PART 5 OF 5 - ITB 26-142-PW Structural Drawings.pdf

PDF 507 KB Posted

Attached to
26-142-PW Hayden Bridge Lower Pond Improvements
Solicitation number
S-P00140-00018019
Issued by
Lane County, Oregon

About this file

This document is a structural drawings file for the Hayden Bridge Filtration Plant Lower Pond Improvements project, prepared by Ausland Group for Eugene Water & Electric Board (EWEB) in Oregon. The project encompasses the design and construction of an overflow structure for the lower pond area, with work governed by the 2022 Oregon Structural Specialty Code (2021 IBC). The structural drawings specify detailed requirements for concrete construction, reinforcing steel, structural steel fabrication, and miscellaneous metals. Design loads include live loads of 100 psf, dead loads of 10 psf, snow loads of 25 psf with no snow drifting, and wind speeds of 98 mph ultimate and 76 mph allowable service design. Seismic design incorporates a Seismic Design Category D classification with specific spectral acceleration parameters (SDS = 0.556, SDI = 0.482) and an equivalent lateral force procedure for analysis. The project is classified as Occupancy Category II with an assumed Site Class D.

Construction specifications mandate ready-mixed concrete conforming to ASTM C94 with 3,000 psi minimum 28-day compressive strength, Grade 60 deformed reinforcing bars per ASTM A706 or A615, and structural steel fabrication per AISC standards with hot-dipped galvanization after fabrication. All welding must be performed by AWS-certified welders using E70 series electrodes, and special inspection is required for concrete field testing, reinforcing steel placement, and post-installed adhesive and mechanical anchors. Fasteners include ASTM A307 grade machine bolts and ASTM F1554 grade 36 anchor bolts with specified nuts and washers. The design incorporates aluminum metal grating with 1/8" bearing bars and handrailing by Golden Railing Inc., along with compacted base rock meeting Oregon Standard Specifications for Construction. Foundation design accommodates bearing pressures of 1,500 psf for the reinforced concrete, flat-bottom tank with a reinforced nonsliding base.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FUNC BY CHK APP

DES

DWN

EWEB WORK ORDER NO.

DATE:

REV DATE DWN CHK APP

DWG NO:

REV

5/ 2/

1:

A

M

JO

N

AT

H

AN

G O

LD

ST

IE

N

STD

STANDARDS CHECKEWEB

PROJECT SHEET NO:

SCALE:

REVISION DESCRIPTION

LINE IS 2 INCHES

AT FULL SIZE

(IF NOT 2" - SCALE ACCORDINGLY)

REV NO.

AUSLAND GROUP

1717 W. SEVENTH AVE.

EUGENE, OREGON 97402

www.AuslandGroup.com

(541) 345-1094

SCOTT METZLER, PE, SE

AS NOTED

05/02/2024

D-36662-S1

S1

SAM

JSG

WATER SYSTEMS

HAYDEN BRIDGE FILTRATION PLANT

LOWER POND IMPROVEMENTS

OVERFLOW STRUCTURE - GENERAL NOTES

GENERAL

ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE CURRENT GOVERNING

EDITION OF THE OREGON STRUCTURAL SPECIALTY CODE (OSSC).

SUBMITTALS AND SHOP DRAWINGS FOR THE ENGINEERS REVIEW WILL BE

REQUIRED AS FOLLOWS:

· CONCRETE MIX DESIGNS;

· REINFORCING STEEL;

· STRUCTURAL STEEL AND MISCELLANEOUS METALS, MILL CERTIFICATES, WPS (PQR

IF APPLICABLE), WELDER CERTIFICATIONS, FILLER METAL;

CONTRACTOR SHALL SUBMIT 3 SETS OF PRINTS FOR REVIEW. FABRICATION SHALL NOT

PROCEED UNTIL SUBMITTALS AND/OR SHOP DRAWINGS HAVE BEEN REVIEWED BY THE

ENGINEER.

CONSTRUCTION LIABILITY

THE CONSTRUCTION CONTRACTOR AND SUBCONTRACTORS AGREE THAT IN

ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, THE

CONSTRUCTION CONTRACTOR AND SUBCONTRACTORS WILL BE REQUIRED TO ASSUME

SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE

OF CONSTRUCTION OF THE PROJECT, INCLUDING SAFETY OF ALL PERSONS AND

PROPERTY; THAT THIS REQUIREMENT SHALL BE MADE TO APPLY CONTINUOUSLY AND

NOT LIMITED TO NORMAL WORKING HOURS, AND THE CONSTRUCTION CONTRACTOR

AND SUBCONTRACTORS FURTHER AGREE TO DEFEND, INDEMNIFY AND HOLD THE

DESIGN PROFESSIONAL HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN

CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT.

DIVISION 03 - CONCRETE

CONCRETE

CONCRETE SHALL BE CONSTRUCTED IN ACCORDANCE WITH ACI 301 & 318 - CURRENT

EDITION. CONCRETE SHALL BE READY-MIXED CONCRETE IN ACCORDANCE WITH ASTM

C94. MAXIMUM WATER-CEMENT RATIO, BY WEIGHT SHALL BE AS FOLLOWS:

AIR ENTRAINING AGENTS SHALL CONFORM TO ASTM C260. CEMENT SHALL CONFORM

TO ASTM C150, TYPE II.

SLUMP WILL BE MEASURED AT THE TRUCK DISCHARGE. PUMPING OF CONCRETE MAY

REQUIRE ADMIXTURES TO INCREASE SLUMP BEYOND THE MAXIMUM SLUMP LISTED

ABOVE. ADMIXTURES ARE SUBJECT TO THE ENGINEER'S REVIEW. THE SPECIAL

INSPECTOR SHALL BE PROVIDED WITH A BATCH TICKET AND WEIGHT TAG UPON

DELIVERY OF EACH LOAD OF CONCRETE.

ALL CONCRETE SHALL BE PLACED WITH MECHANICAL VIBRATION OF CONCRETE, UNO.

ALL CONCRETE SHALL BE CURED IN ACCORDANCE WITH ACI 308.1

REINFORCING STEEL

ALL BARS SHALL BE GRADE 60 DEFORMED BARS CONFORMING TO ASTM A706 OR A615.

LAP SPLICES SHALL BE IN ACCORDANCE WITH ACI 318 UNLESS NOTED OTHERWISE ON

THE PLANS. BARS TO BE WELDED OR FIELD BENT SHALL CONFORM TO ASTM A706.

NON-SHRINK GROUT

NON-SHRINK GROUT SHALL BE FLOWABLE, WITH A MINIMUM 7 DAY COMPRESSIVE

STRENGTH OF 5000 PSI. NON-SHRINK GROUT SHALL BE MASTERFLOW 928 AS

MANUFACTURED BY BASF CONSTRUCTION CHEMICALS OR APPROVED EQUAL.

ADHESIVE ANCHORING SYSTEMS FOR CONCRETE

ADHESIVE ANCHORING SYSTEMS SHALL BE HILTI HIT-HY 200 SYSTEM, SIMPSON SET-3G

SYSTEM OR APPROVED EQUAL. INSTALLATION OF ANCHORS AND ADHESIVE INCLUDING

DRILLING AND CLEANING OF HOLES SHALL BE IN ACCORDANCE WITH THE CURRENT ICC

ES-REPORT. SPECIAL INSPECTION REQUIRED.

28 DAY COMPRESSIVE

STRENGTH

NON-AIR

ENTRAINED AIR-ENTRAINED

3000 PSI CONCRETE .55 .55

CONCRETE

ELEMENT

MIN. 28 DAY

COMPRESSIVE

STRENGTH

MAX. SIZE

AGGREGATE

(INCHES)

MAX.

SLUMP

(INCHES)

TOTAL AIR

CONTENT

FOOTINGS 3000 1 1/2 4 --

FASTENER GRADE & SIZE NUT CLASS NUT STYLE WASHER

ASTM A36 OR ASTM A307A,

4" TO 1 12"

ASTM A563A HEX ASTM F844

ASTM A307B, 14" TO 4" ASTM A563A HEAVY HEX ASTM F844

DIVISION 05 - METALS

STRUCTURAL STEEL AND MISCELLANEOUS IRON

STRUCTURAL STEEL AND MISCELLANEOUS IRON SHALL BE CONSTRUCTED IN

ACCORDANCE WITH AISC CODE OF STANDARD PRACTICE - CURRENT EDITION.

· WIDE FLANGE AND STRUCTURAL TEE SHAPES SHALL CONFORM TO ASTM A992.

· CHANNELS AND ANGLES SHALL CONFORM TO ASTM A36

· STRUCTURAL PLATE SHALL CONFORM TO ASTM A36 OR ASTM A572

· HOLLOW STRUCTURAL SECTIONS - ASTM A500, GRADE B (46 KSI)

· STEEL PIPE - ASTM A53, GRADE B (35 KSI)

STRUCTURAL STEEL AND MISCELLANEOUS IRON SHALL BE HOT DIPPED GALVANIZED

AFTER FABRICATION.

WELDING

ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS PER AWS "STANDARD

QUALIFICATION PROCEDURE" TO PERFORM THE TYPE OF WORK REQUIRED. ALL

WELDING SHALL BE IN ACCORDANCE WITH THE CURRENT AWS WELDING CODE. ARC

WELDING ELECTRODES SHALL BE E70 SERIES FOR A36, A572 & A992 MATERIAL, AND E80

SERIES FOR A706 REINFORCING STEEL.

MACHINE BOLTS, ANCHOR BOLTS, STUDS AND THREADED RODS

1. BOLTS AND RODS SHALL CONFORM TO ASTM A307 GRADE A OR B OR A36.

2. ANCHOR BOLTS SHALL CONFORM TO ASTM F1554 GRADE 36

3. NUTS SHALL BE AS SHOWN BELOW AND FINISH SHALL MATCH FASTENER.

4. HEADED STUDS AND WELDING SHALL CONFORM TO AWS D1.1-CURRENT EDITION,

TYPE B STUDS.

5. STAINLESS STEEL FASTENERS SHALL CONFORM TO ASTM F593 TYPE 304 OR 316.

METAL GRATING

METAL GRATING SHALL BE ALUMINUM AND CONFORM TO THE REQUIREMENTS OF THE

METAL BAR GRATING MANUAL OF NAAMM UNLESS OTHERWISE NOTED. MINIMUM

BEARING BAR SIZE SHALL BE 1/8" WIDE x 1-1/2" DEEP. SPACING SHALL NOT EXCEED

1-13/16" ON CENTER. EACH GRATING PIECE SHALL BE ANCHORED TO THE SUPPORTING

STRUCTURE WITH MANUFACTURERER SUPPLIED CLIPS WITHIN 4” OF EACH CORNER.

MAXIMUM WEIGHT OF EACH PIECE SHALL BE 80 LBS.

ALUMINUM

ALUMINUM SHALL BE 6061-T6 ALLOY. ALL WELDS SHALL BE IN ACCORDANCE WITH

AWS D1.2.

HANDRAILING

HANDRAILING SHALL BE SCH 40 ALUMINUM W/ SCH 80 POST RIVETED RAIL SYSTEM BY

GOLDEN RAILING INC. OR APPROVED EQUAL. SYSTEM SHALL INCLUDE ALL

APPURTANCES NECESSARY FOR A COMPLETE HANDRAIL TO LIMITS SHOWN ON PLAN

VIEW, DWG S2.

DIVISION 31 - EARTHWORK

COMPACTED BASE ROCK

COMPACTED BASE ROCK SHALL CONFORM TO THE REQUIREMENTS OF BASE

AGGREGATE IN THE OREGON STANDARD SPECIFICATIONS FOR CONSTRUCTION.

STRUCTURAL CRITERIA

1. PLANS AND CALCULATIONS FOR THE STRUCTURAL

DESIGN WERE BASED UPON THE 2022 OREGON

STRUCTURAL SPECIALTY CODE (2021 IBC)

2. DESIGN LOADS ARE AS FOLLOWS:

2.1. VERTICAL:

2.2. LATERAL:

WIND:

SEISMIC:

A. IS = 1.0 OCCUPANCY CATEGORY II

C. SITE CLASS D (ASSUMED)

D. SDS = 0.556 SDI = 0.482

E. SEISMIC DESIGN CATEGORY: D

F. SFRS: REINFORCED CONCRETE, FLAT-BOTTOM,

2.3. FOUNDATION:

BEARING PRESSURES 1500 psf TOTAL LOAD

LIVE LOAD:

DEAD LOAD:

SNOW LOAD:

Pf = 20 psf Ce = 1.0 Ct = 1.0 Is = 1.0 Cs = N/A

100 psf 10 psf 25 psf NO SNOW DRIFTING

A. BASIC WIND SPEED VULT = 98 MPH VASD = 76 MPH

B. OCCUPANCY CATEGORY II

C. WIND EXPOSURE B

D. INTERNAL PRESSURE Coef GCpi = N/A

E. COMPONENTS & CLADDING PRESSURE = N/A

B. SS = 0.653 SI = 0.376

GROUND-SUPPORTED TANK WITH REINFORCED,

NONSLIDING BASE

G. DESIGN BASE SHEAR V = 4.64k

H. CS = 0.278

I. R = 2.0

J. ANALYSIS PROCEDURE: EQUIVALENT LATERAL

FORCE PROCEDURE

CONCRETE FIELD TESTING CONTINUOUS TAKING OF STRENGTH SPECIMENS, SLUMP, AIR

CONTENT AND TEMPERATURE TESTS.

CONCRETE FIELD TESTING PERIODIC

VERIFY USE OF APPROVED CONCRETE MIX DESIGN.

VERIFY SHAPE AND LOCATION AND DIMENSIONS OF

CONCRETE ELEMENT

POST INSTALLED ADHESIVE

& MECHANICAL ANCHORS

IN HARDENED CONCRETE

PERIODIC SPECIAL INSPECTION AS OUTLINED IN THE ANCHOR

MANUFACTURER'S RESEARCH REPORT

CAST-IN-PLACE ANCHORS

AND ITEMS EMBEDDED IN

CONCRETE

PERIODIC SIZE, LOCATION, TYPE AND EMBEDMENT OF ITEMS

TO BE CAST IN CONCRETE

REINFORCING STEEL

PERIODIC

PERIODIC INSPECTION OR SIZE, GRADE,

CLEARANCE, AND ALIGNMENT OF REINFORCING

STEEL PRIOR TO THE CASTING OF THE ELEMENT

ELEMENT INSPECTION

FEQUENCY NOTES

CONCRETE

SPECIAL INSPECTION SCHEDULE

SCALE:

OVERFLOW STRUCTURE - PLAN VIEW

NORTH

A S2

B S2

B

S2 SIM

SCALE:

SECTION

SCALE:

SECTION

SCALE:

SECTION

PLANSECTION

SCALE:

DETAIL

FUNC BY CHK APP

DES

DWN

EWEB WORK ORDER NO.

DATE:

REV DATE DWN CHK APP

DWG NO:

REV

5/ 2/

1:

A

M

JO

N

AT

H

AN

G O

LD

ST

IE

N

STD

STANDARDS CHECKEWEB

PROJECT SHEET NO:

SCALE:

REVISION DESCRIPTION

LINE IS 2 INCHES

AT FULL SIZE

(IF NOT 2" - SCALE ACCORDINGLY)

REV NO.

AUSLAND GROUP

1717 W. SEVENTH AVE.

EUGENE, OREGON 97402

www.AuslandGroup.com

(541) 345-1094

SCOTT METZLER, PE, SE

AS NOTED

05/02/2024

D-36662-S2

S2

SAM

JSG

WATER SYSTEMS

HAYDEN BRIDGE FILTRATION PLANT

LOWER POND IMPROVEMENTS

OVERFLOW STRUCTURE PLAN & DETAILS

SCALE:

OVERFLOW STRUCTURE - ELEVATION

FUNC BY CHK APP

DES

DWN

EWEB WORK ORDER NO.

DATE:

REV DATE DWN CHK APP

DWG NO:

REV

5/ 2/

1:

A

M

JO

N

AT

H

AN

G O

LD

ST

IE

N

STD

STANDARDS CHECKEWEB

PROJECT SHEET NO:

SCALE:

REVISION DESCRIPTION

LINE IS 2 INCHES

AT FULL SIZE

(IF NOT 2" - SCALE ACCORDINGLY)

REV NO.

AUSLAND GROUP

1717 W. SEVENTH AVE.

EUGENE, OREGON 97402

www.AuslandGroup.com

(541) 345-1094

SCOTT METZLER, PE, SE

AS NOTED

05/02/2024

D-36662-S3

S3

SAM

JSG

WATER SYSTEMS

HAYDEN BRIDGE FILTRATION PLANT

LOWER POND IMPROVEMENTS

OVERFLOW STRUCTURE - ELEVATION