Addendum_2_Plan_Sheets.pdf
PDF 896 KB Posted
- Attached to
- Public Works EV Charging Electrical Upgrades
- Solicitation number
- FY2026-ITB-152
- Issued by
- Champaign County, Illinois
About this file
This document is a bid/permit set for the Urbana Public Works EV Charging Electrical Upgrades project located at 704 S. Glover Avenue in Urbana, Illinois. The project involves installing electric vehicle (EV) charging stations, with provisions for ten charging stations - five currently active (EVC 01, 03, 05, 07, 09) and five future stations (marked with (F) prefix). The electrical upgrades include a new main switchboard (SWB) with a 1200A MCB rated at 208/120V, three-phase, four-wire configuration. The site plan details the layout of charging stations, electrical infrastructure, and site grading, with specific instructions for field verification of exact charger locations.
The electrical service responsibility schedule indicates that both furnishing and installation of key components like transformers, conduits, conductors, and EV chargers will be handled by the Electrical Contractor (EC). The project includes utility coordination for new electric service from existing utility poles, secondary service to the building, and provisions for future electrical service to a potential new addition. The one-line diagrams show existing and proposed electrical configurations, with detailed feeder schedules and load classifications. The project appears to be funded through municipal infrastructure improvements, with a focus on expanding electric vehicle charging capabilities for the Urbana Public Works facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Public_Works_EV_Charging_Electrical_Upgrades_(Addendum_#2_Revision).pdf | ||
| Addendum_2_Project_Manual_Pages.pdf | ||
| Bid_Bond_Form_(AIA_A310).pdf | ||
| Project_Manual.pdf | ||
| Plans.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4
:2
A
M E0.2
GENERAL
INFORMATION
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
a. EXCEPTION: ALL RECESSED LUMINAIRES IN HARD CEILINGS SHALL HAVE FEED-THRU JUNCTION
BOXES.
6. MAXIMUM SIX FOOT FLEXIBLE LUMINAIRE WHIP SHALL BE USED FOR FINAL CONNECTIONS TO LIGHT FIXTURES INSTALLED IN LAY-IN CEILINGS. MAXIMUM FOUR LUMINAIRE WHIPS SHALL BE CONNECTED FROM ONE JUNCTION BOX. FEED THRU BETWEEN LUMINAIRES SHALL NOT BE ALLOWED.
5. NO SHARING OF NEUTRALS ALLOWED. CIRCUIT SHALL HAVE DEDICATED NEUTRAL CONDUCTORS.
ONE CIRCUIT, ONE NEUTRAL.
4. DERATING OF CONDUCTOR AMPACITY SHALL BE APPLIED PER NEC.
3. EACH RACEWAY SHALL CONTAIN AN INSULATED EQUIPMENT GROUNDING CONDUCTOR PER NEC.
2. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. #10 AWG SHALL BE USED FOR HOME RUNS OF 20 AMP
BRANCH CIRCUITS OVER 100 FEET IN LENGTH.
1. MINIMUM CONDUIT SIZE SHALL BE 3/4".
N. WHERE CONDUIT AND WIRING RUNS ARE NOT SHOWN ON FLOOR PLANS, THE CONTRACTOR SHALL DETERMINE AND PROVIDE THE REQUIRED CONDUIT AND WIRING FOR SPECIFIED CIRCUITING IN
ACCORDANCE WITH NEC AND THE FOLLOWING MINIMUM REQUIREMENTS:
M. ALL FLOOR MOUNTED SWITCH GEAR, UNIT SUBSTATIONS, BOXES AND TRANSFORMERS LARGER THAN 75 KVA SHALL BE INSTALLED ON A NOMINAL 4” HOUSEKEEPING PAD. PAD SHALL EXTEND FROM ELECTRICAL
EQUIPMENT 6” IN ANY DIRECTION.
L. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED
WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC.
K. CONTRACTOR SHALL NOT SCALE DRAWING FOR QUANTITIES. CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING ALL MEASUREMENTS.
J. HAZARDOUS AREAS: IN DESIGNATED ROOMS AND AREAS, IT IS NOT THE INTENT TO SHOW EACH EXPLOSION-PROOF COMPONENT, SUCH AS SEAL-OFFS, JUNCTION BOXES, ETC. THE CONTRACTOR SHALL COMPLETE ALL WORK IN STRICT COMPLIANCE WITH THE APPLICABLE ARTICLES 500 OF THE N.E.C.
I. PRIOR TO SUBMITTING BID PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS AND VISIT CONSTRUCTION SITE TO BE FAMILIAR WITH EXISTING CONDITIONS UNDER WHICH THEY WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT.
NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR
FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
H. PROVIDE AND INSTALL IN EACH PANEL, TYPEWRITTEN NEAT TWO-COLUMN CIRCUIT INDEX CARD SET UNDER PLASTIC COVERS ON INSIDE OF DOORS. EACH ODD-NUMBERED CIRCUIT SHALL BE IN SEQUENCE ON ONE COLUMN AND THE EVEN-NUMBERED CIRCUITS ON THE OTHER COLUMN (E.G. 1,3,5...,2,4,6...).
EACH CIRCUIT SHALL BE IDENTIFIED AS TO THE USE AND ROOM NAME(S) OR AREA(S). THE CONTRACTOR
SHALL CONFIRM ROOM NAMES AND/OR ROOM NUMBERS WITH THE ARCHITECT PRIOR TO PROJECT
COMPLETION.
G. THE ELECTRICAL CONTRACTOR SHALL BE HELD FINANCIALLY RESPONSIBLE FOR ANY AND ALL COSTS OF THE ENGINEERS TIME REQUIRED TO REVIEW AND RESEARCH NON-SPECIFIED EQUIPMENT SUBMITTED FOR SUBSTITUTION BY THE ELECTRICAL CONTRACTOR. THESE COSTS SHALL BE AUTOMATICALLY
INVOICED TO THE CONTRACTOR UNLESS SUCH SUBSTITUTIONS FOLLOW THE GUIDELINES FOR
SUBSTITUTION AND ARE WITHIN THE PROPER TIME FRAME AS OUTLINED IN OTHER SECTIONS OF THIS
SPECIFICATION.
1. ALL PENETRATIONS OF FIRE-RESISTIVE FLOORS OR SHAFT WALLS SHALL BE PROTECTED BY MATERIALS AND INSTALLATION DETAILS THAT CONFORM TO UNDERWRITERS' LABORATORIES LISTINGS
FOR "THROUGH-PENETRATION FIRE STOP SYSTEMS." THE CONTRACTOR SHALL SUBMIT SHOP
DRAWING DETAILS, FURNISHED BY THE MANUFACTURER OF THE FIRE STOP MATERIAL, WHICH SHOW COMPLETE CONFORMANCE TO THE UL LISTING AND SHALL BE SPECIFIC FOR EACH PENETRATION WITH ALL VARIABLES DEFINED. THESE FINAL AND APPROVED DRAWINGS SHALL BE READILY AVAILABLE TO
THE LOCAL INSPECTORS AT ALL TIMES AT THE PROJECT SITE.
F. REFER TO ARCHITECTURAL PLANS TO CONFIRM ALL FIRE-RATED CEILINGS AND WALLS.
E. THE CONTRACTOR SHALL CONTACT AND OBTAIN FROM THE UTILITY COMPANY ALL INFORMATION, REQUIREMENTS, THEIR CONSTRUCTION DRAWINGS AND SPECIFICATIONS TO COMPLETE THE
ELECTRICAL PRIMARY/SECONDARY SERVICE TO THIS PROJECT. INCLUDE IN BASE BID, BUT NOT LIMIT TO, TRENCHING, BACKFILL, TRANSFORMER CONCRETE PAD, CONDUITS, METERING REQUIREMENTS, AND PROVIDE COMPLIANT EQUIPMENT IN THE CORRECT SEQUENCE, CONTRIBUTION COSTS, ENGINEERING
FEE AND SERVICE CHARGES FOR ALL ELECTRICAL SERVICES TO THIS PROJECT.
D. GROUT AND SEAL ALL CONDUIT PENETRATIONS OF WALLS AND FLOOR SLABS TO PRESERVE FIRE RATING
AND WATERTIGHT INTEGRITY.
C. COORDINATE SCHEDULE OF CONSTRUCTION WITH THE OWNER, OTHER TRADES AND UTILITIES INVOLVED BEFORE TRENCHING AND INSTALLATION OF UNDERGROUND CONDUIT. USE EXTREME CAUTION DURING EXCAVATION TO LOCATE EXISTING UNDERGROUND PIPING, CONDUITS, ETC. LOCATE AND PROTECT ANY
BURIED UTILITIES IN AREAS OF EXCAVATION.
B. PRIOR TO ROUGH-IN AND FINAL CONNECTION OF EQUIPMENT, VERIFY ELECTRICAL REQUIREMENTS OF
EQUIPMENT WITH OTHER TRADES CONSTRUCTION DOCUMENTS AND FINALIZED SHOP DRAWINGS.
VERIFICATION SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: VOLTAGE, AMPERAGE, TOTAL LOAD, OVER-CURRENT PROTECTION REQUIREMENTS, MOUNTING HEIGHT OF ELECTRICAL CONNECTION, CABLE TYPE AND SIZE, WIRING DIAGRAMS.
A. SEE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, ELEVATIONS, AND BUILDING DETAILS. VERIFY LOCATION OF ALL WALL OUTLETS, SWITCHES, ETC., WITH ARCHITECTURAL DRAWINGS AND ACTUAL
CONDITIONS.
COMMON REQUIREMENTS:
K. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING
HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
J. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE OWNER'S FACILITIES. NOTICE SHALL BE REQUIRED IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY OWNER. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY
TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
I. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.
H. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT
NECESSARY TO MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
G. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE
INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL
OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE
APPROVAL OF THE ARCHITECT AND/OR THE OWNER.
F. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED, THAT IT WILL NOT PROTRUDE BEYOND THE FINISHED SURFACE. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR
SHALL CUT AND CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
E. WHERE EXISTING LUMINAIRES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
D. OUTLETS FROM WHICH LUMINAIRES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE
COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
C. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS
AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND
CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR
REPLACE OLD WIRING WITH NEW.
B. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE. WHERE EXPOSED WORK IS REQUIRED IN FINISHED AREAS, THE CONTRACTOR SHALL USE WIREMOLD RACEWAY WITH #500 BEING
THE MINIMUM SIZE ACCEPTABLE.
1. DRAWINGS SHOW EXISTING CONDITIONS OF THE SITE. AN ATTEMPT HAS BEEN MADE TO SHOW EXISTING BUILDING, SITE DETAILS, ETC., BUT ACCURACY CANNOT BE GUARANTEED. VERIFY EXACT LOCATIONS OF ALL CIRCUITS, CONDUITS, PIPING, EQUIPMENT, ETC. VERIFY ALL SITE AND BUILDING
DETAILS.
A. RENOVATION OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN, ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, LUMINAIRES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY.
RENOVATION NOTES:
I. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO
REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
6. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR
OWNER'S REPRESENTATIVE.
5. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND
MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
4. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
3. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
2. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
1. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
H. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
G. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT
DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
F. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR
NEW DEVICES.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" LUMINAIRES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT
DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID
CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" LUMINAIRE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.
D. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE
ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.
C. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, LUMINAIRES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING
CIRCUIT CONTINUITY IS MAINTAINED.
B. REMOVE ALL EXISTING WIRING DEVICES, LUMINAIRES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING
WHICH REQUIRES CONTINUATION THROUGH THE AREA.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS
DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.
DEMOLITION:
%Z IMPEDANCE
(E) EXISTING (ALSO COVERED BY TEXT
WEIGHT)
(F) FUTURE
(PART) PARTIAL CIRCUIT
(R) RELOCATE
A AMPERES
AC 6" ABOVE COUNTER
ADA AMERICANS WITH DISABILITIES ACT
AF AMPERES FRAME
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTION CAPACITY
AL ALUMINUM
AT AMPERES TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAM CAMERA
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTER CLOCKWISE
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CO CONDUIT ONLY
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
CW CLOCKWISE
D DEDICATED
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DR DUPLEX RECEPTACLE
DWG DRAWING(S)
EC ELECTRICAL CONTRACTOR
ELC ELEVATOR CONTRACTOR
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
F FUSED
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FLA FULL LOAD AMPERES
FMC FLEXIBLE METAL CONDUIT
FO FIBER OPTIC
FPC FIRE PROTECTION CONTRACTOR
FS FUSED SWITCH
FSC FOOD SERVICE CONTRACTOR
FSD FIRE/SMOKE DAMPER
FT FOOT/FEET
FVNR FULL VOLTAGE, NON-REVERSING
FVR FULL VOLTAGE, REVERSING
G/GND GROUND/GROUNDING
GC GENERAL CONTRACTOR
GEN GENERATOR
GF GROUND FAULT
GFI/GFCI GROUND FAULT INTERRUPTER
H HORIZONTALLY MOUNTED
HG HOSPITAL GRADE
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HZ FREQUENCY
I/O INPUT/OUTPUT
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
ISC SHORT CIRCUIT CURRENT
JB JUNCTION BOX
K KELVIN (COLOR TEMPERATURE)
KCMIL 1000 CIRCULAR MILS
KV KILOVOLTS
KVA KILVOLT-AMPERES
KW KILOWATTS
KWH KILOWATT-HOUR
LAN LOCAL AREA NETWORK
LC LIGHTING CONTACTOR
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FOOT
LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT
LM LUMEN
LTG LIGHTING
LV LOW VOLTAGE
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
ABBREVIATIONSGENERAL NOTES
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MEPFP MECHANICAL, ELECTRICAL, PLUMBING,
FIRE PROTECTION
MGB MASTER GROUND BAR
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SWITCHBOARD
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MVA MEGAVOLT-AMPERES
MW MEGAWATT
MWH MEGAWATT-HOURS
N NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OWN OWNER
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PC PLUMBING CONTRACTOR
PF POWER FACTOR
PH PHASE
PIR PASSIVE INFRARED
PLC PROGRAMMABLE LOGIC CONTROLLER
PNL PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWC PRE-WIRED CONTROLS
PWR POWER
RCPT RECEPTACLE
REQD REQUIRED
RF RADIO FREQUENCY
RM ROOM
RMC RIGID METAL CONDUIT
RNC RIGID NON-METALLIC CONDUIT (SCH 40)
RVAT REDUCED VOLTAGE -
AUTOTRANSFORMER
SC SHORT CIRCUIT
SCC SHORT CIRCUIT CURRENT RATING
SDP SUBDISTRIBUTION PANEL
SEC SECONDARY
SHLD SHIELD(ED) (AS IN CABLE)
SHT SHEET
SPD SURGE-PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SR SINGLE RECEPTACLE
SS SURGE SUPPRESSOR (ISOLATED
GROUND TYPE)
ST SHUNT TRIP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBD TO BE DETERMINED
TC TIMECLOCK
TCC TEMPERATURE CONTROLS
CONTRACTOR
TEMP TEMPERATURE
TR TAMPER RESISTANT
TT THERMAL TRIP SWITCH
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U UTILITY
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERUPTABLE POWER SUPPLY
USB STANDARD DUPLEX WITH 2 USB PORTS
V VOLTS
VA VOLT-AMPERES
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VND VENDOR
W WATTS
W WIRE
WHM WATTHOUR METER
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
1 08/22/2025 ADD 02
M
T
F J J J J J J J J J J
SWB
4'-4 3/8"
9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 19'-6 1/8"
CT/PT
2EVC
SWB-15
T-704
SWB-16
(F)EVC
EVC
(F)EVC
EVC
(F)EVC
EVC
(F)EVC
EVC
(F)EVC
SWB-17 SWB-18
SWB-19 SWB-20
SWB-21
SWB-22 SWB-23 SWB-24
5 1 5 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4
:3
A
M E2.1
FIRST FLOOR POWER
PLAN
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
0 4 8 16
NORTH
PLAN
A. NOT USED
GENERAL NOTES
SCALE: 1/8" = 1'-0"
FIRST FLOOR POWER PLAN
#KEYNOTES
1 PROVIDE ELECTRIC VEHICLE CHARGER FROM ONE OF THE THREE SHORT LISTED
VENDORS BELOW. ELECTRIC VEHICLE CHARGER SHALL MEET THE CITY'S
SPECIFICATION:
(1) CHARGRPOINT CPF50 WALL MOUNTED SINGLE PORT WITH 23' CABLE.
(2) FORD PRO AC CHARGING STATION 48A SERIES 2, WALL MOUNTED, SINGLE PORT.
(3) FRACTALEV 80A CHARGING STATION, WALL MOUNTED, SINGLE PORT.
2 PROVIDE NEW SWITCHBOARD. VERIFY DIMENSIONS OF SPACE AND OF
SWITCHBOARD PRIOR TO ORDERING AND INSTALLATION. IF SWITCHBOARD DOES
NOT FIT IN EXISTING SPACE, CONTACT THE ENGINEER TO DETERMINE A NEW
LOCATION.
3 EXISTING UTILITY POLE.
4 EXISTING PANELBOARDS ARE NOT SHOWN WITHIN THE BUILDING. CONTRACTOR TO
VERIFY PANELBOARD LOCATIONS AND RATED VOLTAGES. IF ANY EQUIPMENT OR
PANELS HAVE RATING ISSUES WITH THE NEW SYSTEM, THE CONTRACTOR IS TO
CONTACT THE ENGINEER.
5 FUTURE ELECTRIC VEHICLE CHARGING LOCATION. PROVIDE CONDUIT AND PULL
STRING BACK TO SWB. PROVIDE BACK BOX ON EXTERIOR WALL. INSTALLATION
SHALL BE THE SAME AS THE NEW ELECRTIC VEHICLE CHARGERS AND BE MADE
WATER TIGHT. LABEL BACK BOX WITH TAG INFORMATION FROM PLANS AND NOTE
WHERE CONDUIT TERMINATES.
6 VERIFY LOCATION OF TRANSFORMER IN FIELD AND WITH CIVIL SITE PLANS.
7 PROVIDE JUNCTION BOX WHERE EXISTING PANELBAORD WAS LOCATED FOR
RE-CONNECTION OF EXISTING PANELS TO NEW SWB.
REMARKS:
R MAIN SWITCHBOARD EC EC -
Q EUSERC CABINET N/A N/A -
P WIRING TERMINATIONS AT METERING EQUIPMENT EC EC -
O CONDUIT FROM TRANSFORMER TO METER EC EC -
N METER SOCKETS EC EC -
M METERS U U -
L C.T. CABINETS EC EC -
K C.T.'S U U -
J SECONDARY CONDUCTORS TO MAIN SWITCHBOARD EC EC -
I SECONDARY CONDUIT(S) TO MAIN SWITCHBOARD EC EC -
H PRIMARY CONDUCTORS U U -
G MANHOLES N/A N/A -
F PRIMARY CONDUIT(S) & DUCT BANK EC EC -
E TRENCHING FROM UTILITY POLE TO TRANSFORMER EC EC -
D BUMPER POSTS (BOLLARDS) OWNER OWNER -
C NEW TRANSFORMER U U -
B NEW TRANSFORMER BASE U U -
A TRANSFORMER SITE COMPACTION EC EC -
ITEM DESCRIPTION FURNISHED BY INSTALLED BY REMARKS
NEW ELECTRICAL SERVICE RESPONSIBILITY SCHEDULE
EQUIPMENT DATA SCHEDULE
DESCRIPTION LOAD DATA
WIRE & CONDUIT REMARKS
MARK EQUIPMENT
F U
R N
IS
H
E D
B Y
IN
S
T A
L L
E D
B Y
LOCATION
L O
A D
V O
L T
A G
E
P H
A S
E
EVC 01 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C
(F)EVC 02 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1
EVC 03 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C
(F)EVC 04 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1
EVC 05 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C
(F)EVC 06 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1
EVC 07 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C
(F)EVC 08 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1
EVC 09 ELECTRIC VEHICLE CHARGER EC EC BUILDING EXTERIOR 20kW 208 1 3#1, 1#8G, 1-1/2"C
(F)EVC 10 (FUTURE) ELECTRIC VEHICLE CHARGER - - BUILDING EXTERIOR - 208 1 1-1/2"C 1
1. PROVIDE ROUGH IN FOR FUTURE CHARGING STATION. PROVIDE CONDUIT AS NOTED AND PULL STRING BACK TO SWB.
REMARKS:
A. NONE
GENERAL NOTES:
EQUIPMENT DATA NOTES:
1 08/22/2025 ADD 02
SITE 704
EXISTING UTILITY
TRANSFORMER
POLE MOUNTED
SEC: 120/240 3P 4W
400AS
400AF
200AT
800AT
PANEL
XX
50AT
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SPACE SPACE
100AT 200AT 100AT 200AT 100AT 100AT 100AT 70AT 50AT 70AT 70AT 50AT
SITE 704
T-704
UTILITY TRANSFORMER
PAD MOUNTED 500KVA
SEC: 208Y/120VAC 3P 4W
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XX
PANEL
XXGROUND
NEUTRAL
M1200 A
AL1200A4G
AL1200A4
J J
EVC
EXISTING UTILITY
TRANSFORMER
POLE MOUNTED
SEC: 120/240 3P 4W
UTIL
1200 AS
1200 AF
J J J J J J J J
(F)EVC
EVC
EVC
EVC
EVC
2 2 2 2 2 2 2 2 2 2 2 22
100A3G
GEN CAM LOCK
CONNECTION
100 A
3 POLES
100 A
3 POLES
100 AF
100 AT
200 AF
200 AT
SWB
5 3 5 3 5 3 5
(F)EVC
(F)EVC
(F)EVC
(F)EVC
66666 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
2211 W. BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:4
:3
A
M E4.1
ONE-LINE DIAGRAM
DGM
WRK
02500543.001
Urbana Public Works EV Charging Electrical Upgrades
City of Urbana
704 S Glover Avenue Urbana Illinois 61802
8/15/2025
08/15/2025
BID/PERMIT SET
TJS
BID/PERMIT SET
A. ALTERNATE BID #2: PROVIDE POWER SYSTEMS STUDY PER SPECIFICATION 26 05 73.
WITH REGARDS TO SPECIFICATION FOR
POWER SYSTEMS STUDIES (260573):
SCALE: 12" = 1'-0"
EXISTING ONE-LINE DIAGRAM
SCALE: 12" = 1'-0"
PROPOSED ONE-LINE DIAGRAM
2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.
1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED
NOTES:
TOTAL DEMAND CURRENT: 278 A
TOTAL CONNECTED CURRENT: 278 A
TOTAL DEMAND: 100000 VA
TOTAL CONNECTED LOAD: 100000 VA
HVAC 100000 VA 100.00% 100000 VA
Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS
TOTAL AMPS: 481 A 481 A 0 A
TOTAL CONNECTED LOAD: 50000 VA 50000 VA 0 VA
24 (F)EVC-10 250 A 100 A 2 0 VA 0 VA
23 HVAC 250 A 100 A 2 10000 VA 10000 VA
22 (F)EVC-08 250 A 100 A 2 0 VA 0 VA
21 HVAC 250 A 100 A 2 10000 VA 10000 VA
20 (F)EVC-06 250 A 100 A 2 0 VA 0 VA
19 EVC-05 250 A 100 A 2 10000 VA 10000 VA
18 (F)EVC-04 250 A 100 A 2 0 VA 0 VA
17 EVC-03 250 A 100 A 2 10000 VA 10000 VA
16 (F)EVC-02 250 A 100 A 2 0 VA 0 VA
15 EVC-01 250 A 100 A 2 10000 VA 10000 VA
14 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA
13 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA
12 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA
11 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA
10 EXISTING PANEL 250 A 50 A 3 0 VA 0 VA 0 VA
9 EXISTING PANEL 250 A 70 A 3 0 VA 0 VA 0 VA
8 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA
7 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA
6 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA
5 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA
4 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA
3 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA
2 EXISTING PANEL 250 A 100 A 3 0 VA 0 VA 0 VA
1 EXISTING PANEL 250 A 200 A 3 0 VA 0 VA 0 VA
ITEM NO. Load Name Frame Rating Sched ule Circu...
Numb er of Poles
A B C REMARKS
MAIN: 1200 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N
RATED AMPERAGE: 1200 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N
PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): 65kA MCB GROUND FAULT PROTECTION (Y/N): N
VOLTAGE: 208/120V SCC RATING (SYM): 65kA MOUNTING: PAD
SWITCHBOARD SWB
FEEDER SCHEDULE
MARK
CONDUIT & CONDUCTORS
(SEE NOTE 1) REMARKS
100A3G 3#1, 1#8G, 1-1/2"C
AL1200A4 4 SETS (4#500, 3-1/2"C) SEE NOTE 2
AL1200A4G 4 SETS (4#500, 1#250G, 3-1/2"C) SEE NOTE 2
UTIL (2) 2"C
2. FEEDERS MARKED WITH AN "AL" ARE ALUMINUM CONDUCTORS.
1. THIS FEEDER SCHEDULE IS BASED ON 60 DEGREE CENTIGRADE (TYPE TW) WIRE AND
TERMINATIONS FOR SIZES #12 TO #1, AND 75 DEGREE CENTIGRADE (TYPE
THHN/THWN) WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS NOTED
OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF OTHER
CONDUIT TYPES REQUIRES RESIZING OF CONDUIT.
REMARKS:
KEYNOTES
1 PROVIDE CONNECTION TO EXISTING BUILDING GROUNDING SYSTEM. SEE DETAILS.
2 RECONNECT EXISTING FEEDER FROM EXISTING PANELBOARD TO NEW CIRCUIT
BREAKER IN NEW SWITCHBOARD.
3 SEE E2.1 FOR BRANCH CIRCUIT SIZES.
4 EXISTING 706 BUILDING POWER FEED. NO WORK ASSOCIATED WITH THIS BUILDING,
SHOWN FOR REFERENCE ONLY.
5 PROVIDE CONDUIT AND ROUGH-IN FOR FUTURE CHARGING STATION. SEE E2.1 FOR
MORE INFORMATION.
6 PROVIDE CIRCUIT BREAKER IN SWB FOR FUTURE ELECTRIC VEHICLE CHARGER.
7 SCOPE WITHIN BOX IS A PART OF ALTERNATE BID #1. ALTERNATE BID #1: PROVIDE
(ATS) AND TEMPORARY GENERATOR CONNECTION ALONG WITH NECESSARY
DISTRIBUTION EQUIPMENT TO CONNECT (2) EVC'S TO BACKUP POWER. ATS SHALL
OPERATE IN MANUAL MODE. INSTALL ATS ENCLOSURE ON EXTERIOR OF BUILDING.
PROVIDE NEMA 3R ENCLOSURES FOR ALL ENCLOSURES (ATS, CIRCUIT BREAKER
ENCLOSURE, AND CAM LOCK ENCLOSURE) ASSOCIATED WITH THIS ALTERNATE.
8 AN EQUALLY RATED ENGINEER APPROVED PANELBOARD (A SQUARE-D I-LINE OR
EQUIVALENT) IS AN ACCEPTABLE SUBSTITUATION IN PLACE OF A FULL
SWITCHBOARD.
1 08/22/2025 ADD 02
8'' ST 8'' ST 8'' ST 8'' ST
T
8'' S
T 8''
S T
8'' S
T 8''
S T
FFE = 734.32
3.8
4.3
4.2
3.9
3.8
4.0
4.5
4.4
3.8
4.0
3.6
4.1
3.7
3.9
3.5
4.0
4.9
4.6
4.6
4.1
733.76
734.17
4.2
4.3
3.8
733.99
4.3
4.3
734.35
E E
E
E E
E E E E E E E
E
E
E
E
E
E E E E E E E E E E E E E E E E E E E E E E E E E
E
3.8
8" S
T
.6
0%
8" ST @ 0.60%
END SIDEWALK HERE
THIS CONTRACT
END CURB HERE
THIS CONTRACT
ADJUST WITH NEW
TYPE 3 FRAME &
GRATE - BY OTHERS
B6.18 CURB AND GUTTER
INLET TYPE A W/TY 3 FRAME & GRATE
RIM (E/P) = 733.52
8" PVC INV (E)= 731.21
8" PVC INV (S)= 731.21
INLET TYPE A W/TY 3 FRAME & GRATE
RIM (E/P) = 733.62
8" PVC INV (W)= 731.32
P.C.C. SIDEWALK, 6"
RIVER ROCK
LANDSCAPING
END CURB HERE
THIS CONTRACT
NEW ELECTRIC SERVICE
FROM UTILITY POLE
NEW ELECTRIC SECONDARY
TO BUILDING
STUB FUTURE ELECTRIC
SERVICE TO NEW UPW ADDITION
REGRADE GRAVEL LOT TO
MANINTAIN STORM INLETS
AS LOW POINTS
8" PVC INV (N)= 731.10
ADJUST
9'
TYP
.3
4'
.5
5.
5'
5.63'
14.74'
9'
R=2.5'
R=2'
8.66'
FIELD VERIFY EXACT LOCATIONS OF VEHICLE
CHARGERS WITH ELECTRICAL ENGINEER AND
OWNER PRIOR TO INSTALLING EQUIPMENT.
1 SCALE:
EV CHARGING STATION SITE PLAN
1"=5' NORTH
U.S. SURVEY FEET
3 5 10
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
EV CHARGING
STATION SITE PLAN
C1.1
DSC
GAB
DSC
PROJECT:
DATE:
PROJECT NO.:
City Of Urbana
Urbana Public Works Ev Charging Electrical Upgrades
704 S.Glover Avenue Urbana Illinois 61802
08/15/2025
02500543.001
DESCRIPTION:DATE:#
ISSUE:
BID/PERMIT SET
08/15/2025
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
2211 WEST BRADLEY AVENUE
CHAMPAIGN, ILLINOIS 61821
(217) 352-7408 / info@f-w.com
1 08/22/2025 ADD 02
RELOCATE AC CONDENSER AND
EXISTING PAD TO THE LOW ROOF
SECTION OF BUILDING. EXTEND
REFRIGERANT LINE ALONG THE
WALL. RUN NEW CONDUCTORS TO
NEW CONDENSER LOCATION.
COORDINATE WITH UTILITY
PROVIDER TO ADJUST GAS
METER TO ACCOMMODATE NEW
PAVEMENT/SIDEWALK
ELEVATIONS. METER IS TO BE SET
ON NEW CONCRETE SIDEWALK.
http://www.f-w.com
| 2025.08.22_add_E_704_Urbana Public Works Remodel - 0231826.00_RVT25 |
| E0.2 - GENERAL INFORMATION |
| E2.1 - FIRST FLOOR POWER PLAN |
| E4.1 - ONE-LINE DIAGRAM |
| C1_EV SITEPLAN - 02500543.001-C1.1 EV CHARGING STATION SITE PLAN |
| 00 4100-FGI-Bid Form-08-22-2025 |
| THE PROJECT AND THE PARTIES |
| 1.1. TO: |
| A. Urbana Public Works (Owner) |
| 1.2. FOR: |
| A. Project: 02500543.001 - Urbana Public Works EV Charging |
| 1.3. DATE: ______________ (Bidder to enter date) |
| 1.4. SUBMITTED BY: (Bidder to enter name and address) |
| A. Bidder's Full Name _________________________ |
| 1.5. OFFER |
| A. The Undersigned, having received and examined the Bidding Documents titled, "EV Charging Stations" dated August 15, 2025, and having visited the site and examined the conditions affecting the Work, we hereby proposes and agrees to furnish all labor, materials, equipment, appliances and services, and to perform operations necessary to complete the Work as required by said Bidding Documents, for the Work identified below. |
| B. Base Bid: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America. |
| C. Alternate Bid 01: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America. |
| D. Alternate Bid 02: _________________________________________________________ _________________________________________________________ dollars ($______________________), in lawful money of the United States of America. (ADD 02) |
| 1.6. ACKNOWLEDGEMENTS |
| A. The Undersigned acknowledges the following: |
| 1.7. CONTRACT TIME |
| A. If this Bid is accepted, we will: |
| B. Complete the Work no later than May 31, 2026 or 120 calendar days from the date of commencement of Work, whichever occurs earlier per A101. (ADD 02) |
| 1.8. BID FORM SIGNATURE(S) |
| A. The Corporate Seal of |
| B. ____________________________________________ |
| C. (Bidder - print the full name of your firm) |
| D. was hereunto affixed in the presence of: |
| E. ____________________________________________ |
| F. (Authorized signing officer, Title) |
| G. (Seal) |
| H. ____________________________________________ |
| I. (Authorized signing officer, Title) |
END OF BID FORM
| 00 4323-RIB-Alternates Form-08-22-2025 |
| PARTICULARS |
| 1.1. THE FOLLOWING IS THE LIST OF ALTERNATES REFERENCED IN THE BID SUBMITTED BY: |
| 1.2. (Bidder) _______________________________ |
| 1.3. Dated ________________ and which is an integral part of the Bid Form. |
| ALTERNATES LIST |
| 2.1. THE FOLLOWING AMOUNTS SHALL BE ADDED TO OR DEDUCTED FROM THE BID AMOUNT. REFER TO SECTION 01 2300 - Alternates. |
| ALTERNATE # 1: ADD $ ________________________ |
| ALTERNATE # 2: ADD $ ________________________ (ADD 02) |
| 01 2300-RIB-Alternates-08-22-2025 |
| PART 1 GENERAL |
| 1.1. SECTION INCLUDES |
| A. Description of Alternates. |
| B. Procedures for pricing Alternates. |
| C. Documentation of changes to Contract Price and Contract Time. |
| 1.2. RELATED REQUIREMENTS |
| A. Document 00 2113 - Instructions to Bidders: Instructions for preparation of pricing for Alternates. |
| B. Document 00 4323 - Alternates Form: List of Alternates as supplement to Bid Form. |
| C. Document 00 5200 - Agreement Form: Incorporating monetary value of accepted Alternates. |
| 1.3. ACCEPTANCE OF Alternates |
| A. Alternates quoted on Bid Forms will be reviewed and accepted or rejected at Owner's option. Accepted Alternates will be identified in the Owner-Contractor Agreement. |
| 1.4. SCHEDULE OF Alternates |
| A. Alternate No. 01 - EV Charging Station Transfer Switch: Provide ATS switches, power distribution, and portable generator connection as shown on plans. |
| B. Alternate No. 02 - Power Study: Provide power study per specifications. (ADD 02) |
| PART 2 PRODUCTS - Not Used |
| PART 3 EXECUTION - Not Used |
2025.08.20 - Pre-Bid Meeting Attendance - 02500543.001