Rebid SPD127-SPDAD-6486 Addendum 2.pdf
PDF 7 MB Posted
- Attached to
- Wildland Firefighting Helitanker Station_REBID
- Solicitation number
- SPD127-SPDAD-6486
- Issued by
- San Bernardino County, California
About this file
This Addendum No. 2 to the Wildland Firefighting Helitanker Station rebid project is issued by the San Bernardino County Department of Public Works Special Districts for Project No. 1378.0185, effective September 1, 2026. The addendum amends bidding requirements, contract documents, general conditions, special conditions, and technical specifications for the construction of a helitanker refueling station at Glen Helen Regional Park. Key amendments include revised tank capacity requirements from 3,000–5,000 gallons to 3,000–8,000 gallons, correction of the hot-tap specification from 12-inch AC pipe to 10-inch Class 150 PVC pipe, and provision of pump test data from the San Bernardino CSA 70 Glen Helen Water System. The document includes comprehensive hydraulic test reports dated June 26, 2026, for Wells #1A, #3, #4, #5, and #6, with reference reports from July 11, 2025, for Wells #3 and #5, detailing pump discharge pressures, flow rates in gallons per minute, total pumping heads, and overall plant efficiency percentages. Additionally, the addendum provides clarification through a questions-and-answers section addressing contractor concerns regarding bond requirements, water supply specifications, hot-tap sizing, SCADA system design, pipeline sizing for dip-site operations, and control valve configurations. All contractors are required to submit a new bid bond, provide dated and signed acknowledgment of the addendum with their sealed bid proposals, and comply with County Standard Plans and Specifications for all hot-tap work.
The addendum specifies that contractors must account for all provisions in submitting bids and that SCADA-related technical queries will be addressed post-award during the construction phase. The document clarifies that while a proposed size-on-size hot tap has not been approved under AWWA C223 standards, a properly restrained cut-in tee connection shall be used instead, with shop drawings required for Special Districts review and approval prior to fabrication. The contractor is responsible for determining appropriate pipeline sizing for the dip site, accounting for 700 feet of line loss and 6.5 feet of lift at the tank's air gap, utilizing the provided hydraulic test reports. Well #3 demonstrated the highest flow capacity at 940 GPM under normal operation with 60 HP motor input, while Well #5 produced 356 GPM with 15 HP motor input, and the pump test data indicates efficiency improvements could reduce annual operational costs significantly across all wells. Updated location maps and infrastructure documentation for the Glen Helen Domestic Water System are included as exhibits to support contractor design and planning efforts.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Wildland Firefighting Helitanker Station Addendum No. 2 Page 1 of 5
SAN BERNARDINO COUNTY
DEPARTMENT OF PUBLIC WORKS
SPECIAL DISTRICTS
ADDENDUM NO. 2
TO THE BIDDING REQUIREMENTS, CONTRACT DOCUMENTS, GENERAL CONDITIONS,
SPECIAL CONDITIONS, AND TECHNICAL SPECIFICATIONS FOR THE
Wildland Firefighting Helitanker Station Rebid
PROJECT NO.: 1378.0185
September 01, 2026
The Contract Bid Documents for the above-referenced project are hereby amended in the following manner and the following manner only:
I. All provisions of Addendum No. 2 are hereby incorporated into the Contract Documents, and Bidders shall account for all provisions pursuant to Addendum No. 2 in submitting their bid proposals. Each Bidder shall include a dated and signed copy of this Addendum with their sealed bid proposal.
1. Item No. 1: Questions and Answers
1. The contractor seeks clarification on whether they may use the bond previously submitted for the prior bid, or must provide a new, complete set of bonds for this rebid.
Response:
The Contractors are mandated to submit a new bid bond when a public works project is rebid, as the prior bids have been rejected and the original solicitation has been canceled. It is imperative that the new bid bond be executed with the appropriate signatures and seals, as failure to do so may result in the bid being rejected as non-responsive.
2. Proposed New 10-inch hot-tap:
To properly design and price the system, please provide the following information at the proposed 10-inch hot-tap location:
a. Available flow in GPM.
b. Static pressure.
c. Residual/dynamic pressure while flowing 800 GPM.
d. If this line is pump-fed, the applicable pump operating information or pump curve showing the available flow and pressure.
Wildland Firefighting Helitanker Station Addendum No. 2 Page 2 of 5
Response:
Please refer to Exhibit A for the attached Pump Check - Hydraulic Test Reports for the San Bernardino CSA 70 Glen Helen Water System. The reports are dated June 26, 2026, and pertain to Wells #1A, #3, #4, # 5, and #6. Additionally, there are reports dated July 11, 2025, for Well #3 and Well #5, for reference.
3. We need the actual GPM and Pressure from the 10” Pump that will be supplying the 10” water supply line now that the 3rd RFQ changed the supply.
Response:
Please refer to Exhibit A for the attached Pump Check - Hydraulic Test Reports for the San Bernardino CSA 70 Glen Helen Water System. The reports are dated June 26, 2026, and pertain to Wells #1A, #3, #4, # 5, and #6. Additionally, there are reports dated July 11, 2025, for Well #3 and Well #5, for reference.
a. Will the hot-tapped 6” line produce, with all the fittings, the 800 GPM needed at the Dip Tank?
Response:
Yes, the hot-tapped 6” line must produce, with all the fittings, the 800 GPM needed at the Dip Tank.
b. Determine what sized line will be needed at the Dip Site to accommodate the 700’ line loss plus 6.5’ lift at the Tank's air gap.
Response:
The awarded contractor for this project shall be responsible for determining the appropriate pipeline size for the Dip Site, utilizing the Hydraulic Test Reports included in this addendum.
This determination must account for a 700-foot line loss, a 6.5-foot lift at the Tank's air gap, and any unforeseen requirement in the project site.
c. Once that is determined, what PSI and GPM are determined at the Dip Tank, we will need to discuss what SCADA Valve.
Response:
The contractor is responsible for determining the PSI and GPM at the Dip Tank after selecting the appropriate pipeline size for the dip site, in accordance with the guidance for item b.
d. This may change to the standard configuration of a single 4” Cla Val and Float to two maybe
(2) Cla Val valves/floats or a Low Flow Solution.
Response:
Please refer to Exhibit A for the Hydraulic Test Reports included in this addendum for detailed information.
Wildland Firefighting Helitanker Station Addendum No. 2 Page 3 of 5
4. Could you please provide some additional information on how the well pump works, specifically regarding pressure and flow management?
Response:
Please refer to Exhibit A for the attached Pump Check - Hydraulic Test Reports for the San Bernardino CSA 70 Glen Helen Water System, dated June 26, 2026, for Wells #1A, #3, #4, #5, and #6. For reference, there are also reports from July 11, 2025, for Wells #3 and #5.
5. Is this pump for irrigation or tank refill?
Response:
These pumps are designed for domestic water use and can supply multiple tank reservoirs.
6. Is the Pump control – On/Off/Variable?
Response:
This pump control utilizes either a manual or a level-type mechanism, which will be verified in the field.
7. Will there be a valve to divert water to the Helicopter site to control pressure and volume?
Response:
There is currently no valve available to divert water to the helicopter site; therefore, it is advisable to utilize a hot tap for this purpose.
8. Does the county have any restrictions on Hot Taps 10 x 10?
Response:
The proposed size-on-size hot tap has not been approved. AWWA C223 establishes minimum requirements for tapping sleeves but does not constitute approval of a size-on-size application.
Considering the extent of the existing main that was removed, along with the associated structural and operational risks, the connection shall be completed using a properly restrained cut-in tee. The contractor awarded for this project must submit shop drawings to the Special Districts for review and approval prior to commencing any fabrication work.
9. Pure County SCADA without interfacing with proprietary remote activation. Co. has SCADA at Pump House, so no integration or encryption issues:
a. What NEMA Demarcation Panel would you recommend placing inside the cabinet to house the County SCADA components?
b. Should we use Fiber or CAT6C for the data backhaul into the cabinet? Then the County plans to connect four (4) Features already installed on HeloPod, which will require wiring into the cabinet.
Wildland Firefighting Helitanker Station Addendum No. 2 Page 4 of 5
c. What components will be required inside the panel to connect to the backhaul cable?
Then connected to control the four (4) Features.
d. Will the Panel need to operate on12 or 24 Volts? This will affect the number of 12V batteries & panels required.
e. How will you control the SCADA 6-inch and 8-inch external Cla Val Fill Valve located just before the Tank? Should this be done at the Pump House before the power conduit runs to the dip site?
Additionally, could you provide information on the following components?
• RTU / PLC
• DC-DC Converter
• DC-AC Inverter
• DC-to-PoE Injector
• (12V or 24V DC) (Stabilized DC) (48V-56V DC)
• Field Sensors
• Actuators / Relays
• Radio / Router
• IP Camera / Radio
Response:
These queries will be addressed following the contract award to the approved contractor and will be clarified during the project's construction phase.
2. Item 2 of Itemized Re-Bid Proposal of Section A – Re-Bid Requirements.
Contractors are hereby informed of an amendment to Section A – Re-Bid Requirements, specifically pertaining to item 2 of the Itemized Re-Bid Proposal, PP 27 of 41. The capacity requirement has been revised; the new requirement mandates that the tank accommodates 3,000 to 8,000 gallons, superseding the previous requirement of 3,000 to 5,000 gallons. All other components of the Base Bid remain unchanged.
3. Item 1.2.1 of Section F – Technical Specifications.
Contractors are hereby informed of an amendment to Section F – Technical Specifications, specifically to item 1.2.1 concerning the capacity of the cistern, on PP 2 of 4. The capacity requirement has been revised to require the tank to accommodate between 3,000 and 8,000 gallons, replacing the former requirement of 3,000 to 5,000 gallons. All other specifications remain unchanged.
Wildland Firefighting Helitanker Station Addendum No. 2 Page 5 of 5
4. Item 1.3.1 of Section F – Technical Specifications.
Contractors are hereby advised of an amendment to item 1.3.1 in Section F – Technical Specifications, specifically concerning the pipeline size, referenced on page 3 of 4. The revised statement should read “Hot Tap 10” Class 150 PVC pipe instead of “Hot Tap 12’ Class 150 AC pipe.” Furthermore, all Hot Tap requirements must comply with the County Standard Plans and Specifications.
5. Location Map of Section G – Contract Drawings
Contractors are hereby notified of the amendment to Section G – Contract Drawings, which now includes an updated Location Map, as presented in Exhibit B. Furthermore, for reference, the Glen Helen Domestic Water System Infrastructure Map is included in Exhibit C as part of this addendum.
ISSUE DATE: 09/01/2026 Date Acknowledged by Bidder: ____________
By: ______________________________ By: ____________________________ Russel Viloria, Project Manager Bidder's Company Name Department of Public Works - Special Districts Project Management Division _____________________________
Bidders Signature j9367 Text Box
EXHIBIT A - PUMP CHECK
PUMPING SYSTEMS ANALYSIS
HYDRAULIC TEST REPORTS
1. Reports dated June 26, 2026 for Wells #1A, #3, #4, #5, and #6.
2. Reports dated July 11, 2025 for Wells # 3, and #5.
San Bernardino CSA 70 Glen Helen Test Date: 06/26/2026 Glen Helen Regional Park Pump type: DWT
Plant: Well #1A
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: No Data SERIAL: N/A
MOTOR: US SERIAL: G07-BF54A-MA18
H.P. 50 LAT/LON: 34.12.477n117.24.469w
METER: 256000-145138 REF #: PC 2541/SCE 41159
TEST RESULTS
TEST 1
Discharge, PSI 82.5 Discharge head, feet 190.6 Standing water level, feet n/a Drawdown, feet n/a Pumping water level, feet 146.7 Total pumping head, feet 337.3 Gallons per minute flow 128 Gallons per foot of drawdown n/a Acre feet pumped per 24 hours 0.566 KW input to motor 15.6 HP input to motor 20.9 Motor load, % BHP 37.7 Measured speed of pump, RPM 1794 KWH per acre foot 661.9 Overall Plant efficiency in % 52.2
Test 1 was the normal operation with the discharge valve throttled as found.
At the time of arrival of the test crew, the pump was operating and was not shut down to obtain a standing water level.
We were unable to measure the gallons per minute flow with our test equipment.
The above flow measurement was obtained using your water meter.
If you have any questions please contact Jon Lee at (951) 653-1910.
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 06/26/2026 j9367 Highlight Well #1A
ANNUAL PUMPING COST ANALYSIS
San Bernardino CSA 70 Glen Helen Test date: 06/26/2026
Plant: Well #1A Meter No.: 256000-145138 H.P. 50
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation during the previous 12-month period.
This pump was found to be operating inefficiently. A new pump, properly designed, should operate with an overall plant efficiency of about 68.0 percent.
A reduction in your energy usage and cost would occur, as shown below, if this pump was redesigned and/or rebuilt.
The following analysis and projection assumes that the water requirement, GPM, total pumping lift and hours of operation will remain as they were at the time of the pump test.
EXISTING IMPROVED
CONDITIONS EFFICIENCY SAVINGS
Total annual kWhrs 60,013 46,010 14,003 Total annual cost $11,318.49 $8,677.46 $2,641.03 kW input to motor 15.6 12.0 3.6 Hours of operation per year 3847 3847 Equivalent 24 hour days 160.3 160.3 Acre feet pumped per 24 hour day 0.566 0.566 Average cost per kWhr $0.1886 $0.1886 Estimated Average cost per hour $2.94 $2.26 Average cost per acre foot $124.84 $95.71 $29.13 kWh per acre foot 661.9 507.5 154.5 Overall plant efficiency % 52.2 % 68.0
North of Glen Helen Parkway east of Glen Helen Road Pump type: DWT
Plant: Well #3
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: Peerless SERIAL: 643768
MOTOR: US SERIAL: A127728785-0011M0003
H.P. 60 LAT/LON: 34.13.119n117.24.718w
METER: 256000-233622 REF #: PC 2537/SCE 33743
TEST RESULTS
TEST 1 TEST 2
Discharge, PSI 18.5 28.5 Discharge head, feet 42.7 65.8 Standing water level, feet 79.8 Drawdown, feet 11.8 10.5 Pumping water level, feet 91.6 90.3 Total pumping head, feet 134.3 156.1 Gallons per minute flow 940 831 Gallons per foot of drawdown 79.7 79.2 Acre feet pumped per 24 hours 4.155 3.674 KW input to motor 49.8 49.0 HP input to motor 66.7 65.7 Motor load, % BHP 105.7 104.0 Measured speed of pump, RPM 1785 KWH per acre foot 287.7 320.1 Overall Plant efficiency in % 47.8 49.9
Test 1 was the normal operation of the pump at the time of the test. The other results were obtained by throttling the pump discharge.
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 06/26/2026 j9367
Well #3
San Bernardino CSA 70 Glen Helen Test date: 06/26/2026
Plant: Well #3 Meter No.: 256000-233622 H.P. 60
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation during the previous 12-month period.
This pump was found to be operating inefficiently. A new pump, properly designed, should operate with an overall plant efficiency of about 68.0 percent.
A reduction in your energy usage and cost would occur, as shown below, if this pump was redesigned and/or rebuilt.
The following analysis and projection assumes that the water requirement, GPM, total pumping lift and hours of operation will remain as they were at the time of the pump test.
EXISTING IMPROVED
CONDITIONS EFFICIENCY SAVINGS
Total annual kWhrs 107,070 75,227 31,843 Total annual cost $19,208.36 $13,495.67 $5,712.69 kW input to motor 49.8 35.0 14.8 Hours of operation per year 2150 2150 Equivalent 24 hour days 89.6 89.6 Acre feet pumped per 24 hour day 4.155 4.155 Average cost per kWhr $0.1794 $0.1794 Estimated Average cost per hour $8.93 $6.28 Average cost per acre foot $51.61 $36.26 $15.35 kWh per acre foot 287.7 202.1 85.6 Overall plant efficiency % 47.8 % 68.0
Plant: Well #4
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: Peerless/American Marsh SERIAL: 643785
MOTOR: US SERIAL: H03410-77523-002R-02
H.P. 60 LAT/LON: 34.12.994n117.24.376w
METER: 259000-077563 REF #: PC 2540/SCE 41178
TEST RESULTS
TEST 1
Discharge, PSI 28.0 Discharge head, feet 64.7 Standing water level, feet 95.5 Drawdown, feet 12.5 Pumping water level, feet 108.0 Total pumping head, feet 172.7 Gallons per minute flow 372 Gallons per foot of drawdown 29.8 Acre feet pumped per 24 hours 1.644 KW input to motor 20.5 HP input to motor 27.5 Motor load, % BHP 42.9 Measured speed of pump, RPM 1791 KWH per acre foot 299.3 Overall Plant efficiency in % 59.0
Test 1 was the normal operation of the pump at the time of the test.
The standing water level was measured down through the pump column.
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 6/26/2026 j9367 Highlight 06/ j9367
Well #4
San Bernardino CSA 70 Glen Helen Test date: 06/26/2026
Plant: Well #4 Meter No.: 259000-077563 H.P. 60
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation during the previous 12-month period.
This pump was found to be operating inefficiently. A new pump, properly designed, should operate with an overall plant efficiency of about 68.0 percent.
A reduction in your energy usage and cost would occur, as shown below, if this pump was redesigned and/or rebuilt.
The following analysis and projection assumes that the water requirement, GPM, total pumping lift and hours of operation will remain as they were at the time of the pump test.
EXISTING IMPROVED
CONDITIONS EFFICIENCY SAVINGS
Total annual kWhrs 39,729 34,486 5,243 Total annual cost $7,719.34 $6,700.53 $1,018.81 kW input to motor 20.5 17.8 2.7 Hours of operation per year 1938 1938 Equivalent 24 hour days 80.8 80.8 Acre feet pumped per 24 hour day 1.644 1.644 Average cost per kWhr $0.1943 $0.1943 Estimated Average cost per hour $3.98 $3.46 Average cost per acre foot $58.16 $50.48 $7.68 kWh per acre foot 299.3 259.8 39.5 Overall plant efficiency % 59.0 % 68.0
US gpm
H ea d
- f t
400375350325300125 275250
200175
10075
81.7
7.4375 in
7.725 in
6.797 in
75 75
Company: San Bernardino CSA 70 GH American-Marsh Pumps Size: 10JC 5 stage Name: Well #4 Catalog: american-marsh.60, Vers 20010a Speed: 1760 rpm 10/23/2012 480_VRT-TURBINE/ENCL - 1800 Dia: 7.4375 in
Design Point: 300 US gpm, 220 ft Curve: 3094
CSA 70 GH Well #4 06/26/2026 Test 1 172.7 h 372 q
North of Glen Helen Parkway east of Glen Helen Road Pump type: SUB
Plant: Well #5
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: No Data SERIAL: N/A MOTOR: Hitachi SERIAL: G27997E H.P. 15 LAT/LON: 34.13.207n117.24.898w
METER: 256000-171574 REF #: PC 2538/SCE 41180
TEST RESULTS
TEST 1 TEST 2
Discharge, PSI 12.0 23.0 Discharge head, feet 27.7 53.1 Standing water level, feet 69.3 Drawdown, feet 12.0 10.0 Pumping water level, feet 81.3 79.3 Total pumping head, feet 109.0 132.4 Gallons per minute flow 356 321 Gallons per foot of drawdown 29.7 32.1 Acre feet pumped per 24 hours 1.574 1.421 KW input to motor 16.2 16.2 HP input to motor 21.7 21.7 Motor load, % BHP 118.7 118.7 Measured speed of pump, RPM n/a KWH per acre foot 247.0 273.7 Overall Plant efficiency in % 45.2 49.5
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight Well #5 j9367
06/26/2026
San Bernardino CSA 70 Glen Helen Test date: 06/26/2026
Plant: Well #5 H.P. 15
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation since new pump and motor.
EXISTING
CONDITIONS
Average Cost per kWh $0.1834
Test 1 Test 2
KW input to motor 16.2 16.2 Acre feet pumped per 24 hour day 1.574 1.421 KWh per acre foot 247.0 273.7 Pumping cost per hour $2.97 $2.97 Pumping cost per acre foot $45.30 $50.19 Overall plant efficiency 45.2 49.5
Plant: Well #6
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: Peerless SERIAL: N/A
MOTOR: US SERIAL: G05-41074167-005R-02
H.P. 60 LAT/LON: 34.13.042n117.24.498w
METER: 259000-077563 REF #: PC 2539/SCE 41179
TEST RESULTS
TEST 1
Discharge, PSI 36.5 Discharge head, feet 84.3 Standing water level, feet 89.7 Drawdown, feet 6.5 Pumping water level, feet 96.2 Total pumping head, feet 180.5 Gallons per minute flow 644 Gallons per foot of drawdown 99.1 Acre feet pumped per 24 hours 2.846 KW input to motor 40.1 HP input to motor 53.7 Motor load, % BHP 80.8 Measured speed of pump, RPM 1783 KWH per acre foot 338.2 Overall Plant efficiency in % 54.6
The available water measurement location does not meet recommended industry standards. We recommend 8-10 diameters of straight pipe for the ideal test location.
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 06/26/2026 j9367
Well #6
San Bernardino CSA 70 Glen Helen Test date: 06/26/2026
Plant: Well #6 H.P. 60
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation since motor work.
EXISTING
CONDITIONS
Average Cost per kWh $0.1943 Estimated
Test 1
KW input to motor 40.1 Acre feet pumped per 24 hour day 2.846 KWh per acre foot 338.2 Pumping cost per hour $7.79 Pumping cost per acre foot $65.71 Overall plant efficiency 54.6
San Bernardino CSA 70 Glen Helen Test Date: 07/11/2025
Plant: Well #3
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: Peerless SERIAL: 643768
MOTOR: US SERIAL: A127728785-0011M0003
H.P. 60 LAT/LON: 34.13.119n117.24.718w
METER: 256000-233622 REF #: PC 2537/SCE 33743
TEST RESULTS
TEST 1 TEST 2
Discharge, PSI 22.5 32.0 Discharge head, feet 52.0 73.9 Standing water level, feet 113.7 Drawdown, feet 9.3 8.1 Pumping water level, feet 123.0 121.8 Total pumping head, feet 175.0 195.7 Gallons per minute flow 767 673 Gallons per foot of drawdown 82.5 83.1 Acre feet pumped per 24 hours 3.389 2.974 KW input to motor 47.2 46.1 HP input to motor 63.2 61.8 Motor load, % BHP 100.1 97.8 Measured speed of pump, RPM 1783 KWH per acre foot 334.2 372.1 Overall Plant efficiency in % 53.6 53.8
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 07/11/2025 j9367
Well #3
San Bernardino CSA 70 Glen Helen Test date: 07/11/2025
Plant: Well #3 Meter No.: 256000-233622 H.P. 60
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation during the previous 12-month period.
This pump was found to be operating inefficiently. A new pump, properly designed, should operate with an overall plant efficiency of about 68.0 percent.
A reduction in your energy usage and cost would occur, as shown below, if this pump was redesigned and/or rebuilt.
The following analysis and projection assumes that the water requirement, GPM, total pumping lift and hours of operation will remain as they were at the time of the pump test.
EXISTING IMPROVED
CONDITIONS EFFICIENCY SAVINGS
Total annual kWhrs 73,726 58,074 15,653 Total annual cost $13,226.52 $10,418.42 $2,808.09 kW input to motor 47.2 37.2 10.0 Hours of operation per year 1562 1562 Equivalent 24 hour days 65.1 65.1 Acre feet pumped per 24 hour day 3.389 3.389 Average cost per kWhr $0.1794 $0.1794 Estimated Average cost per hour $8.47 $6.67 Average cost per acre foot $59.96 $47.23 $12.73 kWh per acre foot 334.2 263.3 71.0 Overall plant efficiency % 53.6 % 68.0
San Bernardino CSA 70 Glen Helen Test Date: 07/11/2025 North of Glen Helen Parkway east of Glen Helen Road Pump type: SUB
Plant: Well #5
A test was made on this well pump and the following information was obtained.
EQUIPMENT
PUMP: No Data SERIAL: N/A MOTOR: Franklin SERIAL: 14C19-13-06274A H.P. 15 LAT/LON: 34.13.207n117.24.898w
METER: 256000-171574 REF #: PC 2538/SCE 41180
TEST RESULTS
TEST 1
Discharge, PSI 13.5 Discharge head, feet 31.2 Standing water level, feet 109.5 Drawdown, feet 5.0 Pumping water level, feet 114.5 Total pumping head, feet 145.7 Gallons per minute flow 222 Gallons per foot of drawdown 44.3 Acre feet pumped per 24 hours 0.979 KW input to motor 14.8 HP input to motor 19.8 Motor load, % BHP 108.4 Measured speed of pump, RPM n/a KWH per acre foot 362.8 Overall Plant efficiency in % 41.1
( 9 5 1 ) 6 5 3 - 1 9 1 0 L i c. 7 9 9 4 9 8 F a x ( 9 5 1 ) 6 5 3 - 1 9 5 0
Highlight 07/11/2025 j9367
Well #5
San Bernardino CSA 70 Glen Helen Test date: 07/11/2025
Plant: Well #5 Meter No.: 256000-171574 H.P. 15
The following cost analysis is presented as an aid to your cost accounting and planning. It is an Estimate based on the pump test data and your energy use or hours of operation during the previous 12-month period.
This pump was found to be operating inefficiently. A new pump, properly designed, should operate with an overall plant efficiency of about 56.0 percent.
A reduction in your energy usage and cost would occur, as shown below, if this pump was redesigned and/or rebuilt.
The following analysis and projection assumes that the water requirement, GPM, total pumping lift and hours of operation will remain as they were at the time of the pump test.
EXISTING IMPROVED
CONDITIONS EFFICIENCY SAVINGS
Total annual kWhrs 21,268 15,604 5,664 Total annual cost $3,900.48 $2,861.78 $1,038.70 kW input to motor 14.8 10.9 3.9 Hours of operation per year 1437 1437 Equivalent 24 hour days 59.9 59.9 Acre feet pumped per 24 hour day 0.979 0.979 Average cost per kWhr $0.1834 $0.1834 Estimated Average cost per hour $2.71 $1.99 Average cost per acre foot $66.53 $48.82 $17.72 kWh per acre foot 362.8 266.2 96.6 Overall plant efficiency % 41.1 % 56.0
EXHIBIT B - UPDATED LOCATION MAP
EXHIBIT C - GLEN HELEN DOMESTIC WATER SYSTEM
INFRASTRUCTURE MAP
Image j9367 Rectangle j9367 Text Box The Glen Helen wells pump directly into the distribution system, which supports overall supply capacity.
j9367 Image
Rectangle
| 2026-09-01T11:36:36-0700 | |
| Russel Viloria | |
| I am the author of this document |