This document provides plans and specifications for the construction project to Renovate Space for a New Mental Health Unit at the Lexington VA Medical Center in Lexington, Kentucky. The project involves renovating existing space to accommodate the new mental health unit. Plans include demolition of existing spaces, construction of new walls, installation of new mechanical, electrical and plumbing systems, and upgrades to fire protection and alarm systems. Bids for the project are due by June 15, 2020. The estimated value of the construction is $5-10 million. The construction is to be completed by January 2021. The solicitation was issued by the Department of Veterans Affairs and the construction work will take place at the Lexington VA Medical Center.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CFM [L/s] CFM [L/s] IN WG [Pa]

SD-1 SECURITY CEILING

DIFFUSER 35 [ 17 ] 130 [ 61 ] 0.240 [ 60 ] LAY-IN 24 x 24 [ 600 x 600 ] 6 x 6, 6 ø [152 x 152], [152 ø ] 27 NONE WHITE KEES SDP3L 3

SD-2 SECURITY CEILING

DIFFUSER 135 [ 64 ] 230 [ 110 ] 0.160 [ 40 ] LAY-IN 24 x 24 [ 600 x 600 ] 9 x 9, 8 ø [229 x 229], [203 ø ] 25 NONE WHITE KEES SDP3L 3

SD-3 SECURITY CEILING

DIFFUSER 235 [ 110 ] 400 [ 190 ] 0.160 [ 40 ] LAY-IN 24 x 24 [ 600 x 600 ] 12 x 12, 12 ø [305 x 305], [305 ø ] 29 NONE WHITE KEES SDP3L 3

SD-4 SECURITY CEILING

DIFFUSER 405 [ 190 ] 600 [ 280 ] 0.160 [ 40 ] LAY-IN 24 x 24 [ 600 x 600 ] 15 x 15, 14 ø [381 x 381], [356 ø ] 29 NONE WHITE KEES SDP3L 3

SD-5 SQUARE LOUVER FACE

CEILING DIFFUSER 70 [ 33 ] 160 [ 76 ] 0.063 [ 16 ] LAY-IN 24 x 24 [ 600 x 600 ] 6" [152 ø ] 16 NONE WHITE TITUS TMS 4

SD-6 SQUARE LOUVER FACE

CEILING DIFFUSER 250 [ 120 ] 435 [ 210 ] 0.066 [ 17 ] LAY-IN 24 x 24 [ 600 x 600 ] 10" [254 ø ] 22 NONE WHITE TITUS TMS 4

SG-1

STEEL DOUBLE

DEFLECTION SUPPLY

GRILLE

150 [ 71 ] 340 [ 160 ] 0.074 [ 19 ] WALL 13.75 x

9.75 [349 x 247] 12x8 [305 X 203] 22 NONE WHITE TITUS 300RL 5

NOTES:

1. SEE FLOOR PLAN FOR THROW PATTERN.

2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.

3. PROVIDE SQUARE TO ROUND ADAPTER.

4. PERTAINS TO OFFICE SPACE IN AREA B ONLY.

5. FOR USE IN ELECTRICAL ROOMS ONLY.

6. PROVIDE BASIS OF DESIGN OR EQUAL.

AIR DEVICE SCHEDULE (SUPPLY)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH

BASIS OF DESIGN

REMARKSMIN MAX

IN x IN [mm x mm] IN [mm ] MANUFATURER MODEL NO

CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]

EG-1 SECURITY GRILLE 160 [ 76 ] 400 [ 190 ] 0.096 24.000 CEILING 13.75 x 13.75 [ 350 x 350 ] 12 x 12, 12 ø [305 x 305], [305 ø ] 20 NONE WHITE KEES SEG-4P3 1

EG-2 SECURITY GRILLE 405 [ 190 ] 560 [ 260 ] 0.096 24.000 CEILING 15.75 x 15.75 [ 400 x 400 ] 14 x 14, 14 ø [355 x 355], [355 ø ] 22 NONE WHITE KEES SEG-4P3 1

RG-1 SECURITY GRILLE 30 [ 14 ] 80 [ 38 ] 0.096 24.000 CEILING 13.75 x 13.75 [ 350 x 350 ] 6 x 6 [152 x 152] 20 NONE WHITE KEES SEG-4P3

RG-2 SECURITY GRILLE 30 [ 14 ] 80 [ 38 ] 0.096 24.000 LAY-IN 24 x 24 [ 600 x 600 ] 6 x 6 [152 x 152] 20 NONE WHITE KEES SEG-4P3

RG-3 SECURITY GRILLE 85 [ 40 ] 160 [ 76 ] 0.096 24.000 LAY-IN 24 x 24 [ 600 x 600 ] 8 x 8 [203 x 203] 20 NONE WHITE KEES SEG-4P3

RG-4 SECURITY GRILLE 160 [ 76 ] 400 [ 190 ] 0.096 24.000 CEILING 13.75 x 13.75 [ 350 x 350 ] 12 x 12 [305 x 305] 20 NONE WHITE KEES SEG-4P3

RG-5 SECURITY GRILLE 405 [ 190 ] 800 [ 380 ] 0.096 24.000 CEILING 19.75 x 19.75 [ 502 x 502 ] 18 x 18 [457 x 457] 20 NONE WHITE KEES SEG-4P3

RG-6 SECURITY GRILLE 130 [ 61 ] 650 [ 310 ] 0.051 13.000 LAY-IN 24 x 12 [ 600 x 300 ] 22 x 10 [558 x 254] 13 NONE WHITE TITUS 350RL 2

RG-7

35 DEGREE

DEFLECTION

STEEL GRILLE

150 [ 71 ] 310 [ 150 ] 0.073 18.000 WALL 13.75 x 19.75 [349 x 247] 12 x 8 [305 X 203] 19 NONE WHITE TITUS 350RL 3

NOTES:

1. PROVIDE SQUARE TO ROUND ADAPTER.

2. PERTAINS TO OFFICE SPACE IN AREA B ONLY.

3. FOR USE IN ELECTRICAL ROOMS ONLY.

4. PROVIDE BASIS OF DESIGN OR EQUAL.

AIR DEVICE SCHEDULE (RETURN)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH

BASIS OF DESIGN

REMARKSMIN MAX

MANUFATURER MODEL NO

RTU-14 UVGI DISINFECTION SYSTEM SCHEDULE

COIL WIDTH 60 INCHES [152 CM]

COIL HEIGHT 45 INCHES [114 CM]

NUMBER OF UV-C LAMPS 2

UV-C LAMP ORIENTATION HORIZONTAL

POSITION RELATIVE TO COIL DOWNSTREAM

AVERAGE IRRADIANCE ON THE SURFACE 1591 µW/CM2 (SEE NOTES 2 & 3) MINIMUM IRRADIANCE ON THE SURFACE 445 µW/CM2 (SEE NOTES 2 & 3)

NOTES:

1)REFER TO DETAIL 4 ON SHEET MH-503 FOR RTU-14 UV-C LAMP POSITIONING DIAGRAM.

2)IRRADIANCE VALUE IS ESTIMATED UV-C LAMP OUTPUT AT END OF LIFE.

3)PROVIDE UV-C REFLECTORS TO MAGNIFY IRRADIANCE VALUES ON THE SURFACES TO BE IRRADIATED.

4)PROVIDE UV-C SHEILDING FOR ALL NON-UV-C RESISTANT MATERIALS PRESENT IN THE EXPOSED CHAMBER SUCH AS BUT NOT LIMITED TO ORGANIC MATERIALS AND ELECTRIC WIRING THAT COULD POSSIBLY BE DEGRADED FASTER THAN THE LIFE OF THE UNIT.

5)PROVIDE UV-C GRID, LAMPS, BULBS, POWER SUPPLIES, UV-C RESISTANT OR SHEILDED ELECTRIC WIRING AND A MINIMUM OF ONE VIEWPORT OF UV-C ABSORBING MATERIAL PER ACCESS DOOR TO UV-C EXPOSED CHAMBER AND ALL INSTALLATION AND ALL WIRING AND HARDWARE FOR A COMPLETELY FUNCTIONAL SYSTEM. PROVIDE

BASIS OF DESIGN OR EQUIVALENT.

6)PROVIDE RADIOMETER SENSOR AND DISPLAY (BIOZONE SCIENTIFIC INTERNATIONAL COIL CARE MODEL 17-7010 OR EQUIVALENT) WITH INTERFACE TO BULB INTENSITY

MONITORING DEVICE (MODEL 17-7010 DISPLAY) VIA BAS (BUILDING AUTOMATION SYSTEM).

7)PROVIDE DETAILED PICTURE(S) OF EXACTLY WHAT THE BAS GRAPHIC OF THE BULB INTENSITY MONITORING DEVICE AND ANY OTHER DDC POINTS CONTROLLING THE UV-C LIGHTING SYSTEM WILL LOOK LIKE WITH SYSTEM SUBMITTAL FOR REVIEW AND APPROVAL. ALL SYSTEM CONTROL POINTS, SETPOINTS, AND ALARMS SHALL BE SHOWN ON THE GRAPHIC, AND ALL SETPOINTS SHALL BE ADJUSTABLE. GRAPHICS SHALL BE PASSWORD PROTECTED IN A TIERED FASHION SO SOME USERS CAN ONLY MONITOR WHILE OTHERS CAN CHANGE VARIOUS SETPOINTS. AT A MINIMUM SHOW OPERATIONAL STATUS OF THE UV LAMPS (ON/OFF STATUS) ON THE BAS GRAPHICS. DEPICT ON/OFF STATUS BY EITHER A STANDARD INCANDESCENT LIGHT BULB ICON OR A BLUE TUBE ICON. ICON SHALL CHANGE TO SOMETHING LIKE FLASHING RED TO REPRESENT NON-

OPERATIONAL STATUS.

8)CONNECT UV LIGHT SYSTEM TO THE SERVICE LIGHTING CIRCUIT AHEAD OF LOCAL SWITCHING. VERIFY CIRCUIT CAN SUPPORT THE ADDITIONAL LOAD PRIOR TO CONNECTION. SEE TOTAL SYSTEM MCA IN SCHEDULE ABOVE. THE 2-LAMP POWER SUPPLY SHALL BE HARDWIRED IN A JUNCTION BOX THAT ALSO HAS A DEDICATED RECEPTACLE TO PLUG IN ONE RADIOMETER VIA THE RADIOMETER’S POWER CORD. PROVIDE A NEW DUAL RECEPTACLE AND USE ONLY ONE FOR THE RADIOMETER.

PROVIDE AS MANY NEW JUNCTION BOXES AND OTHER WIRING AND HARDWARE AS REQUIRED.

9)PROVIDE DEDICATED, LOCKABLE, DISCONNECT SWITCH(ES) OUTSIDE UV-C CHAMBER FOR USE WITH A FORMAL LOCKOUT/TAGOUT PROCEDURE.

10)PROVIDE AUTOMATIC DOOR INTERLOCK SAFETY SWITCH(ES) WIRED IN SERIES WITH EACH OTHER AT EACH DOOR ACCESSING RTU WHERE UV-C LIGHTING IS LOCATED OR CAN BE VIEWED. PROVIDE BASIS OF DESIGN (BIOZONE PART NUMBER CCX-KT-DS) OR EQUIVALENT.

11)PROVIDE WARNING SIGN OUTSIDE EACH ACCESS DOOR TO THE UV-C CHAMPER AND ON ANY ACCESS DOOR WHERE UV-C LIGHT CAN BE VIEWED. SIGN SHALL SAY SOMETHING SIMILAR TO THE FOLLOWING, “WARNING! PROTECT EYES FROM UV LIGHT. TURN OFF UNIT OR DISCONNECT BEFORE SERVICING.”

12)CONTRACTOR SHALL PROVIDE OWNER PERSONNEL A MINIMUM OF 2 HOURS OF MAINTENANCE AND SAFETY TRAINING TEACHING THEM ALL MAINTENANCE AND SAFETY DESCRIBED IN CHAPTER 62, ESPECIALLY IN SECTION 9. MAINTENANCE OF THE 2019 ASHRAE HANDBOOK: HVAC APPLICATIONS ON PAGES 62.13 AND 62.14 AND ALL

MAINTENANCE AND SAFETY TRAINING FROM MANUFACTURER OF UV-C LIGHTING SYSTEM.

13)UV-C LIGHTING SYSTEM IS INTENDED TO FUNCTION 24/7/365 UNLESS TURNED OFF BY SAFETY SWITCH OR FORMALLY TAGGED OUT DISCONNECT FOR SERVICING.

14)INSTALL UV-C SYSTEM PER MANUFACTURER’S INSTRUCTIONS. DESIGN INTENT IS TO MOUNT UV-C LAMPS AND REFLECTORS AS SHOWN ON POSITIONING DIAGRAM, TAGOUT TYPE DISCONNECT, POWER SUPPLIES AND RADIOMETER OUTSIDE RTU BUT INSIDE SERVICE VESTIBULE.

15)SEE SPECIFICATIONS FOR MORE DESIGN INFORMATION.

DISTANCE FROM COIL 12 INCHES [31 CM]

X1, Y1, D1 INCHES [CM] (SEE NOTE 1) X2, Y2, D2 INCHES [CM] (SEE NOTE 1)

UV-C LAMP 1 7, 11, 12 [18, 28, 31] 52, 11, 12 [132, 28, 31]

ELECTRICAL POWER (TOTAL SYSTEM) 240 WATTS

POWER DENSITY 1.12 WATTS/CM

TOTAL SYSTEM (LAMP POWER SUPPLY AND

RADIOMETER) MINIMUM CIRCUIT AMPACITY (MCA) 2.5 AMPS

MAXIMUM IRRADIANCE ON THE SURFACE 2453 µW/CM2 (SEE NOTES 2 & 3)

UV-C LAMP 2 7, 34, 12 [18, 86, 31] 52, 34, 12 [132, 86, 31]

UV-C LAMP LENGTH 45 [115]

UV-C LAMP LIFESPAN 1-YEAR LAMP: 12,000 HOURS 2-YEAR LAMP: 18,000 HOURS

ELECTRICAL POWER (EACH UV-C LAMP) 120 WATTS

UV-C LAMP SYSTEM TYPE (BASIS OF DESIGN)

BIOZONE SCIENTIFIC INTERNATIONAL COILCARE X UVGI DISINFECTION

SYSTEM

• 2-LAMP SYSTEM, MODEL CCX48HO

• SERVED BY ONE, 2-LAMP POWER SUPPLY (100-277 VAC), MODEL CCX-

AEX2BHO

• WITH TWO ENCAPSULATED UV-C LAMPS, MODEL 10-H48000-T

• AND ONE RADIOMETER, MODEL 17-7010 (100-240 VAC)

OR EQUIVALENTS

MARK MODE SERVICE

SUPPLY AIR

(CFM)

RETURN

AIR (CFM)

OUTSIDE

AIR (CFM)

REMOTE

EXHAUST AIR

(CFM)

REMOTE

RELIEF

(CFM)

RELIEF AIR

AT RTU (CFM)

OVERALL POSITIVE

BUILDING AIR

BALANCE (CFM)

THEORETICAL

DIFFERENTIAL

PRESSURE (IN. W.C.)

RTU-14 MIN OUTDOOR AIR 1ST FLOOR 7,760 5,270 2,490 2,290 0 0 200 0.023

RTU-14 ECONOMIZER 1ST FLOOR 7,760 - 7,760 2,290 0 5,270 200 0.023

TABLE 2-1, OVERALL BUILDING AIR BALANCE SUMMARY

(FROM VA 2019 HVAC DESIGN MANUAL, CHAPTER 2, TABLE 2-1, PAGE 45 OF 356)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

596A4-18-107RENOVATE SPACE FOR

NEW MENTAL HEALTH UNIT

LEXINGTON, KY, TROY BOWLING

F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45215 513-522-0956

JRA Architects 3225 Summit Square Place Lexington KY 40509 859-252-6781

C U se rs

\c ra ig \D o cu m e n ts

\R e vi t

L o ca l M o d e ls \M e ch a n ic a l ( cr a ig

.li e g ib e l@ ff e

-s e rv .c o m

.r vt

/1

/2

:0

:1

P

M

MH-603

SCHEDULES

03/24/2020 GC KG/CL03/24/2020

TABLE 2-2, ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE

AHU NO.

ROOM

NO.

ROOM NAME

ROOM SIZE

AHU

PEAK ROOM COOLING LOAD

PEAK ROOM HEATING

LOAD

CALCULATED ROOM AIRFLOW REQUIRED ROOM AIRFLOW

SELECTED DESIGN ROOM

AIRFLOW

SELECTED DESIGN ROOM MINIMUM

AIRFLOW

SELECTED DESIGN

REHEAT TEMP.

ROOM AIR

ROOM

STATUS

ROOM AIR

BALANCE

AREA HEIGHT VOLUME

SYSTEM

TYPE

SENSIBLE LATENT

BTUH W CFM L/S ACH

DELTA T

ACH

OA

ACH

TOTAL AIRFLOW

OUTSIDE

AIRFLOW CFM L/S CFM L/S DEG F DEG C VAV OR CV

(+) OR (-) OR

(0)

SF M^2 FT M CF M^3 VAV OR CV BTUH W BTUH W DEG F DEG C CFM L/S CFM L/S

(E) AC-3 B129B OFFICE 101.3 9.41 8.0 2.44 810.7 22.96 VAV 1136 332.9 205 60.1 0 0.0 55 26.0 4.07 20 11.1 4 2 54 25.5 27 12.8 175 82.6 110 51.9 85 29.4 RETURN VAV (0)

(E) AC-3 B129C OFFICE 108.3 10.06 8.0 2.44 866.6 24.54 VAV 1136 332.9 205 60.1 0 0.0 55 26.0 3.81 20 11.1 4 2 58 27.3 29 13.6 100 47.2 120 56.6 85 29.4 RETURN VAV (0)

(E) AC-3 B129 CORRIDOR 267.7 24.87 8.0 2.44 2141.5 60.64 VAV 1191 349.0 0 0.0 0 0.0 57 26.9 1.60 20 11.1 4 2 143 67.4 71 33.7 300 141.6 300 141.6 85 29.4 RETURN VAV (+)

(E) AC-3 B129A CLOSET 6.0 0.56 8.0 2.44 48.3 1.37 VAV 0 0.0 0 0.0 0 0.0 0 0.0 0.00 20 11.1 4 0 3 1.5 0 0.0 0 0.0 0 0.0 85 29.4 RETURN CV (0)

(E) AC-3 B129D CLOSET 25.3 2.35 8.0 2.44 202.4 5.73 VAV 3747 1098.1 0 0.0 0 0.0 10 4.7 2.96 20 11.1 4 0 13 6.4 0 0.0 0 0.0 0 0.0 85 29.4 RETURN CV (0)

(E) AC-3 B129K PANTRY 18.0 1.67 10.0 3.05 133.0 3.77 VAV 8115 2378.3 0 0.0 0 0.0 12 5.7 5.41 20 11.1 4 2 9 4.2 4 2.1 0 0.0 0 0.0 85 29.4 RETURN CV (0)

(E) AC-3 B129L STUDENTS 62.9 5.84 8.0 2.44 502.9 14.24 VAV 1384 405.6 410 120.2 0 0.0 69 32.6 8.23 20 11.1 4 2 34 15.8 17 7.9 0 0.0 80 37.8 85 29.4 RETURN VAV (0)

(E) AC-3 B129E OFFICE 97.8 9.09 8.0 2.44 782.8 22.17 VAV 1136 332.9 205 60.1 0 0.0 55 26.0 4.22 20 11.1 4 2 52 24.6 26 12.3 100 47.2 105 49.6 85 29.4 RETURN VAV (0)

(E) AC-3 B129F OFFICE 99.6 9.26 8.0 2.44 797.1 22.57 VAV 1136 332.9 205 60.1 0 0.0 55 26.0 4.14 20 11.1 4 2 53 25.1 27 12.5 150 70.8 110 51.9 85 29.4 RETURN VAV (0)

(E) AC-3 B129G OFFICE 92.0 8.55 8.0 2.44 736.0 20.84 VAV 988 289.6 205 60.1 0 0.0 49 23.1 3.99 20 11.1 4 2 49 23.2 25 11.6 150 70.8 105 49.6 85 29.4 RETURN VAV (0)

(E) AC-3 B129H OFFICE 132.0 12.27 8.0 2.44 1056.4 29.91 VAV 1136 332.9 205 60.1 0 0.0 56 26.4 3.18 20 11.1 4 2 70 33.2 35 16.6 175 82.6 150 70.8 85 29.4 RETURN CV (0)

(E) AC-3 B129J SHARED OFFICE 114.1 10.60 8.0 2.44 912.4 25.84 VAV 1532 449.0 410 120.2 0 0.0 76 35.9 5.00 20 11.1 4 2 61 28.7 30 14.4 150 70.8 125 59.0 85 29.4 RETURN VAV (0)

RTU-14 A132 PRIVATE 148.4 13.79 9.3 2.84 1383.8 39.19 VAV 2020 592.0 270 79.1 1267 371.3 97 45.8 4.21 20 11.1 6 2 138 65.3 46 21.8 140 66.1 185 87.3 85 29.4 RETURN CV (+)

RTU-14 A132A TOILET 46.6 4.33 8.0 2.44 372.5 10.55 VAV 511 149.8 0 0.0 0 0.0 25 11.8 4.03 20 11.1 10 0 62 29.3 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A131 PRIVATE 145.5 13.52 9.3 2.84 1356.3 38.41 VAV 1287 377.2 270 79.1 933 273.4 62 29.3 2.74 20 11.1 6 2 136 64.0 45 21.3 140 66.1 185 87.3 85 29.4 RETURN CV (+)

RTU-14 A131A TOILET 43.7 4.06 8.0 2.44 349.9 9.91 VAV 511 149.8 0 0.0 0 0.0 25 11.8 4.29 20 11.1 10 0 58 27.5 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A130 PRIVATE 128.2 11.91 9.3 2.84 1194.7 33.83 VAV 1300 381.0 270 79.1 648 189.9 62 29.3 3.11 20 11.1 6 2 119 56.4 40 18.8 120 56.6 160 75.5 85 29.4 RETURN CV (+)

RTU-14 A130A TOILET 71.2 6.62 8.0 2.44 569.8 16.14 VAV 511 149.8 0 0.0 0 0.0 25 11.8 2.63 20 11.1 10 0 95 44.8 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A129 SEMI-PRIVATE 216.8 20.14 9.3 2.84 2020.8 57.22 VAV 1759 515.5 540 158.3 1032 302.4 84 39.6 2.49 20 11.1 6 2 202 95.4 67 31.8 205 96.7 270 127.4 85 29.4 RETURN CV (+)

RTU-14 A129A TOILET 78.6 7.30 8.0 2.44 628.9 17.81 VAV 1855 543.6 0 0.0 1109 325.0 89 42.0 8.49 20 11.1 10 0 105 49.5 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A128 SEMI-PRIVATE 211.3 19.63 9.3 2.84 1970.4 55.80 VAV 1576 461.9 540 158.3 856 250.9 76 35.9 2.31 20 11.1 6 2 197 93.0 66 31.0 200 94.4 265 125.1 85 29.4 RETURN CV (+)

RTU-14 A128A TOILET 78.3 7.27 8.0 2.44 626.2 17.73 VAV 511 149.8 0 0.0 0 0.0 25 11.8 2.40 20 11.1 10 0 104 49.3 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A127 PRIVATE 151.6 14.08 9.3 2.84 1413.1 40.01 VAV 2022 592.6 270 79.1 1275 373.7 97 45.8 4.12 20 11.1 6 2 141 66.7 47 22.2 145 68.4 190 89.7 85 29.4 RETURN CV (+)

RTU-14 A127A TOILET 48.9 4.55 8.0 2.44 391.0 11.07 VAV 511 149.8 0 0.0 0 0.0 25 11.8 3.84 20 11.1 10 0 65 30.8 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A126 PRIVATE 184.6 17.15 9.3 2.84 1721.4 48.75 VAV 1489 436.4 270 79.1 937 274.6 71 33.5 2.47 20 11.1 6 2 172 81.2 57 27.1 175 82.6 230 108.5 85 29.4 RETURN CV (+)

RTU-14 A126A TOILET 45.2 4.19 8.0 2.44 359.9 10.19 VAV 511 149.8 0 0.0 0 0.0 25 11.8 4.17 20 11.1 10 0 60 28.3 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A125 DAY/DINING ROOM 849.9 78.96 9.3 2.84 7927.5 224.48 VAV 9365 2744.6 4320 1266.1 5607 1643.2 449 211.9 3.40 20 11.1 6 2 793 374.1 264 124.7 800 377.6 1065 502.6 85 29.4 RETURN CV (0)

RTU-14 A124 SEMI-PRIVATE 270.7 25.15 9.3 2.84 2524.2 71.48 VAV 1927 564.7 540 158.3 1595 467.4 92 43.4 2.19 20 11.1 6 2 252 119.1 84 39.7 255 120.3 340 160.5 85 29.4 RETURN CV (+)

RTU-14 A124A TOILET 46.6 4.33 8.0 2.44 373.1 10.57 VAV 511 149.8 0 0.0 0 0.0 25 11.8 4.02 20 11.1 10 0 62 29.3 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A123 LAUNDRY 79.1 7.35 8.0 2.44 632.6 17.91 VAV 17474 5121.1 0 0.0 0 0.0 838 395.5 79.48 20 11.1 10 0 105 49.8 0 0.0 120 56.6 220 103.8 85 29.4 EXHAUST (S) CV (-)

RTU-14 A122 PRIVATE 154.9 14.39 9.3 2.84 1444.5 40.90 VAV 1705 499.7 270 79.1 1728 506.4 85 40.1 3.53 20 11.1 6 2 144 68.2 48 22.7 145 68.4 195 92.0 85 29.4 RETURN CV (+)

RTU-14 A122A TOILET 51.7 4.81 8.0 2.44 413.9 11.72 VAV 511 149.8 0 0.0 0 0.0 25 11.8 3.62 20 11.1 10 0 69 32.6 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A121 PRIVATE 132.9 12.34 9.3 2.84 1238.8 35.08 VAV 1023 299.8 270 79.1 828 242.7 49 23.1 2.37 20 11.1 6 2 124 58.5 41 19.5 125 59.0 165 77.9 85 29.4 RETURN CV (+)

RTU-14 A121A TOILET 45.6 4.24 8.0 2.44 365.1 10.34 VAV 511 149.8 0 0.0 0 0.0 25 11.8 4.11 20 11.1 10 0 61 28.7 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A120 PRIVATE 144.6 13.43 9.3 2.84 1347.8 38.16 VAV 1217 356.7 270 79.1 1320 386.9 67 31.6 2.98 20 11.1 6 2 135 63.6 45 21.2 135 63.7 180 85.0 85 29.4 RETURN CV (+)

RTU-14 A120A TOILET 63.9 5.94 8.0 2.44 511.3 14.48 VAV 646 189.3 0 0.0 292 85.6 36 17.0 4.22 20 11.1 10 0 85 40.2 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A115 MULTI-PURPOSE ROOM 462.0 42.92 9.3 2.84 4307.2 121.97 VAV 6274 1838.7 3280 961.3 3857 1130.4 301 142.1 4.19 20 11.1 4 2 287 135.5 144 67.8 435 205.3 575 271.4 85 29.4 RETURN CV (0)

RTU-14 A119 BREAK ROOM 216.6 20.12 9.3 2.84 1961.9 55.55 VAV 6480 1899.1 1080 316.5 2799 820.3 311 146.8 9.51 20 11.1 4 2 131 61.7 65 30.9 315 148.7 315 148.7 85 29.4 RETURN CV (0)

RTU-14 A116 CORRIDOR 267.3 24.83 9.0 2.74 2402.7 68.04 VAV 1914 560.9 0 0.0 1654 484.7 95 44.8 2.37 20 11.1 4 2 160 75.6 80 37.8 160 75.5 325 153.4 85 29.4 RETURN CV (+)

RTU-14 A117 JAN. 24.2 2.25 10.0 3.05 193.5 5.48 VAV 179 52.5 0 0.0 119 34.9 9 4.2 2.79 20 11.1 10 0 32 15.2 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A118 STAFF TOILET 45.3 4.21 8.0 2.44 362.3 10.26 VAV 595 174.4 0 0.0 313 91.7 30 14.2 4.97 20 11.1 10 0 60 28.5 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A111 GROUP ROOM 243.3 22.60 9.0 2.74 2187.2 61.93 VAV 3480 1019.9 5460 1600.2 0 0.0 108 51.0 2.96 20 11.1 6 2 219 103.2 73 34.4 225 106.2 295 139.2 85 29.4 RETURN CV (+)

RTU-14 A105 LAB CLEAN ROOM 323.7 30.07 9.0 2.74 2909.7 82.39 VAV 592 173.5 0 0.0 0 0.0 28 13.2 0.58 20 11.1 4 0 194 91.5 0 0.0 200 94.4 200 94.4 85 29.4 RETURN CV (+)

RTU-14 A106 TOILET 36.5 3.39 8.0 2.44 291.7 8.26 VAV 212 62.1 0 0.0 0 0.0 10 4.7 2.06 20 11.1 10 0 49 22.9 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A106A ANTEROOM 27.5 2.55 8.0 2.44 219.7 6.22 VAV 299 87.6 0 0.0 0 0.0 14 6.6 3.82 20 11.1 4 2 15 6.9 7 3.5 35 16.5 35 16.5 85 29.4 RETURN CV (+)

RTU-14 A107 LAB SOILED 123.8 11.50 9.0 2.74 1113.9 31.54 VAV 444 130.1 0 0.0 0 0.0 21 9.9 1.13 20 11.1 10 0 186 87.6 0 0.0 90 42.5 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A109 CLEAN UTILITY 91.8 8.53 8.0 2.44 734.6 20.80 VAV 148 43.4 0 0.0 0 0.0 7 3.3 0.57 20 11.1 4 0 49 23.1 0 0.0 50 23.6 50 23.6 85 29.4 RETURN CV (+)

RTU-14 A108 EXAM ROOM 135.7 12.61 9.0 2.74 1219.7 34.54 VAV 716 209.8 410 120.2 0 0.0 41 19.3 2.02 20 11.1 6 2 122 57.6 41 19.2 125 59.0 165 77.9 85 29.4 RETURN CV (0)

RTU-14 A137 CONSULT 100.0 9.29 9.0 2.74 898.9 25.45 VAV 692 202.8 205 60.1 0 0.0 50 23.6 3.34 20 11.1 4 2 60 28.3 30 14.1 60 28.3 120 56.6 85 29.4 RETURN CV (0)

RTU-14 A136 SECLUSION ROOM 82.7 7.68 9.0 2.74 744.3 21.08 VAV 464 136.0 270 79.1 0 0.0 26 12.3 2.10 20 11.1 6 2 74 35.1 25 11.7 80 37.8 105 49.6 85 29.4 RETURN CV (+)

RTU-14 A136A SECLUSION ANTEROOM 69.2 6.42 9.0 2.74 617.6 17.49 VAV 224 65.6 0 0.0 0 0.0 19 9.0 1.85 20 11.1 4 2 41 19.4 21 9.7 40 18.9 75 35.4 85 29.4 RETURN CV (+)

RTU-14 A136B TOILET 50.9 4.73 8.0 2.44 407.4 11.54 VAV 511 149.8 0 0.0 0 0.0 25 11.8 3.68 20 11.1 10 0 68 32.0 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A133 OFFICE: PROGRAM MGR. 104.7 9.73 9.0 2.74 941.4 26.66 VAV 840 246.2 205 60.1 0 0.0 40 18.9 2.55 20 11.1 4 2 63 29.6 31 14.8 130 61.4 130 61.4 85 29.4 RETURN CV (0)

RTU-14 A134 OFFICE: HEAD NURSE 89.8 8.34 9.0 2.74 807.4 22.86 VAV 840 246.2 205 60.1 0 0.0 40 18.9 2.97 20 11.1 4 2 54 25.4 27 12.7 55 26.0 110 51.9 85 29.4 RETURN CV (0)

RTU-14 A143 GROUP ROOM 149.5 13.89 9.0 2.74 1344.2 38.06 VAV 1137 333.2 820 240.3 0 0.0 55 26.0 2.45 20 11.1 6 2 134 63.4 45 21.1 140 66.1 185 87.3 85 29.4 RETURN CV (0)

RTU-14 A141 STAFF STATION 504.6 46.88 8.0 2.44 3992.1 113.04 VAV 8491 2488.5 4095 1200.1 0 0.0 407 192.1 6.12 20 11.1 4 2 266 125.6 133 62.8 410 193.5 540 254.9 85 29.4 RETURN CV (0)

RTU-14 A142 MED ROOM 172.7 16.04 9.0 2.74 1552.1 43.95 VAV 2344 687.0 205 60.1 0 0.0 112 52.9 4.33 20 11.1 6 2 155 73.3 52 24.4 155 73.2 210 99.1 85 29.4 RETURN CV (0)

RTU-14 100-2 CORRIDOR-2 1214.9 112.87 9.3 2.84 10950.4 310.08 VAV 2074 607.8 0 0.0 0 0.0 364 171.8 1.99 20 11.1 4 2 730 344.5 365 172.3 730 344.5 1460 689.0 85 29.4 RETURN CV (+)

RTU-14 A101 SALLY PORT ENTRY 123.8 11.50 9.0 2.74 1113.1 31.52 VAV 148 43.4 0 0.0 0 0.0 9 4.2 0.49 20 11.1 0 0 0 0.0 0 0.0 170 80.2 0 0.0 85 29.4 RETURN CV (+)

RTU-14 A110 SOILED UTILITY 96.2 8.94 8.0 2.44 769.4 21.79 VAV 148 43.4 0 0.0 0 0.0 9 4.2 0.70 20 11.1 10 0 128 60.5 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 100-1 CORRIDOR-1 1584.1 147.17 9.3 2.84 14711.5 416.58 VAV 3413 1000.3 0 0.0 0 0.0 493 232.7 2.01 20 11.1 4 2 981 462.9 490 231.4 990 467.2 1975 932.1 85 29.4 RETURN CV (+)

RTU-14 A112 PATIENT TOILET 46.5 4.32 8.0 2.44 372.2 10.54 VAV 405 118.7 0 0.0 0 0.0 19 9.0 3.06 20 11.1 10 0 62 29.3 0 0.0 0 0.0 0 0.0 85 29.4 EXHAUST (G) CV (-)

RTU-14 A113 CLOSET 47.6 4.42 8.0 2.44 381.0 10.79 VAV 0 0.0 0 0.0 0 0.0 0 0.0 0.00 20 11.1 4 0 25 12.0 0 0.0 0 0.0 0 0.0 85 29.4 RETURN CV (0)

RTU-14 AU104 ELECTRICAL 52.7 4.89 12.0 3.65 630.2 17.85 VAV 829 243.0 0 0.0 0 0.0 0 0 0 0.0 0 0.0 150 70.8 150 70.8 85 29.4 CV (0)

RTU-14 A114 ELEC. 38.0 3.53 12.0 3.65 454.5 12.87 VAV 3166 927.9 0 0.0 0 0.0 0 0 0 0.0 0 0.0 310 146.3 310 146.3 85 29.4 VAV (0)

RTU-14 A102 TOILET 69.3 6.43 8.0 2.44 554.0 15.69 VAV 10 0 92 43.6 0 0.0 0 0.0 CV (-)

RTU-14 A103 TOILET 54.1 5.02 8.0 2.44 432.6 12.25 VAV 10 0 72 34.0 0 0.0 0 0.0 CV (-)

NOTE:

1. FROM VA 2019 HVAC DESIGN MANUAL, CHAPTER 2, TABLE 2-2, PAGE 46 OF 356

Revisions: Date:

LAB CLEAN ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH ISOLATION SECLUSION ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH GROUP ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH EXAM ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH COUNSELOR OFFIC 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

OFFICE 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH NURSING STATION 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH MEDICATION ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH DINING ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

MENTAL HEALTH MULTI-PURPOSE ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

CORRIDORS 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

BREAK ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

CLEAN UTILITY/STORAGE ROOM N/A N/A N/A N/A N/A N/A

LAUNDRY 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

LAB SOILED 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

PANTRY 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

CLOSET N/A N/A N/A N/A N/A N/A

ELECTRICAL ROOMS WITH INTERNAL HEAT GAIN 86 [ 30 ] N/A N/A 40 [ 4 ] N/A N/A

HOUSEKEEPING AID CLOSET (JANITOR ROOM) N/A N/A N/A N/A N/A N/A

AIR HANDLING EQUIPMENT ROOM N/A N/A N/A 50 [ 10 ] N/A N/A

SOILED UTILITY AND STORAGE ROOM N/A N/A N/A N/A N/A N/A

OUTDOOR DESIGN CONDITIONS 87.2 [ 31 ] 77.3 [ 25 ] 64.5 8.8 [ -13 ] -23.9 [ -31 ] 17 -23.9 [ -31 ]

INDOOR AREA DESIGN CONDITIONS

MENTAL HEALTH PATIENT TOILET STANDARD N/A N/A 20 68 [ 20 ] 39.4 [ 4 ] 35

MENTAL HEALTH PATIENT ROOM 75 [ 24 ] 62.5 [ 17 ] 50 70 [ 21 ] 41.1 [ 5 ] 35

HVAC DESIGN DATA

DESIGN CONDITIONS

SUMMER WINTER

LOWEST AVERAGE

ANNUAL

DEWPOINTTEMP WET BULB TEMP

% HUMIDITY

TEMP DEWPOINT TEMP

% HUMIDITY

°F [°C] °F [°C] °F [°C] °F [°C] °F [°C]

CFM [L/s] IN [Pa] IN [mm] BHP HP [kW] LBS

EF-MH ROOF MENTAL

HEALTH RTU-14 2290 [ 1100 ] 0.7 [ 180 ] ROOF EXHAUSTER 18.5 [ 460 ] 58% DIRECT 874 0.35 0.75 [ 1 ] 1 115 900 ECM RTU-14 85 GREENHECK G-183-VG -

1. PROVIDE 24 INCH HIGH, 30 INCH WIDE X 30 LONG INSULATED CURB BY SAME MANUFACTURER AS EXHAUST FAN, ALUMINUM BIRDSCREEN, MOTORIZED SHUT-OFF DAMPER (SEE CONTROL SCHEMATIC DRAWINGS), ALUMINUM EXHAUST FAN, BASIS OF DESIGN OR EQUAL.

NOTES:

FAN SCHEDULE

2. SEE CONTROL DRAWINGS FOR REQUIRED POINTS AND SEQUENCE OF CONTROL FOR INTEGRATION WITH BUILDING AUTOMATION SYSTEM.

TYPE

DIAMETER MIN %

EFF DRIVE FAN MAX

RPM

NOMINAL POWER

PHASE VOLT RPM SPEED

CONTROL MANUFACTURER MODEL NO

MARK LOCATION

AREA AND/OR

BLDG

SERVED

SYSTEM

AND/OR

SERVICE

AIR FLOW TSP

FAN MOTOR ELECTRICAL

CONTROL

SEQUENCE

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

596A4-18-107RENOVATE SPACE FOR

NEW MENTAL HEALTH UNIT

LEXINGTON, KY, TROY BOWLING

F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45215 513-522-0956

JRA Architects 3225 Summit Square Place Lexington KY 40509 859-252-6781

C U se rs

\c ra ig \D o cu m e n ts

\R e vi t

L o ca l M o d e ls \M e ch a n ic a l ( cr a ig

.li e g ib e l@ ff e

-s e rv .c o m

.r vt

/1

/2

:0

:1

P

M

MH-604

SCHEDULES

03/24/2020 GC KG/CL03/24/2020

ROOM AIR BALANCE SCHEDULE

ROOM

NUMBER ROOM NAME

AIR

HANDLING

UNIT

NUMBER

TERMINAL

UNIT

INDIVIDUAL

ROOM

TEMP

CONTROL

RELATIVE

HUMIDITY

SENSOR FOR

DEHUMIDIFICATI

ON

SUPPLY RETURN OR EXHAUST

ROOM AIR

FLOW

(CV/VAV)

ROOM AIR

BALANCE

NET INFILTRATION NET EXFILTRATION

REMARKS

ROOM AIR FLOW

# OF AIR

DEVICES

AIR DEVICE

MARK

SUPPLY

FAN

RETURN OR

EXHAUST (R/E)

ROOM AIR FLOW

# OF AIR

DEVICES

AIR DEVICE

MARK

RETURN OR

EXHAUST FAN CFM L/S CFM L/SCFM L/S CFM L/S

B129B OFFICE (E) AC-3 (E) VAV-29 YES NO 175 83 1 SD-2 (E) 1-SF3 E 175 83 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

B129C OFFICE (E) AC-3 (E) VAV-30 YES NO 100 47 1 SD-1 (E) 1-SF3 E 100 47 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

B129D CLOSET (E) AC-3 (E) VAV-31 NO NO 0 0 N/A N/A (E) 1-SF3 N/A 0 0 N/A N/A N/A CV (0) 0 0 0 0

B129L STUDENTS (E) AC-3 (E) VAV-31 NO NO 0 0 N/A N/A (E) 1-SF3 N/A 0 0 N/A N/A N/A VAV (0) 0 0 0 0

B129K PANTRY (E) AC-3 (E) VAV-31 NO NO 0 0 N/A N/A (E) 1-SF3 N/A 0 0 N/A N/A N/A CV (0) 0 0 0 0

B129 CORRIDOR (E) AC-3 (E) VAV-31 YES NO 300 142 2 SD-2 (E) 1-SF3 N/A 0 0 N/A N/A N/A VAV (+) N/A N/A 300 142

B129A CLOSET (E) AC-3 (E) VAV-31 NO NO 0 0 N/A N/A (E) 1-SF3 N/A 0 0 N/A N/A N/A CV (0) 0 0 0 0

B129E OFFICE (E) AC-3 (E) VAV-30 YES NO 100 47 1 SD-1 (E) 1-SF3 E 100 47 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

B129F OFFICE (E) AC-3 (E) VAV-32 YES NO 150 71 1 SD-2 (E) 1-SF3 E 150 71 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

B129G OFFICE (E) AC-3 (E) VAV-33 YES NO 150 71 1 SD-2 (E) 1-SF3 E 150 71 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

B129H OFFICE (E) AC-3 (E) VAV-34 YES NO 175 83 1 SD-2 (E) 1-SF3 E 175 83 1 EG-1 (E) 3-EF3 CV (0) 0 0 0 0

B129J SHARED OFFICE (E) AC-3 (E) VAV-35 YES NO 150 71 1 SD-2 (E) 1-SF3 E 150 71 1 EG-1 (E) 3-EF3 VAV (0) 0 0 0 0

A132A TOILET RTU-14 CAV-1 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A132 PRIVATE RTU-14 CAV-1 YES NO 140 66 1 SD-2 SF-14 R 65 31 1 RG-2 RF-14 CV (+) N/A N/A 75 35

A131 PRIVATE RTU-14 CAV-2 YES NO 140 66 1 SD-2 SF-14 R 65 31 1 RG-2 RF-14 CV (+) N/A N/A 75 35

A131A TOILET RTU-14 CAV-2 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A130A TOILET RTU-14 CAV-3 NO NO 0 0 N/A N/A SF-14 E 95 45 1 EG-1 EF-MH CV (-) 95 45 N/A N/A

A130 PRIVATE RTU-14 CAV-3 YES NO 120 57 1 SD-1 SF-14 R 25 12 1 RG-2 RF-14 CV (+) N/A N/A 95 45

A129A TOILET RTU-14 CAV-4 NO NO 0 0 N/A N/A SF-14 E 105 50 1 EG-1 EF-MH CV (-) 105 50 N/A N/A

A129 SEMI-PRIVATE RTU-14 CAV-4 YES NO 205 97 2 SD-1 SF-14 R 100 47 1 RG-6 RF-14 CV (+) N/A N/A 105 50

A128 SEMI-PRIVATE RTU-14 CAV-5 YES NO 200 94 2 SD-1 SF-14 R 95 45 1 RG-4 RF-14 CV (+) N/A N/A 105 50

A128A TOILET RTU-14 CAV-5 NO NO 0 0 N/A N/A SF-14 E 105 50 1 EG-1 EF-MH CV (-) 105 50 N/A N/A

A127 PRIVATE RTU-14 CAV-6 YES NO 145 68 1 SD-2 SF-14 R 70 33 1 RG-2 RF-14 CV (+) N/A N/A 75 35

A127A TOILET RTU-14 CAV-6 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A126 PRIVATE RTU-14 CAV-7 YES NO 175 83 1 SD-2 SF-14 R 100 47 1 RG-6 RF-14 CV (+) N/A N/A 75 35

A126A TOILET RTU-14 CAV-7 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A125 DAY/DINING ROOM RTU-14 CAV-8 YES YES 800 378 3 SD-3 SF-14 R 800 378 2 RG-4 RF-14 CV (0) 0 0 0 0

A124 SEMI-PRIVATE RTU-14 CAV-9 YES NO 255 120 2 SD-1 SF-14 R 180 85 1 RG-4 RF-14 CV (+) N/A N/A 75 35

A124A TOILET RTU-14 CAV-9 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A123 LAUNDRY RTU-14 CAV-10 YES NO 120 57 1 SD-1 SF-14 E 220 104 1 DRYER DRYER CV (-) 100 47 N/A N/A

A122A TOILET RTU-14 CAV-11 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A122 PRIVATE RTU-14 CAV-11 YES NO 145 68 1 SD-2 SF-14 R 70 33 1 RG-6 RF-14 CV (+) N/A N/A 75 35

A121 PRIVATE RTU-14 CAV-12 YES NO 125 59 1 SD-1 SF-14 R 50 24 1 RG-2 RF-14 CV (+) N/A N/A 75 35

A121A TOILET RTU-14 CAV-12 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A120A TOILET RTU-14 CAV-13 NO NO 0 0 N/A N/A SF-14 E 85 40 1 EG-1 EF-MH CV (-) 85 40 N/A N/A

A120 PRIVATE RTU-14 CAV-13 YES NO 135 64 1 SD-2 SF-14 R 50 24 1 RG-2 RF-14 CV (+) N/A N/A 85 40

A115 MULTI-PURPOSE ROOM RTU-14 CAV-14 YES YES 435 205 2 SD-2 SF-14 R 435 205 1 RG-5 RF-14 CV (0) 0 0 0 0

A119 BREAK ROOM RTU-14 CAV-15 YES NO 315 149 2 SD-2 SF-14 E 315 149 1 EG-2 EF-MH CV (0) 0 0 0 0

A116 CORRIDOR RTU-14 CAV-16 YES NO 160 76 2 SD-1 SF-14 R 35 17 1 RG-1 RF-14 CV (+) N/A N/A 125 59

A117 JAN. RTU-14 CAV-16 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 50 24 N/A N/A

A118 STAFF TOILET RTU-14 CAV-16 NO NO 0 0 N/A N/A SF-14 E 85 40 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A111 GROUP ROOM RTU-14 CAV-17 YES YES 225 106 2 SD-1 SF-14 R 125 59 1 RG-4 RF-14 CV (+) N/A N/A 100 47

A105 LAB CLEAN ROOM RTU-14 CAV-18 YES NO 200 94 2 SD-1 SF-14 R 50 24 1 RG-2 RF-14 CV (+) N/A N/A 150 71

A109 CLEAN UTILITY RTU-14 CAV-18 NO NO 50 24 1 SD-1 SF-14 N/A 0 0 N/A N/A N/A CV (+) N/A N/A 50 24

A106 TOILET RTU-14 CAV-18 NO NO 0 0 N/A N/A SF-14 E 75 35 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

A106A ANTEROOM RTU-14 CAV-18 NO NO 35 17 1 SD-1 SF-14 N/A 0 0 N/A N/A N/A CV (+) N/A N/A 35 17

A107 LAB SOILED RTU-14 CAV-30 YES NO 90 42 1 SD-1 SF-14 E 200 94 1 EG-1 EF-MH CV (-) 110 52 N/A N/A

A108 EXAM ROOM RTU-14 CAV-19 YES YES 125 59 1 SD-1 SF-14 R 125 59 1 RG-6 RF-14 CV (0) 0 0 0 0

A137 CONSULT RTU-14 CAV-20 YES NO 60 28 1 SD-1 SF-14 R 60 28 1 RG-2 RF-14 CV (0) 0 0 0 0

A136A SECLUSION ANTEROOM RTU-14 CAV-21 NO NO 40 19 1 SD-1 SF-14 N/A 0 0 N/A N/A N/A CV (+) N/A N/A 40 19

A136B TOILET RTU-14 CAV-21 NO NO 0 0 N/A N/A SF-14 E 80 38 1 EG-1 EF-MH CV (-) 80 38 N/A N/A

A136 SECLUSION ROOM RTU-14 CAV-21 YES YES 80 38 1 SD-1 SF-14 R 50 24 1 RG-1 RF-14 CV (+) N/A N/A 40 19

A133 OFFICE: PROGRAM MGR. RTU-14 CAV-22 YES NO 130 61 1 SD-1 SF-14 R 130 61 1 RG-6 RF-14 CV (0) 0 0 0 0

A134 OFFICE: HEAD NURSE RTU-14 CAV-22 NO NO 55 26 1 SD-1 SF-14 R 55 26 1 RG-2 RF-14 CV (0) 0 0 0 0

A143 GROUP ROOM RTU-14 CAV-23 YES YES 140 66 1 SD-2 SF-14 R 140 66 1 RG-6 RF-14 CV (0) 0 0 0 0

A142 MED ROOM RTU-14 CAV-24 YES NO 155 73 1 SD-2 SF-14 R 155 73 1 RG-6 RF-14 CV (0) 0 0 0 0

A141 STAFF STATION RTU-14 CAV-24 YES YES 410 193 3 SD-2 SF-14 R 410 193 1 RG-5 RF-14 CV (0) 0 0 0 0

A110 SOILED UTILITY RTU-14 CAV-25 NO NO 0 0 N/A N/A SF-14 E 150 71 1 EG-1 EF-MH CV (-) 135 64 N/A N/A

A101 SALLY PORT ENTRY RTU-14 CAV-29 YES NO 170 80 1 SD-2 SF-14 N/A 0 0 N/A N/A N/A CV (+) N/A N/A 170 80

100 CORRIDOR RTU-14 CAV-25 YES NO 730 345 3 SD-3 SF-14 R 555 262 2 RG-4 RF-14 CV (+) N/A N/A 185 87

A113 CLOSET RTU-14 CAV-26 NO NO 0 0 N/A N/A SF-14 N/A 0 0 N/A N/A N/A CV (0) 0 0 0 0

A112 PATIENT TOILET RTU-14 CAV-26 NO NO 0 0 N/A N/A SF-14 E 85 40 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

100 CORRIDOR RTU-14 CAV-26 YES NO 990 467 4 SD-3 SF-14 R 935 441 3 RG-4 RF-14 CV (+) N/A N/A 175 83

AU104 ELECTRICAL RTU-14 CAV-27 YES NO 150 71 N/A N/A SF-14 R 150 71 1 RG-7 RF-14 CV (0) 0 0 0 0

A114 ELEC. RTU-14 VAV-28 YES NO 310 146 N/A N/A SF-14 N/A 310 146 N/A N/A N/A VAV (0) 0 0 0 0

A102 TOILET RTU-14 (E) AC-3 NO NO 0 0 N/A N/A (E) 1-SF3 E 95 45 1 EG-1 EF-MH CV (-) 95 45 N/A N/A

A103 TOILET RTU-14 (E) AC-3 NO NO 0 0 N/A N/A (E) 1-SF3 E 95 45 1 EG-1 EF-MH CV (-) 75 35 N/A N/A

CFM [L/s] BTUH [W] °F [°C] °F [°C] GPM [L/s] FT [Pa] HP [W] LBS

UH-1 RTU-14 RTU-14

VESTIBULE HORIZONTAL 340 [ 160 ] 12600 [ 3700 ] 60 [ 16 ] 180 [ 82 ] 1.3 0.08 0.5 [ 13 ] UH-1 0.017 [ 12 ] 1 120 1750 16 MODINE HC 18 -

NOTES:

1. 7'-6" BOTTOM OF UNIT, OR BASIS OF DESIGN.

EAT EWT POWER

PHASE VOLT RPM MANUFACTURER MODEL NO

2. PROVIDE BASIS OF DESIGN OR EQUAL.

HOT WATER UNIT HEATER SCHEDULE

MARK LOCATION AREA AND/OR

BLDG SERVED TYPE UNIT

AIR FLOW MIN CAPACITY

TEMPERATURES

FLOW WPD CONTROL

SEQUENCE

MOTOR OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

NOTE:

GPM [L/s] FT [kPa] FT [kPa] °F [°C] HP [kW] LBS

P-1 RTU-14 ON

ROOF

FIRST

FLOOR HEATING WATER CLOSED COUPLE

IN-LINE WATER 22 [ 1 ] 26 [ 410 ] 2.8 [ 45 ] 180 [ 82 ] 1 56.3 0.5 0.4 1 110 1750 VARIABLE 22 BELL & GOSSETT 55-45 ----

P-2 RTU-14 ON

ROOF

FIRST

FLOOR HEATING WATER CLOSED COUPLE

IN-LINE WATER 22 [ 1 ] 26 [ 410 ] 2.8 N/A 180 [ 82 ] 1 56.3 0.5 0.4 1 110 1750 VARIABLE 22 BELL & GOSSETT 55-45 ----

PUMP SCHEDULE

1. PROVIDE BASIS OF DESIGN OR EQUAL.

FLUID

FLOW HEAD NPSH AVAILABLE TEMPERATURE

SP GR

NOMINAL POWER

PHASE VOLT MAX

RPM

SPEED

CONTROL MANUFATURER MODEL NO REMARKS

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

SYSTEM AND/OR

SERVICE TYPE

CIRCULATING FLUID

MIN %

EFF

ELECTRICAL MOTOR

OPERATING

WEIGHT

BASIS OF DESIGN

NOTE:

GAL [L] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] PSIG [kPa] PSIG [kPa] GAL [L] GAL [L] IN [mm] IN [mm] LBS

ET-1 RTU-14 ON

ROOF

HEATING

WATER

VERTICAL

DIAPHRAGM 205 [ 780 ] 40 [ 4 ] 180 [ 82 ] 10 [ 69 ] 31 [ 210 ] 125 [ 860 ] 31 [ 210 ] 26.9 [ 100 ] 5.7 [ 22 ] 0.75 [ 19 ] 0.75 [ 19 ] 205 BELL & GOSSETT D-60V -

MIN MAX RELIEF VALVE AT TANK

MANUFATURER MODEL NO

EXPANSION TANK SCHEDULE

1. PROVIDE BASIS OF DESIGN OR EQUAL.

MARK LOCATION

SYSTEM

AND/OR

SERVICE

TYPE

APPROX SYSTEM

VOLUME

SYSTEM TEMPERATURE RANGE INITIAL

PRESSURE IN

TANK

MAX OPERATING

PRESSURE

FILL PRESSURE AT TANK

MIN VOLUME

TANK

MIN BLADDER

VOLUME

PIPE SIZE TO

TANK

MAKE-UP WATER

FILL SIZE

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

NOTE:

GPM [L/s] °F [°C] °F [°C] FT [kPa] PSIG [kPa] PSIG [kPa] Cv SIZE [IN] SIZE[MM] LBS/HR [kg/HR] LBS/HR [kg/HR] LBS

HEX-1 RTU-14 ON

ROOF

FIRST

FLOOR

HEATING

WATER

SHELL &

TUBE 25 [ 2 ] 160 [ 71 ] 180 [ 82 ] 9 [ 27 ] 10 [ 69 ] 8 [ 55 ] 10 1.00 [ 25 ] 257.2 [ 5 ] ST2 3/4 257.2 [ 120 ] 89 BELL & GOSSETT SU-43-2 ----

1. PROVIDE BASIS OF DESIGN OR EQUAL.

STEAM TO WATER HEAT EXCHANGER SCHEDULE

FLOW EWT LWT WPD ENT CONTROL

VALVE

ENT HEAT

EXCHANGER

TRAP #

SIZE

[MM]

INCHES

CAPACITY

MANUFATURER MODEL NO

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

SYSTEM

AND/OR

SERVICE

TYPE

WATER CONDITIONS STEAM PRESSURE

CONTROL VALVE

TRAP

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

NOTE:

IN [mm] GPM [L/s] FT [kPa] LBS

AS-1 RTU-14 ON

ROOF

HEATING

WATER

ENHANCED

AIR

SEPARATOR

1 [ 25 ] 25 [ 2 ] 2 [ 6 ] YES 8.8 BELL & GOSSETT EAS-1 ---

AIR SEPARATOR SCHEDULE

SIZE IN FLOW WPD BUILT-IN

STRAINER

REQ'D

MANUFATURER MODEL NO

1. PROVIDE BASIS OF DESIGN OR EQUAL.

MARK LOCATION

SYSTEM

AND/OR

SERVICE

TYPE

AIR SEPARATOR OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

NOTE:

LBS/HR [kg/HR] PSI [kPa] PSI [kPa] IN [mm] LBS MANUFACTURER MODEL NO

ST3 RTU-14 CSG-1 62 [ 28 ] 1 [ 7 ] 10 [ 69 ] FLOAT AND

THERMOSTATIC .5 [ 13 ] 43 SPIRAX SARCO FTI-15

ST1 TOWER

BUILDING

DRIP TRAP

ASSEMBLY 733 [ 330 ] 1 [ 7 ] 10 [ 69 ] FLOAT AND

THERMOSTATIC .75 [ 19 ] 43 SPIRAX SARCO FTI-15 -

ST2 RTU-14 HEX-1, PHC 733 [ 330 ] 1 [ 7 ] 10 [ 69 ] FLOAT AND

THERMOSTATIC .75 [ 19 ] 43 SPIRAX SARCO FTI-15 -

STEAM TRAP SCHEDULE

1. PROVIDE BASIS OF DESIGN OR EQUAL.

MARK LOCATION

SYSTEM

AND/OR

SERVICE

CAPACITY AT MIN

DIFF PRESS

MIN DIFF

PRESS

MIN INLET

PRESS

TRAP TYPE

TRAP SIZE OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

VAV-28 100 A114 RTU-14 6 [ 150 ] 310 [ 150 ] 170 [ 80 ] 23 NONE 0 - - - - - - - - NONE TITUS DESV 3, 4

CAV-1 100 A132 RTU-14 5 [ 130 ] 140 [ 66 ] 140 [ 66 ] 22 NONE 140 5.3 50.4 180 85 0.5 0.11 1 10 NONE TITUS DESV 1, 3 CAV-2 100 A131 RTU-14 5 [ 130 ] 140 [ 66 ] 140 [ 66 ] 22 NONE 140 5.3 50.4 180 85 0.5 0.11 1 10 NONE TITUS DESV 1, 3 CAV-3 100 A130 RTU-14 5 [ 130 ] 120 [ 57 ] 120 [ 57 ] 20 NONE 120 4.5 50.4 180 85 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-4 100 A129; RP-1 IN A129A RTU-14 6 [ 150 ] 205 [ 97 ] 205 [ 97 ] 19 NONE 205 7.7 50.4 180 85 1.2 0.63 1 10 RADIANT PANEL, RP-1 TITUS DESV 2, 3 CAV-5 100 A128 RTU-14 6 [ 150 ] 200 [ 94 ] 200 [ 94 ] 19 NONE 200 7.5 50.4 180 85 1.1 0.51 1 10 NONE TITUS DESV 2, 3 CAV-6 100 A127 RTU-14 5 [ 130 ] 140 [ 66 ] 140 [ 66 ] 22 NONE 140 5.3 50.4 180 85 0.5 0.11 1 10 NONE TITUS DESV 1, 3 CAV-7 100 A126 RTU-14 6 [ 150 ] 175 [ 83 ] 175 [ 83 ] 18 NONE 175 6.6 50.4 180 85 0.7 0.2 1 10 NONE TITUS DESV 1, 3 CAV-8 A125 A125 RTU-14 9 [ 230 ] 800 [ 380 ] 800 [ 380 ] 28 NONE 800 30 50.4 180 85 1.4 0.19 2 10 NONE TITUS DESV 2, 3 CAV-9 100 A124 RTU-14 6 [ 150 ] 225 [ 110 ] 225 [ 110 ] 20 NONE 225 8.4 50.4 180 85 0.8 0.3 1 12 NONE TITUS DESV 1, 3

CAV-11 100 A122 RTU-14 5 [ 130 ] 145 [ 68 ] 145 [ 68 ] 23 NONE 145 5.7 50.4 180 86.2 0.5 0.14 1 10 NONE TITUS DESV 1, 3 CAV-12 100 A121 RTU-14 5 [ 130 ] 125 [ 59 ] 125 [ 59 ] 20 NONE 125 4.7 50.4 180 85 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-13 100 A120; RP-2 IN A120A RTU-14 5 [ 130 ] 135 [ 64 ] 135 [ 64 ] 11 NONE 135 5.3 50.4 180 86.2 0.5 0.12 1 10 RADIANT PANEL, RP-2 TITUS DESV 1, 3 CAV-14 A115 A115 RTU-14 7 [ 180 ] 435 [ 210 ] 435 [ 210 ] 27 NONE 435 16.3 50.4 180 85 0.6 0.11 2 12 NONE TITUS DESV 1, 3 CAV-15 A119 A119 RTU-14 6 [ 150 ] 315 [ 150 ] 315 [ 150 ] 24 NONE 315 12 50.4 180 85 0.6 0.08 2 10 NONE TITUS DESV 1, 3 CAV-16 A116 A116 RTU-14 6 [ 150 ] 160 [ 76 ] 160 [ 76 ] 17 NONE 160 6.5 50.4 180 87.4 0.8 0.28 1 10 NONE TITUS DESV 1, 3 CAV-17 100 A111 RTU-14 6 [ 150 ] 225 [ 110 ] 225 [ 110 ] 20 NONE 225 6.7 50.4 180 78 0.5 0.14 1 10 NONE TITUS DESV 1, 3 CAV-18 100 A105, A106A, A109 RTU-14 6 [ 150 ] 285 [ 130 ] 285 [ 130 ] 23 NONE 285 8.5 50.4 180 78 0.9 0.38 1 10 NONE TITUS DESV 1, 3 CAV-19 100 A108 RTU-14 5 [ 130 ] 125 [ 59 ] 125 [ 59 ] 20 NONE 125 4.6 50.4 180 84 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-20 100 A137 RTU-14 4 [ 100 ] 60 [ 28 ] 60 [ 28 ] 18 NONE 60 3.3 50.4 180 101 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-21 100 A136, A136A RTU-14 5 [ 130 ] 120 [ 57 ] 120 [ 57 ] 20 NONE 120 4.5 50.4 180 84.9 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-22 100 A133, A134 RTU-14 6 [ 150 ] 185 [ 87 ] 185 [ 87 ] 18 NONE 185 5.5 50.4 180 78 0.5 0.09 1 10 NONE TITUS DESV 1, 3 CAV-23 100 A143 RTU-14 5 [ 130 ] 140 [ 66 ] 140 [ 66 ] 24 NONE 140 4.8 50.4 180 81.7 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-24 A141 A142 RTU-14 8 [ 200 ] 565 [ 270 ] 565 [ 270 ] 29 NONE 565 16.9 50.4 180 78 0.7 0.12 2 10 NONE TITUS DESV 1, 3 CAV-25 100 100-2 RTU-14 9 [ 230 ] 730 [ 340 ] 730 [ 340 ] 27 NONE 730 23 50.4 180 79.5 0.9 0.1 2 10 NONE TITUS DESV 1, 3 CAV-26 100 100-1 RTU-14 10 [ 250 ] 990 [ 470 ] 990 [ 470 ] 31 NONE 990 29.6 50.4 180 78 1.2 0.16 2 10 NONE TITUS DESV 1, 3 CAV-29 100 A101 RTU-14 6 [ 150 ] 170 [ 80 ] 170 [ 80 ] 19 NONE 170 5.1 50.4 180 78 0.5 0.08 1 10 NONE TITUS DESV 1, 3 CAV-30 A113 A107 RTU-14 5 [ 130 ] 90 [ 42 ] 90 [ 42 ] 19 NONE 90 4 50.4 180 91.2 0.5 0.08 1 10 NONE TITUS DESV 1, 3

NOTES:

1. PROVIDE 2-WAY CHARACTERIZED CONTROL VALVE WITH A MAX PRESSURE DROP OF 5.0 PSI. PROVIDE FAIL IN PLACE ACTUATOR.

2. PROVIDE 3-WAY MIXING TYPE CHARACTERIZED CONTROL VALVE WITH MAX PRESSURE DROP OF 5.0 PSI. PROVIDE FAIL IN PLACE ACTUATOR.

3. PROVIDE WITH FIBER FREE LINER.

4. COOLING ONLY BOX.

5. PROVIDE BASIS OF DESIGN OR EQUAL.

SINGLE DUCT AIR TERMINAL UNIT SCHEDULE

MARK LOCATION AREA AND/OR ROOM

SERVED

SYSTEM AIR

HANDLING

DUCT INLET SIZE

AIR FLOW

DISCHARGE

NC LEVELS

ADDITIONAL SOUND

ATTUNATION

REQUIRED

CONTROL

TYPE

CONTROL

SEQUENCE

HOT WATER REHEAT COIL PERIMETER

SUPPLEMENTAL HEAT

LINK

BASIS OF DESIGN

REMARKSMAX MIN

MANUFATURER MODEL NO

IN [mm] CFM [L/s] CFM [L/s] CFM MBH EAT EWT LAT GPM WPD ROWS FPI

VAV-10 100 A123 RTU-14 8 [ 200 ] 120 [ 57 ] 40 [ 19 ] 31 NONE 120 4.5 50.4 180 84.5 0.5 0.08 1 10 NONE TITUS DESV 1, 3 VAV-27 100 AU104 RTU-14 5 [ 130 ] 150 [ 71 ] 82 [ 39 ] 25 NONE 0 - - - - - - - - NONE TITUS DESV 3, 4

1. BASIS OF DESIGN: RUSKIN, MODEL FSD60LP. PROVIDE BASIS OF DESIGN OR EQUAL.

FSD-1 A107 2-SF4 AC-4 6 [ 150 ] 3 [ 750 ] 1.5-HR FSD IN A 2-HR WALL

FSD-2 A107 2-SF4 AC-4 6 [ 150 ] 3 [ 750 ] 1.5-HR FSD IN A 2-HR WALL

FSD-3 A107 4-SF4 AC-4 10x6 [250x150] 1 [ 250 ] 1.5-HR FSD IN A 2-HR WALL

FSD-4 A101 2-SF4 AC-4 10 [ 250 ] 3 [ 750 ] 1.5-HR FSD IN A 2-HR WALL

FSD-5 A101 2-SF4 AC-4 10 [ 250 ] 3 [ 750 ] 1.5-HR FSD IN A 2-HR WALL

FSD-6 A107 EF-MH RTU-14 8 [ 200 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-7 A105 SF-14 RTU-14 8 [ 200 ] 1 [ 250 ] 1.5-HR FSD IN A 2-HR WALL

FSD-8 A105 SF-14 OR EF-14 RTU-14 6x6 [150x150] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-9 A107 SF-14 RTU-14 6 [ 150 ] 1 [ 250 ] 1.5-HR FSD IN A 2-HR WALL

FSD-10 A116 2-SF4 AC-4 10 [ 250 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-11 A116 2-SF4 AC-4 10 [ 250 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-12 A116 SF-14 RTU-14 40x16 [1000x400] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-13 A116 SF-14 RTU-14 12 [ 300 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-14 A114 - - 8x8 [200x200] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-15 A114 4-SF4 AC-4 8x6 [200x150] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-16 A116 - - 8x8 [8x8] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-17 A116 - - 12x12 [300x300] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-18 A119 4-SF4 AC-4 6 [ 150 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

FSD-19 A119 - - 8 [ 200 ] 2 [ 500 ] 1.5-HR FSD IN A 2-HR WALL

NOTE:

COMBINATION FIRE/SMOKE DAMPER SCHEDULE

MARK LOCATION FAN SYSTEM

SYSTEM

AND/OR

SERVICE

DUCT SIZE

DUCT

PRESSURE

CLASS REMARKS

IN [mm] IN WG [Pa]

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

596A4-18-107RENOVATE SPACE FOR

NEW MENTAL HEALTH UNIT

LEXINGTON, KY, TROY BOWLING

F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45215 513-522-0956

JRA Architects 3225 Summit Square Place Lexington KY 40509 859-252-6781

C U se rs

\c ra ig \D o cu m e n ts

\R e vi t

L o ca l M o d e ls \M e ch a n ic a l ( cr a ig

.li e g ib e l@ ff e

-s e rv .c o m

.r vt

/1

/2

:0

:2

P

M

MH-605

SCHEDULES

03/24/2020 GC KG/CL03/24/2020Revisions: Date:

NOTE:

GPM [L/s] °F [°C] LBS/HR kg/HR PSIG [kPa] PSIG [kPa] PSIG [kPa] Cv SIZE [IN] SIZE[MM] LBS/HR [kg/HR] LBS/HR [kg/HR] LBS

CSG-1 RTU-14 MENTAL

HEALTH HUMIDIFICATION STEAM-

STEAM

BUILDING

CITY WATER 0.12 [ 0. ] 50 [ 10 ] 62 [ 28 ] 10 [ 69 ] 10 [ 69 ] 5 [ 35 ] 3.5 0.50 [ 13 ] 62 [ 28 ] ST3 2 0.75 62 [ 28 ] 175 DRISTEEM STS-25 -

FLOW EWT ENT CONTROL

VALVE

ENT HEAT

EXCHANGER TRAP # # TRAPS SIZE [MM]

INCHES

CAPACITY EACH

MANUFATURER MODEL NO

CLEAN STEAM GENERATOR SCHEDULE

1. PROVIDE BASIS OF DESIGN OR EQUAL.

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

SYSTEM AND/OR

SERVICE TYPE SOURCE OF

MAKEUP

WATER CONDITIONS

PRODUCED STEAM

FLOW

PRODUCED

STEAM PRESS

STEAM PRESSURE

CONTROL VALVE

TRAP

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

NOTE:

CFM [L/s] °F [°C] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR] LBS

H-1 RTU-14 RTU-14 UNIT-MOUNTED

DISPERSION TUBE 7760 [ 3700 ] 1 50.4 [ 10 ] 31.9 -0.056 70 41.1 [ 5 ] CSG-1 10 [ 69 ] 3 [ 21 ] 62 [ 28 ] C-1 ST-3 62 [ 28 ] 59 DRISTEEM ULTRA-SORB -

STEAM HUMIDIFER SCHEDULE

1. PROVIDE BASIS OF DESIGN OR EQUAL.

Db DEWPOINT

%RH

DEWPOINT PRESS ENT VALVE PRESS ENT

HEATER FLOW

MARK

CAPACITY

MANUFATURER MODEL NO

MARK LOCATION

SYSTEM

AND/OR

SEVICE

HUMIDIFIER TYPE

AIR FLOW # OF

MANIFOLDS

EAT LAT

SOURCE

STEAM

CONTROL

TYPE

TRAP

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

6. PROVIDE BASIS OF DESIGN OR EQUAL.

CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] °F [°C] HP [W] TSP ESP CONTROL FLA HP [W] TSP ESP CONTROL FLA PHASE VOLT

RTU-14 ROOF MENTAL HEALTH 7760 [ 3700 ] 2490 [ 1200 ] 3.2 [ 800 ] 334.2 [ 98 ] 205.7 [ 60 ] 78.9 [ 26 ] 67.8 [ 20 ] 87.2 [ 31 ] 77.3 [ 25 ] 7.5 [ 5600 ] 3.6 1.8 VFD 24 5 [ 3700 ] 2 1.4 VFD 15.2 3 460 17905, SEE NOTE 3 -

4. SCHEDULED SUPPLY AND RETURN FAN HP [W] DATA PERTAINS TO EACH INDIVIDUAL FAN. ALL OTHER DATA PERTAINS TO THE TWO SUPPLY AND TWO RETURN FANS IN ARRAY. SEE RTU-14 DETAIL 4 ON MH-503.

5. ROOF STRUCTURAL LIMIT IS 60 PSF WHICH IS INCLUSIVE OF ALL LOADS.

MIN TOTAL

CAPACITY

MIN SENS

CAPACITY

EAT OAT

SUPPLY FAN RETURN FAN UNIT POWER

CONNECTIONDb Wb Db Wb

2. PROVIDE ALL VARIABLE SPEED MOTOR CONTROLLERS WITH A BYPASS CONTACTOR PER 23 05 11, COMMON WORK RESULTS, 2.8, C.

3. RTU-14 WEIGHT INCLUDES A 14,000 POUND RTU WITH ALUMINUM CASING AND A 1,840 POUND CURB. ALL MECHANICAL EQUIPMENT AND PIPE INSIDE RTU ADDS 2,065 POUNDS SO THE TOTAL WEIGHT OF RTU, CURB, AND EQUIPMENT IS 17,905 POUNDS.

NOTES:

1. PROVIDE 1 FACTORY MOUNTED DISCONNECT SWITCH FOR THE 2 VFDS SERVING THE 2 SUPPLY FANS IN ARRAY AND 1 FACTORY MOUNTED DISCONNECT FOR THE 2 VFDS SERVING THE 2 RETURN FANS IN ARRAY.

RTU-14 CHILLED WATER ROOFTOP UNIT SCHEDULE

MARK LOCATION AREA AND/OR BLDG

SERVED

TOTAL SUPPLY AIR

FLOW

MIN. OUTSIDE AIR

FLOW

TOTAL EXT

STATIC

PRESSURE

COOLING CAPACITY ELECTRICAL DATA

TOTAL OPERATIONAL

WEIGHT (LBS.) REMARKS

RTU-14 ROOF MENTAL

HEALTH ROOFTOP VAV/RH 7760 [ 3700 ] 2490 [ 1200 ] 5270 [ 2500 ] SF-14 RF-14 RTU-14-FF RTU-14-CC RTU-14-PH H-1

UNIT: 14000

EQUIP: 2065

CURB: 1840

TOTAL: 17905

TRANE

CLIMATE

CHANGER

CUSTOM

NOTES:

1. PROVIDE ALL VARIABLE SPEED MOTOR CONTROLLERS WITH A BYPASS CONTACTOR PER 23 05 11, COMMON WORK RESULTS, 2.8, C.

2. SEE ADDITIONAL SCHEDULES FOR PERFORMANCE OF COMPONENTS WITHIN THE AIR HANDLING UNIT.

3. OPERATING WEIGHT IS WHAT IS EXPECTED FROM BASIS OF DESIGN MANUFACTURER. PROVIDE BASIS OF DESIGN OR EQUAL.

4. RTU MANUFACTURER SHALL PROVIDE LOUVERS (EQUAL TO GREENHECK MODEL ESD-635) AT INTAKES THAT PREVENT WATER PENETRATION AND SAME LOUVERS AT OUTLETS, AND ALL LOUVERS SHALL HAVE ALUMINUM BIRDSCREENS.

SUPPLY MIN OA RETURN

MANUFATURER MODEL NO

CFM [L/s] CFM [L/s] CFM [L/s] LBS

RTU-14 ROOFTOP AIR HANDLING UNIT SCHEDULE

MARK LOCATION AREA AND/OR

BLDG SERVED TYPE AIR FLOW

AIR FLOW

SUPPLY FAN

MARK

RETURN FAN

MARK

FINAL FILTER

MARK

COOLING

COIL MARK

STEAM

PREHEAT

COIL MARK

HUMIDIFIER

MARK

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M] LBS

RTU-14-CC RTU-14 MENTAL HEALTH RTU-14 7760 [ 3700 ] 414 [ 2 ] 0.5 [ 130 ] 78.9 [ 26 ] 67.8 [ 20 ] 55 [ 13 ] 54 [ 12 ] 334.2 [ 98 ] 205.7 [ 60 ] 56 [ 4 ] 44 [ 7 ] 56 [ 13 ] 1.4 [ ] 709 TRANE CUSTOM D5DB45060G0FB080HABB0A******* -----

1. PROVIDE BASIS OF DESIGN OR EQUAL.

Db Wb Db Wb FLOW EWT LWT WPD

MANUFATURER MODEL NO

RTU-14 CHILLED WATER COOLING COIL SCHEDULE

NOTE:

MARK LOCATION AREA AND/OR BLDG

SERVED

SYSTEM

AND/OR

SERVICE

AIR FLOW MAX FACE

VELOCITY APD

EAT LAT

TOTAL CAPACITY SENSIBLE

CAPACITY

CHILLED WATER

OPERATIN

G WEIGHT

BASIS OF DESIGN

REMARKS

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] °F [°C] MBH [kW] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] Cv SIZE [IN] SIZE [MM] LBS/HR [kg/HR] LBS/HR [kg/HR] LBS

RTU-14-PH RTU-14 MENTAL

HEALTH RTU-14 EMERGENCY

PREHEAT 7760 [ 3700 ] 414 [ 2 ] 0.038 [ 10 ] 1.3 [ -17 ] 1.3 [ -17 ] 54 [ 12 ] 450.1 [ 1500 ] 10 [ 69 ] 8 [ 55 ] 473.9 [ 220 ] 10 1.00 [ 25 ] 473.9 [ 5 ] ST2 .75 [ 19 ] 473.9 [ 220 ] 109 HEATCRAFT/MODINE

(WITH TRANE CUSTOM RTU) 5JA0701A ---

OAT EAT LAT PRESS ENT VALVE ENT COIL FLOW

MARK

SIZE

INCHES

SIZE

[MM]

CAPACITY

MANUFATURER MODEL NO

NOTE:

1. PROVIDE BASIS OF DESIGN OR EQUAL.

STEAM PREHEAT COIL SCHEDULE

MARK LOCATION AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE

APPLICATION

AIR FLOW MAX FACE

VELOCITY APD

TEMPERATURES

TOTAL MIN

CAPACITY

STEAM

CONTROL VALVE

TRAP

OPERATING

WEIGHT

BASIS OF DESIGN

REMARKS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

596A4-18-107RENOVATE SPACE FOR

NEW MENTAL HEALTH UNIT

LEXINGTON, KY, TROY BOWLING

F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45215 513-522-0956

JRA Architects 3225 Summit Square Place Lexington KY 40509 859-252-6781

C U se rs

\c ra ig \D o cu m e n ts

\R e vi t

L o ca l M o d e ls \M e ch a n ic a l ( cr a ig

.li e g ib e l@ ff e

-s e rv .c o m

.r vt

/1

/2

:0

:2

P

M

MH-606

SCHEDULES

03/24/2020 GC KG/CL03/24/2020Revisions: Date:

NMLKJHGFEDCBBBAAA

3"ø LPS

2"ø LPC

2"ø CWR

2"ø CWS

5 6 2"ø LPC

3"ø LPS

7' - 0"

7' - 0 1/16"

GUIDE

GUIDE

GUIDE

GUIDE

7' - 0"

6' - 11 15/16"

ANCHOR

ANCHOR

(E) 2"ø LPC

A. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.

B. TIE-IN OUTAGE WORK SHALL BE COORDINATED WITH COR DURING OFF PEAK SEASONS.

C. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, APPLICABLE CODES, REGULATIONS, AND OWNER STANDARDS.

D. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND PIPING INSULATION IS APPLIED.

E. LOCATED ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM

AS RECOMMENDED BY THE MANUFACTURER FOR OPTIMUM PERFORMANCE.

F. THE LOCATIONS OF ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. THE EXACT

LOCATIONS NECESSARY TO SECURE THE BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL OF THE OWNER AND

ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

G. LOCATE BALANCE VALVES SO THEY CAN BE ACCESSED THROUGH THE CEILING TILE OR PROVIDE ACCESS PANEL(S).

H. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCE AS RECOMMENDED BY CODE AND MANUFACTURERS.

I. GENERAL CONTRACTOR SHALL PROVIDE ALL ACCESS PANELS IN NON-ACCESSIBLE SUSPENDED CEILINGS AND WALLS FOR ACCESS TO EQUIPMENT SUCH AS VAV BOXES, VALVES, DAMPERS, AND CONTROLS, ETC. SEE MECHANICAL PLANS FOR COORDINATED DAMPER LOCATIONS. IF MORE ACCESS PANELS ARE REQUIRED, COORDINATE LOCATIONS WITH OWNER. ALL CEILING PANELS SHALL BE 24”X24”. PROVIDE PER 08 31 13 ACCESS DOORS AND FRAMES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

596A4-18-107RENOVATE SPACE FOR

NEW MENTAL HEALTH UNIT

LEXINGTON, KY, TROY BOWLING

F F E I n c Engineering and Technical Services 110 Boggs Lane, Suite 170 Cincinnati, OH 45215 513-522-0956

JRA Architects 3225 Summit Square Place Lexington KY 40509 859-252-6781

C U se rs

\c ra ig \D o cu m e n ts

\R e vi t

L o ca l M o d e ls \M e ch a n ic a l ( cr a ig

.li e g ib e l@ ff e

-s e rv .c o m

.r vt

/1

/2

:0

:3

P

M

MP-100

PIPING NEW WORK PLAN - CRAWL

SPACE

03/24/2020 GC KG/CL03/24/2020

1/8" = 1'-0"

1 PIPING NEW WORK PLAN - CRAWL SPACE

DRAWING NOTES:

1 3" LPS UP TO FIRST FLOOR. ROUTE IN EXISTING SHAFT FROM CRAWL SPACE UP TO FIRST FLOOR. PROVIDE END OF

MAIN DRIP LEG AND CONDENSATE TRAP AT BOTTOM OF RISER.

2 2" LPC DN FROM FIRST FLOOR. ROUTE IN EXISTING SHAFT FROM FIRST FLOOR TO CRAWL SPACE.

3 2" CWS UP TO AND 2" CWR DN FROM FIRST FLOOR. ROUTE IN EXISTING CHASE FROM CRAWL SPACE UP TO FIRST

FLOOR.

4 CONNECT 2" CWS AND 2" CWR TO EXISTING MAIN IN CRAWL SPACE. PROVIDE ISOLATION VALVES AND DRAINS AT MAIN

TIE-IN POINTS.

5 CONNECT 2" LPS TO TOP OF…