Addendum_2_Plan_Sheets.pdf

PDF 896 KB Posted

Attached to
Public Works EV Charging Electrical Upgrades
Solicitation number
FY2026-ITB-152
Issued by
Champaign County, Illinois

About this file

This document is a bid/permit set for the Urbana Public Works EV Charging Electrical Upgrades project located at 704 S. Glover Avenue in Urbana, Illinois. The project involves installing electric vehicle (EV) charging stations, with provisions for ten charging stations - five currently active (EVC 01, 03, 05, 07, 09) and five future stations (marked with (F) prefix). The electrical upgrades include a new main switchboard (SWB) with a 1200A MCB rated at 208/120V, three-phase, four-wire configuration. The site plan details the layout of charging stations, electrical infrastructure, and site grading, with specific instructions for field verification of exact charger locations.

The electrical service responsibility schedule indicates that both furnishing and installation of key components like transformers, conduits, conductors, and EV chargers will be handled by the Electrical Contractor (EC). The project includes utility coordination for new electric service from existing utility poles, secondary service to the building, and provisions for future electrical service to a potential new addition. The one-line diagrams show existing and proposed electrical configurations, with detailed feeder schedules and load classifications. The project appears to be funded through municipal infrastructure improvements, with a focus on expanding electric vehicle charging capabilities for the Urbana Public Works facility.

View the file

Other files

File Type Posted
Public_Works_EV_Charging_Electrical_Upgrades_(Addendum_#2_Revision).pdf PDF
Addendum_2_Project_Manual_Pages.pdf PDF
Bid_Bond_Form_(AIA_A310).pdf PDF
Project_Manual.pdf PDF
Plans.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

2211 W. BRADLEY AVENUE

CHAMPAIGN, ILLINOIS 61821

(217) 352-7408 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:4

:2

A

M E0.2

GENERAL

INFORMATION

DGM

WRK

02500543.001

Urbana Public Works EV Charging Electrical Upgrades

City of Urbana

704 S Glover Avenue Urbana Illinois 61802

8/15/2025

08/15/2025

BID/PERMIT SET

TJS

BID/PERMIT SET

a. EXCEPTION: ALL RECESSED LUMINAIRES IN HARD CEILINGS SHALL HAVE FEED-THRU JUNCTION

BOXES.

6. MAXIMUM SIX FOOT FLEXIBLE LUMINAIRE WHIP SHALL BE USED FOR FINAL CONNECTIONS TO LIGHT FIXTURES INSTALLED IN LAY-IN CEILINGS. MAXIMUM FOUR LUMINAIRE WHIPS SHALL BE CONNECTED FROM ONE JUNCTION BOX. FEED THRU BETWEEN LUMINAIRES SHALL NOT BE ALLOWED.

5. NO SHARING OF NEUTRALS ALLOWED. CIRCUIT SHALL HAVE DEDICATED NEUTRAL CONDUCTORS.

ONE CIRCUIT, ONE NEUTRAL.

4. DERATING OF CONDUCTOR AMPACITY SHALL BE APPLIED PER NEC.

3. EACH RACEWAY SHALL CONTAIN AN INSULATED EQUIPMENT GROUNDING CONDUCTOR PER NEC.

2. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. #10 AWG SHALL BE USED FOR HOME RUNS OF 20 AMP

BRANCH CIRCUITS OVER 100 FEET IN LENGTH.

1. MINIMUM CONDUIT SIZE SHALL BE 3/4".

N. WHERE CONDUIT AND WIRING RUNS ARE NOT SHOWN ON FLOOR PLANS, THE CONTRACTOR SHALL DETERMINE AND PROVIDE THE REQUIRED CONDUIT AND WIRING FOR SPECIFIED CIRCUITING IN

ACCORDANCE WITH NEC AND THE FOLLOWING MINIMUM REQUIREMENTS:

M. ALL FLOOR MOUNTED SWITCH GEAR, UNIT SUBSTATIONS, BOXES AND TRANSFORMERS LARGER THAN 75 KVA SHALL BE INSTALLED ON A NOMINAL 4” HOUSEKEEPING PAD. PAD SHALL EXTEND FROM ELECTRICAL

EQUIPMENT 6” IN ANY DIRECTION.

L. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED

WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC.

K. CONTRACTOR SHALL NOT SCALE DRAWING FOR QUANTITIES. CONTRACTOR IS RESPONSIBLE FOR FIELD

VERIFYING ALL MEASUREMENTS.

J. HAZARDOUS AREAS: IN DESIGNATED ROOMS AND AREAS, IT IS NOT THE INTENT TO SHOW EACH EXPLOSION-PROOF COMPONENT, SUCH AS SEAL-OFFS, JUNCTION BOXES, ETC. THE CONTRACTOR SHALL COMPLETE ALL WORK IN STRICT COMPLIANCE WITH THE APPLICABLE ARTICLES 500 OF THE N.E.C.

I. PRIOR TO SUBMITTING BID PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS AND VISIT CONSTRUCTION SITE TO BE FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH THEY WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT.

NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR

FOR ANY ERROR OR NEGLIGENCE ON HIS PART.

H. PROVIDE AND INSTALL IN EACH PANEL, TYPEWRITTEN NEAT TWO-COLUMN CIRCUIT INDEX CARD SET UNDER PLASTIC COVERS ON INSIDE OF DOORS. EACH ODD-NUMBERED CIRCUIT SHALL BE IN SEQUENCE ON ONE COLUMN AND THE EVEN-NUMBERED CIRCUITS ON THE OTHER COLUMN (E.G. 1,3,5...,2,4,6...).

EACH CIRCUIT SHALL BE IDENTIFIED AS TO THE USE AND ROOM NAME(S) OR AREA(S). THE CONTRACTOR

SHALL CONFIRM ROOM NAMES AND/OR ROOM NUMBERS WITH THE ARCHITECT PRIOR TO PROJECT

COMPLETION.

G. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEERS TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY

INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR

SUBSTITUTION AND ARE WITHIN THE PROPER TIME FRAME AS OUTLINED IN OTHER SECTIONS OF THIS

SPECIFICATION.

1. ALL PENETRATIONS OF FIRE-RESISTIVE FLOORS OR SHAFT WALLS SHALL BE PROTECTED BY MATERIALS AND INSTALLATION DETAILS THAT CONFORM TO UNDERWRITERS' LABORATORIES LISTINGS

FOR "THROUGH-PENETRATION FIRE STOP SYSTEMS." THE CONTRACTOR SHALL SUBMIT SHOP

DRAWING DETAILS, FURNISHED BY THE MANUFACTURER OF THE FIRE STOP MATERIAL, WHICH SHOW COMPLETE CONFORMANCE TO THE UL LISTING AND SHALL BE SPECIFIC FOR EACH PENETRATION WITH ALL VARIABLES DEFINED. THESE FINAL AND APPROVED DRAWINGS SHALL BE READILY AVAILABLE TO

THE LOCAL INSPECTORS AT ALL TIMES AT THE PROJECT SITE.

F. REFER TO ARCHITECTURAL PLANS TO CONFIRM ALL FIRE-RATED CEILINGS AND WALLS.

E. THE CONTRACTOR SHALL CONTACT AND OBTAIN FROM THE UTILITY COMPANY ALL INFORMATION, REQUIREMENTS, THEIR CONSTRUCTION DRAWINGS AND SPECIFICATIONS TO COMPLETE THE

ELECTRICAL PRIMARY/SECONDARY SERVICE TO THIS PROJECT. INCLUDE IN BASE BID, BUT NOT LIMIT TO, TRENCHING, BACKFILL, TRANSFORMER CONCRETE PAD, CONDUITS, METERING REQUIREMENTS, AND PROVIDE COMPLIANT EQUIPMENT IN THE CORRECT SEQUENCE, CONTRIBUTION COSTS, ENGINEERING

FEE AND SERVICE CHARGES FOR ALL ELECTRICAL SERVICES TO THIS PROJECT.

D. GROUT AND SEAL ALL CONDUIT PENETRATIONS OF WALLS AND FLOOR SLABS TO PRESERVE FIRE RATING

AND WATERTIGHT INTEGRITY.

C. COORDINATE SCHEDULE OF CONSTRUCTION WITH THE OWNER, OTHER TRADES AND UTILITIES INVOLVED BEFORE TRENCHING AND INSTALLATION OF UNDERGROUND CONDUIT. USE EXTREME CAUTION DURING EXCAVATION TO LOCATE EXISTING UNDERGROUND PIPING, CONDUITS, ETC. LOCATE AND PROTECT ANY

BURIED UTILITIES IN AREAS OF EXCAVATION.

B. PRIOR TO ROUGH-IN AND FINAL CONNECTION OF EQUIPMENT, VERIFY ELECTRICAL REQUIREMENTS OF

EQUIPMENT WITH OTHER TRADES CONSTRUCTION DOCUMENTS AND FINALIZED SHOP DRAWINGS.

VERIFICATION SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: VOLTAGE, AMPERAGE, TOTAL LOAD, OVER-CURRENT PROTECTION REQUIREMENTS, MOUNTING HEIGHT OF ELECTRICAL CONNECTION, CABLE TYPE AND SIZE, WIRING DIAGRAMS.

A. SEE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, ELEVATIONS, AND BUILDING DETAILS. VERIFY LOCATION OF ALL WALL OUTLETS, SWITCHES, ETC., WITH ARCHITECTURAL DRAWINGS AND ACTUAL

CONDITIONS.

COMMON REQUIREMENTS:

K. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING

HARDWARE TO ACCOMPLISH THIS REQUIREMENT.

J. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE OWNER'S FACILITIES. NOTICE SHALL BE REQUIRED IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY OWNER. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY

TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.

I. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.

H. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT

NECESSARY TO MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.

G. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE

INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL

OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE

APPROVAL OF THE ARCHITECT AND/OR THE OWNER.

F. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED, THAT IT WILL NOT PROTRUDE BEYOND THE FINISHED SURFACE. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR

SHALL CUT AND CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

E. WHERE EXISTING LUMINAIRES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.

D. OUTLETS FROM WHICH LUMINAIRES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE

COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.

C. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS

AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND

CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR

REPLACE OLD WIRING WITH NEW.

B. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE. WHERE EXPOSED WORK IS REQUIRED IN FINISHED AREAS, THE CONTRACTOR SHALL USE WIREMOLD RACEWAY WITH #500 BEING

THE MINIMUM SIZE ACCEPTABLE.

1. DRAWINGS SHOW EXISTING CONDITIONS OF THE SITE. AN ATTEMPT HAS BEEN MADE TO SHOW EXISTING BUILDING, SITE DETAILS, ETC., BUT ACCURACY CANNOT BE GUARANTEED. VERIFY EXACT LOCATIONS OF ALL CIRCUITS, CONDUITS, PIPING, EQUIPMENT, ETC. VERIFY ALL SITE AND BUILDING

DETAILS.

A. RENOVATION OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN, ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, LUMINAIRES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY.

RENOVATION NOTES:

I. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO

REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

6. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR

OWNER'S REPRESENTATIVE.

5. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND

MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.

4. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

3. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

2. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

1. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

H. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

G. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT

DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

F. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR

NEW DEVICES.

E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" LUMINAIRES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT

DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID

CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" LUMINAIRE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.

D. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE

ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.

C. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, LUMINAIRES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING

CIRCUIT CONTINUITY IS MAINTAINED.

B. REMOVE ALL EXISTING WIRING DEVICES, LUMINAIRES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING

WHICH REQUIRES CONTINUATION THROUGH THE AREA.

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS

DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.

DEMOLITION:

%Z IMPEDANCE

(E) EXISTING (ALSO COVERED BY TEXT

WEIGHT)

(F) FUTURE

(PART) PARTIAL CIRCUIT

(R) RELOCATE

A AMPERES

AC 6" ABOVE COUNTER

ADA AMERICANS WITH DISABILITIES ACT

AF AMPERES FRAME

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERES INTERRUPTION CAPACITY

AL ALUMINUM

AT AMPERES TRIP

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAM CAMERA

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTER CLOCKWISE

CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CO CONDUIT ONLY

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

CW CLOCKWISE

D DEDICATED

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DPDT DOUBLE POLE DOUBLE THROW

DPST DOUBLE POLE SINGLE THROW

DR DUPLEX RECEPTACLE

DWG DRAWING(S)

EC ELECTRICAL CONTRACTOR

ELC ELEVATOR CONTRACTOR

ELEC ELECTRIC/ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

F FUSED

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FLA FULL LOAD AMPERES

FMC FLEXIBLE METAL CONDUIT

FO FIBER OPTIC

FPC FIRE PROTECTION CONTRACTOR

FS FUSED SWITCH

FSC FOOD SERVICE CONTRACTOR

FSD FIRE/SMOKE DAMPER

FT FOOT/FEET

FVNR FULL VOLTAGE, NON-REVERSING

FVR FULL VOLTAGE, REVERSING

G/GND GROUND/GROUNDING

GC GENERAL CONTRACTOR

GEN GENERATOR

GF GROUND FAULT

GFI/GFCI GROUND FAULT INTERRUPTER

H HORIZONTALLY MOUNTED

HG HOSPITAL GRADE

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTO

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HZ FREQUENCY

I/O INPUT/OUTPUT

ID INSIDE DIAMETER

IDF INTERMEDIATE DISTRIBUTION FRAME

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

ISC SHORT CIRCUIT CURRENT

JB JUNCTION BOX

K KELVIN (COLOR TEMPERATURE)

KCMIL 1000 CIRCULAR MILS

KV KILOVOLTS

KVA KILVOLT-AMPERES

KW KILOWATTS

KWH KILOWATT-HOUR

LAN LOCAL AREA NETWORK

LC LIGHTING CONTACTOR

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FOOT

LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT

LM LUMEN

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPERES

MCB MAIN CIRCUIT BREAKER

ABBREVIATIONSGENERAL NOTES

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MDF MAIN DISTRIBUTION FRAME

MDP MAIN DISTRIBUTION PANEL

MEPFP MECHANICAL, ELECTRICAL, PLUMBING,

FIRE PROTECTION

MGB MASTER GROUND BAR

MH METAL HALIDE

MIN MINIMUM

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MSB MAIN SWITCHBOARD

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MVA MEGAVOLT-AMPERES

MW MEGAWATT

MWH MEGAWATT-HOURS

N NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NF NON-FUSED

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NP NAMEPLATE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OWN OWNER

P POLE

PA PUBLIC ADDRESS

PB PULL BOX

PC PLUMBING CONTRACTOR

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PLC PROGRAMMABLE LOGIC CONTROLLER

PNL PANEL

PR PAIR

PRI PRIMARY

PT POTENTIAL TRANSFORMER

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWC PRE-WIRED CONTROLS

PWR POWER

RCPT RECEPTACLE

REQD REQUIRED

RF RADIO FREQUENCY

RM ROOM

RMC RIGID METAL CONDUIT

RNC RIGID NON-METALLIC CONDUIT (SCH 40)

RVAT REDUCED VOLTAGE -

AUTOTRANSFORMER

SC SHORT CIRCUIT

SCC SHORT CIRCUIT CURRENT RATING

SDP SUBDISTRIBUTION PANEL

SEC SECONDARY

SHLD SHIELD(ED) (AS IN CABLE)

SHT SHEET

SPD SURGE-PROTECTIVE DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPST SINGLE POLE SINGLE THROW

SR SINGLE RECEPTACLE

SS SURGE SUPPRESSOR (ISOLATED

GROUND TYPE)

ST SHUNT TRIP

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TBD TO BE DETERMINED

TC TIMECLOCK

TCC TEMPERATURE CONTROLS

CONTRACTOR

TEMP TEMPERATURE

TR TAMPER RESISTANT

TT THERMAL TRIP SWITCH

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

U UTILITY

UG UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERUPTABLE POWER SUPPLY

USB STANDARD DUPLEX WITH 2 USB PORTS

V VOLTS

VA VOLT-AMPERES

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

VFD VARIABLE FREQUENCY DRIVE

VND VENDOR

W WATTS

W WIRE

WHM WATTHOUR METER

WP WEATHERPROOF

XFMR TRANSFORMER

XP EXPLOSION PROOF

1 08/22/2025 ADD 02

M

T

F J J J J J J J J J J

SWB

4'-4 3/8"

9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 19'-6 1/8"

CT/PT

2EVC

SWB-15

T-704

SWB-16

(F)EVC

EVC

(F)EVC

EVC

(F)EVC

EVC

(F)EVC

EVC

(F)EVC

SWB-17 SWB-18

SWB-19 SWB-20

SWB-21

SWB-22 SWB-23 SWB-24

5 1 5 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

2211 W. BRADLEY AVENUE

CHAMPAIGN, ILLINOIS 61821

(217) 352-7408 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:4

:3

A

M E2.1

FIRST FLOOR POWER

PLAN

DGM

WRK

02500543.001

Urbana Public Works EV Charging Electrical Upgrades

City of Urbana

704 S Glover Avenue Urbana Illinois 61802

8/15/2025

08/15/2025

BID/PERMIT SET

TJS

BID/PERMIT SET

0 4 8 16

NORTH

PLAN

A. NOT USED

GENERAL NOTES

SCALE: 1/8" = 1'-0"

FIRST FLOOR POWER PLAN

#KEYNOTES

1 PROVIDE ELECTRIC VEHICLE CHARGER FROM ONE OF THE THREE SHORT LISTED

VENDORS BELOW. ELECTRIC VEHICLE CHARGER SHALL MEET THE CITY'S

SPECIFICATION:

(1) CHARGRPOINT CPF50 WALL MOUNTED SINGLE PORT WITH 23' CABLE.

(2) FORD PRO AC CHARGING STATION 48A SERIES 2, WALL MOUNTED, SINGLE PORT.

(3) FRACTALEV 80A CHARGING STATION, WALL MOUNTED, SINGLE PORT.

2 PROVIDE NEW SWITCHBOARD. VERIFY DIMENSIONS OF SPACE AND OF

SWITCHBOARD PRIOR TO ORDERING AND INSTALLATION. IF SWITCHBOARD DOES

NOT FIT IN EXISTING SPACE, CONTACT THE ENGINEER TO DETERMINE A NEW

LOCATION.

3 EXISTING UTILITY POLE.

4 EXISTING PANELBOARDS ARE NOT SHOWN WITHIN THE BUILDING. CONTRACTOR TO

VERIFY PANELBOARD LOCATIONS AND RATED VOLTAGES. IF ANY EQUIPMENT OR

PANELS HAVE RATING ISSUES WITH THE NEW SYSTEM, THE CONTRACTOR IS TO

CONTACT THE ENGINEER.

5 FUTURE ELECTRIC VEHICLE CHARGING LOCATION. PROVIDE CONDUIT AND PULL

STRING BACK TO SWB. PROVIDE BACK BOX ON EXTERIOR WALL. INSTALLATION

SHALL BE THE SAME AS THE NEW ELECRTIC VEHICLE CHARGERS AND BE MADE

WATER TIGHT. LABEL BACK BOX WITH TAG INFORMATION FROM PLANS AND NOTE

WHERE CONDUIT TERMINATES.

6 VERIFY LOCATION OF TRANSFORMER IN FIELD AND WITH CIVIL SITE PLANS.

7 PROVIDE JUNCTION BOX WHERE EXISTING PANELBAORD WAS LOCATED FOR

RE-CONNECTION OF EXISTING PANELS TO NEW SWB.

REMARKS:

R MAIN SWITCHBOARD EC EC -

Q EUSERC CABINET N/A N/A -

P WIRING TERMINATIONS AT METERING EQUIPMENT EC EC -

O CONDUIT FROM TRANSFORMER TO METER EC EC -

N METER SOCKETS EC EC -

M METERS U U -

L C.T. CABINETS EC EC -

K C.T.'S U U -

J SECONDARY CONDUCTORS TO MAIN SWITCHBOARD EC EC -

I SECONDARY CONDUIT(S) TO MAIN SWITCHBOARD EC EC -

H PRIMARY CONDUCTORS U U -

G MANHOLES N/A N/A -

F PRIMARY CONDUIT(S) & DUCT BANK EC EC -

E TRENCHING FROM UTILITY POLE TO TRANSFORMER EC EC -

D BUMPER POSTS (BOLLARDS) OWNER OWNER -

C NEW TRANSFORMER U U -

B NEW TRANSFORMER BASE U U -

A TRANSFORMER SITE COMPACTION EC EC -

ITEM DESCRIPTION FURNISHED BY INSTALLED BY REMARKS

NEW ELECTRICAL SERVICE RESPONSIBILITY SCHEDULE

EQUIPMENT DATA SCHEDULE

DESCRIPTION LOAD DATA

WIRE & CONDUIT REMARKS

MARK EQUIPMENT

F U

R N

IS

H

E D

B Y

IN

S

T A

L L

E D

B Y

LOCATION

L O

A D

V O

L T

A G

E

P H

A S

E

EVC 01 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C

(F)EVC 02 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1

EVC 03 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C

(F)EVC 04 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1

EVC 05 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C

(F)EVC 06 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1

EVC 07 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C

(F)EVC 08 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1

EVC 09 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C

(F)EVC 10 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1

1. PROVIDE ROUGH IN FOR FUTURE CHARGING STATION. PROVIDE CONDUIT AS NOTED AND PULL STRING BACK TO SWB.

REMARKS:

A. NONE

GENERAL NOTES:

EQUIPMENT DATA NOTES:

1 08/22/2025 ADD 02

SITE 704

EXISTING UTILITY

TRANSFORMER

POLE MOUNTED

SEC: 120/240 3P 4W

400AS

400AF

200AT

800AT

PANEL

XX

50AT

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

SPACE SPACE

100AT 200AT 100AT 200AT 100AT 100AT 100AT 70AT 50AT 70AT 70AT 50AT

SITE 704

T-704

UTILITY TRANSFORMER

PAD MOUNTED 500KVA

SEC: 208Y/120VAC 3P 4W

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XX

PANEL

XXGROUND

NEUTRAL

M1200 A

AL1200A4G

AL1200A4

J J

EVC

EXISTING UTILITY

TRANSFORMER

POLE MOUNTED

SEC: 120/240 3P 4W

UTIL

1200 AS

1200 AF

J J J J J J J J

(F)EVC

EVC

EVC

EVC

EVC

2 2 2 2 2 2 2 2 2 2 2 22

100A3G

GEN CAM LOCK

CONNECTION

100 A

3 POLES

100 A

3 POLES

100 AF

100 AT

200 AF

200 AT

SWB

5 3 5 3 5 3 5

(F)EVC

(F)EVC

(F)EVC

(F)EVC

66666 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

2211 W. BRADLEY AVENUE

CHAMPAIGN, ILLINOIS 61821

(217) 352-7408 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:4

:3

A

M E4.1

ONE-LINE DIAGRAM

DGM

WRK

02500543.001

Urbana Public Works EV Charging Electrical Upgrades

City of Urbana

704 S Glover Avenue Urbana Illinois 61802

8/15/2025

08/15/2025

BID/PERMIT SET

TJS

BID/PERMIT SET

A. ALTERNATE BID #2: PROVIDE POWER SYSTEMS STUDY PER SPECIFICATION 26 05 73.

WITH REGARDS TO SPECIFICATION FOR

POWER SYSTEMS STUDIES (260573):

SCALE: 12" = 1'-0"

EXISTING ONE-LINE DIAGRAM

SCALE: 12" = 1'-0"

PROPOSED ONE-LINE DIAGRAM

2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.

1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED

NOTES:

TOTAL DEMAND CURRENT: 278 A

TOTAL CONNECTED CURRENT: 278 A

TOTAL DEMAND: 100000 VA

TOTAL CONNECTED LOAD: 100000 VA

HVAC 100000 VA 100.00% 100000 VA

Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS

TOTAL AMPS: 481 A 481 A 0 A

TOTAL CONNECTED LOAD: 50000 VA 50000 VA 0 VA

24 (F)EVC-10 250 A 100 A 2 0 VA 0 VA

23 HVAC 250 A 100 A 2 10000 VA 10000 VA

22 (F)EVC-08 250 A 100 A 2 0 VA 0 VA

21 HVAC 250 A 100 A 2 10000 VA 10000 VA

20 (F)EVC-06 250 A 100 A 2 0 VA 0 VA

19 EVC-05 250 A 100 A 2 10000 VA 10000 VA

18 (F)EVC-04 250 A 100 A 2 0 VA 0 VA

17 EVC-03 250 A 100 A 2 10000 VA 10000 VA

16 (F)EVC-02 250 A 100 A 2 0 VA 0 VA

15 EVC-01 250 A 100 A 2 10000 VA 10000 VA

14 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA

13 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA

12 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA

11 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA

10 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA

9 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA

8 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA

7 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA

6 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA

5 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA

4 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA

3 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA

2 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA

1 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA

ITEM NO. Load Name Frame Rating Sched ule Circu...

Numb er of Poles

A B C REMARKS

MAIN: 1200 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N

RATED AMPERAGE: 1200 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N

PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): 65kA MCB GROUND FAULT PROTECTION (Y/N): N

VOLTAGE: 208/120V SCC RATING (SYM): 65kA MOUNTING: PAD

SWITCHBOARD SWB

FEEDER SCHEDULE

MARK

CONDUIT & CONDUCTORS

(SEE NOTE 1) REMARKS

100A3G 3#1, 1#8G, 1-1/2"C

AL1200A4 4 SETS (4#500, 3-1/2"C) SEE NOTE 2

AL1200A4G 4 SETS (4#500, 1#250G, 3-1/2"C) SEE NOTE 2

UTIL (2) 2"C

2. FEEDERS MARKED WITH AN "AL" ARE ALUMINUM CONDUCTORS.

1. THIS FEEDER SCHEDULE IS BASED ON 60 DEGREE CENTIGRADE (TYPE TW) WIRE AND

TERMINATIONS FOR SIZES #12 TO #1, AND 75 DEGREE CENTIGRADE (TYPE

THHN/THWN) WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS NOTED

OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF OTHER

CONDUIT TYPES REQUIRES RESIZING OF CONDUIT.

REMARKS:

KEYNOTES

1 PROVIDE CONNECTION TO EXISTING BUILDING GROUNDING SYSTEM. SEE DETAILS.

2 RECONNECT EXISTING FEEDER FROM EXISTING PANELBOARD TO NEW CIRCUIT

BREAKER IN NEW SWITCHBOARD.

3 SEE E2.1 FOR BRANCH CIRCUIT SIZES.

4 EXISTING 706 BUILDING POWER FEED. NO WORK ASSOCIATED WITH THIS BUILDING,

SHOWN FOR REFERENCE ONLY.

5 PROVIDE CONDUIT AND ROUGH-IN FOR FUTURE CHARGING STATION. SEE E2.1 FOR

MORE INFORMATION.

6 PROVIDE CIRCUIT BREAKER IN SWB FOR FUTURE ELECTRIC VEHICLE CHARGER.

7 SCOPE WITHIN BOX IS A PART OF ALTERNATE BID #1. ALTERNATE BID #1: PROVIDE

(ATS) AND TEMPORARY GENERATOR CONNECTION ALONG WITH NECESSARY

DISTRIBUTION EQUIPMENT TO CONNECT (2) EVC'S TO BACKUP POWER. ATS SHALL

OPERATE IN MANUAL MODE. INSTALL ATS ENCLOSURE ON EXTERIOR OF BUILDING.

PROVIDE NEMA 3R ENCLOSURES FOR ALL ENCLOSURES (ATS, CIRCUIT BREAKER

ENCLOSURE, AND CAM LOCK ENCLOSURE) ASSOCIATED WITH THIS ALTERNATE.

8 AN EQUALLY RATED ENGINEER APPROVED PANELBOARD (A SQUARE-D I-LINE OR

EQUIVALENT) IS AN ACCEPTABLE SUBSTITUATION IN PLACE OF A FULL

SWITCHBOARD.

1 08/22/2025 ADD 02

8'' ST 8'' ST 8'' ST 8'' ST

T

8'' S

T 8''

S T

8'' S

T 8''

S T

FFE = 734.32

3.8

4.3

4.2

3.9

3.8

4.0

4.5

4.4

3.8

4.0

3.6

4.1

3.7

3.9

3.5

4.0

4.9

4.6

4.6

4.1

733.76

734.17

4.2

4.3

3.8

733.99

4.3

4.3

734.35

E E

E

E E

E E E E E E E

E

E

E

E

E

E E E E E E E E E E E E E E E E E E E E E E E E E

E

3.8

8" S

T

.6

0%

8" ST @ 0.60%

END SIDEWALK HERE

THIS CONTRACT

END CURB HERE

THIS CONTRACT

ADJUST WITH NEW

TYPE 3 FRAME &

GRATE - BY OTHERS

B6.18 CURB AND GUTTER

INLET TYPE A W/TY 3 FRAME & GRATE

RIM (E/P) = 733.52

8" PVC INV (E)= 731.21

8" PVC INV (S)= 731.21

INLET TYPE A W/TY 3 FRAME & GRATE

RIM (E/P) = 733.62

8" PVC INV (W)= 731.32

P.C.C. SIDEWALK, 6"

RIVER ROCK

LANDSCAPING

END CURB HERE

THIS CONTRACT

NEW ELECTRIC SERVICE

FROM UTILITY POLE

NEW ELECTRIC SECONDARY

TO BUILDING

STUB FUTURE ELECTRIC

SERVICE TO NEW UPW ADDITION

REGRADE GRAVEL LOT TO

MANINTAIN STORM INLETS

AS LOW POINTS

8" PVC INV (N)= 731.10

ADJUST

9'

TYP

.3

4'

.5

5.

5'

5.63'

14.74'

9'

R=2.5'

R=2'

8.66'

FIELD VERIFY EXACT LOCATIONS OF VEHICLE

CHARGERS WITH ELECTRICAL ENGINEER AND

OWNER PRIOR TO INSTALLING EQUIPMENT.

1 SCALE:

EV CHARGING STATION SITE PLAN

1"=5' NORTH

U.S. SURVEY FEET

3 5 10

REVIEWED:

DESIGNED:

DRAWN:

SHEET TITLE:

SHEET NUMBER:

FIELD BOOK NO.:

EV CHARGING

STATION SITE PLAN

C1.1

DSC

GAB

DSC

PROJECT:

DATE:

PROJECT NO.:

City Of Urbana

Urbana Public Works Ev Charging Electrical Upgrades

704 S.Glover Avenue Urbana Illinois 61802

08/15/2025

02500543.001

DESCRIPTION:DATE:#

ISSUE:

BID/PERMIT SET

08/15/2025

GROUP

www.f-w.com Engineers | Architects | Surveyors | Scientists

2211 WEST BRADLEY AVENUE

CHAMPAIGN, ILLINOIS 61821

(217) 352-7408 / info@f-w.com

1 08/22/2025 ADD 02

RELOCATE AC CONDENSER AND

EXISTING PAD TO THE LOW ROOF

SECTION OF BUILDING. EXTEND

REFRIGERANT LINE ALONG THE

WALL. RUN NEW CONDUCTORS TO

NEW CONDENSER LOCATION.

COORDINATE WITH UTILITY

PROVIDER TO ADJUST GAS

METER TO ACCOMMODATE NEW

PAVEMENT/SIDEWALK

ELEVATIONS. METER IS TO BE SET

ON NEW CONCRETE SIDEWALK.

http://www.f-w.com

2025.08.22_add_E_704_Urbana Public Works Remodel - 0231826.00_RVT25
E0.2 - GENERAL INFORMATION
E2.1 - FIRST FLOOR POWER PLAN
E4.1 - ONE-LINE DIAGRAM
C1_EV SITEPLAN - 02500543.001-C1.1 EV CHARGING STATION SITE PLAN
00 4100-FGI-Bid Form-08-22-2025
THE PROJECT AND THE PARTIES
1.1. TO:
A. Urbana Public Works (Owner)
1.2. FOR:
A. Project: 02500543.001 - Urbana Public Works EV Charging
1.3. DATE: ______________ (Bidder to enter date)
1.4. SUBMITTED BY: (Bidder to enter name and address)
A. Bidder's Full Name _________________________
1.5. OFFER
A. The Undersigned, having received and examined the Bidding Documents titled, "EV Charging Stations" dated August 15, 2025, and having visited the site and examined the conditions affecting the Work, we hereby proposes and agrees to furnish all labor, materials, equipment, appliances and services, and to perform operations necessary to complete the Work as required by said Bidding Documents, for the Work identified below.
B. Base Bid: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America.
C. Alternate Bid 01: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America.
D. Alternate Bid 02: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America. (ADD 02)
1.6. ACKNOWLEDGEMENTS
A. The Undersigned acknowledges the following:
1.7. CONTRACT TIME
A. If this Bid is accepted, we will:
B. Complete the Work no later than May 31, 2026 or 120 calendar days from the date of commencement of Work, whichever occurs earlier per A101. (ADD 02)
1.8. BID FORM SIGNATURE(S)
A. The Corporate Seal of
B. ____________________________________________
C. (Bidder - print the full name of your firm)
D. was hereunto affixed in the presence of:
E. ____________________________________________
F. (Authorized signing officer, Title)
G. (Seal)
H. ____________________________________________
I. (Authorized signing officer, Title)

END OF BID FORM

00 4323-RIB-Alternates Form-08-22-2025
PARTICULARS
1.1. THE FOLLOWING IS THE LIST OF ALTERNATES REFERENCED IN THE BID SUBMITTED BY:
1.2. (Bidder) _______________________________
1.3. Dated ________________ and which is an integral part of the Bid Form.
ALTERNATES LIST
2.1. THE FOLLOWING AMOUNTS SHALL BE ADDED TO OR DEDUCTED FROM THE BID AMOUNT. REFER TO SECTION 01 2300 - Alternates.
ALTERNATE # 1: ADD $ ________________________
ALTERNATE # 2: ADD $ ________________________ (ADD 02)
01 2300-RIB-Alternates-08-22-2025
PART 1 GENERAL
1.1. SECTION INCLUDES
A. Description of Alternates.
B. Procedures for pricing Alternates.
C. Documentation of changes to Contract Price and Contract Time.
1.2. RELATED REQUIREMENTS
A. Document 00 2113 - Instructions to Bidders: Instructions for preparation of pricing for Alternates.
B. Document 00 4323 - Alternates Form: List of Alternates as supplement to Bid Form.
C. Document 00 5200 - Agreement Form: Incorporating monetary value of accepted Alternates.
1.3. ACCEPTANCE OF Alternates
A. Alternates quoted on Bid Forms will be reviewed and accepted or rejected at Owner's option. Accepted Alternates will be identified in the Owner-Contractor Agreement.
1.4. SCHEDULE OF Alternates
A. Alternate No. 01 - EV Charging Station Transfer Switch: Provide ATS switches, power distribution, and portable generator connection as shown on plans.
B. Alternate No. 02 - Power Study: Provide power study per specifications. (ADD 02)
PART 2 PRODUCTS - Not Used
PART 3 EXECUTION - Not Used

2025.08.20 - Pre-Bid Meeting Attendance - 02500543.001

File details come from the government source that posted it. Updated .