This solicitation requests proposals for renovating the first floor of the Community Living Center at the G.V. (Sonny) Montgomery VA Medical Center in Jackson, Mississippi. The contractor shall furnish all labor, materials, tools, equipment, transportation and supervision to complete the renovation. Key requirements include renovating patient rooms, restrooms, corridors and common areas on the first floor to modernize the space. Proposals are due by July 20, 2020 and the contract is expected to be awarded by August 17, 2020. The period of performance is 365 days. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is the contracting agency.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #2 - 1
July 13, 2020
ADDENDUM NO. 2
PROJECT
U.S. Department of Veterans Affairs Renovate CLC 1ST Floor G.V. (Sonny) Montgomery Department of Veterans Affairs Medical Center Jackson, Mississippi VA Project No. 586-18-103
OWNER
VA U.S. Department of Veterans Affairs 1500 East Woodrow Wilson Avenue Jackson, Mississippi 39216
PROFESSIONAL
Husman Environmental + Construction In association with Barlow Eddy Jenkins, P.A.
Jackson, Mississippi 39202
The following revisions are to become a part of the Contract Documents of the above referenced project. Acknowledge receipt of the Addendum by inserting it's number and date on the Bid Proposal. General Contractors are responsible for bringing this Addendum to the attention of all their Subcontractors and Material Suppliers.
PERTAINING TO THE SPECIFICATIONS
1. INSERT specification section 10 51 13 – METAL LOCKERS, attached as part of this addendum, into the project manual.
2. Section 01 00 00 – General Requirements; item 1.2.B:
a. CLARIFICATION to Alternate No. 3: The deduct will only be for the devices/controls. All conduits and circuitry are to remain a part of the contract.
b. CLARIFICATION to Alternate No. 4: The deduct will only be for the devices/controls. All conduits and circuitry are to remain a part of the contract
c. CLARIFICATION to Alternate No. 5: The deduct shall include all conduits and electrical circuits to the flush valves.
d. CLARIFICATION to Alternate No. 6: The deduct shall only be for the devices/controls. All conduits, circuitry, structure, and custom door frames will remain part of the contract.
e. CLARIFICATION to Alternate No. 7: If the deduct is taken, the existing tube station will be removed and the existing tube from the station will be cut and capped directly above the new ceilings.
3. In specification section 22 40 00 – Plumbing Fixtures, REPLACE paragraphs 2.7, 2.9, 2.10, 2.11, 2.12, 2.13, 2.14, and 2.15 with the paragraphs included as part of this addendum.
PERTAINING TO THE DRAWINGS
1. On sheet GI003, DELETE the note stating “CONSTRUCTION PERSONNEL ENTRANCE- MAN/MATERIAL LIFT CONTRACTOR PERSONNEL ENTRANCE” located at the northeast corner of the building.
Addendum #2 - 2
ADD a note stating “CONSTRUCTION PERSONNEL/MATERIAL ENTRANCE AT BALCONY.
MAINTAIN GROUND FLOOR EMERGENCY EGRESS FROM EXTERIOR DOORS AT THIS
LOCATION” at the exterior balcony along grid line 1, between grid lines J and M.
2. DELETE sheet GI004 issued with the Bid Documents in its entirety. INSERT sheet GI004 attached as part of this addendum
3. On sheet AD101, DELETE the note stating “CONSTRUCTION PERSONNEL ENTRANCE- MAN/MATERIAL LIFT CONTRACTOR PERSONNEL ENTRANCE” located at the northeast corner of the building.
ADD a note stating “CONSTRUCTION PERSONNEL/MATERIAL ENTRANCE AT BALCONY.
MAINTAIN GROUND FLOOR EMERGENCY EGRESS FROM EXTERIOR DOORS AT THIS
LOCATION” at the exterior balcony along grid line 1, between grid lines J and M.
4. On sheet AS401; Architectural Equipment Schedule, item AR-62 Vent Hood shall be equal to Broan Model
BCSQ130SS.
5. On sheet AS404; details 3 and 5, The built-in headboard shall be 1 ¼” thick. The base layer shall be ¾” MDF covered by ½” solid surface material. Edges shall be eased.
6. On sheet AS501; Detail 24, the wood species/finish for the crown molding shall be paint grade poplar or pine/painted.
7. On sheet PL101, provide sink P-418, Rough in 2” waste , 2” vent piping ,½” hot and cold supply piping form nearest plumbing piping that is below the floor and above the ceiling in H-104 Restorative Therapy.
8. On sheet PL101, the mobile dialysis wall boxes shall be Whitehall Manufacturing Model 8195.
9. On sheet PL101, change fixture designation P-2451 to P-521.
10. On sheet PL301, Disregard note that states change to a mixing valve, BFP, & Monitoring station.
11. On sheet FA101, detail A/FA101, the NAC’s and associated items (including the smoke detector) shall be moved to Elec. – H-106 opposite the electrical panels.
End of Addendum
V.A. Medical Center - Community Living Center METAL LOCKERS
Jackson, MS SECTION 10 51 13
July 13, 2020 Page 1 of 5
SECTION 10 51 13
METAL LOCKERS
PART 1 -GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Standard metal lockers.
B. Related Section:
1. Section 06 10 00 Rough Carpentry.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of metal locker.
B. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.
1. Show locker trim and accessories.
2. Include locker identification system and numbering sequence.
3. Include fillers, base, and sloping tops.
C. Samples for Initial Selection: For units with factory-applied color finishes.
D. Samples for Verification: For metal lockers locker benches, in manufacturer's standard sizes.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For qualified Installer.
B. Warranty: Sample of special warranty.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For adjusting, repairing, and replacing locker doors and latching mechanisms to include in maintenance manuals.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Full-size units of the following metal locker hardware items equal to 10 percent of amount installed for each type and finish installed, but no fewer than five units:
a. Locks.
b. Identification plates.
c. Hooks.
July 13, 2020 Page 2 of 5
1.7 QUALITY ASSURANCE
A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project.
B. Source Limitations: Obtain metal lockers and accessories from single source from single manufacturer.
C. Regulatory Requirements: Where metal lockers are indicated to comply with accessibility requirements, comply with the U.S. Architectural
&Transportation Barriers Compliance Board's "Americans with
Disabilities Act (ADA) and Architectural Barriers Act
(ABA)Accessibility Guidelines for Buildings and Facilities" and
ICC/ANSIA117.1.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Do not deliver metal lockers until spaces to receive them are clean, dry, and ready for their installation.
B. Protect lockers from damage during delivery, handling, storage, and installation.
1.9 PROJECT CONDITIONS
A. Field Measurements: Verify actual dimensions of recessed openings by field measurements before fabrication.
1.10 COORDINATION
A. Coordinate sizes and locations for metal lockers.
B. Coordinate sizes and locations of framing, blocking, furring, reinforcements, and other related units of work specified in other
Sections to ensure that metal lockers can be supported and installed as indicated.
1.11 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal lockers that fail in materials or workmanship, excluding finish, within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures.
b. Faulty operation of latches and other door hardware.
2. Damage from deliberate destruction and vandalism is excluded.
3. Warranty Period for Knocked-Down Metal Lockers: Two years from date of Substantial Completion.
PART 2 -PRODUCTS
2.1 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS),Type
B, suitable for exposed applications.
B. Fasteners: Zinc- or nickel-plated steel, slotless-type, exposed bolt heads; with self-locking nuts or lock washers for nuts on moving
July 13, 2020 Page 3 of 5 parts.
C. Anchors: Material, type, and size required for secure anchorage to each substrate.
1. Provide nonferrous-metal or hot-dip galvanized anchors and inserts on inside of walls for corrosion resistance.
2. Provide toothed-steel or lead expansion sleeves for drilled-in-place anchors.
2.2 STANDARD METAL LOCKERS
A. Products: Subject to compliance with requirements, provide one of the following:
1. ASI Storage Solutions; Traditional Plus Collection
2. List Industries Inc.; Classic Line of Superior KD Lockers.
3. Republic Storage Systems Company; Designer Lockers.
B. Locker Arrangement: Triple tier, each tier to be 12”x18”x66”.
C. Body: Assembled by riveting or bolting body components together. Fabricate from unperforated steel sheet as follows:
1. Bottoms: 16 gauge.
2. Tops, sides, backs and shelves: 24 gauge.
D. Doors: 14 gauge, channel shaped on both the lock and hinge side, with angle formations across the top and bottom. Three tier locker doors shall have a 16 gauge full height reinforcement channel.
E. Door Frames: Shall be 16 gauge formed in a channel shape. Vertical members shall have additional flange to provide a continuous door strike. Cross frame members shall also be 16 gauge channel shaped, including intermediate cross frames on triple tier lockers.
F. Hinges: Shall be full length 16 gauge continuous piano type riveted to both door and frame.
G. Recessed Door Handle: Shall be one-piece 20 gauge deep drawn stainless steel cup designed to accommodate locks.
H. Latching: 11 gauge frame hook secured to the frame. The frame shall have a padlock hasp protruding through the recessed handle. A rubber silencer shall be firmly secured to the frame at each latch hook.
I. Equipment: Equip each metal locker with identification plate and three wall hooks.
J. Accessories:
1. Continuous Zee Base: Fabricated from manufacturer's standard thickness, 4 inches.
2. Continuous Sloping Tops: Fabricated from manufacturer's standard thickness, but not less than 0.036-inch (0.91-mm) nominal-thickness steel sheet.
a. Closures: Vertical -end type.
b. Sloping-top corner fillers, mitered.
3. Filler Panels: Fabricated from manufacturer's standard thickness, but not less than 0.048-inch (1.21-mm) nominal-thickness steel sheet.
4. Boxed End Panels: Fabricated from 0.060-inch (1.52-mm) nominal-thickness steel sheet.
5. Finished End Panels: Fabricated from 0.024-inch (0.61-mm)
July 13, 2020 Page 4 of 5 nominal-thickness steel sheet.
6. Finish: Baked enamel.
7. Color(s): As selected by Architect from manufacturer's full range.
2.3 FABRICATION
A. Fabricate metal lockers square, rigid, and without warp and with metal faces flat and free of dents or distortion. Make exposed metal edges safe to touch and free of sharp edges and burrs.
1. Form body panels, doors, shelves, and accessories from one-piece steel sheet unless otherwise indicated.
2. Provide fasteners, filler plates, supports, clips, and closures as required for complete installation.
B. Fabricate each metal locker with an individual door and frame; individual top, bottom, and back; and common intermediate uprights separating compartments. Factory weld frame members of each metal locker together to form a rigid, one-piece assembly.
C. Knocked-Down Construction: Fabricate metal lockers using nuts, bolts, screws, or rivets for nominal assembly at Project site.
D. Hooks: Manufacturer's standard ball-pointed type, aluminum or steel;
zinc plated.
F. Identification Plates: Manufacturer's standard, etched, embossed, or stamped aluminum plates, with numbers and letters at least 1/2 inch high. Attach plates to each locker door, near top, centered, with at least two aluminum rivets.
G. Continuous Base: Formed into channel or zee profile for stiffness, and fabricated in lengths as long as practical to enclose base and base ends of metal lockers; finished to match lockers.
H. Continuous Sloping Tops: Fabricated in lengths as long as practical, without visible fasteners at splice locations; finished to match lockers.
1. Sloping-top corner fillers, mitered.
I. Filler Panels: Fabricated in an unequal leg angle shape; finished to match lockers. Provide slip-joint filler angle formed to receive filler panel.
J. Boxed End Panels: Fabricated with 1-inch-(25-mm-) wide edge dimension, and designed for concealing fasteners and holes at exposed ends of nonrecessed metal lockers; finished to match lockers.
1. Provide one-piece panels for double-row (back-to-back) locker ends.
K. Finished End Panels: Designed for concealing unused penetrations and fasteners, except for perimeter fasteners, at exposed ends of nonrecessed metal lockers; finished to match lockers.
1. Provide one-piece panels for double-row (back-to-back) locker ends.
PART 3 -EXECUTION
3.1 EXAMINATION
A. Examine walls, floors, and support bases, with Installer present, for compliance with requirements for installation tolerances and other
July 13, 2020 Page 5 of 5 conditions affecting performance of the Work.
B. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. General: Install level, plumb, and true; shim as required, using concealed shims.
1. Anchor locker runs at ends and at intervals recommended by manufacturer, but not more than 36 inches (910 mm) o.c. using concealed fasteners, install anchors through backup reinforcing plates, channels, or blocking as required to prevent metal distortion.
2. Anchor single rows of metal lockers to walls near top and bottom of lockers.
B. Knocked-Down Metal Lockers: Assemble with standard fasteners, with no exposed fasteners on door faces or face frames.
C. Equipment and Accessories: Fit exposed connections of trim, fillers, and closures accurately together to form tight, hairline joints, with concealed fasteners and splice plates.
1. Attach hooks with at least two fasteners.
2. Identification Plates: Attach plates to each locker door, near top, centered, with at least two aluminum rivets.
3. Attach sloping-top units to metal lockers, with closures at exposed ends.
4. Attach boxed end panels with concealed fasteners to conceal exposed ends of nonrecessed metal lockers.
5. Attach finished end panels with fasteners only at perimeter to conceal exposed ends of nonrecessed metal lockers.
3.3 ADJUSTING, CLEANING, AND PROTECTION
A. Clean, lubricate, and adjust hardware. Adjust doors and latches to operate easily without binding. Verify that integral locking devices operate properly.
B. Protect metal lockers from damage, abuse, dust, dirt, stain, or paint. Do not permit use during construction.
C. Touch up marred finishes, or replace metal lockers that cannot be restored to factory-finished appearance. Use only materials and procedures recommended or furnished by locker manufacturer.
END OF SECTION
09-01-15
22 40 00 - 1
2.7 WATER CLOSETS
A. (P-101) Water Closet (Floor Mounted, ASME A112.19.2, Figure 6)-office and industrial, elongated bowl, siphon jet 6 L (1.6 gallons) per flush, floor outlet. Top of seat shall be 435 mm to 438 mm (17-1/8 inches to 17-1/4 inches) above finished floor.
1. Seat: Institutional/Industrial, extra heavy duty, chemical resistant, solid plastic, open front less cover for elongated bowls, integrally molded bumpers, concealed check hinge with stainless steel post. Seat shall be posture contoured body design. Color shall be white.
2. Fittings and Accessories: Floor flange fittings-cast iron; Gasket-wax; bolts with chromium plated cap nuts and washers.
3. Flush valve: Large chloramines resistant diaphragm, semi-red brass valve body, exposed chrome plated, non-hold open ADA approved side oscillating handle, water saver design per flush with maximum 10 percent variance, top spud connection, adjustable tailpiece, one-inch IPS screwdriver back check angle stop with vandal resistant cap, high back pressure vacuum breaker, solid-ring pipe support, and sweat solder adapter with cover tube and cast set screw wall flange.
Set centerline of inlet 292 mm (11-1/2 inches) above seat. Seat bumpers shall be integral part of flush valve. Valve body, cover, tailpiece and control stop shall be in conformance with ASTM B584
Alloy classification for semi-red brass.
L. (P-114) Bariatric Floor Mounted Water Closet ASME A112.19.2, Fully enclosed floor mounted with integral seat , siphon jet, white-powder-coated, 14 gage type 304 stainless steel construction with white powder coating and hinged seat with cover, flush valve operated, top of seat
450 mm (18 inches) above floor. Bio-based materials shall be utilized when possible. Rated for bariatric use – 1000 pound minimum capacity.
1. Fittings and Accessories: Gaskets-neoprene, bolts with chromium plated cap nuts and washers, and extra heavy-duty carrier.
2. Flush Valve: exposed chrome plated diaphragm type with low force ADA compliant 6 L (1.6 gallon) per flush, seat bumper, integral screwdriver stop and vacuum breaker, solid-ring pipe support, and escutcheon.
2.9 BATHTUBS
22 40 00 - 2
A. (P-301) Bathtub, free standing type hydro massage bathtub with wall mounted mixing valve, fill control valve and drain shall be furnished by the Owner.
1. Provide rough-in and final waste and water connections including installation of accessories supplied with the fixture.
2. Prior to starting work, obtain from the Owner, the manufacturers’ written installation instruction for the bathtub being installed.
B. (P-302) Bathtub (Recessed, with Shower, Thermostatic Valve, ASME
A112.19.1) enameled cast iron, slip resistant, approximately 1500 mm by
762 mm (60 inches by 30 inches) and 400 mm (16 inches) high, recessed, wide rim.
1. Drain: Pop-up, 40 mm (1-1/2 inches).
2. Shower Installation: Wall mounted, detachable spray assembly with handspray and hose attached to a 762 mm (30 inches) chrome bar with adjustable slide, elevated vacuum breaker, supply wall connection and flange, diverter valve, over the rim tub spout, thermostatic/pressure balanced mixing valve.
3. Shower Head: Metallic shower head with 1500 mm (60 inches) length of rubber lined CRS or chrome plated brass interlocked, metal flexible reinforced hose connection to 15 mm (1/2 inch) supply, with automatic flow control device to limit discharge to not more than
9.5 l/m (2.5 gpm) at 170 kPa (25 psig). Design showerhead to fit in palm of hand. Provide CRS or chrome plated metal wall bar with an adjustable swivel hanger for showerhead. Fasten wall bar securely to wall.
4. Valve: Type T/P combination thermostatic and pressure balancing, wall mounted shower with chrome plated metal lever type operating handle with adjustment for rough-in variation and chrome plated brass or CRS face plate. Valve body shall be any suitable copper alloy. Internal parts shall be copper, nickel alloy, CRS, or thermoplastic material. Valve inlet and outlet shall be 15 mm (1/2 inch) IPS. Provide external screwdriver check stops and temperature limit stops. Set stops for a maximum temperature of 43.3 degrees C
(110 degrees F). All exposed fasteners shall be vandal resistant.
Valve shall provide a minimum of 9.5 L/m (2.5 gpm) at 310 kPa (45 psig) pressure drop.
22 40 00 - 3
2.10 LAVATORIES
A. Dimensions for lavatories are specified, Length by width (distance from wall) and depth.
B. Brass components in contact with water shall contain no more than 0.25 percent lead content by dry weight. Faucet flow rates shall be 3.9 L/m
(1.5 gpm) for private lavatories and either 1.9 L/m (0.5 gpm) or 1.0 liter (0.25 gallons) per cycle for public lavatories.
C. (P-401) Lavatory (Single Lever Handle Control ASME A112.19.2) straight back, approximately 508 mm by 457 mm (20 inches by 18 inches) and a 102 mm (4 inches) maximum apron, first quality vitreous china. Punching for faucet on 102 mm (4 inches) centers. Set with rim 864 mm (34 inches) above finished floor.
1. Faucet: Solid cast brass construction, vandal resistant, heavy-duty single lever handle, center set. Control shall be washerless ceramic disc cartridge type. Provide laminar flow control device, adjustable hot water limit stop, and vandal proof screws. Flow shall be limited to 5.7 L/m (1.5 gpm).
2. Drain: Cast or wrought brass with flat grid strainer offset tailpiece, chrome plated. Provide cover per A.D.A 4-19.4.
3. Stops: Angle type, see paragraph “Stops”. Provide cover per A.D.A 4-
19.4.
4. Trap: Cast copper alloy, 38 mm by 32 mm (1 1/2 inches by 1 1/4 inches) P-trap. Adjustable with connected elbow and 1.4 mm thick (17 gauge) tubing extensions to wall. Exposed metal trap surface and connection hardware shall be chrome plated with a smooth bright finish. Set trap parallel to wall. Provide cover per A.D.A 4-19.4.
D. (P-414) Lavatory (Wrist Control, ASME A112.19.2) straight back, approximately 508 mm by 457 mm (20 inches by 18 inches) and a 102 mm (4 inches) minimum apron, first quality vitreous china. Punching for faucet shall be on 203 mm (8 inches) centers. Set rim 864 mm (34 inches) above finished floor.
1. Faucet: Solid cast brass construction with washerless ceramic mixing cartridge type and centrally exposed rigid gooseneck spout with outlet 102 mm to 127 mm (4 inches to 5 inches) above rim. Provide laminar flow control device. One hundred two millimeter (4-inch) wrist blade type, handles on faucets shall be cast, formed or drop forged copper alloy. Faucet, wall and floor escutcheons shall be either copper alloy or CRS. Exposed metal parts, including exposed
22 40 00 - 4 part under valve handle when in open position, shall be chrome plated with a smooth bright finish.
2. Drain: Cast or wrought brass with flat grid strainer, offset tailpiece, chrome plated.
3. Stops: Angle type. See paragraph “Stops”.
4. Trap: Cast copper alloy, 38 mm by 32 mm (1 1/2 inches by 1 1/4 inches) P-trap. Adjustable with connected elbow and 1.4 mm thick (17 gauge) tubing extension to wall. Exposed metal trap surface, and connection hardware shall be chrome plated with a smooth bright finish. Set trap parallel to the wall.
5. Provide cover for exposed piping, drain, stops and trap per A.D.A.
E. (P-418) Lavatory (Sensor Control, Gooseneck Spout, ASME A112.19.2) straight back, approximately 508 mm by 457 mm (20 inches by 18 inches) and a 102 mm (4 inches) minimum apron, first quality vitreous china with punching for gooseneck spout. Set rim 864 mm (34 inches) above finished floor.
1. Faucet: Solid cast brass construction, chrome plated, gooseneck spout with outlet 102 mm to 127 mm (4 inches to 5 inches) above rim.
Electronic sensor operated, 102 mm (4 inches) center set mounting, // wiring box // 120/24 volt solenoid // plug in transformer // remote mounted transformer // battery operated electronic module // back check valves // solid brass hot-cold water mixer adjusted from top deck with barrier free design control handle // and inline filter. Provide laminar flow control device. Breaking the light beam shall activate the water flow. Flow shall stop when user moves away from light beam. // Provide steel access door with key operated cylinder lock. See Section 08 31 13, ACCESS DOORS AND FRAMES // All connecting wiring between transformer, solenoid valve and sensor shall be cut to length with no excess hanging or wrapped up wiring allowed.
2. Drain: Cast or wrought brass with flat grid strainer with offset tailpiece, brass, chrome plated.
3. Stops: Angle type. See paragraph “Stops”.
4. Trap: Cast copper alloy, 38 mm by 32 mm (1 1/2 inches by 1 1/4 inches) P-trap. Adjustable with connected elbow and 17 gage tubing extension to wall. Exposed metal trap surface and connection hardware shall be chrome plated with a smooth bright finish. Set trap parallel to wall.
22 40 00 - 5
5. Provide cover for exposed piping, drain, stops and trap per A.D.A.
F. (P-421) Bariatric Floor Mounted Pedestal Lavatory (Sensor controlled
ASME A112.19.2), 14 gage type 304 stainless steel construction with white powder coating of lavatory deck. Bio-based materials shall be utilized when possible. Rated for bariatric use – 1000 pound minimum capacity.
1. Faucet: Brass, chrome plated, gooseneck spout with outlet 102 mm to
127 mm (4 inches to 5 inches) above rim. Electronic sensor operated, 102 mm (4 inches) center set mounting, wiring box // 120/24 volt solenoid // plug in transformer solid brass hot/cold water mixer adjusted from top deck with barrier free design control handle // and inline filter. Provide laminar flow control device. Breaking the light beam shall activate the water flow. Flow shall stop when user moves away from light beam. All connecting wiring between transformer, solenoid valve and sensor shall be cut to length with no excess hanging or wrapped up wiring allowed.
G. (P-402) Lavatory (Elbow Control, ASME A112.19.2) straight back, approximately 508 mm by 457 mm (20 inches by 18 inches) and a 102 mm (4 inches) maximum apron, first quality vitreous china. Punching for faucet on 203 mm (8 inches) centers. Set with rim 864 mm (34 inches) above finished floor.
1. Faucet: Solid cast brass construction with washerless ceramic disc mixing cartridge type and centrally exposed rigid gooseneck spout with outlet 127-152 mm (5-6 inches) above rim. Provide laminar flow control device. One hundred millimeters (4 inches) elbow handles on faucets shall be cast, formed or drop forged copper alloy. Faucet, wall and floor escutcheons shall be either copper alloy or CRS. Exposed metal parts, including exposed part under valve handle when in open position, shall have a smooth bright finish. Flow shall be limited to 5.7 L/m (1.5 gpm).
2. Drain: Cast or wrought brass with flat grid strainer and offset tailpiece, chrome plated finish.
3. Stops: Angle type, See paragraph “Stops”.
4. Trap: Cast copper alloy, 38 mm by 32 mm (1 1/2 inches by 1 1/4 inches) P-trap. Adjustable with connected elbow and 1.4 mm thick (17 gauge) tubing extensions to wall. Exposed metal trap surfaces and connection hardware shall be chrome plated with a smooth bright finish. Set trap parallel to wall.
5. Provide cover for exposed piping, drain, stops and trap per
A.D.A.
22 40 00 - 6
2.11 SINKS AND LAUNDRY TUBS
A. Dimensions for sinks and laundry tubs are specified, length by width
(distance from wall) and depth.
C. (P-502) Service Sink (Corner, Floor Mounted) stain resistant terrazzo, 711 mm by 711 mm by 305 mm (28 inches by 28 inches by 12 inches) with
152 mm (6 inches) drop front. Terrazzo, composed of marble chips and white Portland cement, shall develop compressive strength of 20684 kPa
(3000 psig) seven days after casting. Provide extruded aluminum cap on front side.
1. Faucet: Solid brass construction, 9.5 L/m (2.5 gpm) combination faucet with replaceable Monel seat, removable replacement unit containing all parts subject to wear, integral check/stops, mounted on wall above sink. Spout shall have a pail hook, 19 mm (3/4 inch) hose coupling threads, vacuum breaker, and top or bottom brace to wall. Four-arm handles on faucets shall be cast, formed, or drop forged copper alloy. Escutcheons shall be either forged copper alloy or CRS. Exposed metal parts, including exposed part under valve handle when in open position, shall have a smooth bright finish.
Provide 914 mm (36 inches) hose with wall hook. Centerline of rough in is 1219 mm (48 inches) above finished floor.
2. Drain: Seventy six millimeter (3 inches) cast brass drain with nickel bronze strainer.
3. Trap: P-trap, drain through floor.
E. (P-505) Clinic Service Sink (Flushing Rim, Wall Hung) approximately 508 mm by 635 mm (20 inches by 25 inches) by 203 mm (8 inches) deep.
Support with ASME A112.6.1M chair carrier and secure with 10 mm (3/8 inch) bracket studs and nuts. Set sink with rim 762 mm (30 inches) above finished floor. Provide 762 mm (30 inches) CRS drainboard where required, without corrugations and with heavy duty CRS brackets.
1. Faucet: Elbow control, wall hung, integral check/stops, single spout with 19 mm (3/4 inch) hose threaded outlet and pail hook, vacuum breaker and brace to wall. Outlet 356 mm to 381 mm (14 inches to 15 inches) from wall. Exposed metal parts shall be chromium plated with a smooth bright finish. Provide 9.5 L/m (2.5 gpm) laminar flow control device.
22 40 00 - 7
2. Flush valve: Large diaphragm, semi-red brass body, Foot pedal operated, exposed chromium plated flush valve with screwdriver back check straight stop with cap, union outlet, street ells, elevated high pressure vacuum breaker, casing cover, 32 mm (1 1/4 inches) elbow flush connection from finished wall to 38 mm (1 1/2 inches) top spud. Spud coupling, wall and spud flanges.
3. Bed Pan Washer: Mechanical pedal mixing valve, wall hung, with double self-closing pedal valve with loose key stops, renewable seats and supply from valve to nozzle with wall hook hose connection; 1219 mm (48 inches) of heavy duty rubber hose, with extended spray outlet elevated vacuum breaker, indexed lift up pedals having clearance of not more than 13 mm (1/2 inch) above the floor and not less than 356 mm (14 inches) from wall when in operation. Supply pipe from wall to valve stop shall be rigid, threaded, IPS copper alloy pipe. Exposed metal parts shall be chromium plated with a smooth bright finish. Provide valve plate for foot control. Provide inline laminar flow control device.
M. (P-521) Laundry Tub (Plastic, Single Compartment with Legs) fiber reinforced plastic, single bowl with raised back, approximately 635 mm by 559 mm (25 inches by 22 inches) by 356 mm (14 inches) deep, with base and legs.
1. Faucets: Solid brass construction, combination faucet with replacement Monel seat, removable replacement unit containing all parts subject to wear, vacuum breaker, integral stops, mounted on splash back. Lever handles on faucet shall be cast, formed or drop forged copper alloy or CRS. Exposed metal parts, including exposed part under valve handle when in open position, shall have a smooth bright finish.
2. Drain: Stopper.
3. Trap: Cast copper alloy, 38 mm (1 1/2 inches) P-trap. Adjustable with connected elbow, and nipple to wall and escutcheon.
O. (P-524) Sink, (CRS, Double Compartment, Counter Top, ASME A112.19.3, Kitchen Sinks) self-rimming, approximately 838 mm by 559 mm (33 inches by 22 inches) with two compartments inside dimensions approximately 343 mm by 406 mm by 191 mm (13 1/2 inches by 16 inches by 7 1/2 inches), minimum 20 gage CRS. Corners and edges shall be well rounded.
1. Faucet: Kitchen sink, solid brass construction, 8.3 L/m (2.2 gpm) swing spout, chrome plated copper alloy with spray and hose.
22 40 00 - 8
2. Drain: Drain plug with cup strainer, stainless steel.
3. Trap: Cast copper alloy, 38 mm (1 1/2 inches) P-trap with cleanout plug, continuous drain with wall connection and escutcheon.
4. Provide cover for exposed piping, drain, stops and trap per A.D.A.
Q. (P-528) Sink (CRS, Single Compartment, Counter Top ASME A112.19.2, Kitchen Sinks) self-rimming, back faucet ledge, approximately 533 mm by
559 mm (21 inches by 22 inches) with single compartment inside dimensions approximately 406 mm by 483 mm by 191 mm (16 inches by 19 inches by 7 1/2 inches) deep. Shall be minimum of 1.3 mm thick (18 gauge) CRS. Corners and edges shall be well rounded:
1. Faucet: Solid brass construction, 8.3 L/m (2.2 gpm) deck mounted combination faucet with Monel or ceramic seats, removable replacement unit containing all parts subject to ware, swivel gooseneck spout with approximately 203 mm (8 inches) reach with spout outlet 152 mm (6 inches above deck and // 102 mm (4 inches) wrist blades with hose spray. Faucet shall be polished chrome plated.
2. Drain: Drain plug with cup strainer, stainless steel.
3. Trap: Cast copper alloy 38 mm (1 1/2 inches) P-trap with cleanout plug. Provide wall connection and escutcheon.
4. Provide cover for exposed piping, drain, stops and trap per A.D.A.
R. (P-530) Sink (CRS, Single Compartment with Drainboard, Wall Hung, Sensor Controls) 14 gauge CRS approximately 457 mm by 381 mm (18 inches by 15 inches) by 254 mm (10 inches) deep with 203 mm (8 inches) splash back and drainboard at right or left as shown on the drawings. Overall dimensions (sink and drainboard), approximately 1219 mm (48 inches) long by 610 mm (24 inches) wide. Slope drainboard to bead, not less than 6 mm (1/4 inch) high, on front and ends. Corners and edges shall be well rounded. Support sink with 3.5 mm thick (10 gauge) CRS brackets on ASME A112.6.1M, Type I, chair carrier and secure fixture with minimum 10 mm (3/8 inch) all-thread bracket studs and nuts. Set rim of sink 914 mm (36 inches) above finished floor.
1. Drain: Drain plug with cup strainers.
2. Trap: Cast copper alloy, 38 mm (1 1/2 inches) P-trap. Adjustable with connected elbow and nipple the wall and escutcheon.
3. Sensor Control: Provide an infra-red photocell sensor and solenoid valve to control flow automatically, thermostatic control valve with check stops, 24 volt transformer, wire box and steel access door
22 40 00 - 9 with key operated cylinder lock see specification ACCESS DOORS.
Operation: Breaking the light beam shall activate the water flow.
Flow shall stop when the user moves from the light beam.
4. Gooseneck spout: Spout and trim shall be solid brass construction and be chromium plated with smooth bright finish. Provide laminar flow device.
5. Provide cover for exposed piping, drain, stops and trap per A.D.A.
2.12 DISPENSER, DRINKING WATER
A. Standard rating conditions: 10 degrees C (50 degrees F) water with 27 degrees C (80 degrees F) inlet water temperature and 32 degrees C (90 degrees F) ambient air temperature.
E. (P-609) Electric Water Cooler: Mechanically cooled, self contained, wheel chair, bubbler style fully exposed dual height stainless steel fountain, recessed in wall refrigeration system, stainless steel grille, stainless steel support arm, wall mounting box, energy efficient cooling system consisting of a hermetically sealed reciprocating type compressor, 115v, 60 Hz, single phase, fan cooled condenser, permanently lubricated fan motor. Set highest bubbler 1016 mm (40 inches) above finished floor. Provide with bottle filler option.
2.13 SHOWER BATH FIXTURE
A. (P-701) Shower Bath Fixture (Detachable, Wall Mounted, Concealed
Supplies, Type T/P Combination Valve):
1. Shower Installation: Wall mounted detachable spray assembly, 600 mm
(24 inch) wall bar, elevated vacuum breaker, supply elbow and flange and valve. All external trim, chrome plated metal.
2. Shower Head Assembly: Metallic shower head with flow control to limit discharge to 5.7 l/m (1.5 gpm) , 1524 mm (60 inches) length of rubber lined CRS, chrome plated metal flexible, or white vinyl reinforced hose and supply wall elbow. Design showerhead to fit in palm of hand. Provide CRS or chrome plated metal wall bar with an adjustable swivel hanger for showerhead. Fasten wall bar securely to wall for hand support.
3. Valves: Type T/P combination thermostatic and pressure balancing, with chrome plated metal lever type operating handle adjustable for rough-in variations and chrome plated metal or CRS face plate. Valve body shall be any suitable copper alloy. Internal parts shall be copper, nickel alloy, CRS or thermoplastic material. Valve inlet and
22 40 00 - 10 outlet shall be 13 mm (1/2 inch) IPS. Provide external screwdriver check stops, vacuum breaker and temperature limit stops. Set stops for a maximum temperature of 50 degrees C (122 degrees F). All exposed fasteners shall be vandal resistant. Valve shall provide a minimum of 5.7 l/m (1.5 gpm) at 310 kPa (45 psig) pressure drop.
C. (P-703) Shower Bath Fixture (Wall Mounted, Concealed Supplies, Type T/P combination Valve):
1. Shower Installation: Wall mounted showerhead with integral back secured to wall, diverter valve and supply elbow with quick connect for hose assembly and wall hook for hose assembly.
2. Shower Heads: Chrome plated metal head, institutional type, adjustable spray direction, self cleaning head with automatic flow control device to limit discharge to not more than 5.7 l/m (1.5 gpm). Provide mounting and vandal-proof screws. Body, internal parts of showerhead, and flow control fittings shall be copper alloy or
CRS. Install showerhead 1829 mm (72 inches) above finished floor.
3. Valves: Type T/P combination thermostatic and pressure balancing.
Valve body shall be any suitable copper alloy. Internal parts shall be copper, nickel alloy, CRS or thermoplastic material. Valve inlet and outlet shall be 13 mm (1/2 inch) IPS. Provide external combination screwdriver check stops, and temperature limit stops.
Set stops for a maximum temperature of 50 degrees C (122 degrees F).
One piece chrome plated brass or CRS faceplate, with chrome plated metal lever handle with adjustment for rough-in variation. Exposed fasteners shall be vandal resistant. Valve shall provide minimum of
5.7 l/m (1.5 gpm) at 310 kPa (45 psig) pressure drop.
2.14 EMERGENCY FIXTURES
A. (P-708) Emergency Eye and Face Wash (Wall Mounted): CRS, wall mounted, foot pedal control. Mount eye and face wash spray heads 1067 mm (42 inches) above finished floor. Pedal shall be wall mounted, entirely clear of floor, and be hinged to permit turning up. Receptor shall be complete with drain plug with perforated strainer, P-trap and waste connection to wall with escutcheon. Provide with thermostatic mixing valve to provide tepid water from 30 to 35 degrees C (85 to 95 degrees
F). Flow rate shall be 11.4 L/m (3 gpm).
D. (P-709) Emergency Eye and Face Wash (Pedestal Mounted): CRS receptor, pedestal mounted, hand operated. Mount eye and face wash spray heads
22 40 00 - 11
1067 (42 inches) above finished floor through floor waste connection and P-trap. Paint pedestal same color as room interior. Provide with thermostatic mixing valve to provide tepid water from 30 to 35 degrees
C (85 to 95 degrees F). Flow rate shall be 11.4 L/m (3 gpm).
2.15 HYDRANT, HOSE BIBB AND MISCELLANEOUS DEVICES
A. (P-804) Hose Bibb (Single Faucet, Wall Mounted to Concealed Supply
Pipe): Cast or wrought copper alloy, single faucet with replaceable
Monel seat, removable replacement unit containing all parts subject to wear, mounted on wall 914 mm (36 inches) above floor to concealed supply pipe. Provide faucet with 19 mm (3/4 inch) hose coupling thread on spout and vacuum breaker. Four-arm handle on faucet shall be cast, formed or drop forged copper alloy. Escutcheons shall be either forged copper alloy or CRS. Exposed metal parts, including exposed part under valve handle when in open position, shall have a bright finish.
G. (P-808) Washing Machine Supply and Drain Units: Fabricate of 16-gage steel with highly corrosion resistant epoxy finish. Unit to have 51 mm
(2 inches) drain connection, 13 mm (1/2 inch) combination MPT brass sweat connection, ball type shut-off valve, 51 mm (2 inches) cast brass
P-trap . Size 229 mm by 375 mm (9 inches by 14 3/4 inches) rough wall opening 203 mm by 330 mm by 92 mm (8 inches by 13 inches by 3 5/8 inches). Centerline of box shall be 1118 mm (44 inches) above finished floor.
I. (P-809) Dialysis Box: Recessed wall box with continuously welded 18 gage CRS, Type 316, with satin finish. Wall flange and hinged door shall be 16 gage CRS, Type 304, with satin finish. Provide polypropylene ball valve, 19 mm (3/4 inch) male supply outlet and two discharge hose brackets above 38 mm (1 1/2 inches) chemical resisting waste. Furnish each valve with flushing nipple. Provide with indirect drain in box or with separate funnel floor drain.
PROJECT
LIMITS
CONSTRUCTION
STAGING
CONSTRUCTION PERSONNEL/MATERIAL
ENTRANCE AT BALCONY ABOVE.
MAINTAIN GROUND FLOOR EMERGENCY
EGRESS FROM EXTERIOR DOORS AT THIS LOCATION
CONSTRUCTION FENCE
WOODROW WILSON DRIVE
WOODROW WILSON DRIVE
10 FT. WIDE GATE
CONTRACTOR TO REMOVE
GATE/HARDWARE AND
ADJACENT FENCE PANEL FOR
ACCESS TO COURTYARD
LAYDOWN AREA. FENCE, GATE
AND HARDWARE SHALL BE
RESTORED TO WORKING
ORDER AT COMPLETION
OF PROJECT.
CONTRACTOR SHALL TAKE
NECESSARY MEASURES TO
PROTECT TREES IN THE
CONSTRUCTION STAGING/
LAYDOWN AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANTS
321 4 5 6 7 8 9 10
MECHANICAL/ELECTRICAL ENGINEER
Sanders Engineering, Inc.
604 Hwy. 80 W., Suite J Clinton, MS 39056
FIRE PROTECTION ENGINEER
SafeMark, LLC 1852 Century Place Atlanta, GA 30345
IN ASSOCIATION WITH
C :\U se rs
\b ca bu na c.
G
H
AR
C H
IT
EC
TS
\D oc um en ts
R
EV
IT
\V A_
C
LC
_b ca bu na c@ be ja rc h.
co m .rv t 7/
9/
2:
:1
PM
GI004
SITE LAYDOWN/LIMITS PLAN RENOVATE 1st FLOOR CLC
VAMC - JACKSON, MS
586-18-103
11/01/2019 CCB cabu
NOT TO SCALEGI004
1 CONSTRUCTION STAGING PLAN
NOTE:
PARKING FOR CONTRACTOR’S PERSONNEL AND
SUBCONTRACTORS IS RESTRICTED TO THE LIMITS
SHOWN ON THE DRAWINGS FOR LAY-DOWN AREA OR
WORK LIMITS. IF ADDITIONAL PARKING IS REQUIRED
BY THE CONTRACTOR, IT IS THE CONTRACTOR’S
RESPONSIBILITY TO MAKE ANY NECESSARY
ARRANGEMENTS AND COORDINATIONS OFF OF THE
VAMC CAMPUS.
Revisions: Date:
ADDENDUM No. 2 7/13/2020