This asbestos survey report documents the results of testing conducted at the Lexington Veterans Affairs Medical Center in Lexington, Kentucky. The survey identified asbestos-containing materials located within the approximately 12,500 square foot renovation project area, including joint compound within drywall throughout the space excluding one suite. The report provides the material descriptions, locations, and estimated quantities of asbestos present and will be relied upon for regulatory compliance with EPA asbestos regulations prior to the planned renovation by the Department of Veterans Affairs to create a new mental health unit under Solicitation Number 36C24920R0075.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey VA Project: Renovate Space for New Mental Health Unit
VA Project No. 596A4-18-107 Lexington VA Medical Center
Cooper Division 1101 Veterans Affairs Medical Center
Lexington, KY June 17, 2019
Terracon Project No. N1187353
Prepared for:
FFE, Inc.
438 Springfield Pike Suite C Cincinnati, OH 45215
Prepared by:
Terracon Consultants, Inc.
611 Lunken Park Drive Cincinnati, OH 45226
Terracon Consul tants, Inc. 611 Lunken Park Dr ive Cincinnat i , OH 45226-1813 P (513) 321-5816 F (513) 321-0294 terracon.com
June 17, 2019
FFE, Inc.
438 Springfield Pike, Suite C Cincinnati, Ohio 45215
Attn: Mr. Clint Weekley, PE, CBCP, LEED AP President T: (513) 522-0956 E: clint.weekley@ffe-serv.com
Re: Asbestos Survey Report VA Project: Renovate Space for New Mental Health Unit VA Project No. 596A4-18-107 Department of Veterans Affairs Medical Center Cooper Division 1101 Veterans Drive Lexington, KY 40502-2236 Terracon Project No. N1187353
Dear Mr. Weekley:
Terracon is pleased to submit this report which presents the results of our asbestos survey with respect to an approximately 12,500 square foot space on the first floor of the tower building, which is to be renovated, at the Lexington Veterans Affairs Medical Center (VAMC) - Cooper Division in Lexington, Kentucky. The asbestos survey was conducted under the scope of work found under proposal number PN1187353, signed September 20, 2018.
Terracon appreciates the opportunity to provide services to FEE, Inc (Client). If we can provide additional environmental, occupational health, or safety-related services, please contact us at
(513) 321-5816.
Sincerely, Terracon Consultants, Inc.
Joshua Vogel Joseph A. Tussey, CHMM Project Manager Group Manager
Renovate Space for New Mental Health Unit ■ Lexington VAMC - Cooper Division June 17, 2019 ■ Terracon Project No. N1187353
TABLE OF CONTENTS
EXECUTIVE SUMMARY .......................................................................................................................... i
1.0 INTRODUCTION
1.1 Project Objective
1.2 Reliance
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Visual Assessment
3.2 Physical Assessment
3.3 Sample Collection
3.4 Sample Analysis
4.0 REGULATORY OVERVIEW
5.0 FINDINGS AND RECOMMENDATIONS
6.0 LIMITATIONS/GENERAL COMMENTS
APPENDIX A IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)
APPENDIX B ASBESTOS SURVEY SAMPLE LOCATION SUMMARY
APPENDIX C ASBESTOS ANALYTICAL LABORATORY DATA
APPENDIX D LICENSES AND CERTIFICATIONS
APPENDIX E SAMPLE LOCATION DRAWING
APPENDIX F PHOTO LOG
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable i
EXECUTIVE SUMMARY
Terracon Consultants, Inc. (Terracon) conducted an asbestos survey with respect to an approximately 12,500 square foot space on the first floor of the tower building, which is to be renovated, at the Lexington Veterans Affairs Medical Center (VAMC) - Cooper Division in Lexington, Kentucky. We understand that this survey was requested prior to renovation for the purpose of compliance with the EPA National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M). The survey included identifying and sampling suspect asbestos-containing materials (ACM) within the boundaries of the renovation project area, and providing information regarding the identity, location, condition, and approximate quantities of ACM in interior building components. The survey was performed on April 11, 2019 and June 6, 2019 by EPA-accredited and Commonwealth of Kentucky Department of Environmental Protection, Division of Air Quality licensed Asbestos Management Planners in general accordance with our proposal, PN1187353, dated September 20, 2018, and the sampling protocols established in United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E 763, known as the Asbestos Hazard Emergency Response Act (AHERA). Terracon collected a total of 118 bulk samples from 36 homogeneous areas of suspect ACM.
Specific to the subject renovation project area and based on the analytical results of the collected samples, the materials listed below were identified to contain asbestos.
Material Description Material Location(s) % and Type Asbestos
Estimated Quantity
Joint Compound within the Drywall System
Drywall Walls Throughout Project Area
(Excludes B129 Suite)
1.3% Chrysotile by Point Count (PC) in the Joint
Compound Layer; Trace (<1%) by PC in Composite Samples of Gypsum and Joint Compound Analyzed Together
31,000 Square Feet (SF)
Yellow Mastic Beneath 2’ x 2’ Blue Carpet Squares
North Wing of Project Area
0.25% Chrysotile PC 2,500 SF
White Mastic on Fiberglass Duct Insulation
On Fiberglass Insulation Applied Over Duct Work Throughout Project Area
Above Ceilings (Including B129 Suite)
4.8% Chrysotile PC 450 SF
9” x 9” White Floor Tile with Black Mastic and Non-
Asbestos-Containing Brown Mastic and Grey Floor Leveler
Middle Hallway - West End of Project Area and
A140
Floor Tile: 1.3% Chrysotile PC Mastic: 2.1% Chrysotile PC 2,000 SF
Tan/ Black Mastic under Non- Asbestos-Containing
12” x 12” Gray Floor Tile
Main Entrance Lobby of Project Area
1.1% Chrysotile PC 900 SF
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable ii
Material Description Material Location(s) % and Type Asbestos
Estimated Quantity
Interior White Window Caulking At Interior Window Sills Throughout Project Area 1.3% Chrysotile PC 19 SF (26
Windows)
Gray Mortar Behind 4’ x 4’ Yellow Ceramic Wall Tile
Men’s and Women’s Restrooms: A105a, A106, A107, and A141 in Project Area
1.2% Chrysotile PC 800 SF
White Caulking Around Sinks
Men’s and Women’s Restrooms: A105a, A106, A107, and A141 in Project Area
0.5% Chrysotile PC 7 SF (7 Sinks)
9” x 9” Floor Tile with Brown Flashes and Black Mastic
A135 and A136 in Project Area
Floor Tile 1.2% Chrysotile PC Mastic: 4.0% Chrysotile PC 400 SF
Appendix A includes a listing of the above-identified ACMs with conditions and NESHAP material category. A summary of materials sampled during this survey is included in Appendix B; a drawing with approximate sample locations is included in Appendix E; laboratory analytical reports are included as Appendix C; and a photo log with examples of the identified ACM is included as Appendix F.
If the above-identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state EPA regulations, Occupational Safety and Health Administration (OSHA) regulations, and per VA project specifications.
Responsive ■ Resourceful ■ Reliable 1
ASBESTOS SURVEY
VA Project: Renovate Space for New Mental Health Unit
VA Project No. 596A4-18-107 Lexington VA Medical Center
Cooper Division Lexington, Kentucky 40502
Terracon Project No. N1187353 June 17, 2019
1.0 INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an asbestos survey with respect to an approximately 12,500 square foot space on the first floor of the tower building, which is to be renovated, at the Lexington Veterans Affairs Medical Center (VAMC) - Cooper Division in Lexington, Kentucky. The survey was conducted at the site on April 11 and June 6, 2019, by EPA-accredited and Commonwealth of Kentucky Department of Environmental Protection Division of Air Quality certified Asbestos Management Planners in general accordance with our proposal number PN1187353, dated September 20, 2018. The survey involved identifying accessible suspect asbestos-containing materials (ACM), and the collection of samples from those suspect materials using protocols established in United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763 Subpart E, known as the Asbestos Hazard Emergency Response Act (AHERA). Collected samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM). Terracon collected a total of 118 bulk samples from 36 homogeneous areas of suspect ACM. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas.
1.1 Project Objective
We understand that this survey was requested for the purpose of a future planned renovation pertaining to an approximately 12,500 square foot first floor area of the Lexington VAMC - Cooper Division at the above-referenced address. Please note that asbestos surveys are required prior to renovation or demolition to satisfy requirements of the USEPA 40 CFR Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (as well as the state NESHAP equivalent).
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable 2
1.2 Reliance
This report is for the exclusive use of FFE, Inc. (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and FFE, Inc. Reliance on this report by FFE, Inc. and all authorized parties will be subject to the terms, conditions, and limitations stated in this report, and the agreement between Terracon and FFE, Inc. The limitations of liability defined in the agreement between Terracon and FFE, Inc. is the aggregate limit of Terracon’s liability to FFE, Inc.
2.0 BUILDING DESCRIPTION
The survey was limited to an approximately 12,500 square foot area on the first floor of the Lexington VAMC - Cooper Division. See Appendix E for a drawing which indicates the subject area surveyed.
3.0 FIELD ACTIVITIES
The survey was conducted by Mr. Joshua Vogel and Mr. Lemuel Weyer, EPA-accredited and Commonwealth of Kentucky Asbestos Management Planners. Copies of Mr. Vogel’s and Mr.
Weyer’s Kentucky Asbestos Management Planner credentials are attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, known as AHERA. A summary of survey activities is provided below.
3.1 Visual Assessment
Survey activities were initiated with visual observation of the accessible interior areas of the subject space to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.
3.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable 3
3.3 Sample Collection
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.
Terracon collected a total of 118 bulk samples from 36 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix B.
3.4 Sample Analysis
Bulk samples were submitted under chain of custody to International Asbestos Testing Laboratories (IATL) of Mount Laurel, New Jersey for analysis PLM with dispersion staining techniques per USEPA methodology 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. When applicable for samples determined by PLM to have a low asbestos content (<10%), the additional point count (PC) method was utilized. IATL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 101165-0.
4.0 REGULATORY OVERVIEW
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).
The asbestos NESHAP regulation classifies material subject to demolition or renovation as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable 4 other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally include (but is not limited to) cementitious material such as cement pipes, cement siding (Transite™), cement panels, glazing, mortar, and grouts.
In Kentucky, the federal NESHAP regulation has been delegated to the state EPA and is administered under 401 Kentucky Administrative Regulation (KAR) 58:025. The Kentucky Department for Environmental Protection (DEP), Division for Air Quality (DAQ) is responsible for administering and enforcing the federal and state NESHAP regulations as well as administering accreditations for asbestos professionals. NESHAP pre-renovation and pre-demolition notifications (are sent to the regional state EPA office). NESHAP pre-renovation (where >160 SF / 260 LF of friable ACM is removed) and pre-demolition notifications must be submitted to the DAQ office 10 business days prior to project commencement. The Kentucky local regional DAQ office for the subject site is the Frankfort office; 300 Sower Blvd Frankfort, KY 40601; telephone (502-564-3358); contact Ms. Natasha Parker (Natasha.Parker@ky.gov).
The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The USOSHA standard requires that employee exposure to airborne asbestos must not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed
1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as USOSHA’s asbestos permissible exposure limits (PELs). The USOSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.
5.0 FINDINGS AND RECOMMENDATIONS
Specific to the subject renovation project area and based on the analytical results of the collected samples, the materials listed below were identified to contain asbestos.
Material Description Material Location(s) % and Type Asbestos
Estimated Quantity
Joint Compound within the Drywall System
Drywall Walls Throughout Project Area
(Excludes B129 Suite)
1.3% Chrysotile by Point Count (PC) in the Joint
Compound Layer; Trace (<1%) by PC in Composite Samples of Gypsum and Joint Compound Analyzed Together
31,000 Square Feet (SF)
Yellow Mastic Beneath 2’ x 2’ Blue Carpet Squares
North Wing of Project Area 0.25% Chrysotile PC 2,500 SF
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable 5
Material Description Material Location(s) % and Type Asbestos
Estimated Quantity
White Mastic on Fiberglass Duct Insulation
On Fiberglass Insulation Applied Over Duct Work Throughout Project Area
Above Ceilings (Including B129 Suite)
4.8% Chrysotile PC 450 SF
9” x 9” White Floor Tile with Black Mastic and Non-
Asbestos-Containing Brown Mastic and Grey Floor Leveler
Middle Hallway - West End of Project Area and
A140
Floor Tile: 1.3% Chrysotile PC Mastic: 2.1% Chrysotile PC 2,000 SF
Tan/ Black Mastic under Non- Asbestos-Containing
12” x 12” Gray Floor Tile
Main Entrance Lobby of Project Area 1.1% Chrysotile PC 900 SF
Interior White Window Caulking At Interior Window Sills Throughout Project Area 1.3% Chrysotile PC 19 SF (26
Windows)
Gray Mortar Behind 4’ x 4’ Yellow Ceramic Wall Tile
Men’s and Women’s Restrooms: A105a, A106, A107, and A141 in Project Area
1.2% Chrysotile PC 800 SF
White Caulking Around Sinks
Men’s and Women’s Restrooms: A105a, A106, A107, and A141 in Project Area
0.5% Chrysotile PC 7 SF (7 Sinks)
9” x 9” Floor Tile with Brown Flashes and Black Mastic
A135 and A136 in Project Area
Floor Tile 1.2% Chrysotile PC Mastic: 4.0% Chrysotile PC 400 SF
Appendix A includes a listing of the above-identified ACMs with conditions and NESHAP material category. A summary of materials sampled during this survey is included in Appendix B; a drawing with approximate sample locations is included in Appendix E; laboratory analytical reports are included as Appendix C; and a photo log with examples of the identified ACM is included as Appendix F.
If the above-identified ACMs will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state EPA regulations, Occupational Safety and Health Administration (OSHA) regulations, and per VA project specifications.
6.0 LIMITATIONS/GENERAL COMMENTS
In addition to any limitations indicated in other sections of this report, Terracon did not perform sampling which required demolition or destructive activities such as knocking large holes in walls, dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made;
however, confined spaces or areas which may pose a health or safety risk to Terracon personnel
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable 6 were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.
This asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by FFE, Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding quantities, further investigation or remediation deemed necessary.
Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
R es po ns iv e
R es ou rc ef ul
Re lia bl e
AP
PE
N D
IX
A
VA
P ro je ct : R en ov at e
Sp ac e fo r N ew
M en ta l H ea lth
U ni t
VA
P ro je ct
N o.
A4 -1
8-
Le xi ng to n
VA
M ed ic al C en te r C oo pe r D iv is io n
V et er an s
Af fa irs M ed ic al C en te r Le xi ng to n, K Y
ID
EN
TI
FI
ED
A
SB
ES
TO
S-
CO
NT
AI
N
IN
G
M
AT
ER
IA
LS
B
Y
HO
M O
G
EN
EO
US
A R
EA
(H
A)
HA No
M at er ia l D es cr ip tio n
M at er ia l L oc at io n a nd
T yp e As be st os
EP
A
NE
SH
AP
Cl as si fic at io n Co nd iti on Es tim at ed Q ua nt ity
Jo in t C om po un d w ith in th e D ry w al l S ys te m
D ry w al l W al ls Th ro ug ho ut
Pr oj ec t A re a
(E xc lu de s B1
S ui te
1.
3%
C hr ys ot ile b y Po in t C ou nt
(P C
) i n
Jo in t C om po un d;
T ra ce b y
PC
in
C om po si te S am pl es o f G yp su m a nd J oi nt
C om po un d An al yz ed T og et he r
N ot re gu la te d by
E
PA
N
ES
H
AP
1% a sb es to s by c om po si te w ith P
C ho w ev er
, r em ov al o f t he jo in t c om po un d is co ns id er ed
C la ss
II
W or k un de r O
SH
A
.1
G oo d
,0
S qu ar e
Fe et
(S F)
Ye llo w
M as tic B en ea th
’ x
Bl ue C ar pe t S qu ar es
N or th W in g of P ro je ct A re a
0.
C hr ys ot ile
P C
N ot
R eg ul at ed b y
EP
A N
ES
HA
P
1%
R eg ul at ed b y O
SH
A un de r 1
6.
(d ue to ex po su re p ot en tia l)
G oo d 2, SF
W hi te
M as tic o n Fi be rg la ss
D uc t I ns ul at io n
O n
Fi be rg la ss In su la tio n
Ap pl ie d
O ve r D uc t W or k Th ro ug ho ut
Pr oj ec t A re a
Ab ov e C ei lin gs (In cl ud in g
B1
S ui te
4.
8%
C hr ys ot ile P
C C at eg or y
II
N on -F ria bl e G oo d
SF
9” x
” W hi te
F lo or T ile w ith Bl ac k
M as tic a nd N on
As be st os
-C on ta in in g
Br ow n M as tic a nd
G re y Fl oo r
Le ve le r
M id dl e
H al lw ay
W es t E nd o f Pr oj ec t A re a an d A1
Fl oo r T ile : 1
.3
C hr ys ot ile P
C M as tic
: 2 .1
C hr ys ot ile
P C
C at eg or y
II
N on
-F ria bl e
G oo d 2, SF
R es po ns iv e
R es ou rc ef ul
Re lia bl e
HA No
M at er ia l D es cr ip tio n
M at er ia l L oc at io n a nd
T yp e As be st os
EP
A
NE
SH
AP
Cl as si fic at io n Co nd iti on Es tim at ed Q ua nt ity
Ta n/ B la ck
M as tic u nd er
N on
As be st os -C on ta in in g
” x
2” G ra y
Fl oo r T ile
M ai n En tra nc e Lo bb y of P ro je ct Ar ea 1.
1% C hr ys ot ile
P C
C at eg or y I N on -F ria bl e G oo d
SF
In te rio r W hi te W in do w C au lk in g
At In te rio r W in do w
S ills
Th ro ug ho ut P ro je ct A re a
1.
3%
C hr ys ot ile P
C C at eg or y
II
N on -F ria bl e G oo d
S
F (2
W in do w s)
G ra y
M or ta r B eh in d 4’ x
Ye llo w
C er am ic
W al l T ile
M en
’s an d W om en
’s R es tro om s:
A1 a, A
6, A
7, a nd A in Pr oj ec t A re a G re y
Pl as te r:
1.
2%
C hr ys ot ile P
C C at eg or y
II
N on -F ria bl e G oo d
SF
W hi te
C au lk in g Ar ou nd
S in ks M en ’s an d
W om en ’s
R es tro om s:
A1 a, A
6, A
7, a nd
A in
Pr oj ec t A re a
0.
5%
C hr ys ot ile P
C
N ot
R eg ul at ed b y
EP
A N
ES
HA
P
1%
R eg ul at ed b y O
SH
A un de r 1
6.
(d ue to ex po su re p ot en tia l)
G oo d
SF
(7
S in ks
9” x
” F lo or T ile w ith B ro w n Fl as he s an d Bl ac k
M as tic A1 a nd A in P ro je ct A re a
Fl oo r T ile
.2
C hr ys ot ile
P C
M as tic : 4
.0
C hr ys ot ile P
C C at eg or y
II
N on -F ria bl e G oo d
SF
Se e
Ap pe nd ix
B fo r a s um m ar y of s am pl es c ol le ct ed a nd
A pp en di x C fo r d et ai le d an al yt ic al re su lts
It sh ou ld b e no te d th at in ac ce ss ib le /c on ce al ed s us pe ct m at er ia ls , o th er th an th os e id en tif ie d du rin g th is s ur ve y, m ay e xi st
. S ho ul d ad di tio na l s us pe ct m at er ia ls b e un co ve re d pr io r t o or d ur in g de m ol iti on a ct iv iti es , t ho se m at er ia ls m us t b e as su m ed a sb es to s-co nt ai ni ng u nt il sa m pl ed b y a Ke nt uc ky lic en se d as be st os in sp ec to r o r m an ag em en t p la nn er a nd a na ly si s ca n co nf irm o r d en y th ei r a sb es to s-co nt en t.
*E st im at ed q ua nt iti es li st ed a bo ve a re b as ed o n a cu rs or y fie ld e va lu at io n, a nd a ct ua l q ua nt iti es m ay v ar y si gn ifi ca nt ly, e sp ec ia lly if A
C M s ar e pr es en t in h id de n an d/ or in ac ce ss ib le a re as n ot e va lu at ed a s pa rt of th is s ur ve y.
T hi s is n ot a b id di ng d oc um en t a nd c on tra ct or s w ou ld b e re sp on si bl e fo r dr aw in g th ei r o w n co nc lu si on s on q ua nt iti es p re se nt
If th e ab ov e-id en tif ie d
AC
M s wi ll be im pa ct ed b y th e re no va tio n, s uc h m at er ia ls w ou ld n ee d to b e pr op er ly r em ov ed , h an dl ed , a nd d is po se d in ac co rd an ce w ith a pp lic ab le fe de ra l a nd s ta te E
PA
r eg ul at io ns
O cc up at io na l S af et y an d
H ea lth A dm in is tra tio n
(O
SH
A) r eg ul at io ns an d pe r
VA
pr oj ec t s pe ci fic at io ns
Responsive ■ Resourceful ■ Reliable
APPENDIX B
VA Project: Renovate Space for New Mental Health Unit
VA Project No. 596A4-18-107 Lexington VA Medical Center
Cooper Division 1101 Veterans Affairs Medical Center
Lexington, KY
ASBESTOS SURVEY SAMPLE SUMMARY
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
Drywall System:
Drywall and Joint
Compound
A132- Above Doorway
Throughout Main
Renovation Area
(Excludes B129 Suite)
Drywall: None-Detected
(ND)
002 A126- Above Doorway Drywall: ND, Joint Compound: ND, Composite: ND
003 A124- Above Doorway Drywall: ND, Joint Compound: ND, Composite: ND
004 A116- Northeast Corner
Drywall: ND, Joint Compound: Trace
(<1%) Chrysotile by Point Count (PC), Composite: Trace
Chrysotile PC
005 Hallway Outside A119 Drywall: ND
006 Hallway Across from Room A140
Drywall: ND, Joint Compound: ND, Composite: ND
007 Hallway South of A139 Drywall: ND
008 Hallway Outside of A108
Drywall: ND, Joint Compound: 1.3%
Chrysotile PC, Composite: Trace
(<1%) Chrysotile PC
009 North Entrance of Main Lobby
Drywall: ND, Joint Compound: ND, Composite: ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
2’ x 2’ White Small Fissure Ceiling Tile
Hallway Outside Room A119
Throughout
ND
011 Hallway Outside Room
A139 ND
012 Hallway Outside A108 ND
Blue 2’ x 2’
Carpet Squares with Yellow Mastic
A132-Northeast Corner
North Wing
ND
016 A114- Center of East Wall ND
017 A125- Southwest Corner 0.25% Chrysotile PC
6” Blue Cove Base with Tan
Mastic
A132- Northeast Corner
North Wing and East Hallway
Cove Base: ND Mastic: ND
019 A115- Northwest Corner
Cove Base ND Mastic: ND
020 Hallway- South of Doorway of A119
Cove Base: ND Mastic: ND
2’ x 2’ White Pin-Hole
Ceiling Tile
A126- Above Doorway
North Wing Offices
ND
022 A130- Southeast Corner ND
023 A114- Northwest Corner ND
White Interior Door Caulking
A127 Closet Door
Throughout
ND
025 A124 Doorway ND
026 AU104 Doorway ND
7 027 Northeast Corner Room A116 ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
028 Green Carpet with Yellow
Mastic
Northwest Corner ND
029 Southwest Corner ND
Gray Fire-Stop Caulking
Northeast Corner of
AU103
Throughout
ND
031 Northeast Corner of
AU103 ND
032 Northeast Corner of
AU103 ND
12” x 12” Tan Floor Tile with Yellow Mastic
Hallway Outside A140
Room A122, Hallway
Outside of Stairwell 1
Floor Tile: ND Mastic: ND
034 Entrance to Men’s West Restroom Floor Tile: ND
Mastic: ND
035 Doorway of A122 Floor Tile: ND Mastic: ND
White Mastic on Fiberglass
Duct Insulation
Middle of A136 Duct Work Throughout
Above Ceiling Tile Including B129 Suite
4.8% Chrysotile PC
037 East Wall of A132 ND
038 Middle of A114 ND
12” x 12”
Green Floor Tile with
Yellow Mastic
Southwest Corner of Area
Hallway outside A101
Floor Tile: ND, Mastic:
ND, Floor Leveler: ND
040 Northwest Corner of Area
Floor Tile: ND, Mastic:
ND, Floor Leveler: ND
041 Entrance to Office Hallway
Floor Tile: ND, Mastic:
ND, Floor Leveler: ND
12 042
9” x 9” White Floor Tile with
Brown and Black Mastic
Near Doorway of Women’s East
Restroom
Middle Hallway – West and
A140
Floor Tile: 1.3% Chrysotile PC, Brown
Mastic: ND, Black Mastic: 2.1% Chrysotile PC, Floor Leveler: ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. # with Grey Floor
Leveler Northeast Corner of Elevator Lobby
Floor Tile: 1.1% Chrysotile PC, Brown
Mastic: ND
044 Doorway of A143
Floor Tile: 1.2% Chrysotile PC, Brown
Mastic: ND, Black Mastic: 1.7% Chrysotile
PC
6” Brown Cove Base with
Yellow Mastic
Southeast Corner of Elevator Lobby
Hallways
Cove Base: ND, Mastic:
ND
046 Near Entry to Main Lobby
Cove Base: ND, Mastic:
ND
047 Near Entry to A139 Cove Base: ND, Mastic:
ND
2’ x 2’ White Texture Ceiling
Tile
Northeast Corner
Room A116
ND
049 Northwest Corner ND
050 Southeast Corner ND
051 12” x 12” Gray Floor Tile with
Tan/Black Mastic and White Floor
Leveler
Northeast Corner
Main Entrance Lobby
Floor Tile: ND, Tan Mastic: ND, Floor
Leveler: 1.1% Chrysotile PC
052 Northwest Corner Floor Tile: ND, Tan Mastic: ND
053 Southeast Corner Floor Tile: ND, Tan Mastic: ND
4” Black Cove Base with
Yellow Mastic
Southeast Corner
Main Entrance Lobby
Cove Base: ND, Mastic:
ND
055 Middle of West Wall Cove Base: ND, Mastic:
ND
056 Northwest Corner Cove Base: ND, Mastic:
ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
2’ x 2’ White Large Fissure
Ceiling Tile
Northwest Corner
Main Entrance Lobby
ND
058 Northeast Corner ND
059 Southeast Corner ND
White Caulking
A124
Interior Window Sills Throughout
ND
061 A127 1.1% Chrysotile PC
062 A132 1.3% Chrysotile PC
½” Gray
Ceramic Tile with Mortar and Grout
A108- Northwest Corner
Men’s and Women’s
Restrooms, A105a
Tile: ND, Grout: ND, Mortar: ND
064 A108- Northwest Corner
Tile: ND, Grout: ND, Mortar: ND
065 A108- Northwest Corner
Tile: ND, Grout: ND, Mortar: ND
Mortar and
Grout Associated with 4” x 4”
Yellow Ceramic Wall
Tile
Under Sink in Men’s East Restroom
Men’s and Women’s
Restrooms:
A105a, A106, A107, A141, A142
Wall Tile: ND, White Grout ND, Grey
Mortar: 1.1% Chrysotile
PC
067 Under Sink in Men’s East Restroom
Wall Tile: ND, White Grout: ND, Grey Mortar: 1.2%
Chrysotile PC
068 Under Sink in Men’s East Restroom
Wall Tile: ND, White Grout: ND, Grey Mortar: 1.1% Chrysotile PC
White Caulking at Sinks
Men’s Restroom Men’s and Women’s
Restrooms:
A105a, A106, 0.5% Chrysotile PC
070 A105a- Above Sink 0.5% Chrysotile PC
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
071 A108- Above Sink A107, A141, A142 0.25% Chrysotile PC
4” Blue Cove Base with
Yellow Mastic
Southeast Corner
A105
Cove Base: ND, Mastic:
ND
073 Southeast Corner Cove Base: ND, Mastic:
ND
074 Northwest Corner Cove Base: ND, Mastic:
ND
6” Tan Cove Base with
Yellow Mastic
A135- Southeast Corner
A109, A135
Cove Base: ND, Mastic:
ND
076 A109- Northwest Corner
Cove Base: ND, Mastic:
ND
077 A109- Southwest Corner
Cove Base: ND, Mastic:
ND
2’ x 4’ White Pin-Hole
Ceiling Tile
Middle of A112
A112, A135, A136
ND
079 Middle of A135 ND
080 Middle of A136 ND
9” x 9” Floor Tile with Brown
Flashes and Black Mastic
Southwest Corner of A136
A135, A136
Floor Tile 1.1% Chrysotile PC, Mastic:
3.8% Chrysotile PC
082 Southwest Corner of A136
Floor Tile 1.2% Chrysotile PC, Mastic:
3.6% Chrysotile PC
083 Southeast Corner of A135
Floor Tile 1.2% Chrysotile PC, Mastic:
4.0% Chrysotile PC
084 12” x 12” Beige Floor Tile with Yellow Mastic
Northeast Corner of South Room
A137
Floor Tile: ND Mastic: ND
085 Southeast Corner of North Room
Floor Tile: ND Mastic: ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
086 Southeast Corner of North Room
Floor Tile: ND Mastic: ND
White Mastic on Fiberglass
Fitting
Room 105 Pipe Chase
Pipe Chase
ND
088 Room 105 Pipe Chase ND
089 Room 105 Pipe Chase ND
Plaster
Women’s Restroom- West of Door
Restroom Walls and
Ceiling
Finished Coat: ND Base Coat: ND
091 Women’s Restroom- Northeast Corner
Finished Coat: ND Base Coat: ND
092 Men’s Restroom- Southwest Corner
Finished Coat: ND Base Coat: ND
093 A106 North of Doorway
Finished Coat: ND Base Coat: ND
094 A108 South of Doorway
Finished Coat: ND Base Coat: ND
Red Fire-Stop Caulking
Northeast Corner of
AU103
Throughout
ND
096 Northeast Corner of
AU103 ND
097 Northeast Corner of
AU103 ND
30 098 Brown Fire- Stop Caulking
Northeast Corner of AU103 Throughout ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
099 Northeast Corner of
AU103 ND
100 Northeast Corner of
AU103 ND
Red Electrical Putty
AU101
AU101
ND
102 AU101 ND
103 AU101 ND
Drywall System:
Drywall and Joint
Compound
Northwest Corner of B129A
B129 Suite:
Throughout
Drywall: ND, Joint Compound: ND
105 Near Entry to B129B Drywall: ND, Joint Compound: ND
Northwest Corner of
B129C – Patient Flow Command Center
Drywall: ND, Joint Compound: ND
2’x2’ Ceiling Tile with Bird Track Pattern
Northwest Corner of B129A
B129 Suite:
Throughout
ND
108 Near Entry to B129B ND
Northwest Corner of
B129C – Patient Flow Command Center
ND
Grey Sink Undercoating
Under Sink
B129A
ND
111 Under Sink ND
112 Under Sink ND
35 113 Grey Duct Mastic
Northwest Corner of B129C – Patient Flow
Command Center
B129 Suite:
Throughout ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
Sample # Sample Material
Description Sample Location HA
Location(s) Results (% / Type of
Asbestos)HA # SEQ. #
Northwest Corner of
B129C – Patient Flow Command Center
ND
Northwest Corner of
B129C – Patient Flow Command Center
ND
12”x12” Grey Floor Tile with Yellow Mastic
Southwest Corner of B129A – Break Room
B129 Suite:
Throughout
Floor Tile: ND, Mastic:
ND
Northwest Corner of
B129C – Clinical House Supply Office
Floor Tile: ND, Mastic:
ND
Northwest Corner of
B129C – Patient Flow Command Center
Floor Tile: ND, Mastic:
ND
June 17, 2019 ■ Terracon Project No. N1187353
Responsive ■ Resourceful ■ Reliable
APPENDIX C
ASBESTOS ANALYTICAL LABORATORY DATA
Lab No.: 6762983 Client No.: 1-001
Analyst Observation: White/Brown Drywall Client Description: Drywall System: Drywall And Joint Compound
Location: A132-Above Doorway Facility:
Percent Asbestos:
None Detected
Percent Non-Asbestos Fibrous Material:
12 Cellulose 1 Fibrous Glass
Percent Non-Fibrous Material:
Lab No.: 6762984 Client No.: 1-002
Location: A126-Above Doorway
10 Cellulose 5 Fibrous Glass
Lab No.: 6762984(L2)
Analyst Observation: White Joint Compound
Lab No.: 6762984(L3)
Analyst Observation: Composite
8 Cellulose 2 Fibrous Glass
Lab No.: 6762985 Client No.: 1-003
Location: A124-Above Doorway
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER940
Dated : 4/19/2019 3:14:02 Page 1 of 36
Lab No.: 6762985(L2)
Lab No.: 6762985(L3)
Lab No.: 6762986 Client No.: 1-004
Location: A116-Northeast Corner
Lab No.: 6762986(L2)
PC Trace Chrysotile
Lab No.: 6762986(L3)
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 2 of 36
Lab No.: 6762987 Client No.: 1-005
Location: Hallway Outside A119
3 Fibrous Glass
Lab No.: 6762988 Client No.: 1-006
Location: Hallway Across From Room A140 Facility:
Lab No.: 6762988(L2)
Facility:
Lab No.: 6762988(L3)
Facility:
Lab No.: 6762989 Client No.: 1-007
Location: Hallway South Of A139
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 3 of 36
Lab No.: 6762990 Client No.: 1-008
Location: Hallway Outside Of A108
Lab No.: 6762990(L2)
Analyst Observation: Off-White Joint Compound
PC 1.3 Chrysotile
98.7
Lab No.: 6762990(L3)
Lab No.: 6762991 Client No.: 1-009
Location: North Entrance Of Main Lobby
Lab No.: 6762991(L2)
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 4 of 36
Lab No.: 6762991(L3)
9 Cellulose
Lab No.: 6762992 Client No.: 2-010
Analyst Observation: White/Tan Ceiling Tile Client Description: 2'x2' White Small Fissure Ceiling Tile
Location: Hallway Outside Of A119
50 Cellulose 5 Mineral Wool
Lab No.: 6762993 Client No.: 2-011
Location: Hallway Outside Of A139
10 Mineral Wool
Lab No.: 6762994 Client No.: 2-012
10 Mineral Wool
Lab No.: 6762995 Client No.: 3-015
Analyst Observation: Yellow Mastic Client Description: Blue 2'x2' Carpet Squares With Yellow Mastic
Location: A132-Northeast Corner; North Wing Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 5 of 36
Lab No.: 6762996 Client No.: 3-016
Analyst Observation: Yellow/Black Mastic
Location: A114-Center Of East Wall; North
Facility:
PC 0.25 Chrysotile
99.75
Lab No.: 6762997 Client No.: 3-017
Location: A125-Southwest Corner; North
Facility:
Lab No.: 6762998 Client No.: 4-018
Analyst Observation: Dk Blue Cove Base Client Description: 6" Blue Cove Base With Tan Mastic
Wing And East Hallway Facility:
Lab No.: 6762998(L2) Client No.: 4-018
Analyst Observation: Tan/Brown Mastic
Facility:
Lab No.: 6762999 Client No.: 4-019
Location: A115-Northwest Corner; North
Facility:
Lab No.: 6762999(L2) Client No.: 4-019
Analyst Observation: Tan Mastic
Location: A115-Northwest Corner; North
Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 6 of 36
Lab No.: 6763000 Client No.: 4-020
Location: Hallway-South of Doorway Of A119; North Wing And East Hallway Facility:
Lab No.: 6763000(L2) Client No.: 4-020
Location: Hallway-South of Doorway Of A119; North Wing And East Hallway Facility:
Lab No.: 6763001 Client No.: 5-021
Client Description: 2'x2' White Pinhole Ceiling Tile
Location: A126-Above Doorway; North Wing Offices Facility:
40 Cellulose 40 Mineral Wool
Lab No.: 6763002 Client No.: 5-022
Location: A130-Southeast Corner; North
Facility:
30 Cellulose 45 Mineral Wool
Lab No.: 6763003 Client No.: 5-023
Location: A114-Northwest Corner; North
Facility:
40 Mineral Wool
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 7 of 36
Lab No.: 6763004 Client No.: 6-024
Analyst Observation: White Caulk Client Description: White Interior Door Caulking
Location: A127 Closet Door
Lab No.: 6763005 Client No.: 6-025
Location: A124 Doorway
Lab No.: 6763006 Client No.: 6-026
Location: AU104 Doorway
Lab No.: 6763007 Client No.: 7-027
Client Description: Green Carpet With Yellow Mastic
Location: Northeast Corner; Room A116
Lab No.: 6763008 Client No.: 7-028
Location: Northwest Corner; Room A116
Lab No.: 6763009 Client No.: 7-029
Location: Southwest Corner; Room A116
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 8 of 36
Lab No.: 6763010 Client No.: 8-030
Analyst Observation: Grey Caulk Client Description: Grey Firestop Caulking
Location: Northeast Corner Of AU103
Lab No.: 6763010(L2) Client No.: 8-030
PC 1.2 Chrysotile
98.8
Lab No.: 6763011 Client No.: 8-031
Lab No.: 6763011(L2) Client No.: 8-031
Lab No.: 6763012 Client No.: 8-032
Lab No.: 6763013 Client No.: 9-033
Analyst Observation: Tan/White Floor Tile Client Description: 12"x12" Tan Floor Tile With Yellow
Location: Hallway Outside A140; Room A122, Hallway Outside Of Stairwell 1 Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 9 of 36
Lab No.: 6763013(L2) Client No.: 9-033
Location: Hallway Outside A140; Room A122, Hallway Outside Of Stairwell 1 Facility:
Lab No.: 6763014 Client No.: 9-034
Location: Entrance To Men's West Restroom; Room A122, Hallway Outside Of Stairwell 1 Facility:
Lab No.: 6763014(L2) Client No.: 9-034
Location: Entrance To Men's West Restroom; Room A122, Hallway Outside Of Stairwell 1 Facility:
Lab No.: 6763015 Client No.: 9-035
Location: Doorway Of A122; Room A122, Hallway Outside Of Stairwell 1 Facility:
Lab No.: 6763015(L2) Client No.: 9-035
Location: Doorway Of A122; Room A122, Hallway Outside Of Stairwell 1 Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Linda Price
04/17/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 10 of 36
Lab No.: 6763016 Client No.: 10-036
Analyst Observation: White Mastic Client Description: White Duct Mastic
Location: Middle Of A136; Ductwork Throughout Facility:
PC 4.8 Chrysotile
95.2
Lab No.: 6763016(L2) Client No.: 10-036
Analyst Observation: Tan Insulation
Location: Middle Of A136; Ductwork
Facility:
3 Cellulose
Lab No.: 6763017 Client No.: 10-037
Location: East Wall Of A132; Ductwork
Facility:
Lab No.: 6763017(L2) Client No.: 10-037
Location: East Wall Of A132; Ductwork
Facility:
Lab No.: 6763018 Client No.: 10-038
Location: Middle Of A114; Ductwork
Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Michael Lagarde
04/18/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 11 of 36
Lab No.: 6763018(L2)
Facility:
Lab No.: 6763018(L3)
Facility:
Lab No.: 6763019 Client No.: 11-039
Analyst Observation: Green Floor Tile Client Description: 12"x12' Green Floor Tile With Yellow
Location: Southwest Corner Of Area;
Hallway Outside A101 Facility:
Lab No.: 6763019(L2)
Facility:
Lab No.: 6763019(L3)
Analyst Observation: Black/Grey Leveling Compound
Facility:
Lab No.: 6763020 Client No.: 11-040
Location: Northwest Corner Of Area;
Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Michael Lagarde
04/18/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 12 of 36
Lab No.: 6763020(L2)
Facility:
Lab No.: 6763020(L3)
Facility:
2 Cellulose
Lab No.: 6763021 Client No.: 11-041
Location: Entrance To Office Hallway;
Facility:
Lab No.: 6763021(L2)
Facility:
Lab No.: 6763021(L3)
Facility:
Lab No.: 6763022 Client No.: 12-042
Analyst Observation: White Floor Tile Client Description: 9"x9' White Floor Tile With Brown
Location: Near Doorway Of Women's East Restroom; Middle Hallway West Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Michael Lagarde
04/18/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 13 of 36
Lab No.: 6763022(L2)
Analyst Observation: Brown Mastic
Facility:
Lab No.: 6763022(L3)
Analyst Observation: Black Mastic
Facility:
PC 2.1 Chrysotile
97.9
Lab No.: 6763022(L4)
Facility:
Lab No.: 6763023 Client No.: 12-043
Location: Northeast Corner Of Elevator Lobby; Middle Hallway West Facility:
PC 1.1 Chrysotile
98.9
Lab No.: 6763023(L2) Client No.: 12-043
Location: Northeast Corner Of Elevator Lobby; Middle Hallway West Facility:
Lab No.: 6763024 Client No.: 12-044
Location: Doorway Of A143; Middle Hallway West Facility:
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Michael Lagarde
04/18/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 14 of 36
Lab No.: 6763024(L2)
Facility:
Lab No.: 6763024(L3)
Analyst Observation: Black Mastic
Facility:
PC 1.7 Chrysotile
98.3
Lab No.: 6763025 Client No.: 13-045
Analyst Observation: Brown Cove Base Client Description: 6' Brown Cove Base With Yellow Mastic
Location: Southeast Corner Of Elevator Lobby; Hallways Facility:
Lab No.: 6763025(L2) Client No.: 13-045
Location: Southeast Corner Of Elevator Lobby; Hallways Facility:
Lab No.: 6763026 Client No.: 13-046
Location: Near Entry To Main Lobby;
Hallways Facility:
Lab No.: 6763026(L2)
Facility:
1 Cellulose
Laboratory Director
Approved By:
Date Analyzed:
4/12/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Michael Lagarde
04/18/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
611 Lunken Park Drive Cincinnati OH 45226
4/18/2019Report Date:
Report No.: 587712 - PLM Project: Lexington VAMC Project No.: N1187353
PLM BULK SAMPLE ANALYSIS SUMMARY
Dated : 4/19/2019 3:14:02 Page 15 of 36
Lab No.: 6763026(L3)
Facility:
Lab No.: 6763027 Client No.: 13-047
Location: Near Entry To A139; Hallways
Lab No.: 6763027(L2)
Lab No.: 6763027(L3)
Lab No.: 6763028 Client No.: 14-048
Client Description: 2'x2' White Texture Ceiling Tile
Location: Northeast Corner; Room A116
30 Fibrous…