P01 - SOW Package_CLC Addendum to Specification Vol 1 and 2.pdf

PDF 7 MB Posted

Attached to
Y1DZ--"Renovate 1st Floor Community Living Center" at G. V. (Sonny) Montgomery VAMC in Jackson, MS.
Solicitation number
36C25620R0055
Issued by

About this file

This solicitation requests proposals for renovating the first floor of the Community Living Center at the G.V. (Sonny) Montgomery VA Medical Center in Jackson, Mississippi. Contractors must furnish all labor, materials, tools, transportation, and supervision to complete the renovations. Proposals are due by August 15, 2022. The contract award date is September 15, 2022, with project completion expected within 365 calendar days of the award date. The solicitation involves renovating patient rooms, corridors, nurse stations, and common areas on the first floor of the Community Living Center in accordance with the attached statement of work and specifications. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is the contracting agency.

View the file

Other files

File Type Posted
Amendment 0004_Addendum No 2 Renovate First Floor CLC Revised.pdf PDF
Amendment 0004_36C25620R0055 0004.pdf PDF
Amendment 0003_Combined QandA Final 7_21_2020.pdf PDF
Amendment 0003_36C25620R0055 0003.pdf PDF
Amendment 0003_90_TE_VACLC_2018-01-12_IFB.pdf PDF
Amendment 0003_44OP-249548 VA-CLS Reno Asbuilt Dwg 12-12-19.pdf PDF
Amendment 0003_VA CLC AS-BUILTS COMBINE.pdf PDF
Amendment 0003_M0201_AS_BUILT.pdf PDF
Amendment 0003_M0603_AS_BUILT.pdf PDF
Amendment 0003_A0101-Model REVISED 11 25 2019.pdf PDF
Amendment 0002_36C25620R0055 0002.pdf PDF
Amendment 0001_EXHIBIT B PERFORMANCE RELEVANCY SURVEY.docx DOCX document
Amendment 0001_EXHIBIT C PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
Amendment 0001_CLC Site Visit Sign-in Sheet.pdf PDF
Amendment 0001_36C25620R0055 0001.pdf PDF
P01 - CLC_ENVIRONMENTAL PROTECTION CONSIDERATIONS--2019.pdf PDF
P01-SOW Package_CLC FIRE PROTECTION.pdf PDF
P01-SOW Package_CLC Specification Volume 1 FINAL.pdf PDF
P01-SOW Package_CLC GENERAL.pdf PDF
P01- SOW Package_ CLC ARCHITECTURAL.pdf PDF
Final Statement of Work.pdf PDF
P01-SOW Package_CLC Specification Volume 2 FINAL.pdf PDF
P01- SOW Package_CLC ELECTRICAL.pdf PDF
P01 - CLC ASBESTOS Statement.pdf PDF
P01-SOW Package_CLC PLUMBING.pdf PDF
36C25620R0055.docx DOCX document
P01-SOW Package_CLC MECHANICAL.pdf PDF
P01 - CLC ASBESTOS Specification.pdf PDF
SF24 - BID BOND.pdf PDF
P01 - CLC ASBESTOS Construction Waste Specification.pdf PDF
Wage Determination 4_13_2020 Jackson CLC.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum #1 - 1

April 17, 2020

ADDENDUM NO. 1

PROJECT

U.S. Department of Veterans Affairs Renovate CLC 1ST Floor G.V. (Sonny) Montgomery Department of Veterans Affairs Medical Center Jackson, Mississippi VA Project No. 586-18-103

OWNER

VA U.S. Department of Veterans Affairs 1500 East Woodrow Wilson Avenue Jackson, Mississippi 39216

PROFESSIONAL

Husman Environmental + Construction In association with Barlow Eddy Jenkins, P.A.

Jackson, Mississippi 39202

The following revisions are to become a part of the Contract Documents of the above referenced project. Acknowledge receipt of the Addendum by inserting it's number and date on the Bid Proposal. General Contractors are responsible for bringing this Addendum to the attention of all their Subcontractors and Material Suppliers.

PERTAINING TO THE SPECIFICATIONS

1. Under specification section 01 00 00 – GENERAL REQUIREMENTS:

a. CHANGE item 1.2.B, ALTERNATE NO. 1 to read “ALTERNATE NO. 1: Deduct purchase of residential appliances. All utility rough-ins for residential appliances shall remain part of the contract”.

b. REMOVE item 1.2.B, ALTERNATE NO. 5 in its entirety.

2. Under specification section 10 28 00 – TOILET, BATH, AND LAUNDRY ACCESSORIES; DELETE items 2.9 and 2.10 in their entirety.

3. DELETE specification section 08 71 00 – DOOR HARDWARE issued with the Bid Documents in its entirety. INSERT specification section 08 71 00 – DOOR HARDWARE attached as part of this addendum.

4. DELETE specification section 23 09 23 - DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC issued with the Bid Documents in its entirety. INSERT specification section 23 09 23 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC attached as part of this addendum.

PERTAINING TO THE DRAWINGS

1. On sheet GI005 under the “FFE RESPONSIBILITY MATRIX”, CHANGE the following items:

a. Coat Hook – Designed by: O | Procured by: O |Installed by: O

b. Shower Curtain Rod – Designed by: O | Procured by: O | Installed by: O

Addendum #1 - 2

2. On sheet AS101 and sheet AS401-detail 4, DELETE the floor drain and mop sink in Storage/Linen Storage H-118.

3. On sheet AS401 under the “ARCHITECTURAL EQUIPMENT SCHEDULE” CHANGE the Comments section for item AR-03 to read “Equal to Amico Artwall – Complete system and artwork to be by the contractor (artwork selection by V.A.)”.

4. On sheet AS401 under the “TOILET ACCESSORY SCHEDULE” and at the individual plan enlargements, OMIT items TA-02 and TA-03.

5. DELETE sheet AS601 issued with the Bid Documents in its entirety. INSERT sheet AS601 attached as part of this addendum.

6. DELETE sheet MH101 issued with the Bid Documents in its entirety. INSERT sheet MH101 attached as part of this addendum.

7. DELETE sheet MH102 issued with the Bid Documents in its entirety. INSERT sheet MH102 attached as part of this addendum.

8. DELETE sheet MH107 issued with the Bid Documents in its entirety. INSERT sheet MH107 attached as part of this addendum.

9. DELETE sheet MH110 issued with the Bid Documents in its entirety. INSERT sheet MH110 attached as part of this addendum.

10. DELETE sheet PL101 issued with the Bid Documents in its entirety. INSERT sheet PL101 attached as part of this addendum.

11. DELETE sheet PL102 issued with the Bid Documents in its entirety. INSERT sheet PL102 attached as part of this addendum.

End of Addendum

V.A. Medical Center - Community Living Center DOOR HARDWARE

Jackson, MS SECTION 08 71 00

April 23, 2020 Page 1 of 28

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

A. Caulking: Section 07 92 00 JOINT SEALANTS.

B. Application of Hardware: Section 08 14 00, WOOD DOORS / Section 08 11

13, HOLLOW METAL DOORS AND FRAMES / Section 08 41 13, ALUMINUM-FRAMED

ENTRANCES AND STOREFRONTS.

C. Painting: Section 09 91 00, PAINTING.

D. Electrical: Division 26, ELECTRICAL.

E. Fire Detection: Section 28 31 00.

1.3 GENERAL

A. All hardware shall comply with UFAS, (Uniform Federal

Accessible Standards) unless specified otherwise.

B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).

C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

E. The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

April 23, 2020 Page 2 of 28

5. Floor closers.

1.4 WARRANTY

A. Automatic door operators shall be subject to the terms of FAR Clause

52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

A. Submittals shall be in accordance with Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the

VAMC does not have a locksmith).

B. Hardware Schedule: Prepare and submit hardware schedule in the following form:

Hardware Qua nti ty

Size Reference

Publication

Finish Mfr.

Name

Key

Control

UL Mark

(if

ANSI/BHMA

Finish

Item Type No. and

Catal og

No.

Symbols fire rated and listed)

Designation

C. Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

April 23, 2020 Page 3 of 28

D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to Resident Engineer for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number.

These items shall remain on file in Resident Engineer's office until all other similar items have been installed in project, at which time the Resident Engineer will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and

Installer, Architect, Project Engineer and VA Locksmith, Hardware

Consultant, and Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.

April 23, 2020 Page 4 of 28

Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

B. Keying: All cylinders shall be keyed into existing Best Cormax

Great Grand Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be

7 pin type. Keying information shall be furnished at a later date by the Resident Engineer.

1.10 APPLICABLE PUBLICATION:

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

B. American Society for Testing and Materials

(ASTM): F883-04.................Padlocks

E2180-07................Standard Test Method for Determining the

Activity of Incorporated Antimicrobial

Agent(s) In Polymeric or Hydrophobic Materials

C. American National Standards Institute/Builders Hardware

Manufacturers Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.3-08...............Exit Devices, Coordinators, and Auto

Flush

Bolts

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and

Holders A156.11-14..............Cabinet Locks

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series

1000 A156.14-07 .............Sliding and Folding Door

Hardware

A156.15-06..............Release Devices-Closer Holder, April 23, 2020 Page 5 of 28

Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06..............Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal

Systems A156.23-04..............Electromagnetic Locks

A156.24-03..............Delayed Egress Locking Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.31-07 .............Electric Strikes and Frame Mounted

Actuators A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

D. National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Opening Protectives

101-09..................Life Safety Code

E. Underwriters Laboratories, Inc.

(UL): Building Materials Directory

(2008)

PART 2 – PRODUCTS

2.1 BUTT HINGES

A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type A2111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for exterior outswing doors shall have non-removable pins.

Hinges for exterior fire-rated doors shall be of stainless steel material.

2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.

April 23, 2020 Page 6 of 28

Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

B. Provide quantity and size of hinges per door leaf as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm (4-1/2 inches x 4-1/2 inches) hinges.

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 lbs.) or more, furnish 127 mm

(5 inch) high hinges.

C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

A. ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Exterior Hinges: Stainless steel.

2. Base Metal for Interior Hinges: Stainless steel.

3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.

4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.

5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges

April 23, 2020 Page 7 of 28 of minimum width required.

6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

2.3 DOOR CLOSING DEVICES

A. Closing devices shall be products of one manufacturer for each type specified.

2.4 DOOR STOPS

A. Conform to ANSI A156.

B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.

C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.

D. Provide floor stops (Type L02141 or L02161 in office areas; Type

L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

E. Where drywall partitions occur, use floor stops, Type L02141 or

L02161 in office areas, Type L02121 elsewhere.

F. Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

G. Omit stops where floor mounted door holders are required and

April 23, 2020 Page 8 of 28 where automatic operated doors occur.

H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

J. Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

K. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

L. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).

2.5 OVERHEAD DOOR STOPS AND HOLDERS

A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold- open on/off control at all other doors requiring overhead door stops.

2.6 LOCKS AND LATCHES

A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than // six pins // seven pins //. Cylinders for all locksets shall be removable core type. // Cylinders shall be furnished with construction removable cores and construction master keys. // Cylinder shall be removable by special key or tool.

Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System.

Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and

April 23, 2020 Page 9 of 28 closing during construction and prior to the installation of final cores.

B. In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental

Health) areas, shall have lever handles fabricated from cast stainless steel. Provide sectional (lever x rose) lever design matching

Best Locks. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with

122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position.

(This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)

3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

4. Locks on designated doors in Psychiatric (Mental Health) areas

April 23, 2020 Page 10 of 28 shall be paddle type with arrow projection covers and be UL Listed.

Provide these locks with paddle in the down position on both sides of the door. Locks shall be fabricated of wrought stainless steel.

5. Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware (see HW-2B).

2.7 PUSH-BUTTON COMBINATION LOCKS

A. ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.

B. Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA

A156.13, Grade 1. Lever handles and operating components in compliance with the UFAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.

C. Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.

2.8 ELECTROMAGNETIC LOCKS

A. ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's

"Certified Product Directory."

1. Type: Full exterior or full interior, as required by application indicated.

2. Strength Ranking: 1200 lbf.

3. Inductive Kickback Peak Voltage: Not more than 53 V.

4. Residual Magnetism: Not more than 4 lbf (18 N)lbf to separate door from magnet.

B. Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's

"Certified Product Directory".

1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 lbf (67 N) for not more than

3 seconds, as required by NFPA 101.

2. Security Grade: Activated from secure side of door by initiating device.

3. Movement Grade: Activated by door movement as initiating device.

April 23, 2020 Page 11 of 28

4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.

2.9 KEYS

A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

B. Psychiatric keys shall be cut so that first two bittings closest to the key shoulder are shallow to provide greater strength at point of greatest torque.

2.10 KEY CABINET

A. ANSI Standard A156.11. Provide key cabinet made of cold rolled, 1.2 mm (0.0478 inch) thick furniture steel electro-welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam and mechanical pushbutton door lock. Key Cabinet and Key Control System shall accommodate all keys for this project plus 25 percent. Provide minimum number of multiple cabinets where a single cabinet of largest size will not accommodate the required number of keys.

B. Key tags shall consist of two sets: Permanent self-locking and loan key snaphook type with tag colors as follows: Red fiber marker of the permanent self-locking type approximately 32 mm (1-1/4 inch) in diameter engraved with the legend "FILE KEY MUST NOT BE LOANED." Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with the legend "LOAN KEY."

C. The manufacturer of the lock cylinders and locks shall attach a key tag to keys of each lock cylinder and shall mark thereon the respective item number and key change number. Provide each group of keys in a key gathering envelope (supplied by Key Cabinet

Manufacturer) in which the lock manufacturer shall include the

April 23, 2020 Page 12 of 28 following information: Item number, key change number and door number.

The contractor shall furnish the Key Cabinet Manufacturer the hardware and keying schedules and change keys.

D. The Key Cabinet Manufacturer shall set up a three-way cross index system, including master keys, listing the keys alphabetically, the hooks numerically and the key changes numerically on different colored index cards. Index cards shall be typewritten and inserted in a durable binder. Attach the keys to the two sets of numbered tags supplied with the cabinet. (The permanent tag and the loan key tag).

Instruct the owner in proper use of the system. Install cabinet as directed by the Resident Engineer.

2.11 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

A. Conform to ANSI Standard A156.6.

B. Provide protective plates and door edging as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates

25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors.

Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

4. Armor plates for doors are listed under Article "Hardware Sets".

Armor plates shall be thickness as noted in the hardware set, 875 mm (35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all

April 23, 2020 Page 13 of 28

4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate.

Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

2.12 EXIT DEVICES

A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.

B. Surface vertical rod panics shall only be provided less bottom rod;

provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.

April 23, 2020 Page 14 of 28

C. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.

D. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.

E. Exit devices for fire doors shall comply with Underwriters

Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.

2.13 FLUSH BOLTS (LEVER EXTENSION)

A. Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI A156.16, for flush bolts required on lower part of doors.

B. Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.

C. Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).

D. Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.

E. Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).

2.14 FLUSH BOLTS (AUTOMATIC)

A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI

A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI

A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).

B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than

20 minutes; provide fire pins as required by auto flush bolt and door fire labels.

2.15 DOOR PULLS WITH PLATES

A. Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates

April 23, 2020 Page 15 of 28 of door pull plate for cylinders, or turn pieces where required.

2.16 PUSH PLATES

A. Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by

406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide.

Cut plates for cylinders, and turn pieces where required.

2.17 COMBINATION PUSH AND PULL PLATES

A. Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with

38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.

2.18 COORDINATORS

A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.

2.19 THRESHOLDS

A. Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

B. For thresholds at elevators entrances see other sections of specifications.

C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

D. Provide with miter returns where threshold extends more than 12 mm

April 23, 2020 Page 16 of 28

(0.5 inch) beyond face of frame.

2.20 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR

SOUND CONTROL DOORS

A. Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).

2.21 WEATHERSTRIPS (FOR EXTERIOR DOORS)

A. Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length (0.000774m3/s/m).

2.22 MISCELLANEOUS HARDWARE

A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh

Types): Except for fire-rated doors and doors to Temperature Control

Cabinets, equip each single or double metal access door with Lock Type

E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, // except as otherwise specified //. Provide cylinders to operate locking devices where specified for following partitions and doors:

1. Folding doors and partitions.

2. Wicket door (in roll-up door assemblies).

3. Slide-up doors.

4. Swing-up doors.

5. Fire-rated access doors-Engineer's key set.

6. Doors from corridor to electromagnetic shielded room.

7. Day gate on vault door.

C. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers

Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors.

Provide 4 mutes or silencers for frames for each Dutch type door.

Provide 2 mutes for each edge of sliding door which would contact door frame.

2.23 PADLOCKS FOR VARIOUS DOORS, GATES AND HATCHES

A. ASTM E883, size 50 mm (2 inch) wide chain; furnish extended shackles

April 23, 2020 Page 17 of 28 as required by job conditions. Provide padlocks, with key cylinders, for each door in following areas as noted.

B. Key padlocks as follows:

1. Constant Temperature and Cold Rooms in Research

Departments: Research Laboratory Set.

2. Cold Room in Morgue Department: Autopsy Set.

3. Refrigerators in Canteen Department: Canteen Storage Set.

4. All Refrigerator Rooms in Main Kitchen Department: Kitchen

Storage Set.

5. Chain Link Fence Gates for Electrical Substation and other Fenced

Buildings or Areas: Engineer's set, except as otherwise specified.

6. Chain Link Fence Gates for Oxygen Storage Buildings:

Maintenance supply set.

7. Roof Access and Scuttles: Engineer's set.

8. Hinged Wicket in Post Office Partitions: Post Office set.

C. Omit padlocks on communicating refrigerator doors.

2.24 FINISHES

A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91

00, PAINTING.

B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

C. Miscellaneous Finishes:

1. Hinges --exterior doors: 626 or 630.

2. Hinges --interior doors: 652 or 630.

3. Pivots: Match door trim.

4. Door Closers: Factory applied paint finish. Dull or Satin

Aluminum color.

5. Thresholds: Mill finish aluminum.

6. Cover plates for floor hinges and pivots: 630.

7. Other primed steel hardware: 600.

D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.

April 23, 2020 Page 18 of 28

E. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.25 BASE METALS

A. Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA Resident

Engineer for approval.

A. For new buildings locate hardware on doors at heights specified below, with all hand-operated hardware centered within 864 mm (34 inches) to

1200 mm (48 inches), unless otherwise noted:

B. Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm

(40- 5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-

5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

April 23, 2020 Page 19 of 28

3.2 INSTALLATION

A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors // except security bedroom, bathroom and anteroom doors which shall have closer installed parallel arm on exterior side of doors. //. At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.

B. Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8

(hollow core doors) inch) wood

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by

Resident Engineer. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut- outs and screw-hole locations on doors and frames.

E. Hinges Required Per Door:

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

April 23, 2020 Page 20 of 28

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.

All fastenings exposed to weather shall be of nonferrous metal.

G. After locks have been installed; show in presence of Resident Engineer that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent

Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the Resident

Engineer for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

A. Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project

Engineer and VA Locksmith.

3.5 HARDWARE SETS

SET #HW-01

Doors: F101, F103, F108, F110.1, F110.2, F113, F114, F119

6 Hinges A8112 x Size as Required

1 Lockset-Office F04

1 Floor Stop L02121 x 3 Fasteners

1 Set Self-Adhesive Seals R0Y154

1 Coat Hook L03121

6 Door Silencers L03011

April 23, 2020 Page 21 of 28

SET #HW-02

Doors: F102, F106.2, F112

1 Continuous Hinge Integral Hinge Guard Channel x Adjusta-Screws

1 Lockset-Storeroom F07

1 Door Closer (at Rated Doors) C02011/C02021

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

1 Floor Stop L02121 x 3 Fasteners

1 Set Self-Adhesive Seals R0Y154

SET #HW-03

Doors: F104, F105

1 Lockset-Dble Key Public F09

1 Door Closer C02011/C02021

1 Kick Plate J102

1 Mop Plate J103

NOTE: Provide Non-Hold Open Door Closer at Toilet Rooms. Stone Threshold by

Other Trades.

SET #HW-04

Doors: F106.1, F111, F116

1 Lockset-Classroom F05

1 Kick Plate J102

1 Mop Plate J103

1 Floor Stop L02121 x 3 Fasteners

3 Door Silencers L03011

SET #HW-05

Doors: F106.3

3 Hinges A8112 x Size as Required

1 Privacy Set F76B

1 Floor Stop L02121 x 3 Fasteners

1 Coat Hook L03121

1 Set Self-Adhesive Seals R0Y154

1 Auto Door Bottom R0Y223 SA

NOTE: Stone Threshold by Other Trades.

SET #HW-06

Doors: F126, F131.1, F132.1, F133.1, F134.1, F135.1, F136.1, F139.1, F140.1, April 23, 2020 Page 22 of 28

F141.1, F142.1, F143.1, F144.1, F148.1, F149.1, F150.1, F151.1, F152.1, F154.1, F155.1, F156.1, F157.1, F158.1, F159.1

1 Privacy Set F76B

1 Floor Stop L02121 x 3 Fasteners

1 Coat Hook L03121

NOTE: Stone Threshold by Other Trades.

SET #HW-07

Doors: F107.1, F107.2, F109, F115.2, F146, F147

1 Push-button Comb. Lock N3-A156.13 F07 G1 E06

1 Door Closer C02011/C02021

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

SET #HW-08

Doors: F115.1

1 Exit Device Type 1 F08 Lever

1 Rim Cylinder Type as Required

1 Magnetic Holder C00011 Tri-Voltage

1 Door Closer C02011/C02021

1 Kick Plate J102

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

NOTE: Power, Wiring, Conduit and Fire Alarm Connections by Division 260000.

SET #HW-09

Doors: F115.3, F127, F137.2, F137.3, F137.4, F160.2, F160.3, F160.4

1 Set Auto Flush Bolts Type 25 (Less Bottom Bolt)

1 Lockset-Storeroom F07

1 Coordinator Type 21A

2 Door Closer C02011/C02021

2 Kick Plate J102

2 Floor Stop L02121 x 3 Fasteners

1 Astragal R0Y634 x R0Y154 x Thru-Bolts

SET #HW-10

Doors: F115.4

2 Cont. Hinge-Active Leaf Integral Hinge Guard Channel x ThruWire Transfer

April 23, 2020 Page 23 of 28

2 Electromagnetic Lock E18501-1200

2 Elec. Exit Device Type 7 F01 Less Trim

2 Door Closer C02011/C02021

2 Kick Plate J102

2 Floor Stop L02121 x 3 Fasteners

1 Astragal R0Y634 x Thru Bolts

1 Set Self-Adhesive Seals R0Y154

1 Power Supply Regulated, Filtered, 24VDC, AMP. as Required

1 Alarm Contact See Section 280000

1 Patient Wandering System See Section 281000

NOTE: (Includes Keypad, Door Contoller, Door Contacts and

Power Supplies)

2 Card Reader See Section 280000

NOTE: Provide new patient wandering system, with keypad, door controller, door contact and power supplies integrated into hardware, Division 281000.

Electromagnetic Lock to be tied to building fire panel. Card Reader by

Division 280000. 120 VAC power, conduit, and wiring by Division 260000.

SET #HW-11

Doors: F118

1 Door Closer C02011/C02021

1 Kick Plate J102

SET #HW-12

Doors: F117

1 Kick Plate J102

1 Wall Bumper L02251

SET #HW-13

Doors: F120

1 Passage Set F01

1 Door Closer C02011/C02021

1 Kick Plate J102

1 Wall Bumper L02251

SET #HW-14

Doors: F121

April 23, 2020 Page 24 of 28

1 Continuous Hinge Integral Hinge Guard Channel x ThruWire Transfer

1 Elec. Lockset-Storeroom F07 (E01-REX x E06) 24 VDC

1 Power Supply Regulated, Filtered, 24VDC, AMP. as Required

1 Door Closer C02011/C02021

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

1 Saddle Threshold J32300 x 2.5" Wide

1 Auto Door Bottom R0Y223 SA

1 Alarm Contact See Section 280000

SET #HW-15

Doors: F124

1 Passage Set F01

1 Door Closer C02011/C02021

1 Armor Plate J101

1 Floor Stop L02121 x 3 Fasteners

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

1 Set Self-Adhesive Seals R0Y154

1 Auto Door Bottom R0Y223 SA

1 Saddle Threshold J32300 x 2.5" Wide

SET #HW-16

Doors: F125

1 Door Closer C02011/C02021

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

SET #HW-17

Doors: F128

2 Hinges A8112 x Size as Required

1 Electric Hinge 8 Wire Type Size As Required

1 Elec. Lockset-Storeroom F07 (E01-REX x E06) 24 VDC

1 Power Supply Regulated, Filtered, 24VDC, AMP. as Required

1 Door Closer C02011/C02021

1 Floor Stop L02121 x 3 Fasteners

1 Auto Door Bottom R0Y223 SA

1 Set Self-Adhesive Seals R0Y154

1 Saddle Threshold J32300 x 2.5" Wide

1 Alarm Contact See Section 280000

NOTE: 120 VAC Power, Conduit, and Wiring by Division 260000. Card Reader by

Division 280000.

SET #HW-18

April 23, 2020 Page 25 of 28

Doors: F130

1 Push/Pull Latch-Classroom F08 Paddles Down Engraved Push/Pull

1 Mortise Cylinder 25 Cylinder as required x Keyed

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

SET #HW-19

Doors: F131, F132, F133, F134, F135, F136, F139, F140, F141, F142, F143, F144, F148, F149, F150, F151, F152, F154, F155, F156, F157, F158, F159

1 Continuous Hinge Integral Hinge Guard Channel x Swing Clear x

Adjusta-Screws

1 Push/Pull Latch F01 x Paddles Down

1 Armor Plate J101

1 Edge Guards-(@ Wood Doors) J208M / J211 (Verify), Cut for Hardware

1 Overhead Stop C01541 Adjustable

NOTE: No Closer required due to exemption for patient room doors.

SET #HW-20

Doors: F137, F160

1 Exit Device-Exit Only Type 7 F01

1 Exit Device-Classroom Type 7 F08 Lever

1 Rim Cylinder Type as Required

2 Door Closer C02011/C02021

2 Kick Plate J102

2 Wall Bumper L02251

1 Set Self-Adhesive Seals R0Y154

1 Door Sweep R0Y434 x Nylon Brush Insert

1 Astragal Set R0Y834

SET #HW-21

Doors: F123, F138, F153

1 Continuous Hinge Integral Hinge Guard Channel x ThruWire Transfer

1 Exit Device Type 1 F14 x Lever

1 Electromagnetic Lock E18501-1200

1 Door Closer C02011/C02021

1 Kick Plate J102

1 Floor Stop L02121 x 3 Fasteners

1 Set Self-Adhesive Seals R0Y154

1 Power Supply Regulated, Filtered, 24VDC, AMP. as Required

1 Alarm Contact See Section 280000

1 Patient Wandering System See Section 281000

NOTE: (Includes Keypad, Door Contoller, Door Contacts and

Power Supplies)

April 23, 2020 Page 26 of 28

2 Card Reader See Section 280000

NOTE: Provide new patient wandering system, with keypad, door controller, door contact and power supplies integrated into hardware, Division 281000.

Electromagnetic Lock to be tied to building fire panel. Card Reader by

Division 280000. 120 VAC power, conduit, and wiring by Division 260000.

April 23, 2020 Page 27 of 28

Opening List

Opening Hdw Set

F101 HW-01

F102 HW-02

F103 HW-01

F104 HW-03

F105 HW-03

F106.1 HW-04

F106.2 HW-02

F106.3 HW-05

F107.1 HW-07

F107.2 HW-07

F108 HW-01

F109 HW-07

F110.1 HW-01

F110.2 HW-01

F111 HW-04

F112 HW-02

F113 HW-01

F114 HW-01

F115.1 HW-08

F115.2 HW-07

F115.3 HW-09

F115.4 HW-10

F116 HW-04

F117 HW-12

F118 HW-11

F119 HW-01

F120 HW-13

F121 HW-14

F123 HW-21

F124 HW-15

F125 HW-16

F126 HW-06

F127 HW-09

F128 HW-17

F130 HW-18

F131 HW-19

F131.1 HW-06

F132 HW-19

F132.1 HW-06

F133 HW-19

F133.1 HW-06

F134 HW-19

F134.1 HW-06

F135 HW-19

F135.1 HW-06

F136 HW-19

F136.1 HW-06

F137 HW-20

F137.2 HW-09

F137.3 HW-09

F137.4 HW-09

F138 HW-21

F139 HW-19

April 23, 2020 Page 28 of 28

F139.1 HW-06

F140 HW-19

F140.1 HW-06

F141 HW-19

F141.1 HW-06

F142 HW-19

F142.1 HW-06

F143 HW-19

F143.1 HW-06

F144 HW-19

F144.1 HW-06

F146 HW-07

F147 HW-07

F148 HW-19

F148.1 HW-06

F149 HW-19

F149.1 HW-06

F150 HW-19

F150.1 HW-06

F151 HW-19

F151.1 HW-06

F152 HW-19

F152.1 HW-06

F153 HW-21

F154 HW-19

F154.1 HW-06

F155 HW-19

F155.1 HW-06

F156 HW-19

F156.1 HW-06

F157 HW-19

F157.1 HW-06

F158 HW-19

F158.1 HW-06

F159 HW-19

F159.1 HW-06

F160 HW-20

F160.2 HW-09

F160.3 HW-09

F160.4 HW-09

End of Section

23 09 23 - 1

SECTION 23 09 23

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

PART 1 - GENERAL

1.1 DESCRIPTION

A. Provide an expansion of the existing Johnson Controls Metasys direct-digital control system as indicated on the project documents, point list, interoperability tables, drawings and as described in these specifications. Include a complete and working expansion of that direct-digital control system.