P01 JB Combined drawings 22 09 09 Part2.pdf
PDF 9 MB Posted
- Solicitation number
- 36C25523R0026
About this file
This solicitation is for construction services required to replace obsolete air handling units that support Buildings 52 and 53 at the Jefferson Barracks Division of the St. Louis VA Medical Center in St. Louis, Missouri. The project involves replacing the existing AHUs, which date back 35 years and are beyond their useful life, with new equipment and associated mechanical, electrical, and architectural work. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. Responses are due by the date specified in the solicitation, and award of the firm fixed price contract will occur shortly thereafter.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25523R0026 0005.docx | DOCX document | |
| 36C25523R0026_1 Page 5 3 bid items.pdf | ||
| 36C25523R0026 0004.docx | DOCX document | |
| 36C25523R0026 0003.docx | DOCX document | |
| 657-21-106JB - RFI Prebid Jan-2023 Questions.docx | DOCX document | |
| 657-21-106JB Sign In Sheet.pdf | ||
| 36C25523R0026_1 Page 5.pdf | ||
| 36C25523R0026 0002.docx | DOCX document | |
| 36C25523R0026 0001.docx | DOCX document | |
| APPENDIX D - ACM LBP MOLD REPORTS PART 2.pdf | ||
| P01 APPENDIX B - 100 SPECIFICATIONS 22 09 30 Update.pdf | ||
| APPENDIX D - ACM LBP MOLD REPORTS PART 1.pdf | ||
| P01 JB Combined drawings 22 09 09b Part3.pdf | ||
| P01 JB Combined drawings 22 09 09 Part1.pdf | ||
| 36C25523R0026_1.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JE
FFER
SON D
RIV
E
SO
U
TH
G
ATE
E N
TR
AN
C E D
R
IV
E
IN
T
ER
ST
AT
E
IN
TE
R
STA
TE
TO INTERSTATE 255 →
N O
R T H
G A T E
E N
T R
A N C
E D
R
IV
E
KOCH ROAD
KOCH ROAD
MISSISSIPPI RIVER
I-2
LO
T
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
PLAN NORTH
TRUE NORTH
NORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
DISCIPLINE:
G - GENERAL
A - ARCHITECTURE
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
SHEET TYPE
DESIGNATOR
VICINITY MAP
PROJECT TEAM
BUILDING SUMMARY
PROJECT INFORMATION
THE INTENT OF THIS PROJECT IS TO REPLACE OBSOLETE AIR HANDLERS THAT SUPPORT BUILDINGS 52 & 53. THIS INCLUDES ALL ARCHITECTURAL, ELECTRICAL, STRUCTURAL AND HAZARDOUS MATERIAL ABATEMENT NECESSARY TO SAFELY PROVIDE THE NEW EQUIPMENT AND SYSTEM COMPONENTS.
ANNOTATION DRAWING SYMBOLSGENERAL NOTES
PROJECT NAME: FCA REPLACE AIR HANDLING UNITS BUILDINGS 52 & 53
PROJECT NUMBER: 657-21-106JB
PROJECT LOCATION: JEFFERSON BARRACKS VA MEDICAL CENTER, 1 JEFFERSON BARRACKS DR., ST. LOUIS, MO 63125
PROJECT PURPOSE/USE: REPLACE OBSOLETE AHUS THAT SUPPORT BUILDINGS 52 & 53 PER FCA RECOMMENDATIONS
BUILDING 52 AREA:
BASEMENT (EXISTING) 34,923 GSF
LEVEL 01 (EXISTING) 34,963 GSF
LEVEL 02 (EXISTING) 30,936 GSF
BUILDING NUMBER
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION.
THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE
SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW ALL DRAWINGS AND
PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING
PERFORMED BEFORE SUBMITTING COST QUOTATIONS FOR WORK.
3. NOTIFY THE A/E PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES,
DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED
FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE PROVIDED PRIOR TO
CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE A/E.
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL,
STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE
WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS
AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING
JURISDICTION. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED
WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF
PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF
OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL
TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND
EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO
EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL
CONDITION AT THE CONTRACTOR'S EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE
ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE
ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS
PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH RESPECT TO DELIVERY DATE,
QUALITY, OR COST.
9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND
FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE A/E DOES NOT
ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S MEANS AND METHODS OR FOR
TEMPORARY STRUCTURES.
10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR. THE CONTRACTOR SHALL EMPLOY ENGINEERING EXPERTISE AS NEEDED TO
ASSIST IN DEMOLITION.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL
CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE
AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING
CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA
REGULATIONS DURING CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF
BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT,
AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS
FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO
PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD,
RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE
GENERAL CONTRACTOR'S EXPENSE.
13. FLAMMABLE AND COMBUSTIBLE MATERIALS IF USED DURING CONSTRUCTION, SHALL BE
HANDLED AND STORED IN ACCORDANCE WITH NFPA 30.
14. ANY DUCTWORK THAT PENETRATES A RATED ASSEMBLY SHALL BE PROTECTED WITH AN
APPROPRIATE DAMPER AND TIED TO THE FIRE ALARM.
15. ALL ENGINEERED SHOP DRAWINGS ARE TO BE REVIEWED BY THE ARCHITECT AND/OR
ENGINEER OF RECORD PRIOR TO BEING SUBMITTED TO THE BUILDING DEPT. FOR REVIEW.
16. THE GENERAL CONTRACTOR TO BE RESPONSIBLE FOR ABATEMENT OF ALL ASBESTOS
FOUND ON ASBESTOS REPORT PROVIDED BY SCI ENGINEERING.
17. THE GENERAL CONTRACTOR IS TO SUBMIT SUBSTITUTE MATERIAL, SPECIFICATIONS,
PROPOSED +/- COST, AND A SAMPLE FOR APPROVAL IN WRITING TO THE ARCHITECT PRIOR
TO COMMENCEMENT OF WORK.
A101
A101
SCOPE OF WORK SUMMARY:
SHEET NUMBER
WITHIN SERIES
INDEX OF DRAWINGS
BUILDING 53 AREA:
BASEMENT (EXISTING) 28,104 GSF
LEVEL 01 (EXISTING) 24,427 GSF
LEVEL 02 (EXISTING) 24,382 GSF
N O
R T
H
DRAWING INDEX
DEDUCT ALTERNATESNONE AT THIS TIME.
52-AE101
DEMOLITION NOTES
1. FOR DEMOLISHED ITEMS, WHAT IS TAKEN OUT MUST BE LISTED AND REPORTED ON
APPROPRIATE FORM (EE NUMBER ITEMS).
2. ALL EE NUMBERED EQUIPMENT REMOVED DURING SHALL BE DOCUMENTED ON THE BSE
TURN IN FORM AND TURNED IN TO THE COR.
3. ALL EQUIPMENT INSTALLED DURING THIS PROJECT SHALL BE DOCUMENTED ON THE BSE
FORM CHECK IN FORM AND TURNED IN TO THE COR. REFER TO SPECIFICATIONS FOR
FORMS.
OWNER:
Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth, KS 66048-5012
CONTRACTING OFFICER REPRESENTATIVES:
Jefferson Barracks VA Medical Center 1 Jefferson Barracks Drive St. Louis, MO 63125
Lydia Oswald lydia.oswald@va.gov
314.652.4100 x66719
ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Michele M. Kiehl, AIA, LEED AP BD+C Michele.Kiehl@RomanykConsulting.com
855.424.3838 x313
913.908.3280 cell
MECHANICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
402.981.8882 cell
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
15 Sunnen Drive, Suite 104 Plano, Texas 75093
Yumei Wang P.E, RCDD, CTS, LEED AP Yumei.Wang@RomanykConsulting.com
855.424.3838 x311 402.321.3766
PROJECT MANAGER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
402.981.8882 cell
Devin Gates devin.gates@va.gov
314.652.4100 x67669
BUILDING SCHEDULE
1 OUTPATIENT CLINICS - VSO
1G EMERGENCY GENERATOR FOR BUILDING 1
1CC CONNECTING CORRIDORS
2 HEALTHACRE ENVIRONMENT AND FACILITY PROGRAMS
3 DOMICILIARY
3T DOMICILIARY OFFICES
18 FISCAL HUMAN RESOURCES
23 PROSTHETICS
24 CANTEEN - LIBRARY - AUDITORIUM
25 NATIONAL CANTEEN SERVICE EXECUTIVE SUITE
25T NRM IMPACT
51 INPATIENT MENTAL HEALTH
51T NEURO PSYCHIATRIC
52 SPINAL CORD INJURY (SCI)
52G EMERGENCY GENERATOR FOR BUILDING 52
52SG TRANSFER SWITCH GEAR
53 COMMUNITY LONG-TERM CARE (CLC)
53G EMERGENCY GENERATOR FOR BUILDING 53
53T HOME BASE PRIMARY CARE
54 REHAB ILITATION
55 OUTPATIENT CLINICS
55G EMERGENCY GENERATOR FOR BUILDING 55
56 TENANTS (NCA,EES,OIT, OGC)
56G EMERGENCY GENERATOR FOR BUILDING 56
57 ENGINEERING LOGISTICS, LAUNDRY
58 MENTAL HEALTH CLINIC
59 FISCHER HOUSE
60 MAIN KITCHEN
60G EMERGENCY GENERATOR FOR BUILDING 60
60T FOOD - NUTRITION - DIETETICS
75 ENERGY PLANT
89 SECURITY STATION
93 HAZARDOUS WASTE STORAGE
101T CFM MAJOR PROJECTS
101T
53T
52G
52SG
60T
60G
51T
1CC
25T
3 3T 18
56G
BUILDINGS IN
PROJECT SCOPE
NOTE: SEE GC100 SERIES FOR SITE STAGING INFORMATION.
CONTRACTOR ENTRANCE
CONTRACTOR PARKING AND
STORAGE, GRAVEL LOT.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA ST. LOUIS HEALTH CARE SYSTEM
FULLY SPRINKLERED
52 & 53
JEFFERSON BARRACKS
Office of Construction and Facilities Management
B
IM
/V
IS
N
J e ff e rs o n B a rr a c k s R e p la c e
A H
U s B
V
/J e ff e rs o n
B a rr a c k s R e p la c e
A H
U s B
V
.r v t
/9
/2
:2
:4
P M
PROJECT INFORMATION AND SHEET INDEX
AUGUST 25, 2022
657-21-106JB
PROJECT NUMBER - 657-21-106JB
FCA REPLACE AIR HANDLING UNITS
BUILDINGS 52 & 53
BID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
GI100
BID DOCUMENTS
SHEET # SHEET TITLE
52-AE100 BUILDING 52 - LEVEL 00 - RM.GN39- ARCHITECTURAL PLANS
52-AE101 BUILDING 52 - LEVEL 00 - RM. GS08A - ARCHITECTURAL PLANS
52-AE102 BUILDING 52 - LEVEL 02 - RM.2S14 - ARCHITECTURAL PLANS
53-AD101 BUILDING 53 - ROOF PLAN - NORTH WING - DEMOLITION PLAN
53-AD102 BUILDING 53 - ROOF PLAN - SOUTH WING - DEMOLITION PLAN
53-AE140 BUIDLING 53 - OVERALL ROOF PLAN
53-AE141 BUILDING 53 - ROOF PLAN - NORTH WING - ARCHITECTURAL
53-AE142 BUILDING 53 - ROOF PLAN - SOUTH WING - ARCHITECTURAL
53-AE530 BUILDING 53 - ROOF DETAILS
ASBESTOS ABATEMENT
52-HA100 BUILDING 52 - ENLARGED PLANS - ASBESTOS CONTAINING MATERIALS (ACM) TO BE ABATED
52-HA101 BUILDING 52 - ENLARGED PLANS SUSPECT MOLD GROWTH TO BE ABATED
52-HA102 BUILDING 52 - ENLARGED PLANS - SUSPECT MOLD GROWTH LOCATIONS
53-HA100 BUILDING 53 - OVERALL PLAN - SUSPECT MOLD GROWTH TO BE ABATED
FIRE PROTECTION
F-100 FIRE PROTECTION LEGEND, DETAILS, GENERAL NOTES AND ABBREVIATIONS
52-FD100 BUILDING 52 ENLARGED PLANS - FIRE PROTECTION DEMOLITION
52-FD101 BUILDING 52 ENLARGED PLANS - FIRE PROTECTION DEMOLITION
52-FS100 BUILDING 52 ENLARGED PLANS - FIRE PROTECTION
52-FS101 BUILDING 52 ENLARGED PLANS - FIRE PROTECTION
MECHANICAL
M-100 MECHANICAL LEGEND AND GENERAL NOTES
M-101 MECHANICAL ABBREVIATIONS
52-MO100 BUILDING 52 - OVERALL PLAN - BASEMENT & LEVEL 01 - MECHANICAL
52-MO101 BUILDING 52 - OVERALL PLAN - LEVEL 02 & ROOF - MECHANICAL
52-MD100 BUILDING 52 - ENLARGED PLANS - HVAC DEMOLITION
52-MD101 BUILDING 52 - ENLARGED PLANS - HVAC DEMOLITION
52-MD200 BUILDING 52 - ENLARGED PLANS - PIPING DEMOLITION
52-MD201 BUILDING 52 - ENLARGED PLANS - PIPING DEMOLITION
52-MH100 BUILDING 52 - ENLARGED PLANS - HVAC
52-MH101 BUILDING 52 - ENLARGED PLANS - HVAC
52-MP100 BUILDING 52 - ENLARGED PLANS - PIPING
52-MP101 BUILDING 52 - ENLARGED PLANS - PIPING
53-MO100 BUILDING 53 - OVERALL PLAN - BASEMENT & LEVEL 01 - MECHANICAL
53-MO101 BUILDING 53 - OVERALL PLAN - LEVEL 02 & ROOF - MECHANICAL
53-MD100 BUILDING 53 - ENLARGED PLANS - HVAC DEMOLITION
53-MD101 BUILDING 53 - ENLARGED PLANS - HVAC DEMOLITION
53-MD200 BUILDING 53 - ENLARGED PLANS - PIPING DEMOLITION
53-MD201 BUILDING 53 - ENLARGED PLANS - PIPING DEMOLITION
53-MH100 BUILDING 53 - ENLARGED PLANS - HVAC
53-MH101 BUILDING 53 - ENLARGED PLANS - HVAC
53-MP100 BUILDING 53 - ENLARGED PLANS - PIPING
53-MP101 BUILDING 53 - ENLARGED PLANS - PIPING
M-300 MECHANICAL DETAILS
M-301 MECHANICAL DETAILS
M-400 MECHANICAL SCHEDULES
M-500 MECHANICAL EQUIPMENT CONTROLS DIAGRAM
M-501 MECHANICAL EQUIPMENT CONTROLS DIAGRAM
M-502 MECHANICAL EQUIPMENT CONTROLS DIAGRAM
M-600 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-601 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-602 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-603 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-604 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-605 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
M-606 MECHANICAL EQUIPMENT SCHEMATICS DIAGRAM
ELECTRICAL
E-100 ELECTRICAL LEGEND, GENERAL NOTES AND ABBREVIATIONS
ES100 ELECTRICAL SITE PLAN
52-ED100 BUILDING 52 - LEVEL 00 - ELECTRICAL DEMOLITION PLAN
52-ED101 BUILDING 52 - LEVEL 02 - ELECTRICAL DEMOLITION PLAN
52-EP100 BUILDING 52 - LEVEL 00 - ELECTRICAL PLAN
52-EP101 BUILDING 52 - LEVEL 01 - ELECTRICAL PLAN
52-EP102 BUILDING 52 - LEVEL 02 - ELECTRICAL PLAN
53-ED100 BUILDING 53 - ROOF NORTH & PENTHOUSE - ELECTRICAL DEMOLITION PLAN
53-ED101 BUILDING 53 - ROOF SOUTH - ELECTRICAL DEMOLITION PLAN
53-EP100 BUILDING 53 - LEVEL 02 - ELECTRICAL PLAN
53-EP101 BUILDING 53 - ROOF NORTH & PENTHOUSE - ELECTRICAL PLAN
53-EP102 BUILDING 53 - ROOF SOUTH - ELECTRICAL PLAN
E-400 ELECTRICAL SCHEDULES
SHEET # SHEET TITLE
GENERAL INFORMATION
GI100 PROJECT INFORMATION AND SHEET INDEX
GENERAL CONTRACT
GC100 PROJECT STAGING - OVERALL SITE PLAN
GC101 PROJECT STAGING - ENLARGED SITE PLAN
GC102 PROJECT STAGING - CRANE PLAN
GC103 PROJECT STAGING - ROOF TOP EQUIPMENT WEIGHTS
GC104 BUILDING 53 - TEMPORARY HVAC PHASING PLAN
GC105 BUILDING 53 - TEMPORARY HVAC PHASING PLAN
GC106 BUILDING 53 - TEMPORARY HVAC PHASING PLAN
GC107 BUILDING 53 - TEMPORARY HVAC PHASING PLAN
GC108 BUILDING 52 - TEMPORARY HVAC PHASING PLAN
GC109 BUILDING 52 - TEMPORARY HVAC PHASING PLAN
GC110 BUILDING 52 - TEMPORARY HVAC PHASING PLAN
GC111 BUILDING 52 - LEVEL 00 & 01 - INFECTION CONTROL/PHASING PLANS
GC112 BUILDING 52 - LEVEL 02 - INFECTION CONTROL/PHASING PLANS
GC113 BUILDING 53 - LEVEL 02 & ROOF LEVEL - INFECTION CONTROL/PHASING PLANS
GI202 BUILDING 52 - LEVEL 00 & 01 OVERALL - LIFE SAFETY PLAN
GI203 BUILDING 52 & 53 - LEVEL 02 OVERALL - LIFE SAFETY PLAN
ARCHITECTURAL
52 & 53-AC100 BUILDING 52 & 53 - LEVEL 00 & 02 - REFLECTED CEILING PLANS
Revisions: Date:
Revision 1 Date 1
Part 2
SPRINKLER NOTESSPRINKLER DEMO NOTES
DRAWING SYMBOLS
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE DEPARTMENT
OF VETERANS AFFAIRS (VA) STANDARDS.
2. DESIGN BASIS INFORMATION: PROVIDE DESIGN, MATERIALS, EQUIPMENT,
INSTALLATION, INSPECTION, AND TESTING OF THE AUTOMATIC SPRINKLER SYSTEM
IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.
3. ALL WORK SHALL BE IN CONFORMANCE WITH THE NFPA 13 CODE - LATEST EDITION
2019. THE VA SERVES AS AUTHORITY HAVING JURISDICTION.
4. THESE DOCUMENTS ARE INTENDED TO COMPLY WITH APPLICABLE CODES. WHERE
DISCREPANCIES OCCUR, NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR
INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS TO COMPLY WITH THE
CODES AND STANDARDS AT NO ADDITIONAL COST TO THE OWNER.
5. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY INCLUDING ALL LABOR,
MATERIALS, PERMITS, TAXES, FEES, INSPECTIONS, HARDWARE, AND COST FOR
INSTALLATION FOR A COMPLETE AND OPERATIONAL SYSTEM.
6. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW, COMPLETE WITH
MANUFACTURER’S GUARANTEE OR WARRANTY AND SHALL BE LISTED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY.
7. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH APPROPRIATE
FIRE PROOFING MATERIALS TO RESTORE FIRE RATING. REFER TO ARCHITECTURAL
DRAWINGS FOR FIRE RATED WALLS.
8. CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF ALL DEBRIS ON A DAILY
BASIS. ALL NEW MATERIALS AWAITING INSTALLATION SHALL BE KEPT IN AREAS
DESIGNATED BY THE OWNER.
9. DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS. REFER TO DIMENSIONED
ARCHITECTURAL FLOOR PLANS. IF THE DIMENSIONS CANNOT BE DETERMINED BY
THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT THE ENGINEER FOR
ADDITIONAL INFORMATION.
10. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF
DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN ACCORDANCE
WITH THE CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT
BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR
QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE
OWNER AGAINST DEFECTS OR DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
11. INFORMATION CONTAINED ON THE DRAWINGS IS IN ITSELF INCOMPLETE AND VOID
UNLESS USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE
SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC.,
AND SHALL BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH ALL THEREIN BY
REFERENCE, WHICH THE CONTRACTOR CERTIFIES KNOWLEDGE OF BY SIGNING THE
CONTRACT.
12. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF
SHOP DRAWINGS OR PERIODIC OBSERVATION OF CONSTRUCTION, FOR
COMPLIANCE WITH THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE
CONFIRMED AND CORRELATED ON THE JOB SITE AND BETWEEN INDIVIDUAL
DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION PROCESSES AND
CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION, SHORING, SCAFFOLDING,
BRACING, ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE VARIOUS
TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD
CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO
THE ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT PROGRESS UNTIL
WRITTEN PERMISSION FROM THE ENGINEER IS OBTAINED.
13. ALL EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED SO AS TO BE EASILY
ACCESSIBLE. ALL CLEARANCES FOR EQUIPMENT PER MANUFACTURERS GUIDELINES
AND CODE COMPLIANCE SHALL BE REQUIRED.
14. ALL COMPONENTS OF SYSTEMS SHALL BE PROVIDED FOR A COMPLETELY
OPERATIONAL, UNDERSTANDABLE, SAFE, AND CLEAN SYSTEM; INCLUDING BUT NOT
LIMITED TO EXTRANEOUS FIXTURE TRIM AS SPECIFIED, LABELS, SERVICE AND
COMMISSIONING INTO OPERATION, TESTING AND CLEANING, FIRE AND LIFE SAFETY
REQUIREMENTS, AND CONSIDERING THE REQUESTS OF OWNERS PERSONNEL.
15. ELECTRICAL PANELS SHOWN FOR REFERENCE. DO NOT ROUTE ANY COMPONENTS
ABOVE OR IN FRONT OF ELECTRICAL EQUIPMENT. MAINTAIN CODE REQUIRED
CLEARANCES.
16. FIRE PROTECTION CONTRACTOR SHALL REVIEW ALL PROJECT PLANS AND
SPECIFICATIONS, THEN CONTACT OWNER FOR COORDINATION OF DOCUMENTATION
AND SYSTEM REQUIREMENTS PRIOR TO STARTING WORK.
17. ALL REQUIREMENTS FOR WORKING ON FIRE PROTECTION SYSTEM, INCLUDING BUT
NOT LIMITED TO FIRE WATCH, HYDRANT FLOW TESTING, SYSTEM SHUTDOWNS AND
TESTING, ARE THE RESPONSIBILITY OF THE FIRE PROTECTION CONTRACTOR.
18. PLANS ARE DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE OF WORK AND
GENERAL LOCATIONS OF EQUIPMENT, MATERIALS, ETC. NOT ALL RISERS, DROPS,
OFFSETS, VALVES, ETC. ARE SHOWN. PROVIDE RISERS, DROPS, OFFSETS, VALVES,
ETC. AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO AVOID INTERFERENCES
WITH OTHER TRADES. MAKE FINAL CONNECTIONS TO FIXTURES, EQUIPMENT, ETC.
AS REQUIRED AND/OR PER MANUFACTURER'S RECOMMENDATIONS.
19. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LAYOUT OWN WORK
ACCORDINGLY AND IS RESPONSIBLE FOR DETERMINING EXACT LOCATIONS FOR
EQUIPMENT, MATERIALS, ETC.
20. THE EXISTING SPRINKLER SYSTEM SHALL BE MODIFIED PER SPECIFIED PLANS AND
SPECIFICATIONS. FIELD VERIFY EXISTING SPRINKLER SYSTEM REQUIREMENTS PRIOR
TO BIDDING.
21. COORDINATE SCOPE OF WORK WITH THE WORK OF OTHER TRADES PRIOR TO
INSTALLATION. ISSUES DUE TO LACK OF COORDINATION EFFORT WILL BE
CORRECTED AT NO ADDITIONAL COST TO THE OWNER.
22. COORDINATE LOCATION OF SYSTEM COMPONENTS WITHIN LIMITS OF STRUCTURE
AND OTHER ENGINEERED SYSTEMS. ROUTE ALL PIPING IN CONCEALED SPACES AND
INSTALL PIPING AS HIGH AS POSSIBLE. CENTER SPRINKLER HEADS WITHIN CEILING
TILES. OFFSET SYSTEMS ROUTING AS REQUIRED, PROVIDING REQUIRED MATERIALS
AND DRAIN POINTS. PIPE SHALL NOT BE ROUTED IN EXTERIOR WALLS UNLESS
NOTED. COORDINATE ROUTING OF PIPING TO MAINTAIN REQUIRED SERVICE
CLEARANCES AROUND ANY EQUIPMENT AND ELECTRICAL ITEMS.
23. ALL ELEMENTS OF CONSTRUCTION SHALL BE INSTALLED BY SKILLED TRADESMEN OF
THERE PARTICULAR TRADE, AND INSTALLED IN A NEAT WORKMANLIKE MANNER
KEEPING WITH THE HIGHEST STANDARDS OF THE TRADE.
24. COORDINATE SCOPE OF WORK WITH PROJECT SCHEDULES AGREED UPON BY
OWNER AND ALL CONTRACTORS.
25. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS ABOUT DESIGN
STANDARDS, PRODUCTS, DRAWINGS, SUBMITTALS, DOCUMENTATION,
COORDINATION, AND INSTALLATION.
1. ALL PIPING AND DUCTWORK IS SHOWN SCHEMATICALLY BASED ON EXISTING PLANS.
CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATION OF VERIFYING ROUTES
OF ALL EXISTING CONDITIONS AND EXISTING UTILITIES PRIOR TO BIDDING AND
STARTING OF WORK. IF CONDITIONS DIFFER GREATLY CONTACT ENGINEER.
2. COORDINATE SCHEDULE OF WORK WITH OWNER AND PROVIDE SUFFICIENT NOTICE
BEFORE ANY SHUTDOWNS, TO MINIMIZE DISRUPTIONS TO ANY CONCURRENT
OPERATIONS.
3. COMPLY WITH SITE SAFETY PROCEDURES OF OWNER, GENERAL CONTRACTOR, AND
OSHA.
4. DEMOLISH MATERIALS, EQUIPMENT, AND ASSOCIATED SYSTEMS AS SHOWN WITHIN
SCOPE OF WORK AREA AS DESIGNATED/NOTED. DEMOLISH ALL BRANCH DUCT AND
PIPE, SUPPORTS, ACCESSORIES, EQUIPMENT, TERMINAL DEVICES, CONTROLS,
WIRING, CONDUITS, AND ASSOCIATED ITEMS BACK TO RESPECTIVE MAINS. THEN
CAP, SEAL, REPAIR, REINSULATE MAIN CONNECTIONS AS REQUIRED. NOTHING SHALL
BE ABANDONED IN PLACE UNLESS NOTED OTHERWISE. REMOVE ALL DEMOLISHED
ITEMS FROM SITE AND DISPOSE PROPERLY PER LOCAL LAWS.
5. HATCHED OR GRAYED OUT AREAS ARE NOT WITHIN CONTRACT BOUNDARY.
COORDINATE WITH OWNER IF SUCH AREAS REQUIRE ACCESS TO COMPLETE SCOPE
OF WORK, SUCH AS REMOVING A BRANCH MAIN BACK TO LARGER MAIN TO
ELIMINATE DEAD LEGS.
6. INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING
PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW
SYSTEMS. COORDINATE WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS
SCOPE. 8.SAVE NOTED ITEMS FOR REUSE OR OWNERS SALVAGE. STORE NOTED
ITEMS AND OTHER ITEMS IDENTIFIED BY OWNER IN OWNER’S DESIGNATED STORAGE
AREA.
7. PROTECT EXISTING TO REMAIN EQUIPMENT, MATERIALS, AND SURROUND SITE FROM
DAMAGE DURING DEMOLITION. REPAIRS AND REPLACEMENT OF EXISTING TO
REMAIN CONDITIONS SHALL BE THE CONTRACTOR’S RESPONSIBILITY.
8. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS.
H4
H7
A
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
(i.e. SUPPLY FAN #3 - "SUPPLY FAN" - BUILDING 26)
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
NOTES:
1. ADJUST SPRINKLERS AS NECESSARY TO CLEAR OBSTRUCTIONS. PROVIDE A
PIPE HANGER IF THE HORIZONTAL OFFSET LENGTH EXCEEDS 24 IN. [610mm].
2. PROVIDE LENGTH TO SUIT.
PROVIDE NEW UPRIGHT
PENDENT SPRINKER HEAD
1" x 1/2" PIPE
REDUCING COUPLING
SPRINKLER
BRANCH LINE
1/2" SCH 80 CLOSE NIPPLE
1" BLACK STEEL SCH 40
PIPING (TYP.)N
O T
E
NOTE 2
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
52 & 53
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:2
P M
FIRE PROTECTION LEGEND, DETAILS,
GENERAL NOTES AND ABBREVIATIONS
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
F-100
NTS
TYPICAL UPRIGHT SPRINKLER HEAD DETAIL
SPR SPRINKLER LINE
SFPE SAFETY AND FIRE PROTECTION ENGINEER
QRS QUICK RESPONSE SPRINKLERS
PRV PRESSURE REDUCING VALVE
PD PRESSURE DROP OR DIFFERENCE
NPW NON POTABLE WATER
NOM. NOMINAL
NO NORMALLY OPEN
NIC NOT IN CONTRACT
NC NORMALLY CLOSED
FS FLOW SWITCH
FP FIRE PROTECTION
FMERC FACTORY MUTUAL ENGINEERING AND RESEARCH CORPORATION
FM FACTORY MUTUAL
FM FLOW METER
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FD FLOOR DRAIN
FACSUL FIRE ALARM CERTIFICATE SERVICE
DN DOWN
DCW DOMESTIC COLD WATER
C CELSIUS
BFP REDUCED PRESSURE BACKFLOW PREVENTER
AS AUTOMATIC SPRINKLER
AG AIR GAP
SPRINKLER ABBREVIATIONS
Revisions: Date:
SCOPE OF WORK
PIT
FP
F P
F P
FD
M E C H . R M .
G S 0 8
M E C H . R M .
G N 3 9
P H Y S I C A L T H E R A P Y
G N 3 1 H A C
G S 6 0
H A C
G S 5 7
H A C
G S 5 8
H A C
G S 5 9
UT I L I T Y R M . ,
S O I L E D
G S 0 6 B
M E C H . R M .
G S 0 9
W O R K R M .
G S 1 4
T O I L E T , M A L E
G S 1 8 A
T O I L E T , F E M A L E
G S 1 8 B
M E C H . R M .
G S 2 0 A
E N G I N E E R I N G
G S 2 0 B
C O R R I D O R
H 0 0 4
T O I L E T
G S 2 2 F
O F F I C E
G S 2 2 A O F F I C E
G S 2 2 B
O F F I C E
G S 2 2 C
O F F I C E
G S 2 2 D
O F F I C E
G S 2 2 E O F F I C E
G S 2 2 E L E V A T O R
L O B B Y
G S 2 4
EL E V . N O . 3
E 2
T O I L E T
G N 2 7
C L O S E T
G N 2 7 A
H A C
G N 2 8
V E N D I N G R M .
G N 2 9
S T O R A G E
G N 3 0
O F F I C E
G N 3 2
W O R K R M .
G N 3 3
W O R K R M .
G N 3 4
T O I L E T
G N 3 5
S T O R A G E
G N 3 6 O F F I C E
G N 3 7 T O I L E T
G N 3 8
P . T . S T O R A G E
G N 4 3
W H E E L C H A I R S
G N 4 3 A
O F F I C E
G N 4 4
F O Y E R
G N 5 7
D R I V E R ' S T R A I N I N G
G N 4 8
M E C H . R M .
G N 5 0 L I N E N C H U T E
G N 5 2 S T O R A G E
G N 5 3
F . E . C L O S E T
G N 5 1
S T A I R 3
S 0 0 3
S T O R A G E
G N 5 4
F . E . C L O S E T
G N 5 5
P I P E C H A S E
Z 0 0 4
P I P E C H A S E
Z 0 0 5
P I P E C H A S E
Z 0 0 1
P I P E C H A S E
Z 0 0 2
P I P E C H A S E
Z 0 0 3
EL E V . N O . 1
E 1
S T A I R 2
S 0 0 2
O I & T
G S 0 1 A
W H E E L C H A I R
S T O R A G E
G S 0 1
H A C
G S 0 2
F . E . C L O S E T
G S 2 3
EL E V . N O . 2
E 3
C O R R I D O R
H 0 0 4 A
C O R R I D O R
H 0 0 2
C O R R I D O R
H 0 0 3 C O R R I D O R
H 0 0 5
C O R R I D O R
H 0 0 6
S H O P
G S 5 8 A
C H A S E
C H - S - 2
C H A S E
C H - N - 1
CHASE
CH-N-2
C H A S E
C H - S - 3
C H A S E
C H - N - 4 C H A S E
C H - N - 3
O F F I C E
G S 1 4 A
W O R K R M .
G S 1 4 B
C H A S E
C H - S - 5
C H A S E
C H - S - 4
C L O S E T
G N 3 6 A
PI T
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
GN39
MECH. RM.
52-AH-1 (EX)
GS08
MECH. RM.
GS08A
MECH. RM.
52-AH-S2 (EX)
52-FD100
52-FD100
52-MD100
NORTH
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:3
P M
BUILDING 52 ENLARGED PLANS - FIRE
PROTECTION DEMOLITION
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
52-FD100
1/2" = 1'-0"1
MECH RM. GN39 - FIRE PROTECTION DEMOLITION
1/2" = 1'-0"2
MECH RM. GS08 - FIRE PROTECTION DEMOLITION
1/2" = 1'-0"3
MECH RM. GS08A - FIRE PROTECTION DEMOLITION
NTS
KEYPLAN - BASEMENT
NO. DESCRIPTION
1 EXISTING CEILING MOUNTED AIR HANDLING UNIT TO BE REMOVED. REFER TO
MECHANICAL PLANS FOR HVAC AND PIPING DEMOLITION SCOPE. SHOWN FOR
REFERENCE ONLY.
2 REMOVE EXISTING FIRE PROTECTION PIPING, HANGERS, SUPPORTS, SPRINKLER
HEADS TO ALLOW FOR AHU EQUIPMENT REMOVAL.
3 THERE IS NO FIRE PROTECTION WORK ASSOCIATED WITH THIS ROOM. SEE 2/52-MD200
FOR MECHANICAL PIPING DEMOLITION SCOPE.
4 EXISTING SAN PIPING TO REMAIN. SHOWN FOR REFERENCE ONLY.
FP FP
2 S 1 6
S T O R A G E
2 S 1 4
2 S 1 5 2 S 1 6
S T O R A G E
2 S 1 4
2 S 1 5
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
2S14
STORAGE
CH-S-5
CHASE
CHASE
2S15
STORAGE
52-AH4 (EX)
FP
52-MD101
NORTH
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:4
P M
BUILDING 52 ENLARGED PLANS - FIRE
PROTECTION DEMOLITION
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
52-FD101
3/4" = 1'-0"1
BUILDING 52 ENLARGED PLAN - LEVEL 02 - STORAGE 2S14 FIRE PROTECTION DEMOLITION
NTS
KEYPLAN - BLDG 52 - LEVEL 02
NO. DESCRIPTION
1 EXISTING CEILING MOUNTED AIR HANDLING UNIT TO BE REMOVED. REFER TO
MECHANICAL PLANS FOR HVAC AND PIPING DEMOLITION SCOPE. SHOWN FOR
REFERENCE ONLY.
2 REMOVE EXISTING FIRE PROTECTION PIPING, HANGERS, SUPPORTS, SPRINKLER
HEADS TO ALLOW FOR AHU EQUIPMENT REMOVAL.
M E C H . R M .
G S 0 8
M E C H . R M .
G N 3 9
P H Y S I C A L T H E R A P Y
G N 3 1 H A C
G S 6 0
H A C
G S 5 7
H A C
G S 5 8
H A C
G S 5 9
UT I L I T Y R M . ,
S O I L E D
G S 0 6 B
M E C H . R M .
G S 0 9
W O R K R M .
G S 1 4
T O I L E T , M A L E
G S 1 8 A
T O I L E T , F E M A L E
G S 1 8 B
M E C H . R M .
G S 2 0 A
E N G I N E E R I N G
G S 2 0 B
C O R R I D O R
H 0 0 4
T O I L E T
G S 2 2 F
O F F I C E
G S 2 2 A O F F I C E
G S 2 2 B
O F F I C E
G S 2 2 C
O F F I C E
G S 2 2 D
O F F I C E
G S 2 2 E O F F I C E
G S 2 2 E L E V A T O R
L O B B Y
G S 2 4
EL E V . N O . 3
E 2
T O I L E T
G N 2 7
C L O S E T
G N 2 7 A
H A C
G N 2 8
V E N D I N G R M .
G N 2 9
S T O R A G E
G N 3 0
O F F I C E
G N 3 2
W O R K R M .
G N 3 3
W O R K R M .
G N 3 4
T O I L E T
G N 3 5
S T O R A G E
G N 3 6 O F F I C E
G N 3 7 T O I L E T
G N 3 8
P . T . S T O R A G E
G N 4 3
W H E E L C H A I R S
G N 4 3 A
O F F I C E
G N 4 4
F O Y E R
G N 5 7
D R I V E R ' S T R A I N I N G
G N 4 8
M E C H . R M .
G N 5 0 L I N E N C H U T E
G N 5 2 S T O R A G E
G N 5 3
F . E . C L O S E T
G N 5 1
S T A I R 3
S 0 0 3
S T O R A G E
G N 5 4
F . E . C L O S E T
G N 5 5
P I P E C H A S E
Z 0 0 4
P I P E C H A S E
Z 0 0 5
P I P E C H A S E
Z 0 0 1
P I P E C H A S E
Z 0 0 2
P I P E C H A S E
Z 0 0 3
EL E V . N O . 1
E 1
S T A I R 2
S 0 0 2
O I & T
G S 0 1 A
W H E E L C H A I R
S T O R A G E
G S 0 1
H A C
G S 0 2
F . E . C L O S E T
G S 2 3
EL E V . N O . 2
E 3
C O R R I D O R
H 0 0 4 A
C O R R I D O R
H 0 0 2
C O R R I D O R
H 0 0 3 C O R R I D O R
H 0 0 5
C O R R I D O R
H 0 0 6
S H O P
G S 5 8 A
C H A S E
C H - S - 2
C H A S E
C H - N - 1
CHASE
CH-N-2
C H A S E
C H - S - 3
C H A S E
C H - N - 4 C H A S E
C H - N - 3
O F F I C E
G S 1 4 A
W O R K R M .
G S 1 4 B
C H A S E
C H - S - 5
C H A S E
C H - S - 4
C L O S E T
G N 3 6 A
PI T
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
GN39
MECH. RM.
52-AH-1
FP
F P
FP
F P
FP
F P
4"Ø SAN
4"Ø SAN
GS08
MECH. RM.
GS08A
MECH. RM.
52-AH-S2
4"Ø SAN
4"Ø SAN
"Ø
S A
N
"Ø
S A
N
4"Ø SAN
2"Ø SAN
F P
FP
F P
FP
F P
FP
F P
F P
52-FS100
52-FS100
52-FS100
NORTH
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:4
P M
BUILDING 52 ENLARGED PLANS - FIRE
PROTECTION
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
52-FS100
1/2" = 1'-0"1
MECH RM. GN39 - FIRE PROTECTION
1/2" = 1'-0"2
MECH RM. GS08 - FIRE PROTECTION
1/2" = 1'-0"3
MECH RM. GS08A - FIRE PROTECTION
NTS
KEYPLAN -BASEMENT
NO. DESCRIPTION
1 RECONFIGURE PIPING AND INSTALL SPRINKLER HEADS IN THIS AREA AFTER NEW AHU
IS INSTALLED. MODIFY EXISTING SYSTEM, TEST, AND PLACE INTO WORKING
CONDITION. SPRINKLERS UNDER DUCT AND HVAC EQUIPMENT SHALL BE FULLY
CAGED TO PROTECT ANY DAMAGE TO THE SPRINKLER. COORDINATE HEAD AND
PIPING LAYOUT WITH OTHER TRADES.
2 THERE IS NO FIRE PROTECTION WORK ASSOCIATED WITH THIS ROOM.
3 FIRE PROTECTION SERVICE ENTRANCE. SHOWN FOR REFERENCE ONLY.
2 S 1 6
S T O R A G E
2 S 1 4
2 S 1 5 2 S 1 6
S T O R A G E
2 S 1 4
2 S 1 5
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
2S14
STORAGE
CH-S-5
CHASE
CHASE
2S15
STORAGE
FP FPFP
52-AH-4
52-MD101
NORTH
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:4
P M
BUILDING 52 ENLARGED PLANS - FIRE
PROTECTION
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW DAW
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
52-FS101
3/4" = 1'-0"1
BUILDING 52 ENLARGED PLAN - LEVEL 02 - STORAGE 2S14 FIRE PROTECTION
NTS
KEYPLAN - BLDG 52 - LEVEL 02
NO. DESCRIPTION
1 RECONFIGURE PIPING AND INSTALL SPRINKLER HEADS IN THIS AREA AFTER NEW AHU
IS INSTALLED. MODIFY EXISTING SYSTEM, TEST, AND PLACE INTO WORKING
CONDITION. SPRINKLERS UNDER DUCT AND HVAC EQUIPMENT SHALL BE FULLY
CAGED TO PROTECT ANY DAMAGE TO THE SPRINKLER. COORDINATE HEAD AND
PIPING LAYOUT WITH OTHER TRADES.
DUCTWORK SYMBOLSMECHANICAL SYMBOLS MECHANICAL GENERAL NOTESGENERAL DEMOLITION NOTESSYMBOLS - PIPING
10"x8"SA(EX)
LIMIT OF DEMOLITION
SUPPLY DIFFUSER/GRILLE (CEILING, SQUARE 4-WAY)
SEE NOTES 1, 2, 3.
CONNECT NEW DUCT TO EXISTING DUCT
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
FC
10"x8"SA
FLEXIBLE CONNECTION (FC) - EQUIPMENT,
VIBRATION, OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS. VANE SYMBOL ARE NOT
SHOWN ON PLANS)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
DUCT LABELING NOTE:
• INSIDE DIMENSIONS: WIDTH x DEPTH
• SA = SUPPLY AIR
• RA = RETURN AIR
• OA = OUTSIDE AIR SUPPLY
• EA = EXHAUST AIR
EXISTING DUCT TO REMAIN
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED10"x8"
NEW DUCT
EXHAUST GRILLE
SEE NOTES 1, 2, 3.
SD-14
270 CFM
SUPPLY DUCT UP ("X")
EXHAUST DUCT UP ("Y")
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR
GRILLE BELOW DUCT
EXHAUST OR RETURN BOTTOM
REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN REGISTER OR
TOP GRILLE (WALL TYPE)
RETURN DUCT UP ("/")
SUPPLY DUCT DOWN ("X")
EXHAUST DUCT DOWN ("Y")
RETURN DUCT DOWN ("/")
(ROUND) (RECT.)
EG-21
80 CFM
RETURN GRILLE (CEILING)
SEE NOTES 1, 2, 3.
RG-24
270 CFM
NOTES:
1. AIR TERMINAL LABEL:
AIR TERMINAL TYPE
BALANCED FLOW RATE
2. AIR TERMINAL TYPE:
Sx = SUPPLY, Rx = RETURN, Ex = EXHAUST xD = DIFFUSER xG = GRILLE xR = REGISTER (WITH INTEGRATED VOLUME DAMPER)
(EX. SG-14 = SUPPLY GRILLE)
3. REFER TO AIR DEVICE SCHEDULE FOR DETAILS.
NOTES:
1. DEVICE CONTROL/CONNECTION PANEL.
2. MANUFACTURER'S RECOMMENDED MAINTENANCE/OPERATIONAL CLEARANCE. KEEP
THIS AREA CLEAR AND ACCESSIBLE FOR COIL AND PANEL MAINTENANCE AND
REPAIR.
3. HATCHED AREA INDICATES NEC REQIRED 36" WORKING SPACE - MUST BE KEPT
CLEAR.
4. DISPERSION TUBE WITHIN DUCT.
5. AIR VOLUME CONTROL VALVE.
6. REHEAT COIL WITH DUCT TRANSITION.
TERMINAL UNIT WITHOUT REHEAT COIL
EXISTING TEMINAL UNIT - DEMOLITION
TERMINAL UNIT WITH REHEAT COIL
NOTE 2 (TYP)
AIR VOLUME CONTROL VALVE
(ARROW INDICATED DIRECTION OF FLOW)
NOTE 1 (TYP)
DUCT MOUNTED STEAM HUMIDIFIER
NOTE 4
NOTE 3
AIR VOLUME CONTROL VALVE (SUPPLY)
WITH ASSOCIATED REHEAT COIL
NOTE 6
NOTE 5
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE DEPARTMENT OF
VETERANS AFFAIRS (VA) STANDARDS.
2. ALL WORK SHALL BE IN CONFORMANCE WITH THE INTERNATIONAL MECHANICAL CODE -
LATEST EDITION ADOPTED BY THE VA. THE VA SERVES AS AUTHORITY HAVING JURISDICTION.
3. THESE DOCUMENTS ARE INTENDED TO COMPLY WITH APPLICABLE CODES. WHERE
DISCREPANCIES OCCUR, NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR
INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS TO COMPLY WITH THE CODES
AND STANDARDS AT NO ADDITIONAL COST TO THE OWNER.
CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY INCLUDING ALL LABOR, MATERIALS,
PERMITS, TAXES, FEES, INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR A
COMPLETE AND OPERATIONAL SYSTEM.
4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW, COMPLETE WITH
MANUFACTURER’S GUARANTEE OR WARRANTY AND SHALL BE LISTED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY.
5. PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 23 CONTRACTOR SHALL BE
SEALED WITH APPROPRIATE FIRE PROOFING MATERIAL TO RESTORE FIRE RATING. REFER TO
ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS.
6. CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF ALL DEBRIS ON A DAILY BASIS. ALL
NEW MATERIALS AWAITING INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE
OWNER.
7. DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. REFER TO DIMENSIONED
ARCHITECTURAL FLOOR PLANS. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE
INFORMATION GIVEN, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ADDITIONAL
INFORMATION.
8. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF
DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH
THE CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE CONSTRUED
AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE WORK, BUT
RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST DEFECTS OR
DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
9. INFORMATION CONTAINED ON THE MECHANICAL DRAWINGS IS IN ITSELF INCOMPLETE AND
VOID UNLESS USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE
SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC., AND SHALL
BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH ALL THEREIN BY REFERENCE,
WHICH THE CONTRACTOR CERTIFIES KNOWLEDGE OF BY SIGNING THE CONTRACT.
10. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP
DRAWINGS OR PERIODIC OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH THE
CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AND CORRELATED ON THE
JOB SITE AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION
PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION, SHORING,
SCAFFOLDING, BRACING, ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE
VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD
CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE
ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT PROGRESS UNTIL WRITTEN
PERMISSION FROM THE ENGINEER IS OBTAINED.
11. ALL NEW EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED SO AS TO BE EASILY
ACCESSIBLE. ALL CLEARANCES FOR EQUIPMENT PER MANUFACTURERS GUIDELINES AND
CODE COMPLIANCE SHALL BE REQUIRED.
12. ALL COMPONENTS OF SYSTEMS SHALL BE PROVIDED FOR A COMPLETELY OPERATIONAL,
UNDERSTANDABLE, SAFE, AND CLEAN SYSTEM; INCLUDING BUT NOT LIMITED TO
EXTRANEOUS FIXTURE TRIM AS SPECIFIED, SERVICE AND COMMISSIONING INTO OPERATION,
LABELS, TESTING AND CLEANING, FIRE AND LIFE SAFETY REQUIREMENTS, AND CONSIDERING
THE REQUESTS OF OWNERS PERSONNEL.
13. ELECTRICAL PANELS SHOWN FOR REFERENCE. DO NOT ROUTE ANY COMPONENTS ABOVE
OR IN FRONT OF ELECTRICAL EQUIPMENT. MAINTAIN CODE REQUIRED CLEARANCES.
14. ALL DUCTWORK SIZES SHOWN ON DRAWINGS ARE CLEAR INTERIOR DIMENSIONS.
15. PROVIDE CONCEALING FLANGES AT ALL VISIBLE DUCT PENETRATIONS THROUGH WALLS.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL INTERCONNECTING CONTROL WIRING.
17. PLANS ARE DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE OF WORK AND GENERAL
LOCATIONS OF EQUIPMENT, MATERIALS, ETC. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND LAYOUT OWN WORK ACCORDINGLY AND IS RESPONSIBLE FOR
DETERMINING EXACT LOCATIONS FOR EQUIPMENT, MATERIALS, ETC.
18. THE EXISTING MECHANICAL SYSTEMS SHALL BE MODIFIED PER SPECIFIED PLANS AND
SPECIFICATIONS. FIELD VERIFY EXISTING MECHANICAL SYSTEMS REQUIREMENTS PRIOR TO
BIDDING.
19. COORDINATE SCOPE OF WORK WITH THE WORK OF OTHER TRADES PRIOR TO INSTALLATION.
ISSUES DUE TO LACK OF COORDINATION EFFORT WILL BE CORRECTED AT NO ADDITIONAL
COST TO THE OWNER.
COORDINATE LOCATION OF SYSTEM COMPONENTS WITHIN LIMITS OF STRUCTURE AND
OTHER ENGINEERED SYSTEMS. ROUTE ALL MECHANICAL SYSTEMS IN CONCEALED SPACES
AND INSTALL COMPONENTS AS HIGH AS POSSIBLE. OFFSET SYSTEMS ROUTING AS
REQUIRED, PROVIDING REQUIRED MATERIALS. PIPE SHALL NOT BE ROUTED IN EXTERIOR
WALLS UNLESS NOTED. COORDINATE ROUTING OF MECHANICAL SYSTEMS TO MAINTAIN
REQUIRED SERVICE CLEARANCES AROUND ANY EQUIPMENT AND ELECTRICAL ITEMS.
20. ALL ELEMENTS OF CONSTRUCTION SHALL BE INSTALLED BY SKILLED TRADESMEN OF THERE
PARTICULAR TRADE, AND INSTALLED IN A NEAT WORKMANLIKE MANNER KEEPING WITH THE
HIGHEST STANDARDS OF THE TRADE.
21. COORDINATE SCOPE OF WORK WITH PROJECT SCHEDULES AGREED UPON BY OWNER AND
ALL CONTRACTORS.
22. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS ABOUT DESIGN STANDARDS,
PRODUCTS, DRAWINGS, SUBMITTALS, DOCUMENTATION, COORDINATION, AND INSTALLATION.
23. PROVIDE DIRECT-DIGITAL CONTROL SYSTEM(S) AS INDICATED ON THE PROJECT
DOCUMENTS, POINT LIST, INTEROPERABILITY TABLES, DRAWINGS AND AS DESCRIBED IN
THESE SPECIFICATIONS. INCLUDE A COMPLETE AND WORKING DIRECT-DIGITAL CONTROL
SYSTEM. PROVIDE ALL ENGINEERING, PROGRAMMING, CONFIGURATION/SETUP HARDWARE
AND SOFTWARE, OPEN LICENSES, CONTROLS AND INSTALLATION MATERIALS, INSTALLATION
LABOR, COMMISSIONING AND START-UP, TRAINING, FINAL PROJECT DOCUMENTATION AND
WARRANTY. COORDINATE WITH VA TECHNOLOGY STAFF FOR INTEGRATION OF REQUIRED
SITE NETWORK SECURITY INTEGRATION.
24. CONTROLS SHALL BE AN EXTENSION OF THE EXISTING OWNER PROVIDED TEMPERATURE
CONTROL SYSTEM. PROVIDE A COMPLETE AND FUNCTIONAL EXPANDED CONTROL SYSTEM
TO ADD ON TO THE EXISTING SYSTEM TO CONTROL ALL EQUIPMENT PROVIDED UNDER THIS
CONTRACT. PROVIDE COMPONENTS AND PROGRAMMING THAT MATCH EXISTING SYSTEM
AND ARE COMPATIBLE WITH THE EXISTING SYSTEM, INCLUDING BUT NOT LIMITED TO
CONTROL BOARDS, THERMOSTATS, WIRING, AND ACCESSORIES. FIELD VERIFY EXISTING
PROGRAMMING FOR REUSE AND/OR UPDATING. ALL NEW BUILDING CONTROLLERS SHALL BE
NATIVE BACNET. ALL NEW BACNET CONTROLLERS, DEVICES AND COMPONENTS SHALL BE
LISTED BY BACNET TESTING LABORATORIES.
25. SEQUENCES INCLUDED IN THE SUBMITTAL MUST REFLECT WHAT IS ACTUALLY GOING TO BE
PROGRAMMED, INCLUDING SUGGESTED CHANGES TO THE PLANS. COPIED SEQUENCES
FROM THE PLANS WILL NOT BE ACCEPTED. INCLUDE SYSTEM GRAPHICS INDICATING
MONITORED SYSTEMS, DATA (CONNECTED AND CALCULATED) POINT ADDRESSES,
OPERATOR NOTATIONS, NETWORK CONFIGURATION, ETC.
26. ALL SOFTWARE WORK INVOLVING THIS INTEGRATION PROCESS IS THE RESPONSIBILITY OF
THE TEMPERATURE CONTROL CONTRACTOR AND MUST BE COMPLETED BY A TECHNICIAN
CERTIFIED WITH THE EXISTING SYSTEM. THE TCC MUST SUBMIT A COPY OF THE
CERTIFICATION DOCUMENTATION FOR THE SYSTEM PROGRAMMER PRIOR TO COMPLETING
ANY WORK IN ORDER TO INSURE THE INTEGRITY OF THE SYSTEM.
27. THE TCC IS ALSO RESPONSIBLE FOR PROVIDING AND INSTALLING ALL ROUTERS, SWITCHES, JACE’S, SOFTWARE LICENSES, DRIVERS, ETC, AS NEEDED FOR A COMPLETE INSTALLATION
INCLUDING FULL INTEGRATION. THE TCC IS RESPONSIBLE FOR ALL GRAPHICS GENERATION
AND POINT MAPPING OF POINTS TO BE ADDED IN THE PROJECT. THE TCC SHALL UTILIZE THE
EXISTING DATABASE AS AN EXAMPLE FOR ALL PROGRAMMING, GRAPHICS, ANIMATIONS, AND
POINT MAPPING FOR WORK DONE ON THE PROJECT IN ORDER TO MAINTAIN CONSISTENCY
WITHIN THE BAS.
1. ALL PIPING AND DUCTWORK IS SHOWN SCHEMATICALLY BASED ON EXISTING PLANS.
CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATION OF VERIFYING ROUTES
OF ALL EXISTING CONDITIONS AND EXISTING UTILITIES PRIOR TO BIDDING AND
STARTING OF WORK. IF CONDITIONS DIFFER GREATLY CONTACT ENGINEER.
2. COORDINATE SCHEDULE OF WORK WITH OWNER AND PROVIDE SUFFICIENT NOTICE
BEFORE ANY SHUTDOWNS, TO MINIMIZE DISRUPTIONS TO ANY CONCURRENT
OPERATIONS.
3. COMPLY WITH SITE SAFETY PROCEDURES OF OWNER, GENERAL CONTRACTOR, AND
OSHA.
4. DEMOLISH MATERIALS, EQUIPMENT, AND ASSOCIATED SYSTEMS AS SHOWN WITHIN
SCOPE OF WORK AREA AS DESIGNATED/NOTED. DEMOLISH ALL BRANCH DUCT AND
PIPE, SUPPORTS, ACCESSORIES, EQUIPMENT, TERMINAL DEVICES, CONTROLS,
WIRING, CONDUITS, AND ASSOCIATED ITEMS BACK TO RESPECTIVE MAINS. THEN
CAP, SEAL, REPAIR, REINSULATE MAIN CONNECTIONS AS REQUIRED. NOTHING
SHALL BE ABANDONED IN PLACE UNLESS NOTED OTHERWISE. REMOVE ALL
DEMOLISHED ITEMS FROM SITE AND DISPOSE PROPERLY PER LOCAL LAWS.
5. HATCHED OR GRAYED OUT AREAS ARE NOT WITHIN CONTRACT BOUNDARY.
COORDINATE WITH OWNER IF SUCH AREAS REQUIRE ACCESS TO COMPLETE SCOPE
OF WORK, SUCH AS REMOVING A BRANCH MAIN BACK TO LARGER MAIN TO
ELIMINATE DEAD LEGS.
6. INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING
PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW
SYSTEMS. COORDINATE WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS
SCOPE.
7. SAVE NOTED ITEMS FOR REUSE OR OWNERS SALVAGE. STORE NOTED ITEMS AND
OTHER ITEMS IDENTIFIED BY OWNER IN OWNER’S DESIGNATED STORAGE AREA.
8. PROTECT EXISTING TO REMAIN EQUIPMENT, MATERIALS, AND SURROUND SITE FROM
DAMAGE DURING DEMOLITION. REPAIRS AND REPLACEMENT OF EXISTING TO
REMAIN CONDITIONS SHALL BE THE CONTRACTOR’S RESPONSIBILITY.
9. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS.
SYSTEM LABEL SYSTEM DESCRIPTION
?"SYS (EX) GENERAL PIPING - EXISTING TO REMAIN
?" GENERAL PIPING - TO BE DEMOLISHED
?"SYS GENERAL PIPING - NEW WORK
D DRAIN LINE
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
TYPICAL MECHANICAL SYSTEM - SUPPLY PIPING
TYPICAL MECHANICAL SYSTEM - RETURN PIPING
MPS MEDIUM PRESSURE STEAM
MPC MEDIUM PRESSURE CONDENSATE RETURN
GRS GLYCOL-WATER RUN AROUND SUPPLY
GRR GLYCOL-WATER RUN AROUND RETURN
AIR SEPARATOR
BACKFLOW PREVENTER (BFP)
CHEMICAL POT FEEDER
CONTINUATION BREAK
COUPLING
DIRECTION OF FLOW
DIRECTION OF PITCH
FLEX CONNECTION
PRESSURE GAUGE
REDUCER
STEAM TRAP
STRAINER - WYE (BALL DRAIN)
TEST PLUG
THERMOMETER
UNION
BOTTOM CONNECTION
END DROP / DOWN
END UP / RISER
HEADER FLANGE CAP
PIPE END CAP
RISE / DROP IN-LINE
TEE DOWN
TEE UP
TOP CONNECTION
UP & DN / RISER
VALVE - ANGLE
VALVE - BALANCING - CIRCUIT SETTER
VALVE - BALL, NORMALLY CLOSED
VALVE - BALL, NORMALLY OPEN
VALVE - CHECK
VALVE - CONTROL 2-WAY (MODULATING)
VALVE - CONTROL 3-WAY (MODULATING)
VALVE - PPRESSURE REDUCING VALVE (PRV)
VALVE - SHUT-OFF, NORMALLY CLOSED
VALVE - SHUT-OFF, NORMALLY OPEN
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
52 & 53
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:4
P M
MECHANICAL LEGEND AND GENERAL NOTES
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW MS
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
M-100
OUTDOOR DESIGN
CONDITIONS
95.5 76.8 43.3 6.6 -- -- --
°F °F °F °F °F
TEMP
WET BULB
TEMP % HUMIDITY
TEMP
DEWPOINT
TEMP % HUMIDITY
DESIGN
CONDITIONS
SUMMER WINTER LOWEST
AVERAGE
ANNUAL
DEWPOINT
HVAC DESIGN DATA
' 6
G ra p h ic S c a le
/2
G ra p h ic S c a le
/3
G ra p h ic S c a le
/1
G ra p h ic S c a le
/8
G ra p h ic S c a le
/4
G ra p h ic S c a le
/8
G ra p h ic S c a le
/2
G ra p h ic S c a le
/4
G ra p h ic S c a le
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
NOT FOR
PERMITTING OR
CONSTRUCTION
Office of Construction and Facilities Management
FULLY SPRINKLERED
52 & 53
B
IM
/V
IS
N
J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
V
/J e ff e rs o n B a rr a ck s R e p la ce
A H
U s
B
M
E P
V
.r vt
/9
/2
:0
:4
P M
MECHANICAL ABBREVIATIONS
AUGUST 25, 2022
657-21-106JBBID DOCUMENTS FCA REPLACE AIR HANDLING
UNITS BUILDINGS 52 & 53
AW MS
JEFFERSON BARRACKS
#1 JEFFERSON BARRACKS DR., ST LOUIS, MO 63125
M-101
IV INLET VANES
IU INDUCTION UNIT
IS INSECT SCREEN
IRH INTRARED HEATER
IPLV INTERGRATED PART LOAD VALUE
IFB INTEGRAL FACE AND BYPASS
ICF IN-LINE CENTRIFUGAL FAN WPD WATER SIDE PRESSURE DROP
IBT INVERTED BUCKET TRAP Wb WET-BULB (TEMPERATURE)
IAQ INDOOR AIR QUALITY
VSD VARIABLE SPEED DRIVE
HX HEAT EXCHANGER VI VIBRATION ISOLATOR
HWUH HOT WATER UNIT HEATER VFD VARIABLE FREQUENCY DRIVE
HWS HEATING HOT WATER SUPPLY VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
HWR HEATING HOT WATER RETURN V VALVE
HWP HEATING HOT WATER PUMP
HWHC HOT WATER HEATING COIL TWU THRU-WALL UNIT
HWC HOT WATER COIL TU TERMINAL UNIT
H…