P09 Drawings 589A5-15-115B SPS (23 PGS).pdf
PDF 8 MB Posted
- Solicitation number
- 36C25521R0102
About this file
This notice provides details for a competitive solicitation to correct design issues for the Sterile Processing Services (SPS) project at the Colmery O'Neil VA Medical Center in Topeka, Kansas. The scope of work includes modifying the existing air handling unit and supply ductwork, adding a return air grille, modifying supply and exhaust ductwork for the cart wash, removing an abandoned DX coil and components, changing sterilizers from standing boilers to central steam, installing a new hollow metal doorway, adding an N+1 exhaust fan, and providing testing, adjusting, and balancing of the HVAC system. The estimated cost is between $1 million and $5 million. Proposals will be posted on or about July 30, 2021, with an undetermined but estimated 182-day period of performance from notice to proceed. The solicitation number is 36C25521R0102 and will be a firm fixed-price contract under NAICS code 236220.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25521R0102 0002.pdf | ||
| 36C25521R0102 0003.pdf | ||
| Revised Wage Det. 589A5-15-117B SPS.docx | DOCX document | |
| S02 36C25521R0102 589A5-15-117B SPS.docx | DOCX document | |
| 36C25521R0102 0001.pdf | ||
| Response to RFIs 589A5-15-117B SPS.pdf | ||
| Final Specifications 589A5-15-115B SPS (1386 PGS).pdf | ||
| P07 WD KS20210058 07-16-2021.docx | DOCX document | |
| P09 Evaluation Criteria 589A5-15-117B SPS (7 PGS).docx | DOCX document | |
| 36C25521R0102_1.docx | DOCX document | |
| P09 SOW Bid Breakdown (3 PGS).pdf | ||
| P09 Breakout Pricing Request 589A5-15-117B SPS (1 PG).pdf | ||
| P09 Drawing Equipment Cut Sheet 589A5-15-117B SPS (4 PGS).pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
DEPARTMENT OF VETERANS AFFAIRS
RELOCATE STERILE PROCESSING
TOPEKA,KANSAS
PROJECT 589A5-15-117
COVER SHEET
ADDENDUM #1
GI 001
NTS
B007H
B008A
B011B
B006
B013B
B013D
B013A
B011C02
C0-3B
B013
LO
C
K E
R S
(o fc i)
B011A
B009
B006PA
B
6P B
B008
B008B
B010
CLOSET
B006G
12 sq ft
B008C sterad (ofoi) sterad (ofoi)
PIPE CLOSET
B006P
38 sq ft
OFFICE
B006
217 sq ft
STORAGE
B007
93 sq ft
VEST
B013C
55 sq ft
ANTE VESTIBULE
B013
107 sq ft
M. T'LT/L'KRS
B013B
123 sq ft
CART WASH
B008C
97 sq ft
(EX) CORRIDOR
C-03A
207 sq ft emergency eye wash/shower
(cfci)
MECH
B6M
988 sq ft soap dispenser system (ofoi)
F T'LT/LKRS
B013A
113 sq ft
CORRIDOR
C0-3B
204 sq ft
CORRIDOR
C-03C
492 sq ft
VEST
B008A
72 sq ft counter w/ incubators (4) (counter is cfci,incubators are ofci)
STERILIZERS
B009
114 sq ft
PREP / PACK
B008
687 sq ft w ire s he lv 'g
(o fo
i) w ire s he lv
'g (o fo i) wire shelv'g (ofoi) wrap stand (ofoi) work table (ofoi) work table (ofoi) cart (ofoi) cart (ofoi) cart (ofoi) ster (long chamber)
(ofci) washer/ dryer (ofci) washer/ dryer (ofci) wire shelv'g (ofoi) wire shelv'g (ofoi) caviwave (ofci)
R. O. WATER
B010
53 sq ft r.o. system (ofci)
VEST
B011
96 sq ft
HKPG
B011A
62 sq ft
DECONTAM
B012
446 sq ft
CLOSET
B013E
5 sq ft pass-thru dryer (ofci)
B
4M B
B013C
B006G
CORRIDOR
C0-3E
350 sq ft pass-thru window
(cfci)
LOCKERS
(ofci)
5 5 2
6'-0 1/2"
5' -1
1/
2"
'-1
1/
2" 7'
-4
/2
6' -8
1'-4 1/2"
7'-6"
'-2
9'
-1
1/ 2"
5' -1
/2
9'
-1
/2
'-2
8'
-1
/2
6' -7
6' -7
5'
-4
/2
'-8
/2
5'-11"±42'-7 1/2"9'-0 1/2"6'-5"
3'-10" 11'-3"±
'-4
/2
7'-7 3/4"
12'-5 1/2"
2'-7" ster (short chamber)
(ofci)
B6M
MECHANICAL SHAFT
B7M
79 sq ft
B6C
(ex) STAIR #6
B117A
(ex) STAIR #3
B6D
(ex) SILVER RECOV
B6B
(ex) UNOCCUPIED
B7
(ex) MECH B7A
(ex) UNOCCUPIED B7A
(ex) UNOCCUPIED
17151412 18 20 22 24
W
V
T
S
U
R
W
C O
U N
TE
R
WALKWAYWALKWAY
WALKWAY
WALKWAY STAIR #7
MS
SECRETARY
ENTRYS3
P2
P1
COUNTER COUNTER
CORRIDOR
UP
BREAK AREA
S4
UP
U P
U P
A21A
OFFICE
PHARM
162 SF
A21
CHIEF PHARM
PHARM
139 SF
A7
IV RM
PHARM
136 SF
A8
SUPERVISOR
PHARM
123 SF
A9
BREAK
PHARM
213 SF
A9B
OFFICE
PHARM
164 SF
A10A
OFFICE
PHARM
130 SF
A11
VAULT
PHARM
298 SF
A10E
ELEC CL
ES
9 SF
A9C
MECH
ES
51 SF
A7E
ELEC CL
ES
16 SF
A19A
OFFICE
EM
321 SF
B3A
STORAGE
ES
110 SF
A10
PHARMACY
PHARM
3162 SF CORR. CB/2
CORR. CB/4
CORR. CB/3
CORR. CB/1
A16H
ENTRY
DIAG
131 SF
B1A
ENTRY
DIAG
109 SF
A16I
SERVICE DOCK
ES
1155 SF
CORR. CB/3
CONTRACTOR PRIMARY
ACCESS POINT.
INDICATES ARES OF
CONSTRUCTION
NO. TITLE DATE
GI 001 COVER SHEET - ADDENDUM #1 1/13/21
AD 100 DEMOLITION PLAN 1/13/21
AI 100 NEW BASEMENT PLAN 1/13/21
AI 103 EXTERIOR MECHANICAL SHAFT 1/13/21
AI 401 PARTITION TYPES 1/13/21
AF 610 DOOR AND FINISH SCHEDULE 1/13/21
S101 STRUCTURAL - FAN PLATFORM 1/13/21
S102 STRUCTURAL - FAN PLATFORM 1/13/21
S103 STRUCTURAL - FOUNDATION PLAN 1/13/21
MD1-100 BASEMENT PLAN-MECHANICAL DEMOLITION 1/13/21
MG1-103 MECHANICAL DETAILS 1/13/21
MG1-200 MECHANICAL SCHEDULES 1/13/21
MG1-300 MECHANICAL SYMBOLS 1/13/21
MH1-100B BASEMENT PLAN - MECHANICAL 1/13/21
MP1-100 BASEMENT PLAN-MECHANICAL PIPING 1/13/21
MP1-200 OVERALL BASEMENT PLAN - MECHANICAL PIPING 1/13/21
PD1-100 BASEMENT PLAN-PLUMBING DEMOLITION 1/13/21
PP1-100 BASEMENT PLAN-PLUMBING 1/13/21
ED1-100 BASEMENT PLAN-ELECTRICAL DEMOLITION 1/13/21
EG1-600 ELECTRICAL SCHEDULES 1/13/21
EL1-102 BASEMENT PLAN-ELECTRICAL LIGHTING 1/13/21
EY1-100 BASEMENT PLAN-ELECTRICAL SYSTEMS 1/13/21
FAI-100 BASEMENT - FIRE PROTECTION 1/13/21
D at e:
W ed , J an
3, Ti m e:
1:
:0
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
06 Add 1 - MOD 06 01/13/21
95% SUBMITTAL
100% SUBMITTAL
AMENDMENT #2
AMENDMENT #3
AMENDMENT #4
5/20/16 01/20/17 06/23/17 07/25/17 07/25/17
LIST OF DRAWINGS - ADDENDUM #1
NOTE: CLOUDED AREA INDICATES
APPROXIMATE EXTENT OF AREA OF
CONSTRUCTION FOR MEP WORK
NOTE: CLOUDED AREA INDICATES
APPROXIMATE EXTENT OF AREA OF
CONSTRUCTION FOR ARCH &
STRUCT WORK
17151412 18 20 22 24
V
T
S
W
DEMO PLAN
SCALE: 1/4" = 1'-0"
AD 100 0 5 10 FT
1 1
2 2
1 1
EXISTING MECHANICAL ROOM
12 13
DEMO PLAN GENERAL NOTES
A. DEMO ALL EXISTING FLOORING MATERIALS. CERMIC TILE, VINYL TILE,
CARPET, ETC. SEE ABATEMENT SPECIFICATIONS.
B. DEMO EXISTING CEILING GRID. INCLUDE ALL FIXTURES, GRILLS, ETC.
SEE MEP DEMO INFORMATION.SEE ABATEMENT SPECIFICATIONS.
NEW LG METAL FRAMED WALL
ITEMS TO BE REMOVED
EXISTING WALL/ITEM TO REMAIN
EXISTING DOOR AND FRAME TO BE
REMOVED
DEMO PLAN LEGEND
D at e:
T ue , J an
2, Ti m e:
0:
:5
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
DEMOLITION PLAN
AD 100
SMSCALE: 1/4" = 1'-0"
03 Add 1 - MOD 06
95% SUBMITTAL
100% SUBMITTAL
5/20/16 01/20/17
01/13/21
A
A
AI 600
A
A
AI 600
B007H
B008A
B011B
B006
B013B
B013D
B013A
B011C02
C0-3B
B013
LO
C
K E
R S
(o fc i)
B011A
B009
B006PA
B
6P B
B008
B008B
B010
CLOSET
B006G
12 sq ft
B008C sterad (ofoi) sterad (ofoi)
PIPE CLOSET
B006P
38 sq ft
OFFICE
B006
217 sq ft
STORAGE
B007
93 sq ft
VEST
B013C
55 sq ft
ANTE VESTIBULE
B013
107 sq ft
M. T'LT/L'KRS
B013B
123 sq ft
CART WASH
B008C
97 sq ft
(EX) CORRIDOR
C-03A
207 sq ft emergency eye wash/shower
(cfci)
MECH
B6M
988 sq ft soap dispenser system (ofoi)
F T'LT/LKRS
B013A
113 sq ft
CORRIDOR
C0-3B
204 sq ft
CORRIDOR
C-03C
492 sq ft
VEST
B008A
72 sq ft counter w/ incubators (4) (counter is cfci,incubators are ofci)
STERILIZERS
B009
114 sq ft
PREP / PACK
B008
687 sq ft w ire s he lv 'g
(o fo
i) w ire s he lv
'g (o fo i) wire shelv'g (ofoi) wrap stand (ofoi) work table (ofoi) work table (ofoi) cart (ofoi) cart (ofoi) cart (ofoi) ster (long chamber)
(ofci) washer/ dryer (ofci) washer/ dryer (ofci) wire shelv'g (ofoi) wire shelv'g (ofoi) caviwave (ofci)
R. O. WATER
B010
53 sq ft r.o. system (ofci)
VEST
B011
96 sq ft
HKPG
B011A
62 sq ft
DECONTAM
B012
446 sq ft
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A
AI 600
A
A 41A
A
AI 600
A
A
AI 600
A
A
AI 601
A
A
AI 600
A
A
AI 601
A
A
AI 600
A
A
AI 601
A
A
AI 600
A
A
AI 601A
A
AI 600
A
A
AI 601
A
A
AI 600
A
A
AI 601
CLOSET
B013E
5 sq ft
A
A
AI 600
A
A
AI 602
A
A
AI 600
A
A
AI 602
3B
AI 602
A
A
AI 600
A
A
AI 602
pass-thru dryer (ofci)
B
4M B
B013C
B006G
2 3
CORRIDOR
C0-3E
350 sq ft
F.E.
F.E.
F.E.
pass-thru window
(cfci)
F.
E
5 5
LOCKERS
(ofci)
5 5
5 5
6'-0 1/2"
5' -1
1/
2"
'-1
1/
2" 7'
-4
/2
6' -8
1'-4 1/2"
7'-6"
'-2
9'
-1
1/ 2"
5' -1
/2
9'
-1
/2
'-2
8'
-1
/2
6' -7
6' -7
5'
-4
/2
'-8
/2
5'-11"±42'-7 1/2"9'-0 1/2"6'-5"
3'-10" 11'-3"±
'-4
/2
7'-7 3/4"
12'-5 1/2"
2'-7" ster (short chamber)
(ofci)
F.
E ra m p up ra m p up
B6M
MECHANICAL SHAFT
B7M
79 sq ft
17151412 18 20 22 24
V
T
S
W
NEW PLAN-BASEMENT
SCALE: 1/4" = 1'-0"
AI 100
0 5 10 FT
A I 4
2 2
4" CONC HOUSEKEEPING
PAD (SHADED) - VERIFY
LOCATION IN FIELD W/
STEAM GENERATOR
LOCATION
STEAM GENERATOR
RE: MECH (DASHED)
1' -0
1'-0"
1'-0"
EXIST'G AREAWAY - FIELD
VERIFY SIZE
REPAIR WALL AS NECESSARY AFTER
REMOVAL OF DUCT TO MATCH EXISTING
WALL IN CONSTRUCTION AND FIRE RATING
NOTE: COORDINATE LOCATION OF
FLOOR DRAIN W/ MEP DOCUMENTS -
PROVIDE 1/2" x 18" dia DEPRESSION
AROUND FLOOR DRAIN
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
AI 100
NEW BASEMENT PLAN
SMVARIES
Z.
Z.
Z.
Z.
Z Z
3.8 4.7 6 8 10 11.7
Z.
X5.1 X7.4 X9.7X
MECHANICAL
B43M
EXISTING CRAWL SPACE
EXISTING PIPE TUNNEL BELOW CORRIDOR LINK
CORRIDOR
CB/5B
EXISTING SEWAGE
EJECT.
FEC
UP
STAIR #10
B44
EXISTING SUMP PUMP
BIOMED
B42
LOCKER - M
B41
LOCKER - W
B40
BREAK ROOM
B38
FD
WORK AREA
B42B
HSKP
B39
B40
B 42B
B
110 SQ. FT
56 SQ. FT
152 SQ. FT
120 SQ. FT
552 SQ. FT
591 SQ. FT1207 SQ. FT
FD
FD
B38B42
B43
B
BIOMED SERVER ROOM
B42A
149 sq ft
NEW PLAN-IT ROOM
SCALE: 1/8" = 1'-0"
AI 100
MATCH FLOOR HEIGHT OF
ADJACENT AREAS WITH NEW
FLOOR. TOTAL HEIGHT
DIFFERENCE +/- 6”.
NO WORK
0 5 10 FT
NEW BASEMENT PLAN NOTES
A. FIELD VERIFY EXISTING UTILITY LINE AND ELECTRICAL CONDUIT
LOCATIONS-REMOVE EXISTING FUR OUT GYP. BD. OR PLASTER WALLS AND REBUILD
FLUSH AND TIGHT EXISTING ACTUAL OPENINGS, UTILITY LINES AND STRUCTURE.
MAINTAIN MINIMUM STAND-OFF FROM PIPES AND DRAIN LINES 1-1/2”.
NEW LG METAL FRAMED WALL
INDICATES PARTITION TYPE. RE:SHEET
AI-401
NEW WINDOW AND FRAME. REF. WINDOW
SCHEDULE
EXISTING WALL/ITEM TO REMAIN
STAINLESS STEEL GUARD FROM FLOOR TO
CEILING,SCREW-APPLIED
NEW DOOR AND FRAME. RE: DOOR
SCHEDULE
WALL INSET FIRE EXTINGUISHER CABINET
ofoi OWNER FURNISHED, OWNER INSTALLED ofci OWNER FURNISHED, CONTRACTOR INSTALLED
EXISTING DOOR AND FRAME TO BE
REMOVED
FIRE EXTINGUISHER BOX
PLAN LEGEND
D at e:
T ue , J an
2, Ti m e:
0:
:2
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
04 Add 1 - MOD 06 01/13/21
95% SUBMITTAL
100% SUBMITTAL
AMENDMENT #4
5/20/16 01/20/17 07/25/17
HKPG
B011A
62 sq ft
DECONTAM
B012
446 sq ft
'-4
/2
7'-7 3/4"
MECHANICAL SHAFT
B7M
79 sq ft
EXISTING PLAN-MECHANICAL SHAFT
SCALE: 1/4" = 1'-0"
AI 103 0 5 10 FT
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
AI 103
HVAC MODIFICATIONS
VARIES supplemental drawing
D at e:
T ue , J an
2, Ti m e:
0:
:4
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
PIPE BASEMENT
939.9'
BASEMENT
945.9'
FIRST FLOOR
958.5'
SECOND FLOOR
971.1'
THIRD FLOOR
983.7'
ROOF
994.0'
T.O.P 996.38'
EXISTING WALL & PARAPET
SECTION THROUGH EXTERIOR WALL1
MECH. SHAFT ROOF
993.0'
2' -5
X-MECH SHAFT SECTION
Scale: 1/4" = 1'-0"
AI 103
REMOVE EXIST'G EXH FAN re:
MECH (DASHED) - STORE FOR
FUTURE REINSTALLATION at the
DIRECTION OF THE OWNER
REMOVE EXIST'G CAP FLASHING
& WOOD BLOCKING AROUND TOP
OF PARAPET (DASHED)
NEW REINF CONC SLAB RE:
STRUCTURAL
EXIST'G SHAFT ROOF TO REMAIN
- MODIFY AS REQ'D TO INSTALL
NEW MECH
1 1/2" dia GALV PIPE GUARD RAIL - PAINT ROOF CURB re:
AI 103
NEW FAN UNITS re: MECH
AI 103
AI 103
MECHANICAL FLOOR PLATFORM
Scale: 1/4" = 1'-0"
AI 103 0 5 10 FT
FIELD VERIFY LOCATION & SIZE of
EXISTING MECHANICAL SHAFT
MECH SHAFT BELOW (DASHED)
CENTER LINE of MECHANICAL SHAFT
6'-0"
SLOPE TO DRAIN
@EAST EDGE
12'-0" SLAB DIMENSION11
'-9
/2
" S
LA
B D
IM
E
N S
IO
N
'-4
/2
" H A
N D
R A
IL
D
IM
E
N S
IO
N
12'-7" HANDRAIL DIMENSION
EQUAL EQUAL EQUAL
E Q
U A
L E
Q U
A L
E Q
U A
L
EQUAL 3'-0" CLEAR EQUAL
10" to 8" REINF CONC SLAB re:
STRUCTURAL
AI 103
TPO MEMBRANE ROOFING
ADHESIVELY APPLIED to CONC
DECK
FIBRE CANT BELOW ROOFING as
REQ'D
REMOVE EXIST'G PARAPET CAP &
BLOCK'G AS REQ'D, CONSTRUCT
NEW PLATFORM, AND
COUNTERFLASH INTO EXISTING
ROOFING AND FLASHING TO
PROVIDE WEATHERTIGHT
CONNECTION, EA SIDE
REMOVE EXIST'G CONSTRUCTION
(F.V. LOCATION) & SEAL TO
EXIST'G ROOFING/FLASHING TO
PROVIDE WATERTIGHT
CONNNECTION
MODIFY EXISTING LIGHTNING
PROTECTION AS NECESSARY TO
COORDINATE WITH NEW
CONXSTRUCTION
2"
8" 3'
-6
2"
2"1 1/2"
EXIST'G MECH SHAFT
WALL
BENT PLATE
CONTINUOUS AROUND
PERIMETER RE: STRUCT
PREFIN S.M. EDGE
FLASHING - ALLOW
WATER TO SPILL OVER
EDGE EAST SIDE ONLY
CAP BOT OF EA SUPPORT
REINF CONC SLAB on
M'TL DECKING RE:
STRUCTURAL
SEE DETL. FOR TYP
NOTES &
DIMS
AI 103
COORDINATE LOCATION
of MECH PAD & FLASHING w/ MECH
4" M
A X
E Q
U A
L E
Q U
A L
3'-0" cl OPENING IN
CENTER OF EAST
GUARD RAIL
EYELET w/ CHAIN
ACROSS OP'G @
3'-0" a.f.f. EA SIDE OF
OP'G
MECH SHAFT EDGE - EAST SIDE
Scale: 1 1/2" = 1'-0"
AI 103
11' 4 1/2" (F.V.) 2"
3' -6
EXIST'G MECH SHAFT
WALL
2"x4"x3/8" PLATE @ EA
GUARD RAIL SUPPORT -
WELD TO BENT PLATE &
GUARD RAIL SUPPORT
PREFIN S.M. EDGE
FLASHING w/ CONT
CLEAT AROUND
PERIMETER
TURN ROOFING DOWN
BLOCKING & SEAL, CONT
AROUND PERIMETER
1 1/2" d. GALV
GUARDRAIL SUPPORTS,
TOP RAIL &
INTERMEDIATE GUARDS -
EPOXY PAINTED
1 1/2" d. GALV
GUARDRAIL SUPPORTS,
TOP RAIL &
INTERMEDIATE GUARD -
EPOXY PAINTED
TREATED WOOD 2x4
BLOCKING CONT
AROUND PERIMETER
EXP BOLTED to BENT
PLATE/CONC SLAB
1/ 2"
2" 1 1/2"
TPO MEMBRANE
ROOFING ADHESIVELY
APPLIED to CONCRETE
SLAB
CANT STRIP AS REQ'D
SEE DETL. FOR TYP
NOTES &
DIMS
AI 103
E Q
U A
L E
Q U
A L
4" m ax
MECH SHAFT EDGE - WEST SIDE
Scale: 1 1/2" = 1'-0"
AI 103
3' -6
2"
MECH UNIT BASE re:
MECH
COORDINATE SLAB
PENETRATION w/ MECH
6"x4"x3/8" ANGLES w/
CONT WELD - MAINTAIN
LEVEL of TOP ANGLE FOR
SETTING MECH UNIT
CURB
REINF CONC SLAB ON
M'TL DECKING re:
STRUCTURAL
TPO MEMBRANE
ROOFING ADHESIVELY
APPLIED TO CONC DECK
- TURN ROOFING UP &
LAP OVER TOP of CURB
TREATED WOOD
BLOCKING
V A
R
IE
S 8" to
0"
FI
E
LD
V
E R
IF
Y
MECH FAN CURB
Scale: 1 1/2" = 1'-0"
AI 103
GENERAL NOTES - ADDENDUM #1
1. ADDENDUM #1 IS A PART OF ORIGINAL PROJECT # 589A5-15-117 "RELOCATE STERILE PROCESSING
SERVICE" DATED 09/01/15. REFER TO THE ORIGINAL PROJECT CONTRACT DOCUMENTS &
SPECIFICATIONS FOR ADDITIONAL INFORMATION, GENERAL NOTES & ADDITIONAL DETAILS WHICH
MAY BE APPLICABLE TO THIS PROJECT.
2. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE OWNER & VERIFY FLOOR LOAD
CAPACITY FOR THE LOCATION AND DELIVERY PATH OF THE NEW STEAM HEAT EXCHANGER
(APPROXIMATELY 3,800 #, VERIFY WITH EQUIPMENT SUPPLIER) RE: MECHANICAL DOCUMENTS.
3. REMOVE & STORE EXISTING EXHAUST FAN (AT DIRECTION OF OWNER) FOR FUTURE
RE-INSTALLATION
01 Add 1 - MOD 06 01/13/21
THIS IS A NEW SHEET ISSUED IN ADDENDUM #1
Rob Line
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
PARTITION TYPES
AI 401
SM
SCALE: 3/4" = 1'-0"
5"
TYPE 1-FULL HEIGHT W/ SOUND INSULATION
SCALE: 3/4" = 1'-0"
AI 401
EXISTING CONC. DECK. DECK PAN SYSTEM.
CAULK ENTIRE PERIMETER & PENETRATIONS.
(1) LAYER 5/8" TYPE-X GYP. BD. EACH SIDE, TO DECK.
3 5/8" MTL. STUDS AT 16" O.C. GAGE & PROIVIDE HORZ.
BRACING PER MANUFACTURES RECOMMENDATIONS
FOR OVERALL WALL HEIGHT.
PROVIDE CONCEALED BLOCKING AS REQ'D.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
BASE RE: FINISH SCHEDULE.
INSTALL WALL PROTECTION PER FINISH SCHEDULE.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
FINISH FLOOR. RE: FINISH SCHEDULE
PROVIDE FULL DEPTH SOUND INSULATION.
SUSPENDED CEILING RE: FINISH SCHEDULE FOR
TYPE & LOCATION.
5"
TYPE 2-FULL HEIGHT W/O INSULATION
SCALE: 3/4" = 1'-0"
AI 401
EXISTING CONC. DECK. DECK PAN SYSTEM.
CAULK ENTIRE PERIMETER & PENETRATIONS.
(1) LAYER 5/8" TYPE-X GYP. BD. EACH SIDE, TO DECK.
3 5/8" MTL. STUDS AT 16" O.C. GAGE & PROIVIDE HORZ.
BRACING PER MANUFACTURES RECOMMENDATIONS
FOR OVERALL WALL HEIGHT.
PROVIDE CONCEALED BLOCKING AS REQ'D.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
BASE RE: FINISH SCHEDULE.
INSTALL WALL PROTECTION PER FINISH SCHEDULE.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
FINISH FLOOR. RE: FINISH SCHEDULE
SUSPENDED CEILING RE: FINISH SCHEDULE FOR
TYPE & LOCATION.
5"
TYPE 3- FULL HEIGHT RATED WALL(1 HOUR)
SCALE: 3/4" = 1'-0"
AI 401
EXISTING CONC. DECK. DECK PAN SYSTEM.
FIRE CAULK ENTIRE PERIMETER & PENETRATIONS.
(1) LAYER 5/8" TYPE-X GYP. BD. EACH SIDE, TO DECK.
3 5/8" MTL. STUDS AT 16" O.C. GAGE & PROIVIDE HORZ.
BRACING PER MANUFACTURES RECOMMENDATIONS
FOR OVERALL WALL HEIGHT.
PROVIDE CONCEALED BLOCKING AS REQ'D.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
BASE RE: FINISH SCHEDULE.
INSTALL WALL PROTECTION PER FINISH SCHEDULE.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
FINISH FLOOR. RE: FINISH SCHEDULE
SUSPENDED CEILING RE: FINISH SCHEDULE FOR
TYPE & LOCATION.
EXISTING CONC. DECK. DECK IN PAN SYSTEM.
CAULK ENTIRE PERIMETER.
(1) LAYER 5/8" TYPE-X GYP. BD. EACH SIDE, TO DECK.
3 5/8" MTL. STUDS AT 16" O.C. GAGE & PROIVIDE HORZ.
BRACING PER MANUFACTURES RECOMMENDATIONS
FOR OVERALL WALL HEIGHT.
PROVIDE CONCEALED BLOCKING AS REQ'D.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
BASE RE: FINISH SCHEDULE.
INSTALL WALL PROTECTION PER FINISH SCHEDULE.
CORRDINATE WITH PLANS AND ELEVATIONS FOR
LOCATIONS.
FINISH FLOOR. RE: FINISH SCHEDULE
SUSPENDED CEILING RE: FINISH SCHEDULE FOR
TYPE & LOCATION.
6 1/4"
NOTE: USE THIS WALL TYPE/CONSTRUCTION TO
INFILL RATED WALLS WHERE DUCTWORK IS TO BE
REMOVED
TYPE 4-FULL HEIGHT RATED WALL(2 HOUR)
SCALE: 3/4" = 1'-0"
AI 401
FACE OF COL.
7/8” HAT CHANNEL & 5/8” GYP BD IF NO ELECTRICAL
BOXES OR CONDUITS ARE USED AT THE LOCATION.
1 1/2” MTL STUD FURRING & 5/8” GYP BD IF ELECTRICAL
BOXES OR CONDUITS ARE USED AT THE LOCATION.
TYPE 5-FURRING
SCALE: 3/4" = 1'-0"
AI 401
D at e:
T ue , J an
2, Ti m e:
0:
:1
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
01 Add 1 - MOD 06 01/13/21
ROOM FINISH SCHEDULE NOTES
1. AT SMALL AREA (4’X7’±) NORTH OF NEW DOOR C0-3B, ADD GRID CEILING,TILE,PAINT AND VCT FLOOR TO MATCH
EXISTING IN CORRIDOR C0-3A.
DOOR AND FRAME SCHEDULE NOTES
CEILING
PAINT
WALL PROTECTION
GB-1 5/8" GYP. BD. PRIMED AND PAINTED.
AT-1 AC9 ARMSTRONG CLEAN ROOM MYLAR, NO.
1716, 24 X 48 X 5/8 INCHES,
UNPERFORATED, WASHABLE, SCRUBABLE
AND SOIL RESISTANT. PROVIDE BORDER
UNITS AS NECESSARY. NRC VALUE OF 0.55
& CAC VALUE OF 35
FINISH SCHEDULE LEGEND
PRODUCTS LISTED ARE INTENDED TO INDICATE THE LEVEL OF QUALITY REQUIRED.
WP-1 INPRO CORPORATION, #0101, DESIGNER
WHITE, .060 THICK X 48" H SHEET GOODS.
AT-2 USG 2115 24X24X5/8-RATED
BASE
FLOOR
V-1 VINYL SHEET FLOORING - ARMSTRONG
MEDINTECH, 86497 BRUSHED SAND WITH
WELD ROD W0532 IVORY - EXTEND 6" UP
WALLS AND CABINETS TO PROVIDE
INTEGRAL BASE.
BR-1 INTEGRAL BASE EXTEND VERTICALLY
WITH ALUMINUM SQUARE TOP CAP
NOTES: INCLUDE ALL ADDITIONAL HARDWARE SUCH
AS END CAPS, TOP CAP, JOINT CAP, ETC REQUIRED.
BR-2 4" RUBBER COVE
V-2 VINYL SHEET FLOORING - ARMSTRONG
MEDINTECH, 86497 BRUSHED SAND WITH
WELD ROD W0532 IVORY - EXTEND 6" UP
WALLS AND CABINETS TO PROVIDE
INTEGRAL BASE.
EP-1 LATEX EPOXY-EGGSHELL (RES-W1) RE:
SPEC SECTION 09 96 59.
PT-2 LATEX-EGGSHELL
PT-2A LATEX ACCENT COLOR-EGGSHELL
PT-3 EXTERIOR LATEX-EGGSHELL
CERAMIC WALL TILE
CT-1 GLAZED SURFACE-SEE DRAWINGS FOR
SIZE AND CONFIGURATION.
AF-1 ACCESS FLOORING
RE: SPEC SECTION 09 6900
DOOR TYPES
FLUSH PANEL
WOOD DOOR
A
FRAME TYPES
HOLLOW METAL
OR
STAINLESS STEEL
FLUSH PANEL WD
W/ VISION LITE
B
DOOR AND FRAME SCHEDULE
DOOR FRAME DETAILS
NO. ROOM WDTH HT THICK. FIN. TYPE MTL TYPE MTL FIN. RATING JAMB HEAD SILL HDWR REMARKS
B006 OFFICE 3'0" 7'0" 1 3/4" B WD 1 HM 45 MINS
B006G CLOSET 2'6" 7'0" 1 3/4" A WD 1 HM -
B6M 7'0" 7'0" 1 3/4" HDW-3
B006PA PIPE CLOSET 6'0" 7'0" 1 3/4" A WD 1 HM -
B006PB PIPE CLOSET 2'2" 7'0" 1 3/4" A HM 1 HM 45 MINS
B007H STORAGE 3'0" 7'0" 1 3/4" A HM 1 HM 45 MINS
B008 PREP/PACK 4'0" 7'0" 1 3/4" C SS 1 SS 45 MINS
B008A VEST 3'8" 7'0" 1 3/4" D SS 1 SS 45 MINS POWER OPERATED. RE: ELECTRICAL DRAWINGS
B008B VEST 3'8" 7'0" 1 3/4" D SS 1 SS - POWER OPERATED. RE: ELECTRICAL DRAWINGS
B008C CART WASH 2'2" 6'10" 1 3/4" DOOR IS PART OF CART WASH PACKAGE
B009 STERLILIZERS 6'0" 7'0" 1 3/4" A HM 1 HM 45 MINS
B010 R.O. WATER 3'0" 7'0" 1 3/4" A HM 1 HM 45 MINS
B011A HOUSEKEEPING 3'0" 7'0" 1 3/4" A HM 1 HM -
B011B VEST 4'0" 7'0" 1 3/4" D SS 1 AL 45 MINS POWER OPERATED. RE: ELECTRICAL DRAWINGS
B011C VEST 4'0" 7'0" 1 3/4" D SS 1 AL - POWER OPERATED. RE: ELECTRICAL DRAWINGS
B013 ANTE 3'0" 6'8" 1 3/4" B HM 1 HM 45 MINS
B013A F T'LT/LKRS 3'0" 7'0" 1 3/4" A HM 1 HM -
B013B M T'LT/LKRS 3'0" 7'0" 1 3/4" A HM 1 HM -
B013C VEST 3'0" 7'0" 1 3/4" D HM 1 SS - POWER OPERATED. RE: ELECTRICAL DRAWINGS
B013D VEST 3'0" 7'0" 1 3/4" D HM 1 SS - POWER OPERATED. RE: ELECTRICAL DRAWINGS
B014MB MECHANICAL 4'0" 7'0" 1 3/4" A HM 1 HM 90 MIN
B015M MECHANICAL SHAFT 3'0" 7'0" 1 3/4" A HM 2 HM COORDINATE DOOR LOCATION WITH EXHAUST LOCATION C0-3B CORRIDOR 4'0" 7'0" 1 3/4" B HM 1 HM 45 MINS ARMOR PLATE INSIDE.POWER OPERATED. RE: ELECTRICAL DRAWINGS
2" 2"RE: SCHED
2" R
E : S
C H
E D
U
LE
2" 2"RE: SCHED
4" R
E : S
C H
E D
U
LE
11'-7"
2"7'-0"2"4'-1"2"
7' -0
2"
8' -1
1"
2" 8'
-7
2"
2" 1'
-7
8"4"
3' -6
RE: SCHED
R E
: S C
H E
D U
LE
RE: SCHED.
R E
: S C
H E
D U
LE
8" 1'-8"
8"
RE: SCHED
R E
: S C
H E
D U
LE
8"
3' -6
5" 3'-2"
RE: SCHED
R E
: S C
H E
D U
LE
5"
1' -4
5"
3' -0
/2
2" 8'
-7
7' -0
1'
-7
8' -9
4'-1" 7'-0" equal equal
FIXED INSULATED
H.M. PANEL
ACTIVE
LEAF
HELD
LEAF
4"
32" CLR.
1'-0"
1'-6" MIN.
PUSH
SIDE
PULL
SIDE
IF DOOR HAS
CLOSER & A LATCH
1/2"
XX
2"
GYP. BD. AND METAL FRAMING PER PARTITION
SCHEDULE.
DOUBLE STUDS AT JAMB TO BE FASTENED TO
BOTH SIDES OF RUNNER TRACK.
COORDINATE FRAME SIZE WITH PARTITION, TYP.
CONT. SEALANT ALL AROUND BOTH SIDES.
FRAME HM OR SS. SEE SCHEDULE.
DOOR PER SCHEDULE.
11' 4 1/2" (F.V.)
DOOR HEAD DETAIL
Scale: 3" = 1'-0"
AF 610
PARTITION AS SCHEDULED. DOUBLE
STUDS AT JAMB.
CONT. SEALANT BOTH SIDES
OF FRAME
FRAME HM OR SS. SEE
SCHEDULE.
DOOR PER SCHEDULE.
2"
1/ 2"
DOOR JAMB DETAIL
Scale: 3" = 1'-0"
AF 610
WINDOW SCHEDULE
WINDOW SIZE WINDOW STYLE GLASS DETAILS NOTES
NO. ROOM W
ID
TH
H E
IG
H
T
O P
E R
A
TI
O N
M A
TE
R
IA
L
FI
N
IS
H
H E
A D
D E
TA
IL
JA
M
B D
E
TA
IL
S
IL
L D
E
TA
IL
01 OFFICE 3'0" 4'0" Fixed Glass HM PT RATED
01 OFFICE 3'0" 4'0" Fixed Glass HM PT RATED
02 DECONTAM 2'4" 4'3" Custom HM PT OPERABLE PASS THRU WINDOW
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
09/01/15
1 RJ
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
N
A B C
D
E
G
F
RELOCATE STERILE
PROCESSING SERVICE
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
ROBERT JUNK
keith
DOOR & FINISH SCHEDULE
AF 610SM
SMSCALE: 3" = 1'-0"
1. FINISH HARDWARE FOR DOOR #B6M IS AS FOLLOWS:
NOTE: MATCH STYLE AND FINISH OF
HARDWARE WITH EXISTING FINISH
HARDWARE IN AREA.
REMARKS LEGEND ABBREVIATIONS
GL GLASS
HM HOLLOW METAL
WD WOOD
STL STEEL
AL ALUMINUM
MFR MANUFACTURER
TEMP TEMPERED
RTD RATED
MTL METAL
FS FIRE/SMOKE RATING
TYPICAL DETAILS DOOR SCHEDULE LEGEND
ROOM FINISH SCHEDULE
NORTH EAST SOUTH WEST
NO. ROOM FLOOR BASE WALLS CEILING NOTES
B006 OFFICE V-2 BR-2 PT-2A PT-2 PT-2 PT-2 AT-2 =('Space'.'remarks')
B006G CLOSET V-2 BR-2 PT-2 PT-2 PT-2 PT-2 AT-2 =('Space'.'remarks')
B6M MECH NA NA NONE NONE NONE NONE - =('Space'.'remarks')
B006P PIPE CLOSET - - NONE NONE NONE NONE - =('Space'.'remarks')
B007 STORAGE V-2 BR-2 PT-2 PT-2 PT-2 PT-2 GB-1 =('Space'.'remarks')
B008 PREP / PACK V-1 BR-1 EP-1/WP-1 PT-2/WP-1 PT-2/WP-1 PT-2/WP-1 GB-1 =('Space'.'remarks')
B008A VEST V-1 BR-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B008C CART WASH NA NA NONE NONE NONE NONE - =('Space'.'remarks')
B009 STERILIZERS V-1 BR-1 EP-1 EP-1 NONE EP-1 AT-1 =('Space'.'remarks')
B010 R. O. WATER V-2 BR-2 NONE EP-1/WP-1 EP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B011 VEST V-1 BR-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B011A HKPG V-2 BR-2 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B012 DECONTAM V-1 BR-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B013 ANTE VESTIBULE V-2 BR-1 PT-2 PT-2 PT-2 PT-2 GB-1 =('Space'.'remarks') B013A F T'LT/LKRS V-2 BR-1 EP-1/CT-1 CT-1 CT-1 CT-1 AT-1 =('Space'.'remarks')
B013B M. T'LT/L'KRS V-2 BR-1 EP-1/CT-1 CT-1 CT-1 CT-1 AT-1 =('Space'.'remarks')
B013C VEST V-1 BR-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 EP-1/WP-1 GB-1 =('Space'.'remarks')
B42A BIOMED SERVER ROOM AF-1 BR-2 EP-1 EP-1 EP-1 EP-1 - =('Space'.'remarks')
C-03A (EX) CORRIDOR MATCH VCT BR-2 NONE PT-2 PT-2 PT-2 - =('Space'.'remarks')
C-03C CORRIDOR V-2 BR-2 EP-1 EP-1 EP-1 EP-1 AT-2 =('Space'.'remarks')
C0-3B CORRIDOR V-2 BR-2 EP-1 EP-1 EP-1 EP-1 AT-2 =('Space'.'remarks')
C0-3E CORRIDOR V-2 BR-2 EP-1 EP-1 EP-1 EP-1 AT-2 =('Space'.'remarks')
FLUSH PANEL
STAINLESS STEEL
W/ BORROWED LITE
C
3” X 3” X 1/4” S.S. CORNER GUARD.
SCREW ATTACHED TO METAL STUD
BACK UP.
GYP BD. AND METAL STUD WALL. RE:
FLOOR PLAN.
WALL PROTECTION AS INDICATED IN
SCHEDULE. EXTEND BEHIND
CORNER GUARDS, DOOR AND
WINDOW FRAMES, ETC. WHERE
FLOORING EXTENDS UP WALLS TO
SERVE AS BASE, START WALL
PROTECTION AT TOP OF BASE.
EXIST'G MECH SHAFT
WALL
CORNER GUARD
Scale: 3" = 1'-0"
AF 610
FLUSH PANEL
STAINLESS STEEL
W/ BORROWED LITES
D
GALVANIZED
HOLLOW METAL-EXTERIOR
D at e:
T ue , J an
2, Ti m e:
0:
:5
A M
Fi le n am e:
To pe ka
V A
R el oc at e S te ril e P ro ce ss in g- S te am
G en er at or .v w x
GALVANIZED
HOLLOW METAL-EXTERIOR
FLUSH PANEL
GALV. H.M. W/ FIXED GALV H.M
SIDELIGHT AND TRANSOM
E
V A
R
IE
S 8" to
0"
FI
E
LD
V
E R
IF
Y
INSUL H,.M. DOOR & FRAME
RE: DOOR SCHEDULE
EXIST'G WALL BEYOND -
FIELD VERIFY WIDTH
EXIST'G CONST TO REMAIN
2" 5/
8"
2"6"
16 ga BENT GALV H.M.
THRESHOLD CONT ACROSS
OPENING - SET IN SEALANT
& SLOPE SLIGHTLY TO
DRAIN TO OUTSIDE
SEALANT
5" +/-
EXTERIOR DOOR THRESHOLD
Scale: 1 1/2" = 1'-0"
AF 610
7'-0" DOOR OP'G
FIELD VERIFY OPENING SIZE
2"5/8" 5/8"
FIELD VERIFY SIDELIGHT WIDTH
INSUL H.M. SIDE PANEL
16 ga H.M. FRAME &
ANCHORAGE - FILL W/ BATT
INSULATION - SET IN
SEALANT BED ON SILL
BELOW
INSUL H.M. DOOR & FIN
HARDWARE RE: DOOR
SCHEDULE
16 ga H.M. THRESHOLD
FULL WIDTH OF OPENING -
SET IN SEALANT BED
16 ga H.M. FRAME DOUBLE
MULLION - FILL W/ BATT
INSULATION
6"
INTERMEDIATE MULLION
Scale: 1 1/2" = 1'-0"
AF 610
8" 2"
EXIST'G WALL - FIELD
VERIFY WIDTH
INSUL H.M. DOOR & FIN
HARDWARE RE: DOOR
SCHEDULE
16 ga H.M. FRAME &
ANCHORAGE - FILL W/ BATT
INSULATION
SEALANT CONT AROUND
PERIMETER INSIDE AND
OUTSIDE
16 ga H.M. THRESHOLD
FULL WIDTH OF OPENING -
SET IN SEALANT BED
2" 5/8"
2" 6"
5"
7'-0" DOOR OP'G
EXTERIOR JAMB
Scale: 1 1/2" = 1'-0"
AF 610
MECHANICAL A HM 3 HM - 4, 5 5 SIM 6 SEE DOOR TYPE & FRAME TYPE FOR INSUL. HM SIDELIGHT & TRANSOMHW-E6
06 Add 1 - MOD 06 01/13/21
95% SUBMITTAL
100% SUBMITTAL
AMENDMENT #2
AMENDMENT #3
AMENDMENT #4
5/20/16 01/20/17 06/23/17 07/25/17 07/25/17
810.06.00.010.0
W
U
R
04M
05M
07M
03M
06M
05M
10M
09M
08M
08M 01M
T
(TYP.)
(TYP.)
(TYP.)
(TYP.)
N
BASEMENT FLOOR PLAN-MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
T T
T
T
06M
06M 06M 06M
02M
02M
02M
1. EXISTING AIR UNIT AND ASSOCIATED DUCTWORK, CHILLED WATER AND STEAM COILS
AND PIPING, CONTROLS, AND ALL ACCESSORIES TO BE REMOVED.
2. REMOVE EXISTING AIR TRANSFER BOOT.
3. REMOVE EXISTING SUPPLY DUCT.
4. REMOVE EXISTING RETURN GRILLE.
5. REMOVE EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK.
6. REMOVE EXISTING THERMOSTAT AND ASSOCIATED WIRING.
7. REMOVE EXISTING HEATING FAN COIL UNITS, ASSOCIATED PIPING AND CONTROLS. CAP
PIPING BELOW FLOOR OR AT MAIN.
8. REMOVE EXISTING EXHAUST REGISTER AND ASSOCIATED DUCTWORK. CAP AT MAIN.
9. REMOVE EXISTING LOUVER. RETAIN FOR REUSE.
10. REMOVE EXISTING RELIEF DUCTWORK TO PLENUM.
11. PREPARE EXISTING CHILLED WATER PIPING FOR CONNECTION OF NEW PIPING.
12. REMOVE EXISTING THERMOSTAT AND CONTROL WIRING.
13. RELOCATE TEMPERATURE CONTROL PANEL, EXTEND WIRING TO NEW LOCATION.
14. REMOVE EXISTING ABANDONED CONDENSING UNIT AND ASSOCIATE PIPING AND
CONTROLS.
15. REFRIGERANT PIPING TO BE REMOVED, BOTH EXTERIOR AND INTERIOR TO POINT OF
SLAB PENETRATION. PATCH AND REPAIR WALL/FLOOR AS REQUIRED TO MATCH
EXISTING.
16. REMOVE EXISTING WALL LOUVER.
17. REMOVE MEDIUM PRESSURE STEAM AND CONDENSATE PIPING, VALVES, SUPPORTS AND
ACCESSORIES.
18. CAP MEDIUM PRESSURE STEAM AND CONDENSATE AT SLAB.
19. REMOVE EXISTING SUPPLY AND RETURN DUCTWORK, FITTINGS, HANGERS AND
ACCESSORIES.
20. REMOVE EXISTING CHILLED WATER SUPPLY AND RETURN PIPING, VALVES, ACCESSORIE
AND HANGERS.
21. REMOVE ALL REFRIGERANT PIPING AND FITTINGS IN ENTIRETY. PATCH, REPAIR AND
SEAL EXISTING WALL PENETRATIONS AIRTIGHT.
22. REMOVE EXISTING CONDENSING UNIT, ALL ASSOCIATED PIPING AND CONTROLS IN
ENTIRETY. REMOVE EXISTING CONCRETE PAD.
FLOOR PLAN NOTES##M
07M
(TYP.)
03M
T
03M
05M (TYP)
05M (TYP)
04M
(TYP)
16M 18M
17M
T
12M
19M
20M
11M
15M
13M
14M 14M
21M
22M
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
01/20/17
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
www.junkarchitects.com
802 Broadway, 5th floor Kansas City, MO 64105
Tele 816 472 7722 Fax 816 472 1822 www.lankfordfendler.com
7007 College Boulevard, Ste. 450 Overland Park, KS 66211
Phone: 816-221-1411 Fax: 816-221-1429
RELOCATE STERILE
PROCESSING SERVICE
T im e : 1
0:
:1
A M
F ile n a m e
: 1
To pe ka V
A R el oc at e
S te ril e
P ro ce ss in g-
P ro je ct
F ile sa ra h.
vw xw
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
01 As-Builts 10/09/19 02 01/13/21Post Bid Addn. #1
MD1-100
BASEMENT PLAN-
MECHANICAL DEMOLITION
LDR DMB
DUCT, SEE FLOOR
PLAN FOR SIZE
FUSIBLE LINK
FIRE RATED WALL
FIRE DAMPER SLEEVE
'S' CLIP CONNECTION
(TYPICAL)
DUCT ACCESS DOOR
NOTES:
1. INSTALLATION MUST MEET FIRE DAMPER MANUFACTURER'S
RECOMMENDATIONS AND LISTINGS ALONG WITH
NFPA STANDARDS.
2. USE DYNAMIC RATED DAMPER FOR DUCTED APPLICATIONS,
NON-DUCTED LOCATIONS MAY BE STATIC RATED.
3. ANGLES ON ONE SIDE ONLY PERMITTED IN ACCORDANCE
WITH UL LISTING.
4. SEE PLAN DRAWINGS FOR LOCATIONS OF FIRE DAMPERS.
1/4"-1/2" VOID
ELASTOMERIC FIRE-
RESISTIVE CAULK (TYP)
MOUNTING ANGLE TO OVERLAP WALL ON ALL SIDES,
SECURE MOUNTING ANGLE TO FIRE DAMPER SLEEVE
UL LABELED FIRE DAMPER
FIRE DAMPER DETAIL2 NO SCALE
CONDENSATE PUMP
(TYP) RE: SCHEDULEREDUCER (TYP)
UNION OR FLANGE (TYP)
NON-SLAM
CHECK VALVE (TYP)
SHUT-OFF VALVE (TYP)
PUMPED CONDENSATE
MAKE-UP WATER (WHERE
SHOWN OR REQUIRED)
MAKE-UP WATER SOLENOID VALVE
VENT TO ATMOSPHERE FULL SIZE OF TANK
TAPPING, TERMINATE 3'-0" ABOVE ROOF OR
7'-0" ABOVE GRADE OR WALK SURFACE
OVERFLOW DRAIN FULL SIZE TO
FLOOR DRAIN AND INDIRECT WASTE
LOW PRESSURE RETURN
STRAINER WITH
BLOW DOWN VALVE
RECEIVER
4" CONCRETE HOUSEKEEPING
PAD, DOWELED INTO FLOOR
CONDENSATE PUMP DETAIL5 NO SCALE MECH ROOM B-014 M
CHECK
VALVE
C.W. FROM BACK FLOW PREVENTER
VENT FULL SIZE OF TAPPING "TO ATMOSPHERE",
TERMINATE 3'-0" ABOVE ROOF OR
9'-0" ABOVE GRADE OR WALK SURFACEUNION (TYP)
SELF-CONTAINED TEMP.
CONTROL VALVE. SET 140°
STRAINER WITH BLOW DOWN VALVE
GLOBE VALVE
MANUAL BYPASS
FROM BOILER BLOW DOWN
DRAIN WHERE SHOWN
FROM BOILER WATER COLUMN
MOTORIZED BLOW DOWN VALVE
SHUT OFF VALVE (TYP)
THERMOMETER
AFTER COOLING FITTING
BLOW DOWN SEPARATOR
PIPE TO DRAIN FULL SIZE OF SEPARATOR
TAPPING AND INDIRECT WASTE
BLOWDOWN SEPARATOR DETAIL3 NO SCALE MECH ROOM B-014 M
INVERTED BUCKET TRAP
LPC TO LPC
MAIN
STRAINER WITH
BLOW DOWN VALVE
HP CONDENSATE
150 PSI ASME
FLASH TANK
PIPE FULL SIZE TO DRAIN
AND INDIRECT WASTE
THERMOSTATIC
AIR VENT
TO LPS MAIN
LPS
PRESSURE
RELIEF VALVE
6" DIRT LEG
TO FLOOR DRAIN AND
INDIRECT WASTE
FLASH TANK DETAIL
4 HIGH PRESSURE CONDENSATE
NO SCALE
CONSTANT VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM1 NO SCALE
WITH SUPPLEMENTAL HEATING
PIPE HANGERS - PROVIDE LOAD RATED
DOUBLE 1" DEFLECTION SPRING
ISOLATORS FOR FIRST TWO ON EACH SIDE
OF PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINER
FLEXIBLE
CONNECTION
BALL OR
BUTTERFLY TYP.
NOTES:
1. SUPPORT PUMP INDEPENDENTLY ON 1" DEFLECTION SPRING ISOLATORS FROM
STRUCTURE ABOVE OR FROM WALL ANGLE SUPPORTS . DO NOT SUPPORT PUMP
FROM MOTOR.
BALANCING
VALVE
CWS
CWR
NOTES:
1. ARRANGEMENT SHOWN IS SCHEMATIC, ADJUST TO
SUIT FIELD CONDITIONS OR MEET LOCAL CODE
REQUIREMENTS.
2. REFER TO COIL TYPICAL PIPING DETAIL.
STRUCTURE
HANG FAN COIL UNIT FROM EXISTING STRUCTURE
WITH RUBBER IN SHEAR VIBRATION ISOLATORS
AND 3/8" MIN. THREADED ROD - SIZE AND NUMBER
AS REQUIRED
FAN
COIL
CONTROL VALVE (TYP)
BALANCE VALVE (TYP)
COIL DRAIN VALVE WITH CAPPED 3/4" HOSE THREAD
AT LOWEST POINT OF COIL (TYP)
SECONDARY DRAIN PAN, ROUTE CONDENSATE
TO VISIBLE LOCATION
DISCHARGE GRILLE WITH OPPOSED BLADE
DAMPERINLET
HORIZONTAL 2 PIPE FAN COIL UNIT PIPING DETAIL8 NO SCALE
IN-LINE PUMPS - CONNECTIONS6 NO SCALE
MANUAL AIR VENT AT
HIGH POINT
PRESSURE TRANSDUCER
COMPATIBLE WITH
EXISTING JOHNSON
CONTROLS DDC SYSTEM
1 1/2" HPR
3" HPS
(60PSI)
1 1/2" DI
MAKE-UP FEED
WATER
P
RELIEF FULL
SIZE TO
ATMOSPHERE
TUBE PULL
P
UNION (TYP)
PIPING FULL SIZE OF
HEAT EXCHANGER
CONNECTION
MANUEL DRAIN/
BLOWDOWN PIPE
TO FLOOR DRAIN
AUTOMATIC
BLOWDOWN VALVE
TO CONDENSATE
COOLER RE: DETAIL
(SIMILAR)
3" HPS
PIPING CRAWL
SPACE.
END OF LINE
TRAP RE: DETAIL
HEAT EXCHANGER DETAIL9 NO SCALE
1-HX-1
CONTROL
VALVE
PIPE THROUGH
FLOOR (TYP)
REDUNDANT
SHUTOFF
VALVE
CONDENSATE DRAIN FULL
SIZE TO FLOOR DRAIN
2 1/2" H
PS
1 1/2" H
PR
HPS
HPR
TO EXISTING STEAM LOADS
ANCHOR (TYP)
GATE VALVE (TYP)
FROM BOILER PLANT
CONNECTION DETAIL
7 STEAM AND CONDENSATE
NO SCALE
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN COIL IS NOT
SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT PIPING
INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT PIPING
INDEPENDENT OF COIL
WATER COIL
REDUCER, IF REQUIRED
FLOW ELEMENT
DRAIN WHEN COIL IS NOT
SELF-DRAINING
DRAIN
NOTE:
1.
2.
3.
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2
HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4" [100mm]Ø PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm]Ø PIPE & LARGER.
PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE
OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS,
VALES, OR EQUIPMENT.
THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM
UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.
FE
FE
TI
TI
TEMPERATURE
INDICATION TO ECC
SEE CONTROL
DIAGRAM
2 OR 3 WAY VALVE AS
INDICATED. (TYP)
WATER COILS-PIPING CONNECTIONS10 NO SCALE
CALIBRATED BALANCE VALVE, SET
MINIMUM FLOW AT 5GPM, REFER
TO SEQUENCE OF OPERATION.REDUNDANT
SHUTOFF VALVE
TEST PLUG (TYP)
TEST PLUG
(TYP)
MANUAL AIR VENT
PIPE THRU FLOOR
(TYP)
3/4" DRAIN (TYP)CWS
TEST PLUG (TYP)
MODULATING
CONTROL VALVE
MG1-103
MECHANICAL DETAILS
LDR DMB
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
F
E
D
C
B
A
97 8654321
ARCHITECTS/ENGINEERS:
File Path
Colmery O'Neil VA Medical Center 2200 Gage Blvd. ,Topeka,KS
VA EASTERN KANSAS
HEALTH CARE SYSTEM
Dwight D. Eisenhower VA Medical Center Leavenworth
Colmery-O'Neil VA Medical Center Topeka
01/20/17
Drawing Title:
Scale:
Approved:
Building Number:
Location:
Project Title:
Checked By: Drawing No.
Project No.
Drawn By:
Date:
Dwg. Of
Building Key Plan:
RELOCATE STERILE
PROCESSING SERVICE
T im e : 1
0:
:1
A M
F ile n a m e
: 1
To pe ka V
A R el oc at e
S te ril e
P ro ce ss in g-
P ro je ct
F ile sa ra h.
vw xw
802 Broadway, 5th Flr T:816 472 7722 Kansas City, MO F:816 472 1822 64105 www.junkarchitects.com
7007 College Blvd T:816-221-1411 Ste.450 F: 816-221-1429 Overland Park,KS 66211 www.lankfordfendler.com
8246 Marshall Drive T:913-284-0274 Lenexa,KS F:913-284-0293 66214 www.atcgroupservices.com
01 As-Builts 10/09/19 N
A B C
D
E
G
F
02 Post Bid Addn. #1 01/13/21
FAN SCHEDULE
MARK
NO.
1-EF-1
1-EF-2
NOTES: 1.
2.
3.
4.
5.
MANUFACTURER
GREENHECK
GREENHECK
PROVIDE WITH MOTOR COVER, BACKDRAFT DAMPER, BYPASS AIR PLENUM, DAMPER AND WEATHER HOO,D EXHAUST DISCHARGE NOZZLE, EXTENDED LUBE LINES, PROTECTIVE CORROSION RESISTANT COATING, INLET FLEXIBLE DUCT CONNECTION, 125 MPH WIND LOAD RATED, MINIMUM HEIGHT ABOVE CURB 120" PROVIDE WITH REMOTE MOUNTED VARIABLE FREQUENCY DRIVE WITH DISCONNECT. ROOF FAN DISCONNECT BY ELECTRICAL CONTRACTOR.
PROVIDE WITH HEAVY LOAD CURB WITH CURB SEALS, COMBINED FOR DUAL FANS. CURB MAY BE EITHER BY FAN MANUFACTURER OR A COMPARABLE FIELD FABRICATED CURB.
CONTROL THRU BUILDING MANAGEMENT SYSTEM. ONE FAN OPERATES CONTINUOUSLY, SECOND FAN IS STANDBY. REFER TO CONTROL SEQENCES FOR LEAD/LAG OPERATION.
EF-1 AND ASSOCIATED CURB IS EXISTING TO BE REMOVED AND REINSTALLED AT NEW LOCATION ON NEW DUAL FAN CURB.
MODEL
VK-H-18-17
VK-H-18-17
TYPE
UPBLAST
UPBLAST
EXHAUST
AIRFLOW
(CFM)
E.S.P.
(IN W.G.)
0.75 0.75
MAX BYPASS
AIRFLOW
(CFM)
TOTAL
AIRFLOW
(CFM)
T.S.P.
(IN W.G.)
1.20 1.20
FAN
TYPE
TUBULAR CENTRI
TUBULAR CENTRI
RPM
DRIVE
BELT
BELT
MIN EFFECTIVE
PLUME
HEIGHT (FT)
VOLT
ELECTRICAL
ø
HZ
HP/
WATTS
NOTES
1,2,3,4,5 1,2,3,4
CONSTANT AIR VOLUME BOX SCHEDULE
MARK
NO.
1-CAV-1
1-CAV-2
1-CAV-3
1-CAV-4
1-CAV-5
1-CAV-6
1-CAV-7
1-CAV-8
1-CAV-9
NOTES: 1.
2.
3.
4.
MANUFACTURER
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PROVIDE WITH FACTORY INSTALLED JOHNSON CONTROLS ELECTRONIC DIGITAL CONTROLLER AND DIGITAL ROOM SENSOR WITH DISPLAY COMPATIBLE WITH THE EXISTING FACILITY JOHNSON CONTROLS DIGITAL CONTROL SYSTEM.
PROVIDE WITH SOLID METAL LINER, RUBBER IN SHEAR HANGER BRACKETS, 24V TRANSFORMER FOR TEMPERATURE CONTROLS.
ELECTRIC HEATING COIL MATCHED TO TERMINAL BOX, FACTORY WIRED WITH INTEGRAL DISCONNECT SWITCH, HINGED ACCESS PANEL HAND AS INDICATED ON DRAWING, AIRFLOW SWTCH, AUTOMATIC AND MANUAL THERMAL RESETS, CONTACTORS, 24V CONTROL TRANSFORMER, LOW WATT DENSITY ELEMENTS.
CONSTANT VOLUME WITH REHEAT CONTROL SEQUENCE.
MODEL
SDV-5000
SDV-5000
SDV-5000
SDV-5000
SDV-5000
SDV-5000
SDV-5000
SDV-5000
SDV-5000
INLET
SIZE
COOLING
CFM
HEATING
CFM
MAX.
NC
@1"WC
VOLT
BOX ELECTRICAL
ø
HZ
HEATING
MBH
34.1 51.1 54.6 27.3 20.4 13.6 10.2 3.4 6.8
HEATING
KW
STAGED
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
VOLT
HEATER ELECTRICAL
ø
HZ
NOTES
1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4
COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE
MARK
NO.
1-CRAC-1
1-CRAC-2
NOTES: 1
MANUFACTURER
LIEBERT
LIEBERT
PROVIDE INDOOR UNIT WITH MERV 8 FILTERS, INFRARED HUMIDIFIER, ELECTRIC REHEAT COIL, DIGITAL COMPRESSOR, UPFLOW DISCHARGE AIR PLENUM, DISCONNECT SWITCH, MICROPROCESSOR BASED ROOM SENSOR AND CONTROL PANEL, ALL OPERATING AND SAFETY CONTROLS.
EACH AIR CONDITIONING UNIT MATCHED TO LIEBERT MCM040 AIR COOLED CONDENSER ON ROOF (CU-1 and CU-2) 105F AMBIENT, 208/3/60.
PROVIDE LOW AMBIENT CONTROLPIPE REFRIGERANT IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS.
MODEL
PDX018
PDX018
ARRANGEMENT
VERT
VERT
AIRFLOW
CFM
SPACE
CONDITIONS
68/45% 68/45%
TOTAL
MBH
62.3 62.3
SENS.
MBH
60.4 60.4
REHEAT CAPACITY
KW
13.6 13.6
STAGES
EXT.
S.P.
(IN W.G.)
0.5 0.5
HUMIDIFICATION
CAPACITY
(LBS./HR.)
7.7 7.7
VOLT
ELECTRICAL
ø
HZ
MOTOR
HP
4.2 4.2
NOTES
1,2 1,2
DIFFUSER SCHEDULE
MARK
NO.
SA
SB
SC
SD
SE
SF
SG
SH
SI
SJ
SK
RA
RB
RC
RD
EA
EB
EC
ED
EE
EF
EG
NOTES:
*CONTRACTOR SHALL VERIFY CEILING TYPE PRIOR TO ORDERING DIFFUSERS.
1.
2.
3.
4.
MANUFACTURER
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PRICE
PROVIDE WITH MANUAL DAMPER.
ALUMINUM CONSTRUCTION.
PROVIDE WITH MSBG BURGLER BARS BEHIND GRILLE.
SEAL ALL DIFFUSER FRAMES IN GYPBOARD CEILINGS AIRTIGHT.
MODEL
ASCDA
SCDA
ASCDA
ASCDA
SCDA
SCDA
ASCDA
ASCDA
PDDR
PDDR
PDDR
APDDR
PDDR
APDDR
APDDR
APDDR
APDDR
630DAL
FACE
SIZE
(IN.)
12x12 24x24 24x24 12x12 24x24 24x24 12x12 24x24 18x12 26x14 26x22
24x24 24x24 24x24 40x26
12x12 24x24 24x24 24x24 24x24 12x12 22x12
NECK
SIZE
(IN.)
16x10 24x12 24X20
38x24
14x14
20x10
NO.
OF
SLOTS
FRAME
TYPE*
SURFACE
SURFACE
SURFACE
SURFACE
LAY-IN
LAY-IN
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
LAY-IN
LAY-IN
LAY-IN
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
FINISH
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
NOTES
1,2
1,2
1,2 1,2
1,2
1,2 1,2 1,2
1,2
STEAM HUMIDIFIER SCHEDULE
MARK
NO.
1-H-1 1-H-2
NOTES: 1.
2.
3.
4.
5.
MANUFACTURER
ARMSTRONG
ARMSTRONG
FURNISH AND INSTALL WITH 24V ELECTRIC MODULATING STEAM CONTROL VALVE, HIGH LIMIT HUMIDISTAT, DUCT PRESSURE SWITCH AND RETURN
DUCT MOUNTED HUMIDISTAT. PROVIDE WITH 120V/24V CONTROL TRANSFORMER.
VALVING ARRANGEMENT AND CONFIGURATION TO BE AS DETAILED OR AS REQUIRED BY UNIT MANUFACTURER.
MAXIMUM VAPOR TRAIL DUE TO SPACE LIMITATIONS.
PROVIDE WITH 304 STAINLESS STEEL FABRICATED DRAIN PAN BELOW HUMIDIFIER AND DUCT, EXTENDED 4' MINIMUM DOWNSTREAM OF HUMIDIFIER.
DUCT ON EITHER SIDE OF HUMIDIFIER TO BE CONSTRUCTED OF STAINLESS STEEL, RE: SPECIFICATION.
AS SPECIFIED OR DRI-STEEM ULTRASORB MODEL MP DISPERSION PANEL TYPE OR EQUAL MANUFACTURER.
MODEL
H-90 H-90
MANIFOLD
QUANTITY
& MODEL
(1) M-1
(1) M-1.5
AIR
FLOW
(CFM)
HUMIDITY
LOAD
#/HR
DUCT
SIZE
(IN.xIN.)
20x10 16x14
VAPOR
TRAIL LENGTH
(FT.)
ENTERING
TEMP.
(°F) 55-90 55-90
ENTERING
RH
ROOM
TEMP.
(°F)
ROOM
RH
NOTES
1,2,3,4,5 1,2,3,4,5
AIR HANDLING UNIT SCHEDULE
MARK
NO.
1-AHU-1
NOTES: 1.
2.
3.
4.
5.
MANUFACTURER
TRANE
COOLING COIL BASED ON 45F EWT/55 LWT.
DOUBLE WALL CLIMATE CHANGER WITH THE FOLLOWING SECTIONS: OUTSIDE AIR INTAKE WITH GRID AIRFLOW MONITOR STATION, MIXING BOX SIDE ACCESS FILTER SECTION, INTEGRAL FACE AND BYPASS STEAM PREHEAT COIL, ACCESS SECTION, STEAM HUMIDIFIER, ACCESS SECTION, DIRECT EXPANSION COOLING COIL WITH UV LIGHTS, FAN SECTION WITH INTERNALLY ISOLATED FAN AND MOTOR, DIFFUSER SECTION, ACCESS SECTION, FINAL FILTER SECTION. PROVIDE WITH FAN VFD WITH DISCONNECT SWITCH WITH INLET FUSES, BYPASS, HOA SELECTOR, MANUAL SPEED CONTROLLER, STALL PREVENTION, PHASE SHORT CIRCUIT AND GROUND FAULT PROTECTION, UL 508C LISTED. PRE FILTERS SHALL BE 2" MERV 7 MERV PLEATED FILTERS & MERV 11 CARTRIDGE FILTERS, FINAL FILTERS SHALL BE 12" MERV 14 CARTRIDGE FILTERS. UNIT CONTROLS INCLUDING DAMPER ACTUATORS BY OTHERS TO ACCOMPLISH THE SPECIFIED SEQUENCE OF OPERATION.
TOTAL STATIC PRESSURE INCLUDES A DIRTY FILTER ALLOWANCE OF 1.5".
MODULAR UNIT COMPONENTS SHALL BE BROKEN INTO SECTIONS FOR DELIVERY THAT CAN BE BROUGHT INTO EXISTING BUILDING THRU EXISTING DOOR OR WINDOW OPENINGS.
REMOVE EXISTING DX COOLING COIL, ASSOCIATED PIPING AND CONTROLS FROM UNIT CASING. PREPARE FOR INSTALLATION OF NEW CHILLED WATER COIL.
MODEL
CSAA012UA
ARRANGEMENT
HORIZONTAL DRAW THRU
AIRFLOW
CFM
RETURN
AIRFLOW
CFM
MIN VENT
AIRFLOW
CFM
MIN
O.A.
CFM
FAN
TYPE
AF
FAN
SIZE
FAN
RPM
MOTOR
HP
15.0
EXT.
S.P.
(IN W.G.)
1.50
TOTAL
S.P.
(IN W.G.)
8.24
E.D.B.
(°F) 13.0
L.D.B.
(°F) 54.6
STEAM IFB COIL
LB/HR
15 PSIG
SENS
MBH
242.1
APD
(IN W.G.)
0.32
E.R.H.
HUMIDIFIER
L.R.H.
LB/HR
15 PSIG
APD
(IN W.G.)
0.04
E.D.B.
(°F)
E.W.B.
(°F)
L.D.B.
(°F)
DX COOLING COIL
L.W.B.
(°F)
TOTAL
MBH
SENS.
MBH
VOLT
ELECTRICAL
ø
HZ
NOTES
1,2,3,4,5
STEAM BOILER SCHEDULE
MARK
NO.
1-B-1
1-B-2
NOTES: 1.
2.
MANUFACTURER
CHROMALOX
CHROMALOX
BOILER TO PRODUCE CLEAN STEAM, STAINLESS STEEL ASME CONSTRUCTION, PROVIDE WITH
FACTORY DISCONNECT SWITCH, CSD-1 TRIM INCLUDING TEMP GAGE, HI-PRESSURE LIMIT,
LOW WATER CUT OFF, ALL OPERATING AND SAFETY CONTROLS, HEAT TIMER DIGISPAN TSC
ELITE BOILER CONTROLLER WITH LEAD/LAG, BUILDING DDC SYSTEM TO MONITOR DISCHARGE
PRESSURE & SAFETY LOCKOUTS.
CAPACITY AT 212F WITH 50F FEEDWATER.
MODEL
CSSB-180A
CSSB-180A
INPUT
KW
LBS/
HR
STEAM
PRESS
VOLT
ELECTRICAL
ø
HZ
NOTES
1,2
1,2
CONDENSATE PUMP SCHEDULE
MARK
NO.
1-P-1
NOTES: 1.
MANUFACTURER
HOFFMAN
DUPLEX LOW NPSH PUMP, CAST IRON RECEIVER, INTEGRAL FLOAT SWITCHES, UNIT MOUNTED CONTROL PANEL WITH DISCONNECT SWITCHES, WATER LEVEL GAGE, DISCHARGE PRESSURE GAGE, INLET STRAINER
MODEL
NO.
23CB9-25
USE
STEAM CONDENSATE
RESERVOIR SIZE
(GALLONS)
FLOW
RATE
(GPM)
HEAD
(FT.)
MOTOR
SPEED
(RPM)
VOLT
ELECTRICAL
ø
HZ
HP
(2) 1/2
NOTES
CHILLED WATER COIL SCHEDULE
MARK
NO.
1-CWC-1
NOTES: 1.
2.
MANUFACTURER
TRANE
COOLING COIL TYPE UW WITH COPPER TUBES, ALUMINUM FINS AND GALVANIZED CASING.
COIL TO BE COMPATIBLE WITH AND MATCH SIZE OF THE EXISTING TRANE AIR HANDLING UNIT CASING.
MODEL
DUWB32055G0FB168D
ARRANGEMENT
HORIZONTAL
AIRFLOW
CFM
FACE AREA
SF
12.3
COIL SIZE
WIDTH
IN
HEIGHT
IN
E.D.B.
(°F) 92.2
E.W.B.
(°F) 73.0
L.D.B.
(°F) 46.9
L.W.B.
(°F) 46.4
CHILLED WATER COIL CONDITIONS
TOTAL
MBH
514.3
SENS.
MBH
AIR
DP
1.45
CW
GPM
CW
EWT (°F)
43.0
CW
LWT (°F)
51.9
CW
DP FT
NO. OF
ROWS
NOTES
1,2
CLEAN STEAM HEAT EXCHANGER SCHEDULE
MARK
NO.
1- HX-1
NOTES: 1.
2.
3.
4.
MANUFACTURER
CEMLINE
SKID MOUNTED FACTORY PACKAGED CUSTOM BUILT, ASME CONSTRUCTED AND STAMPED UNFIRED STEAM TO STEAM HEAT EXCHANGER, 316 STAINLESS STEEL VESSEL, TUBE AND TUBE SHEET WITH CAST IRON HEAD, 0.0005 FOULING FACTOR, 3" VESSEL INSULATION AND 20 GAGE ENAMELED STEEL JACKET . PROVIDE WITH ALL REQUIRED OPERATING ACCESSORIES AND CONTROLS FOR A COMPLETE FUNCTIONING UNIT, INCLUDING INLET STRAINER, SEPARATOR, PRESSURE GAGES, DUAL F&T TRAPS, ONE FOR COIL AND ONE FOR DRIP AHEAD OF THE PILOT OPERATED ELECTRIC CONTROL VALVE, LEVEL CONTROLLER, MANUAL BLOWOFF VALVES, LOW WATER, HIGH PRESSURE CUTOFF, MAKE-UP WATER SOLENOID VALVE, VACUUM BREAKER TIMER BASED AUTOMATIC BLOWDOWN VALVE TO DILUTE AND MAINTAIN WATER AT A SAFE LEVEL, MODULTING FEEDWATER CONTROLS, AND SOLENOID VALVE.
120V POWER FOR CONTROLS.
PROVIDE 'STEAMTROL' SOLID STATE CONTROLS, INCLUDE THE FOLLOWING FUNCTIONS:
POWER ON
LOW WATER
HIGH WATER
WATER FEED
HIGH PRESSURE
LOW PRESSURE
BLOW DOWN OPERATING
OPERATING PRESSURE
ALARM HORN AND LIGHT
LCD TOUCHSCREEN
BUILDING AUTOMATION SYSTEM INTERFACE WITH EXISTING JOHNSON CONTROLS SYSTEM.
CONTRACTOR SHALL PROVIDE AN EQUIPMENT DELIVERY PATH FOR THE NEW HEAT EXCHANGER AS REQUIRED, INCLUDING REMOVAL AND REINSTALLATION OF EXISTING PIPING AND EQUIPMENT, DEMOLITION AND REPAIR OF DOORWAYS AND WALLS AND/OR PROVIDING WALL KNOCKOUT PANELS. AT CONTRACTOR OPTION, THE SKID MOUNTED PACKAGE HEAT EXCHANGER MAY BE DISASSEMBLED FOR DELIVERY AND REASSEMBLED IN PLACE TO FACILITE ENTRY INTO THE MECHANICAL ROOM. THE REASSEMBLED UNIT SHALL BE TESTED IN THE PRESENCE OF AND IN ACCORDANCE WITH ALL MANUFACTURER REQUIREMENTS. THE REASSEMBLED UNIT SHALL BE CERTIFIED TO BE IN COMPLIANCE WITH
ALL MANUFACTURER STANDARDS AND OPERATING PARAMETERS.
MODEL
V410USG2448
PLANT
STEAM
PRESSURE
PSI
STEAM
FLOW INPUT
CAPACITY
LBS/HR
CLEAN
STEAM
PRESSURE
PSI
STEAM
FLOW OUTPUT
CAPACITY
LBS/HR
VOLTS
ELECTRICAL
PHASE
HZ
NOTES
1,2,3,4
PUMP SCHEDULE
MARK
NO.
1-CWP-1
1-CWP-2
NOTES: 1.
2.
3.
4.
MANUFACTURER
BELL AND GOSSETT
BELL AND GOSSETT
INLINE PUMP, PROVIDE WITH SPRING VIBRATION ISOLATION HANGERS.
ONE PUMP IS STANDBY.
PROVIDE WITH VARIABLE FREQUENCY DRIVE WITH INTEGRAL STARTER AND DISCONNECT SWITCH WITH AUXILARY CONTACTS
FOR CONTROL INTERFACE.
CONTROL THRU BUILDING MANAGEMENT SYSTEM. ONE PUMP OPERATES CONTINUOUSLY, SECOND PUMP IS STANDBY.
REFER TO CONTROL SEQENCES FOR LEAD/LAG OPERATION.
MODEL
E-80 E-80
SIZE
2x2x7B 2x2x7B
FLUID
WATER
WATER
MAX
TEMP.
(ºF)
FLOW
RATE
(GPM)
115.0 115.0
HEAD
(FT. H20)
PUMP
EFFICIENCY
MOTOR
SPEED
(RPM)
MOTOR
SIZE
(HP)
VOLT
ELECTRICAL
ø
HZ
NOTES
1,2,3,4 1,2,3,4
CHILLED WATER FAN COIL UNIT SCHEDULE
MARK
NO.
1-FCU-1
NOTES: 1
MANUFACTURER
TRANE
COOLING ONLY UNIT. PROVIDE WITH REAR ACCESS FILTER HOUSING AND MERV 8 FILTERS, HIGH CONDENSATE UNIT SHUTDOWN.
PROVIDE WITH HANGER HARDWARE WITH RUBBER IN SHEAR VIBRATION ISOLATORS. MOUNT AS HIGH AS POSSIBLE.
INDOOR
UNIT
MODEL
BCHD054
ARRANGEMENT
HORIZONTAL
AIRFLOW
CFM
TSP
IN., WG
1.6
ESP
IN., WG
0.5
RPM
HP
1.0
SPACE
CONDITIONS
(DB°F/WB°F)
80/71
TOTAL
CAP.
(MBH)
92.8
SENS.
CAP.
(MBH)
62.3
EWT
°F 43.0
LWT
°F 53.0
CHILLED WATER
GPM
18.5
WPD
IN., WG
12.3
VOLT
ELECTRICAL
ø
HZ
NOTES
1,2
589A5-15-117
No. Description Date on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .