Gateway National Recreation Area Repair Park Telecommunications Damaged by Hurricane Sandy Richmond County, New York Solicitation No. P15PS00589
GATE 201049B
AMENDMENT NO. 0003
August 12, 2015
Responses to Questions
1. Question: Is submission by email acceptable?
Answer: Refer to Amendment No. 2.
2. Question: Is traffic control required? If yes, are police required and should that cost be included in our Bid?
Answer: No. Refer to these references: 2.3.10 Access - Coordinate construction efforts with the Contracting Officer such that there is minimal impact to the work of the National Park Service personnel and the visiting public. G10 1.4.6 GROUND DISTURBANCE - 4. Road access to buildings must remain open at all times; all other internal roads may only be interrupted between the hours of 6:00PM and 6:00AM with 48-hour previous notice and approval from the Park. Z10 1.2 WORK RESTRICTIONS - Access must be maintained to all park facilities at all times. During construction of ductbanks under pavement at Sandy Hook Unit, access to all buildings and other facilities must be maintained via detour or partial roadway, sidewalk, and MUP closures. Coordinate any roadway, sidewalk, and MUP closures, detours, and staging with NPS prior to construction.
3. Question: Can we use square lids for the Hand-holes?
Answer: No. Refer to Sheet E.402 COMMUNICATION HANDHOLE AND DUCT DETAILS and Specification G40 TELECOMMUNICATION SYSTEM Section 1.7.3.2 HANDHOLES.
4. Question: Does the fiber cable have to be armored or is non-armored acceptable?
Answer: Cable may be non-armored. Refer to Specification G40 TELECOMMUNICATION SYSTEM Section 1.7.2 CABLES AND WIRING and Sheet G.001 GENERAL NOTES for fiber optic cable requirements.
5. Question: If non-armored cable is acceptable do we need to install a tracer wire with cable?
Answer: No.
6. Question: Is there a typical size for existing manholes/hand-holes?
Answer: The existing telecommunications handholes installed under the Fast Track portion and under the MUP 3 Project were designed to be 4’x4’x4’. The existing telecommunications concrete pits along Hartshorne Drive are approximately 5’x7’.
7. Question: Is there going to be a specific naming convention that is going to be used during installation or is the contractor to create one?
Answer: NPS shall provide the naming convention direction by identifying an asset number to the Contractor.
8. Question: Is there an average distance from the point of entry (POE) to the termination point that we can use for bidding purposes? If it is more than 50 feet, it is safe to assume that we will have to install IMC or RMC?
Answer: Per note #32 on Sheet G.001 GENERAL NOTES – The anticipated length of interior cabling is approximately 50 feet from building penetration (POE) to telecommunications termination enclosure (termination point) for most buildings). Building 102 will require approximately 200 feet from building penetration to the telecommunications termination enclosure. Other buildings may also require more than 50 feet from building penetration to the telecommunications termination enclosure;
these buildings will be determined once the final telecommunications termination enclosure locations have been determined for each building. Per Specification G40 TELECOMMUNICATION SYSTEM Section 1.7.3.3.5 DUCTBANK SIZE, cables entering a building from the outside and not rated for inside plant use may not extend beyond 50 feet (15 m) from the cable’s point of entry into the building. The point of entry is defined as the place where the cable penetrates the exterior wall or floor. The point of entry may be extended beyond the 50-feet (15-m) limitation by using either rigid metal conduit (RMC) or IMC, both of which shall be grounded. IMCs/RMCs are discussed on Page 80, Specification G40 TELECOMMUNICATION SYSTEM Section 1.7.3.3 CONDUITS AND
DUCTBANKS.
9. Question: Is it the government’s intention that the contractor bid using wall mount splice enclosures?
Answer: Splice cases for the transition from outdoor-rated cable to interior-rated cable are described in Specification G40 TELECOMMUNICATION SYSTEM Section 1.6.2.2.2 FIBER CABLE ENTRANCE. Final termination enclosure requirements are listed on Sheet G.001 GENERAL
NOTES.
10. Question: If rack mount enclosures are required, are there existing racks or will the contractor be responsible for procuring and installing new racks (wall mount or free standing).
Answer: Yes. Page 14 states: Terminate the fiber on newly provided enclosures/networking racks.
Sheets E.201 through E.213/E.301 through E.313 denote the equipment required for each building.
Any equipment noted as anything other than “existing” shall be provided by the contractor.
11. Question: What fiber termination type is to be used (ie. LC, SC, ST)?
Answer: Per Sheet G.001 GENERAL NOTES, terminate all fiber optic strands with non-keyed LC connectors.
12. Question: Are fiber optic splice cases permitted?
Answer: Splice cases are permitted for the transition from outdoor-rated cable to interior-rated cable, transition cable quantities, transition cable sizes, and where standard spool lengths prohibit a continuous fiber optic cable run only and are described in Specification G40 TELECOMMUNICATION SYSTEM Section 1.6.2.2.2 FIBER CABLE ENTRANCE.
13. Question: Is there are requirement for the quantity of slack required in each hand-hole?
Answer: Service loops shall be provided at each handhole as well as at each termination panel and shall comply with the requirements provided in Amendment #1.
14. Question: The links in the project scope document do not seem to be working, lead to a page that is not found.
Example: The work of this RFP shall be performed in accordance with the Denver Service Center (DSC) Workflows website, http://www.nps.gov/dscw.htm.
Answer: Try this link: http://www.nps.gov/dsc/workflows/dbbdesdevelop.htm
15. Question: It was stated during the pre-bid meeting that the bulk of the engineering that is required is building penetrations. Is this a correct assumption?
Answer: Somewhat. The penetrations are important, but so are the other project requirements.
http://www.nps.gov/dscw.htm