Plans.pdf
PDF 17 MB Posted
- Attached to
- Public Works EV Charging Electrical Upgrades
- Solicitation number
- FY2026-ITB-152
- Issued by
- Champaign County, Illinois
About this file
This is a bid/permit set of electrical design documents for the Urbana Public Works EV Charging Electrical Upgrades project, prepared by Farnsworth Group for the City of Urbana, Illinois. The project is located at 704 S Glover Avenue and involves installing electric vehicle (EV) charging stations at a municipal facility. The design includes provisions for ten EV charging stations, with seven active stations and three future locations, utilizing chargers from vendors like ChargePoint, Ford Pro, and FractalEV. The electrical design involves a new switchboard, electrical service upgrades, and modifications to the existing electrical infrastructure to support the EV charging capabilities.
The project's electrical design includes a 1200A main switchboard, connection to an existing utility transformer, and detailed plans for power distribution, grounding, and future expansion. The design incorporates specific technical specifications for conduit, wiring, circuit breakers, and equipment mounting, with careful attention to electrical code compliance and safety standards. The documents are part of a bid/permit set dated August 15, 2025, indicating the project is planned for near-future implementation. The design also includes provisions for potential backup power through an alternate bid option that would provide an automatic transfer switch and temporary generator connection for two EV chargers.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GROUP
G R
O U
P
PROJECT NO.: DATE:
NOT FOR CONSTRUCTION
PROFESSIONAL REGISTRATIONS
LOCATION MAP
SHEET INDEX
IMAGE © < COPYRIGHT NOTICE >
2211 W. Bradley Avenue - Champaign, Illinois 61821 - Phone: (217) 352-7408 / info@f-w.com
Design Firm Registration #184001856
/1
/2
:0
:4
A
M
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
C it y o f U rb a n a
BID/PERMIT SET
U rb a n a P u b lic W o rk s E
V C h a rg in g E le c tr ic a l U p g ra d e s
B
ID
/P E
R M
IT
S
E T
C1.1 EV CHARGING STATION SITE PLAN
C2.1 GENERAL NOTES AND LEGENDS
C3.1 DETAILS
C3.2 DETAILS
C3.3 DETAILS
E0.1 GENERAL INFORMATION
E0.2 GENERAL INFORMATION
E0.3 SPECIFICATIONS
E0.4 SPECIFICATIONS
E0.5 SPECIFICATIONS
ED1.1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
E2.1 FIRST FLOOR POWER PLAN
E4.1 ONE-LINE DIAGRAM
E6.1 DETAILS
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
TIM SUTYAK
11/30/2025
ELECTRICAL
SUPERVISION. I AM A DULY LICENSED PLUMBER UNDER THE
LAWS OF THE STATE OF ILLINOIS.
SITE LOCATION
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
DENNIS CUMMINS
CIVIL
SUPERVISION. I AM A DULY LICENSED PLUMBER UNDER THE
LAWS OF THE STATE OF ILLINOIS.
08/15/2025 11/30/2025
08/12/2025
8'' ST 8'' ST 8'' ST 8'' ST
T
8'' S
T 8''
S T
8'' S
T 8''
S T
FFE = 734.32
3.8
4.3
4.2
3.9
3.8
4.0
4.5
4.4
3.8
4.0
3.6
4.1
3.7
3.9
3.5
4.0
4.9
4.6
4.6
4.1
733.76
734.17
4.2
4.3
3.8
733.99
4.3
4.3
734.35
E E
E
E E
E E E E E E E
E
E
E
E
E
E E E E E E E E E E E E E E E E E E E E E E E E E
E
3.8
8" S
T
.6
0%
8" ST @ 0.60%
END SIDEWALK HERE
THIS CONTRACT
END CURB HERE
THIS CONTRACT
ADJUST WITH NEW
TYPE 3 FRAME &
GRATE - BY OTHERS
B6.18 CURB AND GUTTER
INLET TYPE A W/TY 3 FRAME & GRATE
RIM (E/P) = 733.52
8" PVC INV (E)= 731.21
8" PVC INV (S)= 731.21
INLET TYPE A W/TY 3 FRAME & GRATE
RIM (E/P) = 733.62
8" PVC INV (W)= 731.32
P.C.C. SIDEWALK, 6"
RIVER ROCK
LANDSCAPING
END CURB HERE
THIS CONTRACT
NEW ELECTRIC SERVICE
FROM UTILITY POLE
NEW ELECTRIC SECONDARY
TO BUILDING
STUB FUTURE ELECTRIC
SERVICE TO NEW UPW ADDITION
REGRADE GRAVEL LOT TO
MANINTAIN STORM INLETS
AS LOW POINTS
8" PVC INV (N)= 731.10
ADJUST
9'
TYP
.3
4'
.5
5.
5'
5.63'
14.74'
9'
R=2.5'
R=2'
8.66'
FIELD VERIFY EXACT LOCATIONS OF VEHICLE
CHARGERS WITH ELECTRICAL ENGINEER AND
OWNER PRIOR TO INSTALLING EQUIPMENT.
1 SCALE:
EV CHARGING STATION SITE PLAN
1"=5' NORTH
U.S. SURVEY FEET
3 5 10
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
EV CHARGING
STATION SITE PLAN
C1.1
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com http://www.f-w.com
CONSTRUCTION FOR THIS PROJECT SHALL BE IN ACCORDANCE WITH THESE PLANS, THE SPECIAL PROVISIONS
ACCOMPANYING THESE PLANS, AND THE FOLLOWING SPECIFICATIONS:
A. "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION", CURRENT EDITION, BY THE ILLINOIS
DEPARTMENT OF TRANSPORTATION.
B. "SUPPLEMENTAL SPECIFICATIONS AND RECURRING SPECIAL PROVISIONS", CURRENT EDITION, BY THE
ILLINOIS DEPARTMENT OF TRANSPORTATION.
C. "STANDARD SPECIFICATIONS FOR WATER AND SEWER MAIN CONSTRUCTION IN ILLINOIS", CURRENT EDITION
D. "IDOT DRAINAGE MANUAL"
E. CITY OF URBANA STANDARDS.
THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, PROCEDURES, TECHNIQUES OR SEQUENCES OF CONSTRUCTION, NOR SAFETY ON THE JOB SITE, NOR SHALL THE ENGINEER BE RESPONSIBLE FOR THE CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER NOR THE PRESENCE OF THE ENGINEER AT A CONSTRUCTION SITE SHALL RELIEVE THE CONTRACTOR OF THEIR OBLIGATIONS, DUTIES AND RESPONSIBILITIES, INCLUDING ANY HEALTH AND SAFETY PRECAUTIONS REQUIRED BY ANY REGULATORY
AGENCIES.
IN ADDITION, THE "STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION" SHALL BE MODIFIED AS
FOLLOWS:
UNDER SECTION 105.01, ADD THE FOLLOWING SENTENCE:
NOTHING CONTAINED HEREIN SHALL RELIEVE THE CONTRACTOR OF ITS DUTY TO OBSERVE AND COMPLY WITH ALL APPLICABLE LAWS, NOR SHALL THE ENGINEER BE RESPONSIBLE FOR CONTRACTOR'S COMPLIANCE OR
NON-COMPLIANCE WITH SUCH LAWS.
UNDER SECTION 107.01, ADD THE FOLLOWING SENTENCE:
THE ENGINEER SHALL NOT BE RESPONSIBLE FOR CONTRACTOR'S DUTY TO OBSERVE AND COMPLY WITH THE
PROVISIONS OF THIS SECTION, OR FOR CONTRACTOR'S FAILURE TO DO SO.
THE CONTRACTOR SHALL NOTIFY THE ENGINEER (PH. 217-352-7408) AND THE OWNER (PH. 217-384-2342) AT LEAST
72 HOURS IN ADVANCE OF THE START OR RESTART OF CONSTRUCTION.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO ASCERTAIN EXISTING FIELD CONDITIONS PRIOR TO BIDDING ON
THE CONTRACT.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO CONSTRUCTION
AND ORDERING MATERIALS.
THE CONTRACTOR SHALL DISPOSE OF ALL REMOVAL ITEMS OFF OF THE RIGHT-OF-WAY.
ELECTRONIC FILES AND/OR ELECTRONIC SURVEY INFORMATION INCLUDING CADD FILES WILL BE AVAILABLE TO
THE CONTRACTOR.
ANY REFERENCE STANDARDS THROUGHOUT THE PLANS SHALL BE INTERPRETED TO BE THE LATEST STANDARDS
OF THE ILLINOIS DEPARTMENT OF TRANSPORTATION.
HORIZONTAL COORDINATES ARE BASED ON THE ILLINOIS STATE PLANE COORDINATE SYSTEM, EAST ZONE, NAD 83 (2011).
ALL ELEVATIONS SHOWN ON THE PLANS ARE BASED ON NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD 88).
THE CONTRACTOR, AT HIS OWN EXPENSE, SHALL BE REQUIRED AS REQUESTED BY THE ENGINEER TO REMOVE
ALL ROAD SIGNS WHICH INTERFERE WITH CONSTRUCTION OPERATIONS.
THE CONTRACTOR SHALL SUBMIT A PROGRESS SCHEDULE WITHIN 10 DAYS OF CONTRACT AWARD NOTIFICATION.
THE CONTRACTOR SHALL PROTECT AND CAREFULLY PRESERVE ALL PROPERTY MARKERS AND/OR MONUMENT UNTIL THE OWNER, AUTHORIZED SURVEYOR, OR AGENT HAS WITNESSED, OR REFERENCED THEIR LOCATION.
THE CONTRACTOR WILL BE RESPONSIBLE FOR HAVING AN AUTHORIZED SURVEYOR RE-ESTABLISH ANY SECTION
OR SUBSECTION MONUMENT DESTROYED BY HIS OPERATIONS.
EXISTING UTILITIES ARE SHOWN ON THE PLANS. THE CONTRACTOR SHALL COORDINATE THE LOCATING OF THESE UTILITIES PRIOR TO COMMENCING ANY EXCAVATION OR BORING IN THEIR VICINITY. SHOULD THESE UTILITIES BE DAMAGED BY THE CONTRACTOR'S OPERATIONS, THE CONTRACTOR SHALL REPAIR THEM TO THE
SATISFACTION OF, AND AT NO COST TO, THE OWNER.
THE CONTRACTOR SHALL COORDINATE ACTIVITIES WITH ALL UTILITIES WITHIN THE PROJECT LIMITS. THE LOCATIONS OF EXISTING UTILITIES AS SHOWN ON THE PLANS ARE BASED ON CAREFUL FIELD INVESTIGATION AND THE BEST INFORMATION AVAILABLE, BUT ARE NOT GUARANTEED. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THEIR EXACT LOCATIONS FROM THE UTILITY COMPANIES AND BY FIELD INSPECTION AT NO ADDITIONAL COST. THE CONTRACTOR IS REQUIRED TO CONTACT J.U.L.I.E. AT, 1-800-892-0123 OR 811, PRIOR TO PROCEEDING WITH ANY EXCAVATION AND WORK ON THE PROJECT. THIS WORK WILL NOT BE
PAID FOR SEPARATELY AND SHALL BE CONSIDERED AS INCLUDED IN THE CONTRACT.
DURING CONSTRUCTION THE CONTRACTOR MAY ENCOUNTER VARIOUS TYPES OF UNDERGROUND UTILITIES THAT MAY NOT BE SHOWN ON THE PLANS OR ARE FOUND TO DIFFER FROM THE PLANS. THE CONTRACTOR SHALL COOPERATE WITH THE ENGINEER AND THE OWNER OF THE UTILITY WHILE THE UTILITY COMPANY ADJUST THEIR FACILITIES IF NECESSARY. IF IT IS DETERMINED THAT THE UTILITY HAS BEEN ABANDONED, THE CONTRACTOR SHALL BE DIRECTED TO REMOVE THE UTILITY LINES THAT CONFLICT WITH HIS WORK AND CAP OR PLUG THE LINES AS DIRECTED BY THE ENGINEER. THIS WORK SHALL NOT BE PAID FOR SEPARATELY AND SHALL
BE CONSIDERED AS INCLUDED IN THE CONTRACT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANUP OF THE SITE PRIOR TO FINAL ACCEPTANCE WITH ARTICLE 104.06 OF THE STANDARD SPECIFICATIONS. THIS WORK SHALL ALSO INCLUDE CLEANING ALL DRAINAGE FACILITIES OF FOREIGN MATERIALS IN ACCORDANCE WITH ARTICLE 602.15 OF THE STANDARD SPECIFICATIONS.
THIS WORK SHALL BE DONE AS DIRECTED BY THE ENGINEER AND NO ADDITIONAL COMPENSATION WILL BE
ALLOWED.
THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING DRAINAGE THROUGHOUT CONSTRUCTION OF THIS
PROJECT AT NO ADDITIONAL COST.
CONTRACTOR SHALL CAREFULLY PROTECT ANY TREES OR SHRUBS NOT INCLUDED IN THE CONTRACT FOR REMOVAL. SNOW FENCE SHALL BE ERECTED TWO FEET FROM TREES AND SHRUBS TO REMAIN, THAT ARE IMMEDIATELY ADJACENT TO THE WORK, FOR PROTECTION DURING CLEARING AND CONSTRUCTION OPERATIONS.
COST OF THIS WORK SHALL BE CONSIDERED AS INCLUDED IN THE CONTRACT AND NO ADDITIONAL
COMPENSATION WILL BE ALLOWED.
CONTRACTOR SHALL STRIP TOPSOIL WITHIN THE PROPOSED IMPROVEMENTS AND STOCKPILE AT A LOCATION
DESIGNATED BY THE OWNER. CONTRACTOR SHALL COORDINATE WITH OWNER FOR LOCATION.
SHRUBS, BUSHES, AND STUMPS THAT INTERFERE WITH THE CONSTRUCTION OPERATIONS SHALL BE REMOVED AS SHOWN IN THE PLANS AND AS DIRECTED BY THE ENGINEER. COST OF REMOVAL OF SHRUBS, BUSHES, OR STUMPS SHALL BE INCLUDED IN THE CONTRACT AND NO ADDITIONAL COMPENSATION WILL BE ALLOWED.
GRADING SHALL BE DONE BY HAND AROUND LIGHT POLES, UTILITY POLES, SIGN POSTS, SHRUBS, TREES AND OTHER NATURAL OR MAN-MADE WHERE SHALLOW FILLS OR CUTS ARE ADJACENT TO THESE ITEMS. IT IS THE INTENT THAT ITEMS THAT DO NOT NEED TO BE DISTURBED BY THE CONSTRUCTION SHALL BE PRESERVED. THE DECISION AS TO ITEMS TO REMAIN IN PLACE SHALL BE AS DIRECTED BY THE ENGINEER. THIS WORK WILL NOT BE PAID FOR SEPARATELY, BUT SHALL BE CONSIDERED INCLUDED IN THE CONTRACT UNIT PRICE FOR THE VARIOUS
PAY ITEMS AND NO ADDITIONAL COMPENSATION WILL BE ALLOWED.
GENERAL NOTES
1. THE EXISTING TOPOGRAPHIC INFORMATION INDICATED FOR THIS PROJECT IS
BASED ON A TOPOGRAPHIC SURVEY PREPARED BY FARNSWORTH GROUP,
INC. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE TOPOGRAPHIC
INFORMATION INDICATED ON THE DRAWINGS AND SHALL DETERMINE THE
EXACT LOCATION AND ELEVATION OF ALL EXISTING TOPOGRAPHIC
INFORMATION ABOVE OR BELOW GROUND, SHOWN OR NOT SHOWN, PRIOR
TO CONSTRUCTION. DISCREPANCIES IN EXISTING TOPOGRAPHIC DATA SHALL
BE REPORTED TO THE ENGINEER IMMEDIATELY FOR REVIEW.
2. CONTRACTOR SHALL NOTIFY AND COORDINATE UTILITY ABANDONMENTS
AND RELOCATIONS WITH APPROPRIATE UTILITY COMPANY AFFECTED AS MAY
BE NECESSARY. SEE COVER SHEET FOR CONTACT LISTINGS OF LOCAL
UTILITIES.
3. CONTRACTORS SHALL CONTACT J.U.L.I.E. AT 1-800-892-0123, LOCAL UTILITY
COMPANIES AT LEAST 48 HOURS PRIOR TO CONSTRUCTION OR EXCAVATION
FOR FIELD LOCATION OF BURIED UTILITIES.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING UTILITY
PROVIDERS AND HAVING ALL UNDERGROUND UTILITIES PROPERLY LOCATED
PRIOR TO ANY DEMOLITION.
5. UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE ONLY AND
SHOULD BE FIELD VERIFIED BY THE CONTRACTOR. UNKNOWN UTILITIES MAY
BE DISCOVERED AND SHOULD BE REPORTED TO THE ENGINEER.
6. CONTRACTOR SHALL REMOVE ALL EXISTING UTILITIES AND DRAIN TILES
INDICATED WITHIN THE PROPOSED BUILDING FOOTPRINTS, AND BACKFILL
WITH APPROVED GRANULAR MATERIAL.
7. CONTRACTOR SHALL COMPLY WITH ALL UTILITY PROVIDER REQUIREMENTS
WHEN DISCONNECTING EXISTING UTILITY SERVICE FROM BUILDINGS TO BE
REMOVED.
8. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT
DAMAGE TO OTHER AREAS ADJACENT TO NEW CONSTRUCTION OR AREAS
WHERE VARIOUS SYSTEM CONNECTIONS OR EXTENSIONS ARE REQUIRED.
9. TEMPORARY BARRICADES PERTAINING TO THE CONTRACTOR'S ACTIVITIES
SHALL BE INSTALLED TO PREVENT POSSIBLE INJURY TO PEDESTRIANS IN
AND AROUND CONSTRUCTION AREAS IN ACCORDANCE WITH OSHA
REQUIREMENTS.
10. PRIOR TO ANY DEMOLITION TAKING PLACE, PERIMETER EROSION CONTROL
MEASURES MUST BE IN PLACE.
11. NO BURNING OR BURYING OF ANY DEMOLITION MATERIAL IS PERMITTED ON
SITE.
12. ALL EXISTING STRUCTURES LOCATED ON-SITE TO BE DEMOLISHED SHALL BE
REMOVED IN ACCORDANCE WITH CURRENT EPA GUIDELINES. ALL VOIDS DUE
TO UNDERGROUND STRUCTURES DEMOLITION SHALL BE BACKFILLED WITH
GRANULAR MATERIAL AND COMPACTED.
13. UNDERGROUND STORAGE TANKS SHALL BE REMOVED BY LICENSED
CONTRACTORS IN COMPLIANCE WITH ALL UST REGULATIONS. IF PETROLEUM
IS FOUND NOTICE TO IEPA SHALL BE CONDUCTED. ANY REMEDIATION
EFFORTS SHALL BE HANDLED UNDER A SEPARATE NEGOTIATED CONTACT.
1. ALL PAVEMENT DIMENSIONS ARE MEASURED TO EDGE OF PAVEMENT.
2. HORIZONTAL TRANSITION TO EXISTING CURBS WITHIN 3.5' AS SHOWN ON THE
PLANS.
3. BUILDING DIMENSIONS AND UTILITY CONNECTION LOCATIONS SHALL BE
VERIFIED BY THE CONTRACTOR WITH THE ARCHITECT'S PLANS PRIOR TO
STARTING ANY SITEWORK.
4. ALL PAVEMENT STRIPING SHALL BE 4" YELLOW PAINT PAVEMENT MARKING
LINE.
5. SPECIFICATIONS ADOPTED BY REFERENCE IN THESE PLANS REFER TO THE
LATEST PUBLISHED REVISION THEREOF.
6. ALL PUBLIC/PRIVATE WALKWAYS SHALL NOT EXCEED 2% CROSS SLOPE. ANY
WALK CONSTRUCTED WITH A CROSS SLOPE GREATER THAN 2% SHALL BE
REMOVED AND REPLACED AT CONTRACTORS EXPENSE.
7. THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS,
PROCEDURES, TECHNIQUES, OR SEQUENCES OF CONSTRUCTION, NOR
SAFETY ON THE JOB SITE, NOR SHALL THE ENGINEER BE RESPONSIBLE FOR
THE CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE
WITH THE CONTRACT DOCUMENTS. NEITHER THE PROFESSIONAL ACTIVITIES
OF THE ENGINEER NOR THE PRESENCE OF THE ENGINEER AT A
CONSTRUCTION SITE SHALL RELIEVE THE CONTRACTOR OF THEIR
OBLIGATIONS, DUTIES, AND RESPONSIBILITIES INCLUDING ANY HEALTH AND
SAFETY PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES.
DEMOLITION NOTES
STANDARD LAYOUT NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING UTILITY COMPANIES AND
HAVING ALL UNDERGROUND UTILITIES PROPERLY LOCATED. CALL THE TOLL-FREE
J.U.L.I.E. TELEPHONE NUMBER, 1-800-892-0123, BEFORE STARTING LOCATED PRIOR TO
ANY CONSTRUCTION. EXCAVATION. ALLOW 48 HOURS FOR OTHER THAN EMERGENCY
ASSISTANCE.
2. ALL FILL AREAS SHALL BE STRIPPED OF ALL TOPSOIL PRIOR TO PLACING
EMBANKMENT MATERIAL. LAWN AREAS THAT HAVE RECEIVED EMBANKMENT
MATERIAL SHALL RECEIVE AT LEAST 6" OF TOPSOIL AS THE FINAL COURSE OF FILL IN
PREPARATION FOR SEEDING OPERATIONS. ALL LAWN AREAS DISTURBED DURING
CONSTRUCTION SHALL BE REPAIRED AND RESTORED TO THE SATISFACTION OF THE
OWNER.
3. EMBANKMENT MATERIAL SHALL BE PLACED IN NO MORE THAN 8" LIFTS AND SHALL BE
COMPACTED TO 95% OF STANDARD PROCTOR DENSITY.
4. TEMPORARY SILTATION PROTECTION SHALL BE CONSTRUCTED AS SILT FILTER
BASKETS IN ALL EXISTING AND PROPOSED INLETS AND MANHOLES AND SILT FILTER
FENCE WHERE INDICATED ON THE PLANS TO PROTECT FROM SILTATION ONTO
ADJACENT PROPERTY AND ROADWAYS.
5. PERMANENT STABILIZATION SHALL INCLUDE THE SEEDING OR SODDING OF LAWN
AREAS DISTURBED AND PAVED SURFACE COURSE FOR ROADWAYS AND PARKING.
ALL PERMANENT SEEDING SHALL TAKE PLACE IMMEDIATELY FOLLOWING FINAL
GRADING OPERATIONS IN ANY COMPLETED AREA WITHIN THE CONSTRUCTION LIMITS.
SEED MIX SHALL BE 100% TURF TYPE TALL FESCUE WITH AT LEAST 3 VARIETIES,
APPROVED BY THE ENGINEER PRIOR TO SEEDING. SEED SHALL BE SOWN AT A RATE
OF 200 POUNDS PER ACRE.
6. ALL SEEDED AREAS SHALL BE MULCHED USING MULCH METHOD 2 OR 3
7. NO CONSTRUCTION WASTE MATERIALS WILL BE BURIED ON SITE. ALL TRASH AND
CONSTRUCTION DEBRIS WILL BE HAULED TO THE LOCAL MUNICIPAL DUMP AND
DISPOSED OF IN ACCORDANCE WITH STATE AND LOCAL SOLID WASTE MANAGEMENT
REGULATIONS.
8. THE CONTRACTOR SHALL PROVIDE SOLID WASTE COLLECTION DURING
CONSTRUCTION TO MINIMIZE POLLUTION.
9. ALL HAZARDOUS WASTE MATERIALS WILL BE DISPOSED OF IN THE MANNER
SPECIFIED BY LOCAL OR STATE REGULATION OR BY THE MANUFACTURER. THE
CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING THESE PROCEDURES DURING
CONSTRUCTION.
10. THE CONTRACTOR SHALL PROVIDE A STABILIZED CONSTRUCTION ENTRANCE IN
ACCORDANCE WITH THE DETAIL INCLUDED WITH THESE PLANS AT LOCATIONS
INDICATED ON THE PLANS TO HELP REDUCE VEHICLE TRACKING OF SEDIMENTS. ANY
EXCESS MUD, DIRT OR ROCK TRACKED ONTO EXISTING STREETS WILL BE CHECKED
FOR DAILY AND REMOVED AS NECESSARY.
11. ALL TEMPORARY AND PERMANENT EROSION CONTROL MEASURES SHALL BE IN
ACCORDANCE WITH THE REQUIREMENTS OF THE ILLINOIS EPA AND THE PROJECT
STORM WATER POLLUTION PLAN.
12. TEMPORARY EROSION CONTROL MEASURES SHALL BE INSTALLED ON THE FIRST DAY
OF CONSTRUCTION ACTIVITIES. ALL BARE SOIL SURFACES NOT IN MAJOR
CONSTRUCTION AREAS SHALL BE TEMPORARILY SEEDED WITHIN 7 DAYS, WEATHER
AND SOIL CONDITIONS PERMITTING. THE CONTRACTOR SHALL INSPECT THE EROSION
CONTROL SYSTEM WEEKLY, AND AFTER RAINFALL EVENTS. DEFICIENCIES SHALL BE
NOTED AND CORRECTED IMMEDIATELY.
13. PERMANENT GROUND COVER SHALL BE IN ACCORDANCE WITH THE IDOT STANDARD
SPECIFICATIONS.
14. THE CONTRACTOR SHALL INSPECT THE EROSION CONTROL SYSTEM IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NPDES GENERAL PERMIT FOR STORM WATER
DISCHARGES FROM CONSTRUCTION ACTIVITIES AND THE STORM WATER POLLUTION
PREVENTION PLAN PREPARED FOR THIS PROJECT AND AVAILABLE FROM OWNER.
15. ADDITIONAL EROSION CONTROL REQUIREMENTS ARE INDICATED IN THE STORM
WATER POLLUTION PREVENTION PLAN PREPARED FOR THIS PROJECT.
16. AREAS HAVING SLOPES GREATER THAN 25% SHALL BE STABILIZED IN ACCORDANCE
WITH ONE OF THE FOLLOWING TWO METHODS:
A. SODDING
B. EROSION CONTROL BLANKET.
17. ALL FIELD TILE SHALL BE REMOVED UNDER PROPOSED BUILDING AREAS. CAP ENDS
OF TILES TO REMAIN IN SERVICE. MAINTAIN IN SERVICE LINES THAT DO NOT IMPACT
THE CONSTRUCTION AREA.
18. UNLESS NOTED OTHERWISE, ALL STORM SEWER SHALL BE:
1.1. POLYVINYL CHLORIDE (PVC) PIPE
A. PIPE & FITTING MATERIAL - POLYVINYL CHLORIDE (PVC) PIPE: ASTM D3034
(SDR-35) NSF 14.
B. GASKETS - FLEXIBLE ELASTOMERIC, ASTM F477
C. FITTINGS - PVC SDR 26, ASTM D3034
D. JOINTS - ASTM D3212
E. BEDDING - CLASS II, ASTM 2321
1.2 REINFORCED CONCRETE PIPE (RCP)
A. PIPE MATERIAL - REINFORCED CONCRETE PIPE
B. GASKETS - FLEXIBLE RUBBER OR PREFORMED FLEXIBLE JOINT SEALANT.
C. BEDDING - IDOT GRADATION CA-6 OR CA-7.
20. CULVERTS SHALL BE REINFORCED CONCRETE CULVERT, STORM DRAIN AND SEWER
PIPE.
21. ALL CLEAN-OUTS (SANITARY AND STORM), THAT ARE BUILT IN CONCRETE PAVEMENT
AREAS, SHALL BE NEENAH R-1976.
22. TEMPORARY SECURITY FENCE SHALL CONSIST OF 6 FT. CHAIN LINK PANELS WITH
SELF SUPPORTING BASE. PANELS SHALL BE SECURED TO ADJOINING PANELS. SHOP
DRAWINGS REQUIRED. THE CONTRACTOR SHALL DEPLOY AS NEEDED TO MAINTAIN
SITE SECURITY.
GRADING & EROSION CONTROL NOTES
OE
OT
T
ASPHALT PAVEMENT REMOVAL
CONCRETE REMOVAL
CURB REMOVAL
GAS SERVICE REMOVAL
TELEPHONE LINE REMOVAL
BUSH REMOVAL
SIDEWALK REMOVAL
DECIDUOUS TREE
REMOVAL
NON-DECIDUOUS
TREE REMOVAL
GRAVEL PAVEMENT REMOVAL
ST STORM SEWER REVOMAL
ASPHALT PAVEMENT 1-1/2"
MILL FOR NEW PAVEMENT
PAVEMENT SAWCUT LINE
ST
SA
W
WATER METER PIT W/ METER
WATER SERVICE
SANITARY SERVICE
STORM SEWER
GAS SERVICE
ELECTRIC CONDUITS
END SECTION
STORM INLET
CURB INLET
STORM MANHOLE
SANITARY MANHOLE
SEWER CLEAN OUTCONCRETE MONOLITHIC
CURB & GUTTER
COMBINED CONCRETE CURB
& GUTTER TYPE M (MODIFIED)
DEPRESSED CURB
GROUND CONTOUR
SILT FENCE
G
E
ACCESSIBLE PATH
DETECTABLE WARNING STRIP
FINISHED TOP OF WALK ELEV.
FINISHED PAVEMENT ELEV.
DRAINAGE DIRECTION
INLET PROTECTION
BOLLARD
EROSION CONTROL WATTLE
SF
IP
SEEDING AND MULCHINGS
EC
EXISTING LEGEND
DEMOLITION LEGEND
ORANGE CONSTRUCTION FENCING
OVERHEAD TELEPHONE LINE REMOVAL
ELECTRIC LINE REMOVAL
OVERHEAD ELECTRIC LINE REMOVAL
PROPOSED LEGEND
205.48'
SITE LIGHTING
NOTE: NOT ALL ITEMS ARE DEPICTED ON THESE PLANS
NOTE: NOT ALL ITEMS ARE DEPICTED ON THESE PLANS
NOTE: NOT ALL ITEMS ARE DEPICTED ON THESE PLANS
HMA SURFACE COURSE, 3"
AGG. BASE COURSE, 8"
PCC PAVEMENT, 6"
AGG. BASE COURSE, 4"
BENCHMARKS
BM 241: NAIL IN SOUTH FACE OF POWER POLE AT THE NORTHWEST CORNER OF NEW
BLDG ON NORTH END OF SITE
ELEV: 733.65
BM 242: CUT SQUARE ON NORTHEAST CORNER OF CONCRETE LIGHT BASE ON NORTH
SIDE OF NORTH ENTRANCE TO SITE.
ELEV: 735.96
BM 243: CUT SQUARE ON SOUTHEAST CORNER OF CONCRETE LIGHT BASE.
ELEV: 735.24
BM 250: CUT + ON NORTHWEST CORNER CONCRETE LIGHT BASE, SOUTH SIDE SITE, 18'
EAST OF GATE TO REAR YARD.
ELEV: 736.59
BM 251: EXISTING CUT SQUARE ON NORTHEAST CONER OF CONCRETE LIGHT BASE ON
SOUTH SIDE OF THE SOUTH ENTRANCE TO SITE, EAST SIDE GLOVER
ELEV: 738.36
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GENERAL NOTES
AND LEGENDS
C2.1
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
SIDE ELEVATION
PLAN VIEW
TYPICAL FLAT/ RECTANGULAR/ ROLLED CURB
INLET FILTER
TYPICAL CURB BOX
INLET FILTER
TYPICAL ROUND
INLET FILTER
5 SCALE:
TEMPORARY DIVERSION DIKE
NOT TO SCALE3 SCALE:
IPP FLEXSTORM INLET FILTER DETAIL
NOT TO SCALE
6 SCALE:
STABILIZED CONSTRUCTION
ENTRANCE
NOT TO SCALE4 SCALE:
CONCRETE WASHOUT AREA DETAIL
NOT TO SCALE
1 SCALE:
TEMPORARY EROSION CONTROL SYSTEMS STANDARD 280001-07 (1 of 2)
NOT TO SCALE
2 SCALE:
TEMPORARY EROSION CONTROL SYSTEMS STANDARD 280001-07 (2 of 2)
NOT TO SCALE
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
DETAILS
C3.1
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
1 SCALE:
CONCRETE PAVEMENT DETAIL
NOT TO SCALE
6" PORTLAND CEMENT
CONCRETE PAVEMENT
4" AGGREGATE BASE, TYPE
B
COMPACTED SUB GRADE
SCALE:
CONCRETE WALK WITH FLUSH EDGE DETAIL
Not To Scale
PREPARED EARTH SUBGRADE
(STOP REINF. AT JOINTS)
1-#5 TOP AND BOTTOM
#4 AT 48"C VERT.
PAVEMENT
VARIES - REFER TO PLAN
CONCRETE WALK
SCALE:
CONCRETE WALK (TYPE SPECIAL)
Not To Scale
PREPARED EARTH SUBGRADE
(STOP REINF. AT JOINTS)
1-#5 TOP AND BOTTOM
#4 AT 48"C VERT.
VARIES - REFER TO PLAN
CONCRETE WALK
PAVEMENT
(NEENAH R-7506 OR EQUIV
METAL CLEANOUT BOX
CLEANOUT PLUG
CONCRETE RIM
CLEANOUT PLUG
FINISHED GRADE
FINISHED GRADE
CONCRETE CLEANOUT BOX
W/METAL FRAME AND COVER
(NEENAH R-1976 OR EQUIV)
SCALE:
CLEANOUT DETAIL
Not To Scale4
6 SCALE:
REVERSE CURB & GUTTER DETAIL
NOT TO SCALE
6"
COMPACTED SUBGRADE
6 X 6 - W1.4 X W1.4 WWM @ MIDPOINT
OF CONCRETE THICKNESS
P.C. CONCRETE SIDEWALK
SLOPE (2% MAX.)
FINISHED
FLOOR
1/ 2"
PEA GRAVEL BACKFILL
GEOTEXTILE FABRIC 45°0'0"
5'
SUB-BASE GRANULAR
MATERIAL, TYPE B
4"
LIGHT BROOM FINISH
1/2" EXPANSION JOINT WITH SEALANT AND BACKER ROD
3'
1'
1'
NOTE:
APPLY DETAIL AT LEAST 2' BEYOND
DOORWAY THRESHOLD ON BOTH SIDES.
BUILDING EXTERIOR
ANCHOR GEOTEXTILE FABRIC
ANCHOR GEOTEXTILE FABRIC
CONTROL JOINT
5 SCALE:
DOOR THRESHOLD
NOT TO SCALE7 SCALE:
SEWER PIPE BEDDING DETAIL
NOT TO SCALE
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
DETAILS
C3.2
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
DETAILS
C3.3
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTED
SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE
CEILING FAN
QUADRUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
SINGLE RECEPTACLE
QUADRUPLEX RECEPTACLE
UTILITY KILOWATT-HOUR METER
DUPLEX RECEPTACLE - EMERGENCY POWER
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE - SPLIT WIRED
DUPLEX RECEPTACLE - ABOVE COUNTER
MAGNETIC STARTER
SAFETY SWITCH - FUSIBLE
SAFETY SWITCH - NON-FUSIBLE
EQUIPMENT - MOTOR CONNECTION
BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED
DISTRIBUTION PANELBOARD OR SWITCHBOARD
MOTOR CONTROL CENTER
BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED
CONTROL PANEL
TRANSFORMER
POWER
AUTOMATIC TRANSFER SWITCH
METER
CIRCUIT BREAKER
GROUND
ONE-LINE DIAGRAM
GENERATOR
DELTA-WYE TRANSFORMER
SWITCH
SERVICE DROP
HAND DRYER
CONDUIT - CAPPED
CABLE TRAY
SEALING FITTING
EXPANSION FITTING
CONDUIT FITTING (CONDULET)
JUNCTION BOX
CONDUIT - FLEXIBLE
CONDUIT - CONTINUED
CONDUIT - CONCEALED BELOW
SLAB OR GRADE
CONDUIT - UP AND DOWN
(CHANGE IN ELEVATION)
CONDUIT - TURNING UP
CONDUIT - EXPOSED
CONDUIT - CONCEALED IN
SUSPENDED CEILING OR WALL
CONDUIT - TURNING DOWN
REVISION CALL-OUT
ROOM NUMBER
FEEDER CALL-OUT
KEYNOTE
MECHANICAL EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
GENERAL
JUNCTION BOX - EMERGENCY POWER
FOOD SERVICE EQUIPMENT DESIGNATION
WIRING AND CONDUITS
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLITION EQUIPMENT (TYPICAL)
WALL MOUNT BRACKET (TYPICAL)
T-1
45 KVA 3Ø
480VAC
208Y/120VAC
# AF
# AT
# A
# A
G
ST
SPD
VFD
GROUND FAULT
PROTECTED BREAKER
SHUNT TRIP BREAKER
CONTACTOR
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
DRAWOUT CIRCUIT BREAKER# AF
# AT
FUSE
PANELBOARD
SURGE PROTECTION DEVICE
THERMAL OVERLOAD
VARIABLE FREQUENCY DRIVE
K KIRK KEY INTERLOCK
DPM DIGITAL POWER METER
QUADRUPLEX RECEPTACLE - ABOVE COUNTER
PP POWER POLE
Room name
101A
PLUMBING EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
J
J
M
G
# A
# POLES
PANEL
M
F
VFD
T
POLE MOUNTED TRANSFORMERT
J
H
DUPLEX RECEPTACLE (NEMA 5-20R)
C CONTROLLED
D DEDICATED
GFI GROUND FAULT CIRCUIT INTERRUPTER
HG HOSPITAL GRADE
IG ISOLATED GROUND TYPE
SS SURGE SUPPRESSOR
TR TAMPER RESISTANT
USB STANDARD DUPLEX WITH USB PORTS
WP WEATHERPROOF
XP EXPLOSION PROOF
FLOOR BOX - SEE SPECS OR KEYED NOTES ON
PLAN FOR DETAILS
COMBINATION STARTER
VFD VARIABLE FREQUENCY DRIVE
GROUND BAR
100A4G
# KVA/KW
480Y/277V, 3Ø, 4W
49 ELECTRONIC OVERLOAD
AHU
GWH1
ENCLOSED CIRCUIT BREAKERC
GENERATOR ANNUNCIATOR PANELGAP
J DEAD FRONT GFI WIRING DEVICE
GFI
B EMERGENCY POWER OFF PUSH BUTTON
AUTOMATIC TRANSFER SWITCHATS
SWITCH
TT MANUAL MOTOR SWITCH WITH THERMAL TRIP
GFI GFI FEED-THRU DEVICE
VARIABLE FREQUENCY DRIVEVFD
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:0
:4
A
M E0.1
GENERAL
INFORMATION
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:0
:4
A
M E0.2
GENERAL
INFORMATION
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
a. EXCEPTION: ALL RECESSED LUMINAIRES IN HARD CEILINGS SHALL HAVE FEED-THRU JUNCTION
BOXES.
6. MAXIMUM SIX FOOT FLEXIBLE LUMINAIRE WHIP SHALL BE USED FOR FINAL CONNECTIONS TO LIGHT FIXTURES INSTALLED IN LAY-IN CEILINGS. MAXIMUM FOUR LUMINAIRE WHIPS SHALL BE CONNECTED FROM ONE JUNCTION BOX. FEED THRU BETWEEN LUMINAIRES SHALL NOT BE ALLOWED.
5. NO SHARING OF NEUTRALS ALLOWED. CIRCUIT SHALL HAVE DEDICATED NEUTRAL CONDUCTORS.
ONE CIRCUIT, ONE NEUTRAL.
4. DERATING OF CONDUCTOR AMPACITY SHALL BE APPLIED PER NEC.
3. EACH RACEWAY SHALL CONTAIN AN INSULATED EQUIPMENT GROUNDING CONDUCTOR PER NEC.
2. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. #10 AWG SHALL BE USED FOR HOME RUNS OF 20 AMP
BRANCH CIRCUITS OVER 100 FEET IN LENGTH.
1. MINIMUM CONDUIT SIZE SHALL BE 3/4".
O. WHERE CONDUIT AND WIRING RUNS ARE NOT SHOWN ON FLOOR PLANS, THE CONTRACTOR SHALL DETERMINE AND PROVIDE THE REQUIRED CONDUIT AND WIRING FOR SPECIFIED CIRCUITING IN
ACCORDANCE WITH NEC AND THE FOLLOWING MINIMUM REQUIREMENTS:
N. ALL FLOOR MOUNTED SWITCH GEAR, UNIT SUBSTATIONS, BOXES AND TRANSFORMERS LARGER THAN 75 KVA SHALL BE INSTALLED ON A NOMINAL 4” HOUSEKEEPING PAD. PAD SHALL EXTEND FROM ELECTRICAL
EQUIPMENT 6” IN ANY DIRECTION.
M. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED
WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC.
L. CONTRACTOR SHALL NOT SCALE DRAWING FOR QUANTITIES. CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING ALL MEASUREMENTS.
K. HAZARDOUS AREAS: IN DESIGNATED ROOMS AND AREAS, IT IS NOT THE INTENT TO SHOW EACH EXPLOSION-PROOF COMPONENT, SUCH AS SEAL-OFFS, JUNCTION BOXES, ETC. THE CONTRACTOR SHALL COMPLETE ALL WORK IN STRICT COMPLIANCE WITH THE APPLICABLE ARTICLES 500 OF THE N.E.C.
3. PROVIDE A SEPARATE 120V CONTROL CIRCUIT FOR ELEVATOR CAR LIGHTS, ALARM, ETC.
2. PROVIDE A TELEPHONE OUTLET AND 120V POWER JUNCTION BOX IN LOCATION DESIGNATED BY THE
ELEVATOR SHOP DRAWINGS.
1. PROVIDE A TOGGLE SWITCH, 120V DUPLEX RECEPTACLE AND LUMINAIRE DOWN IN ELEVATOR PIT FOR
MAINTENANCE AND SERVICE (CONFIRM EXACT LOCATIONS PRIOR TO ROUGH-IN).
J. ELEVATOR SYSTEM: THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY, COORDINATE
AND CONFIRM WITH THE ELEVATOR EQUIPMENT INSTALLER ALL THE FOLLOWING:
I. PRIOR TO SUBMITTING BID PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS AND VISIT CONSTRUCTION SITE TO BE FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH THEY WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT.
NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR
FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
H. PROVIDE AND INSTALL IN EACH PANEL, TYPEWRITTEN NEAT TWO-COLUMN CIRCUIT INDEX CARD SET UNDER PLASTIC COVERS ON INSIDE OF DOORS. EACH ODD-NUMBERED CIRCUIT SHALL BE IN SEQUENCE ON ONE COLUMN AND THE EVEN-NUMBERED CIRCUITS ON THE OTHER COLUMN (E.G. 1,3,5...,2,4,6...).
EACH CIRCUIT SHALL BE IDENTIFIED AS TO THE USE AND ROOM NAME(S) OR AREA(S). THE CONTRACTOR
SHALL CONFIRM ROOM NAMES AND/OR ROOM NUMBERS WITH THE ARCHITECT PRIOR TO PROJECT
COMPLETION.
G. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEERS TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY
INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR
SUBSTITUTION AND ARE WITHIN THE PROPER TIME FRAME AS OUTLINED IN OTHER SECTIONS OF THIS
SPECIFICATION.
1. ALL PENETRATIONS OF FIRE-RESISTIVE FLOORS OR SHAFT WALLS SHALL BE PROTECTED BY MATERIALS AND INSTALLATION DETAILS THAT CONFORM TO UNDERWRITERS' LABORATORIES LISTINGS
FOR "THROUGH-PENETRATION FIRE STOP SYSTEMS." THE CONTRACTOR SHALL SUBMIT SHOP
DRAWING DETAILS, FURNISHED BY THE MANUFACTURER OF THE FIRE STOP MATERIAL, WHICH SHOW COMPLETE CONFORMANCE TO THE UL LISTING AND SHALL BE SPECIFIC FOR EACH PENETRATION WITH ALL VARIABLES DEFINED. THESE FINAL AND APPROVED DRAWINGS SHALL BE READILY AVAILABLE TO
THE LOCAL INSPECTORS AT ALL TIMES AT THE PROJECT SITE.
F. REFER TO ARCHITECTURAL PLANS TO CONFIRM ALL FIRE-RATED CEILINGS AND WALLS.
E. THE CONTRACTOR SHALL CONTACT AND OBTAIN FROM THE UTILITY COMPANY ALL INFORMATION, REQUIREMENTS, THEIR CONSTRUCTION DRAWINGS AND SPECIFICATIONS TO COMPLETE THE
ELECTRICAL PRIMARY/SECONDARY SERVICE TO THIS PROJECT. INCLUDE IN BASE BID, BUT NOT LIMIT TO, TRENCHING, BACKFILL, TRANSFORMER CONCRETE PAD, CONDUITS, METERING REQUIREMENTS, AND PROVIDE COMPLIANT EQUIPMENT IN THE CORRECT SEQUENCE, CONTRIBUTION COSTS, ENGINEERING
FEE AND SERVICE CHARGES FOR ALL ELECTRICAL SERVICES TO THIS PROJECT.
D. GROUT AND SEAL ALL CONDUIT PENETRATIONS OF WALLS AND FLOOR SLABS TO PRESERVE FIRE RATING
AND WATERTIGHT INTEGRITY.
C. COORDINATE SCHEDULE OF CONSTRUCTION WITH THE OWNER, OTHER TRADES AND UTILITIES INVOLVED BEFORE TRENCHING AND INSTALLATION OF UNDERGROUND CONDUIT. USE EXTREME CAUTION DURING EXCAVATION TO LOCATE EXISTING UNDERGROUND PIPING, CONDUITS, ETC. LOCATE AND PROTECT ANY
BURIED UTILITIES IN AREAS OF EXCAVATION.
B. PRIOR TO ROUGH-IN AND FINAL CONNECTION OF EQUIPMENT, VERIFY ELECTRICAL REQUIREMENTS OF
EQUIPMENT WITH OTHER TRADES CONSTRUCTION DOCUMENTS AND FINALIZED SHOP DRAWINGS.
VERIFICATION SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: VOLTAGE, AMPERAGE, TOTAL LOAD, OVER-CURRENT PROTECTION REQUIREMENTS, MOUNTING HEIGHT OF ELECTRICAL CONNECTION, CABLE TYPE AND SIZE, WIRING DIAGRAMS.
A. SEE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, ELEVATIONS, AND BUILDING DETAILS. VERIFY LOCATION OF ALL WALL OUTLETS, SWITCHES, ETC., WITH ARCHITECTURAL DRAWINGS AND ACTUAL
CONDITIONS.
COMMON REQUIREMENTS:
K. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING
HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
J. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE OWNER'S FACILITIES. NOTICE SHALL BE REQUIRED IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY OWNER. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY
TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
I. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.
H. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT
NECESSARY TO MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
G. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE
INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL
OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE
APPROVAL OF THE ARCHITECT AND/OR THE OWNER.
F. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED, THAT IT WILL NOT PROTRUDE BEYOND THE FINISHED SURFACE. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR
SHALL CUT AND CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
E. WHERE EXISTING LUMINAIRES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
D. OUTLETS FROM WHICH LUMINAIRES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE
COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
C. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS
AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND
CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR
REPLACE OLD WIRING WITH NEW.
B. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE. WHERE EXPOSED WORK IS REQUIRED IN FINISHED AREAS, THE CONTRACTOR SHALL USE WIREMOLD RACEWAY WITH #500 BEING
THE MINIMUM SIZE ACCEPTABLE.
1. DRAWINGS SHOW EXISTING CONDITIONS OF THE SITE. AN ATTEMPT HAS BEEN MADE TO SHOW EXISTING BUILDING, SITE DETAILS, ETC., BUT ACCURACY CANNOT BE GUARANTEED. VERIFY EXACT LOCATIONS OF ALL CIRCUITS, CONDUITS, PIPING, EQUIPMENT, ETC. VERIFY ALL SITE AND BUILDING
DETAILS.
A. RENOVATION OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN, ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, LUMINAIRES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY.
RENOVATION NOTES:
I. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO
REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
6. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR
OWNER'S REPRESENTATIVE.
5. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND
MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
4. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
3. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
2. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
1. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
H. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
G. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT
DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
F. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR
NEW DEVICES.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" LUMINAIRES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT
DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID
CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" LUMINAIRE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.
D. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE
ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.
C. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, LUMINAIRES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING
CIRCUIT CONTINUITY IS MAINTAINED.
B. REMOVE ALL EXISTING WIRING DEVICES, LUMINAIRES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING
WHICH REQUIRES CONTINUATION THROUGH THE AREA.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS
DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.
DEMOLITION:
%Z IMPEDANCE
(E) EXISTING (ALSO COVERED BY TEXT
WEIGHT)
(F) FUTURE
(PART) PARTIAL CIRCUIT
(R) RELOCATE
A AMPERES
AC 6" ABOVE COUNTER
ADA AMERICANS WITH DISABILITIES ACT
AF AMPERES FRAME
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTION CAPACITY
AL ALUMINUM
AT AMPERES TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAM CAMERA
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTER CLOCKWISE
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CO CONDUIT ONLY
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
CW CLOCKWISE
D DEDICATED
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DR DUPLEX RECEPTACLE
DWG DRAWING(S)
EC ELECTRICAL CONTRACTOR
ELC ELEVATOR CONTRACTOR
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
F FUSED
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FLA FULL LOAD AMPERES
FMC FLEXIBLE METAL CONDUIT
FO FIBER OPTIC
FPC FIRE PROTECTION CONTRACTOR
FS FUSED SWITCH
FSC FOOD SERVICE CONTRACTOR
FSD FIRE/SMOKE DAMPER
FT FOOT/FEET
FVNR FULL VOLTAGE, NON-REVERSING
FVR FULL VOLTAGE, REVERSING
G/GND GROUND/GROUNDING
GC GENERAL CONTRACTOR
GEN GENERATOR
GF GROUND FAULT
GFI/GFCI GROUND FAULT INTERRUPTER
H HORIZONTALLY MOUNTED
HG HOSPITAL GRADE
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HZ FREQUENCY
I/O INPUT/OUTPUT
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
ISC SHORT CIRCUIT CURRENT
JB JUNCTION BOX
K KELVIN (COLOR TEMPERATURE)
KCMIL 1000 CIRCULAR MILS
KV KILOVOLTS
KVA KILVOLT-AMPERES
KW KILOWATTS
KWH KILOWATT-HOUR
LAN LOCAL AREA NETWORK
LC LIGHTING CONTACTOR
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FOOT
LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT
LM LUMEN
LTG LIGHTING
LV LOW VOLTAGE
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
ABBREVIATIONSGENERAL NOTES
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MEPFP MECHANICAL, ELECTRICAL, PLUMBING,
FIRE PROTECTION
MGB MASTER GROUND BAR
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SWITCHBOARD
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MVA MEGAVOLT-AMPERES
MW MEGAWATT
MWH MEGAWATT-HOURS
N NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OWN OWNER
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH PHASE
PIR PASSIVE INFRARED
PLC PROGRAMMABLE LOGIC CONTROLLER
PNL PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWC PRE-WIRED CONTROLS
PWR POWER
RCPT RECEPTACLE
REQD REQUIRED
RF RADIO FREQUENCY
RM ROOM
RMC RIGID METAL CONDUIT
RNC RIGID NON-METALLIC CONDUIT (SCH 40)
RVAT REDUCED VOLTAGE -
AUTOTRANSFORMER
SC SHORT CIRCUIT
SCC SHORT CIRCUIT CURRENT RATING
SDP SUBDISTRIBUTION PANEL
SEC SECONDARY
SHLD SHIELD(ED) (AS IN CABLE)
SHT SHEET
SPD SURGE-PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SR SINGLE RECEPTACLE
SS SURGE SUPPRESSOR (ISOLATED
GROUND TYPE)
ST SHUNT TRIP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBD TO BE DETERMINED
TC TIMECLOCK
TCC TEMPERATURE CONTROLS
CONTRACTOR
TEMP TEMPERATURE
TR TAMPER RESISTANT
TT THERMAL TRIP SWITCH
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U UTILITY
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERUPTABLE POWER SUPPLY
USB STANDARD DUPLEX WITH 2 USB PORTS
V VOLTS
VA VOLT-AMPERES
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VND VENDOR
W WATTS
W WIRE
WHM WATTHOUR METER
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:0
:4
A
M E0.3
SPECIFICATIONS
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
A. THE WORK TO BE PERFORMED UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, TRANSPORTATION, CONSTRUCTION, FACILITIES, AND INCIDENTALS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF ALL ELECTRICAL WORK AS SHOWN AND INDICATED ON THE CONTRACT DRAWINGS, AND/OR HEREIN SPECIFIED WITH THE INTENT THAT THE INSTALLATION SHALL BE COMPLETE IN EVERY RESPECT, READY FOR USE. COMPLY WITH THE LATEST EDITION IN FORCE OF THE NFPA CODES INCLUDING THE NATIONAL ELECTRICAL CODE AND ALL APPLICABLE LOCAL, STATE, AND FEDERAL
CODES.
WORK INCLUDED
IDENTIFICATION PRODUCTS
GROUNDING PRODUCTS
SWITCHBOARDS
I-LINE PANELBOARDS
METER CENTERS
CT CABINETS
B. SUBMIT ELECTRONIC COPIES OF OPERATING AND MAINTENANCE MANUAL/RECORD DOCUMENTS.
MANUAL/RECORD DOCUMENTS SHALL CONSIST OF MANUFACTURER'S STANDARD PRODUCT DATA,
MANUFACTURER'S CURRENT PRINTED OPERATING AND MAINTENANCE INSTRUCTIONS, LIST OF ORIGINAL SPARE PARTS, LIST OF SUPPLIERS DISTRIBUTING SPARE PARTS, RECOMMENDED QUANTITIES TO BE MAINTAINED IN
STORAGE AND ALL WARRANTIES. MANUAL SHALL INCLUDE INFORMATION ON THE FOLLOWING:
IDENTIFICATION PRODUCTS
GROUNDING PRODUCTS
SWITCHBOARDS
I-LINE PANELBOARDS
METER CENTERS
CT CABINETS
A. SUBMIT ELECTRONIC COPIES OF PRODUCT DATA, SHOP DRAWINGS, WIRING DIAGRAMS AND LITERATURE ON SYSTEMS INDICATED BELOW. LITERATURE SHALL BE MARKED TO INDICATE THE SIZE, TYPE OR MODEL BEING
PROPOSED AND ALL ACCESSORIES TO BE PROVIDED.
SUBMITTALS
B. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEER'S TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR SUBSTITUTION AND ARE WITHIN
THE PROPER TIME FRAME AS OUTLINED IN OTHER SECTIONS OF THIS SPECIFICATION.
A. "APPROVED EQUAL" INDICATES THE SPECIFYING ENGINEER SHALL APPROVE ALL CONTRACTOR PROPOSED
ALTERNATE MATERIAL OR MANUFACTURERS. ENGINEER'S DECISION IS FINAL.
GENERAL
B. MANUFACTURER'S WARRANTY ON ALL EQUIPMENT SHALL BE FOR A TIME PERIOD OF ONE (1) YEAR FROM
SUBSTANTIAL COMPLETION UNLESS NOTED OTHERWISE.
A. CONTRACTOR'S WARRANTY ON COMPLETE ELECTRICAL INSTALLATION SHALL BE FOR A TIME PERIOD OF ONE
(1) YEAR FROM SUBSTANTIAL COMPLETION.
WARRANTY
B. COORDINATE INSTALLATION OF SERVICE ENTRANCE THOROUGHLY WITH UTILITY COMPANY. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS RELATED TO SERVICE ENTRANCE WORK, INCLUDING ANY CHARGES
FROM THE UTILITY COMPANY.
A. IN GENERAL, COORDINATE WORK THOROUGHLY WITH OTHER TRADES, OWNER AND UTILITY COMPANIES TO
PROVIDE EFFICIENT FLOW OF THE WORK AND TIMELY COMPLETION OF THE CONTRACT.
COORDINATION
C. "APPROVED EQUAL" INDICATES THE SPECIFYING ENGINEER SHALL APPROVE ALL CONTRACTOR PROPOSED
ALTERNATE MATERIAL OR MANUFACTURERS. ENGINEER'S DECISION IS FINAL.
B. IDENTIFICATION: LAMINATED PLASTIC LABELS ON ALL EQUIPMENT, SWITCHES, CONTROLS, ETC.
A. IN GENERAL ALL MATERIALS SHALL BE: NEW, U.L. LISTED FOR THE SPECIFIC APPLICATION AS SPECIFIED OR AS
REQUIRED, AND INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
BASIC MATERIALS
E. CONTRACTOR SHALL RESTORE ALL DISTURBED AREAS TO EXISTING CONDITIONS INCLUDING, BUT NOT LIMITED
TO, SODDING AND REMOVAL/REPLACEMENT OF EXISTING PLANTINGS.
D. PROVIDE UNDERGROUND WARNING TAPE AT 12 INCH DEPTH. TAPE SHALL BE MADE OF ACID AND ALKALI RESISTANT POLYTHENE FILM, SIX INCHES WIDE, AND READ "CAUTION BURIED ELECTRICAL LINE" OVER ENTIRE
LENGTH.
C. OTHER AREAS: USE EXCAVATED OR BORROWED MATERIALS FREE OF DEBRIS. NEATLY MOUND MATERIALS TO
COMPENSATE FOR LATER SETTLEMENT.
B. UNDER SIDEWALKS AND PAVED AREAS, BACKFILL ALL TRENCHES WITH COMPACTED, CLEAN, WASHED, GRANULAR BACKFILL COMPACTED TO NOT LESS THAN 100% OF STANDARD PROCTOR MAXIMUM DRY DENSITY.
A. TRENCHES SHALL BE EXCAVATED TO UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE WORKING ROOM AND MINIMUM OF 6" TO 9" INCHES ON BOTH SIDES OF CONDUIT. CONDUIT SHALL BE 24" MINIMUM BELOW
FINISHED GRADE.
EXCAVATION AND BACKFILL
N. PROVIDE CONDUIT SEALING FITTINGS IN ACCORDANCE WITH NEC AND WHERE INDICATED ON DRAWINGS.
LOCATE FITTINGS AT SUITABLE, APPROVED, ACCESSIBLE LOCATIONS AND FILL WITH U.L. LISTED SEALING COMPOUND. INSTALL SEALING FITTINGS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS.
M. WHEN NOTED ON DRAWINGS, CONDUIT SHALL BE INSTALLED EXPOSED WITH CONDUIT PARALLEL TO AND AT
RIGHT ANGLES TO NEARBY SURFACES OR STRUCTURAL MEMBERS.
L. CONDUIT SHALL BE INSTALLED CONCEALED UNLESS NOTED OTHERWISE ON DRAWINGS.
K. LT CONDUIT SHALL BE USED FOR CONNECTION TO VIBRATING EQUIPMENT IN OUTDOOR LOCATIONS, IN DAMP OR WET INDOOR LOCATIONS, HAZARDOUS LOCATIONS, OR WHERE REQUIRED BY NEC AND WHERE NOTED ON
THE DRAWINGS.
J. FLEXIBLE METAL CONDUIT SHALL BE USED FOR CONNECTION TO VIBRATING EQUIPMENT IN INDOOR DRY LOCATIONS, FOR CONNECTION TO INDOOR RECESSED LIGHT FIXTURES (SIX FOOT MAXIMUM LENGTH), WHERE
REQUIRED BY NEC AND WHERE NOTED ON DRAWINGS.
I. PVC CONDUIT SHALL BE USED IN UNDERGROUND INSTALLATIONS, BELOW CONCRETE FLOOR SLAB (WITH RGS
CONDUIT STUB UPS), WHERE REQUIRED BY NEC AND WHERE NOTED ON THE DRAWINGS.
H. RGS CONDUIT SHALL BE USED IN OUTDOOR EXPOSED LOCATIONS, INDOOR DAMP OR WET LOCATIONS, HAZARDOUS LOCATIONS, OR WHERE REQUIRED BY NEC AND WHERE NOTED ON DRAWINGS.
G. EMT MAY BE USED WHERE PERMITTED BY NEC EXCEPT WHERE OTHER TYPE IS SPECIFIED HEREIN OR NOTED
ON DRAWINGS.
F. MINIMUM CONDUIT SIZE SHALL BE 3/4".
E. LIQUIDTIGHT FLEXIBLE METAL (LT) CONDUIT: FLEXIBLE STEEL CONDUIT WITH PVC JACKET WITH APPROVED FITTINGS, SIZED AS SHOWN ON DRAWINGS OR IF NOT SIZED ON THE DRAWINGS, IN ACCORDANCE WITH NEC
AND OTHER APPLICABLE PORTIONS OF THE CONTRACT DOCUMENTS.
D. FLEXIBLE METAL CONDUIT: FLEXIBLE STEEL CONDUIT WITH ZINC COATING AND APPROVED FITTINGS, SIZED AS SHOWN ON DRAWINGS OR IF NOT SIZED ON THE DRAWINGS, IN ACCORDANCE WITH NEC AND OTHER
APPLICABLE PORTIONS OF THE CONTRACT DOCUMENTS.
C. RIGID NON-METALLIC (PVC) CONDUIT: SCHEDULE 40 PVC TYPE COMPLYING WITH NEMA TC2, U.L. 651, AND ARTICLE 347 OF NEC. FITTINGS SHALL BE PVC, CHEMICAL SOLVENT SEALING TYPE. SIZED AS SHOWN ON THE DRAWINGS OR IF NOT SIZED ON THE DRAWINGS, IN ACCORDANCE WITH NEC AND OTHER APPLICABLE
PORTIONS OF THE CONTRACT DOCUMENTS.
B. RIGID GALVANIZED STEEL (RGS) CONDUIT: COMPLYING WITH ANSI C80.1, THREADED CONDUIT WITH APPROVED FITTINGS, SIZED AS SHOWN ON DRAWINGS OR IF NOT SIZED ON THE DRAWINGS, IN ACCORDANCE WITH NEC
AND OTHER APPLICABLE PORTIONS OF THE CONTRACT DOCUMENTS.
A. ELECTRICAL METALLIC TUBING (EMT): COMPLYING WITH ANSI C80.3 WITH COMPRESSION TYPE FITTINGS, SIZED AS SHOWN ON DRAWINGS OR IF NOT SIZED ON THE DRAWINGS, IN ACCORDANCE WITH NEC AND OTHER
APPLICABLE PORTIONS OF CONTRACT DOCUMENTS.
CONDUIT
4. BE U.L. LISTED AND LABELED FOR THEIR APPLICATION.
3. BE OF PROPER SIZE AND SHAPE FOR CONDUITS ENTERING THEM.
2. BE NEMA TYPE 3R OR NEMA TYPE 4 FOR INDOOR DAMP OR WET LOCATIONS AND OUTDOOR LOCATIONS.
1. BE NEMA TYPE 1 FOR INDOOR DRY LOCATIONS.
B. ALL PULL/JUNCTION BOXES AND ENCLOSURES SHALL:
4. BE CAST TYPE FOR EXPOSED WORK BELOW 10'-0" AFF.
3. BE U.L. LISTED AND NEC RATED FOR THEIR APPLICATION.
2. BE OF PROPER SIZE AND SHAPE…
This is the start of the file's text. The full file is on GovTribe.