PLAN SET 20190501 FINAL.pdf

PDF 1 MB Posted

Attached to
RFP # 38F-19 Traction Power Sub Meter Pilot Project
Solicitation number
BD-19-1206-40000-40000-36461
Issued by
Suffolk County, Massachusetts

About this file

This document is a plan set for the Massachusetts Bay Transportation Authority (MBTA) Fiber Optic Communication System (FOCS) Design. The project details the installation of a fiber optic communication network across multiple MBTA stations, including Braintree Station and Washington Village Station. The work includes furnishing and installing new fiber optic cable, network switches, data cabinets, patch panels, and other related equipment. The contractor will be responsible for verifying all distances and coordinating with the MBTA project engineer on the exact locations of the new equipment. The response due date and public opening for this contract opportunity is at the MBTA offices in Boston, Massachusetts.

The plan set provides detailed diagrams and equipment specifications for the fiber optic network, including the quantity and types of meters, switches, and other devices to be installed at each location. Pricing terms, funding sources, and incumbent information are not included in this document. This appears to be a technical design specification rather than a formal solicitation, so those commercial details would likely be found in the related state and local contract opportunity referenced.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

ISSUE FOR BID

633 17th Street, Suite 1500 Denver, Colorado 80202 633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 2 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 2 OF 8

FOCN-JA001

FIBER OPTIC CABLE BLOCK DIAGRAM

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 2 OF 8

FOCN-JA001

FIBER OPTIC CABLE BLOCK DIAGRAM

COMMUNICATIONS4/28/19

DSE

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 2 OF 8

FOCN-JA001

FIBER OPTIC CABLE BLOCK DIAGRAM

COMMUNICATIONS4/28/19

DSE

4th Floor

DATA CABINET

NO-EMI

45 HIGH STREET

DATA CONTROL CENTER

2nd

Floor

DATA CABINET

NON-EMI

BRAINTREE STATION

WASHINGTON VILLAGE STATION

10 PARK PLAZA 21 ARLINGTON AVE

WORKSTATION

WITH EMS

LICENSE

SIGNAL

INSTRUMENT

HOUSE

24 PORT INDUSTRIAL

SWITCH

24 PORT CAT 6

PATCH PANEL

WIDE AREA NETWORK

(EXISTING)

WIDE AREA NETWORK

(EXISTING)

WIDE AREA NETWORK

(EXISTING)

WIDE AREA NETWORK

(EXISTING)

FIBER DISTRIBUTION

PANEL 12 PORT SM-ST

FIBER DISTRIBUTION

PANEL 12 PORT SM-ST

48 PORT NETWORK

SWITCH NON-

RUGGEDIZED

ELECTRONIC

METERING SYSTEM /

APP / DB SYSTEM

FIBER DISTRIBUTION

PANEL 12 PORT SM-ST

UPS

OUTSIDE

DATA CABINET

(EXISTING)

NEW SOLID STATE METERS

(QUANTITY=4)

UPS

FIBER OPTIC CABLE

12f FO SM

12f FO SM

NEW SOLID STATE METERS

(QUANTITY=9)

FIBER DISTRIBUTION

PANEL 12 PORT SM-ST

(NEW)

24 PORT INDUSTRIAL

NETWORK SWITCH (NEW)

TRACTION POWER SUBSTATION

TRACTION POWER SUBSTATION

NEW DATA

CABINET

NEMA 4 - EMI

DATA CABINET

(EXISTING)

WORKSTATION

WITH EMS

LICENSE

24 PORT CAT 6

PATCH PANEL (NEW)

24 PORT INDUSTRIAL

NETWORK SWITCH (EXISTING)

FIBER DISTRIBUTION

PANEL (EXISTING)

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

FIBER DISTRIBUTION

PANEL (EXISTING)

FIBER DISTRIBUTION

PANEL (EXISTING)

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 3 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 3 OF 8

FOCN-JA002

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 3 OF 8

FOCN-JA002 COMMUNICATIONS4/29/19

DSE

FIBER OPTIC CABLE ROUTING BRAINTREE STATION

NOTE 1 TERMINATE ALL CAT 6 CABLING IN A RJ45 JUNCTION BOX

IN THE BASE OF THE POWER CABINET, CONNECT THE METER

WITH A CAT 6 SHIELDED PATCH CABLE.

NOTE2 FURNISH AND INSTALL 12F SM FO CABLE IN EXISTING

UNDERGROUND CONDUIT. CONTRACTOR TO VERIFY ALL

DISTANCES

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

BRAINTREE STATION

SIGNAL INSTRUMENT HOUSE

24 PORT INDUSTRIAL SWITCH (NEW)

24 PORT CAT 6

PATCH PANEL (NEW)

FIBER DISTRIBUTION PANEL 12 PORT SM-ST

(NEW)

OUTSIDE

DATA CABINET (EXISTING)

NEW SOLID STATE METERS (QUANTITY=4)

UPS (NEW)

FIBER OPTIC CABLE

12f FO SM (NEW)

TRACTION POWER SUBSTATION

NEW DATA CABINET

NEMA 4 - EMI

FIBER DISTRIBUTION PANEL (EXISTING)

WIDE AREA NETWORK

(EXISTING)

WIDE AREA NETWORK

(EXISTING)

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 4 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 4 OF 8

FOCN-JA003

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 4 OF 8

FOCN-JA003 COMMUNICATIONS4/28/19

DSE

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 4 OF 8

FOCN-JA003 COMMUNICATIONS4/28/19

DSE

FIBER OPTIC CABLE ROUTING

WASHINGTON VILLAGE STATION

NOTE 1 TERMINATE ALL CAT 6 CABLING IN A RJ45 JUNCTION BOX

IN THE BASE OF THE POWER CABINET, CONNECT THE METER

WITH A CAT 6 SHIELDED PATCH CABLE.

NOTE 2 EXISITNG DATA CABINENT HAS EXISTING NETWORK

EQUIPMENT. COORDINATE WITH MBTA PROJECT ENGINEER FOR

THE EXACT LOCATION OF THE NEW EQUIPMENT.

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

ETHERNET

FIBER PATCH CABLES

FIBER OPTIC CABLE

EXISTING SYSTEMS

RESPONSIBILTY OF THE

CONTRACTOR

LEGEND

WASHINGTON VILLAGE STATION

NEW SOLID STATE METERS (QUANTITY=9)

FIBER DISTRIBUTION

PANEL 12 PORT SM-ST

(NEW)

24 PORT INDUSTRIAL NETWORK SWITCH (NEW)

TRACTION POWER SUBSTATION

DATA CABINET (EXISTING)

24 PORT CAT 6

PATCH PANEL (NEW)

24 PORT INDUSTRIAL NETWORK SWITCH (EXISTING)

FIBER DISTRIBUTION PANEL (EXISTING)

WIDE AREA NETWORK

(EXISTING)

WIDE AREA NETWORK

(EXISTING)

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 5 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 5 OF 8

FOCN-JA004

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 5 OF 8

FOCN-JA004 COMMUNICATIONS4/28/19

DSE

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 5 OF 8

FOCN-JA004 COMMUNICATIONS4/28/19

DSE

FIBER DISTRIBUTION EQUIPMENT AT TPSS

2 U SUMMIT EXTREME NETWORK SWITCH

24 PORT

1 U FIBER DISTRIBUTION PANEL

12 PORT CLOSED

1 U FIBER DISTRIBUTION PANEL

12 PORT OPEN

SINGLE MODE ST CONNECTORS

12F SINGLE MODE FIBER OPTIC CABLE

DIGITAL ELECTRIC POWER METERS

(QUANTITY VARIED)

NOTE 1 FIBER OPTIC PATCH CABLES HAVE ST CONNECTORS.

NOTE 2 FIBER OPTIC CABLE IS FUSION SPLICED USING ST PIGTAIL

CONNECTORS.

NOTE 3 24 PORT SWITCH IS SHOWN AS TYPICAL, 48 PORT

NETWORK SWITCH FOR DATA CENTER WILL HAVE SAME

CONNECTIVITY CONFIGURATION.

NOTE 1

NOTE 2

NOTE 3

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 6 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 6 OF 8

FOCN-JA005

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 6 OF 8

FOCN-JA005 COMMUNICATIONS4/28/19

DSE

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 6 OF 8

FOCN-JA005 COMMUNICATIONS4/28/19

DSE

EQUIPMENT ENCLOSURE AT TPSS

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

UL®

CAT.5e

LISTED

S M A R T P R O - U P S

Release Lock

TOP WITH EXHAUST FANS

42U NEMA 4 EMI RATED CABINET DOORS – FRONT AND REAR SIDES

CABLE MANAGEMENT

INDUSTRIAL NETWORK SWITCH

CAT 6 24 PORT PATCH PANEL

PULL OUT SHELF

POWER DISTRIBUTION UNIT

CABLE MANAGEMENT

FIBER DISTRIBUTION PANEL

POWER DISTRIBUTION UNIT

GROUND

NEW CABINENTS

GROUND

NEW CABINENTS

UNINTERRUPTIBLE POWER SUPPLY WITH

BATTERIES

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 7 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 7 OF 8

FOCN-JA006

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 7 OF 8

FOCN-JA006 COMMUNICATIONS4/28/19

DSE

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 7 OF 8

FOCN-JA006 COMMUNICATIONS4/28/19

DSE

EQUIPMENT ENCLOSURE AT OCC

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

UL®

CAT.5e

LISTED

S M A R T P R O - U P S

TOP WITH EXHAUST FANS

42U CABINET DOORS – FRONT AND REAR SIDES

CABLE MANAGEMENT

48 PORT NETWORK SWITCH

CAT 6 24 PORT PATCH PANEL

PULL OUT KEYBOARD

POWER DISTRIBUTION UNIT

CABLE MANAGEMENT

FIBER DISTRIBUTION PANEL

VIDEO MONITOR

APPLICATION / DATABASE SERVER

UNINTERRUPTIBLE POWER SUPPLY WITH

BATTERIES

P OW E R

4-PORT WITH USB SHARE

Model : B006-VUA4-K-R

KVM SWITCH

AUTO SCAN K/M RESET

ON LINE

SELECTED

USB LINE

1 2 3 4KVM SWITCH

POWER DISTRIBUTION UNIT

CISCO NEXUS 2348TQ-ESTATID

2/1

2/2

2/3

2/4

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 3217 18 19 20 21 22 23 241 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

GROUND

NEW CABINENTS

GROUND

NEW CABINENTS

633 17th Street, Suite 1500 Denver, Colorado 80202

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 8 OF 8

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 8 OF 8

FOCN-JA007

MASSACHUSETTS BAY TRANSPORTATION AUTHORITY

FIBER OPTIC COMMUNICATION SYSTEM (FOCS) DESIGN

SIZE FSCM NO DWG NO REV

SCALE 1 : 1 SHEET 8 OF 8

FOCN-JA007 COMMUNICATIONS4/29/19

DSE

FIBER OPTIC CABLE CONDUIT ROUTING

BRAINTREE STATION

NOTE 1. INSTALL 2 - 2" CONDUITS BETWEEN THE TRACTION POWER SUBSTATION TO THE COMMUNICATIONS MANHOLE. FIELD MEASURE THE DISTANCE FOR ACCURACY. ANY EXPOSED CONDUIT SHALL BE GRC. TRANSITION TO SCHEDULE 80 PVC TO RUN BETWEEN BUILDING AND COMMUNICATIONS MANHOLE AT A DEPTH OF 36 INCHES BELOW FINISHED GRADE.

NOTE 2. FURNISH AND INSTALL 12F SM FO CABLE FROM TRACTION POWER SUBSTATION IN NEWLY INSTALLED CONDUIT TO COMMUNICATIONS MANHOLE. USE THE EXISTING MULE TAPE TO PULL FIBER OPTIC CABLE THOUGH TO THE SIGNAL BUNGALOW VAULT.

PULL IN ADDITIONAL MULE TAPE ALONG WITH FIBER OPTIC CABLE FOR FUTURE USE.

NOTE 3. CONTINUE THE INSTALLATION OF THE FIBER OPTIC CABLE FROM THE SIGNAL BUNGALOW VAULT ALONG THE SIGNAL BUNGALOW IN THE EXISTING LADDER RACK AND TERMINATE THE FIBER IN THE EXISITING FIBER RACK.

FIBER OPTIC CABLE

EXISTING SYSTEMS

LEGEND

FIBER OPTIC CABLE

EXISTING SYSTEMS

LEGEND

BRAINTREE STATION

SIGNAL BUNGALOW

COMMUNICATIONS

MANHOLE

COMMUNICATIONS

MANHOLE (EXISTING)

WITH MULE TAPE TO

SIGNAL BUNGALOW VAULT

TRACTION POWER SUBSTATION

TWO 2" CONDUITS TO BE

INSTALLED FROM TRACTION

POWER SUBSTATION TO

COMMUNICATIONS

MANHOLE

633 17th Street, Suite 1500 Denver, Colorado 80202 633 17th Street, Suite 1500 Denver, Colorado 80202

SIGNAL BUNGALOW

EXISITING

FIBER RACK

SIGNAL

BUNGALOW

VAULT

NOTE 1

NOTE 2

NOTE 2

NOTE 2

NOTE 3

GRC

PVC

dweinberger Callout Communications Manhole with Mule tape connected to Signal Bungalow vault dweinberger Callout cable to be pulled in ladder tray to existing fiber rack dweinberger Callout Signal vault under bungalow dweinberger Callout install two 2" conduits from TPSS underground to communications Manhole along ROW

PLAN SET 20190428 FINAL.vsdx
TOC
FOCN-JA001
FOCN-JA002
FOCN-JA003
FOCN-JA004
FOCN-JA005
FOCN-JA006