P01-SOW Package_CLC FIRE PROTECTION.pdf
PDF 3 MB Posted
- Attached to
- Y1DZ--"Renovate 1st Floor Community Living Center" at G. V. (Sonny) Montgomery VAMC in Jackson, MS.
- Solicitation number
- 36C25620R0055
About this file
This solicitation requests proposals to renovate the first floor of the Community Living Center at the G.V. (Sonny) Montgomery VA Medical Center in Jackson, Mississippi. Contractors shall provide all labor, materials, equipment, transportation and supervision to complete the renovation. The solicitation includes attachments with instructions, important dates, a statement of work and specifications. Proposals are due by [date redacted] and the contract is expected to be awarded by [date redacted]. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is the contracting agency. The renovation scope includes demolition of existing fire alarm systems, sprinkler piping and installation of new systems throughout the first floor in accordance with attached drawings and specifications.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FA001
NEW FIRE ALARM SYSTEMS
GENERAL NOTES
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
1. CONTRACTOR SHALL MAINTAIN AND RESTORE ALL CONDUITS AND CONDUCTORS PASSING THROUGH THE RENOVATED AREAS
SERVICING OTHER UNDISRUPTED AREAS.
2. CONTRACTOR TO REMOVE ALL ACCESSIBLE WIRING OR CAP AND LABEL JUNCTION BOXES FOR RE-USE IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE.
3. EXISTING EQUIPMENT SUCH AS WIRING, DEVICES, CONDUITS, ETC. SHALL BE COMPLETELY REMOVED. CUT/CAP CONDUITS AT THE
AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT
PROTECTIVE DEVICES AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
4. THE CONTRACTORS SHALL USE ACTUAL FIELD MEASUREMENT VERIFIED WHILE ON SITE. NOTIFY THE ARCHITECT/ENGINEER
PROJECT MANAGER IF ANY DISCREPANCIES ARE FOUND PRIOR TO PROCEEDING WITH WORK.
5. FIRESTOPPING OF ALL PENETRATIONS IN RATED WALLS SHALL BE PROVIDED .
6. CONDUIT SHALL BE INSTALLED AND CONCEALED IN FINISHED AREA(S) UNLESS NOTED OTHERWISE.
7. COORDINATE FINAL INSTALLATION AND LOCATION OF FIRE ALARM CONTROL PANELS, VOICE EVACUATION PANELS, REMOTE
ANNUNCIATOR PANELS, AND DEVICES WITH ARCHITECTURAL ELEVATIONS, THE CONTRACTOR, ARCHITECT/ENGINEER PROJECT
MANAGER PRIOR TO ROUGH IN.
8. PROVIDE A COMPLETE AND OPERATIONAL FIRE ALARM SYSTEM WITH VOICE EVACUATION INCLUDING ALL MODULES, RELAYS, COMPONENTS, WIRING, PROGRAMMING AND CONNECTIONS.
9. EACH FIRE ALARM CONTROL PANEL, VOICE EVACUATION PANEL OR REMOTE POWER SUPPLY SHALL BE FED FROM A DEDICATED
BRANCH CIRCUIT AND PERMANENTLY IDENTIFIED AT THE CONTROL UNIT. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED
MARKING AND NOT DAMAGE OR OBSCURE THE OVERCURRENT PROTECTIVE DEVICE. WHERE A CIRCUIT BREAKER IS THE
DISCONNECTING MEANS AN APPROVED BREAKER LOCKING DEVICE SHALL BE INSTALLED.
10. PROVIDE SECONDARY (STANDBY) POWER PER NFPA 72 TO OPERATE THE FIRE ALARM SYSTEM/MASS NOTIFICATION SYSTEM UNDER
SUPERVISORY CONDITIONS FOR 24 HOURS AND ALL ALARM DEVICES FOR AN ADDITIONAL 15 MINUTES AT THE MAXIMUM
CONNECTED LOAD.
11. VOICE INTELLIGIBILITY: CONTRACTOR TO ENSURE THAT A CIS VALUE OF 0.7 OR GREATER IS PROVIDED IN EACH AREA WHERE THE
BUILDING OCCUPANTS COULD TYPICALLY BE FOUND.
12. THE INSTALLING CONTRACTOR IS RESPONSIBLE FOR LABELING ALL CIRCUITS THAT SERVE FIRE PROTECTION EQUIPMENT AT THE
RESPECTIVE ELECTRICAL POWER PANEL.
13. CIRCUITS THAT FEED FIRE PROTECTION EQUIPMENT SHALL BE MARKED AT THE EQUIPMENT SERVED AND MUST BE IDENTIFIED ON
THE AS-BUILT MARK UP OF FIRE ALARM DRAWINGS.
14. PULL ALL CONDUCTORS SPLICE FREE; CONDUCTORS MUST BE CONTINUOUS FROM DEVICE TO DEVICE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS PROHIBITED.
15. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP OR THE DEVICE SCREW TERMINALS. TERMINAL STRIPS ARE ONLY PERMITTED
WHERE DIRECT CONNECTION TO A DEVICE IS NOT POSSIBLE.
16. RUN ALL WIRING TO AND WITHIN CONTROL PANELS IN THE VERTICAL OR HORIZONTAL PLANE, MAKE ALL TURNS AT 90 DEGREE
ANGLES, AND TIGHTLY BUNDLE, WRAP, AND IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. CONDUCTOR
MARKINGS MUST BE PRINTED LABELS, PERMANENTLY AFFIXED TO THE CONDUCTOR VIA SHRINK WRAP.
17. MARK INCOMING CABLES TO EACH DEVICE. IDENTIFY THE CIRCUIT NUMBER AT ALL TERMINATIONS.
18. ALL CONDUCTORS MUST BE INSTALLED IN CONDUIT (EMT MINIMUM). CONDUIT SIZING AND ROUTING IS THE RESPONSIBILITY OF THE
FIRE ALARM CONTRACTOR.
19. FIRE ALARM CONTRACTOR SHALL PROVIDE CONDUIT FILL CALCULATIONS IN ACCORDANCE WITH NFPA 70.
20. NOTIFICATION APPLIANCE CIRCUITS SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT EDITION. MINIMUM
WIRING SIZE SHALL BE 16 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM NOTIFICATION APPLIANCE CIRCUITS.
21. SIGNALING LINE CIRCUIT (SLC) SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT ADDITION. MINIMUM
WIRING SIZE SHALL BE 18 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM SIGNALING LINE CIRCUITS.
22. INITIATING DEVICE CIRCUITS (IDC) SHALL CONFORM TO CLASS B, REQUIREMENTS AS PER NFPA-72 CURRENT ADDITION. MINIMUM
WIRING SIZE SHALL BE 16 AWG AND BE APPROVED/SUITABLE FOR FIRE ALARM INITIATING DEVICE CIRCUITS.
23. ALL WIRING SHALL BE PLENUM RATED AND SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED.
24. DETECTORS SHALL NOT BE LOCATED WHERE AIR FROM HVAC SUPPLY DIFFUSERS COULD DILUTE SMOKE BEFORE IT REACHES THE
DETECTORS. DETECTORS SHALL NOT BE INSTALLED WITHIN 3 FEET (1 METER) OF AIR SUPPLY GRILLES OR DIFFUSERS.
25. DETECTORS SHALL BE LOCATED ON THE CEILING SO THEY ARE VISIBLE AND ACCESSIBLE FROM THE FLOOR LEVEL FOR
MAINTENANCE AND TESTING OF THE DEVICES.
26. DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL.
DETECTORS THAT HAVE BEEN INSTALLED DURING CONSTRUCTION AND FOUND TO HAVE A SENSITIVITY OUTSIDE THE LISTED AND
MARKED SENSITIVITY RANGE SHALL BE REPLACED AS OUTLINED IN NFPA 72.
27. POWER LIMITED CIRCUITS SHALL NOT BE PLACED IN THE SAME CONDUIT, ENCLOSURE, OR RACEWAY WITH NON-POWER LIMITED
CIRCUITS. POWER LIMITED CIRCUITS SHALL BE ISOLATED FROM NON-POWER LIMITED CIRCUITS, ELECTRIC LIGHTS, OR POWER
CIRCUITS BY A MINIMUM OF 2 INCHES.
28. ALL STROBE NOTIFICATION APPLIANCES SHALL BE SYNCHRONIZED IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 72.
FLASHING BUILDING ALARM NOTIFICATION STROBES SHALL BE SYNCHRONIZED WHERE COLLOCATED IN THE SAME FIELD OF VIEW
OR SPACE.
29. UPON OPERATION OF A FIRE ALARM INITIATING DEVICE, THE FIRE ALARM WILL ACTIVATE NOTIFICATION APPLIANCES IN THE ZONE
OF ALARM ORIGIN ONLY. SIMULTANEOUSLY THE FIRE ALARM SYSTEM WILL SEND A VOICE MESSAGE TO THE REST OF THE BUILDING
AND OTHER BUILDINGS AS NECESSARY TO NOTIFY ENOUGH STAFF TO RESPOND TO THE ZONE OF ALARM ORIGIN. NO VISIBLE
APPLIANCES WILL BE ACTIVATED OUTSIDE OF THE ZONE OF ALARM ORIGIN.
30. SMOKE ALARM NOTIFICATION APPLIANCES SHALL BE LOCATED IN RESIDENT SLEEPING ROOMS AND ACTIVATE A LOCAL ALARM UPON
DETECTION OF SMOKE. SMOKE ALARM SOUNDER SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT
SOUND LEVEL OR 5 dB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND LEVEL OF
AT LEAST 75 dBA, WHICHEVER IS GREATER, MEASURED AT THE PILLOW LEVEL. SMOKE ALARM SOUNDER BASES SHALL BE LISTED
FOR PRODUCING A LOW-FREQUENCY 520Hz WAVEFORM.
31. CONTRACTOR TO COORDINATE FIRE ALARM ZONES WITH SMOKE COMPARTMENTS AND SPRINKLER ZONES.
32. CONTRACTOR TO COORDINATE WITH FACILITIES MANAGER AREA REPORTING FOR INITIATING DEVICE ACTIVATION.
33. SMOKE ALARM DEVICE ACTIVATION SHALL REPORT ALARM CONDITION TO LOCAL FIRE ALARM CONTROL PANEL & ANNUNCIATOR.
SMOKE ALARM SHALL INITIATE A LOCAL AUDIBLE ALARM AND ACTIVATE LOCAL VISIBLE APPLIANCE ONLY.
34. BUILDINGS SHALL COMMUNICATE TROUBLE, SUPERVISORY, AND ALARM SIGNALS TO A DESIGNATED 24-HOUR STAFFED LOCATION.
35. SEE FIRE PROTECTION DRAWING FP502 FOR PENETRATION DETAILS.
FIRE ALARM GENERAL NOTES
DEVICE LEGEND
SYMBOL DESCRIPTION
FIRE ALARM CONTROL PANEL (EXISTING)
NAC AND AUX POWER SUPPLY
FIRE ALARM ANNUNCIATOR
MANUAL PULL STATION
PHOTOELECTRIC SMOKE DETECTOR
STROBE, WALL MOUNT
STROBE, CEILING MOUNT
TAMPER SWITCH
WATERFLOW SWITCH
AMPLIFIER CABINET
SPEAKER, CEILING MOUNT
SS
PHOTOELECTRIC SMOKE ALARM WITH 520Hz SOUNDER BASE
MAGNETIC DOOR HOLDER
SPEAKER/STROBE, CEILING MOUNT
MONITOR MODULE
CONTROL MODULE
FIRE ALARM TERMINAL CABINET
RELAY MODULE
KEY BYPASS SWITCH WITH INDICATOR LAMP
RATE OF RISE & FIXED TEMPERATURE HEAT DETECTOR
S
DUCT MOUNTED SMOKE DETECTOR
DN DN
DN
A B C D E F H J K L M N O P R S T U V WG
F
SS
F
F
F
SS
SSSS
SS
S
S
S
S
S
S
S
S
SSSS SS
SSSSSS
SS
SSSSSSSSSS
SS
SS SS SS SS SS
S
S
S
S
SSS
S
FA101
A
S S
S
S
Bedroom
H-144
Bedroom
H-139
Bedroom
H-138
Bedroom
H-134
Bedroom
H-133
Bedroom
H-146
Bedroom
H-141
Bedroom
H-140
Bedroom
H-135
Bedroom
H-132
Bedroom
H-153
Bedroom
H-154
Bedroom
H-159
Bedroom
H-160
Bedroom
H-165
Bedroom
H-166
Bedroom
H-162
Bedroom
H-161
Bedroom
H-156
Bedroom
H-155
Clean Utility
H-152
Soiled Utility
H-151
Bath Suite
H-131
Medicine Stor.
H-128
Oxygen Storage
H-116
House Keeping
H-115
Office
H-114
Family Lounge
H-129
Office
H-113
Office
H-112
Staff Lounge
H-111
Office
H-110
Shared Office
H-109
Shared Office
H-107
Bedroom
H-145
Conference
H-102
Locker Room
H-100
Toilet
H-100A
Toilet
H-100B
Laundry
H-117
Storage/Linen
Storage
H-118
Toilet
H-145.1
Toilet
H-144.1
Toilet
H-139.1
Toilet
H-138.1
Toilet
H-134.1
Toilet
H-133.1
Toilet
H-146.1
Toilet
H-141.1
Toilet
H-140.1
Toilet
H-135.1
Toilet
H-132.1
Toilet
H-155.1
Toilet
H-156.1
Toilet
H-161.1
Toilet
H-162.1
Toilet
H-166.1
Toilet
H-153.1
Toilet
H-154.1
Toilet
H-159.1
Toilet
H-160.1
Toilet
H-165.1
Toilet
H-150.1
Bariatric Bedroom
H-130
Toilet
H-130.1
Bariatric Bedroom
H-150
Telecom Closet
H-125
Closet
H-120
Kitchen
H-121
Public Toilet
H-119
Corridor
H-105.4
Corridor
H-105.3
Stair #2
H-002
Stair #3
H-003
Restorative
Therapy
H-104
Elec.
H-106
OT Office
H-101.1
Occupational
Therapy
H-101
PT Office
H-103.1
Physical Therapy
H-103
Staff Stor.
H-108
ADL
H-101.3
Living
H-124
Living
H-122
Ward Nurse
H-127
Waiting
H-126
Corridor
H-105
Stair #1
H-001
Elec.
H-142
Storage
H-143
Storage
H-137
Storage
H-164
Storage
H-163
Elec.
H-157
Alcove
H-158
Alcove
H-136
Recreation/Dining/Events
H-123
Corridor
H-105
Storage
H-101.2
W/C & Walker
Storage
H-105.2
Corridor
H-105.1
FA501
FA501
FA501
FA501
FA501
FA501
FA501
FA501
FA502
FA502
S
Telecom Closet
H-125
FA501
DN
STAIR
CONFERENCE
N O P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FA101
NEW FIRE ALARM SYSTEMS
PLAN - FIRST FLOOR
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019
1/8" = 1'-0"
FA101
FIRST FLOOR - NEW LAYOUT
Revisions: Date: SEL JCB
A. SEE FA001 FOR ADDITIONAL GENERAL NOTES
B. EXISTING FIRE ALARM SYSTEM EQUIPMENT,
CONDUCTORS, RACEWAYS, NOTIFICATION
APPLIANCES AND INITIATING DEVICES ON THE
FIRST FLOOR OF THE CLC ARE TO BE REMOVED
AND REPLACED WITH NEW.
C. NEW FIRE ALARM SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 72.
D. THE NEW NOTIFICATION APPLIANCE POWER
SUPPLIES AND AMPLIFIER PANELS SHALL BE
CONNECTED TO THE FIRE ALARM CONTROL
PANEL AND CAPABLE OF REPORTING TO
EMERGENCY RESPONDERS.
E. FIRE ALARM SYSTEM TO PROVIDE HVAC UNIT
SMOKE DETECTION AND AUTOMATIC SHUTDOWN
OF ELEVATOR RECALL FUNCTIONS.
F. SMOKE ALARM DEVICES LOCATED IN SLEEPING
ROOMS SHALL BE PRODUCE A SQUARE
WAVEFORM WITH A FREQUENCY OF 520 Hz.
G. STROBES ARE ONLY TO BE ACTIVATED IN THE
ZONE OF ALARM ORIGIN.
1 FIRE SUPPRESSION TAMPER SWITCH TO BE
MONITORED BY FIRE ALARM CONTROL PANEL.
2 FIRE SUPPRESSION WATERFLOW SENSOR TO BE
MONITORED BY FIRE ALARM CONTROL PANEL.
3 SLEEPING ROOMS SHALL BE EQUIPPED WITH A
STROBE THAT IS SET TO 110CD AND LOCATED NO
LESS THAN 24 INCHES FROM THE TOP OF THE
LENSES TO THE FINISHED CEILING.
4 LOCATE STROBE NO MORE THAN 16'-0" AWAY
FROM THE PILLOW.
5 LOCATE SMOKE DETECTOR NO MORE THAN 21'-0"
FROM CENTERLINE OF EACH ELEVATOR DOOR.
6 LOCATE SMOKE DETECTOR NO LESS THAN 36 IN.
HORIZONTALLY FROM AN AIR SUPPLY REGISTER.
7 PROVIDE ADDITIONAL NOTIFICATION APPLIANCE
CIRCUIT POWER SUPPLIES FOR STROBE
NOTIFICATION APPLIANCES & LOW-VOLTAGE
SMOKE DETECTOR SOUNDER BASES.
8 EXISTING FIRE ALARM CONTROL PANEL TO BE
DEMOLISHED. NEW FIRE ALARM CONTROL PANEL
TO BE LOCATED ON GROUND LEVEL IN
MECHANICAL ROOM G132.1.
9 LOCATE HEAT DETECTOR NO MORE THAN
24-INCHES FROM SPRINKLER HEAD. COORDINATE
LOCATION OF SMOKE DETECTOR WITH FIRE
PROTECTION CONTRACTOR.
0 5 10
GRAPHIC SCALE
1/4" = 1'-0"
FA101
A
TELECOM CLOSET H125 - ENLARGEMENT DETAIL
0 5 10
GRAPHIC SCALE
1/8" = 1'-0"
FA101
FIRST FLOOR - DEMOLITION LAYOUT
0 5 10
GRAPHIC SCALE
A B C D E F H J K L M N O P R S T U V WG
U P
PENTHOUSE
P001
MACHINE
PLATFORM
KNOCK OUT
SLAB FOR
FUTURE
ELEVATORS
S
S
F
FA501
FA501
FA501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FA102
NEW FIRE ALARM SYSTEMS
PLAN - ROOF
RENOVATE ROOF CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019
1/8" = 1'-0"
FA102
ROOF LEVEL - NEW LAYOUT
Revisions: Date: SEL JCB
1 MOUNT EMERGENCY CONTROL FUNCTION RELAY
MODULE WITHIN 36-INCHES FROM ELEVATOR
CONTROLLER.
0 5 10
GRAPHIC SCALE
A. SEE FA001 FOR ADDITIONAL GENERAL NOTES
B. EXISTING FIRE ALARM SYSTEM EQUIPMENT,
CONDUCTORS, RACEWAYS, NOTIFICATION
APPLIANCES AND INITIATING DEVICES ON THE
FIRST FLOOR OF THE CLC ARE TO BE REMOVED
AND REPLACED WITH NEW.
C. NEW FIRE ALARM SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 72.
D. THE NEW NOTIFICATION APPLIANCE POWER
SUPPLIES AND AMPLIFIER PANELS SHALL BE
CONNECTED TO THE FIRE ALARM CONTROL
PANEL AND CAPABLE OF REPORTING TO
EMERGENCY RESPONDERS.
E. FIRE ALARM SYSTEM TO PROVIDE HVAC UNIT
SMOKE DETECTION AND AUTOMATIC SHUTDOWN
OF ELEVATOR RECALL FUNCTIONS.
F. SMOKE ALARM DEVICES LOCATED IN SLEEPING
ROOMS SHALL BE PRODUCE A SQUARE
WAVEFORM WITH A FREQUENCY OF 520 Hz.
G. STROBES ARE ONLY TO BE ACTIVATED IN THE
ZONE OF ALARM ORIGIN.
UPUP
UPUP
DN
DN
UP
UP
A
A
B
B
C
C
D
D E
F
F G J M O P
R
S
T
T
U
U
V
V
W
W
EXISTING FITNESS CENTER
(TO BE REPLACED BEFORE PROJECT BEGINS)
(EXISTING)
AR-14
AR-12AR-12
EQ-03
EQ-03
AR-05
L
AR-60
AR-01
EWC
AR-01
AR-01
AR-01
AR-01
AR-30L
AR-01
AR-59 AR-59
AR-17
Bedroom
G148
SIM.G165
Bedroom
G149
SIM.G165
Bedroom
G150
SIM.G165
Bedroom
G151
SIM.G165
Bedroom
G152
SIM.G165
Bedroom
G153
SIM.G165
Bedroom
G142
SIM.G165
Bedroom
G143
SIM.G165
Bedroom
G144
SIM.G165
Bedroom
G145
SIM.G165
Bedroom
G146
SIM.G165
Bedroom, Bariatric
G141
SIM.G161
Bath Suite
G154
Bedroom, Bariatric
G161
Soiled Utility
G174
Clean Utility
G173
Bedroom
G172
SIM.G165
Bedroom
G171
SIM.G165
Bedroom
G170
SIM.G165
Bedroom
G169
SIM.G165
Bedroom
G168
SIM.G165
Bedroom
G166
SIM.G165
Bedroom
G165
Bedroom
G164
SIM.G165
Bedroom
G163
SIM.G165
Bedroom
G162
SIM.G165
Office
G123
Family
Lounge
G107
Medicine
Storage
G106
Telecom
Closet
G113
Conference
G131
Staff Lounge
G126
Office
G127
Office
G128
Mechanical
(E)
G132
Mechanical
(E)
G132.1
Concierge
Station
G105
Sitting Area
G104
Multi-Purpose
Area
G112
Laundry
G109
Shared Office
G129
Toilet
G148.1
SIM.G165.1
Toilet
G149.1
SIM.G165.1
Toilet
G150.1
SIM.G165.1
Toilet
G151.1
SIM.G165.1
Toilet
G152.1
SIM.G165.1
Toilet
G153.1
SIM.G165.1
Toilet
G146.1
SIM.G165.1
Toilet
G145.1
SIM.G165.1
Toilet
G144.1
SIM.G165.1
Toilet
G143.1
SIM.G165.1
Toilet
G142.1
SIM.G165.1
Toilet
G141.1
SIM.G161.1
Toilet
G166.1
SIM.G165.1
Toilet
G165.1
Toilet
G164.1
SIM.G165.1
Toilet
G163.1
SIM.G165.1
Toilet
G162
SIM.G165.1
Toilet
G161.1
Storage
G140.1
Corridor
G140
Corridor
G160
Stairs
G167
Stairs
G147
Stairs
G133
Lobby
G103
Oxygen
Storage-
Empty
G121
Storage
G140.2
Elec
G160.2
Storage
G160.4
Alcove
G160.5
Toilet
G172.1
SIM.G165.1
Toilet
G171.1
SIM.G165.1
Toilet
G170.1
SIM.G165.1
Toilet
G169.1
SIM.G165.1
Toilet
G168.1
SIM.G165.1
Foyer
G101
Lobby
G103
Vestibule
G100
Elevator
C1-G
Elevator
C2-G
Locker Room
G130
Toilet
G130.2
Toilet
G130.1
Elec
G120.1
Storage/Linen
Storage
G110
Kitchen
G111
House
Keeping
G122
Alcove
G140.5
Elec Closet
G140.4
Storage
G140.3
Storage
G160.3
Office
G124
Multi-Purpose
Area
G102
Oxygen
Storage - Full
G121.1
Public Toilet
G108
Corridor
G175
Office
G125
Closet
G114
S
FA501
FA501
FA502
FA501
FA501
FA501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FA103
NEW FIRE ALARM SYSTEMS
PLAN - LOWER LEVEL
RENOVATE GROUND FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019
1/8" = 1'-0"
FA103
LOWER LEVEL - NEW LAYOUT
Revisions: Date: SEL JCB
A. SEE FA001 FOR ADDITIONAL GENERAL NOTES
B. FIRE ALARM SYSTEM EQUIPMENT, CONDUCTORS,
RACEWAYS, NOTIFICATION APPLIANCES AND
INITIATING DEVICES ON THE LOWER LEVEL OF
THE CLC ARE TO BE INSTALLED UNDER SEPARATE
CONTRACT UNLESS OTHERWISE NOTED.
C. NEW FIRE ALARM SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 72.
1 PROVIDE NEW FIRE ALARM CONTROL PANEL
LOCATED IN MECHANICAL ROOM G132.1.
2 PROVIDE AMPLIFIER CABINET FOR NEW SPEAKER
NOTIFICATION APPLIANCES.
3 PROVIDE SMOKE DETECTOR ABOVE FIRE ALARM
CONTROL PANEL.
4 PROVIDE FIRE ALARM TERMINAL CABINET. VERIFY
FIRE ALARM TERMINAL CABINET LOCATION WITH
OWNERS REPRESENTATIVE.
0 5 10
GRAPHIC SCALE
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
FA501
NEW FIRE ALARM SYSTEMS
EQUIPMENT DETAILS
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
FLUSH MOUNTED
REMOTE ANNUNCIATOR PANEL
SURFACE MOUNTED
FIRE ALARM CONTROL PANEL
SURFACE MOUNTED
VOICE EVACUATION PANEL
FLUSH MOUNTED
SMOKE/HEAT DETECTOR
FLUSH MOUNTED PULL STATION
SURFACE MOUNTED
MONITOR MODULE
SURFACE MOUNTED
CONTROL/RELAY MODULE
SURFACE MOUNTED
NOTIFICATON APPLIANCE
CIRCUIT PANEL
FLUSH MOUNTED
SMOKE ALARM DETECTOR
A
M
WALL MOUNTED (SURFACE)
SPEAKER/STROBE
WALL MOUNTED (FLUSH)
STROBE ONLY
CEILING MOUNTED (FLUSH)
STROBE ONLY
CEILING MOUNTED (FLUSH)
SPEAKER/STROBE
WALL MOUNTED (FLUSH)
SLEEPING ROOM
STROBE NOTIFICATION APPLIANCE
64 POINT FIRE
ALARM TERMINAL CABINET
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
FA502
NEW FIRE ALARM SYSTEMS
EQUIPMENT DETAILS
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
DUCT MOUNTED
SMOKE DETECTOR
A
M
64 POINT FIRE
ALARM TERMINAL CABINET
HVAC SUPPLY AND RETURN
DETECTION AND SHUTDOWN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FA601
NEW FIRE ALARM SYSTEMS
RISER DIAGRAM AND MATRIX
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
S
FIRE ALARM & VOICE EVACUATION
NOTIFICATION SYSTEM RISER DIAGRAM
BUILDING FIRE ALARM FUNCTIONS
I N
P U
T S
OUTPUTS
AREA SMOKE DETECTOR ACTIVATION
D
IS
P
LA
Y A
LA
R
M M
E S
S A
G E
A T
FA
C
P A
N D
R E
M O
TE
F
A A
P
D
IS
P
LA
Y
TR
O U
B
LE
M E
S S
A G
E A
T
FA
C P
A N
D R
E M
O
TE
F A
A P
D
IS
P
LA
Y S
U P
E R
VI
S
O R
Y M
E S
S A
G E
A T
FA
C
P A
N D
R E
M O
TE
F
A A
P
A C
TI
VA
TE
P
R E
-R E
C O
R D
E D
F
IR
E A
LA
R
M M
E S
S A
G E
F
IR
E
A
LA
R M
S
TR
O B
E S
IN
Z
O N
E O
F A
C
TI
VA
TI
O N
S E
N D
A
LA
R M
S
IG
N A
L
TO
C E
N
TR
A L
S
TA
TI
O
N M
O N
IT
O
R
IN
G S
TA
TI
O N
S E
N D
T R
O U
B
LE
S
IG
N A
L
TO
C E
N
TR
A L
S
TA
TI
O
N M
O N
IT
O
R
IN
G S
TA
TI
O N
S E
N D
S U
P E
R
VI
S O
R Y
S
IG
N A
L
TO
C E
N
TR
A L
S
TA
TI
O
N M
O N
IT
O
R
IN
G S
TA
TI
O N
R E
C O
R D
E
VE
N
TS
IN
S
YS
TE
M H
IS
TO
R Y
M E
M O
R Y
A C
TI
VA
TE
O
U
TS
ID
E
W A
TE
R
FL
O
W B
E
LL
NOTIFICATION
A B C D E F G H P Q
MANUAL PULL STATION ACTIVATION
SPRINKLER TAMPER SWITCH ACTIVATION
SPRINKLER WATERFLOW SWITCH ACTIVATION
SYSTEM AC POWER FAILURE
SYSTEM LOW BATTERY
OPEN CIRCUIT
GROUND FAULT
WIRE-TO-WIRE SHORT NOTIFICATION APPLIANCE CIRCUIT (NAC)
WIRE-TO-WIRE SHORT SIGNALING LINE CIRCUIT (SLC)
PANEL
REPORTING
CENTRAL
STATION
FACP
CONTROL
FIRE ALARM & VOICE EVACUATION
NOTIFICATION OPERATIONAL MATRIX
F
IN ROOM SMOKE ALARM ACTIVATION
P R
IN
T
E
VE
N T
A T
TH
E
F
IR
E A
LA
R
M C
O N
TR
O
L P
A N
E L
P R
IN
TE
R
A C
TI
VA
TE
L
O C
A L
S O
U N
D E
R B
A S
E A
N D
L O
C A
L S
TR
O
B E
N O
TI
FI
C A
TI
O
N A
P P
LI
A
N C
E
A C
TI
VA
TE
P
R E
-R E
C O
R D
E D
F
IR
E A
LA
R
M M
E S
S A
G E
F A
C
IL
IT
Y
W
ID
E (C
O O
R D
IN
A
TE
W
IT
H
F A
C
IL
IT
IE
S M
A N
A G
E R
SS
R E
LE
A
S E
M A
G N
E
TI
C A
LL
Y
H E
LD
O
P E
N D
O O
R S
S
1 STROBE NOTIFICATION APPLIANCES SHALL BE
SYNCHRONIZED WITH FIRE ALARM CONTROL
PANEL ON LOWER LEVEL.
2 EXISTING FIRE ALARM CONTROL PANEL TO BE
REMOVED
3 NEW FIRE ALARM CONTROL PANEL TO BE
LOCATED ON GROUND LEVEL IN MECHANICAL
ROOM G132.1.
4 DEMOLISH FIRE ALARM CIRCUITS AND CONNECT
TO NEW FIRE ALARM CIRCUIT WHEN EXISTING
FIRE ALARM CONTROL PANEL ON LEVEL ONE IS
DECOMMISSIONED.
DOOR RELEASE SMOKE DETECTOR
O P
E N
L O
C K
E D
E G
R E
S S
D O
O R
S O
N F
LO
O
R O
F
FI
R E
O R
IG
IN
ELEVATOR MACHINE ROOM HEAT DETECTOR
IN
IT
IA
TE
E
LE
VA
TO
R S
H U
T D
O W
N A
N D
D
IS
C O
N N
E C
T E
LE
VA
TO
R
P O
W E
R
TOP OF SHAFT ELEVATOR HEAT DETECTOR
TOP OF SHAFT ELEVATOR SMOKE DETECTOR
IN
IT
IA
TE
E
LE
VA
TO
R R
E C
A
LL
T O
P R
IM
A
R Y
LE
VE
L O
F E
G R
E S
S D
IS
C
H A
R G
E
IN
IT
IA
TE
E
LE
VA
TO
R R
E C
A
LL
T O
A
LT
E R
N A
TE
L
E
VE
L O
F E
G R
E S
S D
IS
C
H A
R G
E
SMOKE DETECTOR IN ELEVATOR LOBBY (UPPER LEVEL)
SMOKE DETECTOR IN ELEVATOR LOBBY (LOWER LEVEL)
ELEVATOR MACHINE ROOM SMOKE DETECTOR
ELEVATOR SHUNT-TRIP KEY BYPASS ACTIVATION
ELEVATOR LOSS OF POWER
IL
LU
M
IN
A
TE
E
LE
VA
TO
R S
H U
N T
B
YP
A S
S
IN
D
IC
A
TO
R L
A M
P
S
S
DUCT MOUNTED SMOKE DETECTOR ACTIVATION
IN
IT
IA
TE
A
IR
H A
N D
LE
R
S H
U
TD
O W
N
I J K L M N O R S
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FP001
NEW FIRE PROTECTION SYSTEMS
GENERAL NOTES
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
1. PROVIDE FULLY AUTOMATIC WET PIPE FIRE SPRINKLER SUPPRESSION SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.
2. CONTRACTOR SHALL SUBMIT FABRICATION DRAWINGS FOR REVIEW AND APPROVAL BY THE FIRE PROTECTION ENGINEER PRIOR TO
COMMENCEMENT OF WORK.
3. THE CONTRACTORS SHALL USE DIMENSIONS WHERE INDICATED ON THE DRAWINGS AND COMPARE WITH ACTUAL FIELD MEASUREMENT.
CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER PROJECT MANAGER IF ANY DISCREPANCIES ARE FOUND PRIOR TO PROCEEDING WITH
WORK. DO NOT SCALE FROM DRAWINGS.
4. ANY CONFLICTS BETWEEN THE SPECIFICATION AND DRAWINGS SHALL BE SUBMITTED AS REQUEST FOR INFORMATION. CONTRACTOR SHALL
NOT PROCEED WITH ANY NEW WORK, EXCEPT AT THEIR OWN RISK UNTIL CLARIFICATIONS HAVE BEEN ISSUED BY THE ARCHITECT / ENGINEER
PROJECT MANAGER.
5. FIRE SPRINKLER SYSTEM ABOVE GROUND PIPING SHALL BE STANDARD WEIGHT SCHEDULE 10 OR SCHEDULE 40 BLACK STEEL PIPE COMPLYING
WITH ASTM A135 AND ASTM A795. SPRINKLER SYSTEM PIPING SHALL BE APPROVED BY FACTORY MUTUAL FOR USE IN FIRE SUPPRESSION
SYSTEMS.
6. FITTINGS SHALL BE CAST IRON CONFORMING TO ASME B16.4, STEEL CONFORMING TO ASME B16.9 OR ASME B16.11, OR MALLEABLE IRON
CONFORMING TO ASME B16.3. FITTINGS INTO WHICH SPRINKLERS, DROP NIPPLES OR RISER NIPPLES (SPRIGS) ARE SCREWED SHALL BE
THREADED TYPE. PLAIN-END FITTINGS WITH MECHANICAL COUPLINGS, FITTINGS THAT USE STEEL GRIPPING DEVICES TO BITE INTO THE PIPE
AND SEGMENTED WELDED FITTINGS SHALL NOT BE USED.
7. JOINTS AND FITTINGS SHALL BE DESIGNED FOR NOT LESS THAN 175 PSI SERVICE AND SHALL BE THE PRODUCT OF THE SAME MANUFACTURER;
SEGMENTED WELDED FITTINGS SHALL NOT BE USED. FITTING AND COUPLING HOUSES SHALL BE MALLEABLE IRON CONFORMING TO ASTM
A47/A47M, GRADE 32510; DUCTILE IRON CONFORMING TO ASTM A536, GRADE 65-45-12. GASKET SHALL BE THE FLUSH TYPE THAT FILLS THE
ENTIRE CAVITY BETWEEN THE FITTING AND THE PIPE. NUTS AND BOLTS SHALL BE HEAT-TREATED STEEL CONFORMING TO ASTM A183 AND
SHALL BE CADMIUM PLATED OR ZINC ELECTROPLATED.
8. PIPE THREADS, FITTINGS, FLANGES AND MECHANICAL COUPLINGS SHALL COMPLY WITH APPLICABLE ASME STANDARDS AS LISTED IN NFPA 13.
THREADS SHALL COMPLY WITH NATIONAL PIPE THREAD (NPT) STANDARDS.
9. FIRESTOPPING OF ALL PENETRATIONS IN RATED WALLS SHALL BE PROVIDED PER REQUIREMENTS OF ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
10. SPRINKLER PIPING SHALL BE CONCEALED ABOVE FINISHED CEILINGS WHERE PROVIDED.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WORK WITH ALL TRADES. CONFLICTS WHICH PROHIBIT PROPER INSTALLATION OF
THE SYSTEMS AS DESIGNED SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PROJECT MANAGER.
12. CONTRACTOR SHALL OBTAIN APPROVAL FROM THE OWNER PRIOR TO WELDING AND CUTTING OPERATIONS. HOT WORK PERMITS MUST BE
PROVIDED AND PROPER NOTICE RECEIVED PRIOR TO PERFORMING SUCH OPERATIONS IN BUILT AREAS.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND AVOIDING ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, STRUCTURAL MEMBERS, PIPES AND OTHER OBSTRUCTIONS ENCOUNTERED. COORDINATE LOCATIONS WITH ALL OTHER
SUBCONTRACTORS PERFORMING WORK. REFERENCE ARCHITECTURE REFLECTED CEILING PLANS FOR THE LOCATIONS OF LIGHT FIXTURES, CEILING FANS, DUCT WORK AND OTHER EQUIPMENT.
14. REFER TO STRUCTURAL, ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR LOCATIONS OF OTHER DISCIPLINE
EQUIPMENT AND REQUIRED CLEARANCES.
15. ALL WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED PENETRATIONS. CEILINGS AND FLOORS SHALL BE SEALED TO THE FULL
THICKNESS OF THE PENETRATION WITH APPROVED FIRE STOPPING MATERIALS OF EQUAL OR GREATER FIRE RESISTANCE TO THE PENETRATED
BARRIER SEE DETAILS ON DRAWING FP502.
16. ALL DAMAGE TO WALLS, CEILINGS, FLOORS OR ARCHITECTURAL FEATURES FROM PENETRATIONS, REMOVALS, INSTALLATIONS OR OTHER
ACTIONS OF THE CONTRACTOR SHALL BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS BY THE CONTRACTOR TO MATCH
ADJACENT WORK, WHETHER SPECIFICALLY NOTED OR NOT.
17. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, BENT OR BURNED WITHOUT PRIOR AUTHORIZATION FROM THE STRUCTURAL ENGINEER OF
RECORD. COORDINATE WITH STRUCTURAL FOR PIPE PENETRATION LOCATIONS TO BE PROVIDED IN STRUCTURAL MEMBERS.
18. ALL SPRINKLER HEADS SHALL BE PROTECTED DURING ANY PAINTING OR OTHER CONSTRUCTION ACTIVITIES WHICH MAY COAT THE SPRINKLER
HEADS WITH FINISH MATERIALS. PROTECT SPRINKLER HEADS USING BAGS, TAPE AND PLASTIC COVERINGS. MANUFACTURER SUPPLIED
SHIPPING COVERS ARE NOT ADEQUATE TO PREVENT PAINT ACCUMULATION ON HEADS. COVERINGS SHALL BE REMOVED PRIOR TO
ACCEPTANCE.
19. SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF ACOUSTICAL CEILING TILES WHERE PROVIDED. SPRINKLERS SHALL BE INSTALLED
WITHIN 1" VARIANCE IN EITHER DIRECTION.
20. COORDINATE LOCATIONS OF FLOW SWITCHES AND TAMPER SWITCHES WITH FIRE ALARM CONTRACTOR.
21. SPRINKLERS SHALL BE UL LISTED FM APPROVED CLOSED HEAD SPRINKLERS.
22. OWNER SHALL NOT BE RESPONSIBLE FOR DISPOSAL OF ANY MATERIALS OR CLEAN-UP OF THE CONSTRUCTION SITE. CONTRACTOR SHALL
DISPOSE OF ANY DEMOLISHED MATERIALS OR SCRAPS NOT FURNISHED AS PART OF THE NEW WORK.
23. ALL EXPOSED FIRE PROTECTION PIPING SHALL BE PAINTED RED UTILIZING LEAD-FREE PAINT.
24. SPRINKLER SYSTEM SHALL BE BRACED AND RESTRAINED IN ACCORDANCE TO THE SEISMIC REQUIREMENTS OF NFPA 13.
25. FIRE PROTECTION PIPING SHALL BE FURNISHED, INSTALLED AND TESTED PER NFPA 13, 2016 AND FM DATA SHEET 2-0. ALL PIPING SHALL BE
PRESSURE TESTED AT 200-PSI FOR TWO (2) HOURS WITH "NO" LEAKS. LEAKS SHALL BE REPAIRED BY TIGHTENING OR REPLACEMENT OF
FITTINGS. WRAPPING, CAULKING, OR OTHER MEANS SHALL NOT BE ALLOWED.
26. AUTOMATIC SPRINKLERS SHALL BE SCHEDULE 40 FOR ALL PIPE SIZES 1-1/2" AND SMALLER. ALL PIPING 2" AND LARGER CAN BE SCHEDULE 10 AS
LONG AS IT IS ROLL GROOVED.
FIRE SUPPRESSION GENERAL NOTES
HANGAR SCHEDULE
MAXIMUM HORIZONTAL DISTANCE BETWEEN PIPE HANGARS (ft-in)
NOMINAL PIPE DIAMETER (in.)
PIPING MATERIAL
1 1
2 2
3 3
4 > 4
STEEL PIPE NA 12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0
NOTES:
-HANGARS MUST BE INSTALLED A MINIMUM OF 3 in. IN THE HORIZONTAL DIRECTION FROM UPRIGHT SPRINKLERS.
-SEE DETAIL NUMBERS 8 & 9 ON SHEET FP501.
DEVICE LEGEND
= QUICK RESPONSE, 5.6 K, 155°F UPRIGHT FIRE SPRINKLER HEAD
= FIRE SUPPRESSION PIPE
= PIPE ELEVATION CHANGE - PIPE DROP SIZE DENOTED "DN"
= HYDRAULIC REFERENCE NODE
= PIPE END CAP OR BLIND FLANGE
= PIPE ELEVATION CHANGE - PIPE RISER SIZE DENOTED "RN"
= PIPE ELEVATION ABOVE BUILDING FIRST LEVEL SLAB
NEGATIVE ELEVATIONS INDICATE BELOW SLAB ELEVATION
= NOMINAL PIPE DIAMETER (DN)
= CENTER TO CENTER LENGTH DIMENSION
H01
= APPROXIMATE PIPE HANGER LOCATION
#1 SEE DETAIL NO. 4 ON SHEET FP501
= FIRE SPRINKLER RISER
= FLEXIBLE PIPE TO SPRINKLER HEAD
= QUICK RESPONSE, WHITE, 5.6 K, 155°F SEMI-RECESSED
PENDENT FIRE SPRINKLER HEAD
= STANDARD RESPONSE, 5.6 K, 286°F UPRIGHT FIRE SPRINKLER HEAD
= QUICK RESPONSE, 5.6 K, 286°F UPRIGHT FIRE SPRINKLER HEAD WITH GUARD
= DRY, CORROSION RESISTANT, QUICK RESPONSE
5.6K 155°F SIDEWALL SPRINKLER HEAD
DN DN
DN
A B C D E F H J K L M N O P R S T U V WG
FP501
FP501
(TYP.)
FP501
(TYP.)
FP501
(TYP.)
FP501
(TYP.)
FP501
FP501
FP501
(TYP.)
FP501
(TYP.)
Bedroom
H-144
Bedroom
H-139
Bedroom
H-138
Bedroom
H-134
Bedroom
H-133
Bedroom
H-146
Bedroom
H-141
Bedroom
H-140
Bedroom
H-135
Bedroom
H-132
Bedroom
H-153
Bedroom
H-154
Bedroom
H-159
Bedroom
H-160
Bedroom
H-165
Bedroom
H-166
Bedroom
H-162
Bedroom
H-161
Bedroom
H-156
Bedroom
H-155
Clean Utility
H-152
Soiled Utility
H-151
Bath Suite
H-131
Medicine Stor.
H-128
Oxygen Storage
H-116
House Keeping
H-115
Office
H-114
Family Lounge
H-129
Office
H-113
Office
H-112
Staff Lounge
H-111
Office
H-110
Shared Office
H-109
Shared Office
H-107
Bedroom
H-145
Conference
H-102
Locker Room
H-100
Toilet
H-100A
Toilet
H-100B
Laundry
H-117
Storage/Linen
Storage
H-118
Toilet
H-145.1
Toilet
H-144.1
Toilet
H-139.1
Toilet
H-138.1
Toilet
H-134.1
Toilet
H-133.1
Toilet
H-146.1
Toilet
H-141.1
Toilet
H-140.1
Toilet
H-135.1
Toilet
H-132.1
Toilet
H-155.1
Toilet
H-156.1
Toilet
H-161.1
Toilet
H-162.1
Toilet
H-166.1
Toilet
H-153.1
Toilet
H-154.1
Toilet
H-159.1
Toilet
H-160.1
Toilet
H-165.1
Toilet
H-150.1
Bariatric Bedroom
H-130
Toilet
H-130.1
Bariatric Bedroom
H-150
Telecom Closet
H-125
Closet
H-120 Kitchen
H-121
Public Toilet
H-119
Corridor
H-105.4
Corridor
H-105.3
Stair #2
H-002
Stair #3
H-003
Restorative
Therapy
H-104
Elec.
H-106
OT Office
H-101.1
Occupational
Therapy
H-101
PT Office
H-103.1
Physical Therapy
H-103
Staff Stor.
H-108
ADL
H-101.3
Living
H-124
Living
H-122
Ward Nurse
H-127
Waiting
H-126
Corridor
H-105
Stair #1
H-001
Elec.
H-142
Storage
H-143
Storage
H-137
Storage
H-164
Storage
H-163
Elec.
H-157
Alcove
H-158
Alcove
H-136
Recreation/Dining/Events
H-123
Corridor
H-105
Storage
H-101.2
W/C & Walker
Storage
H-105.2
C o r r i d o r
H
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FP101
NEW FIRE PROTECTION SYSTEMS
PLAN - FIRST FLOOR
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
1/8" = 1'-0"
FX101
1st FLOOR - NEW LAYOUT
Revisions: Date: 11/01/2019 SEL JCB
A. SEE DRAWING FP001 FOR ADDITIONAL GENERAL
NOTES.
B. DEMOLISH AND REMOVE EXISTING FIRST FLOOR
SPRINKLER PIPING, VALVES AND HEADS AND
PROVIDE NEW LAYOUT FOR 100% SPRINKLER
COVERAGE.
C. PLAN DRAWINGS REFLECT SCHEMATIC PIPING
AND SPRINKLER HEAD LAYOUT. CONTRACTOR TO
CONFIRM PIPE SIZES AND SPRINKLER HEAD
SPACING WITH HYDRAULIC CALCULATION.
D. NEW SPRINKLER HEADS SHALL BE QUICK
RESPONSE, SEMI-RECESSED.
E. COORDINATE SPRINKLER BRANCH LINE AND HEAD
LOCATIONS WITH FINAL ARCHITECTURAL
REFLECTED CEILING PLAN AND MECHANICAL
DUCTS AND LIGHTING.
F. NEW FLOOR CONTROL VALVE, DRAIN,
INSPECTORS TEST AND TAMPER SWITCH
LOCATION SHALL BE COORDINATED WITH OWNER.
G. EXISTING FIRE DEPARTMENT HOSE VALVE AND
TAMPER TO REMAIN.
H.
1 EXISTING RISER LOCATION.
2 NEW FLOOR CONTROL VALVE. CONFIRM
LOCATION WITH OWNER.
3 NEW SPRINKLER CROSS MAINS LOCATED IN
CORRIDORS.
4 CONNECT NEW 4" SPRINKLER MAIN TO EXISTING
4" SPRINKLER RISER.
0 5 10
GRAPHIC SCALE
SOURCE DATA POINTS
WATER SUPPLY INFORMATION
PRESSURE FLOW
DATE OF FLOW TEST / INFO :
LOCATION OF FLOW TEST DATA :
SOURCE OF FLOW TEST DATA :
09/16/2019
BUILDING 7, 1ST FLOOR
70.00 0.00
65.00 722.00
55.00 1381.00
HYDRANT FLOW TEST BY:
INTERNATIONAL FIRE & SAFETY
A B C D E F H J K L M N O P R S T U V WG
U P
PENTHOUSE
P001
MACHINE
PLATFORM
KNOCK OUT
SLAB FOR
FUTURE
ELEVATORS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FP102
NEW FIRE PROTECTION SYSTEMS
PLAN - ROOF
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
1/8" = 1'-0"
FX102
ROOF LEVEL
Revisions: Date: 11/01/2019 SEL JCB
0 5 10
GRAPHIC SCALE
A. SEE DRAWING FP001 FOR ADDITIONAL GENERAL
NOTES.
1 THIS AREA REMAINS UNTOUCHED AND
SPRINKLERS SHALL REMAIN IN OPERATION
DURING CONSTRUCTION
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FP501
NEW FIRE PROTECTION SYSTEMS
EQUIPMENT MOUNTING DETAILS
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
CHECK
VALVE
PRESSURE
GAUGE
WATERFLOW
SWITCH
DRAIN
RISER
SPRINKLER RISER
INSPECTOR’S
TEST AND DRAIN
CONNECTION
TO
SPRINKLER
SYSTEM
INDICATING-TYPE FLOOR
CONTROL VALVE WITH
SUPERVISORY SWITCH
SPRINKLER FLOOR
CONTROL VALVE DETAIL
SPRINKLER BRANCH
LINE DETAIL
SPRINKLER FLEXHEAD
BRANCH LINE DETAIL
PIPE RING
CONCRETE ANCHOR
ALL THREAD ROD
DRILLED CONCRETE
HANGER DETAIL
SPRINKLER PIPE
SEMI-RECESSED PENDENT
SPRINKLER HEAD
UPRIGHT
SPRINKLER HEAD 7
DRY SIDEWALL SPRINKLER HEAD
LONGITUDINAL SWAY BRACE
WITH NON-THREADED FITTINGS
LATERAL SWAY BRACE
WITH NON-THREADED FITTINGS
Sprinkler branch line
FlexHead sprinkler drop
Ceiling grid mounting bracket Adjustable hub
Suspended t-bar grid
Sprinkler head
(not included)
Ceiling tile
SPRINKLER HEAD
WITH GUARD
AIR RELEASE VALVE
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
CONSTRUCTION
DOCUMENTS
V P u b l i c R
E V
I T
V
A C
L C b c a b u n a c b e j a r c h c o m r v t
A
M
FP502
NEW FIRE PROTECTION SYSTEMS
DETAILS
RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019Revisions: Date: SEL JCB
System No. C-AJ-1291
SECTION A-A
CA
J 1
1. Floor or Wall Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 30-7/8 in. (784 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through-Penetrant — One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe or conduit and periphery of opening shall be min 0 in. to max 7/8 in. (22 mm). Pipe or conduit to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be used:
A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. (152 mm) diam (or smaller) steel conduit.
F. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT).
3. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between pipe and concrete, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/pipe interface on the top surface of floor and on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 07, 2015
A
C
CL
ASS I F I ED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
Hilti Firestop Systems
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating — 2 Hr F Rating — 2 Hr
T Rating — 0 Hr FT Rating — 0 Hr
FH Rating — 2 Hr
FTH Rating — 0 Hr
Hilti Firestop Systems
System No. W-L-1054
SECTION A-A
W L
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
October 14, 2015
A
1A
2 1B
C
CL
ASS IF IED
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings —1 and 2 Hr (See Items 1 and 3) F Ratings — 1 and 2 Hr (See Items 1 and 3)
T Rating — 0 Hr FT Rating — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft FH Ratings —1 and 2 Hr (See Items 1 and 3)
L Rating at 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft
L Rating at 400 F — Less Than 1 CFM/sq ft
Hilti Firestop Systems Page: 2 of 2Page: 1 of 2
W L
54System No. W-L-1054
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152
mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly.
2. Through-Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall.
At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
October 14, 2015
File details come from the government source that posted it. Updated .