROJECT IMAGE
IMAGE © < COPYRIGHT NOTICE >
S T
A T
E O
F I O
W A
D E
P A
R T
M E
N T
O F
C O
R R
E C
T
IO
N S
/2
/2
:3
:1
A
M
0211435.00
CLARINDA CORRECTIONAL FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA DEPARTMENT OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA 51632
11/18/2022
C L
A R
IN
D
A C
O R
R E
C T
IO
N
A L F
A C
IL
IT
Y
K
IT
C H
E N
L
A U
N D
R Y
A D
D
IT
IO
N
B
ID
S E
T
BID SET
11/18/2022
ARCHITECT:
FARNSWORTH GROUP
14225 University Ave Ste 110 Waukee, IA 50263
ENGINEERS:
BISHOP ENGINEERING
3501 104th St, Urbandale, IA 50322
KPFF CONSULTING ENGINEERS
604 Locust St Ste. 202 Des Moines, IA 50309
IMEG
2882 106th St Des Moines, IA 50263
RIPPE ASSOCIATES
10400 Yellow Circle Drive Ste 100 Minneapolis, MN 55343
CONSULTANT:
CLARINDA CORRECTIONAL FACILITY
200 N. 16TH St, Clarinda, IA 51632
ROBERT C.
RIDGWAY
07570
L
IC
E N
S E
D P
R
OFESS IONA
L A
R C
H
IT
E C
* IO W A *
T ROBERT C. RIDGWAY Date
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct personal supervision and responsible charge.
I am a duly licensed architect under the laws of the state of Iowa.
Signature:
License Expires:
Pages or sheets covered by this seal:
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF IOWA
NATHAN T. KRESS (DATE)
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2023
PAGES OR SHEETS COVERED BY THIS SEAL
NATHAN T.
KRESS
21136
PROFESSIONAL
D E
S N
E C I
L
E N
G I
NE
E
R
I OWA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2022
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P23167
L
IC
E N
L E
N G
I N E
E R
TONY E.
DELOUIS
TONY E. DELOUIS
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2023
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P20825
L
IC
E N
L E
N G
I N E
E R
ERIC J.
HENDERSON
ERIC J. HENDERSON
C0.1, C1.1, C2.1, C3.1, C4.1, C5.1, C6.1, C6.2, C7.1
L
IC
E N
S E D
PROFESS IONAL
EN
G
IN
E
E R
I OWA
23468
SUNDERMAN
SETH
V.
SIGNED: DATE:
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS PREPARED BY
ME OR UNDER MY DIRECT PERSONAL SUPERVISION AND THAT I AM A DULY
LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
PAGES OR SHEETS COVERED BY THIS SEAL:
SETH V. SUNDERMAN, P.E. 23468
LICENSE RENEWAL DATE: DEC. 31, 2023
ST 30" ST 30"
ST
ST
ST 24" ST 24"
ST 30"
ST 30"
6" DEPTH PCC ON 12"
DEPTH PREPARED
SUBGRADE
(REF. DETAIL 1, C6.1)
PROPOSED BUILDING
TOTAL BLDG. AREA = 22,250 SF
BLDG . HEIGHT = 28'-6"
FF=1049.24'
SAN 6" SAN 6" SAN 6"
ST
ST 24" ST 24"
MA
TC
H
EX
PROP. CONTRACTOR STORAGE AREA
6" DEPTH CLASS A ROADSTONE
PROP. CONTRACTOR & TRAILER PARKING
6" DEPTH CLASS A ROADSTONE
CO
ST
ST
S
D D
D
D
37'
.1'
113.93'
113.89'
11.08'
11'
62.43'
.94
92.87'53.44'
.95
.81
20'
.89
20'17'
8.2 8'
55.86'
33.48'
0.9
9'
14.
06'
2'
5' 14.
47'
58.63'
.93
6'
6'
6' 6'
228.66'
.12
4" DEPTH 3/4"
DIA GREY TRAP
ROCK, TYP. TEMPORARY
MANGATE
12' HT TEMPORARY
SECURITY FENCE
(RAZOR WIRE & FENCE
PROVIDED BY OWNER, NIC)
TEMPORARY DELIVERY GATE
(BY OTHERS, NIC. CONTRACTOR TO
COORDINATE SECURITY &
CONSTRUCTION WITH OWNER)
16' WIDE SLIDING
GATE /W MOTOR
(BY OWNER, NIC)
EXTERIOR VISITOR AREA
TO BE REMOVED AND
REINSTALLED
(BY OWNER, NIC)
6" DEPTH CLASS A ROADSTONE
GRAVEL SHOULDER TO BE 5' OFF
OF SECURITY FENCE6" DEPTH CLASS A
ROADSTONE
GRAVEL SHOULDER
6" DEPTH PCC FLUME W/
6" CURB
PCC FLUME
(MATCH EX. PAVEMENT &
DEPTH)
6" DEPTH CLASS A
ROADSTONE GRAVEL
SHOULDER
6" DEPTH CLASS A ROADSTONE
GRAVEL SHOULDER TO BE 5' OFF
BACK OF CURB
12' HT TEMPORARY
SECURITY FENCE
(RAZOR WIRE & FENCE
PROVIDED BY OWNER, NIC)
TEMP. 6" DEPTH CLASS A
ROADSTONE
4" DEPTH 3/4"
DIA GREY TRAP
ROCK, TYP.
4" DEPTH 3/4"
DIA GREY TRAP
ROCK, TYP.
5.99'
5.96'
R2'
R2'
R1
R1'40 .1'
6" DEPTH PCC W/ 6" CURB
ON PREPARED SUBGRADE
5" DEPTH SIDEWALK BEHIND
BACK OF CURB W/ EXPANSION JOINT
MATCH EX. CURB DESIGN
2' WIDE FLUME TO
MAINTAIN EX
DRAINAGE
PATTERNS
NEW GENERATOR
PAD (REF. ELEC)
6" BOLLARD, 4' HT. PAINTED HIGH
VISIBILITY YELLOW, TYP.
(REF. DETAIL 5, C6.1)
R10'
R10'
PCC PAVEMENT AT MINIMUM 6" DEPTH OR 1"
GREATER THAN EXISTING ADJACENT PAVEMENTS
G4" G
4"
130.0'
.4'
27.7'
25.4'
5.5'
5.3
.6'
69.9'1.1'
59.
9'
.8'
57.7'
5.0
8.7 1'
51.
6'
62.2'
.5'
16.67'
BUILDING DOOR PAD (TYP.)
REF. TO STRUCTURAL
BUILDING DOOR PAD (TYP.)
REF. TO STRUCTURAL
5'
CONTRACTOR TO COORDINATE W/
OWNER FOR REMOVAL OF TEMPORARY
DELIVERY GATES AT END OF CONSTRUCTION
AND RESTORE ORIGINAL FENCE AND GRANULAR SECTION
6" BOLLARD, 4' HT. HIGH VISIBILITY
YELLOW, TYP.
(REF. ARCH PLANS FOR LOCATION
SEE DETAIL 5, C6.1 FOR BOLLARD DETAIL)
S
9.91'
.28
10.71'
.65
(BY OWNER, NIC)
(BY OWNER, NIC)
GRAVEL DRIVE
6" DEPTH CLASS A ROAD STONE
(BY OWNER, NIC)
REF. TO DETAIL
16, C6.1 FOR
SECURITY LATCH
10" DEPTH PCC
REINFORCED COLLAR, TYP.
(REF. DETAIL 16, C6.1)
5" DEPTH PCC ISLAND CAP
5'
5'
APPROX. 2'
ROCK STRIP
FENCE 6" OFF PAVEMENT
5" DEPTH PCC ON 6"
PREPARED SUBGRADE
5" DEPTH PCC ON 6"
PREPARED SUBGRADE
10" DEPTH PCC
REINFORCED COLLAR, TYP.
(REF. DETAIL 16, C6.1)
TEMPORARY SECURITY
CHECK POINT SHED. BY
OTHERS, NIC. CONTRACTOR
TO COORDINATE SECURITY &
CONSTRUCTION WITH
OWNER)
JOB TRAILERS
XX
X X
X X
X X
X X
X
CP #9000
CP #9001
CP #9002
CP #9003
Y A DR
Y A DR
Y A DR
CP #9004
EX. 12' BARBED WIRE
CHAIN LINK SECURITY FENCE
CP #9005
CP #9006
CP #9007
CP #9008
CP #9009
CP #9010
CP #9100
CP #9101
H Y D
WV
WVEP
GV
FO
EP
S
EP
CO
EP
X X
X X
X X
X X
X
X
X X X X
EX. 12' BARBED WIRE SECURITY FENCE
EX. GRAVEL
EX. GRAVEL
EX. NO PARKING SIGN
EX. HANDICAP
PARKING SIGN
EX. NO
PARKING
SIGN
EX. LAW
ENFORCEMENT
ONLY SIGN
EX. DO NOT
ENTER SIGN
EX. BUILDING
(MEDIUM SECURITY PRISON)
FF=1049.24
EX. DOOR
EX. DOOR
EX. SECURITY GATE EX. SECURITY GATE
CP #9012
CP #9013
CP #9014
CP #9015
CP #9016
EP
EP EP
EP
X X
X
X X X
EX. BASKETBALL HOOP
EX. BASKETBALL HOOP
EX. SECURITY
GATE
EX. PING
PONG TABLE
EX. HORSESHOE PITS
EX. OUTDOOR TABLES
EX. SECURITY BOOTH
EX. SECURITY GATE
EX. CONCRETE SIDEWALK
EX. CONCRETE DRAINAGE DITCH
EX. GRAVEL EX. CONCRETE
DRAINAGE
GUTTER
SAN 8" SAN 8" SAN 8" SAN
SA
N
SA
N
SA
N
SA
N
EX. SECURITY GATE
X
EX. SECURITY GATE
EX. 10' CHAIN LINK SECURITY FENCE
EX. 12' BARBED WIRE CHAIN LINK SECURITY FENCE
EX. POLE W/ CAMERA
EX. SKID
PLATE
WATER SHUT-OFF VALVE
EX. CIGARETTE
DISPOSAL
TRASH CAN
EX. POLE W/ CAMERA
32.
0'
129.0'
32.0'
9.0
32.
0'
57.8'
.3'
141.2'
1.8
EX. 10' BARBED WIRE
CHAIN LINK
SECURITY FENCE
EX
. G
RA
VE
L
EX
. C
ON
CR
ET
E
XXX
XXX
X X
X
X X
X X
ST 24" ST 24"
W8" W8" W8" W8"
W6" W6"G 6" G 6" G 6" G 6"
CATVCATV
CATV
CATV
CATV
CATV
CATV
CATV
CATV
CATV
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W8" W8" W8" W8" W8" W8" W8"
W 8"
W 8"
W 8"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6" G 6" G 6" G 6" G 6" G 6" G 6"
G 6"
G 6"
G 6"
TE
LE
TE
LE
TELE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TELE
U/ E
U/ E
U/E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/E U/E
U/E U/E
U/E U/E
U/E
U/E
U/E U/E
U/E U/E
EX. LIFT STATION
SAN
SA
N
SA
N
SAN SAN
SAN
SA
N
SA
N
ST
12"
EX. SIGN
EX. GAZEBO
SAN
4"
SAN
4"
SAN
4"
GM
EX. GAS
METER AND
TREE
ST
STSTST
ST
ST
ST
ST
ST
ST
EX. FRENCH DRAIN
EX. FRENCH DRAIN
X X X X X
X X
X X X X X
DRAWN PER
AERIAL IMAGE
DRAWN PER AERIAL IMAGE
DRAWN PER AERIAL IMAGE
DRAWN PER AERIAL IMAGE
DRAWN PER AERIAL IMAGE
S
S
S S
SAN
SAN
SAN
EX. BOLLARD (TYP.)
N 16TH STREET
PRIVATE ACCESS DRIVE
EX. ROOF DRAIN (TYP.)
EX. ROOF DRAIN (TYP.)
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
0211435.00
CLARINDA
CORRECTIONS
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
100% CONSTRUCTION
DOCUMENTS
SVS
LR
SVS
1 12/22/2022 ADDENDUM 1.0
GRAPHIC SCALE
030 15 30 60
L:\
LA
ND
P
RO
JE
CT
S
\21
C
LA
RI
ND
A
CO
RR
EC
TI
ON
AL
K
IT
CH
EN
LA
UN
DR
Y
AD
DI
TI
ON
\D
W G\
C2
LA
YO
UT
.D W
G
/22 /20
:02 :02
A M
LAYOUT PLAN
C2.1
GENERAL NOTES:
1. CONTRACTOR TO PROVIDE GRADATION TESTING FOR
GRANULAR MATERIAL DELIVERED TO THE SITE GRADATION
TESTING IS TO BE CONDUCTED AND REVIEWED BY
GEOTECHNICAL FIRM PRIOR TO GRANULAR MATERIAL BEING
INSTALLED.
2. IF GRANULAR MATERIAL ARE INSTALLED THAT DO NOT MEET THE
APPROVED GEOTECHNICAL REPORT AND SPECIFICATIONS. THE
CONTRACTOR, SHALL AT THEIR OWN EXPENSE, REMOVE AND
REPLACE THE DEFICIENT GRANULAR MATERIAL PER
SPECIFICATION.
3. CONTRACTOR TO COORDINATE WITH OWNER TO MAINTAIN
SECURITY AND FOR ANY MODIFICATION OF THE SECURITY FENCE
AND GATES
4. CONTRACTOR TO REMOVE TEMPORARY GRAVEL DRIVE AND RESTORE TO
ORIGINAL CONDITION AFTER COMPLETION OF PROJECT
PAVEMENT & ASPHALT PLACEMENT NOTES:
1. SEE PROJECT SPECIFICATION 32 13 13 FOR ADDITIONAL
INFORMATION ON LASER SCREED REQUIREMENTS.
2. CONTRACTOR TO CONNECT TO EXISTING PCC PAVEMENTS WITH
IOWA SUDAS TYPICAL BT JOINT.
3. CONTRACTOR TO REPLACE PCC PAVEMENTS FOR STORM
SEWER INSTALLATION PER SUDAS. CONTRACTOR TO REPLACE
PAVEMENTS WITH A MINIMUM THICKNESS THAT IS 1" GREATER
THAN THE EXISTING PAVEMENT THICKNESS.
4. CONTRACTOR TO COORDINATE WITH PROPERTY OWNER FOR
TRAILER PARKING & STAGING AREA.
BUILDING & STRUCTURAL NOTES:
1. SEE FINAL ARCHITECTURAL PLANS FOR BUILDING DIMENSIONS.
2. CONTRACTOR TO REFER TO ARCHITECTURAL PLANS FOR
DETAILED BUILDING CONSTRUCTION INFORMATION.
3. CONTRACTOR TO REFER TO STRUCTURAL PLANS FOR DETAILED
BUILDING FOUNDATION AND STOOP LOCATIONS AND DETAILED
CONSTRUCTION INFORMATION.
RESTORATION NOTES:
1. CONTRACTOR TO REMOVE AND RESTORE TEMPORARY
CONSTRUCTION AREAS TO PREVIOUS WORKING CONDITION
AFTER CONSTRUCTION.
2. CONTRACTOR TO DISPOSE/STOCKPILE EXCESS EARTH & GRAVEL
WASTE IN AREA DESIGNATED BY OWNER.
BID SET
XX
X X
X X
X X
X X
X
EX INTAKE
RIM=1045.30
FL(NE)= 1043.85
FL(SE)= 1043.30
EX INTAKE
RIM=1045.25
FL(SE)= 1044.15
Y A DR
Y A DR
Y A DR
EX RCP24" FES
FL=1040.58
H Y D
WV
WVEP
GV
FO
EP
S
EX SAN MH
RIM=1044.32
INV(N)= 1035.67
*RIM=1042.50
*INV(N)=1034.00
*BOTTOM=1029.50
*INV(OUT)=1038.00
*PER REF. CCF C2.1 UTILITY PLAN
EP
CO
EP
X X
X X
X X
X X
X
X
X X X X
EX. BUILDING
(MEDIUM SECURITY PRISON)
FF=1049.24
EX 12" CPP
W/ HEADWALL
AND GRATE
FL=1039.20
EX 12" CPP
FL=1039.62
EX RCP24" FES
FL=1039.59
EX INTAKE
RIM=1039.64
EX " CPP
FL=1037.57
EX INTAKE
RIM=1043.78
FL= 1041.89EX " CPP
FL=1041.89
EP
EP EP
EP
X X
X
X X X
SAN 8" SAN 8" SAN 8" SAN
SA
N
SA
N
SA
N
SA
N
X
APPROX. LOCATION PER
ALLIANT ENERGY MAP
32.
0'
129.0'
32.0'
9.0
32.
0'
57.8'
.3'
141.2'
1.8
XXX
XXX
X X
X
X X
X X
ST 24" ST 24"
W8" W8" W8" W8"
W6" W6"G 6" G 6" G 6" G 6"
CATVCATV
CATV
CATV
CATV
CATV
CATV
CATV
CATV
CATV
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W 8"
W8" W8" W8" W8" W8" W8" W8"
W 8"
W 8"
W 8"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6"
G 6" G 6" G 6" G 6" G 6" G 6" G 6"
G 6"
G 6"
G 6"
TE
LE
TE
LE
TELE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TE
LE
TELE
U/ E
U/ E
U/E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/ E
U/E U/E
APPROX. LOCATION
PER LEO A DALY
UTILITY PLAN SHEET
APPROX. LOCATION
PER LEO A DALY
UTILITY PLAN SHEET
U/E U/E
U/E U/E
U/E
U/E
U/E U/E
U/E U/E
APPROX. LOCATION
PER LEO A DALY
UTILITY PLAN SHEET
SAN
SA
N
SA
N
SAN SAN
SAN
SA
N
SA
N
ST
12"
SAN
4"
SAN
4"
SAN
4"
GM
ST
STSTST
ST
ST
ST
ST
ST
ST
X X X X X
X X
X X X X X
S
S
S S
SANITARY SEWER GRINDER MANHOLE
RIM=1045.60
INV=1036.40
BOTTOM=1035.90
(REF. CCF C2.1 UTILITY PLAN)
SANITARY SEWER MANHOLE
RIM=1045.40± (PAV.)
INV(W)=1038.50
INV=1036.70
(REF. CCF C2.1 UTILITY PLAN)
SANITARY SEWER MANHOLE
RIM=1046.20
INV(IN)=1037.25
(REF. CCF C2.1 UTILITY PLAN)
SANITARY SEWER MANHOLE
RIM=1046.50
INV(IN)=1042.00
INV(OUT)=1040.65
(REF. CCF C2.1 UTILITY PLAN)
SAN
SAN
SAN
APPROX. LOCATION PER CCF
SEWER MAIN EXTENSION PLAN
1-26-2000
N 16TH STREET
PRIVATE ACCESS DRIVE
ST 30" ST 30"
ST
ST
ST 24" ST 24"
ST 30"
ST 30"
PROPOSED BUILDING
TOTAL BLDG. AREA = 22,250 SF
BLDG . HEIGHT = 28'-6"
FF=1049.24'
SAN 6" SAN 6" SAN 6"
ST
ST 24" ST 24"
CO
ST
ST
S
D D
D
D
149 LF- 30" N-12
@ S=0.35%
STRUCT #4A
30" FES W/ FOOTING &
APRON GUARD
FL=1040.80
124 LF- 30" N-12
@ S=0.35%
8 L
F-
" N -1
S =0
.35
3 L
F-
" N -1
S =0
.35
STRUCT #4
30" NYLOPLAST W/ BOLTED FLAT
GRATE
RIM=1044.87
FL(W/E)=1041.31
(REF. DETAIL 16, C6.1 FOR
SECURE LATCH SYSTEM)
STRUCT #3
30" NYLOPLAST W/ BOLTED FLAT GRATE
RIM=1045.18
FL(N/E)=1041.75
(REF. DETAIL 16, C6.1 FOR SECURE
LATCH SYSTEM)
STRUCT #2
24" NYLOPLAST W/
BOLTED FLAT GRATE
RIM=1045.25
FL(N/S)=1042.23
(REF. DETAIL 16, C6.1
FOR SECURE LATCH
SYSTEM)
STRUCT #1
18" NYLOPLAST W/ BOLTED FLAT
GRATE
RIM=1046.30
FL(S)=1042.66
(REF. DETAIL 16, C6.1 FOR
SECURE LATCH SYSTEM)
STRUCT #5A
24" NYLOPLAST W/ BOLTED SOLID LID
RIM=1049.11
FL(W)=1045.25
FL(E)=1044.75
(REF. DETAIL 16, C6.1 FOR SECURE
LATCH SYSTEM)
STRUCT #5
24" NYLOPLAST W/ BOLTED
SOLID LID
RIM=1049.11
FL(W)=1046.01
(REF. DETAIL 16, C6.1 FOR
SECURE LATCH SYSTEM)
PROP. GREASE
INTERCEPTOR
CONNECTION
INV= 1043.36
(REF. TO MEP PLAN
FOR CONTINUATION)
149 LF 6" SANI. SWR
@ 1.0% SLOPE
SANI MH W/
BOLTED LID &
MUFFIN MONSTER
RIM=1047.25
INV(E/W)=1039.95
(REF. DETAIL 16,
C6.1)
STRUCT #6
24" NYLOPLAST W/ BOLTED
FLAT GRATE
RIM=1045.11
FL(W/SW)=1041.62
(REF. DETAIL 16, C6.1 FOR
SECURE LATCH SYSTEM)
117 LF- 24" RCP
@ S=0.85%
(BORE & JACK)
STRUCT #6A
24" FES W/ FOOTING &
APRON GUARD
FL=1040.80
STRUCT #7
24" FES W/ FOOTING &
APRON GUARD
FL=1040.58
STRUCT #7A
24" FES W/ FOOTING &
APRON GUARD
FL=1039.59
CONTRACTOR TO CONNECT
TO EX. 10" PIPE W/ "WYE"
CONNECTION
NEW 6" INV=1038.46
EX. 10" INV=1036.06±
VERIFY INV. ELEV.
PRIOR TO
CONSTRUCTION
SANI CLEANOUT
RIM=1049.09
INV(SE)=1041.87
*CRITICAL CROSSINGS*
(CONTRACTOR TO VERIFY
DEPTHS & AVOID CONFLICTS)
61 LF- 24"
SLOTTED DRAIN
S=0.25%
48 LF- 24"
SLOTTED DRAIN
S=0.25%
38 LF- 24"
SLOTTED DRAIN
S=0.10%
28 LF- 24"
SLOTTED DRAIN
S=0.25%
127 LF- 24"
SLOTTED DRAIN
S=0.25%
149 LF- 24" N-12
@ S=2.10%
65 LF- 24" N-12
@ S=1.26%
*CRITICAL CROSSINGS*
(CONTRACTOR TO VERIFY
DEPTHS & AVOID CONFLICTS)
SANI SWR SERVICE
CONNECTION
INV=1042.20
(REF. PLUMB. FOR CONTI.)
ROOF DRAIN LINE
DOWNSPOUT. TYP.
(REF. ARCH)
6" DIA ROOF
DRAIN LINE @
2.0% MIN. (TYP)
CONNECT ROOF DRAIN LINE
TO STORM WITH WYE
CONNECTION. (TYP)
GENERATOR PAD
*CRITICAL CROSSING*
FL(STORM)=1041.12
INV(SAN)=1039.13
FL=1041.62
G4" G
4"
PROP. 4" GAS LINE
SEE MEP PLAN FOR DETAILS
SHOWN FOR COORDINATION PURPOSES ONLY
CONNECT TO NEW STORM
W/ WYE & INSERTA TEE FITTINGS
S
MANUAL BYPASS
STRUCTURE
RIM=1047.64
INV(E/W)=1040.05
(REF. DETAIL 3,
C6.2)
ROOF DRAIN LINE
DOWNSPOUT. TYP.
(REF. ARCH)
6" DIA ROOF
DRAIN LINE @
2.0% MIN. (TYP)
CONNECT
BUILDING ROOF
DOWN SPOUTS
TO 24" SLOTTED
DRAIN
18 LF 6" SANI. SWR
@ 1.80% SLOPE
14 LF 6" SANI. SWR
@ 1.80% SLOPE
29 LF 6" SANI. SWR
@ 11.58% SLOPE
FL=1041.12
10 LF 6" SANI. SWR
@ 1.0% SLOPE
CONNECT
EXISTING
BUILDING ROOF
DOWN SPOUTS
TO 24" SLOTTED
DRAIN
BUILDING GAS SERVICE
CONNECTION (REF. TO MEP PLAN)
CONNECT
EXISTING
BUILDING ROOF
DOWN SPOUTS
TO 24" SLOTTED
DRAIN
ELECTRICAL CONTRACTOR TO
PROVIDE POWER FROM THE
EXISTING ELECTRIC POWER POLE
TO THE PROPOSED JOB TRAILERS.
(REF TO MEP PLANS)
ELECTRICAL CONTRACTOR TO PROVIDE
POWER TO TEMP. SECURITY SHED.
(REF TO MEP PLANS)
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
0211435.00
CLARINDA
CORRECTIONS
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
100% CONSTRUCTION
DOCUMENTS
SVS
LR
SVS
1 12/22/2022 ADDENDUM 1.0
GRAPHIC SCALE
030 15 30 60
L:\
LA
ND
P
RO
JE
CT
S
\21
C
LA
RI
ND
A
CO
RR
EC
TI
ON
AL
K
IT
CH
EN
LA
UN
DR
Y
AD
DI
TI
ON
\D
W G\
C4 U
TI
LIT
Y.
DW
G
/22 /20
:05 :23
A M
UTILITY PLAN
C4.1
ELECTRIC CRITICAL CROSSING NOTES:
1. FOR ALL CRITICAL CROSSINGS WITH EXISTING ELECTRICAL,
CONTRACTOR SHALL FIELD VERIFY LOCATION & ELEVATION OF
EX ELECTRICAL LINE.
2. FOR CROSSING WITH WATER MAIN, BEND WATER MAIN UNDER
ELECTRICAL LINES AS NEEDED.
3. FOR ALL OTHER UTILITY CROSSINGS, CONTRACTOR SHALL
COORDINATE WITH UTILITY PROVIDER FOR ADJUSTMENT OF
ELECTRICAL LINE.
GENERAL NOTES:
1. CONTRACTOR TO PROVIDE GRADATION TESTING FOR
GRANULAR MATERIAL DELIVERED TO THE SITE GRADATION
TESTING IS TO BE CONDUCTED AND REVIEWED BY
GEOTECHNICAL FIRM PRIOR TO GRANULAR MATERIAL BEING
INSTALLED.
2. IF GRANULAR MATERIAL ARE INSTALLED THAT DO NOT MEET
THE APPROVED GEOTECHNICAL REPORT AND
SPECIFICATIONS. THE CONTRACTOR, SHALL AT THEIR OWN
EXPENSE, REMOVE AND REPLACE THE DEFICIENT
GRANULAR MATERIAL PER SPECIFICATION.
3. GENERATOR PAD IS SHOWN FOR REFERENCE ONLY AND
MAY NOT BE DRAWN TO ACTUAL SIZE. PAD SHALL CONFORM
TO ALL UTILITY COMPANY DESIGN STANDARDS AND
SPECIFICATIONS.
UTILITY NOTES:
1. ALL PROPOSED UTILTIES SHALL BE PRIVATE, UNLESS NOTED
OTHERWISE.
2. ALL WATER LINES SHALL HAVE A MINIMUM OF 5.5' OF COVER
UNLESS NOTED OTHERWISE.
3. FIRE HYDRANT ASSEMBLY SHALL INCLUDE THE TEE, BRANCH,
VALVE AND HYDRANT.
4. PIPE LENGTHS CALLED OUT ON PLANS INCLUDE FLARED END
SECTION, WHERE APPLICABLE.
5. STORM SEWER CALLED OUT AS RCP MUST BE CLASS III RCP.
6. STORM SEWER CALLED OUT AS N-12 MAY BE EITHER N-12 OR CLASS
III RCP.
7. FOR RCP PIPE, ASSOCIATED F.E.S. MUST BE RCP. FOR N-12 PIPE,
ASSOCIATED F.E.S. SHALL BE CMP.
8. NITRILE GASKETS ARE REQUIRED WHERE WATER MAIN CROSSES
UNDER STORM SEWER.
9. C900 PIPE REQUIRED FOR SANITARY SEWER WHERE WATER MAIN
CROSSES UNDER SANITARY SEWER.
10. ALL NYLOPLAST BASINS SHALL HAVE CASTINGS SECURELY
FASTENED TO THE BASIN BODY, AND ALL GRATES SHALL BE
BOLTED DOWN TO THE CASTINGS.
11. REFER TO MEP & TECHNOLOGICAL PLANS FOR ALL
ELECTRICAL/FIBER/CONDUIT/GAS ROUTING & LOCATIONS. SAID
UTILITIES HAVE BEEN SHOWN FOR COORDINATION PURPOSES
ONLY.
12. CONTRACTOR TO COORDINATE WITH UTILITY PROVIDER FOR SITE
SERVICE CONNECTIONS AND ROUTINGS TO AVOID CONFLICT WITH
THE BUILDING CONSTRUCTION.
13. CONTRACTOR TO COORDINATE WITH CITY OF CLARINDA FOR ANY
PERMITTING AND CONSTRUCTION REQUIREMENTS FOR WORK
WITHIN CITY ROW AND CONNECTION TO PUBLIC UTILITIES PRIOR TO
CONSTRUCTION.
14. CONTRACTOR SHALL ADJUST EXISTING UTILITY RIMS AND
STRUCTURES TO GRADE. CONTRACTOR TO REFER TO MEP PLANS
FOR ALL LIGHTING FIXTURE , POWER POST AND CHARGING
STATIONS TYPES AND LOCATIONS. EXTERIOR LIGHT FIXTURE,
POWER POST AND CHARGING STATIONS HAVE BEEN SHOWN FOR
COORDINATION ONLY.
15. CONTRACTOR TO COORDINATE WITH UTILITY PROVIDER FOR
ELECTRIC SERVICES.
16. CONTRACTOR TO COORDINATE WITH MEP PLAN FOR SANITARY
SEWAGE GRINDER FOR ELECTRICAL CONNECTION, PANEL AND
TECHNOLOGY SERVICE TO BUILDING.
17. CONTRACTOR TO CONNECT TO BUILDING SERVICE AND PLUMBING.
CONTRACTOR TO REFER TO MEP PLANS FOR FINAL DESIGN
BID SET
A1 A2 A4 A5E-1
AA
AB
A3
4" CONCRETE SLAB ON GRADE
W/ 6X6-W2.1XW2.1 WWR - TOP
OF SLAB EL =(0'-0")
4" CONCRETE SLAB ON GRADE
W/ 6X6-W2.1XW2.1 WWR - TOP
OF SLAB EL =(0'-0")
TYP CONC FTG - SEE
FOUNDATION PLAN NOTES
TYP CONC FTG - SEE
FOUNDATION PLAN NOTES
H
SS
6X 6X
3/
F6X
[-4 '-0
46'-2" 25'-2" 18'-6" 3'-2" 37'-0"
B5
S5.1 B5
S5.1
B5
S5.1
B5
S5.1
B5
S5.1
B5
S5.1
B5
S5.1
B2
S5.1
TYP
TYP CONC FTG - SEE
FOUNDATION PLAN NOTES
TYP CONC FTG - SEE
FOUNDATION PLAN NOTES
E5
S5.1
D3
S5.1
/4
/4
/4
/8
11' - 6"
B1
S5.1
TYP
.0
10" PRECAST INSUL
WALL PANEL PER
PRECAST SUPPLIER,
TYP
10" PRECAST INSUL
WALL PANEL PER
PRECAST SUPPLIER,
TYP
10" PRECAST INSUL
WALL PANEL PER
PRECAST SUPPLIER,
TYP
A4
S5.2
BOT OF EXSTG FTG EL = ( -3'-6" ) - VIF
BOT OF EXSTG FTG EL = ( -3'-6" ) - VIF
FTG STEP
FTG STEP
BOT OF NEW FTG TO ALIGN
W/ BOT OF EXSTG FTG
BOT OF NEW FTG TO ALIGN
W/ BOT OF EXSTG FTG
A2
S5.5
EXSTG 3'-0"X3'-0" (WIDTH X DEPTH)
CONC FTG - VIF 4
D3
S5.1
4'-0"
2'-5"
DEMO EXSTG
ENTRY SLAB &
FTGS
-4'-0"
-4'-0"
-4'-0"
-4'-0"
-3'-0"
22' - 2 1/4" 29' - 0"
-3'-0"
-0'-6" -VIF
-0'-6" -VIF
A2
S5.5
SIM
5'-0"
BOT OF EXSTG FTG EL = ( -3'-6" ) - VIF
6'-6"
A3
S5.25
H
SS
6X 6X
1/
F6X
[-4 '-0
B1
S5.2
REMOVE & REPLACE
EXISTING ENTRY SLAB -
PROTECT EXISTING
FOOTING OR REPLACE
EXISTING FOOTING IF
DAMAGED
V
IF
B3
S5.2
V
IF
4' -0
B3
S5.1
B3
S5.1
TRENCH DRAIN -
SEE MEP DWGS
TRENCH DRAIN -
SEE MEP DWGS
D1
S5.1
D1
S5.1
FOUNDATION PLAN NOTES:
• CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION
• INDICATES TOP OF FOOTING ELEVATION AT CONTINUOUS FOOTINGS.
• [ _'-_" ] INDICATES TOP OF FOOTING ELEVATION AT ISOLATED FOOTINGS.
• FOR TYPICAL CONCRETE SLAB JOINTS SEE
• FOR TYPICAL CONCRETE CAP SEE
• FOR TYPICAL WALL CORNER & INTERSECTION SEE
• FOR TYPICAL STEPPED FOOTING SEE
• FOR TYPICAL OPENINGS IN CONCRETE WALL SEE
• STRUCTURAL CMU WALLS ARE SHOWN PER THESE PLANS. FOR NON LOAD BRG CMU WALLS (SHOWN IN HALFTONE), SEE
ARCH DWGS. ALL NON LOAD BRG CMU WALLS SHALL HAVE THICKENED SLABS, SEE
• ALL CONTINUOUS FOOTINGS SHALL BE 2'-6"X1'-0" (WIDTH X DEPTH) W/ 3-#5 CONT BOT & #5 @18" OC TRANS BOT UNO ON PLAN.
• FOR TYPICAL BELOW SLAB SUBGRADE PREP SEE
• IF UNSUITABLE BEARING SOILS ARE ENCOUNTERED AT THE BASE OF THE PLANNED FOOTING EXCAVATION, THEN THE
FOOTING EXCAVATIONS SHALL BE OVER-EXCAVATED AND FILLED BELOW THE FOOTING - SEE AND GEOTECHNICAL REPORT - SOIL BEARING SURFACE AND OVER-EXCAVATION AND FILL WORK SHALL BE TESTED BY A QUALIFIED INDEPENDENT
SOILS TESTING FIRM
• FOR FOUNDATION PLAN AT GENERATOR SEE
• INDICATES 4" DEPRESSED SLAB FOR FLOOR TROUGH - SEE . SEE FOOD SERVICE DWGS FOR LOC.
• INDIATES 2 1/2" DEPRESSED SLAB - SEE . SEE FOOD SERVICE DWGS FOR LOC.
• FOR STAIR FRAMING INFORMATION SEE
A1/ S5.1
A2/ S5.1 A3/ S5.1
A5/ S5.1
B1/ S5.1
A6/ S5.1
C1/ S5.1
E1/ S5.1
2/ S1.1 C5/ S5.1
E2/ S5.1
1/ S2.1
D5
S5.1
TYP
6" CONC FROST PAD
W/ #5 @ 10" OC EA
WAY - COORD SIZE &
LOC W/ MEP & CIVIL
2'-0"X1'-0" (WIDTH X
DEPTH) CONC FTG W/
2-#5 CONT BOT & #5
@18" OC TRANS BOT -
TYP 4 SIDES OF
FROST PAD
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:1 :4
A
M S1.1
FOUNDATION PLAN -
AREA 'A'
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
BID SET
1/8" = 1'-0"
FOUNDATION PLAN - AREA 'A'
ISOLATED FOOTING SCHEDULE
MARK SIZE REINFORCING
F6X1 6'-0"X6'-0"X1'-0" 6-#5 BOT EA WAY
F9X1.5 9'-0"X9'-0"X1'-6" 12-#5 BOT EA WAY
1/8" = 1'-0"
FOUNDATION PLAN - GENERATOR FROST PAD
1 12/22/2022 ADDENDUM 1.0
"T
"T
S L A
B T
H
IC
K N
E S
S x
S L A
B T
H
IC
K N
E S
S
WWR 2x4 KEY CONT
CONC SLAB - SEE PLAN
1'-0"
WWR
CONC SLAB - SEE PLAN
SAW-CUT JOINT
CONSTRUCTION JOINT
SAW-CUT JOINT
• CONCRETE SLAB JOINTS SHALL BE EITHER CONSTRUCTION OR SAW-CUT JOINTS
• LOCATE CONSTRUCTION JOINTS ON COLUMN CENTERLINE
• LOCATE SAW-CUT JOINTS BETWEEN CONSTRUCTION JOINTS
• LOCATE SLAB JOINTS AT PARTITIONS WHERE POSSIBLE
• MAXIMUM SPACING OF SLAB JOINTS SHALL NOT EXCEED 10'-0" IN ANY DIRECTION
CONC SLAB ON
GRADE - SEE PLAN
SAW-CUT JOINT OR
CONSTRUCTION
JOINT - SEE TYP
DTL
STL COL - SEE PLAN
1/2" EXP JT MAT
AROUND COL
FINISH SAW-CUT-
TO-EXP JT W/ A
SMALL DIAMETER
SAW BLADE - TYP
STL BASE PL
(BELOW SLAB ON
GRADE) - SEE DTLS
SAW-CUT JOINT OR
CONSTRUCTION
JOINT - SEE TYP
DTL
2-#4 EA SIDE - PROVIDE 1"
COVER FROM TOP OF SLAB
& STOP EA BAR 2" CLEAR
OF JOINT @ EA END
2x4 KEY IF CON-
STRUCTION JOINT
IS DESIRED
PROVIDE CORNER REINF
SAME SIZE AND SPACING
AS HORIZ REINF-
ALTERNATE DIRECTION OF
LEG
PROVIDE CORNER REINF
SAME SIZE AND SPACING
AS HORIZ REINFORCING
WALL INTERSECTION WALL CORNER
2' - 0" 2' - 0"
2x4 KEY IF
CONSTRUCTION
JOINT IS
DESIRED
PROVIDE
CORNER REINF
SAME SIZE &
SPACING AS
HORIZ REINF
WALL INTERSECTION WALL CORNER
2' - 0" 2' - 0"
1/4
1 1/2" GROUT
SEE TYP DTL FOR SLAB
ON GRADE JOINTS @ COL
CONC FTG-SEE PLAN
FOR SIZE & REINF
CL OF COL, BASE PL & FTG
STL COL-SEE PLAN
BASE PL W/ 4-3/4"⌀X9" EMBED HD
ANCHORS
-1" THICK BASE PL @ HSS8X8
-3/4" THICK BASE PL @ HSS6X6
EL-SEE PLAN
EL-SEE PLAN
EQ EQ
1 1/2" - TYP
1 1/2" - TYP
BITUMINOUS PAINT
COL BELOW SLAB
WALL REINF
FTG REINF
CONTRACTOR'S
OPTION- SLOPE
F O
U N
D A
T
IO
N W
A L L
MIN (3'-0" MINIMUM)
1'-0" 4'-0" NOMINAL
3'-0" LAP
F O
O T
IN
G
M A
X
EL-SEE PLAN
1' - 0"
CMU WALL -
SEE S0.1
CONC SLAB-SEE PLAN
DRILL & EPOXY WALL REINF
5" MIN INTO SLAB
2-#5 CONT
PANEL PANEL
SECTION A-A
A
A
EL-SEE PLAN
CONC SLAB ON
GRADE - SEE PLAN
1/2' EXP JT MAT
PRECAST INSUL WALL
PANEL PER PRECAST
SUPPLIER
1" GROUT
SHIMS BY PRECAST
SUPPLIER
CONC FTG - SEE
PLAN FOR SIZE &
REINF
EL-SEE PLAN
CONN BY PRECAST
SUPPLIER
GRID
RIGID INSUL - SEE
ARCH DWGS
EL = (-1'-0")
1' - 0" EQ
EQEQ
CONC WALL W/ #4 @ 16"
OC EA WAY EA FACE
CONC SLAB ON
GRADE - SEE PLAN
MIN 4" CRUSHED
AGGREGATE
MIN 1'-8" COMPACTED
FILL PER THE
GEOTECHNICAL
REPORT
EXPOSED SUBGRADE COMPACTED PER THE
GEOTECHNICAL REPORT AND EVALUATED
BY THE PROJECT GEOTECHNICAL
ENGINEER - NOTE THAT ADDITIONAL FILL
MAY BE REQD AS A BUFFER ZONE TO
MITIGATE EXPASNIVE SOILS - SEE
GEOTECHNICAL REPORT
• REFERENCE THE GEOTECHNICAL REPORT
FOR PLACEMENT AND COMPACTION
REQUIREMENTS
• NOTE EXISTING SOIL MAY BE SUSCEPTIBLE TO
DISTURBANCE FROM CONSTRUCTION
TRAFFIC- REFERENCE THE GEOTECHNICAL
REPORT FOR STABILIZATION OPTIONS
EXISTG CONC
SLAB ON GRADE
EXISTG
PRECAST WALL
CONC SLAB ON
GRADE - SEE PLAN
1/2" EXP JT MAT
S E
E P
L A
N
V
IF
SEE PLAN - VIF
C O
V E
R
C
O V
E R
PRECAST INSUL WALL PANEL
PER PRECAST SUPPLIER
1" GROUT
SHIMS BY PRECAST
SUPPLIER
CONC FTG - MATCH
EXSTG FTG DEPTH
EL-SEE PLAN
EL-SEE PLAN
VIF
SEE PLAN
#5 @ 18" OC BOT BARS -
DRILL & EPOXY 4" INTO
EXSTG FTG
#5 @ 18" OC BOT BARS -
DRILL & EPOXY 4" INTO
EXSTG FTG
6-#5 TOP & BOT CONT
EMBED PL SHALL NOT EXTEND ABOVE SLAB SURFACE
CONN BY PRECAST SUPPLIER
• EXCAVATION ARE SHOWN VERTICAL: HOWEVER, THE SIDEWALLS SHOULD BE SLOPED
AS NECCESSARY FOR SAFETY
• BASE BID SHALL NOT INCLUDE OVER-EXCAVATION. ABOVE DETAIL IS ONLY APPLIED IF
SOFT SPOTS ARE DISCOVERED DURING EXCAVATION.
EL- SEE PLAN
D
2/3 D2/3 D
FDN WALL- SEE PLAN
CONC FTG- SEE PLAN
EXTEND OVER-EXCAVATION
WIDTH AT GRANULAR
STRUCTURAL FILL
CONTRACTOR OPTION:
LEAN CONC FILL TO MATCH
FTG WIDTH
D= OVER-EXCAVATION TO
REMOVE EXISTG &
POSSIBLE FILL
MATERIALS BELOW FDN
OVER-EXCAVATION
SHALL EXTEND BELOW
BOT OF FDN W/ MIN
DEPTH AS REQD TO
ACHIEVE REQD BEARING
CAPACITY
EL-SEE PLAN
EL-SEE PLAN
CONC SLAB ON
GRADE- SEE PLAN
CMU WALL- SEE PLAN
CONC FTG- SEE PLAN
FOR SIZE & REINF
GROUT ALL CELLS AND
VOIDS SOLID BELOW
GRADE
1/2" EXP JT MAT
S P
L
IC
E P
E R
S
.1
DOWELS W/ STD HOOK INTO
FTG - MATCH CMU WALL
REINF BAR SIZE & SPACING
EL-SEE PLAN
EL = (-0'-10")
FREEZER WALLS PER
MFR - SEE ARCH DWGS
FOR LOC
RIGID INSUL - SEE
ARCH DWGS
5" CONC SLAB W/ 6X6-
W2.1XW2.1 WWR
1/2" GROUT
MIN
10"
CONC SLAB ON
GRADE - SEE PLAN
DRAIN - SEE PLUMBING
@ KITCHEN DWG
4" MIN
EXTEND THICKEEND
SLAB & BASE SLAB
AROUND PLUMBING
T Y
P
TYP
2' - 0"
#5X4'-0" DIAGONAL
REINF EA FACE-TYPICAL
1'-6" OPENING OR
GREATER
ADDED REINF @ OPNGS
SHALL BE EQUAL TO REINF
DISPLACED-DIVIDED
EQUALLY BETWEEN EACH
SIDE
• ALL DESIRED OPENINGS SHALL BE SUBMITTED TO EOR
FOR REVIEW PRIOR TO CONSTRUCTION
EQ 1'-0" EQ
CONC FTG-SEE PLAN
FOR SIZE & REINF
M
IN
IM
U
M
CONC WALL W/ #4 @ 16"
OC EA WAY EA FACE
VOID FORM
FROST PAD - SEE PLAN
GRADE EL-
FIELD VERIFY
#4 @ 12" OC THUS:
24"
24"
1/4
3 SIDES
1 1/2" GROUT
EXSTG FTG
CL OF COL, BASE PL & FTG
STL COL-SEE PLAN
1" BASE PL W/ 4-3/4"⌀
THREADED RODS - DRILL
& EPOXY 6" EMBED INTO
EXSTG FTG - SEE BASE PL
DIAGRAM ABOVE
EL-SEE PLAN
EL-SEE PLAN
VIF
BITUMINOUS PAINT
COL BELOW SLAB
S5.1
E5
S5.1
E5
SIM
SEE TYP DTL FOR
SLAB ON GRADE
JOINTS @ COL
EXISTG
PRECAST WALL
1 1/2" 5" 1 1/2"
/2
/2
/2
/2
/2
EXSTG PRECAST FACE
OF COL/BASE PL
1/4
DRILL & EPOXY #4X1'-0"
DOWELS @ 18" OC W/ 4"
EMBED INTO EXISTG
CONC SLAB ON GRADE
EXISTG CONC
SLAB ON GRADE CONC SLAB ON
GRADE - SEE PLAN
EL-SEE PLAN
GRATE - SEE FOOD
SERVICE DWGS
3-#4 CONT EA SIDE
M
IN4
M
IN4
GROUT - SEE FOOD
SERVICE DWGS
• SEE FOOD SERVICE DWGS FOR ALL INFORMATION NOT SHOWN ABOVE
SEE FOOD SERVICE DWGS
CONC SLAB ON
GRADE - SEE PLAN
/2
C V
R
#4 BENT REINF @ 12" OC-
VERIFY BEND LENGTH W/
SUPPLIER
/2
C V
R
2'-0" TYP
STEP HEIGHT ≤ 4"
CONC SLAB ON
GRADE - SEE PLAN
S E
E P
L A
N
#4 CONT
_8" CONTRACTOR OPTION:
CONSTRUCTION JOINT
BEND SLAB REINF
AS REQD
6" 6"
2' - 0"
CONC SLAB ON
GRADE -SEE PLAN
OPTIONAL CONSTRUCTION
JOINT - SEE TYP DETAIL
PREMANUFACTURED
CAST-IN-PLACE
TRENCH DRAIN
FORMING SYSTEM -
SEE MEP DWGS
4-#4 CONT
#4 BENT REINF @ 12"
OC - VERIFY BEND
LENGTH W/ SUPPLIER
EL-SEE CIVIL
DWGS
CONC FTG - SEE
PLAN FOR SIZE &
REINF
EL-SEE PLAN
EQ
CONC WALL W/ #4 @ 16"
OC EA WAY EA FACE
EQ
PAVEMENT - SEE
CIVIL DWGS
SEE PLAN
STL COL - SEE PLAN
1 1/2" GROUT
1 1/2" TYP
1 1/2" TYP
3/4" BASE PL W/ 4-3/4" F1554
THREADED RODS - DRILL & EPOXY
6" EMBED INTO CONC WALL
1/4
EL-SEE PLAN
CONC SLAB ON
GRADE - SEE PLAN
#5 CONT @ 12" OC
WASHER - SEE ARCH
DWGS
#5 TRANS @ 12" OC
.1'-0" MIN EA EA SIDE
OF WASHER
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:1 :4
A
M S5.1
STRUCTURAL
DETAILS
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
BID SET
3/4" = 1'-0" A1
TYP CONC SLAB JOINTS
3/4" = 1'-0"
A2
TYP SLAB ON GRADE JOINTS @ COL
1/2" = 1'-0" A3
TYP CONC WALL PLANS
1/2" = 1'-0" B2
TYP STL COL @ NEW FTG
1/2" = 1'-0" A5
TYP STEPPED FTG
3/4" = 1'-0" B1
TYP THICKENED SLAB @ PARTITION CMU
3/4" = 1'-0"
B5
PRECAST WALL @ FTG
3/4" = 1'-0" A6
TYP SUBGRADE PREP
1" = 1'-0" D3
NEW SLAB @ EXSTG WALL
3/4" = 1'-0" C1
TYP FTG OVER-EXCAVATION
3/4" = 1'-0" B6
CMU @ FTG
1" = 1'-0" C3
INSULATED SLAB
1/2" = 1'-0" E1
TYP OPENING THROUGH CONC WALL
3/4" = 1'-0" D5
FTG @ FROST PAD
1/2" = 1'-0" E6
STL COL @ EXSTG FTG
1" = 1'-0"
E5
NEW SLAB @ EXSTG SLAB
1" = 1'-0" C5
FLOOR TROUGH DTL
3/4" = 1'-0" E2
TYP SLAB ON GRADE STEP
1" = 1'-0" B3
TYP TRENCH DRAIN
1 12/22/2022 ADDENDUM 1.0
3/4" = 1'-0" E3
STAIR COL @ WALL
1" = 1'-0" D1
THICKENED SLAB BELOW WASHERS
S1
PD
PE
P5
P4 P3
AB
AC
AD
AE
AF
AG
AH
A1 A2 A4 A5A3
MECH
M3.0
EF-2
EF-3
EF-9
EF-5
EF-6
EF-7
EF-8
INSTALL CONDENSING UNIT PER
CONDENSING UNIT SUPPORT
DETAIL 1/M4.2 (TYP.).
4"⌀ DRYER VENT DN.
REFER TO 5/M4.1 FOR
DRYER VENT DETAIL.
EF-4
CU-2
CU-1A
CU-1B
REFER TO 2/M4.2 FOR
KITCHEN GREASE EXHAUST
FAN DETAIL (TYP.)
LIQ (TYP.2)
SUC (TYP.2)
LIQ (TYP.2)
SUC (TYP.2)
LIQ (TYP.2)
SUC (TYP.2)
AREA 'A'
AREA 'B'
MECH
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4 :1
P
M M1.4
LEVEL 02 PLAN -
AREA B -
MECHANICAL
MIKMCC
DAVING
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
N O R
HT
1/8" = 1'-0"
LEVEL 02 PLAN - AREA B - MECHANICAL
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
KEYNOTES:
1. LOCATE FAN 10FT MINIMUM FROM ROOF EDGE
SO RAILING IS NOT REQUIRED.
1 12/22/2022 ADDEDNUM 1.0
S1
P5
AE
AF
A2 A4A3
MECH
OAL-1
98x28 RA REFER TO 3/M4.1 FOR
LOUVER INSTALLATION
DETAIL (TYP.)
OAL-2
AHU-1 DDC CONTROL
PANEL
DOAS-1 DDC
CONTROL PANEL
40x16 RAAHU-1
DOAS-1
M3.0
M3.0
LOCATE GLOBAL REFERENCE
POINTS FOR FMCS ON NORTH
FACE OF PENTHOUSE
60x28 SA
98x28 OA
30x30 OA
72x72 OA
UH-2
48x24 RA
RAL-1
72x48 EA
168x72 OA
UH-2
LIQ (TYP.2)
SUC (TYP.2)
LIQ (TYP.2)
SUC (TYP.2)
LIQ (TYP.2)
SUC (TYP.2)
x O
A
GV-1
40"X20" OA DUCT DN
TO OPEN AT 1' AFF.
MECH
44x20 SA1
72x30 EA
LEVEL 02
16'-6"
A2
ROOF
31'-2"
28x60 SA
28x98 RA
DOAS-1
28x98 OA
OAL-1
72x168 OA
24x48 RA
REFER TO 1/M4.3 FOR
DOAS-1 DETAIL.
3'-0"
10⌀ FLUE
(TYP.2)
A2 A4E-1A3
A2
A3 A4
A2
A3 A4
LEVEL 02
16'-6"
A2
ROOF
31'-2"
RAL-1
16x40 RA x R
A
AHU-1
REFER TO 2/M4.3 FOR
AHU-1 DETAIL.
ALLOW FOR 3'-0"
CLEARANCE TO ACCESS
OPPOSITE SIDE OF AHU.
12x86 SA
20x44 SA
6⌀ FLUE
86x12 RA
CONNECTION
86x18 EA
CONNECTION
86x18 OA
CONNECTION
A2 A3
A2
A3
A2
A3
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4 :1
P
M M3.0
ENLARGED PLAN -
MECHANICAL
MIKMCC
DAVING
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
N O R
HT
1/4" = 1'-0"
LEVEL 02 PLAN - AREA B - MECHANICAL ENLARGED PLAN
1/4" = 1'-0"
SECTION - DOAS-1
1/4" = 1'-0"
SECTION - AHU-1
KEYNOTES:
1. MAINTAIN A 36"X80" MINIMUM CLEAR PATHWAY
BETWEEN LOUVER AND VERTICAL DUCT AT
DOAS-1.
2. INSTALL AHU-1 AND DOAS-1 ON A 4"
HOUSEKEEPING PAD.
3. ROUTE REFRIGERANT PIPING FROM AIR
HANDLING UNIT/DOAS TO CONDENSING UNIT
PER MANUFACTURER RECOMMENDATIONS.
4. INSTALL OUTSIDE AIR FLOW MEASURING
STATION IN STRAIGHT SECTION OF DUCTWORK.
5. CONTRACTOR TO FIT ALL EQUIPMENT AND
SHIPPING SPLITS THROUGH EITHER THE MAIN
MECHANICAL ROOM DOORS OR OAL-1
OPENING. FOR THE LOUVER OPENING SIZE,
REFER TO THE ARCHITECTURAL PLANS.
6. MAINTAIN 36"X80" MINIMUM CLEAR PATHWAY
BETWEEN RETURN DUCT AND FLOOR.
7. GV-1 TO BE LOCATED ON ROOF OF
MECHANICAL PENTHOUSE. REFER TO 3/M4.2
FOR ROOF SUPPORT - FAN/HOOD CURB DETAIL.
8. 6"⌀ FLUE VENT UP THRU ROOF TO
MANUFACTURER'S VENT KIT. REFER TO 4/M4.1
FOR GAS VENT THRU ROOF DETAIL.
9. 10"⌀ FLUE VENT UP THRU ROOF TO
MANUFACTURER'S VENT KIT. REFER TO 4/M4.1
FOR GAS VENT THRU ROOF DETAIL. (TYP.2)
1 12/22/2022 ADDEDNUM 1.0
262 45 8
TOP VIEW
PROFILE VIEW
98x26 RETURN AIR
DAMPER AND OPENING
98x26 OUTSIDE AIR
DAMPER AND OPENING
98x26 RETURN AIR
DAMPER AND OPENING
98x26 OUTSIDE AIR
DAMPER AND OPENING
8 2 4
3 10
12 6 5 8
18 18
108x24 SUPPLY AIR
OPENING
108x24 SUPPLY AIR
OPENING
VFD
VFD
TOP VIEW
PROFILE VIEW
SPLIT SPLIT
SPLIT
SPLIT
SPLIT
SPLIT SPLIT
6 19 20
21 22 19 8
86x18 OUTDOOR AIR
DAMPER AND OPENING
86x18 OUTDOOR AIR
DAMPER AND OPENING
86x18 EXHAUST AIR
DAMPER AND OPENING
86x18 EXHAUST AIR
DAMPER AND OPENING
86x12 RETURN AIR OPENING
86x12 RETURN AIR OPENING
86x12 SUPPLY AIR OPENING
86x12 SUPPLY AIR OPENING
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4 :1
P
M M4.3
MECHANICAL
DETAILS
MIKMCC
DAVING
0211435.00
CLARINDA
CORRECTIONAL
FACILITY - KITCHEN &
LAUNDRY ADDITION
STATE OF IOWA - DEPARTMENT
OF CORRECTIONS
2000 N 16TH ST, CLARINDA, IA
51632
11/18/2022
MIKMCC
BID SET
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2022 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #21007688.00
NO SCALE
DOAS-1 DETAIL
1 NO SCALE
AHU-1 DETAIL
KEYNOTES:
1. 8" BASERAIL.
2. DX COOLING COIL.
3. INDIRECT FIRED NATURAL GAS HEATING COIL.
4. CENTRIFUGAL PLENUM SUPPLY FAN.
5. ACCESS DOOR, MINIMUM WIDTH OF 12".
6. ACCESS DOOR, MINIMUM WIDTH OF 16".
7. ACCESS DOOR, MINIMUM WIDTH OF 24".
8. ACCESS DOOR, MINIMUM WIDTH OF 30" OR LARGER IF REQUIRED FOR FAN
ACCESS AND MOTOR REMOVAL.
9. MIXING BOX WITH ANGLED FILTER SECTION, MERV 8 FILTERS.
10. DISCHARGE PLENUM.
11. DAMPERS OVER THE SINGLE STAGE HEATING COIL SECTIONS (QUANTITY: 3).
NO COIL OVER MODULATING COIL.
12. ACCESS DOOR, MINIMUM WIDTH OF 28" OR LARGER IF REQUIRED FOR FILTER
REMOVAL.
13. VERTICAL ECONOMIZER SECTION.
14. CENTRIFUGAL PLENUM RETURN FAN.
15. MERV 8 FILTER RACK.
16. 6"⌀ STAINLESS STEEL FLUE.
17. 10"⌀ STAINLESS STEEL FLUE.
18. MODULE TO CONTAIN LED MARINE LIGHTS.
19. ACCESS DOOR, MINIMUM WIDTH OF 14".
20. ACCESS DOOR, MINIMUM WIDTH OF 28" OR LARGER IF REQUIRED FOR FAN
ACCESS AND MOTOR REMOVAL.
21. ACCESS DOOR, MINIMUM WIDTH OF 18" OR LARGER IF REQUIRED FOR FILTER
REMOVAL.
22. ACCESS DOOR, MINIMUM WIDTH OF 10".
23. ACCESS DOOR, MINIMUM WIDTH OF 20".
1 12/22/2022 ADDEDNUM 1.0