PART C - DRAWINGS AND ATTACHMENTS_07172024.pdf
PDF 33 MB Posted
- Attached to
- DBB Multiple Facility & Infrastructure Project, Lombrum Naval Base, Los Negros Island, Papua New Guinea
- Solicitation number
- N6274224R6717
About this file
This document is a solicitation package for a Multiple Facility & Infrastructure Project at the Lombrum Naval Base in Papua New Guinea. The package includes the following parts: Part A - Solicitation, Proposal Form and Documents; Part B - NAVFAC Specifications Work Order; Part C - Drawings and Attachments; and Part D - Exhibits such as the Pre-Proposal Inquiries Form, Offeror Experience Project Data Sheet, Past Performance Questionnaire, and Bill of Quantities.
The solicitation number is N6274224R6717, and the closing date for pre-proposal inquiries is August 12, 2024. An organized pre-proposal site visit is scheduled for August 6-8, 2024. The proposal due date is August 28, 2024 at 11:00 am Thailand Time. The contracting agency is the Department of the Navy Naval Facilities Engineering Command. The solicitation seeks offers for the design-build-bid multiple facility and infrastructure project at the Lombrum Naval Base on Los Negros Island in Papua New Guinea.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DBB Multiple Facility & Infrastructure Project N6274224R6717 Lombrum Naval Base, Los Negros Island, Papua New Guinea PART C
PART C - DRAWINGS AND ATTACHMENTS
TABLE OF CONTENTS
DRAWINGS
01 GENERAL
02 CIVIL
03.01 ARCHITECTURAL – FACILITY WIDE
03.02 ARCHITECTURAL – SMALL BOAT AND BOSUN FACILITY
03.03 ARCHITECTURAL – REGIONAL MARITIME TRAINING FACILITY
04.01 INTERIOR DESIGN – FACILITY WIDE
04.02 INTERIOR DESIGN – SMALL BOAT AND BOSUN FACILITY
04.03 INTERIOR DESIGN – REGIONAL MARITIME TRAINING CENTER
05.01 STRUCTURAL – FACILITY WIDE
05.02 STRUCTURAL – SMALL BOAT AND BOSUN FACILITY
05.03 STRUCTURAL – REGIONAL MARITIME TRAINING CENTER
06.01 ELECTRICAL – FACILITY WIDE
06.02 ELECTRICAL – SMALL BOAT AND BOSUN FACILITY
06.03 ELECTRICAL – RIGIONAL MARITIME TRAINING CENTER
07.01 PLUMBING AND SANITARY DRAINAGE – FACILITY WIDE
07.02 PLUMBING AND SANITARY DRAINAGE – SMALL BOAT AND BOSUN FACILITY
07.03 PLUMBING AND SANITARY DRAINAGE – REGIONAL MARITIME TRAINING CENTER
ATTACHMENTS
01 SITE LOCATION
02 EXISTING SITE PLAN
03 SITE PLAN
04 PROPOSED LOCATION OF THE SMALL BOAT & BOSUN FACILITY
05 PROPOSED LOCATION OF THE REGIONAL MARITIME TRAINING CENTER
06 SITE PHOTOS
07 PAPUA NEW GUINEA HISTORICAL WEATHER DATA
G-001
FINAL SUBMITTAL
MULTIPLE FACILITY AND INFRASTRUCTURE PROJECTS AT
LOMBRUM NAVAL BASE, PAPUA NEW GUINEA (PNG)
G-002
INDEX OF DRAWINGS
A
A
A
A
A
A
AA
A
A
A
B
B
C
D
E
F
G G
H I
J
K
L
M
N O P
Q
R
S
T
U
V
W
X
X
Y Z
AA
AB
AC
AD
AE AF
AG
AG
AG
AG
AG
AH
AI
AJ
AK
AK
AK
AK
AL
AMAN AO
AP
AR
AQ
AG
PLAN
NORTH
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P
RKEY PLAN
GRAPHIC SCALE
SATISFACTORY TO DATE
/0
/2
:1
:0
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G -G
E N c a m e ro n .l o n g
.r v t
As indicated
G-101
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322558
ML ML
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
N
EW
G U
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V F A C
P A C
IF
IC
G -1
F A C
IL
IT
Y
W
ID
E
G E N E R A L
E X
IS
TI
N G
S
IT
E
P
LA
N
01 JUL 2024
SCALE: 1 : 4000
B1
EXISTING SITE PLAN
0 40 80 120 160 200 m
SCALE 1:4000 AT ORIGINAL SIZE
A
EXISTING FACILITIES
A MARRIED QUARTERS
B LOMBRUM PRIMARY SCHOOL
C GUARDHOUSE
D LOMBRUM FIELD HOSPITAL
E HMPNGS TARANGUA CHAPEL
F GENERAL MARARTHURS HOUSE
G SAILORS ACCOMMODATION
H PNGDF COMCEN
I PNGDF ARMOURY
J RCP 2 GENERATOR FARM
K PNGDF SQUADRON SUPPORT FACILITY
L FINGER JETTY
M SMALL BOAT JETTY
N RPC 2 STAFF GYMNASIUM
O BARGE LANDING
P LODA WHARF
Q PNG POWER STATION
R HMPNGS TARANGUA HEADQUARTERS
S RPC 2 WAREHOUSES
T DCP ACCOMMODATION
U OFFICERS ACCOMMODATION
V RPC 2 SEWERAGE PLANT
W DECONSTRUCTED RPC1
X MAGAZINE
Y PNGDF CIV ACCOMMODATION
Z PNG-P ACCOMMODATION
AA TRAINING FACILITY
BB HMPNGS TARANGUA HALL
AC RPC 2 PRODUCTION LAUNDRY
AD RPC 2 KITCHEN
AE RPC 2 MESS HALL
AF PNGDF SAILORS CLUB
AG RPC 2 DOMESTIC ACCOMMODATION
AH OFFICERS MESS
AI SAILORS COMBINED KITCHEN & MESS HALL
AJ SAILORS RECREATIONAL FACILITY
AK SECOND WORLD WAR NISSEN HUTS
AL PNGDF PARADE GROUND
AM RPC 2 MULTIPURPOSE SPORTS HALL
AN RPC 2 SPORTS FIELD
AO PNGDF RUGBY FIELD
AP RPC 2 HAZARDOUS MATERIALS STORE & FUEL PUMPS
AQ SECOND WORLD WAR NAVAL FUEL TANKS
AR FRONT SENTRY POST
DEMOLISH ALL STRUCTURES, HARDSTANDS AND
MISCELLANEOUS ITEMS WITHIN THE SITE
NISSEN HUT AND GENERATOR TO
REMAIN. USN TO ENSURE EXISTING
STRUCTURE IS NOT DAMAGED
DEMOLITION WORKS BY OTHER
PARTY (NOT IN SCOPE)
DEMOLITION WORKS BY OTHER
PARTY (NOT IN SCOPE)
TREE TO BE
RETAINED AND
PROTECTED
TREE TO BE
RETAINED AND
PROTECTED
NOTES:
1. ALL HARDSTANDS, ROADS AND FOOTPATHS TO BE REMOVED UNLESS SPECIFIED OTHERWISE.
2. ALL MISCELLANEOUS STRUCTURES AND ASSOCIATED INFRASTRUCTURE TO BE REMOVED
UNLESS SPECIFIED OTHERWISE.
3. DISCONNECT AND CAP AND SEAL 100mm BELOW GROUND LEVEL THE ENGINEERING SERVICES.
ALL TERMINATIONS AND CAPPINGS ARE TO BE RECORDED AND PHOTOGRAPHED.
4. THE CONTRACTOR IS TO BE AWARE OF ALL OVERHEAD ELECTRIFIED SERVICES IN PATH OF
WORKS AND TO TAKE CAUTION.
5. EXISTING TRAINING CENTRE IN NISSEN HUT AND ADJACENT GENERATOR TO BE RETAINED AND
PROTECTED.
6. TREES ON SITE TO BE RETAINED AN PROTECTED AS INDICATED.
DEMOLITION LEGEND
DEMOLITION WORKS
STRUCTURE TO BE RETAINED
DEMOLITION WORKS BY OTHER PARTY
(NOT IN SCOPE)
HARDSTAND, FOOTINGS
AND MISCELLANEOUS
ITEMS TO BE DEMOLISHED
EXISTING NISSEN HUT AND
GENERATOR TO BE RETAINED
DEMOLITION WORKS BY
OTHER PARTY (NOT IN SCOPE)
HARDSTAND AND MISCELLANEOUS
ITEMS TO BE DEMOLISHED
NOT IN SCOPE
DEMOLITION WORKS BY
OTHER PARTY (NOT IN SCOPE)
IMAGE 2 - EXISTING NISSEN HUTS AND OTC SITE IMAGE 3 - EXISTING NISSEN HUTS AND OTC SITE
TREES TO BE RETAINED
AND PROTECTED
IMAGE 1 - OTC SITE
HARDSTAND, FOOTINGS
AND MISCELLANEOUS
ITEMS TO BE DEMOLISHED
EXISTING NISSEN HUT AND
GENERATOR TO BE RETAINED
TREE TO BE RETAINED
AND PROTECTED
TREE TO BE RETAINED
AND PROTECTED
PLAN
NORTH
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P
RKEY PLAN
GRAPHIC SCALE
5 10 15 20 25
SCALE 1:500 AT ORIGINAL SIZE
m
SATISFACTORY TO DATE
/0
/2
:1
:1
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G -G
E N c a m e ro n .l o n g
.r v t
As indicated
G-102
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322559
ML ML
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V F A C
P A C
IF
IC
G -1
D E M O
LI
TI
O N
P
LA
N
01 JUL 2024
SCALE: 1 : 500
B1
DEMOLITION SITE PLAN
A
SCALE: 1 : 100
A1
REFERENCE PHOTOS
SM
AL
L B
OA
TS
JE
TT
Y
A A A A A A A A
A A
A A
A A
A
EE
E
E
E
E
E
E
E
E
E
E
E
E
EEEE
HV
HV
HV
HV
HV
HV
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
W
SSD
SSD
SSD
SSD
SSD
SSD
SSD
SSD
SSD
SSD
SSD
SSD SSD SSD
E E
E
E
E
E
E
E
E
E E E E
E
C
C
C
C
C
C
C
C
C
C
C
C
C
C
W
W
W
W
W
W
W
W
W
W
W
WW
W
W
W
W
W
W
W
W
W
W
W
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
SW
SW
SW
SW
SW
SW
SW
SW
SW
F
F
F
F
F
F
F
F
F
F
F
F
F
F
FFFFF
E(OH)
E(OH)
W
W
W
W
S
SW
SW
SW
CK 2.5
3.0
2.6
2.7
2.8
2.9
3.0
2.72.8
2.9
3.0
3.0
3.5
4.0
2.7
2.7
2.8
2.8
2.9
2.9
3.1
3.1 3.1
3.1
3.2
3.3
3.4
3.6
3.7
3.8
3.9
4.1
4.0
4.1
4.2
4.3
4.4
2.6
2.7
2.8
3.0
2.9
3.1
3.2
3.3
3.0 3.5 4.0
W
W
W
SW-02
E: 541257.091
N: 9774284.319
CL: 2.970
0.6m x 0.6m GIP
CLASS D
SW-03
E: 541254.473
N: 9774290.058
CL: 2.970
0.6m x 0.6m GIP
CLASS D
C C
RM
SSD
SSD
uIL 2.147 ∅ 225
RCP
21.0m 0.4% dIL 2.054 uIL 2.024 ∅ 225
RCP
2.5m 0.5% dIL 2.011
SW-04
E: 541265.533
N: 9774297.103
CL: 2.970
0.6m x 0.6m GIP
CLASS D
S S
W W
W
E: 541268.724 N: 9774266.054
CL: 2.720
0.6m x 0.6m JUNCTION PIT
CLASS D
LV
LV
LV
LV
LV
SW-01
LV
uIL 2.295 ∅ 225
RCP
12.3m 0.5% dIL 2.234 uIL 2.204 ∅ 225
RCP
5.5m 0.5% dIL 2.177
CK
CONNECT INTO WATER RETICULATION
MAIN CONSTRUCTED BY PROJECT 225.
COORDINATE WITH PROJECT 225 FOR
FINAL CONNECTION POINT.
STRUCTURAL RETAINING WALL
REFER DETAIL ON S-506.
DRAINAGE OUTFALL TO SEA.
SEPTIC TANK
REFER TO PLUMING DRAWING PA101.
KERB TRANSITION TO FINISHED SURFACE LEVEL.
CONNECT INTO LOW VOLTAGE RETICULATION
MAIN CONSTRUCTED BY PROJECT 225.
COORDINATE WITH PROJECT 225 FOR
FINAL CONNECTION POINT.
CONNECT INTO COMMS RETICULATION
MAIN CONSTRUCTED BY PROJECT 225.
COORDINATE WITH PROJECT 225 FOR
FINAL CONNECTION POINT.
E: 541317.119 N: 9774289.745
IL: 2.243
SSD
E(OH)
SW
RS
W E
C
LV
W C S
SW-01
E: 541268.724
N: 9774266.054
CL: 2.720
0.6m x 0.6m JUNCTION PIT
CLASS D
uIL 3.490 ø300
RCP
20.7m 1.0% dIL 3.280
4.0 3.6
4.1
3.0
LEGEND
EXISTING SUBSOIL DRAINAGE
EXISTING OVERHEAD ELECTRICITY
EXISTING SEWER
EXISTING RISING SEWER
EXISTING WATER
EXISTING ELECTRICAL SERVICE
EXISTING TELECOMMUNICATION SERVICE
EXISTING HEADWALL AND CULVERT
NEW STORMWATER SERVICE
NEW LOW VOLTAGE ELECTRICAL SERVICE
NEW WATER SERVICE
NEW TELECOMMUNICATION SERVICE
NEW SEWER SERVICE
NEW WATER SLUICE VALVE
NEW STORMWATER GRATED PIT
NEW STRUCTURE ID
EASTING
NORTHING
COVER LEVEL
PIT TYPE
PIT CLASS
UP STREAM INVERT LEVEL
PIPE SIZE
MATERIAL
LENGTH
GRADE
DOWN STREAM INVERT LEVEL
MAJOR CONTOURS 0.5m EXISTING MINOR CONTOURS 0.1m EXISTING MAJOR CONTOURS 0.5m
MINOR CONTOURS 0.1m
CASTELLATED KERBCK
A SWALE TYPE A
S
EXISTING STORMWATER
HV EXISTING HIGH VOLTAGE SERVICE
F EXISTING FUEL SERIVCE
NEW CONCRETE HOLDING TANK REFER PA101
NEW RETAINING WALL
ROCK SCOUR PROTECTION
FINAL SUBMITTAL
C-101 20m
1:200
KEY PLAN
TN
PLAN
NORTH
A1GENERAL CONSTRUCTION PLAN
1:200
RIGID PAVEMENT TYPE 1
RIGID PAVEMENT TYPE 3
ELECTRICAL CONNECTION
FOR HOLDING TANK PUMP.
SBBF
SOFT LANDSCAPING
E: 541289.905 N: 9774283.608
CL: 2.942
CONCRETE HOLDING TANK
S-01
0.0
-1.5
-1.0
-0.5
0.0
-1.5
-1.5
-1.0
-1.0
-0.5
-0.5
-0.5
-0.5
SM
AL
L B
OA
TS
JE
TT
Y
A A A A A A A A
A A
A A
A A
A
FINAL SUBMITTAL
C-102 20m
1:200
KEY PLAN
A1BULK EARTHWORKS PLAN
1:200
TN
PLAN
NORTH
BULK EARTHWORKS LEGEND
ENGINEERED FILL REFER TO C-501
FILL CONTOUR (POSITIVE)0.5
CUT CONTOUR (NEGATIVE)-0.5
EARTHWORKS IN FILL
SBBF
EXISTING FOOTINGS DEMOLISHED
AND BACKFILLED BY OTHER
CONTRACTOR. THE CONTRACTOR
SHALL PROOF ROLL AND COMPACT
TO SUBGRADE LEVEL.
-2.0
EARTHWORKS IN CUT
-1.5 -1.0 -0.5 0
STRUCTURAL RETAINING WALL
REFER DETAIL ON S-506.
0.5
SM
AL
L B
OA
TS
JE
TT
Y
SAW CUT EXISTING PAVEMENT AND CONFIRM ADEQUATE DEPTH
AND CONDITION TO FORM SPECIFIED CONSTRUCTION JOINT.
SJ
DEJ
IJ
SJ
EJ
EJ
EJ
EJ
SJ
SJ
SJ
EJ SJ EJ SJEJ SJEJEJEJ SJSJSJSJ
TJDE
J
LE
IJ
IJ
SJ
TJTJ TJ TJ TJ TJ TJ TJ TJ TJ TJ
DEJ
IJ
DEJL
EJ
EJ
EJ
SJ
SJ
SJ
IJ
1.58
EJ
B
EJ
B
EJB
EJ
B
EJ
B
IJ
IJ
IJ IJ
MW1
J5
A1
A5
J1
DE
J
DE
J
DEJ
SJSJSJSJ
SJ
SJ
SJ
SJ
EJ
SJ
MW1
MW2
J1
GRID SETOUT
SCHEDULE
GRID
A1
A5
J1
J5
EASTING
541288.740
541298.410
541257.870
541267.540
NORTHING
9774308.333
9774293.150
9774288.671
9774273.489
HARDSTAND SETOUT
SCHEDULE
POINT NUMBER
EASTING
541269.333
541275.147
541310.293
541289.275
541255.461
541270.396
NORTHING
9774264.485
9774255.356
9774277.741
9774310.742
9774289.205
9774265.755
ELEVATION
2.819
2.800
2.460
3.010
3.010
2.804
WALL SETOUT
SCHEDULE
POINT NAME
MW1
MW2
EASTING
541253.305
541252.425
NORTHING
9774287.936
9774296.530
FINAL SUBMITTAL
C-103 10m
1:100
KEY PLAN
A1PAVEMENT JOINTING AND SETOUT PLAN
1:100
TN
PLAN
NORTH
LEGEND
RIGID PAVEMENT TYPE 1
RIGID PAVEMENT TYPE 3
ARCHITECTURAL GRID
SETOUT POINT
XXX
WALL SETOUT POINTXXX
SJ SAWN / WEAKENED PLAN JOINT
EJ EXPANSION JOINT
IJ ISOLATION JOINT
EJB EDGE JOINT: BUTT
C2RETAINING WALL SETOUT PLAN
1:100
TJ TRANSVERSE JOINT
DEJ DOWELLED EXPANSION JOINT
HARDSTAND / GENERAL SETOUT POINTXXX
TRIMMER BARS IN ACCORDANCE
WITH DETAILS ON C-503
SBBF
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
A
AA
A
A
A
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
SSSS
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E(OH)
E
E
E
E
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
E(OH)E(OH)E(OH)
E(OH) E(OH) E(OH)
E(OH)
E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH) E(OH)
E E
E
3.0
3.5
4.0
2.8 2.9
3.1 3.2
3.3 3.4
3.6 3.7
3.8 3.9
4.1
4.2
4.3
3.0
3.5
4.0
3.1 3.2
3.3 3.4
3.6 3.7
3.8 3.9
4.1
4.2
4.0
3.8
3.9
4.1
4.2
4.3
3.0
3.5
3.5
2.6
2.72.82.9
3.1
3.1
3.2
3.2
3.2
3.3
3.3
3.4
3.4
3.6
3.6 3.7
3.7
3.7
3.7 3.8
3.8
3.5 4.03.6 3.7 3.8 3.9 4.1 4.2 4.3
S
W
LV
LV
W W
W W
W W
W W W W W W W W W W W W W W W W W W
SV
SV
SV
SV
SV
SV
SV
E(OH)
SW
RS
W E C
LV
W C S
SW-01
E: 541268.724
N: 9774266.054
CL: 2.720
0.6m x 0.6m JUNCTION PIT
CLASS D
uIL 3.490 ø300
RCP
20.7m 1.0% dIL 3.280
4.0 3.6
4.1
3.0
LEGEND
EXISTING OVERHEAD ELECTRICITY
EXISTING SEWER
EXISTING RISING SEWER
EXISTING WATER
EXISTING ELECTRICAL SERVICE
EXISTING TELECOMMUNICATION
EXISTING HEADWALL AND CULVERT
NEW STORMWATER SERVICE
NEW LOW VOLTAGE ELECTRICAL SERVICE
NEW WATER SERVICE
NEW TELECOMMUNICATION SERVICE
NEW SEWER SERVICE
NEW SEWER MAINTENANCE HOLE
NEW WATER SLUICE VALVE
NEW COMMS PIT
NEW STORMWATER GRATED PIT
NEW STRUCTURE ID
EASTING
NORTHING
COVER LEVEL
PIT TYPE
PIT CLASS
UP STREAM INVERT LEVEL
PIPE SIZE
MATERIAL
LENGTH
GRADE
DOWN STREAM INVERT LEVEL
MAJOR CONTOURS 0.5m EXISTING MINOR CONTOURS 0.1m EXISTING MAJOR CONTOURS 0.5m
MINOR CONTOURS 0.1m
KERB ONLY
2.0m KERB TRANSITION TO FLUSH
KO
KT
A SWALE TYPE A
4 CHANNEL TYPE 4
S
EXISTING STORMWATER
C-151
TN
PLAN
NORTH
25m
1:250
12.50
KEY PLAN
RMTC
ABLUTIONS
CONSTRUCT NEW SEWER
MAINTENANCE HOLE OVER
EXISTING STUB PROVIDED BY
PROJECT 225. EXACT
LOCATION TBC ON SITE.
PROVIDE END CAP TO NEW WATER
SERVICE FOR FUTURE CONNECTION.
INSTALL NEW 50mm WATER SERVICE.
INSTALL NEW 32mm WATER SERVICE
TO RMTC AND ABLUTIONS BLOCK.
EXISTING ROAD
EXISTING ROAD
INSTALL NEW ELECTRICAL
PIT AND CONDUIT.
EX
IS
TI
NG
R
OA
D
EXISTING
BUILDING
EXISTING
BUILDING
uIL 2.487 ø300
RCP
17.4m
1.0% MIN
dIL 2.312 uIL 3.298 ø300
RCP
21.8m 2.0% dIL 2.862 uIL 3.177 ø300
RCP
14.4m 1.0% dIL 3.033 uIL 3.301 ø300
RCP
7.7m 2.0% dIL 3.147m uIL 3.700
TRENCH
DRAIN
13.5m 1.0% dIL 3.565m uIL 2.713 ø300
RCP
10.4m 2.0% dIL 2.504 uIL 3.182 ø300
RCP
12.6m 2.0% dIL 2.930
STRUCTURAL ON-GRADE STAIR. STAIRS TO INCLUDE LATHAM
493S SAFETY INSERTTREAD (OR EQUAL APPROVED BY CONTRACT
ADMINISTRATOR) ALUMINIUM AND YELLOW SAFETY RUFAZEL LRV 51.33.
CONTRACTOR TO SUPPLY AND INSTALL PROPRIETARY NCC COMPLIANT
HANDRAIL SOLUTION TO STAIRS. HANDRAILS AND ASSOCIATED BASE
PLATES, POST AND CONNECTION KNUCKLES ARE TO BE GRADE 316
STAINLESS STEEL AND 48.3mm DIA WITH MIRROR POLISH FINISH. APPLY
SAME TREATMENT TO ALL STAIRS SERVICES RMTC.
SW-03
E: 541453.537
N: 9774598.197
CL: 4.060
0.9m x 0.9m GIP
CLASS D
SW-02
E: 541467.937
N: 9774581.818
CL: 4.210
0.9m x 0.9m GIP
CLASS D
SW-01
E: 541425.768
N: 9774544.745
CL: 4.100
0.9m x 0.9m GIP
CLASS D
SW-04
E: 541420.181
N: 9774578.251
CL: 4.21
0.9m x 0.9m GIP
CLASS D
SEW-02
E: 541417.588
N: 9774562.972
CL: 4.25
1.2m MAINTENANCE HOLE
CLASS D
SEW-01
E: 541408.644
N: 9774555.109
CL: 4.075
1.2m MAINTENANCE HOLE
CLASS D
INSTALL ACODRAIN KLASSICDRAIN K300 (OR EQUIVALENT)
TO MANUFACTURER'S SPECIFICATION.
GENERATOR LINK BOX.
B1GENERAL CONSTRUCTION PLAN
1:250
KO
KT KT
STORMWATER PIPE TO
BREAK INTO SIDE OF OPEN
CHANNEL AND MAKE GOOD.
STORMWATER PIPE TO
BREAK INTO SIDE OF OPEN
CHANNEL AND MAKE GOOD.
STORMWATER PIPE TO
BREAK INTO SIDE OF OPEN
CHANNEL AND MAKE GOOD.
RIGID PAVEMENT TYPE 2
RIGID PAVEMENT TYPE 3
SOFT LANDSCAPING
FLEXIBLE PAVEMENT TYPE 1
uIL 2.509 Ø150
PVC-U PN12
11.9m 1.5% dIL 2.330
ENGINEERED CORONUS MATERIAL
0.5
0.5
0.00.0 0.50.5
3.0
3.5
3.5
2.6
2.72.82.9
3.1
3.1
3.2
3.2
3.2
3.3
3.3
3.4
3.4
3.6
3.6 3.7
3.7
3.7
3.7 3.8
3.8
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
A
AA
A
A
A
C-152
TN
PLAN
NORTH
25m
1:250
12.50
KEY PLAN
B1BULK EARTHWORKS PLAN
1:250
ABLUTIONS
EXISTING ROAD
EXISTING ROAD
EX
IS
TI
NG
R
OA
D
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING TREE MUST BE
RETAINED AND PROTECTED.
EXISTING TREE MUST BE
RETAINED AND PROTECTED.
EARTHWORKS VOLUMES
AREA = 4,500m² CUT = 360m³ GENERAL FILL = 900m³ ENGINEERED FILL = 1,330m³ GRUBBED MATERIAL = 675m³
RMTC
BULK EARTHWORKS LEGEND
ENGINEERED FILL REFER TO C-501
NOTE
CUT AND FILL VOLUMES
· ARE NET VOLUMES WITH NO ALLOWANCE FOR BULKING OR COMPACTION.
· DO NOT INCLUDE THE ADDITIONAL VOLUMES ASSOCIATED WITH EXCAVATION
BATTERS AND ENGINEERED FILL BATTERS.
FILL CONTOUR (POSITIVE)0.5
CUT CONTOUR (NEGATIVE)-0.5
EARTHWORKS IN FILL
-0.5
EARTHWORKS IN CUT
0 -0.5 -1.0
1.5
2.50
6.1
3.003.00
.00
9.20
2.7
2.50 2.25
1.50
1.5
EJ
EJ
EJ
EJ
EJ
EJ
EJ EJEJ
EJEJ
EJ
EJ
IJ
EJ EJ EJ
EJEJEJEJEJEJ
EJ EJ
EJ EJ EJ
IJ
SJ
SJ
SJ
SJ
SJSJ
SJSJ SJ
SJ SJ SJ SJ SJ SJ SJ
SJ SJ
SJ
SJ
SJ
SJSJ
SJ
IJ
IJ
IJ
IJ
IJ
IJ
IJ
IJ
SJ
IJ
IJ
IJ IJ
IJ IJ
SJ
EJ
SJ
SJ
1.5
2.200
IJIJ1.5
AA1
A1
H1
A31
H31
BL2
BR2
FL2
FR2
BR1
BL1
FR1
FL1
3.54
2.00
3.00
EJB
EJB
R2R2
901 902
905906
FLEXIBLE PAVEMENT
SETOUT SCHEDULE
POINT NAME
EASTING
541428.654
541473.247
541475.218
541469.375
NORTHING
9774539.790
9774578.864
9774576.615
9774570.993
905 541466.867 9774567.371
906 541431.616 9774536.414
ELEVATION
3.731
3.600
3.645
3.800
3.900
3.686
SIGN SETOUT
SCHEDULE
POINT NAME
BL2
BR2
FL2
FR2
EASTING
541455.811
541457.313
541456.207
541457.714
NORTHING
9774567.659
9774568.980
9774567.208
9774568.533
SIGN SETOUT
SCHEDULE
POINT NAME
BL1
BR1
FL1
FR1
EASTING
541450.406
541451.908
541450.797
541452.304
NORTHING
9774562.907
9774564.228
9774562.452
9774563.777
GRID SETOUT
SCHEDULE
GRID
A1
A31
AA1
H1
H31
EASTING
541415.433
541455.989
541408.041
541423.753
541464.308
NORTHING
9774556.497
9774592.152
9774564.905
9774547.034
9774582.689
C-153
TN
PLAN
NORTH
10m
1:100
KEY PLAN
A1PAVEMENT JOINTING AND SETOUT PLAN
1:100
LEGEND
RIGID PAVEMENT TYPE 2
RIGID PAVEMENT TYPE 3
ARCHITECTURAL GRID
SETOUT POINT
XXX
SIGN SETOUT POINTXXX
SJ SAWN / WEAKENED PLAN JOINT
EJ EXPANSION JOINT
IJ ISOLATION JOINT
EJB EDGE JOINT: BUTT
RMTC
FLEXIBLE PAVEMENT TYPE 1
FLEXIBLE PAVEMENT SETOUT POINTXXX
TRIMMER BARS IN ACCORDANCE
WITH DETAILS ON C-503
ABLUTIONS
ENGINEERED CORONUS MATERIAL
RIGID PAVEMENT TYPE 3
ENGINEERED CORONUS FILL
NATURAL SUBGRADE
PR
OV
ID
E
1m E
NG
IN
EE
RE
D
FI
LL
BE
LO
W
G
RU
BB
ED
S
UR
FA
CE
2 MAX
MINIMUM 1500 UNO
SW
3 MAX
SOFT LANDSCAPING
2000 UNO
2 MAX
SW
3 MAX
2 MAX
1SW
S
3 MAX
750 UNO
S
S
1 MAX
TYPICAL EDGE OF BUILDING TREATMENT DETAIL
SLAB ON GROUND IN CUT
SCALE 1:20
GRUBBED SURFACE LEVEL 150mm
BELOW EXISTING GROUND LEVEL
PROVIDE ISOLATION JOINT BETWEEN
STRUCTURAL SLAB AND RIGID
PAVEMENT TYPE 3
FINISHED GROUND LEVEL
APPROXIMATE LOCATION OF EXCAVATION
USED TO CALCULATE BULK EARTHWORKS
VOLUMES
ENGINEERED FILL PLACED AND COMPACTED IN MAXIMUM
200mm LIFTS. 100% STANDARD COMPACTION TO
AS3798-2007 LEVEL 1 REQUIREMENTS
STRUCTURAL SLAB ON
GROUND
1 MAX2 MAX
S
SW 1
3 MAX
TYPICAL EDGE OF BUILDING TREATMENT DETAIL
SUSPENDED SLAB IN CUT
SCALE 1:20
NATURAL SUBGRADE
ENGINEERED CORONUS FILL
RIGID PAVEMENT TYPE 3
SOFT LANDSCAPING
FINISHED GROUND LEVEL
GRUBBED SURFACE LEVEL 150mm
BELOW EXISTING GROUND LEVEL
PROVIDE ISOLATION JOINT BETWEEN
STRUCTURAL SLAB AND RIGID
PAVEMENT TYPE 3
500MINIMUM 1500 UNO
ENGINEERED FILL PLACED AND COMPACTED IN MAXIMUM
200mm LIFTS. 100% STANDARD COMPACTION TO
AS3798-2007 LEVEL 1 REQUIREMENTS
APPROXIMATE LOCATION OF EXCAVATION
USED TO CALCULATE BULK EARTHWORKS
VOLUMES
PR
OV
ID
E
1m E
NG
IN
EE
RE
D
FI
LL
BE
LO
W
G
RU
BB
ED
S
UR
FA
CE
TYPICAL EDGE OF BUILDING TREATMENT DETAIL
SLAB ON GROUND IN FILL
SCALE 1:20
TYPICAL EDGE OF BUILDING TREATMENT DETAIL
SUSPENDED SLAB IN FILL
SCALE 1:20
STRUCTURAL SLAB / STRIP
FOOTING
STRUCTURE
STRUCTURE
STRUCTURE
PROVIDE ISOLATION JOINT BETWEEN
STRUCTURAL SLAB AND RIGID
PAVEMENT TYPE 3
500MINIMUM 1500 UNO
500MINIMUM 1500 UNO
PROVIDE ISOLATION JOINT BETWEEN
STRUCTURAL SLAB AND RIGID
PAVEMENT TYPE 3
STRUCTURE
PR
OV
ID
E
1m E
NG
IN
EE
RE
D
FI
LL
BE
LO
W
G
RU
BB
ED
S
UR
FA
CE
PR
OV
ID
E
1m E
NG
IN
EE
RE
D
FI
LL
BE
LO
W
G
RU
BB
ED
S
UR
FA
CE
STRUCTURAL SLAB / STRIP
FOOTING
STRUCTURAL SLAB ON
GROUND
NATURAL SUBGRADE
NATURAL SUBGRADE
RIGID PAVEMENT TYPE 3
RIGID PAVEMENT TYPE 3
FINISHED GROUND LEVEL
FINISHED GROUND LEVEL
APPROXIMATE LOCATION OF
EXCAVATION USED TO CALCULATE
BULK EARTHWORKS VOLUMES
APPROXIMATE LOCATION OF
EXCAVATION USED TO CALCULATE
BULK EARTHWORKS VOLUMES
GRUBBED SURFACE LEVEL 150mm
BELOW EXISTING GROUND LEVEL
GRUBBED SURFACE LEVEL 150mm
BELOW EXISTING GROUND LEVEL
SOFT LANDSCAPING
SOFT LANDSCAPING
EXISTING GROUND LEVEL
EXISTING GROUND LEVEL
750 UNO
2000 UNO
2000 UNO
750 UNO
2000 UNO
750 UNO
ENGINEERED CORONUS FILL
ENGINEERED CORONUS FILL
2% 2%
2%2%
C-501
FINAL SUBMITTAL
2m
1:20
REFER TO SPECIFICATION FOR PAVEMENT FINISH
100mm PLAIN CONCRETE PAVEMENT (PCP) CHARACTERISTIC
FLEXURAL STRENGTH OF 4.8 MPa (MIN) AT 28 DAYS
ENGINEERED CORONUS FILL MINIMUM 300mm CBR>40%
REFER SPECIFICATION
EXISTING SUBGRADE
REFER TO SPECIFICATION FOR PAVEMENT FINISH
RIGID TYPE 3
(MOWING STRIP/BUILDING PERIMETER)
SCALE 1:10
RIGID TYPE 2
(FOOTPATH/UNTRAFFICKED)
SCALE 1:10
RIGID TYPE 1
(HEAVY DUTY/TRAFFICKED)
SCALE 1:10
POLYETHYLENE SHEETING, 0.25mm MIN THICKNESS MEDIUM IMPACT
RESISTANCE (AS2870)
200mm COMPACTED CORONOUS MATERIAL (WITH MINIMUM CBR 40%)
COMPRESSIVE STRENGTH 5 MPA
TREATED SUBGRADE LAYER 300mm CBR>5%, REFER SPECIFICATION
190mm PLAIN CONCRETE PAVEMENT (PCP) CHARACTERISTIC
FLEXURAL STRENGTH AS SPECIFIED
EXISTING SUBGRADE
REFER TO SPECIFICATION FOR PAVEMENT FINISH
POLYETHYLENE SHEETING, 0.25mm MIN THICKNESS MEDIUM IMPACT
RESISTANCE (AS2870)
150mm COMPACTED CORONOUS MATERIAL (WITH MINIMUM CBR 40%)
COMPRESSIVE STRENGTH 5 MPA
TREATED SUBGRADE LAYER 300mm CBR>5%, REFER SPECIFICATION
150mm PLAIN CONCRETE PAVEMENT (PCP) CHARACTERISTIC FLEXURAL
STRENGTH AS SPECIFIED
EXISTING SUBGRADE
R5
300 150 300
R515
2.0%2.0%
R5 0R50
DE
PT
H
OF BA
SE
CASTELLATED KERB
SCALE 1:10
R50R50
EXPANSION JOINTS @ MAX 12m CTRS / TOOL JOINTS @ MAX 3m CTRS ALL RADII TO BE 20mm U.N.O.
KERB ONLY 'KO' AGAINST FLEXIBLE PAVEMENT
SCALE 1:10
COMPACTED SUBGRADE
(AS SPECIFIED)
SUBBASE
BASE
NOMINAL KERB FACE.
BOLT DOWN BOLLARD DETAIL
SCALE 1:10
PROVIDE RED REFLECTIVE TAPE
Ø150mm GALVANISED STEEL FIXED BOLLARD (POWDER COATED 'SAFETY YELLOW'), 1300mm
HIGH WITH PLASTIC CAP AND REFLECTIVE TAPE
ATTACHED. BOLLARD INSTALLED IN
ACCORDANCE WITH MANUFACTURERS
SPECIFICATIONS AND DETAILS
250 x 250 x 12mm THICK GALVANISED STEEL BASE PLATE FIXED USING 16mm GALVANISED
CHEMSET FIXING LUGS (4 OFF)
PROVIDE WHITE
REFLECTIVE TAPE
PROOF ROLL AND COMPACT EXISTING MATERIAL
CBR >45%
200m CORONOUS MATERIAL SOAKED CBR 45%
COMPACTED TO 98% MMDD
150m CORONOUS MATERIAL SOAKED CBR 45%
COMPACTED TO 95% MMDD
SELECT CORONOUS FILL SOAKED CBR 45%
MIN 500mm THICKNESS
200m CORONOUS MATERIAL SOAKED CBR 45%
COMPACTED TO 98% MMDD
150m CORONOUS MATERIAL SOAKED CBR 45%
COMPACTED TO 95% MMDD
EXISTING SUBGRADE
FLEXIBLE TYPE 1
OVER EXISTING ROAD SURFACE
SCALE 1:10
FLEXIBLE TYPE 1
OVER INSITU SILTY SANDY SOILS
SCALE 1:10
NOTES
1. PCP INCLUDES 15mm CONSTRUCTION TOLERANCE.
THE LENGTH AND WIDTH OF PCP SLABS SHOULD BE
LIMITED TO MAXIMUM 4.3m UNLESS NOTED
OTHERWISE.
2. CONCRETE PAVEMENT SHALL HAVE 28 DAYS MIN.
COMPRESSIVE STRENGTH OF 40 Mpa.
3. LEAN MIX CONCRETE (LCS) SHALL HAVE 28 DAYS
MIN. COMPRESSIVE STRENGTH OF 4.5 Mpa.
FINAL SUBMITTAL
C-502 1m
1:10
0.50
SL92 MESH CENTRED
SUBGRADE BEAM 32MPa CONCRETE
WITH STEEL-FLOAT FINISH
ISOLATION JOINT 'IJ'
NTS
· JOINT TO BE CONSTRUCTED AGAINST STRUCTURES
STRUCTURE
PAVEMENT AS SPECIFIED
PCP
LCS
PAVEMENT JOINT
PA
VE
M
EN
T
JO
IN
T
4-N12 500mm LONGITUDINAL BARS AT 150mm CENTRES WITH 50mm - 70mm COVER. PROVIDE ISOLATION JOINT 'IJ' TO ALL INTERFACES
BETWEEN NEW CONCRETE AND EXISTING EDGE TREATMENT.
· THE ABOVE SHOWN DESIGN INTENT APPLIES TO ALL DRAINAGE
/ SEWER PITS, SERVICE PITS, COLUMNS AND SLAB
PENETRATIONS
SCALE 1:20
TRIMMER BAR ARRANGEMENTS 'TB'
±5
D/
SEALANT RESERVOIR - TYPE 1 SEALANT RESERVOIR - TYPE 2
PROVIDE SILICONE SEALANT
TO JOINT TOPPING
BOND BREAKING STRIP
JOINT FILLER
INDUCING SAWCUT
SEALANT RESERVOIR
PROVIDE SILICONE SEALANT
TO JOINT TOPPING
CLOSED CELL EXPANDED
POLYETHYLENE FOAM BACKING ROD
· TO ALSO BE USED AS A 'STOPWORK JOINT'
· JOINT TO BE INSTALLED TO MANUFACTURER'S SPECIFICATIONS
TRANSVERSE JOINT
'TJ': FORMED AND TIED
NTS
TIEBAR 500mm INTO SLABTYPE 1 PAVEMENT
D/
DEFORMED TIEBAR (1000mm) AT 500mm SPACINGS
DE
PT
H
OF
B
AS
E D
1st PLACED SLAB 2nd PLACED SLAB
PCP
LCS
PCP
· JOINT TO BE SAWN AS SOON AS CONCRETE HAS
HARDENED SUFFICIENTLY THAT IT WILL NOT BE
DAMAGED BY SAWING (MAX 24HRS)
PAVEMENT AS SPECIFIED
SAWN JOINT 'SJ'
NTS
PCP PCP
LCS
EXPANSION JOINT 'EJ'
NTS
TYPE 3 PAVEMENT 1
2nd PLACED SLAB1st PLACED SLAB
PCP
LCS
PCP
DOWELLED EXPANSION JOINT 'DEJ'
NTS
TYPE 1 PAVEMENT
DEBOND THIS END OF
DOWEL MIN 275mm
CIRCULAR DOWEL (450mm) AT 300mm SPACINGS
· SEE TABLE FOR DOWEL DIAMETER
1st PLACED SLAB 2nd PLACED SLAB
PCP PCP
LCS
±25
D/
±2
DE
PT
H
OF
B
AS
E D
50 - 100
BUTT EDGE
EDGE JOINT 'EJB': BUTT
NTS
EARTHWORKS
VERGE/BATTER
300 MIN
80mm PERFORATED PIPE
CLASS SN8 TYPE 1 PVC
GEOTEXTILE BIDUM A24 OR
SIMILAR WRAPPED AROUND
NO-FINES CONCRETE WITH
200mm MIN OVERLAP
- 8
PCP
LCS
DE
PT
H
OF
B
AS
E D 15
BASE SLAB
THICKNESS (mm)
DOWEL DIAMETER
(mm)
150 < D ≤ 175
175 < D ≤ 200
200 < D ≤ 260
D > 260
DOWEL DIAMETER
CONCAVE CORRUGATIONS
TOP AND BOTTOM
CORRUGATION
FIRST PLACED SLAB
CORRUGATION DEPTH 9
FILLER
DOWEL CAPDOWEL
17 +3,-0
FINAL SUBMITTAL
C-503 0.5m
1:5
0.250
1m
1:10
0.50
2m
HEAD WALL
W
L
GEOTEXTILE. REFER
TO NOTE 7
HEAD WALL
ROCK PAD
FLOW
FLOW
T
RE
FE
R
NO
TE
L
W
ROCK PAD.
REFER TO TABLES.
BLINDING
ROCK PAD OUTLET PIPE/CULVERT STRUCTURE
SCALE 1:20
SECTION
PLAN
SWALE TYPE A
SCALE 1:10
(MIN)500
(MIN)
EQUIVALENT PIPE DIAMETER Ø675
SL62 MESH CENTRALLY PLACED
50mm DIA. WEEP HOLES AT 1500mm MAXIMUM SPACING
FILTER MATERIAL. REFER NOTE 2
FILTER FABRIC. REFER NOTES 3 & 4
50mm BLINDING
TOPSOIL TO TOP OF CHANNEL LIP
CHANNEL TYPE 4
SCALE 1:10
100mm TOPSOIL
STORMWATER PIPE TO BREAK
INTO SIDE OF OPEN CHANNEL
AND MAKE GOOD
NOTES
1. D50 = NOMINAL ROCK SIZE (DIAMETER) OF WHICH 50% OF THE ROCKS
ARE SMALLER (I.E. THE MEAN ROCK SIZE).
2. L = MINIMUM LENGTH OF ROCK PROTECTION.
3. ROCKS SHALL BE ANGULAR IN NATURE. IF SMOOTH ROCKS ARE
USED INCREASE THE ROCK SIZE (D50) BY 36%.
4. WHERE THE WIDTH OF THE ROCK PAD IS GOVERNED BY THE WIDTH
OF THE RECEIVING CHANNEL, THE ROCK PROTECTION WILL EXTEND
2 / 3 MINIMUM UP THE BANKS OF THE CHANNEL.
5. THE ROCK PAD SHOULD BE 180 DEGREES TO AND ALIGNED WITH
THE ANGLE OF DISCHARGE. THE THICKNESS OF THE ROCK PAD TO
BE AT LEAST TWO LAYERS OF NOMINAL SIZE ROCK.
6. THE SURFACE ELEVATION OF THE DOWNSTREAM END OF THE ROCK
PAD SHOULD BE LEVEL WITH THE INVERT OF THE RECEIVING
CHANNEL. THE ROCKS SHOULD BE RECESSED INTO THE OUTLET
CHANNEL TO MINIMISE THE RISK OF EROSION AROUND THE OUTER
EDGES OF THE ROCK PAD.
7. ROCK PROTECTION WILL OVERLAY A GEOFABRIC. REFER TO
STORMWATER SPECIFICATION. THE GEOTEXTILE FILTER CLOTH
MUST HAVE SUFFICIENT STRENGTH AND MUST BE SUITABLY
OVERLAPPED TO WITHSTAND THE INITIAL PLACEMENT OF THE ROCK.
8. THE ROCK SHOULD BE DURABLE AND RESISTANT TO WEATHERING,
AND SHOULD BE PROPORTIONED SO THAT NEITHER THE BREADTH
NOR THE THICKNESS OF A SINGLE ROCK IS LESS THAN ONE-THIRD
ITS LENGTH. THE MAXIMUM ROCK SIZE (SAY D90) GENERALLY
SHOULD NOT EXCEED TWICE THE NOMINAL (MEAN) ROCK SIZE (D50).
REFER TO SPECIFICATION FOR ROCK STRENGTH.
NOTES
1. WORKS TO BE CARRIED OUT IN ACCORDANCE WITH SECTION 7 OF
DOW SPECIFICATION FOR ROAD AND BRIDGE WORKS JUNE 2015, AND
022A STORMWATER SPECIFICATION.
2. FILTER MATERIAL IN ACCORDANCE WITH "FILTER MATERIAL" SECTION
2.1 OF 022A STORMWATER SPECIFICATION AND COMPACTED TO 90%
MDD AS PER AS1289.5.1.1.
3. FILTER FABRIC TO BE IN ACCORDANCE WITH "SUBSOIL DRAINAGE"
SECTION 2.2 OF 022A STORMWATER SPECIFICATION.
4. FILTER FABRIC TO BE PLACED BETWEEN BACKFILL MATERIAL AND
FILTER MATERIAL. FILTER FABRIC SHALL ALSO BE PLACED OVER
WEEP HOLES TO PREVENT FILTER MATERIAL BLOCKING WEEP HOLES.
5. CONSTRUCTION JOINTS TO BE PROVIDED IN CONCRETE BASE EVERY
3m AND AT TRANSITION, BEND HORIZONTAL AND VERTICAL IN THE
CHANNELS GEOMETRY.
6. REFER PLANS FOR SIZE OF CHANNEL USED. CONCRETE CHANNEL
MAY ALSO BE PRECAST. BUTYL RUBBER SEALANT REQUIRED
BETWEEN EACH PRECAST ELEMENT IF CONCRETE CHANNEL IS CAST
IN SITE PROVIDE CONSTRUCTION JOINTS EVERY 3m.
7. CONSTRUCTION JOINTS TO BE PROVIDED EVERY 3m FOR CAST INSITU
CONCRETE CHANNELS
8. WHERE CHANNELS ARE CAST INSITU INSTALL WEEPHOLES TO AVOID
REINFORCEMENT.
9. SIDES OF STONE CHANNELS WIL BE STONE PITCHING IN
ACCORDANCE WITH SECTION 9 OF THE SPECIFICATION.
10.BASE OF CHANNELS TO BE N32 CONCRETE CAST INSITU IN
ACCORDANCE WITH SECTION 4 OF THE SPECIFICATION.
DRAINAGE NOTES
1. ALL DIMENSIONS IN mm, UNLESS OTHERWISE STATED.
2. D50 = 200mm, ROCK PROTECTION TO BE MIN 500mm THICK +
PLACED ON WELL COMPACTED SUBGRADE FREE FROM ORGANIC
MATERIAL.
3. IF SWALE INVERT IS ABOVE EXISTING CHANNEL INVERT, BANK
EROSION PROTECTION IS TO BE PROVIDEDTO EXISTING
CHANNEL BANK IN ACCORDANCE WITH DOW SPECIFICATION.
4. WHERE DOWN PIPES DISCHARGE INTO CONCRETE OR STONE
PITCHED CHANNELS THE OUTSIDE OF THE DOWN PIPE SHALL BE
SEALED AGAINST THE CHANNEL WALL WITH MORTAR GROUTING
AS SPECIFIED IN SECTION 9.1.2 AND 14.6.2 OF THE DOW
SPECIFICATION FOR ROADS AND BRIDGE WORKS 2015.
5. THE MORTAR SHALL BE APPLIED WITH A TROWEL OR PRESSURE
THE CONTRACTOR IS TO ENSURE THE DOWN PIPE IS SEALED TO
THE CHANNEL FOR THE ENTIRE THICKNESS OF THE CHANNEL
WALL.
6. THE DOWN PIPE AND SURROUNDING GROUTING SHALL BE
FINISHED FLUSH AND SMOOTH TO THE CHANNEL WALL.
7. REFER TO DRAWING MED-CV-070 FOR CHANNEL SETOUT.
FINAL SUBMITTAL
C-504 1m
1:10
0.50
2m
10% MAX
HEAD WALL
HEADWALL TO HEADWALL
TYPE 3 RIGID PAVEMENT
HEAD WALL
10% MAX
M
IN
RE
FE
R
NO
TE
COMPACTED GRAVEL BACKFILL
(TYP.). REFER NOTE 7
0m m
100mm BLINDING
TYPE 3 RIGID
PAVEMENT
BOLLARDS TO BE INSTALLED AT PATHS
LEADING TO ROAD CROSSINGS - IN LINE
WITH EDGE OF WINGWALL.
TO ROAD
M
IN
2000 MAX SPACING
A
ASECTION
SCALE 1:20
CROSSING WITH INSUFFICIENT DEPTH
SCALE 1:20
FOOTPATH OVER CULVERT DETAIL
SCALE 1:20
FINAL SUBMITTAL
C-505 5m
1:50
2.50
LANDING REQUIRED AT EACH
CHANGE OF DIRECTION
SJEJ SJEJ 15
001 IN 8 MAX
KERB KERB ONLYTRANSITION
A
B
EQUIDISTANT TO TANGENT POINT
MIN = 1.00m MAX = 2.25m
MIN
1.0m
MAX
2.25m
LANDING
LANDING
EJ
EJ
SJ
SJ
SJ
SJ
SJ
SJ
EJ
SJ
SJSJ
SJ
EJSJSJSJSJ EJEJ
SJ
SJ
EJ
EJ
SJ
ROAD
FLEXIBLE TYPE 11.5m MINIMUM LANDING 1.25m RAMP AT 1:8 MAX 1.5m MINIMUM LANDING FOOTPATH
FOOTPATH
RIGID TYPE 3
A
B
NOTES
1.EXPANSION JOINT TO BE USED AS EVERY 4TH JOINT.
2.MAXIMUM WIDTH:LENGTH RATIO OF 1.5 BETWEEN JOINTS.
FINAL SUBMITTAL
C-506 10m
1:100
2m
E
M
IN
IM
UM
m m
U
NT
RA
FF
IC
KE
D
AR
EA
S
M
IN
IM
UM
0m m
T
RA
FF
IC
KE
D
AR
EA
RS
MIN 600 FROM STORMWATER & FUEL IN CONDUCTIVE ENCLOSURES
MIN 500 FROM OTHER SERVICES IN CONDUCTIVE ENCLOSURES
MIN 500 TO SEWER & >Ø65 WATER
MIN 300 TO FUEL
MIN 100 TO ALL OTHER SERVICES
PAVEMENT / LANDSCAPE TOPSOIL
SELECT BACKFILL
MECHANICAL PROPERTIES - FREE OF STONES, STABLE
AND HAVE LOW PLASTICITY THERMAL CONDUCTIVITY -
MATERIALS THAT HAVE LOW THERMAL CONDUCTIVITY
SUCH AS SAND WILL NOT BE UTILISED
OTHER SERVICE
OTHER
SERVICE
M
IN
F
RO
M S
TO
RM
W
AT
ER
F
UE
L
IN
C
ON
DU
CT
IV
E
EN
CL
OS
UR
ES
M
IN
O
TH
ER
F
RO
M S
ER
VI
CE
S
IN
C
ON
DU
CT
IV
E
EN
CL
OS
UR
ES
M
IN
T O
FU
EL
Ø6
W
AT
ER
M
IN
T
O
SE
W
ER
M
IN
T O
AL
L
OT
HE
R
SE
RV
IC
ES
M
IN
IM
UM
m m
U
NT
RA
FF
IC
KE
D
AR
EA
S
M
IN
IM
UM
m m
T
RA
FF
IC
KE
D
AR
EA
RS
MIN 300 TO SEWER, FUEL & WATER
MIN 100 TO ALL OTHER SERVICES
PAVEMENT / LANDSCAPE TOPSOIL
COMPACTED BEDDING SAND
OTHER SERVICE
OTHER
SERVICE
M
IN
T O
FU
EL
S
EW
ER
M
IN
Ø6
W
AT
ER
M
IN
T O
AL
L
OT
HE
R
SE
RV
IC
ES
DRAINAGE PIPE TRENCH DETAIL
SCALE 1:5
ELECTRICITY TRENCH DETAIL
DIRECT BURIED
M
IN
IM
UM
m m
U
NT
RA
FF
IC
KE
D
AR
EA
S
M
IN
IM
UM
m m
T
RA
FF
IC
KE
D
AR
EA
RS
PAVEMENT / LANDSCAPE TOPSOIL
COMPACTED BEDDING SAND
OTHER SERVICE
OTHER
SERVICE
M
IN
F
RO
M E
LE
CT
RI
CA
L
IF
IN
C
ON
DU
CT
IV
E
EN
CL
OS
UR
E
M
IN
T O
AL
L
OT
HE
R
SE
RV
IC
ES
PRESSURE PIPE TRENCH DETAIL
SW
RS / W / F
MIN 500 FROM ELECTRICAL IF IN CONDUCTIVE ENCLOSURE
MIN 300 TO STORMWATER
MIN 100 TO ALL OTHER SERVICES
POLYMERIC MARKING TAPE
NOTE: CLEARANCES SHOWN FOR <Ø65 WATER
REFER TO TABLE FOR ALL OTHER PRESSURE SERVICES.
150 MIN
100 MIN
150 MIN
NOTE: CLEARANCES SHOWN FOR STORMWATER DRAINAGE. REFER TO TABLE FOR SEWER
VALUES.
SCALE 1:5
SCALE 1:5
POLYMERIC MARKING TAPE
TRENCH FILL
SERVICE CROSSING UNDER CHANNEL
OTHER SERVICE
SELECT TRENCH
BACKFILL MATERIAL PER
SERVICE SPECIFICATION
SCALE 1:10
DE
SI
RA
BL
E
M
IN
UNDERGROUND UTILITY CLEARANCES (mm)
MINIMUM COVER
COMMUNICATIONS
(HB29 2000)
ELECTRICAL
(AS 3000-2018)
SEWER
(AS 3500.3) (WSA 02 &
04)
STORMWATER
(AS 3500.3)
WATER <Ø65
(AS 3500.1)
WATER >Ø65
(WSA 03) FUEL
UNTRAFFICKE
D TRAFFICKED H V H V H V H V H V H V H V
COMMUNICATIONS
(HB29 2000) 600 1000 100 100 100 100 3001 1501 100 100 100 100 300 150 100 100
ELECTRICAL
(AS 3000-2018) 600 1000 100 100 100 100 5001* 2251
500* 600*
600*
500*
500* 5001* 300
500* 600*
600*
SEWER
(AS 3500.3) (WSA 02 &
04)
(500 MIN.)+ 3001 1501 5001* 2251
500* 3001 1501 300 300 100 100 1000a
600b 500a
300b 300 300
STORMWATER
(AS 3500.3) 450
(500 MIN.)+ 100 100 100
600* 600* 300 300 100 100 300 100 300 150 300 300
WATER <Ø65
(AS 3500.1) 450
(600 MIN.)+ 100 100 100
500* 500* 100 100 300 100 100 100 100 100 100 100
WATER >Ø65
(WSA 03) 450
(600 MIN.)+ 300 150 5001* 300
500* 1000a
600b 500a
300b 300 150 100 100 300 150 300 300
FUEL
900 900 100 100 300
600* 600* 300 300 300 300 100 100 300 300 100 100
* MINIMUM SEPARATION OF CONDUCTIVE ENCLOSURES TO LOW VOLTAGE ELECTRICAL EARTHING ELECTRODE
+ MINIMUM DEPTH WHEN CONCRETE ENCASED
1 WSA Values a Gravity Sewer b Pressure Sewer
SCALE 1:20
OVERHEAD
POWERLINE
CLEARANCES (mm) H V
BUILDINGS 2100 3700
TREES/BUSHES 2100 2100
* MINIMUM SEPARATION OF CONDUCTIVE
ENCLOSURES TO LOW VOLTAGE
ELECTRICAL EARTHING ELECTRODE
+ MINIMUM DEPTH WHEN CONCRETE
ENCASED
SCALE 1:20
MINIMUM INTERNAL DIMENSIONS FOR
STORMWATER AND INLET PITS
DEPTH TO INVERT OF
OUTLET
MINIMUM INTERNAL DIMENSIONS (mm)
RECTANGULAR CIRCULAR
WIDTH LENGTH DIAMETER
≤ 450 350 350 -
≤ 600 450 450 600
> 600 ≤ 900 600 600 900
> 900 ≤ 1200 600 900 1000
> 1200 900 900 1000
SCALE 1:20
FINAL SUBMITTAL
C-507 0.5m
1:5
0.250
1m
MINIMUM PIPE COVER
(mm)
LOCATION MINIMUM
COVER #
NON ROADWAYS
- GENERAL
- INDUSTRIAL/COMMERCIAL
SEALED ROADS 600
MAJOR ROADWAYS /
EMBANKMENTS 750
FREEWAYS 1200
SPRING LINE TRENCH
CLEARANCE
NOMINAL DIAMETER (DN) MINIMUM CLEARANCE
'Lc' TO AS/NZS 2566.1
≤150 100
>150 - ≤300 150
>300 - ≤450 200
>450 - ≤900 300
>900 - ≤1500 350
TRENCH WIDTH TO BE SUFFICIENT TO SAFELY LAY
THE PIPE AND COMPACT THE SIDE SUPPORT ZONE.
PIPE SIZE (DN)
BEDDING AND OVERLAY DEPTH
'Lb' (min) 'Lo'
≤150 75 100
200 - 450 100 150
>450 - ≤900 150 150
MARKING TAPE
WHERE SPECIFIED
TYPE 'B'
(SUPPORT TRENCH STRATA OTHER THAN SAND)
SCALE 1:10
'Lo
'Lb
TR
EN
CH
F
IL
L
PI
PE
E M
BE
DM
EN
T
SPRING LINE TRENCH CLEARANCE DETAIL
SCALE 1:10
SPRING LINE
'Lc' 'Lc'
NOTES:
1. ALL DIMENSIONS IN MILLIMETRES.
2. THIS DRAWING TO BE READ IN CONJUNCTION WITH
WAT-1201.
3. EMBEDMENT, TRENCH FILL AND COMPACTION TO MEET
REQUIREMENTS OF WSA-03 PART 3.
4. WHERE TRENCH FLOOR CONSISTS OF MATERIALS
MARKED WITH * ON WAT-1200 OBTAIN GEOTECHNICAL
ADVICE.
FINAL SUBMITTAL
C-508 1m
ARCHITECTURAL SYMBOLS
WINDOW
NUMBER
ROOM
LONG
NAME
A1
A-301
ROOM TAG
DETAIL NUMBER ROOM NAME
ROOM NUMBER
EXTERIOR ELEVATION
TAG
ELEVATION NUMBER
DIRECTION OF VIEW
SHEET REFERENCE
A1
A-301
BUILDING SECTION TAG
DETAIL NUMBER
SHEET REFERENCE
A1
A-301
BUILDING
A-501
B
DOOR NUMBER
(REFER TO DOOR
SCHEDULE)101
A-401
INTERIOR ELEVATION
TAG
INTERIOR
ELEVATION
NUMBER
A1
A1
A1
A1
DETAIL TAG
SHEET REFERENCE
DOOR TAGWINDOW TAG
SHEET REFERENCE
EW:XX DENOTES WALL TYPE, REFER TO SHEET
PT:XX
CL CENTRELINE OF ELEMENT
FALL FALL DIRECTION SYMBOL
LEVEL DATUM
TILE SETOUT
B
C
PLAN
NORTH
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P
RKEY PLAN
SATISFACTORY TO DATE
/0
/2
:0
:3
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G
A -G
E N c a m e ro n .l o n g
.r v t
1 : 1
A-001
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322571
ML ML
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V A L
P A C
IF
IC
A -0
F A C
IL
IT
Y
W
ID
E
N O
TE
S A B B R E V
IA
TI
O N
A N D
LE
G E N D
01 JUL 2024
1 DIMENSION SHOWN IN CONTRACT DOCUMENTS ARE NOMINAL AND
THEREFORE SHALL BE CONFIRMED ON SITE VIA SURVEYED INFORMATION,
OR CALCULATED INFORMATION AND DETAIL SHOP DRAWINGS BEFORE
COMMENCEMENT OF THE WORKS. CO-ORDINATE THE DESIGN AND FINAL
SITE DIMENSIONS IN CONJUNCTION WITH ALL TRADES.
2 THESE DRAWINGS INDICATE THE GENERAL SCOPE OF THE PROJECT IN
TERMS OF ARCHITECTURAL DESIGN CONCEPT, DIMENSIONS OF THE
BUILDING, THE MAJOR ARCHITECTURAL ELEMENTS AND THE TYPE OF
STRUCTURAL, MECHANICAL, ELECTRICAL SYSTEMS. THE CONTRACTOR
SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF WORK.
3 THE USE OF REPRODUCTIONS OF THESE CONTRACT DRAWINGS BY ANY
CONTRACTOR, SUB-CONTRACTOR, ERECTOR, FABRICATOR, OR MATERIAL
SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS SIGNIFIES HIS
ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT AND
OBLIGATES HIMSELF TO ANY JOB EXPENSE, REAL OR IMPLIED ARISING DUE
TO ANY ERRORS THAT MAY OCCUR HEREON.
4 THESE DRAWINGS ARE TO BE COORDINATED WITH THE SPECIFICATIONS.
REFER TO SPECIFICATIONS FOR PRODUCT GENERAL REQUIREMENTS,
METHODS OF INSTALLATION, AND QUALITY OF WORKMANSHIP.
5 ALL WORKS SHALL BE PERFORMED IN ACCORDANCE WITH STANDARDS OF
BEST PRACTICE BY WORKERS SKILLED IN THEIR RESPECTIVE TRADES.
6 ALL FASTENERS AND CONNECTORS SHALL BE SUITABLE FOR THE CLIMATIC
CONDITIONS FOR MANUS, PNG
7 CONTRACTOR TO PROVIDE SAMPLE MATERIAL FINISHES FOR APPROVAL.
10 ALL WORKS MUST CONFORM THE REQUIREMENTS OF NCC AND APPLICABLE
REGULATORY AGENCIES HAVING JURISDICTION.
13 ENSURE DISCHARGE FROM EXITS COMPLY WITH D1.10
14 ALL DOOR HARDWARE TO BE COMPLIANT HARDWARE FOR BCA ACCESS,
MFPE, SECURITY AND AS 1428. DESIGN DRAWINGS FOR DESIGN
PERFORMANCE DETAILS.
15 FIRE EXTINGUISHERS TO BE PROVIDED. REFER TO WAYFINDING DRAWING
SHEETS
16 THE CONTRACTOR MUST VERIFY FINISH SELECTION OF EXTERIOR AND
INTERIOR FINISHES WITH THE CONTRACTING OFFICER, I.E.
WALL/CEILING/ROOF/FLOOR TEXTURES AND COLORS.
18 FOR ALL DETAILED MATERIALS / FINISHES SCHEDULED AND CODED AS
SHOWN ON THE CONTRACT DRAWING SETS, REFER TO THE PROJECT
SPECIFICATION.
19 ALL WALL MOUNTED FITTINGS ARE TO BE PROVIDED WITH IN-WALL
BLOCKING.
AB ANCHOR BOLT
ACS PNL ACCESS PANEL
ADJ ADJUST
ALT ALTERNATE, ALTITUDE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
BD BOARD
BLDG BUILDING
BLW BELOW
BM BEAM
BMT BASE METAL THICKNESS
BOS BOTTOM OF SLAB / STEEL
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
C TO C CENTER TO CENTER
CAB CABINET
CEM CEMENT
CER CERAMIC
CFC COMPRESSED FIBRE CEMENT
CI CAST IRON
CIP CAST IRON PIPE
CJ CONTROL / CONSTRUCTION JOINT
CLG CEILING
CLG REG CEILING REGISTER
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNDS CONDENSATE
CNSTR CONSTRUCTION
CNTR CNTR
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONT CONTINUE / CONTINUOUS
ARCHITECTURAL ABBREVIATIONS
CORR CORRIDOR
CPT CARPET / COMMON PATH OF TRAVEL
CT CERAMIC TILE
CTR CENTER
D DEPTH / DEEP
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DPC DAMP PROOF COURSE
DR DRAIN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC / ELECTRICAL
EPDM ETHLENE PROPYLENE DIEN MONOMER
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION / EXPOSED / EXPAND
EXT EXTERIOR
FD FLOOR DRAIN
FDTN FOUNDATION
FF FINISH FACE
FFL FINSHED FLOOR LEVEL
FG FIGURE
FHC FIRE HOUSE CABINET
FIN FLR FINISHED FLOOR
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUB / FACE OF SLAB
FR FRAME / FIRE RATING / FIRE RESISTANT
FT FOOT, FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GL GLASS / GROUND LEVEL
GR GROSS
GSU GLAZED STRUCTURAL UNIT
GYP GYPSUM
H HIGH
HB HOSE BIB
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVY HEAVY
ID INSIDE DIAMETER
INSUL INSULATION / INSULATED
INT INTERIOR
J-BOX JUNCTION BOX
JAN JANITOR CLOSET
LAV LAVATORY
LB POUND
LT LIGHT
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURING
MIN MINIMUM / MINUTE
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING / MOTOR OPERATED
MTD MOUNTED
MTG MOUNTING / MEETING
MTL METAL
MWP MEMBRANE WATERPROOFING
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
PCT PERCENT
PEJ PREMOLDED EXPANSION JOINT
PL PROPERTY LINE
PLAS PLASTER / PLASTIC
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
QT QUARRY TILE
R RADUIS / RISER
RA RETURN AIR
RAD RETURN AIR DUCT
RB RESILIENT BASE
RD ROOF DRAIN / ROAD
REFL REFLECT
REFR REFRIGERATION
REINF REINFORCE
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RHS RIGHT HAND SIDE
RL ROOF LEADER
RM ROOM
RND ROUND
RO ROUGH OPENING
RS ROUGH SAWN
RT RIGHT
S SOUTH
SAPC SUSPENDED ACOUSTICAL PANEL CEILING
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SH SHINGLES / SINGLE HUNG
SIM SIMILAR
SPC SUSPENDED PLASTER CEILING
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STOR STORAGE
STR STRAIGHT STRIKE / STRINGERS
SUSP SUSPENDED
T&B TOP AND BOTTOM
TEL TELEPHONE
THK THICK
THRES THRESHOLD
THRU THROUGH
TOS TOP OF SLAB / STEEL
TYP TYPICAL
U/S UNDERSIDE
UON UNLESS OTHERWISE NOTED
V VOLT
VAR VARIATION
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION / VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WASTE / WATT / WEST / WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET / WALL COVERING
WD WOOD
WH WATER HEATER
WP WATERPROOFING / WEATHERPROOF / WORKING
POINT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
XRMR TRANSFORMER
GENERAL NOTES
35 35
CO:SLAB
RC:03
RC:06
(7
IN
C M
E
RI
SE
R
RE
FE
R
TO
S
TA
IR
D
ET
AI
L
NOMINAL 5° ANGLE TO ALL STEPS
EQ EQ
MW:06
TYP. TREAD
END CAP AS PER
MANUFACTURER DETAIL
CO:02
MW:06
FFL
RC:06
RC:03
RC:04
RC:02
RC:05
MW:09
RC:01
CAST IN SAFETY INSERT TREAD
STOPPED 10mm FROM EDGES OF
CONCRETE STEPS
MAX
ø 125
MAX. 125mm
CO:SLAB
RC:01
RC:02
RC:03
RC:04
RC:06
RC:05
MW:09
FFL
FIXING TO TIMBER COLUMN AS PER
MANUFACTURER DETAILS
S.S. BOLT DOWN POST ANCHOR
TO SUIT POST, REFER TO
STRUCTURAL DETAILS
PLASTIC PACKING SHIM AS
SPECIFIED, TO ISOLATE POST
ANCHOR FROM CONCRETE SLAB
100 100
CO:SLAB
RC:06
RC:05
RC:04
RC:03
RC:02
RC:01
MW:09
ST:COL
140 x 140mm
FFL
(7
IN
C
M E
(75 IN CME)
A1 A-501
Sim
A2 A-501
Sim
CO:SLAB
S.S. BOLT DOWN POST
ANCHOR TO SUIT POST, REFER
TO STRUCTURAL DETAILS
FIXING TO TIMBER
COLUMN AS PER
MANUFACTURER DETAILS
140 x 140mm
ST:COL
RC:01
MW:09
RC:01
(7
IN
C
M E
A1 A-501
Sim
CO:SLAB
S.S. BOLT DOWN POST
ANCHOR TO SUIT POST, REFER
TO STRUCTURAL DETAILS
FIXING TO TIMBER
COLUMN AS PER
MANUFACTURER DETAILS
RC:01
MW:09
ST:COL
140 x 140mm
MID RAIL FOR TYPE 2
AS REQUIRED
S.S. BOLT DOWN POST ANCHOR
TO SUIT POST, REFER TO
STRUCTURAL DETAILS
E Q
E
Q
CO:SLAB
FIXING TO TIMBER
COLUMN AS PER
MANUFACTURER DETAILS
RC:06
RC:05
RC:01
RC:02
RC:03
RC:04
ST:COL
MW:09
140 x 140mm
MID RAIL FOR TYPE 2
AS REQUIRED
S.S. BOLT DOWN POST
ANCHOR TO SUIT POST, REFER
TO STRUCTURAL DETAILS
E Q
E
Q
CO:SLAB
FIXING TO TIMBER
COLUMN AS PER
MANUFACTURER DETAILS
RC:06
RC:05
RC:02
RC:03
RC:04
ST:COL
MW:09
RC:01
140 x 140mm
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P R
SATISFACTORY TO DATE
/0
/2
:0
:4
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G
A -G
E N c a m e ro n .l o n g
.r v t
As indicated
A-501
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322572
ML JL
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V A L
P A C
IF
IC
A -5
F A C
IL
IT
Y
W
ID
E
A R C H
IT
E C
TU
R A L
TY
P
IC
A L H A N D R A
IL
D E
TA
IL
S
S H E E T
01 JUL 2024
SCALE: 1 : 5
D1
TYP. MW:09 - RAILING BASEPLATE PLAN
SCALE: 1 : 10
A4
TYP. MW:09 - STAIR TREAD DETAIL
SCALE: 1 : 10
B1
TYP. MW:09 - RAILING MID CONNECTION DETAIL
SCALE: 1 : 10
B2
TYP. MW:09 - RAILING POST CONNECTION DETAIL
SCALE:
B4
TYP. MW:09 - HANDRAIL 3D VIEW
SCALE: 1 : 5
D2
TYP. MW:09 - HANDRAIL DETAIL PLAN - CORNER POST
SCALE: 1 : 5
D4
TYP. MW:09 - HANDRAIL DETAIL PLAN - MID POST
SCALE: 1 : 10
A1
TYP. MW:09 - HANDRAIL TO COLUMN CONNECTION
SCALE: 1 : 10
A2
TYP. MW:09 - HANDRAIL TO COLUMN CONNECTION
KEYNOTE ABBREVIATIONS LEGEND
CODE DESCRIPTION
CO:02 REINFORCED CONCRETE STAIR IN TIMBER FLOAT FINISHED WITH CAST IN LATHAM
YELLOW NON SLIP ACS20 ALUMINUM 20X30 TO DETAIL.
CO:SLAB CONCRETE SLAB TO STRUCTURAL DETAILING
MW:06 493S SAFETY INSERT TREAD/ LATHAM (OR EQUAL APPROVED)/ALUMINIUM/SAFETY
YELLOW RUFAZEL LRV 51.33
MW:09 AXIOM HERITAGE ALUMINIUM HANDRAIL WITH OVAL TOP RAIL IN ANODISED ALUMINIUM
FINISH, TO BE INSTALLED AS PER MANUFACTURER SPECIFICATIONS
RC:01 AXIOM OVAL HANDRAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER DETAILS
RC:02 AXIOM 38 x 25mm TOP RAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:03 AXIOM 55 x 55mm POST ANODISED ALUMINIUM FINISH AS PER MANUFACTURER DETAILS RC:04 AXIOM 20 x 20mm BALUSTER ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:05 AXIOM 38 x 25mm BOTTOM RAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:06 AXIOM 100 x 70 x 14mm THICK BASE PLATE ANODISED ALUMINIUM FINISH, FOR FIXING TO
CONCRETE AS PER MANUFACTURER DETAILS
ST:COL TIMBER COLUMN AS PER STRUCTURAL DETAIL, ALL CUT EDGES OF TIMBER TO BE
TREATED AND COATED WITH QUANTEC (SIMILAR/ EQUAL) TO PREVENT MOISTURE AND
ROT DAMAGE. ALL TOPS OF COLUMN ARE TO BE CHAMFERED AT A 10 DEGREE ANGLE
TO REMOVE SHARP EDGES FORMED BY THE INTERSECTION WITH ROOF. TOPS OF
COLUMNS TO FOLLOW RAKE OF STRUCTURE ABOVE
0 200 400 600 800 1000 mm
SCALE 1:20 AT ORIGINAL SIZE
0 50 100 150 200 250 mm
SCALE 1:5 AT ORIGINAL SIZE
GRAPHIC SCALE
0 100 200 300 400 500 mm
SCALE 1:10 AT ORIGINAL SIZE
1800 MAX SPAN 1800 MAX SPAN
CL CL CL
S.S. BOLT DOWN POST
ANCHOR TO SUIT POST, REFER
TO STRUCTURAL DETAILS
FIXING TO TIMBER
COLUMN AS PER
MANUFACTURER DETAILS
140 x 140mm
ST:COL
RC:05
RC:06
RC:02
RC:01
MW:09
RC:03
RC:04
CL
ø 125
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P R
SATISFACTORY TO DATE
/0
/2
:0
:5
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G
A -G
E N c a m e ro n .l o n g
.r v t
1 : 10
A-502
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322573
ML JL
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V A L
P A C
IF
IC
A -5
F A C
IL
IT
Y
W
ID
E
A R C H
IT
E C
TU
R A L
TY
P
IC
A L H A N D R A
IL
D E
TA
IL
S
S H E E T
01 JUL 2024
SCALE: 1 : 10
D1
TYP. MW:09 - COLUMN TO COLUMN HANDRAIL DETAIL
SCALE: 1 : 10
B1
TYP. MW:09 - TOP OF STAIR HANDRAIL DETAIL
KEYNOTE ABBREVIATIONS LEGEND
CODE DESCRIPTION
MW:09 AXIOM HERITAGE ALUMINIUM HANDRAIL WITH OVAL TOP RAIL IN ANODISED ALUMINIUM
FINISH, TO BE INSTALLED AS PER MANUFACTURER SPECIFICATIONS
RC:01 AXIOM OVAL HANDRAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER DETAILS
RC:02 AXIOM 38 x 25mm TOP RAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:03 AXIOM 55 x 55mm POST ANODISED ALUMINIUM FINISH AS PER MANUFACTURER DETAILS RC:04 AXIOM 20 x 20mm BALUSTER ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:05 AXIOM 38 x 25mm BOTTOM RAIL ANODISED ALUMINIUM FINISH AS PER MANUFACTURER
DETAILS
RC:06 AXIOM 100 x 70 x 14mm THICK BASE PLATE ANODISED ALUMINIUM FINISH, FOR FIXING TO
CONCRETE AS PER MANUFACTURER DETAILS
ST:COL TIMBER COLUMN AS PER STRUCTURAL DETAIL, ALL CUT EDGES OF TIMBER TO BE
TREATED AND COATED WITH QUANTEC (SIMILAR/ EQUAL) TO PREVENT MOISTURE AND
ROT DAMAGE. ALL TOPS OF COLUMN ARE TO BE CHAMFERED AT A 10 DEGREE ANGLE
TO REMOVE SHARP EDGES FORMED BY THE INTERSECTION WITH ROOF. TOPS OF
COLUMNS TO FOLLOW RAKE OF STRUCTURE ABOVE
0 200 400 600 800 1000 mm
SCALE 1:20 AT ORIGINAL SIZE
0 50 100 150 200 250 mm
SCALE 1:5 AT ORIGINAL SIZE
GRAPHIC SCALE
0 100 200 300 400 500 mm
SCALE 1:10 AT ORIGINAL SIZE
EXTERIOR
INTERIOR
STRUCTURAL ZONE
S
TR
U C
TU
R
A L
ZO
N
E
V A
R
IE
S
CD:FURRING
CD:SARKING1
EW:01
IN:01
CD:01
ST:STUD
CFC:01
EXTERIOR INTERIOR
HEAD DETAIL
BASE DETAIL
STRUCTURE (REFER TO
STRUCTURAL DETAIL)
FILL ALL GAPS WITH
POLYURETHANE SEALANT
SHIM PACKING AS REQUIRED
FOAM INFILL TO PROFILE OF
SHEETING
FOLDED ALUMINIUM FLASHING
FULLY SEALED FIXED TO TIMBER
BLOCKING FRAMING TO COVER
OPENING BETWEEN RAFTERS
SLOPE AWAY
STRUCTURAL ZONE
VARIES
T Y
P
RF:01
AL:02
TIMBER BEAM WITH
S/S FIXING AND S/S
CONNECTION PLATE
NOTE: EW:01A DOES NOT
INCLUDE IN:01
TIMBER PACKER
FFL
ST:RAFTER
RF:EG1
AL:02
RF:RTB
ST:RAFTER
ST:BEAM
RF:FASCIA
EW:01
AL:02
CD:FURRING
CD:SARKING1
IN:01
RE:01
TT:21
DPC:01
CD:01
RF:CRS
AD:01
CD:CAPPING
ST:STUD
ST:STUD
CO:SLAB
NOTE: SLAB SECTION AND
FLOOR FINISH VARIES
A-525
C4
AD:04
SC:01
CFC:01
RF:PKR
RF:AP
EXTERIOR INTERIOR
HEAD DETAIL
BASE DETAIL
FFL
REINFORCED
BLOCKWORK (REFER
TO STRUCTURAL
DETAIL)
FILL ALL GAPS WITH POLYURETHANE
SEALANT
SHIM PACKING AS
REQUIRED
FOAM INFILL TO PROFILE OF
SHEETING
FOLDED ALUMINIUM FLASHING FULLY
SEALED FIXED TO TIMBER BLOCKING
FRAMING TO COVER OPENING WITH
S/S BRACKET SUPPORT FIXED
BETWEEN RAFTERS
SLOPE AWAY
STRUCTURAL ZONE
VARIES
AL:02
FOAM INFILL TO PROFILE
OF ROOF SHEETING
AL:02
FOLDED ALUMINIUM FLASHING FULLY
SEALED FIXED TO TIMBER BLOCKING
FRAMING TO COVER OPENING BETWEEN
RAFTERS,
AL:02
RF:05
ST:RAFTER
RF:EG1
RF:FASCIA
ST:STEEL RAFTER
CD:FURRING
CD:SARKING1
IN:01
ST:STEEL BEAM
CD:SARKING1
IN:01
CD:FURRING
EW:01
RE:01
RF:AP
TT:21
DPC:01
CD:01
AL:02
RF:CRS
AD:01
AD:01
CD:CAPPING
RF:APRON
ST:STUD
CO:SLAB
ST:STUD
NO
M.
ST:ST BRACE
NOTE: SLAB
SECTION AND
FLOOR FINISH
VARIES
A-525
C4
AD:04
SC:01
CFC:01
CFC:01
CFC:01
RF:02
TYP. WELDED END PLATE TO STEEL RAFTER
REFER TO STRUCTURAL DETAIL, USING
CUPHEAD BOLTS RAFTER TO FASCIA
CONNECTION WINDOW AS
SCHEDULED
SOLID SURFACE
WINDOW REVEAL,
COLOUR: OFFWHITE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
S Y S T E M S
C O M M A N D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A V F A C
P A C
IF
IC
A U S T R A L
IA
FINAL SUBMITTAL
S Y M
D E S C R
IP
T
IO
N
D A T E
A P P R
SATISFACTORY TO DATE
/0
/2
:0
:0
A
M
C U s e rs
\c jlo n g
\D o c u m e n ts
\R e v it
L o c a l F ile s \B
L D
G -P
X X
X -1
-G
A -G
E N c a m e ro n .l o n g
.r v t
1 : 5
A-503
M U
LT
IP
L E
F A C
IL
IT
Y
A N D
IN
F R A S
TR
U C
TU
R E
RP
17322574
ML JL
P R O
JE
C
TS
A T
LO
M B R U M
N A V A L B A S E
RYS
1820549
N62742-24-R-6717
LO
M B R U M P A P U A
IN
EA
(P N G
P A P U A
IN
EA
D
EF
EN
C E
FO
R C E
RYS
N A V A L
P A C
IF
IC
A -5
F A C
IL
IT
Y
W
ID
E
A R C H
IT
E C
TU
R A L
E X
TE
R N A L S E C
TI
O N
TY
P
IC
A L D E
TA
IL
S
S H E E T
01 JUL 2024
SCALE: 1 : 5
D1
EW01 - TYPICAL PARTITION PLAN
SCALE: 1 : 5
A1
EW:01 -TYPICAL PARTITION DETAIL
KEYNOTE ABBREVIATIONS LEGEND
CODE DESCRIPTION
AD:01 SEALANT ON BACKING ROD
AD:04 CLOSED CELL FOAM THERMAL BREAK
AL:02 0.9mm FOLDED ALUMINUM FLASHING PANEL, FLASH & SEAL ALL JOINTS TO MATCH
ROOF SHEET OR AS DOCUMENTED; ANODISED MARINE GRADE ALUMINIUM
(EXPOSED/VISIBLE)
CD:01 ALUMINIUM SHEET CLADDING PERMALITE WAVELINE WALL SHEETING WITH REFLECTED
FOIL SARKING ON ALUMINIUM TOPHAT ISOLATED FURRING
CD:CAPPING 0.9mm FOLDED ALUMINUM J CAPPING WITH FOLDED END; ANODISED 25 MICRON FINISH
MARINE GRADE ALUMINIUM
CD:FURRING ISOLATED LIGHT GAUGE ALUMINIUM FURRING WALL FRAMING SYSTEM WITH HEAVY
DUTY (MIN. 3.5mm THK) SELF ADHESIVE (OR EQUIVALENT) CLOSED CELL FOAM TAPE OR
DENSO TAPE ISOLATOR TO BLOCKWORK; SECURE FURRING CHANNELS TO MASONRY
WALLS WITH NYLON WALL PLUGS AND S/S FIXINGS
CD:SARKING1 BRADFORD THERMOSEAL 753HD REFLECTIVE FOIL ROOF SARKING BETWEEN WALL
SHEETING AND TOP HATS/FURRING CHANNELS WITH PRESSURE TAPE AT LAPS IN
ACCORDANCE WITH AS/NZS 4200.2.
CFC:01 9mm CFC LINING FOR WALL FINISH, TAPED AND SET WITH PAINT FINISH
CO:SLAB CONCRETE SLAB TO STRUCTURAL DETAILING
DPC:01 HEAVY ALCOR 0.55mm BITUMEN COATED ALUMINIUM DAMPCOURSE, ALCOR OR
EQUALLY APPROVED
EW:01 PERMALITE WAVELINE ALUMINIUM CLADDING (GLACIER WHITE IN COLOUR)/REFLECTED
FOIL SARKING/EQUAL TO ULLRICH (NZ) UA3813 50mm x 110mm x 4mm TOP HAT ALLOY 6005A T5 MILL RUN AND 50mm HIGH DENSITY EXTRUDED CLOSED CELL POLYSTYRENE XPS DOUBLE FOIL FACE BOARD/ KWILA (MERBAU) KILN DRY TIMBER STUDS/9mm CFC
INTERNAL WALL LINING TAPE AND SET WITH PAINT FINISH.
IN:01 50mm HIGH DENSITY EXTRUDED CLOSED CELL POLYSTYRENE XPS DOUBLE FOIL FACE
BOARD, EQUAL TO KINGSPAN KOOLTHERM K8 (R3.5 DOWN GRADED VALUE R1.9) MIN
40mm - MAX 50mm THK) CLOSED CELL BOARD INSULATION, FULLY TAPED JOINTS WITH 96mm WIDTH 3M 425 FOIL.
RE:01 SHEET VINYL ROLL WITH COVE FILLET SKIRTING MIN 150MM, WITH ANODISED
ALUMINIUM WALL CAPPING
RF:01 ALUMINIUM ROOFING PERMALITE LT7 SAHARA COLOUR WITH REFLECTIVE FOIL
SARKING, WHITE BACK LIGHT ANTICON LAYER (FLUFFY SIDE UP), AUSMESH 300 PVC
(PLASTIC VINYL COATED) 300mmx150mmX2mm STANDARD TO AS/NZS 4389 ON
ALUMINIUM PURLINS AS SPECIFIED. WHEN NO ANTICON INSULATION IS USED AND ONLY
REFLECTIVE SARKING IS USED PROVIDE A FOIL WITH A WITH WHITE BACKED FOIL TO
VISIBLE FACES I.E. FOR COVERED WALKWAYS OR EAVES.
RF:02 ALUMINIUM ROOFING PERMALITE LT7 SAHARA COLOUR WITH REFLECTIVE FOIL
SARKING WITH WHITE BACK VISIBLE, AUSMESH 300 PVC (PLASTIC VINYL…
This is the start of the file's text. The full file is on GovTribe.