P01-SOW Package_CLC FIRE PROTECTION.pdf

PDF 3 MB Posted

Attached to
Y1DZ--"Renovate 1st Floor Community Living Center" at G. V. (Sonny) Montgomery VAMC in Jackson, MS.
Solicitation number
36C25620R0055
Issued by

About this file

This solicitation requests proposals to renovate the first floor of the Community Living Center at the G.V. (Sonny) Montgomery VA Medical Center in Jackson, Mississippi. Contractors shall provide all labor, materials, equipment, transportation and supervision to complete the renovation. The solicitation includes attachments with instructions, important dates, a statement of work and specifications. Proposals are due by [date redacted] and the contract is expected to be awarded by [date redacted]. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is the contracting agency. The renovation scope includes demolition of existing fire alarm systems, sprinkler piping and installation of new systems throughout the first floor in accordance with attached drawings and specifications.

View the file

Other files

File Type Posted
Amendment 0004_Addendum No 2 Renovate First Floor CLC Revised.pdf PDF
Amendment 0004_36C25620R0055 0004.pdf PDF
Amendment 0003_Combined QandA Final 7_21_2020.pdf PDF
Amendment 0003_36C25620R0055 0003.pdf PDF
Amendment 0003_90_TE_VACLC_2018-01-12_IFB.pdf PDF
Amendment 0003_44OP-249548 VA-CLS Reno Asbuilt Dwg 12-12-19.pdf PDF
Amendment 0003_VA CLC AS-BUILTS COMBINE.pdf PDF
Amendment 0003_M0201_AS_BUILT.pdf PDF
Amendment 0003_M0603_AS_BUILT.pdf PDF
Amendment 0003_A0101-Model REVISED 11 25 2019.pdf PDF
Amendment 0002_36C25620R0055 0002.pdf PDF
Amendment 0001_EXHIBIT B PERFORMANCE RELEVANCY SURVEY.docx DOCX document
Amendment 0001_EXHIBIT C PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
Amendment 0001_CLC Site Visit Sign-in Sheet.pdf PDF
Amendment 0001_36C25620R0055 0001.pdf PDF
P01 - CLC_ENVIRONMENTAL PROTECTION CONSIDERATIONS--2019.pdf PDF
P01-SOW Package_CLC Specification Volume 1 FINAL.pdf PDF
P01-SOW Package_CLC GENERAL.pdf PDF
P01- SOW Package_ CLC ARCHITECTURAL.pdf PDF
Final Statement of Work.pdf PDF
P01-SOW Package_CLC Specification Volume 2 FINAL.pdf PDF
P01- SOW Package_CLC ELECTRICAL.pdf PDF
P01 - CLC ASBESTOS Statement.pdf PDF
P01-SOW Package_CLC PLUMBING.pdf PDF
36C25620R0055.docx DOCX document
P01-SOW Package_CLC MECHANICAL.pdf PDF
P01 - CLC ASBESTOS Specification.pdf PDF
SF24 - BID BOND.pdf PDF
P01 - CLC ASBESTOS Construction Waste Specification.pdf PDF
P01 - SOW Package_CLC Addendum to Specification Vol 1 and 2.pdf PDF
Wage Determination 4_13_2020 Jackson CLC.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FA001

NEW FIRE ALARM SYSTEMS

GENERAL NOTES

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

1. CONTRACTOR SHALL MAINTAIN AND RESTORE ALL CONDUITS AND CONDUCTORS PASSING THROUGH THE RENOVATED AREAS

SERVICING OTHER UNDISRUPTED AREAS.

2. CONTRACTOR TO REMOVE ALL ACCESSIBLE WIRING OR CAP AND LABEL JUNCTION BOXES FOR RE-USE IN ACCORDANCE WITH THE

NATIONAL ELECTRIC CODE.

3. EXISTING EQUIPMENT SUCH AS WIRING, DEVICES, CONDUITS, ETC. SHALL BE COMPLETELY REMOVED. CUT/CAP CONDUITS AT THE

AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT

PROTECTIVE DEVICES AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

4. THE CONTRACTORS SHALL USE ACTUAL FIELD MEASUREMENT VERIFIED WHILE ON SITE. NOTIFY THE ARCHITECT/ENGINEER

PROJECT MANAGER IF ANY DISCREPANCIES ARE FOUND PRIOR TO PROCEEDING WITH WORK.

5. FIRESTOPPING OF ALL PENETRATIONS IN RATED WALLS SHALL BE PROVIDED .

6. CONDUIT SHALL BE INSTALLED AND CONCEALED IN FINISHED AREA(S) UNLESS NOTED OTHERWISE.

7. COORDINATE FINAL INSTALLATION AND LOCATION OF FIRE ALARM CONTROL PANELS, VOICE EVACUATION PANELS, REMOTE

ANNUNCIATOR PANELS, AND DEVICES WITH ARCHITECTURAL ELEVATIONS, THE CONTRACTOR, ARCHITECT/ENGINEER PROJECT

MANAGER PRIOR TO ROUGH IN.

8. PROVIDE A COMPLETE AND OPERATIONAL FIRE ALARM SYSTEM WITH VOICE EVACUATION INCLUDING ALL MODULES, RELAYS, COMPONENTS, WIRING, PROGRAMMING AND CONNECTIONS.

9. EACH FIRE ALARM CONTROL PANEL, VOICE EVACUATION PANEL OR REMOTE POWER SUPPLY SHALL BE FED FROM A DEDICATED

BRANCH CIRCUIT AND PERMANENTLY IDENTIFIED AT THE CONTROL UNIT. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED

MARKING AND NOT DAMAGE OR OBSCURE THE OVERCURRENT PROTECTIVE DEVICE. WHERE A CIRCUIT BREAKER IS THE

DISCONNECTING MEANS AN APPROVED BREAKER LOCKING DEVICE SHALL BE INSTALLED.

10. PROVIDE SECONDARY (STANDBY) POWER PER NFPA 72 TO OPERATE THE FIRE ALARM SYSTEM/MASS NOTIFICATION SYSTEM UNDER

SUPERVISORY CONDITIONS FOR 24 HOURS AND ALL ALARM DEVICES FOR AN ADDITIONAL 15 MINUTES AT THE MAXIMUM

CONNECTED LOAD.

11. VOICE INTELLIGIBILITY: CONTRACTOR TO ENSURE THAT A CIS VALUE OF 0.7 OR GREATER IS PROVIDED IN EACH AREA WHERE THE

BUILDING OCCUPANTS COULD TYPICALLY BE FOUND.

12. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR LABELING ALL CIRCUITS THAT SERVE FIRE PROTECTION EQUIPMENT AT THE

RESPECTIVE ELECTRICAL POWER PANEL.

13. CIRCUITS THAT FEED FIRE PROTECTION EQUIPMENT SHALL BE MARKED AT THE EQUIPMENT SERVED AND MUST BE IDENTIFIED ON

THE AS-BUILT MARK UP OF FIRE ALARM DRAWINGS.

14. PULL ALL CONDUCTORS SPLICE FREE; CONDUCTORS MUST BE CONTINUOUS FROM DEVICE TO DEVICE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS PROHIBITED.

15. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP OR THE DEVICE SCREW TERMINALS. TERMINAL STRIPS ARE ONLY PERMITTED

WHERE DIRECT CONNECTION TO A DEVICE IS NOT POSSIBLE.

16. RUN ALL WIRING TO AND WITHIN CONTROL PANELS IN THE VERTICAL OR HORIZONTAL PLANE, MAKE ALL TURNS AT 90 DEGREE

ANGLES, AND TIGHTLY BUNDLE, WRAP, AND IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. CONDUCTOR

MARKINGS MUST BE PRINTED LABELS, PERMANENTLY AFFIXED TO THE CONDUCTOR VIA SHRINK WRAP.

17. MARK INCOMING CABLES TO EACH DEVICE. IDENTIFY THE CIRCUIT NUMBER AT ALL TERMINATIONS.

18. ALL CONDUCTORS MUST BE INSTALLED IN CONDUIT (EMT MINIMUM). CONDUIT SIZING AND ROUTING IS THE RESPONSIBILITY OF THE

FIRE ALARM CONTRACTOR.

19. FIRE ALARM CONTRACTOR SHALL PROVIDE CONDUIT FILL CALCULATIONS IN ACCORDANCE WITH NFPA 70.

20. NOTIFICATION APPLIANCE CIRCUITS SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT EDITION. MINIMUM

WIRING SIZE SHALL BE 16 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM NOTIFICATION APPLIANCE CIRCUITS.

21. SIGNALING LINE CIRCUIT (SLC) SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT ADDITION. MINIMUM

WIRING SIZE SHALL BE 18 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM SIGNALING LINE CIRCUITS.

22. INITIATING DEVICE CIRCUITS (IDC) SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT ADDITION. MINIMUM

WIRING SIZE SHALL BE 16 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM INITIATING DEVICE CIRCUITS.

23. ALL WIRING SHALL BE PLENUM RATED AND SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED.

24. DETECTORS SHALL NOT BE LOCATED WHERE AIR FROM HVAC SUPPLY DIFFUSERS COULD DILUTE SMOKE BEFORE IT REACHES THE

DETECTORS. DETECTORS SHALL NOT BE INSTALLED WITHIN 3 FEET (1 METER) OF AIR SUPPLY GRILLES OR DIFFUSERS.

25. DETECTORS SHALL BE LOCATED ON THE CEILING SO THEY ARE VISIBLE AND ACCESSIBLE FROM THE FLOOR LEVEL FOR

MAINTENANCE AND TESTING OF THE DEVICES.

26. DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL.

DETECTORS THAT HAVE BEEN INSTALLED DURING CONSTRUCTION AND FOUND TO HAVE A SENSITIVITY OUTSIDE THE LISTED AND

MARKED SENSITIVITY RANGE SHALL BE REPLACED AS OUTLINED IN NFPA 72.

27. POWER LIMITED CIRCUITS SHALL NOT BE PLACED IN THE SAME CONDUIT, ENCLOSURE, OR RACEWAY WITH NON-POWER LIMITED

CIRCUITS. POWER LIMITED CIRCUITS SHALL BE ISOLATED FROM NON-POWER LIMITED CIRCUITS, ELECTRIC LIGHTS, OR POWER

CIRCUITS BY A MINIMUM OF 2 INCHES.

28. ALL STROBE NOTIFICATION APPLIANCES SHALL BE SYNCHRONIZED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 72.

FLASHING BUILDING ALARM NOTIFICATION STROBES SHALL BE SYNCHRONIZED WHERE COLLOCATED IN THE SAME FIELD OF VIEW

OR SPACE.

29. UPON OPERATION OF A FIRE ALARM INITIATING DEVICE, THE FIRE ALARM WILL ACTIVATE NOTIFICATION APPLIANCES IN THE ZONE

OF ALARM ORIGIN ONLY. SIMULTANEOUSLY THE FIRE ALARM SYSTEM WILL SEND A VOICE MESSAGE TO THE REST OF THE BUILDING

AND OTHER BUILDINGS AS NECESSARY TO NOTIFY ENOUGH STAFF TO RESPOND TO THE ZONE OF ALARM ORIGIN. NO VISIBLE

APPLIANCES WILL BE ACTIVATED OUTSIDE OF THE ZONE OF ALARM ORIGIN.

30. SMOKE ALARM NOTIFICATION APPLIANCES SHALL BE LOCATED IN RESIDENT SLEEPING ROOMS AND ACTIVATE A LOCAL ALARM UPON

DETECTION OF SMOKE. SMOKE ALARM SOUNDER SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT

SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND LEVEL OF

AT LEAST 75 dBA, WHICHEVER IS GREATER, MEASURED AT THE PILLOW LEVEL. SMOKE ALARM SOUNDER BASES SHALL BE LISTED

FOR PRODUCING A LOW-FREQUENCY 520Hz WAVEFORM.

31. CONTRACTOR TO COORDINATE FIRE ALARM ZONES WITH SMOKE COMPARTMENTS AND SPRINKLER ZONES.

32. CONTRACTOR TO COORDINATE WITH FACILITIES MANAGER AREA REPORTING FOR INITIATING DEVICE ACTIVATION.

33. SMOKE ALARM DEVICE ACTIVATION SHALL REPORT ALARM CONDITION TO LOCAL FIRE ALARM CONTROL PANEL & ANNUNCIATOR.

SMOKE ALARM SHALL INITIATE A LOCAL AUDIBLE ALARM AND ACTIVATE LOCAL VISIBLE APPLIANCE ONLY.

34. BUILDINGS SHALL COMMUNICATE TROUBLE, SUPERVISORY, AND ALARM SIGNALS TO A DESIGNATED 24-HOUR STAFFED LOCATION.

35. SEE FIRE PROTECTION DRAWING FP502 FOR PENETRATION DETAILS.

FIRE ALARM GENERAL NOTES

DEVICE LEGEND

SYMBOL DESCRIPTION

FIRE ALARM CONTROL PANEL (EXISTING)

NAC AND AUX POWER SUPPLY

FIRE ALARM ANNUNCIATOR

MANUAL PULL STATION

PHOTOELECTRIC SMOKE DETECTOR

STROBE, WALL MOUNT

STROBE, CEILING MOUNT

TAMPER SWITCH

WATERFLOW SWITCH

AMPLIFIER CABINET

SPEAKER, CEILING MOUNT

SS

PHOTOELECTRIC SMOKE ALARM WITH 520Hz SOUNDER BASE

MAGNETIC DOOR HOLDER

SPEAKER/STROBE, CEILING MOUNT

MONITOR MODULE

CONTROL MODULE

FIRE ALARM TERMINAL CABINET

RELAY MODULE

KEY BYPASS SWITCH WITH INDICATOR LAMP

RATE OF RISE & FIXED TEMPERATURE HEAT DETECTOR

S

DUCT MOUNTED SMOKE DETECTOR

DN DN

DN

A B C D E F H J K L M N O P R S T U V WG

F

SS

F

F

F

SS

SSSS

SS

S

S

S

S

S

S

S

S

SSSS SS

SSSSSS

SS

SSSSSSSSSS

SS

SS SS SS SS SS

S

S

S

S

SSS

S

FA101

A

S S

S

S

Bedroom

H-144

Bedroom

H-139

Bedroom

H-138

Bedroom

H-134

Bedroom

H-133

Bedroom

H-146

Bedroom

H-141

Bedroom

H-140

Bedroom

H-135

Bedroom

H-132

Bedroom

H-153

Bedroom

H-154

Bedroom

H-159

Bedroom

H-160

Bedroom

H-165

Bedroom

H-166

Bedroom

H-162

Bedroom

H-161

Bedroom

H-156

Bedroom

H-155

Clean Utility

H-152

Soiled Utility

H-151

Bath Suite

H-131

Medicine Stor.

H-128

Oxygen Storage

H-116

House Keeping

H-115

Office

H-114

Family Lounge

H-129

Office

H-113

Office

H-112

Staff Lounge

H-111

Office

H-110

Shared Office

H-109

Shared Office

H-107

Bedroom

H-145

Conference

H-102

Locker Room

H-100

Toilet

H-100A

Toilet

H-100B

Laundry

H-117

Storage/Linen

Storage

H-118

Toilet

H-145.1

Toilet

H-144.1

Toilet

H-139.1

Toilet

H-138.1

Toilet

H-134.1

Toilet

H-133.1

Toilet

H-146.1

Toilet

H-141.1

Toilet

H-140.1

Toilet

H-135.1

Toilet

H-132.1

Toilet

H-155.1

Toilet

H-156.1

Toilet

H-161.1

Toilet

H-162.1

Toilet

H-166.1

Toilet

H-153.1

Toilet

H-154.1

Toilet

H-159.1

Toilet

H-160.1

Toilet

H-165.1

Toilet

H-150.1

Bariatric Bedroom

H-130

Toilet

H-130.1

Bariatric Bedroom

H-150

Telecom Closet

H-125

Closet

H-120

Kitchen

H-121

Public Toilet

H-119

Corridor

H-105.4

Corridor

H-105.3

Stair #2

H-002

Stair #3

H-003

Restorative

Therapy

H-104

Elec.

H-106

OT Office

H-101.1

Occupational

Therapy

H-101

PT Office

H-103.1

Physical Therapy

H-103

Staff Stor.

H-108

ADL

H-101.3

Living

H-124

Living

H-122

Ward Nurse

H-127

Waiting

H-126

Corridor

H-105

Stair #1

H-001

Elec.

H-142

Storage

H-143

Storage

H-137

Storage

H-164

Storage

H-163

Elec.

H-157

Alcove

H-158

Alcove

H-136

Recreation/Dining/Events

H-123

Corridor

H-105

Storage

H-101.2

W/C & Walker

Storage

H-105.2

Corridor

H-105.1

FA501

FA501

FA501

FA501

FA501

FA501

FA501

FA501

FA502

FA502

S

Telecom Closet

H-125

FA501

DN

STAIR

CONFERENCE

N O P

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FA101

NEW FIRE ALARM SYSTEMS

PLAN - FIRST FLOOR

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019

1/8" = 1'-0"

FA101

FIRST FLOOR - NEW LAYOUT

Revisions: Date: SEL JCB

A. SEE FA001 FOR ADDITIONAL GENERAL NOTES

B. EXISTING FIRE ALARM SYSTEM EQUIPMENT,

CONDUCTORS, RACEWAYS, NOTIFICATION

APPLIANCES AND INITIATING DEVICES ON THE

FIRST FLOOR OF THE CLC ARE TO BE REMOVED

AND REPLACED WITH NEW.

C. NEW FIRE ALARM SYSTEM SHALL MEET THE

REQUIREMENTS OF NFPA 72.

D. THE NEW NOTIFICATION APPLIANCE POWER

SUPPLIES AND AMPLIFIER PANELS SHALL BE

CONNECTED TO THE FIRE ALARM CONTROL

PANEL AND CAPABLE OF REPORTING TO

EMERGENCY RESPONDERS.

E. FIRE ALARM SYSTEM TO PROVIDE HVAC UNIT

SMOKE DETECTION AND AUTOMATIC SHUTDOWN

OF ELEVATOR RECALL FUNCTIONS.

F. SMOKE ALARM DEVICES LOCATED IN SLEEPING

ROOMS SHALL BE PRODUCE A SQUARE

WAVEFORM WITH A FREQUENCY OF 520 Hz.

G. STROBES ARE ONLY TO BE ACTIVATED IN THE

ZONE OF ALARM ORIGIN.

1 FIRE SUPPRESSION TAMPER SWITCH TO BE

MONITORED BY FIRE ALARM CONTROL PANEL.

2 FIRE SUPPRESSION WATERFLOW SENSOR TO BE

MONITORED BY FIRE ALARM CONTROL PANEL.

3 SLEEPING ROOMS SHALL BE EQUIPPED WITH A

STROBE THAT IS SET TO 110CD AND LOCATED NO

LESS THAN 24 INCHES FROM THE TOP OF THE

LENSES TO THE FINISHED CEILING.

4 LOCATE STROBE NO MORE THAN 16'-0" AWAY

FROM THE PILLOW.

5 LOCATE SMOKE DETECTOR NO MORE THAN 21'-0"

FROM CENTERLINE OF EACH ELEVATOR DOOR.

6 LOCATE SMOKE DETECTOR NO LESS THAN 36 IN.

HORIZONTALLY FROM AN AIR SUPPLY REGISTER.

7 PROVIDE ADDITIONAL NOTIFICATION APPLIANCE

CIRCUIT POWER SUPPLIES FOR STROBE

NOTIFICATION APPLIANCES & LOW-VOLTAGE

SMOKE DETECTOR SOUNDER BASES.

8 EXISTING FIRE ALARM CONTROL PANEL TO BE

DEMOLISHED. NEW FIRE ALARM CONTROL PANEL

TO BE LOCATED ON GROUND LEVEL IN

MECHANICAL ROOM G132.1.

9 LOCATE HEAT DETECTOR NO MORE THAN

24-INCHES FROM SPRINKLER HEAD. COORDINATE

LOCATION OF SMOKE DETECTOR WITH FIRE

PROTECTION CONTRACTOR.

0 5 10

GRAPHIC SCALE

1/4" = 1'-0"

FA101

A

TELECOM CLOSET H125 - ENLARGEMENT DETAIL

0 5 10

GRAPHIC SCALE

1/8" = 1'-0"

FA101

FIRST FLOOR - DEMOLITION LAYOUT

0 5 10

GRAPHIC SCALE

A B C D E F H J K L M N O P R S T U V WG

U P

PENTHOUSE

P001

MACHINE

PLATFORM

KNOCK OUT

SLAB FOR

FUTURE

ELEVATORS

S

S

F

FA501

FA501

FA501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FA102

NEW FIRE ALARM SYSTEMS

PLAN - ROOF

RENOVATE ROOF CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019

1/8" = 1'-0"

FA102

ROOF LEVEL - NEW LAYOUT

Revisions: Date: SEL JCB

1 MOUNT EMERGENCY CONTROL FUNCTION RELAY

MODULE WITHIN 36-INCHES FROM ELEVATOR

CONTROLLER.

0 5 10

GRAPHIC SCALE

A. SEE FA001 FOR ADDITIONAL GENERAL NOTES

B. EXISTING FIRE ALARM SYSTEM EQUIPMENT,

CONDUCTORS, RACEWAYS, NOTIFICATION

APPLIANCES AND INITIATING DEVICES ON THE

FIRST FLOOR OF THE CLC ARE TO BE REMOVED

AND REPLACED WITH NEW.

C. NEW FIRE ALARM SYSTEM SHALL MEET THE

REQUIREMENTS OF NFPA 72.

D. THE NEW NOTIFICATION APPLIANCE POWER

SUPPLIES AND AMPLIFIER PANELS SHALL BE

CONNECTED TO THE FIRE ALARM CONTROL

PANEL AND CAPABLE OF REPORTING TO

EMERGENCY RESPONDERS.

E. FIRE ALARM SYSTEM TO PROVIDE HVAC UNIT

SMOKE DETECTION AND AUTOMATIC SHUTDOWN

OF ELEVATOR RECALL FUNCTIONS.

F. SMOKE ALARM DEVICES LOCATED IN SLEEPING

ROOMS SHALL BE PRODUCE A SQUARE

WAVEFORM WITH A FREQUENCY OF 520 Hz.

G. STROBES ARE ONLY TO BE ACTIVATED IN THE

ZONE OF ALARM ORIGIN.

UPUP

UPUP

DN

DN

UP

UP

A

A

B

B

C

C

D

D E

F

F G J M O P

R

S

T

T

U

U

V

V

W

W

EXISTING FITNESS CENTER

(TO BE REPLACED BEFORE PROJECT BEGINS)

(EXISTING)

AR-14

AR-12AR-12

EQ-03

EQ-03

AR-05

L

AR-60

AR-01

EWC

AR-01

AR-01

AR-01

AR-01

AR-30L

AR-01

AR-59 AR-59

AR-17

Bedroom

G148

SIM.G165

Bedroom

G149

SIM.G165

Bedroom

G150

SIM.G165

Bedroom

G151

SIM.G165

Bedroom

G152

SIM.G165

Bedroom

G153

SIM.G165

Bedroom

G142

SIM.G165

Bedroom

G143

SIM.G165

Bedroom

G144

SIM.G165

Bedroom

G145

SIM.G165

Bedroom

G146

SIM.G165

Bedroom, Bariatric

G141

SIM.G161

Bath Suite

G154

Bedroom, Bariatric

G161

Soiled Utility

G174

Clean Utility

G173

Bedroom

G172

SIM.G165

Bedroom

G171

SIM.G165

Bedroom

G170

SIM.G165

Bedroom

G169

SIM.G165

Bedroom

G168

SIM.G165

Bedroom

G166

SIM.G165

Bedroom

G165

Bedroom

G164

SIM.G165

Bedroom

G163

SIM.G165

Bedroom

G162

SIM.G165

Office

G123

Family

Lounge

G107

Medicine

Storage

G106

Telecom

Closet

G113

Conference

G131

Staff Lounge

G126

Office

G127

Office

G128

Mechanical

(E)

G132

Mechanical

(E)

G132.1

Concierge

Station

G105

Sitting Area

G104

Multi-Purpose

Area

G112

Laundry

G109

Shared Office

G129

Toilet

G148.1

SIM.G165.1

Toilet

G149.1

SIM.G165.1

Toilet

G150.1

SIM.G165.1

Toilet

G151.1

SIM.G165.1

Toilet

G152.1

SIM.G165.1

Toilet

G153.1

SIM.G165.1

Toilet

G146.1

SIM.G165.1

Toilet

G145.1

SIM.G165.1

Toilet

G144.1

SIM.G165.1

Toilet

G143.1

SIM.G165.1

Toilet

G142.1

SIM.G165.1

Toilet

G141.1

SIM.G161.1

Toilet

G166.1

SIM.G165.1

Toilet

G165.1

Toilet

G164.1

SIM.G165.1

Toilet

G163.1

SIM.G165.1

Toilet

G162

SIM.G165.1

Toilet

G161.1

Storage

G140.1

Corridor

G140

Corridor

G160

Stairs

G167

Stairs

G147

Stairs

G133

Lobby

G103

Oxygen

Storage-

Empty

G121

Storage

G140.2

Elec

G160.2

Storage

G160.4

Alcove

G160.5

Toilet

G172.1

SIM.G165.1

Toilet

G171.1

SIM.G165.1

Toilet

G170.1

SIM.G165.1

Toilet

G169.1

SIM.G165.1

Toilet

G168.1

SIM.G165.1

Foyer

G101

Lobby

G103

Vestibule

G100

Elevator

C1-G

Elevator

C2-G

Locker Room

G130

Toilet

G130.2

Toilet

G130.1

Elec

G120.1

Storage/Linen

Storage

G110

Kitchen

G111

House

Keeping

G122

Alcove

G140.5

Elec Closet

G140.4

Storage

G140.3

Storage

G160.3

Office

G124

Multi-Purpose

Area

G102

Oxygen

Storage - Full

G121.1

Public Toilet

G108

Corridor

G175

Office

G125

Closet

G114

S

FA501

FA501

FA502

FA501

FA501

FA501

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FA103

NEW FIRE ALARM SYSTEMS

PLAN - LOWER LEVEL

RENOVATE GROUND FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019

1/8" = 1'-0"

FA103

LOWER LEVEL - NEW LAYOUT

Revisions: Date: SEL JCB

A. SEE FA001 FOR ADDITIONAL GENERAL NOTES

B. FIRE ALARM SYSTEM EQUIPMENT, CONDUCTORS,

RACEWAYS, NOTIFICATION APPLIANCES AND

INITIATING DEVICES ON THE LOWER LEVEL OF

THE CLC ARE TO BE INSTALLED UNDER SEPARATE

CONTRACT UNLESS OTHERWISE NOTED.

C. NEW FIRE ALARM SYSTEM SHALL MEET THE

REQUIREMENTS OF NFPA 72.

1 PROVIDE NEW FIRE ALARM CONTROL PANEL

LOCATED IN MECHANICAL ROOM G132.1.

2 PROVIDE AMPLIFIER CABINET FOR NEW SPEAKER

NOTIFICATION APPLIANCES.

3 PROVIDE SMOKE DETECTOR ABOVE FIRE ALARM

CONTROL PANEL.

4 PROVIDE FIRE ALARM TERMINAL CABINET. VERIFY

FIRE ALARM TERMINAL CABINET LOCATION WITH

OWNERS REPRESENTATIVE.

0 5 10

GRAPHIC SCALE

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

FA501

NEW FIRE ALARM SYSTEMS

EQUIPMENT DETAILS

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

FLUSH MOUNTED

REMOTE ANNUNCIATOR PANEL

SURFACE MOUNTED

FIRE ALARM CONTROL PANEL

SURFACE MOUNTED

VOICE EVACUATION PANEL

FLUSH MOUNTED

SMOKE/HEAT DETECTOR

FLUSH MOUNTED PULL STATION

SURFACE MOUNTED

MONITOR MODULE

SURFACE MOUNTED

CONTROL/RELAY MODULE

SURFACE MOUNTED

NOTIFICATON APPLIANCE

CIRCUIT PANEL

FLUSH MOUNTED

SMOKE ALARM DETECTOR

A

M

WALL MOUNTED (SURFACE)

SPEAKER/STROBE

WALL MOUNTED (FLUSH)

STROBE ONLY

CEILING MOUNTED (FLUSH)

STROBE ONLY

CEILING MOUNTED (FLUSH)

SPEAKER/STROBE

WALL MOUNTED (FLUSH)

SLEEPING ROOM

STROBE NOTIFICATION APPLIANCE

64 POINT FIRE

ALARM TERMINAL CABINET

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

FA502

NEW FIRE ALARM SYSTEMS

EQUIPMENT DETAILS

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

DUCT MOUNTED

SMOKE DETECTOR

A

M

64 POINT FIRE

ALARM TERMINAL CABINET

HVAC SUPPLY AND RETURN

DETECTION AND SHUTDOWN

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FA601

NEW FIRE ALARM SYSTEMS

RISER DIAGRAM AND MATRIX

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

S

FIRE ALARM & VOICE EVACUATION

NOTIFICATION SYSTEM RISER DIAGRAM

BUILDING FIRE ALARM FUNCTIONS

I N

P U

T S

OUTPUTS

AREA SMOKE DETECTOR ACTIVATION

D

IS

P

LA

Y A

LA

R

M M

E S

S A

G E

A T

FA

C

P A

N D

R E

M O

TE

F

A A

P

D

IS

P

LA

Y

TR

O U

B

LE

M E

S S

A G

E A

T

FA

C P

A N

D R

E M

O

TE

F A

A P

D

IS

P

LA

Y S

U P

E R

VI

S

O R

Y M

E S

S A

G E

A T

FA

C

P A

N D

R E

M O

TE

F

A A

P

A C

TI

VA

TE

P

R E

-R E

C O

R D

E D

F

IR

E A

LA

R

M M

E S

S A

G E

F

IR

E

A

LA

R M

S

TR

O B

E S

IN

Z

O N

E O

F A

C

TI

VA

TI

O N

S E

N D

A

LA

R M

S

IG

N A

L

TO

C E

N

TR

A L

S

TA

TI

O

N M

O N

IT

O

R

IN

G S

TA

TI

O N

S E

N D

T R

O U

B

LE

S

IG

N A

L

TO

C E

N

TR

A L

S

TA

TI

O

N M

O N

IT

O

R

IN

G S

TA

TI

O N

S E

N D

S U

P E

R

VI

S O

R Y

S

IG

N A

L

TO

C E

N

TR

A L

S

TA

TI

O

N M

O N

IT

O

R

IN

G S

TA

TI

O N

R E

C O

R D

E

VE

N

TS

IN

S

YS

TE

M H

IS

TO

R Y

M E

M O

R Y

A C

TI

VA

TE

O

U

TS

ID

E

W A

TE

R

FL

O

W B

E

LL

NOTIFICATION

A B C D E F G H P Q

MANUAL PULL STATION ACTIVATION

SPRINKLER TAMPER SWITCH ACTIVATION

SPRINKLER WATERFLOW SWITCH ACTIVATION

SYSTEM AC POWER FAILURE

SYSTEM LOW BATTERY

OPEN CIRCUIT

GROUND FAULT

WIRE-TO-WIRE SHORT NOTIFICATION APPLIANCE CIRCUIT (NAC)

WIRE-TO-WIRE SHORT SIGNALING LINE CIRCUIT (SLC)

PANEL

REPORTING

CENTRAL

STATION

FACP

CONTROL

FIRE ALARM & VOICE EVACUATION

NOTIFICATION OPERATIONAL MATRIX

F

IN ROOM SMOKE ALARM ACTIVATION

P R

IN

T

E

VE

N T

A T

TH

E

F

IR

E A

LA

R

M C

O N

TR

O

L P

A N

E L

P R

IN

TE

R

A C

TI

VA

TE

L

O C

A L

S O

U N

D E

R B

A S

E A

N D

L O

C A

L S

TR

O

B E

N O

TI

FI

C A

TI

O

N A

P P

LI

A

N C

E

A C

TI

VA

TE

P

R E

-R E

C O

R D

E D

F

IR

E A

LA

R

M M

E S

S A

G E

F A

C

IL

IT

Y

W

ID

E (C

O O

R D

IN

A

TE

W

IT

H

F A

C

IL

IT

IE

S M

A N

A G

E R

SS

R E

LE

A

S E

M A

G N

E

TI

C A

LL

Y

H E

LD

O

P E

N D

O O

R S

S

1 STROBE NOTIFICATION APPLIANCES SHALL BE

SYNCHRONIZED WITH FIRE ALARM CONTROL

PANEL ON LOWER LEVEL.

2 EXISTING FIRE ALARM CONTROL PANEL TO BE

REMOVED

3 NEW FIRE ALARM CONTROL PANEL TO BE

LOCATED ON GROUND LEVEL IN MECHANICAL

ROOM G132.1.

4 DEMOLISH FIRE ALARM CIRCUITS AND CONNECT

TO NEW FIRE ALARM CIRCUIT WHEN EXISTING

FIRE ALARM CONTROL PANEL ON LEVEL ONE IS

DECOMMISSIONED.

DOOR RELEASE SMOKE DETECTOR

O P

E N

L O

C K

E D

E G

R E

S S

D O

O R

S O

N F

LO

O

R O

F

FI

R E

O R

IG

IN

ELEVATOR MACHINE ROOM HEAT DETECTOR

IN

IT

IA

TE

E

LE

VA

TO

R S

H U

T D

O W

N A

N D

D

IS

C O

N N

E C

T E

LE

VA

TO

R

P O

W E

R

TOP OF SHAFT ELEVATOR HEAT DETECTOR

TOP OF SHAFT ELEVATOR SMOKE DETECTOR

IN

IT

IA

TE

E

LE

VA

TO

R R

E C

A

LL

T O

P R

IM

A

R Y

LE

VE

L O

F E

G R

E S

S D

IS

C

H A

R G

E

IN

IT

IA

TE

E

LE

VA

TO

R R

E C

A

LL

T O

A

LT

E R

N A

TE

L

E

VE

L O

F E

G R

E S

S D

IS

C

H A

R G

E

SMOKE DETECTOR IN ELEVATOR LOBBY (UPPER LEVEL)

SMOKE DETECTOR IN ELEVATOR LOBBY (LOWER LEVEL)

ELEVATOR MACHINE ROOM SMOKE DETECTOR

ELEVATOR SHUNT-TRIP KEY BYPASS ACTIVATION

ELEVATOR LOSS OF POWER

IL

LU

M

IN

A

TE

E

LE

VA

TO

R S

H U

N T

B

YP

A S

S

IN

D

IC

A

TO

R L

A M

P

S

S

DUCT MOUNTED SMOKE DETECTOR ACTIVATION

IN

IT

IA

TE

A

IR

H A

N D

LE

R

S H

U

TD

O W

N

I J K L M N O R S

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FP001

NEW FIRE PROTECTION SYSTEMS

GENERAL NOTES

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

1. PROVIDE FULLY AUTOMATIC WET PIPE FIRE SPRINKLER SUPPRESSION SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.

2. CONTRACTOR SHALL SUBMIT FABRICATION DRAWINGS FOR REVIEW AND APPROVAL BY THE FIRE PROTECTION ENGINEER PRIOR TO

COMMENCEMENT OF WORK.

3. THE CONTRACTORS SHALL USE DIMENSIONS WHERE INDICATED ON THE DRAWINGS AND COMPARE WITH ACTUAL FIELD MEASUREMENT.

CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER PROJECT MANAGER IF ANY DISCREPANCIES ARE FOUND PRIOR TO PROCEEDING WITH

WORK. DO NOT SCALE FROM DRAWINGS.

4. ANY CONFLICTS BETWEEN THE SPECIFICATION AND DRAWINGS SHALL BE SUBMITTED AS REQUEST FOR INFORMATION. CONTRACTOR SHALL

NOT PROCEED WITH ANY NEW WORK, EXCEPT AT THEIR OWN RISK UNTIL CLARIFICATIONS HAVE BEEN ISSUED BY THE ARCHITECT / ENGINEER

PROJECT MANAGER.

5. FIRE SPRINKLER SYSTEM ABOVE GROUND PIPING SHALL BE STANDARD WEIGHT SCHEDULE 10 OR SCHEDULE 40 BLACK STEEL PIPE COMPLYING

WITH ASTM A135 AND ASTM A795. SPRINKLER SYSTEM PIPING SHALL BE APPROVED BY FACTORY MUTUAL FOR USE IN FIRE SUPPRESSION

SYSTEMS.

6. FITTINGS SHALL BE CAST IRON CONFORMING TO ASME B16.4, STEEL CONFORMING TO ASME B16.9 OR ASME B16.11, OR MALLEABLE IRON

CONFORMING TO ASME B16.3. FITTINGS INTO WHICH SPRINKLERS, DROP NIPPLES OR RISER NIPPLES (SPRIGS) ARE SCREWED SHALL BE

THREADED TYPE. PLAIN-END FITTINGS WITH MECHANICAL COUPLINGS, FITTINGS THAT USE STEEL GRIPPING DEVICES TO BITE INTO THE PIPE

AND SEGMENTED WELDED FITTINGS SHALL NOT BE USED.

7. JOINTS AND FITTINGS SHALL BE DESIGNED FOR NOT LESS THAN 175 PSI SERVICE AND SHALL BE THE PRODUCT OF THE SAME MANUFACTURER;

SEGMENTED WELDED FITTINGS SHALL NOT BE USED. FITTING AND COUPLING HOUSES SHALL BE MALLEABLE IRON CONFORMING TO ASTM

A47/A47M, GRADE 32510; DUCTILE IRON CONFORMING TO ASTM A536, GRADE 65-45-12. GASKET SHALL BE THE FLUSH TYPE THAT FILLS THE

ENTIRE CAVITY BETWEEN THE FITTING AND THE PIPE. NUTS AND BOLTS SHALL BE HEAT-TREATED STEEL CONFORMING TO ASTM A183 AND

SHALL BE CADMIUM PLATED OR ZINC ELECTROPLATED.

8. PIPE THREADS, FITTINGS, FLANGES AND MECHANICAL COUPLINGS SHALL COMPLY WITH APPLICABLE ASME STANDARDS AS LISTED IN NFPA 13.

THREADS SHALL COMPLY WITH NATIONAL PIPE THREAD (NPT) STANDARDS.

9. FIRESTOPPING OF ALL PENETRATIONS IN RATED WALLS SHALL BE PROVIDED PER REQUIREMENTS OF ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

10. SPRINKLER PIPING SHALL BE CONCEALED ABOVE FINISHED CEILINGS WHERE PROVIDED.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK WITH ALL TRADES. CONFLICTS WHICH PROHIBIT PROPER INSTALLATION OF

THE SYSTEMS AS DESIGNED SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PROJECT MANAGER.

12. CONTRACTOR SHALL OBTAIN APPROVAL FROM THE OWNER PRIOR TO WELDING AND CUTTING OPERATIONS. HOT WORK PERMITS MUST BE

PROVIDED AND PROPER NOTICE RECEIVED PRIOR TO PERFORMING SUCH OPERATIONS IN BUILT AREAS.

13. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND AVOIDING ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, STRUCTURAL MEMBERS, PIPES AND OTHER OBSTRUCTIONS ENCOUNTERED. COORDINATE LOCATIONS WITH ALL OTHER

SUBCONTRACTORS PERFORMING WORK. REFERENCE ARCHITECTURE REFLECTED CEILING PLANS FOR THE LOCATIONS OF LIGHT FIXTURES, CEILING FANS, DUCT WORK AND OTHER EQUIPMENT.

14. REFER TO STRUCTURAL, ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR LOCATIONS OF OTHER DISCIPLINE

EQUIPMENT AND REQUIRED CLEARANCES.

15. ALL WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED PENETRATIONS. CEILINGS AND FLOORS SHALL BE SEALED TO THE FULL

THICKNESS OF THE PENETRATION WITH APPROVED FIRE STOPPING MATERIALS OF EQUAL OR GREATER FIRE RESISTANCE TO THE PENETRATED

BARRIER SEE DETAILS ON DRAWING FP502.

16. ALL DAMAGE TO WALLS, CEILINGS, FLOORS OR ARCHITECTURAL FEATURES FROM PENETRATIONS, REMOVALS, INSTALLATIONS OR OTHER

ACTIONS OF THE CONTRACTOR SHALL BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS BY THE CONTRACTOR TO MATCH

ADJACENT WORK, WHETHER SPECIFICALLY NOTED OR NOT.

17. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, BENT OR BURNED WITHOUT PRIOR AUTHORIZATION FROM THE STRUCTURAL ENGINEER OF

RECORD. COORDINATE WITH STRUCTURAL FOR PIPE PENETRATION LOCATIONS TO BE PROVIDED IN STRUCTURAL MEMBERS.

18. ALL SPRINKLER HEADS SHALL BE PROTECTED DURING ANY PAINTING OR OTHER CONSTRUCTION ACTIVITIES WHICH MAY COAT THE SPRINKLER

HEADS WITH FINISH MATERIALS. PROTECT SPRINKLER HEADS USING BAGS, TAPE AND PLASTIC COVERINGS. MANUFACTURER SUPPLIED

SHIPPING COVERS ARE NOT ADEQUATE TO PREVENT PAINT ACCUMULATION ON HEADS. COVERINGS SHALL BE REMOVED PRIOR TO

ACCEPTANCE.

19. SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF ACOUSTICAL CEILING TILES WHERE PROVIDED. SPRINKLERS SHALL BE INSTALLED

WITHIN 1" VARIANCE IN EITHER DIRECTION.

20. COORDINATE LOCATIONS OF FLOW SWITCHES AND TAMPER SWITCHES WITH FIRE ALARM CONTRACTOR.

21. SPRINKLERS SHALL BE UL LISTED FM APPROVED CLOSED HEAD SPRINKLERS.

22. OWNER SHALL NOT BE RESPONSIBLE FOR DISPOSAL OF ANY MATERIALS OR CLEAN-UP OF THE CONSTRUCTION SITE. CONTRACTOR SHALL

DISPOSE OF ANY DEMOLISHED MATERIALS OR SCRAPS NOT FURNISHED AS PART OF THE NEW WORK.

23. ALL EXPOSED FIRE PROTECTION PIPING SHALL BE PAINTED RED UTILIZING LEAD-FREE PAINT.

24. SPRINKLER SYSTEM SHALL BE BRACED AND RESTRAINED IN ACCORDANCE TO THE SEISMIC REQUIREMENTS OF NFPA 13.

25. FIRE PROTECTION PIPING SHALL BE FURNISHED, INSTALLED AND TESTED PER NFPA 13, 2016 AND FM DATA SHEET 2-0. ALL PIPING SHALL BE

PRESSURE TESTED AT 200-PSI FOR TWO (2) HOURS WITH "NO" LEAKS. LEAKS SHALL BE REPAIRED BY TIGHTENING OR REPLACEMENT OF

FITTINGS. WRAPPING, CAULKING, OR OTHER MEANS SHALL NOT BE ALLOWED.

26. AUTOMATIC SPRINKLERS SHALL BE SCHEDULE 40 FOR ALL PIPE SIZES 1-1/2" AND SMALLER. ALL PIPING 2" AND LARGER CAN BE SCHEDULE 10 AS

LONG AS IT IS ROLL GROOVED.

FIRE SUPPRESSION GENERAL NOTES

HANGAR SCHEDULE

MAXIMUM HORIZONTAL DISTANCE BETWEEN PIPE HANGARS (ft-in)

NOMINAL PIPE DIAMETER (in.)

PIPING MATERIAL

1 1

2 2

3 3

4 > 4

STEEL PIPE NA 12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0

NOTES:

-HANGARS MUST BE INSTALLED A MINIMUM OF 3 in. IN THE HORIZONTAL DIRECTION FROM UPRIGHT SPRINKLERS.

-SEE DETAIL NUMBERS 8 & 9 ON SHEET FP501.

DEVICE LEGEND

= QUICK RESPONSE, 5.6 K, 155°F UPRIGHT FIRE SPRINKLER HEAD

= FIRE SUPPRESSION PIPE

= PIPE ELEVATION CHANGE - PIPE DROP SIZE DENOTED "DN"

= HYDRAULIC REFERENCE NODE

= PIPE END CAP OR BLIND FLANGE

= PIPE ELEVATION CHANGE - PIPE RISER SIZE DENOTED "RN"

= PIPE ELEVATION ABOVE BUILDING FIRST LEVEL SLAB

NEGATIVE ELEVATIONS INDICATE BELOW SLAB ELEVATION

= NOMINAL PIPE DIAMETER (DN)

= CENTER TO CENTER LENGTH DIMENSION

H01

= APPROXIMATE PIPE HANGER LOCATION

#1 SEE DETAIL NO. 4 ON SHEET FP501

= FIRE SPRINKLER RISER

= FLEXIBLE PIPE TO SPRINKLER HEAD

= QUICK RESPONSE, WHITE, 5.6 K, 155°F SEMI-RECESSED

PENDENT FIRE SPRINKLER HEAD

= STANDARD RESPONSE, 5.6 K, 286°F UPRIGHT FIRE SPRINKLER HEAD

= QUICK RESPONSE, 5.6 K, 286°F UPRIGHT FIRE SPRINKLER HEAD WITH GUARD

= DRY, CORROSION RESISTANT, QUICK RESPONSE

5.6K 155°F SIDEWALL SPRINKLER HEAD

DN DN

DN

A B C D E F H J K L M N O P R S T U V WG

FP501

FP501

(TYP.)

FP501

(TYP.)

FP501

(TYP.)

FP501

(TYP.)

FP501

FP501

FP501

(TYP.)

FP501

(TYP.)

Bedroom

H-144

Bedroom

H-139

Bedroom

H-138

Bedroom

H-134

Bedroom

H-133

Bedroom

H-146

Bedroom

H-141

Bedroom

H-140

Bedroom

H-135

Bedroom

H-132

Bedroom

H-153

Bedroom

H-154

Bedroom

H-159

Bedroom

H-160

Bedroom

H-165

Bedroom

H-166

Bedroom

H-162

Bedroom

H-161

Bedroom

H-156

Bedroom

H-155

Clean Utility

H-152

Soiled Utility

H-151

Bath Suite

H-131

Medicine Stor.

H-128

Oxygen Storage

H-116

House Keeping

H-115

Office

H-114

Family Lounge

H-129

Office

H-113

Office

H-112

Staff Lounge

H-111

Office

H-110

Shared Office

H-109

Shared Office

H-107

Bedroom

H-145

Conference

H-102

Locker Room

H-100

Toilet

H-100A

Toilet

H-100B

Laundry

H-117

Storage/Linen

Storage

H-118

Toilet

H-145.1

Toilet

H-144.1

Toilet

H-139.1

Toilet

H-138.1

Toilet

H-134.1

Toilet

H-133.1

Toilet

H-146.1

Toilet

H-141.1

Toilet

H-140.1

Toilet

H-135.1

Toilet

H-132.1

Toilet

H-155.1

Toilet

H-156.1

Toilet

H-161.1

Toilet

H-162.1

Toilet

H-166.1

Toilet

H-153.1

Toilet

H-154.1

Toilet

H-159.1

Toilet

H-160.1

Toilet

H-165.1

Toilet

H-150.1

Bariatric Bedroom

H-130

Toilet

H-130.1

Bariatric Bedroom

H-150

Telecom Closet

H-125

Closet

H-120 Kitchen

H-121

Public Toilet

H-119

Corridor

H-105.4

Corridor

H-105.3

Stair #2

H-002

Stair #3

H-003

Restorative

Therapy

H-104

Elec.

H-106

OT Office

H-101.1

Occupational

Therapy

H-101

PT Office

H-103.1

Physical Therapy

H-103

Staff Stor.

H-108

ADL

H-101.3

Living

H-124

Living

H-122

Ward Nurse

H-127

Waiting

H-126

Corridor

H-105

Stair #1

H-001

Elec.

H-142

Storage

H-143

Storage

H-137

Storage

H-164

Storage

H-163

Elec.

H-157

Alcove

H-158

Alcove

H-136

Recreation/Dining/Events

H-123

Corridor

H-105

Storage

H-101.2

W/C & Walker

Storage

H-105.2

C o r r i d o r

H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FP101

NEW FIRE PROTECTION SYSTEMS

PLAN - FIRST FLOOR

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

1/8" = 1'-0"

FX101

1st FLOOR - NEW LAYOUT

Revisions: Date: 11/01/2019 SEL JCB

A. SEE DRAWING FP001 FOR ADDITIONAL GENERAL

NOTES.

B. DEMOLISH AND REMOVE EXISTING FIRST FLOOR

SPRINKLER PIPING, VALVES AND HEADS AND

PROVIDE NEW LAYOUT FOR 100% SPRINKLER

COVERAGE.

C. PLAN DRAWINGS REFLECT SCHEMATIC PIPING

AND SPRINKLER HEAD LAYOUT. CONTRACTOR TO

CONFIRM PIPE SIZES AND SPRINKLER HEAD

SPACING WITH HYDRAULIC CALCULATION.

D. NEW SPRINKLER HEADS SHALL BE QUICK

RESPONSE, SEMI-RECESSED.

E. COORDINATE SPRINKLER BRANCH LINE AND HEAD

LOCATIONS WITH FINAL ARCHITECTURAL

REFLECTED CEILING PLAN AND MECHANICAL

DUCTS AND LIGHTING.

F. NEW FLOOR CONTROL VALVE, DRAIN,

INSPECTORS TEST AND TAMPER SWITCH

LOCATION SHALL BE COORDINATED WITH OWNER.

G. EXISTING FIRE DEPARTMENT HOSE VALVE AND

TAMPER TO REMAIN.

H.

1 EXISTING RISER LOCATION.

2 NEW FLOOR CONTROL VALVE. CONFIRM

LOCATION WITH OWNER.

3 NEW SPRINKLER CROSS MAINS LOCATED IN

CORRIDORS.

4 CONNECT NEW 4" SPRINKLER MAIN TO EXISTING

4" SPRINKLER RISER.

0 5 10

GRAPHIC SCALE

SOURCE DATA POINTS

WATER SUPPLY INFORMATION

PRESSURE FLOW

DATE OF FLOW TEST / INFO :

LOCATION OF FLOW TEST DATA :

SOURCE OF FLOW TEST DATA :

09/16/2019

BUILDING 7, 1ST FLOOR

70.00 0.00

65.00 722.00

55.00 1381.00

HYDRANT FLOW TEST BY:

INTERNATIONAL FIRE & SAFETY

A B C D E F H J K L M N O P R S T U V WG

U P

PENTHOUSE

P001

MACHINE

PLATFORM

KNOCK OUT

SLAB FOR

FUTURE

ELEVATORS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FP102

NEW FIRE PROTECTION SYSTEMS

PLAN - ROOF

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

1/8" = 1'-0"

FX102

ROOF LEVEL

Revisions: Date: 11/01/2019 SEL JCB

0 5 10

GRAPHIC SCALE

A. SEE DRAWING FP001 FOR ADDITIONAL GENERAL

NOTES.

1 THIS AREA REMAINS UNTOUCHED AND

SPRINKLERS SHALL REMAIN IN OPERATION

DURING CONSTRUCTION

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FP501

NEW FIRE PROTECTION SYSTEMS

EQUIPMENT MOUNTING DETAILS

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

CHECK

VALVE

PRESSURE

GAUGE

WATERFLOW

SWITCH

DRAIN

RISER

SPRINKLER RISER

INSPECTOR’S

TEST AND DRAIN

CONNECTION

TO

SPRINKLER

SYSTEM

INDICATING-TYPE FLOOR

CONTROL VALVE WITH

SUPERVISORY SWITCH

SPRINKLER FLOOR

CONTROL VALVE DETAIL

SPRINKLER BRANCH

LINE DETAIL

SPRINKLER FLEXHEAD

BRANCH LINE DETAIL

PIPE RING

CONCRETE ANCHOR

ALL THREAD ROD

DRILLED CONCRETE

HANGER DETAIL

SPRINKLER PIPE

SEMI-RECESSED PENDENT

SPRINKLER HEAD

UPRIGHT

SPRINKLER HEAD 7

DRY SIDEWALL SPRINKLER HEAD

LONGITUDINAL SWAY BRACE

WITH NON-THREADED FITTINGS

LATERAL SWAY BRACE

WITH NON-THREADED FITTINGS

Sprinkler branch line

FlexHead sprinkler drop

Ceiling grid mounting bracket Adjustable hub

Suspended t-bar grid

Sprinkler head

(not included)

Ceiling tile

SPRINKLER HEAD

WITH GUARD

AIR RELEASE VALVE

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS

321 4 5 6 7 8 9 10

MECHANICAL/ELECTRICAL ENGINEER

Sanders Engineering, Inc.

604 Hwy. 80 W., Suite J Clinton, MS 39056

FIRE PROTECTION ENGINEER

SafeMark, LLC 1852 Century Place Atlanta, GA 30345

IN ASSOCIATION WITH

CONSTRUCTION

DOCUMENTS

V P u b l i c R

E V

I T

V

A C

L C b c a b u n a c b e j a r c h c o m r v t

A

M

FP502

NEW FIRE PROTECTION SYSTEMS

DETAILS

RENOVATE 1st FLOOR CLC

VAMC - JACKSON, MS

586-18-103

11/01/2019Revisions: Date: SEL JCB

System No. C-AJ-1291

SECTION A-A

CA

J 1

1. Floor or Wall Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 30-7/8 in. (784 mm).

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Through-Penetrant — One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe or conduit and periphery of opening shall be min 0 in. to max 7/8 in. (22 mm). Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be used:

A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.

C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.

E. Conduit — Nom 6 in. (152 mm) diam (or smaller) steel conduit.

F. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT).

3. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between pipe and concrete, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/pipe interface on the top surface of floor and on both surfaces of wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

A

Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.

January 07, 2015

A

C

CL

ASS I F I ED

Classified by Underwriters Laboratories, Inc.

to UL 1479 and CAN/ULC-S115

US

Hilti Firestop Systems

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F Rating — 2 Hr F Rating — 2 Hr

T Rating — 0 Hr FT Rating — 0 Hr

FH Rating — 2 Hr

FTH Rating — 0 Hr

Hilti Firestop Systems

System No. W-L-1054

SECTION A-A

W L

A

Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.

October 14, 2015

A

1A

2 1B

C

CL

ASS IF IED

Classified by Underwriters Laboratories, Inc.

to UL 1479 and CAN/ULC-S115

US

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F Ratings —1 and 2 Hr (See Items 1 and 3) F Ratings — 1 and 2 Hr (See Items 1 and 3)

T Rating — 0 Hr FT Rating — 0 Hr

L Rating at Ambient — Less Than 1 CFM/sq ft FH Ratings —1 and 2 Hr (See Items 1 and 3)

L Rating at 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr

L Rating at Ambient — Less Than 1 CFM/sq ft

L Rating at 400 F — Less Than 1 CFM/sq ft

Hilti Firestop Systems Page: 2 of 2Page: 1 of 2

W L

54System No. W-L-1054

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152

mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.

The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly.

2. Through-Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit.

D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.

E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe.

3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall.

At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.

October 14, 2015

File details come from the government source that posted it. Updated .